piping iso checklist

3
CHECKLIST FOR PIPING ISOMETRICS INPUT REQUIRED 1. P&ID of those pipe lines 2. Line list 3. Piping layout 4. Piping material specification 5. Construction piping isometrics supports marked layout also PIPING ISOMETRIC DRAWINGS CHECKLIST 1. Fix the north positions 2. The isometrics drawn to not to scale 3. Mention the dimensions parallel to the pipe line (aligned dimensions) 4. Mention the elevation and centre line of the pipe 5. Mention the pipe line tag numbers 6. Reference position ( like column, beam, wall, equipments with coordination as needed) 7. Bill of materials reference (part) numbers for each components 8. Mention the piping branch connection & continuation 9. Mention the pump nozzle, vessel nozzle connection 10. Mentions the equipment No., nozzle No., flange connection elevation (FOF,EOF) 11. If one pipe line drawn in more than one sheet means must be mentioned the sheet reference numbers and continuation reference numbers 12. Mention the continuation line in dotted that bill of materials doesn’t include in isometrics that components must include in continuation isometric sheet (refer flow directions) 13. Flow direction 14. Insulation, insulation thickness 15. Pipe tracing (electrical /steam tracing) to be denoted 16. the BOM sheet use to be serial no, components quantities, dimension size, materials weight material

Upload: vniranjan

Post on 09-Nov-2015

24 views

Category:

Documents


5 download

DESCRIPTION

checklist for piping

TRANSCRIPT

CHECKLIST FOR PIPING ISOMETRICS

checklist for Piping isometricsInput required 1. P&ID of those pipe lines2. Line list 3. Piping layout4. Piping material specification 5. Construction piping isometrics supports marked layout alsopiping isometric DRAWINGS CHECKLIST 1. Fix the north positions

2. The isometrics drawn to not to scale

3. Mention the dimensions parallel to the pipe line (aligned dimensions)4. Mention the elevation and centre line of the pipe

5. Mention the pipe line tag numbers

6. Reference position ( like column, beam, wall, equipments with coordination as needed)

7. Bill of materials reference (part) numbers for each components 8. Mention the piping branch connection & continuation9. Mention the pump nozzle, vessel nozzle connection

10. Mentions the equipment No., nozzle No., flange connection elevation (FOF,EOF)11. If one pipe line drawn in more than one sheet means must be mentioned the sheet reference numbers and continuation reference numbers12. Mention the continuation line in dotted that bill of materials doesnt include in isometrics that components must include in continuation isometric sheet (refer flow directions)13. Flow direction

14. Insulation, insulation thickness

15. Pipe tracing (electrical /steam tracing) to be denoted 16. the BOM sheet use to be serial no, components quantities, dimension size, materials weight material specification (like materials, dimension, ASME B 36.10 Pipe dimension standards , ASTM A 106 Gr B this is chemical composition standards) 17. Autocad / Esapro follow the different layers for pipe line, dimension, tag, and letters.

18. Stress Iso shall be includes design temperature, design pr, operating temp., operating pr, hydro pr, materials.19. Stress Iso shall be excluded BOM.20. Drawn the slope as per P&ID and piping layouts

21. incase of reference taken from adjacent pipe line means that adjacent pipe line tag should appear completely.

22. (a) for stainless steel pipe supports trunions special class

(b) all other spec. pipe supports trunions are as per line class

23. Pipe supports should not be provided with in the spool piece removable area 24. P&ID numbers in the isometrics should be from origin P&ID numbers 25. Note on safety valve outlet line going to atmosphere (End to be chamber 45 downwards )

26. for wafer type butter fly valve/wafer type check valve, special (extra) length through bolts to be used

27. For commissioning Temp, strainers not to be included in the MTO list (i.e Temp, presu, strainer supplied by commissioning contractor)

28. anubar type flow transmitter in the isometrics as per instrumentation recommendation only hole to be provided on the pipe and orientation has to be mentioned

29. revisions comes in the isometrics properly clouded the particular portion & put revision symbol 30. Process vent/ drains, Hydro test vent & drains for modeling Lucite standards to be followed 31. IFC issue back drafting level after updating of all comments designer to take iso print out and through the isos , all previous items are properly appearing in the isometrics drawing 32. (a) Pipe supports to be moved through MDS only. Not by using move commands (b) dont use out spec. comments 33. branch connection to be checked with the branch table 34. For all valves normally (by default) reduced bore ball valves are used. if full bore ball valve are mentioned in P&ID 35. for ductile & malliable iron double flanged type butterfly valves flat face flanges to be used 36. wherever mono flange used for INST. Tapping extra bolt length to be used as per INST. Recommendation 37. wherever extended spindle valves in the isometrics, spindle length to be indicate in the isometrics38. wherever chain operated valves isometrics chain length to be indicated in isometrics 39. standards colors codes for checking isometrics;

Yellow for correction

Red for addition

Blue for deleted items

Green for information

40. the MTO column fabrication/ erection split-up to be properly checked

41. comments from stress /supports/inst/ MTO to be properly checked

42. for line size 1 & < 1 field supports to suit at site ( notes has to be indicate )

43. valves special notes : LO-LC lock open/lock closed to be marked in iso44. for small bore particular piping add note : contractor and FW construction shall verify route and modify as necessary to suit site condition ( refer doc) fluid codes: WCS /WCR , RF, WD, WP,AI,AS,AN,GN,AM

45. note for actuated valve size 1 and below as actuated valves are heavy, adequate supports shall be placed either side off the valves close vicinity

46. safety valves inlet line extra bolt length has to provide