post-frame building design manual

105

Upload: chuck-achberger

Post on 27-Apr-2015

13.903 views

Category:

Documents


9 download

DESCRIPTION

Post-frame buildings are structurally efficient buildings composed of main members such as posts and trusses and secondary components such as purlins, girts, bracing and sheathing Snow and wind loads are transferred from the sheathing to the secondary members. Loads are transferred to the ground through the posts that typically are embedded in the ground or surface-mounted to a concrete or masonry foundation.

TRANSCRIPT

Page 1: Post-Frame Building Design Manual
Page 2: Post-Frame Building Design Manual
Page 3: Post-Frame Building Design Manual
Page 4: Post-Frame Building Design Manual
Page 5: Post-Frame Building Design Manual
Page 6: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

1-1

Chapter 1: INTRODUCTION TO POST-FRAME BUILDINGS 1.1 General 1.1.1 Main Characteristics. Post-frame build-ings are structurally efficient buildings composed of main members such as posts and trusses and secondary components such as purlins, girts, bracing and sheathing Snow and wind loads are transferred from the sheathing to the secondary members. Loads are transferred to the ground through the posts that typically are embedded in the ground or surface-mounted to a concrete

or masonry foundation. Figure 1.1 illustrates the structural components of a post-frame building. 1.1.2 Use. Post-frame construction is well-suited for many commercial, industrial, agricul-tural and residential applications. Post-frame offers unique advantages in terms of design and construction flexibility and structural efficiency. For these reasons, post-frame construction has experienced rapid growth, particularly in non-agricultural applications.

Figure 1.1. Simplified diagram of a post-frame building. Some components such as per-manent roof truss bracing and interior finishes are not shown.

Truss

Wall girt

Doorway

Wall cladding

Purlin

Ridge cap

Pressure preservativetreated post

Concrete footing

Pressure preservative treated splash board

Roof cladding

Page 7: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

1-2

1.2 Evolution 1.2.1 The concept of pole-type structures is not new. Archeological evidence exists in abun-dance that pole buildings have been used for human housing for thousands of years. In Amer-ica, pole buildings began appearing on farms in the 19th century (Norum, 1967). 1.2.2 Pole-type construction resurfaced in 1930 when Mr. H. Howard Doane introduced the "modern pole barn" as an economical alternative to conventional barns (Knight, 1989). Mr. Doane was the founder of Doane's Agricultural Service, a firm specializing in managing farms for absen-tee owners. These early pole barns were con-structed with red cedar poles that were naturally resistant to decay, trusses spaced 2 ft on-center, 1-inch nominal purlins and galvanized steel sheathing. In the 1940s, pole barn construction was refined by using creosote preservative-treated sawn posts, wider truss and purlin spacings, and im-proved steel sheathing. Mr. Bernon G. Perkins, an employee of Doane's, is credited for many of the refinements to Doane's original pole barn. In 1949, Mr. Perkins applied for the first patent on the pole building concept through Doane's Agri-cultural Service, and the patent was issued in 1953. Rather than protecting their patent, they publicized the concept and encouraged its use throughout the world. In 1995, the post-frame building concept was recognized as an Historic Agricultural Engineering Landmark by the American Society of Agricultural Engineers. 1.2.3 In the past two decades, post-frame con-struction has been further enhanced by the de-velopments of metal-plate connected wood trusses, nail- and glue-laminated posts, high-strength steel sheathing, fasteners and dia-phragm design methods. Composites such as laminated posts and structural composite lumber offer advantages of superior strength and stiff-ness, dimensional stability, and they can be ob-tained in a variety of sizes and pressure pre-servative treatments. Developments in metal-plate connected wood truss technology allow clear spans of over 80 feet. Design procedures were introduced in the early 1980s to more ac-curately account for the effect of diaphragm ac-

tion on post and foundation design (Knight, 1990). New roof panel constructions using high-strength steel and customized screw fasteners have dramatically improved diaphragm stiffness and strength. 1.3 Advantages 1.3.1 Reliability. Outstanding structural per-formance of post-frame buildings under adverse conditions such as hurricanes is well-documented. Professor Gurfinkel, in his wood engineering textbook, cites superior perform-ance of post-frame buildings over conventional construction during hurricane Camille in 1969 (Gurfinkel, 1981). Harmon et. al (1992) reported that post-frame buildings constructed according to engineered plans generally withstood hurri-cane Hugo (wind gusts measured at 109 mph). Since post-frame buildings are relatively light weight, seismic forces do not control the design unless significant additional dead loads are ap-plied to the structure (Faherty and Williamson, 1989; Taylor, 1996). 1.3.2 Economy. Significant savings can be ob-tained with post-frame construction in terms of materials, labor, construction time, equipment and building maintenance. For example, post-frame buildings require less extensive founda-tions than other building types because the wall sections between the posts are non-load bear-ing. Embedded post foundations commonly used in post-frame require less concrete, heavy equipment, labor, and construction time than conventional perimeter foundations. Additionally, embedded post foundations are better-suited for wintertime construction. 1.3.3 Versatility. Post-frame construction facili-tates design flexibility. Posts can be embedded into the ground or surface-mounted to a con-crete foundation. Steel sheathing can be re-placed with wood siding, brick veneer, and con-ventional roofing materials, to satisfy the ap-pearance and service requirements of the cus-tomer. One-hour fire-rated wall and roof/ceiling constructions have been developed for wood framed assemblies. Exposed glued-laminated and solid-sawn timbers can be substituted for trusses made from dimension lumber to achieve desired architectural effects.

Page 8: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

1-3

1.4 Industry Profile 1.4.1 Post-frame construction has experienced tremendous growth since World War II. This growth was fueled by the abundant supplies of steel and pressure preservative-treated wood, together with the need for low-cost structures. In the 1950s and 1960s, the pole barn industry was characterized by large numbers of inde-pendent builders (Knight, 1989). During this time, pole builders were expanding from their traditional agricultural base into other construc-tion markets. This expansion into code-enforced construction required rigorous documentation of engineering designs and more involvement in the building code arena. 1.4.2 NFBA. Approximately 20 builders met in 1969 to discuss challenges facing the post-frame building industry. The group voted in favor of forming the National Frame Builders Associa-tion (NFBA). The NFBA became incorporated in 1971 and the first national headquarters was established in Chicago, Illinois. Today, the Na-tional Frame Builders Association is headquar-tered in Lawrence, Kansas and includes over 300 contractors and suppliers, with regional branches throughout the U.S. In addition, a Ca-nadian Division of NFBA was created in 1984. 1.4.3 The post-frame industry has become one of the fastest growing segments of the total con-struction industry. Based on light-gauge steel sales, post-frame industry revenues are esti-mated to be from 2 to 2.5 billion dollars in 1990. 1.5 Terminology AF&PA: American Forest & Paper Association (formerly National Forest Products Association). AITC: American Institute of Timber Construc-tion. ALSC: American Lumber Standard Committee. ANSI: American National Standards Institute APA: The Engineered Wood Association (for-merly the American Plywood Association)

ASAE: The Society for engineering in agricul-tural, food, and biological systems (formerly American Society of Agricultural Engineers). Anchor Bolts: Bolts used to anchor structural members to a foundation. Commonly used in post-frame construction to anchor posts to the concrete foundation. ASCE: American Society of Civil Engineers. AWC: American Wood Council. The wood prod-ucts division of the American Forest & Paper Association (AF&PA). AWPB: American Wood Preservers Bureau. Bay: The area between adjacent primary frames in a building. In a post-frame building, a bay is the area between adjacent post-frames. Bearing Height: Vertical distance between a pre-defined baseline (generally the grade line) and the bearing point of a component. Bearing Point: The point at which a component is supported. Board: Wood member less than two (2) nominal inches in thickness and one (1) or more nominal inches in width. Board-Foot (BF): A measure of lumber volume based on nominal dimensions. To calculate the number of board-feet in a piece of lumber, multi-ply nominal width in inches by nominal thickness in inches times length in feet and divide by 12. BOCA: Building Officials & Code Administrators International, Inc. The organization responsible for maintaining and publishing the National Building Code. Bottom Chord: An inclined or horizontal mem-ber that establishes the bottom of a truss. Bottom Plank: See Splashboard. Butt Joint: The interface at which the ends of two members meet in a square cut joint.

Page 9: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

1-4

Camber: A predetermined curvature designed into a structural member to offset the anticipated deflection when loads are applied. Check: Separation of the wood that usually ex-tends across the annual growth rings (i.e., a split perpendicular-to-growth rings). Commonly re-sults from stresses that build up in wood during seasoning. Cladding: The exterior and interior coverings fastened to the wood framing. Clear Height: Vertical distance between the finished floor and the lowest part of a truss, raf-ter, or girder. Collars: Components that increase the bearing area of portions of the post foundation, and thus increase lateral and vertical resistance. Components and Cladding: Elements of the building envelope that do not qualify as part of the main wind-force resisting system. In post-frame buildings, this generally includes individ-ual purlins and girts, and cladding. Diaphragm: A structural assembly comprised of structural sheathing (e.g., plywood, metal clad-ding) that is fastened to wood or metal framing in such a manner the entire assembly is capable of transferring in-plane shear forces. Diaphragm Action: The transfer of load by a diaphragm. Diaphragm Design: Design of roof and ceiling diaphragm(s), wall diaphragms (shearwalls), primary and secondary framing members, com-ponent connections, and foundation anchorages for the purpose of transferring lateral (e.g., wind) loads to the foundation structure. Dimension Lumber: Wood members from two (2) nominal inches to but not including five (5) nominal inches in thickness, and 2 or more nominal inches in width. Eave: The part of a roof that projects over the sidewalls. In the absence of an overhang, the eave is the line along the sidewall formed by the intersection of the wall and roof planes.

Fascia: Flat surface (or covering) located at the outer end of a roof overhang or cantilever end. Flashing: Sheet metal or plastic components used at major breaks and/or openings in walls and roofs to insure weather-tightness in a struc-ture. Footing: Support base for a post or foundation wall that distributes load over a greater soil area. Frame Spacing: Horizontal distance between post-frames (see post-frame and post-frame building). In the absence of posts, the frame spacing is generally equated to the distance be-tween adjacent trusses (or rafters). Frame spac-ing may vary within a building. Gable: Triangular portion of the endwall of a building directly under the sloping roof and above the eave line. Gable Roof: Roof with one slope on each side. Each slope is of equal pitch. Gambrel Roof: Roof with two slopes on each side. The pitch of the lower slope is greater than that of the upper slope. Girder: A large, generally horizontal, beam. Commonly used in post-frame buildings to sup-port trusses whose bearing points do not coin-cide with a post. Girt: A secondary framing member that is at-tached (generally at a right angle) to posts. Girts laterally support posts and transfer load be-tween wall cladding and posts. Glued-Laminated Timber: Any member com-prising an assembly of laminations of lumber in which the grain of all laminations is approxi-mately parallel longitudinally, in which the lami-nations are bonded with adhesives. Grade Girt: See Splashboard. Grade Line (grade level): The line of intersec-tion between the building exterior and the top of the soil, gravel, and/or pavement in contact with the building exterior. For post-frame building

Page 10: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

1-5

design, the grade line is generally assumed to be no lower than the lower edge of the splash-board. Header: A structural framing member that sup-ports the ends of structural framing members that have been cut short by a floor, wall, ceiling, or roof opening. Hip Roof: Roof which rises by inclined planes from all four sides of a building. IBC: International Building Code. ICBO: International Conference of Building Offi-cials. The organization responsible for maintain-ing and publishing the Uniform Building Code. Knee Brace: Inclined structural framing member connected on one end to a post/column and on the other end to a truss/rafter. Laminated Assembly: A structural member comprised of dimension lumber fastened to-gether with mechanical fasteners and/or adhe-sive. Horizontally- and vertically-laminated as-semblies are primarily designed to resist bend-ing loads applied perpendicular and parallel to the wide face of the lumber, respectively. Laminated Veneer Lumber (LVL) A structural composite lumber assembly manufactured by gluing together wood veneer sheets. Each ve-neer is orientated with its wood fibers parallel to the length of the member. Individual veneer thickness does not exceed 0.25 inches. Loads: Forces or other actions that arise on structural systems from the weight of all perma-nent construction, occupants and their posses-sions, environmental effects, differential settle-ment, and restrained dimensional changes.

Dead Loads: Gravity loads due to the weight of permanent structural and non-structural components of the building, such as wood framing, cladding, and fixed service equipment. Live Loads: Loads superimposed by the construction, use and occupancy of the building, not including wind, snow, seismic or dead loads.

Seismic Load: Lateral load acting in the horizontal direction on a structure due to the action of earthquakes. Snow Load: A load imposed on a structure due to accumulated snow. Wind Loads: Loads caused by the wind blowing from any direction.

Lumber Grade: The classification of lumber in regard to strength and utility in accordance with the grading rules of an approved (ALSC accred-ited) lumber grading agency. LVL: see Laminated Veneer Lumber. Main Wind-Force Resisting System: An as-semblage of structural elements assigned to provide support and stability for the overall structure. Main wind-force resisting systems in post-frame buildings include the individual post-frames, diaphragms and shearwall Manufactured Component. A component that is assembled in a manufacturing facility. The wood trusses and laminated columns used in post-frame buildings are generally manufactured components. MBMA: Metal Building Manufacturers Associa-tion. NDS®: National Design Specification® for Wood Construction. Published by AF&PA. Mechanically Laminated Assembly: A lami-nated assembly in which wood laminations have been joined together with nails, bolts and/or other mechanical fasteners. Metal Cladding: Metal exterior and interior cov-erings, usually cold-formed aluminum or steel sheet, fastened to the structural framing. NFBA: National Frame Builders Association. NFPA: National Fire Protection Association Nominal size: The named size of a member, usually different than actual size (as with lum-ber).

Page 11: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

1-6

Orientated Strand Board (OSB): Structural wood panels manufactured from reconstituted, mechanically oriented wood strands bonded with resins under heat and pressure. Orientated Strand Lumber (OSL): Structural composite lumber (SCL) manufactured from mechanically oriented wood strands bonded with resins under heat and pressure. Also known as laminated strand lumber (LSL) OSB: See Orientated Strand Board. Parallel Strand Lumber (PSL): Structural com-posite lumber (SCL) manufactured by cutting 1/8-1/10 inch thick wood veneers into narrow wood strands, and then gluing and pressing the strands together. Individual strands are up to 8 feet in length. Prior to pressing, strands are ori-ented so that they are parallel to the length of the member. Pennyweight: A measure of nail length, abbre-viated by the letter d. Plywood: A built-up panel of laminated wood veneers. The grain orientation of adjacent ve-neers are typically 90 degrees to each other. Pole: A round, unsawn, naturally tapered post. Post: A rectangular member generally uniform in cross section along its length. Post may be sawn or laminated dimension lumber. Com-monly used in post-frame construction to trans-fer loads from main roof beams, trusses or raf-ters to the foundation. Post Embedment Depth: Vertical distance be-tween the bottom of a post and the lower edge of the splashboard. Post Foundation: The embedded portion of a structural post and any footing and/or attached collar. Post Foundation Depth: Vertical distance be-tween the bottom of a post foundation and the lower edge of the splashboard. Post-Frame: A structural building frame consist-ing of a wood roof truss or rafters connected to vertical timber columns or sidewall posts.

Post-Frame Building: A building system whose primary framing system is principally comprised of post-frames. Post Height: The length of the non-embedded portion of a post. Pressure Preservative Treated (PPT) Wood: Wood pressure-impregnated with an approved preservative chemical under approved treatment and quality control procedures. Primary Framing: The main structural framing members in a building. The primary framing members in a post-frame building include the columns, trusses/rafters, and any girders that transfer load between trusses/rafters and col-umns. PSL: See Parallel Strand Lumber. Purlin: A secondary framing member that is attached (generally at a right angle) to rafters/ trusses. Purlins laterally support rafters and trusses and transfer load between exterior clad-ding and rafters/trusses. Rafter: A sloping roof framing member. Rake: The part of a roof that projects over the endwalls. In the absence of an overhang, the rake is the line along the endwall formed by the intersection of the wall and roof planes. Ridge: Highest point on the roof of a building which describes a horizontal line running the length of the building. Ring Shank Nail: See threaded nail. Roof Overhang: Roof extension beyond the endwall/sidewall of a building. Roof Slope: The angle that a roof surface makes with the horizontal. Usually expressed in units of vertical rise to 12 units of horizontal run. SBC: Standard Building Code (see SBCCI). SBCCI: Southern Building Code Congress In-ternational, Inc. The organization responsible for maintaining and publishing the Standard Build-ing Code.

Page 12: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

1-7

Secondary Framing: Structural framing mem-bers that are used to (1) transfer load between exterior cladding and primary framing members, and/or (2) laterally brace primary framing mem-bers. The secondary framing members in a post-frame building include the girts, purlins and any structural wood bracing. Self-Drilling Screw: A screw fastener that com-bines the functions of drilling and tapping (thread forming). Generally used when one or more of the components to be fastened is metal with a thickness greater than 0.03 inches Self-Piercing Screw: A self-tapping (thread forming) screw fastener that does not require a pre-drilled hole. Differs from a self-drilling screw in that no material is removed during screw in-stallation. Used to connect light-gage metal, wood, gypsum wallboard and other "soft" mate-rials. SFPA: Southern Forest Products Association Shake: Separation of annual growth rings in wood (splitting parallel-to-growth rings). Usually considered to have occurred in the standing tree or during felling. Shearwall: A vertical diaphragm in a structural framing system. A shearwall is any endwall, sidewall, or intermediate wall capable of trans-ferring in-plane shear forces. Siphon Break: A small groove to arrest the cap-illary action of two adjacent surfaces. Soffit: The underside covering of roof over-hangs. Soil Pressure: Load per unit area that the foun-dation of a structure exerts on the soil. Span: Horizontal distance between two points.

Clear Span: Clear distance between adja-cent supports of a horizontal or inclined member. Horizontal distance between the facing surfaces of adjacent supports. Effective Span: Horizontal distance from center-of-required-bearing-width to center-of-required-bearing-width, or the "clear

span" for rafters and joists in conventional construction. Out-To-Out Span: Horizontal distance be-tween the outer faces of supports. Com-monly used in specifying metal-plate-connected wood trusses. Overall Span: Total horizontal length of an installed horizontal or inclined member.

SPIB: Southern Pine Inspection Bureau. Skirtboard: See Splashboard. Splashboard: A preservative treated member located at grade that functions as the bottom girt. Also referred to as a skirtboard, splash plank, bottom plank, and grade girt. Splash Plank: See Splashboard. Stitch (or Seam) Fasteners: Fasteners used to connect two adjacent pieces of metal cladding, and thereby adding shear continuity between sheets. Structural Composite Lumber (SCL): Recon-stituted wood products comprised of several laminations or wood strands held together with an adhesive, with fibers primarily oriented along the length of the member. Examples include LVL and PSL. Threaded Nail: A type of nail with either annual or helical threads in the shank. Threaded nails generally are made from hardened steel and have smaller diameters than common nails of similar length. Timber: Wood members five or more nominal inches in the least dimension. Top Chord: An inclined or horizontal member that establishes the top of a truss. TPI: Truss Plate Institute. Truss: An engineered structural component, assembled from wood members, metal connec-tor plates and/or other mechanical fasteners, designed to carry its own weight and superim-posed design loads. The truss members form a

Page 13: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

1-8

semi-rigid structural framework and are assem-bled such that the members form triangles. UBC: Uniform Building Code (see ICBO). Wane: Bark, or lack of wood from any cause, on the edge or corner of a piece. Warp: Any variation from a true plane surface. Warp includes bow, crook, cup, and twist, or any combination thereof.

Bow: Deviation, in a direction perpendicular to the wide face, from a straight line drawn between the ends of a piece of lumber. Crook: Deviation, in a direction perpendicu-lar to the narrow edge, from a straight line drawn between the ends of a piece of lum-ber. Cup: Deviation, in the wide face of a piece of lumber, from a straight line drawn from edge to edge of the piece. Twist: A curl or spiral of a piece of lumber along its length. Measured by laying lumber on a flat surface such that three corners contact the surface. The amount of twist is equal to the distance between the flat sur-face and the corner not contacting the sur-face.

WCLIB: West Coast Lumber Inspection Bureau Web: Structural member that joins the top and bottom chords of a truss. Web members form the triangular patterns typical of most trusses. WTCA: Wood Truss Council of America. WWPA: Western Wood Products Association. 1.6 References Faherty, K.F. and T.G. Williamson. 1989. Wood Engineering and Construction Handbook. McGraw-Hill Publishing Company, New York, NY. Gurfinkel, G. 1981. Wood Engineering (2nd Ed.). Kendall/Hunt Publishing Company, Dubuque, Iowa.

Harmon, J.D., G.R. Grandle and C.L. Barth. 1992. Effects of hurricane Hugo on agricultural structures. Applied Engineering in Agriculture 8(1):93-96. Knight, J.T. 1989. A brief look back. Frame Building Professional 1(1):38-43. Knight, J.T. 1990. Diaphragm design - technol-ogy driven by necessity. Frame Building Profes-sional 1(5):16,44-46. Norum, W.A. 1967. Pole buildings go modern. Journal of the Structural Division, ASCE, Vol. 93, No.ST2, Proc. Paper 5169, April, pp.47-56. Taylor, S.E. 1996. Earthquake considerations in post-frame building design. Frame Building News 8(3):42-49.

Page 14: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

2-1

Chapter 2: BUILDING CODES, DESIGN SPECIFICATIONS AND ZONING REGULATIONS

2.1 Introduction 2.1.1 Definition. A building code is a legal document that helps ensure public health and welfare by establishing minimum standards for design, construction, quality of materials, use and occupancy, location and maintenance of all buildings and structures. 2.1.2 Model Versus Active Codes. A model code is a code that is written for general use (i.e., a code that is not written for use by a spe-cific state, county, town, village, company or individual). An active code is a model or spe-cially written code that has been adopted and is enforced by a regulatory agency such as a state or local government. It follows that in a given jurisdiction, acceptance of a model building code is voluntary until the model code becomes part of the active code in the jurisdiction. 2.1.3 Active Code Variations. The content and administration of active building codes varies not only between states, but frequently between municipalities within a state. Some states have established a hierarchy structure of state, county and township/village/city building codes. In this situation, more localized governing areas can modify the state (or county) codes, provided the changes result in more strict provisions. Despite local differences in content and admini-stration, most active building codes share the common trait of regulating components of con-struction based on building occupancy and use. 2.2 Major Model Building Codes 2.2.1 Current Codes. There are currently three primary model building codes in the United States. These are the Uniform Building Code (UBC) published by the International Congress of Building Officials, the National Building Code published by the Building Officials and Code Administrators International (BOCA) and the Standard Building Code published by the Southern Building Code Congress International

(SBCCI). These model building codes are com-monly referred to as the UBC, BOCA and the Southern Building Code, respectively. 2.2.2 Adoption. Most states have adopted (and enforce) all or a major portion of one of the three model building codes. As shown in figure 2.1, western states have adopted the UBC, north-eastern states the BOCA code, and states in the southwest the Southern Building Code. 2.2.3 Development. Model building codes are consensus documents continually studied and annually revised by building officials, industry representatives and other interested parties. 2.2.4 International Building Code. On De-cember 9, 1994, the three model building code agencies (BOCA, ICBO and SBCCI) created the International Code Council (ICC). The ICC was established in response to technical disparities among the three major model codes. Since its founding, the ICC has worked to create a single model building code for the U.S. This code, which is entitled the International Building Code is now complete and will replace the three model codes over the next couple years. With all states adopting the same model code, it will be less difficult for building designers to work in different regions of the country. 2.3 Building Classification 2.3.1 General. Building codes give criteria for classifying buildings based on: (1) use or occu-pancy, and (2) type of construction. 2.3.2 Occupancy Classifications. Occupancy classifications include assembly, business, edu-cational, factory and industrial, high-hazard, in-stitutional, mercantile, residential and storage. Occupancy classifications have requirements on the number of occupants and building separa-tion, height and area. Other limits exist, for ex-ample on lighting, ventilation, sanitation, fire

Page 15: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

2-2

Figure 2.1. Approximate areas of model building code influence. Wisconsin and New York building codes are developed by their respective state code agencies and are not necessarily influenced by current model codes.

protection and exiting, depending on the specific classification and building code. 2.3.2 Types of Construction. Classification by type of construction is primarily based on the fire resistance ratings of the walls, partitions, struc-tural elements, floors, ceilings, roofs and exits. Specific requirements vary somewhat between model building codes. There are two primary source documents for determining the fire resistance of assemblies: the Fire Resistance Design Manual, published by the Gypsum Association, and the Fire Resis-tance Directory, published by Underwriters Laboratories, Inc. The fire resistance of wood framed assemblies can generally be increased by using fire retar-dant treated (FRT) wood or larger wood mem-bers. Codes allow FRT wood to be used in cer-

tain areas of noncombustible construction. The superior fire resistance of large timber members is recognized by the codes with the inclusion of a "heavy timber" classification. To qualify for heavy timber construction, nominal dimensions of timber columns must be at least 6- by 8-inches and primary beams shall have nominal width and depth of at least 6- by 10-inches.

2.3.2.1 NFBA Sponsored Fire Test. In January of 1990, the National Frame Build-ers Association had Warnick Hersey Inter-national, Inc., conduct a one-hour fire en-durance test on the exterior wall shown in figure 2.2. The wall met all requirements for a one-hour rating as prescribed in ASTM E-119-88. The wall sustained an applied load of 10,400 lbf per column throughout the test. Copies of the fire test report can be obtained from NFBA.

Uniform Building Code (ICBO)National Building

Code (BOCA)

Standard Building Code (SBCCI)

Page 16: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

2-3

Figure 2.2. Construction details for exterior wall that obtained a one-hour fire endurance rating during a January 1990 test conducted for the National Frame Builders Association by Warnock Hersey International, Inc. Details of the test are available from NFBA upon request.

2.4 Specifications and Standards 2.4.1 General. Design of buildings is covered in the model building codes either by direct provi-sions or by reference to approved engineering specifications and standards. Engineering speci-fications and standards provide criteria and data needed for load calculation, design, testing and material selection. They are based on the best available information and engineering judgment. 2.4.2 Wood Design Specifications. The tech

nical literature for wood design and construction is somewhat fragmented. New design specifica-tions and standards are continually under devel-opment, and existing documents are periodically revised. Keeping abreast of this literature re-quires a determined effort on the part of the de-sign professional. To assist in this effort, Table 2.1 gives a partial list of engineering design specifications, standards and other technical references specifically related to post-frame construction. The reader is encouraged to main-tain communication with the organizations isted in Table 2.1 concerning new and revised publi-cations.

A A

Nominal 2- by 4-inch nailers, 24 in. o.c.

3- by 24- by 48-inchmineral wool, attach with 3 in. square cap nails (3

per 48 in. width)

Fire side nailers, nominal 2- by 4-inches

24 in. o.c.

Gold Bond 5/8 in. Fireshield G Type X, attached with 1-7/8 in. cement coated nails

(0.0195 in. shank, 1/4 head, 7 in. o.c.)

Metal cladding 29 gage

Nominal 2- by 2-inch blocking between nailers (nailed to nominal 2- by

6-inch edge blocks)

4-1/16- by 5-1/4-inch glue-laminated column

10 ft

Nail-laminated column fabricated from 3 nominal 2- by 6-inch No. 2 KD19 SP members

Nominal 2- by 4-inch blocking attached to column

Section B-B

Section A-A

Unexposed nominal 2- by 4-inch nailers 24

in. o.c.

B

B1 ft 8 ft 1 ft

Attach metal cladding 12 in. o.c. with 1.5 in. hex head screws with neoprene washers

FIRE SIDE

Page 17: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

2-4

Of the documents listed in Table 2.1, the primary engineering design specification cited by the model building codes for wood construction is the National Design Specification® for Wood Construction (NDS®), published by the American Forest & Paper Association (AF&PA). The NDS was first issued in 1944 and in 1992 it became a consensus standard through the American Na-tional Standards Institute (ANSI). 2.5 Zoning Regulations 2.5.1 General. Zoning laws are established to-control construction activities and regulate land use, in terms of types of occupancy, building

height, and density of population and activity. Zoning laws may also dictate building appear-ance and location on property, parking signs, drainage, handicap accessibility, flood control and landscaping. Typically land is zoned for residential, commercial, industrial or agricultural uses. 2.5.2 Development and Enforcement. Zoning laws are developed by municipalities. They (and building codes) are principally enforced by the granting of building permits and inspection of construction work in progress. Certificates of occupancy are issued when completed buildings satisfy all regulations.

Table 2.1. Partial list of technical references related to post-frame building design and construction

Organization & Address Publications

AF&PA American Forest & Paper Association 1111 19th Street, N.W., Suite 800 Washington, D.C. 20036 http://www.awc.org/

Allowable stress design (ASD) manual for engineered wood

construction National design specification® (NDS®) for wood construction NDS commentary Design values for wood construction (NDS supplement) Load and resistance factor design (LRFD) manual for engi-

neered wood construction Wood frame construction manual (WFCM) for one-and two-

family dwellings Span tables for joists and rafters

AITC American Inst. of Timber Construction 7012 S. Revere Parkway, Suite 140 Englewood, CO 80112

Timber construction manual

ANSI American National Standards Institute 11 West 42nd Street New York, NY 10036 http://www.ansi.org/

ANSI/AF&PA National design specification for wood construc-tion (see AF&PA)

ANSI Standard A190 structural glued laminated

Page 18: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

2-5

Table 2.1. Partial list of technical references related to post-frame building design and construction Organization & Address Publications

APA The Engineered Wood Association P.O. Box 11700 7011 South 19th Street Tacoma, WA 98411 http://www.apawood.org/

APA design/construction guide; residential and commercial Plywood design specification (PDS) Diaphragms and shear walls Performance standard for APA EWS I-joists Panel handbook & grade glossary

ASAE 2950 Niles Road St. Joseph, MI 49085-9659 http://asae.org/

ASAE EP288 Agricultural building snow and wind loads ASAE EP484.2 Diaphragm design of metal-clad, wood-frame

rectangular buildings ASAE EP486 Post and pole foundation design ASAE EP558 Load tests for metal-clad, wood-frame dia-

phragms ANSI/ASAE EP559 Design requirements and bending proper-

ties for mechanically laminated columns

ASCE American Society of Civil Engineers 1801 Alexander Bell Drive Reston, Virginia 20191-4400 http://www.asce.org/

ASCE Standard 7 Minimum Design Loads for Buildings and

Other Structures Standard for load and resistance factor design (LRFD) for engi-

neered wood construction Guide to the use of the wind load provisions of ASCE 7-95

AWPA American Wood Preservers Assoc. P.O. Box 5690 Granbury, TX 76049

Standard C2 lumber, timbers, bridge ties and mine ties - pre-

servative treatment by pressure processes Standard C15 wood for commercial-residential construction -

preservative treatment by pressure processes Standard C16 wood used on farms - preservative treatment by

pressure processes Standard C23 round poles and posts used in building construc-

tion - preservative treatment by pressure processes Standard M4 standard for the care of preservative-treated wood

products

AWPI American Wood Preservers Institute 2750 Prosperity Avenue, Suite 550 Fairfax, Virginia 22031-4312 http://www.awpi.org/

Answers to often-asked questions about treated wood Management of used treated wood products booklet

Gypsum Association 810 First St., NE, #510 Washington DC, 20002 http://www.gypsum.org/

Fire resistance design manual GA-600 Design data - gypsum board GA-530

Page 19: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

2-6

Table 2.1. Partial list of technical references related to post-frame building design and construction Organization & Address Publications

ICC International Code Council http://www.intlcode.org/ BOCA International, Inc. 4051 West Flossmoor Road Country Club Hills, IL 50478-5794 http://www.bocai.org/ ICBO 5360 Workman Mill Road Whittier, CA 90601-2298 http://www.icbo.org/ SBCCI, Inc. 900 Montclair Road Birmingham, AL 35213-1206 http://www.sbcci.org/

International building code International energy conservation code International zoning code International property maintenance code commentary International property maintenance code International fuel gas code International mechanical code commentary International mechanical code International mechanical code supplement International private sewage disposal code International one and two family dwelling code International plumbing code commentary International plumbing code

MBMA Metal Building Manufacturers Assoc. 1300 Sumner Ave Cleveland, OH 44115-2851 http://www.mbma.com/

Low rise building systems manual Metal building systems

NFBA National Frame Builders Association 4840 W. 15th St., Suite 1000 Lawrence, KS 66049-3876 http://www.postframe.org/

Post wall assembly fire test

NFPA National Fire Protection Association 1 Batterymarch Park Quincy, MA 02269-9101 http://www.nfpa.org/

NFPA 1: Fire prevention code NFPA 13: Installation of sprinkler NFPA 70: National electrical code NFPA 72: National fire alarm code NFPA 101: Life safety code

SPIB Southern Pine Inspection Bureau 4709 Scenic Highway Pensacola, Fl. 32504-9094 http://www.SPIB.org/

Grading rules Standard for mechanically graded lumber Kiln drying southern pine

Page 20: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

2-7

Table 2.1. Partial list of technical references related to post-frame building design and construction Organization & Address Publications

SFPA & Southern Pine Council Southern Forest Products Association P. O. Box 641700 Kenner, LA 70064-1700 http://www.southernpine.com/ http://www.SFPA.org/

Southern pine use guide Southern pine joists & rafters: construction guide Southern pine joists & rafters: maximum spans Post-frame construction guide Southern pine headers and beams Pressure-treated southern pine Permanent wood foundations: design & construction guide

TPI Truss Plate Institute 583 D'Onofrio Drive, Suite 200 Madison, WI 53719

ANSI/TPI 1-1995 National design standard for metal plate con-

nected wood truss construction HIB-91 Summary sheet: handling, installing & bracing metal

plate connected wood trusses HIB-98 Post frame summary sheet: recommendations for han-

dling, installing & temporary bracing metal plate connected wood trusses used in post-frame construction

HET-80 Handling & erecting wood trusses: commentary and recommendations

DSB-89 Recommended design specifications for temporary bracing of metal plate connected wood trusses

UL Underwriters Laboratories, Inc. 333 Pfingsten Road Northbrook, IL 60062-2096 http://www.ul.com/

Fire resistance directory

WTCA Wood Truss Council of America One WTCA Center 6425 Normandy Lane Madison, WI 53711 http://www.woodtruss.com/

Metal plate connected wood truss handbook Commentary for permanent bracing of metal plate connected

wood trusses Standard responsibilities in the design process involving metal

plate connected wood trusses

WWPA Western Wood Products Association 522 SW Fifth Ave., Suite 500 Portland, Oregon 97204-2122 http://www.wwpa.org/

Western woods use book Western lumber span tables Western lumber grading rules

Page 21: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

2-8

Page 22: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

3-1

Chapter 3: STRUCTURAL LOAD AND DEFLECTION CRITERIA

3.1 Introduction 3.1.1 Load Variations. Most structural loads exhibit some degree of random behavior. For example, weather-related loads such as snow, wind and rain fluctuate over time and locations. Extensive research has been conducted to characterize this load variation, and to refine procedures for determining design loads within the context of the intended building occupancy and use. 3.1.2 Codes. Calculation procedures for mini-mum design loads are given in the model build-ing codes. Buildings shall be designed to safely carry all loads specified by the governing build-ing code. In the absence of a code, minimum design loads shall be calculated according to recommended engineering practice for the re-gion and application under consideration. It is impractical to describe detailed load calcula-tion procedures in this chapter because of dif-ferences between building codes and frequent revisions of these codes. Instead, general con-cepts and key references related to structural loads and deflection criteria are presented, with an emphasis on issues that apply to post-frame buildings. 3.2 Technical References on Structural Load Determination 3.2.1 ANSI/ASCE 7 Standard. The National Bureau of Standards published a report titled Minimum Live Load Allowable for Use in Design of Buildings in 1924. The report was expanded and published as ASA Standard A58.1-1945. This standard has undergone several revisions to become the current ASCE Standard ANSI/ASCE 7 Minimum Design Loads for Build-ings and Other Structures. At the time this de-sign manual was written, the most recent revi-sion of ASCE 7 was 1999 (ASCE, 1999); how-ever, the edition most commonly used is ASCE 7-93. The ASCE 7 standard is periodically re-vised and balloted through the ANSI consensus

approval process, and then must be adopted by the model building codes. Design professionals should check the governing building code for the latest adopted edition. For clarity of presenta-tion, this manual uses and will refer to ASCE 7-93. ASCE 7-93 is the primary technical source used by the model codes concerning dead, live, snow, wind, rain and seismic loads. Basically, the model codes attempt to distill the rigorous ASCE 7-93 procedures into a simpler, easy-to-use format. Many specific load calculation pro-cedures differ between the model codes; how-ever, most of the basic concepts mimic ASCE 7-93. Background information on the wind load provisions in ASCE 7-88 (which are essentially the same as in ASCE 7-93) are given by Mehta et al. (1991). 3.2.2 Low Rise Building Systems Manual. The Low Rise Building Systems Manual, pub-lished by the Metal Building Manufacturers As-sociation (1986), is recognized by model build-ing codes as an excellent technical resource document for calculating structural loads on low-rise buildings (e.g. post-frame buildings). This document will be referred to as MBMA-86 throughout this manual. Because wind and crane loads frequently control the design of low-rise metal buildings, the coverage of these loads within MBMA-86 is especially thorough. Another attractive feature of MBMA-86 is the extensive collection of example load calculations. 3.2.3 ASAE EP288.5 Standard. Agricultural buildings generally fall into a separate class from other types of buildings due to the lower risks involved. The American Society of Agricul-tural Engineers publishes a snow and wind load standard, EP288.5, intended for agricultural buildings (ASAE, 1999). The major differences between agricultural and other types of buildings are that lower values are used for importance and roof snow conversion factors (due to rela-tively lower risk factors for property and non-public use). If the local governing building code applies to agricultural buildings, then the design load criteria in the code must be followed.

Page 23: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

3-2

Table 3.1. Approximate Weights of Construction Materials (from Hoyle and Woeste, 1989)

Material Weight (lb/ft2) Material Weight

(lb/ft2) Ceilings Roofs (continued)

Acoustical fiber tile 1.0 Plywood (per inch thickness) 3.0 Gypsum board (see Walls) Roll roofing 1.0 Mechanical duct allowance 4.0 Shingles Suspended steel channel system 2.0 Asphalt 2.0 Wood purlins (see Wood, Seasoned) Clay tile 9.0-14.0 Light gauge steel (see Roofs) Book tile, 2-in. 12.0

Book tile, 3-in 20.0 Floors Ludowici 10.0

Hardwood, 1-in. nominal 4.0 Roman 12.0 Plywood (see Roofs) Slate, ¼ in. 10.0 Linoleum, 1/4-in. 1.0 Wood 3.0 Vinyl tile, 1/8-in. 1.4

Walls Roofs Wood paneling, 1-in. 2.5

Corrugated Aluminum Glass, plate, 1/4-in. 3.3 14 gauge 1.1 Gypsum board (per 1/8-in. thick- 0.55 16 gauge 0.9 Masonry, per 4-in. thickness 18 gauge 0.7 Brick 38.0 20 gauge 0.6 Concrete block 20.0

Built-Up Cinder concrete block 20.0 3-ply 1.5 Stone 55.0 3-ply with gravel 5.5 Porcelain-enameled steel 3.0 5-ply 2.5 Stucco, 7/8-in. 10.0 5-ply with gravel 6.5 Windows, glass, frame, and sash 8.0

Corrugated Galvanized steel 16 gauge 2.9 Wood, Seasoned Density

318 gauge 2.4 lb/ft3 20 gauge 1.8 Cedar 32.022 gauge 1.5 Douglas-fir 34.0 24 gauge 1.3 Hemlock 31.0 26 gauge 1.0 Maple, red 37.0 29 gauge 0.8 Oak 45.0

Insulation, per inch thickness Poplar, yellow 29.0 Rigid fiberboard, wood base 1.5 Pine, lodgepole 29.0 Rigid fiberboard, mineral base 2.1 Pine, ponderosa 28.0 Expanded polystyrene 0.2 Pine, Southern 35.0 Fiberglass, rigid 1.5 Pine, white 27.0 Fiberglass, batt 0.1 Redwood 28.0

Lumber (see Wood, Seasoned) Spruce 29.0

Page 24: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

3-3

3.3 Minimum Design Loads Sections 3.4, 3.5, 3.6, 3.7, and 3.8 give general load requirements, sources of load data and references for making detailed load calculations. Detailed calculation procedures are not provided due to differences between the model codes and the frequency of code revisions. 3.4 Dead Loads 3.4.1 Definition. Dead loads are the gravity loads due to the combined weights of all perma-nent structural and nonstructural components of the building, such as sheathing, trusses, purlins, girts and fixed service equipment. These loads are constant in magnitude and location through-out the life of the building. 3.4.2 Code Application. Minimum design dead loads shall be determined according to the gov-erning building code. In the absence of a build-ing code, dead load data can be found in ASCE 7-93, or actual weights of materials and equip-ment can be used. 3.4.3 Special Considerations. Design dead loads that exceed the weights of construction materials and permanent fixtures are permitted, except for when checking building stability under wind loading. Using inflated design dead loads may lead to conservative designs for gravity load conditions; however, it would not be a con-servative assumption for designing anchorage to counteract uplift, overturning and sliding due to wind loads. In the cases of wind uplift and over-turning, the dead load used in design must not exceed the actual dead load of the construction. 3.4.4 Weights of Construction Materials. Ta-ble 3.1 lists approximate weights of materials. commonly used in post-frame construction. 3.5 Live Loads 3.5.1 Definition. Live loads are defined as the loads superimposed by the construction, main-tenance, use and occupancy of the building, and therefore do not include wind, snow, seismic or dead loads.

Technical Note Horizontal Uniform Dead Load Calculation Many structural analysis programs (e.g. Purdue Plane Structures Analyzer) require that the dead load associated with a sloping surface be repre-sented as a uniform load, wDL, acting on a hori-zontal plane as shown in figure 3.1. For a given horizontal distance, bH, a sloping roof surface contains more material and is heavier than a flat one. Thus, wDL increases as roof slope in-creases. Load wDL is obtained by multiplying the unit weight of the roof assembly, wR, by the slope length, bS, and dividing the resulting product by the horizontal length, bH. Numerically, this is equivalent to dividing wR by the cosine of the roof slope. Example: For a roof at a 4:12 slope, with materi-als weighing 4 lbm for each square foot of roof surface area, the equivalent load, wDL, to apply to the horizontal plane would be: wDL = (4 lbm/ft2)/(cos 18.4°) = 4.21 lbm/ft2

Figure 3.1. Roof dead load represented by an equivalent uniform load acting on a horizontal plane. 3.5.2 Code Application. Design live loads shall be determined so as to provide for the service requirements of the building, but should never be lower than the minimum live load specified in

wDL

θ

bH

bS

Rafter or truss top chord

Roof assembly with weight wR per unit area

Page 25: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

3-4

the governing building code. In the absence of a governing building code, the minimum live loads found in ASCE 7-93 are recommended. The minimum roof live load recommended for agri-cultural buildings in ASAE Standard EP288.5 is 12 psf. Some agricultural buildings do not nec-essarily pose a "low risk", and the ASAE higher minimum live load reflects the possibility of high-value agricultural constructions now common in the United States 3.5.3 Reductions. In some cases, reductions are allowed for uniform loads to account for the low likelihood of the loads simultaneously occur-ring over the entire tributary area. 3.6 Snow Loads 3.6.1 Code Application. Minimum design snow loads shall be determined by the provisions of the governing building code. The presentation of snow loads varies among the model codes, but they all follow the basic concepts presented in ASCE 7-93. In the absence of a building code, procedures given in ASCE 7-93 are recom-mended. For low-risk agricultural buildings, snow load calculation procedures given in ASAE EP288.5 are permitted. 3.6.2 Ground Snow Load Maps. ASCE 7-93 presents ground snow load maps that corre-spond to a mean recurrence interval of 50 years. These maps do not give snow load values for areas that are subject to extreme variations in snowfall, such as western mountain regions. In some regions, the best and only reliable source for ground snow loads is local climatic records. 3.6.3 Roof Snow Loads. Roof snow loads are influenced by a number of factors besides ground snow load. These factors include roof slope, temperature and coefficient of friction of the roof surface, and wind exposure. Snow loads are also adjusted by an importance factor to account for risk to property and people. The basic form of the snow load calculation found in ASCE 7-93 is: pf = R Ce Ct I Cs Pg (3-1) where:

pf = roof snow load in psf, R = roof snow factor that relates roof

load to ground snowpack, Ce = snow exposure factor, Ct = roof temperature factor, I = importance factor, Cs = roof slope factor, and Pg = ground snow load in psf (50-yr

mean recurrence). The roof snow factor, R, varies from 0.6 for Alaska to 0.7 for the contiguous United States. The snow exposure factor in the model codes accounts for the combined effects of R and Ce given in Equation 3-1. The thermal factor de-fined in ASCE 7-93 varies from 1.0 for heated structures to 1.2 for unheated structures. The thermal factor is not included in the model build-ing codes. The importance factors range from 0.8 to 1.2 depending on the specific building code. Roof slope factors vary linearly from 0 to 1 as roof slope increases from 15 to 70 degrees. 3.6.5 Special Considerations. Several factors, such as multiple gables, roof discontinuities, and drifting can cause snow to accumulate unevenly on roofs. These factors must be considered in the design. Specific recommendations and cal-culation procedures are given in the model codes and ASCE 7-93. 3.7 Wind Loads 3.7.1 Controlling Factors. Wind loads are in-fluenced by wind speed, building orientation and geometry, building openings and exposure. Wind loading on structures is a complex phe-nomenon and is being actively researched. 3.7.2 Code Application. Minimum design wind loads shall be determined by the provisions of the governing building code. In the absence of a building code, procedures given in ASCE 7-93 or MBMA-86 are recommended. For low-risk agricultural buildings, wind load calculation pro-cedures given in ASAE EP288.5 are permitted. 3.7.3 Design Wind Speed. ASCE 7-93 gives a map showing basic wind speeds throughout the United States that correspond to a mean recur-rence interval of 50 years. Local weather rec-

Page 26: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

3-5

ords should be used in regions that have un-usual wind events. Detailed procedures and il-lustrations for calculating wind loads on low-rise buildings are given in MBMA-86. Technical Note Wind Speed Wind speeds are derived from data which reflect both magnitude and duration. Wind speeds can be reported as peak gusts, or can be averaged over some time interval. The time interval may be fixed, as with mean hourly speeds, or vari-able, as with “fastest-mile” wind speeds. Fast-est-mile wind speeds are used in ANSI/ASCE 7-93 to calculate design loads, and are defined on the basis of the period of time that one mile of wind takes to pass an anemometer at a stan-dard elevation of 10 meters. The U.S. National Weather Service no longer collects fastest-mile wind speed data; instead, they record 3-second gust speeds. The 1995 and later revisions of ASCE-7 base wind loads on 3-second gust wind speeds. 3.7.4 Effective Wind Velocity Pressure. The first step in determining wind loads is to calcu-late the effective wind velocity pressure. The most severe exposure factors that will apply dur-ing the service life of the structure should be used. Wind velocity pressure is a function of the wind speed, exposure and importance. The equation for calculating wind velocity pressure, qz , is given by: qz = 0.00256 Kz (I V)2 (3-2) where:

Kz = velocity pressure exposure coeffi-cient,

I = importance factor, and V = basic wind speed in mph (50-year

mean recurrence interval). The velocity pressure exposure coefficient is a function of height above ground and exposure category. Exposure categories account for the effects of ground surface irregularities caused by natural topography, vegetation, location and building construction features. ASCE 7-93 lists four wind exposure categories, whereas the

model codes publish fewer exposure categories. Importance factors vary from 0.95 for agricul-tural buildings (25-year recurrence interval) to 1.07 for buildings that represent a high hazard to property and people in the event of failure (100-year recurrence interval). Wind pressure is re-lated to the square of its speed, therefore the terms V and I are squared in equation 3-2. The model building codes simplify the calculation in equation 3-2 by publishing tables of effective wind velocity pressures, Pb, for a base wind speed and various heights. 3.7.5 Pressure Coefficients. Wind loads are calculated for each part of the building by multi-plying the effective wind pressure by a pressure coefficient. The pressure coefficient, which may be different for each planar portion of the build-ing, accounts for building orientation, geometry and load sharing. It also accounts for localized pressures at eaves, overhangs, corners, etc. Wind pressures, qi, for the ith building surface are calculated by: qi = Cpi qz (3-3) where: Cpi = ith pressure coefficient, and qz = wind velocity pressure. The wind velocity pressure is based on the wall height for the windward wall and on the mean roof height for the leeward wall and roof. Wind pressures act normal to the building surfaces. Inward pressures are denoted with positive signs, while outward pressures (suction) are denoted with negative signs. Technical Note Components of Wind Load Many structural analysis programs require uni-form loads to be entered in terms of their hori-zontal and vertical components. Wind loads act normal to building surfaces, so an adjustment is needed for sloping members such as roof trusses. The roof wind load, w, shown in figure 3.2a is equivalent to the horizontal and vertical components shown in figure 3.2b. The relation-ship depicted in figure 3.2 can be proven as fol-lows:

Page 27: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

3-6

1. Convert the uniform wind load, w, to its re-

sultant vector force. R = w (span)/(cos θ) 2. Multiply resultant force, R, by cos θ to obtain

its vertical component. Fy = R (cos θ) = w (span) 3. Divide the vertical component, Fy, by the

span to obtain the horizontally projected up-lift pressure, whoriz.

whoriz = Fy /(span) = w (span)/(span) = w The vertically projected uniform load can be proven similarly. A common mistake is to multi-ply the normal pressure by sine and cosine of the roof slope to obtain the two components.

Figure 3.2. Illustration of wind load acting nor-mal to inclined surface and equivalent horizontal and vertical load components. A common mis-take is to multiply the normal load by sin(θ) and cos(θ) for the vertical and horizontal compo-nents, respectively. 3.7.6 Main Frames. Different pressure coeffi-cients are used to calculate wind loads on main frames as compared to components and clad-ding. Main frames include primary structural sys-tems such as rigid and braced frames, braced trusses, posts, poles and girders. Since

these members have relatively large tributary areas, localized wind effects tend to be aver-aged out over the tributary areas. Pressure coef-ficients for main members reflect this averaging effect. 3.7.7 Components and Cladding. Wind pres-sures are higher on small areas due to localized gust effects. This observation has been verified by wind tunnel studies (MBMA, 1986), as well as site inspections of wind-induced building failures (Harmon, et al., 1992). For this reason, compo-nents and cladding have higher pressure coeffi-cients than main frames. Components and clad-ding include members such as purlins, girts, cur-tain walls, sheathing, roofing and siding. 3.7.8 Openings. Wind loads are significantly affected by openings in the structure. ASCE 7-93 and the model building codes specify internal wind pressure coefficients (or adjustments to external pressure coefficients) for structures with different amounts and types of openings. Each model code has slightly different definitions and wind load coefficients for open, closed and par-tially open buildings. In general, "openings" refer to permanent or other openings that are likely to be breached during high winds. For example, if window glazings are likely to be broken during a windstorm, the windows are considered open-ings. However, if doors and windows and their supports are designed to resist design wind loads, they need not be considered openings. It should be noted that internal wind pressures act against all interior surfaces and therefore do not contribute to sidesway loads on a building. 3.8 Seismic Loads 3.8.1 Cause. Earthquakes produce lateral forces on buildings through the sudden move-ment of the building’s foundation. Building re-sponse to seismic loading is a complex phe-nomenon and there is considerable controversy as to how to translate knowledge gained through research into practical design codes and stan-dards. 3.8.2 Code Application. Seismic loads shall be determined by the provisions of the governing building code. In the absence of a building code, procedures given in ASCE 7-93 are recom-mended. Sweeping changes were made in the

(a)

θ

w

(b)

w

Page 28: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

3-7

1993 revision of ASCE 7 with respect to seismic loads. The seismic provisions in ASCE 7-93 were based on work by the Building Seismic Safety Council under sponsorship of the Federal Emergency Management Agency. 3.8.3 Lateral Force. Basic concept of seismic load determination for low-rise buildings is to calculate an equivalent lateral force at the ground line as follows: V = Cs W (3-4) where: V = total lateral force, or shear, at the

building base W = total dead load, plus other applica-

ble loads specified in the code or ASCE 7-93. For most single-story post-frame buildings, the only other minimum applicable load is a por-tion (20% minimum) of the flat roof snow load. If the flat roof snow load is less than 30 psf, the applicable load to be included in W is permitted to be taken as zero.

Cs = seismic design coefficient = 1.2 Av S/(T2/3 R) Av = coefficient representing effective

peak velocity-related acceleration S = coefficient for the soil profile charac-

teristics R = response modification factor T = fundamental period of the building 3.8.4 Seismic loads rarely control post-frame building design because of the relatively low building dead weight as compared with other types of construction (Taylor, 1996; Faherty and Williamson, 1989). For post-frame buildings, lateral loads from wind usually are much greater than those from seismic forces. 3.9 Load Combinations for Allowable Stress Design 3.9.1 Code Application. Every building ele-ment shall be designed to resist the most critical load combinations specified in the governing building code.

3.9.2 Load Combinations. Except when appli-cable codes provide otherwise, the following load combinations shall be considered (as a minimum) and the combination which results in the most conservative design for each building element shall be used. Note that different load combinations may control the design of different components of the structure. Case 1: Dead + Floor Live + Roof Live (or Snow) Case 2: Dead + Floor Live + Wind (or Seismic) Case 3: Dead + Floor Live + Wind + ½ Snow Case 4: Dead + Floor Live + ½ Wind + Snow Case 5: Dead + Floor Live + Snow + Seismic 3.9.3 Floor Live Loads. Most post-frame build-ings are single story and therefore would not have floor live loads acting on the post-frames. When a concrete floor is used in a single story building, consideration must be given to antici-pated live and equipment loading. 3.9.4 Reductions. Reductions in some of the load terms in Cases 1 through 5 are permitted, depending on governing building code or refer-ence document. With some exceptions, the model building codes permit allowable stresses used in allowable stress design to be increased one-third when considering wind or seismic forces either acting alone or when combined with vertical loads. The allowable stress in-crease for wind loading can be traced back to the New York City Building Code of 1904 (Elli-fritt, 1977), and appears to be based on judg-ment rather than engineering theory. It should be noted that ASCE 7-93 does not include the one-third increase factor, but instead specifies load combination factors that are intended to account for the low probability of maximum live, seismic, snow and wind loads occurring simul-taneously. The commentary of ASCE 7-93 im-plies the stress increase for wind and seismic found in codes is not appropriate if the com-bined load effects are also reduced by the load combination factors published in ASCE 7-93. Finally, the National Design Specification (NDS) for Wood Construction (NF&PA, 199) addresses the issue of load combination versus load dura-tion factors by stating, “The load duration fac-tors, CD, in Table 2.3.2 and Appendix B are in-dependent of load combination factors, and both shall be permitted to be used in design calcula-tions.”

Page 29: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

3-8

3.10 Load Duration Factors for Wood It is well documented that wood has the property of being able to carry substantially greater loads for short durations than for long durations of loading. This property is accounted for in design through the application of load duration factors to all allowable design values except modulus of elasticity and compression perpendicular to grain. Additional restrictions and details on load duration adjustments can be found in Chapter 2 and Appendix B of the NDS (AF&PA, 1997). 3.10.1 Snow Load. The cumulative duration of maximum snow load over the life of a structure is generally assumed to be two months. It should be emphasized that the two-month pe-riod does not necessarily mean that the design snow load from any one event would last two months. Rather, it means that the total time that the roof supports the full design snow load over the life of the structure is two months. If the cu-mulative full design load is two months, an al-lowable stress increase of 15 percent is allowed (AF&PA, 1997). However, in some situations, such as unheated or heavily insulated buildings in cold climates, longer snow load durations may occur and the stress increase may not be justi-fied. 3.10.2 Wind Load. The cumulative duration of maximum wind (and seismic) loads over the life of a structure is generally assumed to be 10 minutes (AF&PA, 1997), if design wind loads are based on ASCE 7-93, and the corresponding load duration factor is 1.6. Other load duration adjustments may be appropriate when design wind loads are based on earlier versions of ASCE 7-93 or other standards (with different wind gust duration assumptions). 3.11 Deflection 3.11.1 Code Application. Post-frame building components must meet deflection limits speci-fied in the governing building code. 3.11.2 Exception to Code Requirements. Girts supporting corrugated metal siding are typically not subjected to deflection limitations unless their deflection compromises the integrity of an interior wall finish. Because of the inherent

flexibility of corrugated metal siding, girt deflec-tions present no serviceability problems, and consequently, girt size is generally only stress dependent. 3.11.3 Time Dependent Deflection. In certain situations, it may be necessary to limit deflection under long term loading. Published modulus of elasticity, E, values for wood are intended for the calculation of immediate deflection under load. Under sustained loading, wood members exhibit additional time-dependent deformation (i.e. creep). It is customary practice to increase cal-culated deflection from long-term loading by a factor of 1.5 for glued-laminated timber and sea-soned lumber, or 2 for unseasoned lumber (see Appendix F, AF&PA, 1997). Thus, total deflec-tion is equal to the immediate deflection due to long-term loading times the creep deflection fac-tor, plus the deflection due to the short-term or normal component of load. For applications where deflection is critical, the published value of E (which represents the average) may be re-duced as deemed appropriate by the designer. The size of the reduction depends on the coeffi-cient of variation of E. Typical values of E vari-ability are available for different wood products (see Appendix F, AF&PA, 1997). 3.11.4 Shear Deflection. Shear deflection is usually negligible in the design of steel beams; however, shear deflection can be significant in wood beams. Approximately 3.4 percent of the total beam deflection is due to shear for wood beams of usual span-to-depth proportions (i.e. 15:1 to 25:1). For this reason, the published value of E in the Supplement to the National De-sign Specification is 3.4 percent less than the true flexural value (AF&PA, 1993). This correc-tion compensates for the omission of the shear term in handbook beam deflection equations. For span-to-depth ratios over 25, the predicted deflection using the published E value will ex-ceed the actual deflection. Similarly, for span-to-depth ratios less than 15, predicted deflections will be significantly less than actual. This could lead to unconservative designs (with respect to serviceability) for post-frame members such as door headers. Practical information on the ef-fects of shear deformation on beam design is given in Appendix D of Hoyle and Woeste (1989) for rectangular wood beams and Triche (1990) for wood I-beams.

Page 30: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

3-9

3.12 References American Forest & Paper Association (AF&PA). 1997. ANSI/AF&PA NDS-1997 - National Design Specification for Wood Construction. AF&PA, Washington, D.C. American Forest & Paper Association (AF&PA). 1993. Commentary to the National Design Specification for Wood Construction. AF&PA, Washington, D.C. ASAE. 1999. ASAE EP288.5: Agricultural build-ing snow and wind loads. ASAE Standards 1999, 46th edition, ASAE, St. Joseph, MI. American Society of Civil Engineers (ASCE). 1993. Minimum design loads for buildings and other structures. ANSI/ASCE 7-93, ASCE, New York, NY. American Society of Civil Engineers (ASCE). 1999. Minimum design loads for buildings and other structures. ANSI/ASCE 7-99, ASCE, New York, NY. Ellifritt, D.S. 1977. The mysterious 1/3 stress increase. American Institute of Steel Construc-tion Engineering Journal (4):138-140. Faherty, K.F. and T.G. Williamson. 1989. Wood Engineering and Construction Handbook. McGraw-Hill, New York, NY. Hoyle, R.J. and F.E. Woeste. 1989. Wood Technology in the Design of Structures. Ames, IA: Iowa State University Press. Mehta, K.C., R.D. Marshall and D.C. Perry. 1991. Guide to the Use of the Wind Load Provi-sions of ASCE 7-88 (formerly ANSI A58.1). American Society of Civil Engineers, New York, NY. Metal Building Manufacturers Association (MBMA). 1986. Low rise building systems man-ual. MBMA, Cleveland, OH. Taylor, S.E. 1996. Earthquake considerations in post-frame building design. Frame Building News 8(3):42-49.

Page 31: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

3-10

Page 32: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

4-1

Chapter 4: STRUCTURAL DESIGN OVERVIEW

4.1 Introduction 4.1.1 General. The aim of this chapter is to give a broad overview of post-frame building design, and then highlight unique aspects of post-frame that require special design considerations. Post-frame is a special case of light-frame wood con-struction. Light-frame construction is accepted by all model building codes, and the design pro-cedures are well documented. The design rules that apply to light-frame wood construction also apply to post-frame. However, there are some aspects of post-frame that are not as familiar to building designers, such as diaphragm design, interaction between post-frames and dia-phragms, and post foundation design. Hence, Chapters 5, 6, 7 and 8 focus on these topics in more detail. 4.1.2 Primary Framing. Primary framing is the main structural framing in a building. In a post-frame building, this includes the columns, trusses (or rafters), and any girders that transfer load between trusses and columns. Each truss and the post(s) to which it is attached form an individual "post-frame". Post-frames collect and transfer load from roof purlins and wall girts to the foundation. In the context of wind loading in standards and building codes, post-frames are an integral part of the main wind-force resisting system. Specific sections dedicated to primary framing include: Section 4.2 Posts, Section 4.3 Trusses, Section 4.4 Girders, and Section 4.5 Knee braces. 4.1.3 Secondary Framing. Secondary framing includes any framing member used to (1) trans-fer load between cladding and primary framing members, and/or (2) laterally brace primary framing members. The secondary framing members in a post-frame building include the girts, purlins and any structural wood bracing such as permanent truss bracing. Specific sec-tions dedicated to secondary framing include: Section 4.6 Roof Purlins, Section 4.7 Wall Girts, and Section 4.8 Large Doors. 4.1.4 Diaphragms and Shearwalls. When cladding is fastened to the wood frame of a post-frame building, large shearwalls and roof

and ceiling diaphragms are formed that can add considerable rigidity to the building. In many post-frame buildings, diaphragms and shear-walls are carefully designed and become an in-tegral part of the main wind-force resisting sys-tem. Roof and Ceiling Diaphragms are covered in Section 4.9 and Shearwalls in Section 4.10. 4.1.5 Limitations. The structural design of buildings involves making many judgments, such as determining design loads, structural analogs and analyses, and selecting materials that can safely resist the calculated forces. New research or testing could justify a change of de-sign procedure for the industry or for an individ-ual designer. The considerations presented here are not exhaustive, since many issues in a spe-cific building design will require unique treat-ment. 4.2 Posts 4.2.1 General. The function of the wood post is to carry axial and bending loads to the founda-tion. Posts are embedded in the ground or at-tached to either a conventional masonry or con-crete wall or a concrete slab on grade. Posts can be solid sawn, mechanically laminated, glued-laminated or wood composite. Any portion of a post that is embedded or exposed to weather must be pressure-treated with pre-servative chemicals to resist decay and insect damage. 4.2.2 Controlling Load Combinations. The load combination that usually controls post de-sign is dead plus wind plus one-half snow; how-ever, local codes may stipulate different load combinations. It is possible for any one of the combinations to be critical; therefore, they all should be considered for a specific building de-sign. For example, maximum gravity load will govern truss-to-post bearing and post founda-tion bearing; whereas wind minus dead load will govern the truss-to-post connection (for uplift). 4.2.3 Force Calculations. The diaphragm analysis method presented in Chapter 5 is the most accurate method to determine design

Page 33: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

4-2

moments, and axial and shear forces in posts. Historically, some designers calculated the maximum post moment for embedded posts by using the simple structural analog of a propped cantilever (i.e. fixed reaction at the post bottom and pin reaction at the top). The implicit as-sumption of this analog is that the roof dia-phragm and shearwalls are infinitely stiff. This model may be adequate for buildings with ex-tremely stiff roof diaphragms and for conserva-tively estimating shear forces in the roof dia-phragm; however, it may underestimate the maximum post moment for many post-frame buildings. The analysis procedures described in Chapter 5 are more reliable since they account for the flexible behavior of the roof diaphragm. If posts are embedded, generally two bending moments must be calculated - one at the groundline and the other above ground. Ground-line bending moment and shear values are used in embedded post foundation design calcula-tions. For surface-attached posts, the bottom reaction can be modeled as a pin, and generally only one bending moment is calculated. 4.2.4 Combined Stress Analysis. Forces in-volved in post design subject the posts to com-bined stress (bending and axial) and must be checked for adequacy using the appropriate in-teraction equation from the NDS (AF&PA, 1997). In theory, every post length increment must sat-isfy the interaction equation, but in practice, a minimum of two locations are checked: the point of maximum interaction near the ground level (column stability factor, Cp, equal to 1.0) and the upper section of the posts where the maximum moment occurs in conjunction with column ac-tion (Cp<1.0). 4.2.5 Shear Stress. The shear stress due to lateral loading (wind or seismic) rarely controls post design, but should always be checked as a matter of good practice. Other loads such as bulk loads from stored materials may influence final post design. 4.2.6 Deflection. A post deflection limit is not normally specified for post-frame buildings, but interior finishes may require it. Refer to the de-flection criteria in Chapter 3.

4.2.7 Connections. Truss-to-post connection must be designed for bearing as well as uplift. Connection design procedures are given in the NDS (AF&PA, 1997). This connection should be modeled as a pin unless moment-carrying ca-pacity can be justified. Direct end grain bearing is desirable and is often achieved by notching the post to receive the truss. When designing the truss-to-post connection for uplift, it is impor-tant to accurately estimate the weights of con-struction materials if any counteracting credit is to be taken. For surface-attached posts, the bottom connec-tion needs to be checked for maximum shear and uplift forces. For embedded posts attached to collars or footings, the connections must be properly designed to withstand gravity and uplift loads, and corrosion-resistant fasteners must be used. 4.2.8 Construction Alternatives. The posts in post-frame buildings can be solid sawn, me-chanically-laminated, glued-laminated or wood composite. Allowable design stresses are pub-lished in the NDS or are available from the manufacturers. Treated wood is used for the embedded part of the post, but no treatment is required on the parts that are not in contact with the ground and are protected by the building envelope. 4.2.9 Foundation. Post-frame building founda-tions include posts embedded in the ground or surface-attached on a concrete foundation. Em-bedded posts shall be designed to resist sides-way and overturning forces due to wind or seis-mic loads, as well as wind uplift, and gravity loads. Post foundation design is an important aspect of post-frame building design that is not well known in the structural engineering design community, and therefore Chapter 8 is dedi-cated to this subject. If a concrete slab is used, it only needs to be designed for interior loads since exterior building loads are transferred di-rectly to the ground through the posts. Another option is to attach the posts to a con-crete foundation. In this case, the concrete must be designed to carry the exterior building loads as well as interior. Connections must be de-signed to attach the posts to the concrete.

Page 34: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

4-3

4.2.10 Pressure Preservative Treatment (PPT). Treated foundation systems have been accepted by the model codes and have a history of successful performance in residential wood construction. The most common pressure pre-servative treatment used in post-frame construc-tion is chromated copper arsenate (CCA). CCA can increase the potential for metal-fastener corrosion, and may require hot-dipped galva-nized or stainless steel fasteners. The minimum waterborne treatment retention for structural posts used in post-frame buildings is 0.6 lb/ft3 (pcf) as defined in AWPA Standard C15 (AWPA, 1995a). Technical Note Wood Preservative Treatments

When the moisture content of wood exceeds 20% on a dry weight basis in the presence of oxygen, it is vulnerable to attack by insects and decaying fungi. Although some species of wood (and the heartwood of other species) are natu-rally resistant to these types of attack, most structural woods used in North America are not. These structural wood species must be chemi-cally treated to protect them from decay and maintain their strength throughout the structural design life. The chemicals used for preservative treatment of the wood are typically injected into the wood using pressure processes. Wood that has been chemically treated in this manner is accepted by all major building codes. The type of preserva-tive treatment and the required amount of reten-tion by the wood depends on the end use of the wood component. It is assumed that the de-signer is already familiar with the use of pre-servative treated wood for above-ground appli-cations (such as wood decks); this section will concentrate specifically on preservative treat-ments and retention levels appropriate for use in post foundations. Preservative chemicals abate wood decay by altering the wood as a potential food source for insects and fungi. The preservatives typically used in North America are waterborne arsenic-based, pentachlorophenol (penta) and creosote. Waterborne arsenic-based preservatives include chromated copper arsenate (CCA), ammoniacal

copper arsenate (ACA), and ammoniacal copper zinc arsenate. CCA is available in three formula-tions: CCA-A, CCA-B, and CCA-C. CCA-C is the most popular of the three formulations due to its increased resistance to leaching. Penta is an oil-borne preservative, and creosote is a coal-tar based preservative that is its own carrier. While penta and creosote offer superior resistance in high salt environments, waterborne preservatives are typically more popular since the final product has a clean surface, is pain-table, and is relatively odorless. Waterborne pre-servatives do provide a strong potential for cor-rosion of metal connectors and fasteners; follow the manufacturers recommendations for the use of stainless or hot-dipped galvanized fasteners. While the major building codes endorse the use of preservative-treated wood for foundation ap-plications, it is imperative that the preservative retention guidelines be followed. The American Wood Preservers Association has published standards for the preservative treatment of wood for various applications (AWPA, 1991). Care must be taken that the appropriate standard is considered when specifying treatment for post foundation systems. For example, most water-borne preservative-treated lumber sold has a preservative retention level of 0.4 pcf (pounds of preservative per cubic foot of wood), which is the retention level specified by AWPA Standard C2 for lumber in contact with the ground. This differs, however, from the AWPA Standard C15 governing the treatment of structural posts used in foundations; the required preservative reten-tion for waterborne preservatives under this standard is 0.6 pcf. The AWPA C15 required retention level for post foundations using penta as a preservative is 0.6 pcf, while the required retention level for creosote is 12.0 pcf. The rate at which treatments are absorbed into wood, and the depth of penetration of the treat-ment, varies from wood species to wood spe-cies. Whereas Southern Pine species take treatment quite well, most other species must be incised to comply with AWPA retention require-ments. Incising can adversely affect lumber strength properties. Consult AF&PA for specifi-cations regarding the use of incised wood in structural applications.

Page 35: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

4-4

Quality assurance is critical to the performance of treated wood. The treating industry has de-veloped a quality control and treatment quality marking program accredited by the American Lumber Standards Committee. Any treated members specified for use in a post foundation should be stamped by an approved agency (e.g., AWPA, Southern Pine Inspection Bureau (SPIB), etc.) to assure that the members have been treated in accordance with AWPA Stan-dard C15 and to the appropriate retention level. Treated wood suppliers provide Material Safety Data Sheets (MSDS) or Consumer Information Sheets with the product. These sheets contain special instructions about the care, handling and disposal of treated wood. Federal law dictates that these sheets must be provided to all em-ployees exposed to the materials. Saw cuts or drilled holes made after treatment may expose untreated wood. This problem is especially critical if the newly exposed wood is in the splash zone or in contact with the ground. When using nail-laminated posts, the cut end of the treated lumber should be placed upward, above the ground level; otherwise, brush-applied, soaked, or dipped field treatments are recommended. AWPA Standard M4 outlines procedures for field treatment; some chemicals require a certified pesticide applicators license to apply. The chemical suppliers should be con-sulted for application restrictions. 4.3 Trusses 4.3.1 General. Together with posts, wood trusses are primary structural elements of post-frame buildings. Two excellent sources of tech-nical information on trusses are the Truss Plate Institute (TPI) and the Wood Truss Council of America (WTCA). Trusses must be properly de-signed, handled and installed. These responsi-bilities are shared by the building owner, con-tractor and designer, and the truss designer and manufacturer. The importance of a clear under-standing of responsibilities among these parties cannot be overstated, and is covered in WTCA 1-1995 Standard Responsibilities in the Design Process Involving Metal Plate Connected Wood Trusses and ANSI/TPI-1-1995 National Design

Standard for Metal Plate Connected Wood Truss Construction. 4.3.2 Design Loads. The controlling load com-bination for truss design often is snow plus dead load. The unbalanced snow load case should be checked per the applicable building code, or for agricultural buildings, engineering practice ASAE EP288.5 (ASAE, 1999a) should be con-sulted. However, all other applicable load com-binations must be checked. For example, a wind load combination may cause stress reversal in some truss elements as discussed later in this chapter. Truss loads are normally represented by listing the top-chord live and dead, and bottom-chord live and dead loads, respectively. Truss design loads are typically expressed in units of pounds per square foot (psf). An example of truss load-ing would be 20-4-0-1 (psf is implied). Both live and dead loads apply to the vertically projected tributary areas of the top and bottom chords. Often, a bottom-chord live load is not required, so the preceding nomenclature would be short-ened to 20-4-1 psf. 4.3.3 Design. This design manual does not present specifics of roof truss design. Metal-plate-connected wood trusses in the United States are designed according to the provisions of ANSI/TPI 1-1995. Other designs are based on proprietary test information, along with de-sign criteria from the NDS (AF&PA, 1997). Model building codes recognize either of these approaches. ANSI-TPI 1-1995 mentions two types of struc-tural analyses. The “simplified method” is a type of pin joint analysis that has been calibrated to account for partial joint fixity. This method uses tables of factors to determine chord moments and member buckling lengths. The simplified method has been the predominate method for a number of years; however, it will eventually be phased out by TPI. The other type of analysis which is sometimes referenced as the “exact method”, is a stiffness matrix method of analy-sis. Plane frame structures analyzers are be-coming more commonly used and provide for more sophisticated and accurate analyses. Re-gardless of analysis methods, structural model-ing assumptions are important and can dramati-cally influence the design (Brakeman, 1994).

Page 36: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

4-5

For example, partial fixity at truss plate joints as well as eccentricity at heel joints, can be mod-eled a variety of ways. The heel joint usually gets the most attention since heel joint modeling decisions can greatly influence truss design. The size, and in some cases the orientation, of truss plates is dependent on proprietary design values. These values are available from the manufacturers or from research reports pre-pared by the model code agencies, Such as ICBO, SBCCI and BOCA. Trusses can be obtained pre-engineered from the manufacturer. It is important to consider wind loading on trusses as stress reversals can occur and overstress some members. This de-sign is complicated by the fact that wind loads are influenced by building geometry, so this in-formation must be communicated to the truss designer. Any structural bracing (e.g. knee braces) or redundant supports must be included in the truss design. 4.3.4. Truss-to-Post Connection. The connec-tion between the truss and post is critical. De-signers must consider both gravity forces and uplift forces. With some truss-to-post connection designs, it might be necessary to examine the impact of the connection on the forces induced in the truss chords, heel joints, and post. Obser-vations from several building investigations re-vealed that the individual trusses and posts were designed properly, but the connection be-tween the two units was not. Many different methods and hardware have been used to de-sign the connection, such as bolts, nails, truss anchors, and combinations of the same. Unless otherwise governed by a specific code, the de-sign of this connection should meet NDS (AF&PA, 1997) requirements. 4.3.5 Stress Reversal. The trusses used in post-frame buildings are typically long span and, consequently, have long webs. When the truss becomes part of a post-frame building, it is pos-sible, under certain loading conditions, for a ten-sion web in the truss design to become a com-pression web. Stress reversal can also occur in truss chords due to a wind uplift loading combined with dead

load. This load case may not frequently control the size of the truss chord lumber, but it makes compression in the bottom chord possible. This situation is one reason that lateral bracing of the bottom chord is required (TPI, 1989; 1991a; 1991b). 4.3.6 Temporary Bracing. Temporary bracing is required to ensure stability of trusses during their installation and until permanent bracing for trusses and the building are in place. This area is the most difficult to manage in the field. According to WTCA 1-1995 and ANSI/TPI 1-1995, determination and installation of tempo-rary bracing is the responsibility of the building contractor. Truss Plate Institute (TPI) publication HIB-98 is a “summary sheet” that contains “rec-ommendations for handling, installing and tem-porary bracing metal plate connected wood trusses used in post-frame construction.” An-other TPI summary sheet (i.e., HIB-91) contains similar recommendation for trusses with on cen-ter spacings two feet or less and spans less than 60 feet. Both HIB-98 and HIB-91 are for-matted as accident-prevention brochures for use by builders, building contractors, licensed con-tractors, erectors, and erection contractors. 4.3.7 Permanent Bracing. Permanent truss bracing is critical to the performance of the roof system. Roof trusses are designed with the as-sumption that their elements are held sufficiently in-plane (ANSI/TPI, 1995). The primary function of permanent roof-truss bracing is to hold all trusses of the roof in the intended vertical plane. HIB-98, provides guidance for the placement of temporary truss bracing, which, if left in place, may function as part of the permanent bracing system. Building designers are responsible for designing permanent bracing. For trusses spaced 4 ft or less, DSB-89 (TPI, 1989) provides a calculation method for temporary and perma-nent bracing designs. For trusses spaced greater than 4 ft (1.22 m) on-center, similar prin-ciples can be used, but designers must consider that the longer lengths involved may cause the bracing members to buckle. A commentary cov-ering permanent bracing of metal plate con-nected wood trusses is available from WTCA (1999).

Page 37: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

4-6

4.4 Girders 4.4.1 General. Girders are heavy beams used to span large openings (e.g., doors) and to sup-port trusses located between posts. For exam-ple, when roof truss spacing is less than the post spacing, girders (sometimes called head-ers) are needed to carry the intermediate trusses. This is a common occurrence over large door openings. These beams are consid-ered main wind-force resisting members. Verti-cally nail-laminated lumber, structural composite lumber, glued-laminated beams and steel I-beams are all commonly used as girders. There is an abundant supply of structural-composite lumber products from manufacturers who pub-lish their own allowable stresses. Often, the critical load combination is dead plus snow load, although all applicable load combinations must be checked. 4.4.2 Design Criteria. Girders are designed as bending members. Any one of the four criteria used for the design of bending members can control design (i.e. bending, shear, compression perpendicular to grain, and deflection). Shear can often control girder design. Also note that formulae found in most handbooks account for bending but not shear deflection. Designers should consider the impact of shear deflection on the total deflection of a girder. Hoyle and Woeste (1989) provide formulae for calculating shear deflection of wood beams. 4.4.3 Vertically Laminated Lumber. The de-sign of girders for a post-frame building is rou-tine structural design except when a girder is fabricated by vertically laminating three or more pieces of dimension lumber. In this case, the allowable bending stress can be increased using the repetitive member factors published in ANSI/ASAE EP559 (ASAE, 1999b). These val-ues are given in table 7.3. 4.4.4 Connections. Girder attachment to posts and individual roof trusses is a fundamental part of girder design. When designing girder-to-post connections, both uplift and gravity must be considered. When designing truss-to-girder connections, special consideration must be given to situations in which trusses are hung off the side of the girder. In such cases truss-to-girder connections should be designed to pre-vent rotation between the trusses and girder, or

the girder must be sized to handle additional stresses due to torsion. 4.5 Knee Braces 4.5.1 General. Knee braces are intended to supplement the resistance of post frames under lateral loads, and can influence the unsupported length of columns. They have been used less and less in recent years. 4.5.2 Effectiveness. Knee brace effectiveness is highly dependent on the stiffness of its con-nections to the post and truss. If the connections at the ends of the brace are flexible or not very stiff due to the use of a few nails, the roof dia-phragm carries the bulk of the load, and the brace is ineffective (Gebremedhin and Woeste, 1986). If the brace connections are made very stiff (by installing many nails or bolts) the brace could effectively resist the wind loading but could overload the truss. 4.5.3 Analysis. Knee braces induce primary bending moments in truss chords if attached between panel points. Knee braces induce sec-ondary bending moments when attached directly to panel points. If knee braces are to be used in a post-frame design, load sharing among the truss, post, knee brace, connections, and dia-phragm (when applicable) must be included in the structural analysis. 4.6 Roof Purlins 4.6.1 General. Roof purlins are typically 2- by 4-inch or 2- by 6-inch lumber, and are key struc-tural elements of the roof assembly. They resist gravity loads, wind loads, roof diaphragm chord forces, and provide lateral bracing to truss top chords (or rafters). To fulfill the chord-bracing role, the purlins must be supported against lat-eral movement by attachment to sheathing or metal cladding that provides the needed roof diaphragm strength. Not all roof cladding mate-rials provide diaphragm strength and/or purlin lateral support; one example is standing seam roofing, which is fastened with clips that allow adjacent sheets to slide. 4.6.2 Classification. Purlins in post-frame buildings fall into the category of “component

Page 38: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

4-7

and cladding,” which is recognized by all three model building codes. Components and clad-ding collect the loads and distribute them to the primary structural elements, identified as the main wind-force resisting system. Wind loads are much greater at eaves, ridges, edges, cor-ners and other discontinuities. Purlin spacing and fasteners are critical in these areas. If these areas fail under extreme wind loading, the build-ing envelope will be breached, and internal wind pressures will change dramatically. 4.6.3 Orientation. Purlins are installed on-edge or flat. When they are used on-edge, they may be either placed on top of the truss or recessed between the trusses. Purlins placed on-edge are frequently overlapped and fastened together at the overlap. When used flat, purlins are installed on top of the trusses. 4.6.4 Truss Chord Bracing. Purlin spacing is a factor in truss design since purlins provide lat-eral support to the truss top chord. In some cases, the slenderness ratio for weak-axis truss chord buckling between purlins can be greater than that for strong-axis buckling. Therefore, when specifying trusses, the building designer should inform the truss-design engineer of the planned purlin spacing. 4.6.5 Design Loads. Purlin design often is con-trolled by the dead plus snow load combination, or dead plus wind load (especially in the edge zones of the roof). Dead loads used for design may exceed actual weights for gravity load cal-culations; however, inflated dead loads cannot be used to offset wind uplift or wind overturn moments. In these cases, offsetting loads can-not exceed actual weights of materials. 4.6.6 Design Criteria. Purlins members should be checked for bending strength, shear capac-ity, and deflection. If the roof assembly is func-tioning as a structural diaphragm, purlins will also be subjected to axial forces. Purlins shall be designed to carry bending about both axes. Weak axis bending may be omitted if it can be demonstrated by test or analysis that the roof sheathing provides support. The connections between the purlins and rafters should be de-signed for both gravity loads and wind uplift forces. Purlin hangers are often used when pur-

lins are recessed, and their capacity should be verified for the various loading cases. In general, the provisions of the NDS (AF&PA, 1997) apply for the connections and stress analysis. 4.7 Wall Girts 4.7.1 General. Girts are used to collect wind-induced wall loads and distribute them to the post frames. For end walls, the wind loads are distributed to structural end-wall posts. 4.7.2 Classification. Girts belong to the “com-ponent and cladding” category for determining the design wind load. 4.7.3 Orientation. Girts are either installed flat on post faces or recessed between the posts. Girts recessed between posts are almost always orientated with the narrow edge facing the clad-ding, and in this position, are frequently used to support both interior and exterior clad-ding/sheathing. 4.7.4 Post Bracing. Girts provide lateral sup-port to side-wall columns. With girts securely installed, the slenderness ratio of the post weak axis is greatly reduced. Therefore, posts can usually be designed to carry the axial loads us-ing the slenderness ratio of the strong axis. 4.7.5 Design Loads. Girts are normally de-signed to resist only wind load. Wind loads are much greater at corners and other discontinui-ties. Girt spacing and fasteners are critical in these areas. If these areas fail, the building en-velope will be breached, and internal wind pres-sures will change dramatically. The dead load of the girt and attached steel is normally negligible for girt design. Cladding is attached to the girts by nails or screws, and the stiffness of these connections does not allow the girts to undergo significant bending stress or deflection from the action of the small dead loads present. However, the wall dead load should be included in total dead load calcula-tions for the post foundation. Girts must be design to resist forces induced by stored materials, especially granular materials such as fertilizer or seeds/grain. Care should be

Page 39: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

4-8

taken to assure that the capacity of wall panels, fasteners and girts are not exceeded by these forces. 4.7.6 Design Criteria. Girts are designed as bending members for which the usual bending-member design criteria apply. The critical con-nections between the girts and the post should be checked for both wind pressure and suction. The top wall girt may be constructed to carry chord forces from the roof diaphragm and, if so, must be checked for the appropriate axial loads. The NDS (AF&PA, 1997) provisions apply for the connections and stress analysis. 4.8 Large Doors 4.8.1 General. Large doors are common in post-frame buildings. Door components must be designed to withstand design wind loads, and are treated as “components and cladding” for such calculations. 4.8.2 Open Doors. It is not uncommon for building owners to leave large doors open, even during periods of high wind. If an owner antici-pates that this will occur, the building must be designed accordingly. Note that a large opening on one side of the structure is generally associ-ated with increased internal wind pressure coef-ficients, and thus can significantly increase roof uplift forces. 4.9 Roof and Ceiling Diaphragms 4.9.1 General. Roof and ceiling diaphragms are used to resist lateral (sidesway) forces applied to the building by wind, earthquake and stored material. Under lateral load, roof and ceiling dia-phragms act as large stiff plates. These plates support and distribute loads to wall posts. Con-ceptually, diaphragm design is easy to under-stand, but the application of the procedure re-quires analysis tools and data. Diaphragms made from plywood are well docu-mented, as well as those made entirely from steel. Less information is available about wood-framed, metal-clad diaphragms which are preva-lent in the post-frame building industry. This is a major factor in post-frame building design and is covered in more depth in Chapter 5.

4.9.2 Design Properties. Diaphragm perform-ance depends on factors such as the steel, steel sheet-to-sheet fasteners, steel-to-wood fasten-ers, and the wood frame. There is no standard steel panel construction, so diaphragm strength and stiffness depend on the specific construc-tion used. Strength and stiffness data on labora-tory test panels are generally required to derive design values. Most post-frame buildings have much greater spans than laboratory test panels; therefore, test data must be extrapolated to prac-tical building sizes as explained in Chapter 6. 4.10 Shearwalls 4.10.1 General. A large portion of the shear forces induced in roof and ceiling diaphragms is transferred to the building foundation by shear-walls. In many post-frame buildings, the only walls available to transfer this shear are exterior walls (i.e., endwalls and sidewalls). Where pre-sent, interior partition walls can be designed to transfer additional shear. 4.10.2 Endwalls. Endwalls in post-frame build-ings resist wind loads perpendicular to the build-ing end wall and simultaneously help transmit roof shears (due to parallel-to-end wall wind components) to the ground. In the diaphragm design procedure described in Chapter 5, maximum roof shears occur at the endwalls. The roof shear is transferred into the top truss chord or rafter of the endwall, through the end-wall to the ground level, and finally to the ground by posts or to posts connected to a concrete slab. In addition to shear forces, the end wall is subject to overturning forces. Wirt et al. (1992) have published procedures for analyzing and designing end-wall foundations. 4.10.3 Wall Openings. Allowances must be made for openings in shearwalls. One common practice in post-frame construction is to place large doorways in the building endwalls. Proce-dures for accounting for the opening and ways to reinforce the remaining wall are given in Chapter 5. 4.10.4 Partitioning. Partitioning of the building into structural segments is one method to re-duce maximum roof shears and endwall shears. For example, if it is not practical to reinforce an

Page 40: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

4-9

endwall that has a large door installed, the alter-native is to install a structural partition in the center of the building. The structural partition must meet the shear requirements delivered by the roof diaphragm. Buttresses, inside or outside the walls, can be used to reduce the effective length of the building with respect to maximum roof and end-wall shears. 4.11 References ASAE. 1999a. ASAE EP 288.5: Agricultural building snow and wind loads. ASAE Standards, 46th edition. ASAE, St. Joseph, MI. ASAE. 1999b. ANSI/ASAE EP 559: Design re-quirements and bending properties for mechani-cally-laminated posts. ASAE Standards, 46th edition. ASAE, St. Joseph, MI. American Forest & Paper Association (AF&PA). 1997. National design specification for wood construction. AF&PA, Washington, D.C. American Wood-Preservers' Assc. (AWPA). 1995a. Wood for commercial-residential con-struction. Preservative treatment by pressure process, C-15. In Book of Standards. AWPA, Stevensville, MD. American Wood-Preservers’ Assc. (AWPA). 1995b. Lumber, timbers, bridge ties, and mine ties, pressure treatment, C2-90. In Book of Standards. AWPA, Stevensville, MD. American Wood-Preservers' Assc. (AWPA). 1995c. Care of pressure treated wood products, M4-90. In Book of Standards. AWPA, Stevens-ville, MD. Brakeman, D.B. 1994. Which truss design method is the correct one? Peaks 16(1):1-3. Gebremedhin, K.G., and F.E. Woeste. 1986. Diaphragm design with knee brace slip for post-frame buildings. Transactions of the American Society of Agricultural Engineers 23(2):538-542. Hoyle, R.J. and F.E. Woeste. 1989. Wood tech-nology in the design of structures. Fifth edition. Iowa State University Press, Ames, IA. Truss Plate Institute (TPI). 1989. Recommended design specifications for temporary bracing of

metal plate connected wood trusses. DSB-89. TPI, Madison, WI. Truss Plate Institute (TPI). 1998. HIB-98 sum-mary sheet. TPI, Madison, WI. Truss Plate Institute (TPI). 1995. ANSI/TPI 1-1995 National design standard for metal plate connected wood truss construction. TPI, Madi-son, WI. Wirt, D.L., F.E. Woeste, D.E. Kline and T.E. McLain. 1992. Design procedures for post-frame end walls. Applied Engineering in Agriculture 8(1):97-105. Wood Truss Council of America (WTCA). 1995. Standard responsibilities in the design process involving metal plate connected wood trusses. WTCA 1-1995. WTCA, Madison, WI. Wood Truss Council of America (WTCA). 1999. Commentary for permanent bracing of metal plate connected wood trusses. WTCA, Madison, WI.

Page 41: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

4-10

Page 42: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-1

Chapter 5: DIAPHRAGM DESIGN

5.1 Introduction 5.1.1 2-D Frame Analysis. Prior to the 1980’s, the common method of analysis for post-frame structures in agricultural, commercial and light industrial applications was to consider the struc-ture as a system of independently-acting, two-dimensional (2-D) post-frames. Although a 2-D frame analysis method works well for designing frames under vertical loadings; it is often too conservative for designing buildings against sidesway. In addition, many 2-D frames offer little or no resistance to loads acting normal to the frames (e.g., wind acting normal to the end-walls). 5.1.2 Diaphragm Action. A considerable por-tion of the horizontal load applied to many post-frame structures is actually resisted by roof and ceiling diaphragms and shearwalls. As previ-ously stated (section 4.9), roof and ceiling dia-phragms are large plates that are formed when cladding is attached to roof and ceiling framing, respectively. These large plates help redistribute load throughout the structure. This redistribution of load by the diaphragms is called diaphragm action. A shearwall is any wall – interior or exte-rior – with a measurable amount of racking re-sistance. Most of the load to which a diaphragm is subjected, is transferred to the foundation by shearwalls orientated parallel to the direction of applied load. Figure 5.1 illustrates a situation in which wind load directed at a sidewall, is trans-ferred via the roof diaphragm to the endwalls and one interior wall. Under this loading, the two endwalls and the one interior wall function as shearwalls. When the same wind load is di-rected toward the endwall, the sidewalls function as shearwalls in transferring the load from the roof diaphragm to the foundation system. 5.1.3 Post-Frame Contributions. Whenever load is applied normal to the sidewall of a struc-ture, any post-frame with measurable racking resistance functions like the interior shearwall in figure 5.1. The amount of load that an individual post-frame will transfer to the foundation is de-pendent on (1) the in-plane shear stiffness of the diaphragm, and (2) the racking stiffness of the

post-frame relative to that of other post-frames and shearwalls. If a diaphragm is constructed in such a way that it is quite stiff in shear, dia-phragm action will be enhanced and the dia-phragm will transfer load from post-frames with low racking stiffness to shearwalls and post-frames with high racking stiffness. However, if the shear stiffness of the diaphragm is relatively low, load transfer will be minimal and the behav-ior of the structure will be much more in accor-dance with the assumption of independently act-ing post-frames.

Figure 5.1. Example of diaphragm action in which the roof diaphragm transfers load to three shearwalls – one interior and two exterior walls. 5.1.4 Endwall Loadings. Virtually all post-frame buildings are longer than they are wide. It follows, that diaphragms in such buildings, when viewed from the endwall, appear as narrow, deep plates. For endwall loadings, these narrow, deep diaphragms are generally assumed to have an infinite shear stiffness, which means that every structural element attached to the diaphragm, shifts the same amount when the diaphragm shifts without rotating. For example, under an endwall loading, the roof diaphragm would ensure equal displacement of the top of endwall posts and the top of each sidewall.

Eave displacement

Roof diaphragm

End shearwall

Intermediate shearwall

Deformed structureUndeformed structure

Wind load

Page 43: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-2

5.1.5 Diaphragm Design. When diaphragm action is accounted for in overall building design, the design process is referred to as diaphragm design. Diaphragm design is a relatively straight forward process when a diaphragm is (1) as-sumed to have infinite shear stiffness, and/or (2) only attached to two shearwalls/post-frames (as is generally the case with endwall loadings). When neither of these conditions applies (gen-erally true with loads normal to the sidewall) diaphragm design is more complex. 5.1.6 ASAE EP484.2. The current diaphragm design procedure is outlined in ANSI/ASAE EP484.2: Diaphragm Design of Metal-Clad, Wood-Frame Rectangular Buildings (ASAE, 1999a). This procedure, which is outlined in the following sections, can be broken into five steps: Step 1. Construct a finite element model of

the building by breaking the structure into frame, shearwall, and diaphragm elements (Section 5.2)

Step 2. Assign stiffness values to frames and shearwall elements (Section 5.3) and diaphragm elements (Section 5.4).

Step 3. Calculate structural loads (i.e., eave loads) for the model (Section 5.5).

Step 4. Determine the distribution of load to individual elements (Section 5.6).

Step 5. Check to make sure that loads do not exceed allowable values (Section 5.7).

5.2 Structural Model 5.2.1 General. The model developed in this section is only applicable for determining the distribution of loads that are applied parallel to individual post-frames (a.k.a., primary frames). As previously stated, an individual post-frame consists of an individual truss and any attached posts. 5.2.2 Diaphragm Sectioning. The process of modeling a post-frame building for diaphragm design begins with the dividing of individual roof and ceiling diaphragms into sections, herein re-ferred to as diaphragm sections. Diaphragm sectioning is a straight-forward process with in-terior post-frames, interior shearwalls, ridge lines and any other abrupt changes in roof and ceiling slopes servings as lines of demarcation between diaphragm sections.

Figure 5.2. (a) Perspective view of a four-bay post-frame building with (b) roof and ceiling dia-phragms. Sectioning of (c) roof diaphragms, and (d) ceiling diaphragm.

1a

1b

2a

2b

3a

3b

4a

4b

(c)

(d)

1 2 3 4 5

1c 2c 3c 4c

1 2 3 4 5

(a)

(b)

Diaphragm "a"Diaphragm "b"

Diaphragm "c"

Page 44: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-3

Figures 5.2a shows a post-frame building with three interior post-frames. Drawing a line along each interior frame and the ridge results in the eight (8) roof diaphragm sections shown in fig-ure 5.2c, and the four ceiling diaphragm sec-tions shown in figure 5.2d. To avoid confusion when assigning properties to diaphragm sections, it is helpful to identify each diaphragm section with a two-digit identifier. The first digit identifies the bay associated with the section. Bays are generally numbered from left-to-right, as shown in figures 5.2c and 5.2d. The second digit identifies the specific roof or ceiling slope. In figure 5.2, letters have been used to identify these slopes, with letters “a” and “b” rep-resenting different roof slopes, and letter “c” used to identify ceiling sections. 5.2.3 Discretization. The process of breaking a structure into elements for analysis is referred to as discretization. For diaphragm design, a struc-ture is broken into frame elements and dia-phragm elements. Each post-frame is consid-ered a separate frame element, as is each shearwall orientated in the same direction as the post-frames. The example building shown in figure 5.2 would be modeled with five (5) frame elements. These frame elements have been identified in figures 5.2c and 5.2d with the encir-cled numbers (as with individual bays, number-ing is generally from left-to-right). Each dia-phragm element models the diaphragm sections within a single bay. For example, diaphragm sections 1a, 1b, and 1c in figure 5.2 would be represented with a single diaphragm element. It follows that the number of diaphragm elements is equal to the number of building bays, which in turn, is one less than the number of frame ele-ments. Discretization of a four-bay building is shown in figure 5.3a. 5.2.4 Spring Model. To determine the distribu-tion of horizontally applied loads to individual diaphragm and frame elements requires only a single stiffness property for each element. For this reason, diaphragm and frame elements are generally represented with simple springs. As shown in figure 5.3b, frame elements are repre-sented with springs of stiffness, k, and dia-phragm elements are represented as springs with stiffness Ch. The element (or spring) con-nection points (a.k.a. nodes) are taken to repre-

sent locations at the eave of each frame/shearwall. Horizontal components of applied building loads are typically uniformly distributed along the length of the building as shown in figure 5.3a. For modeling purposes, this uniform load is con-verted into a set of equivalent concentrated loads that are applied at the nodes as shown in figure 5.3b. Because of the location of their ap-plication, these forces are referred to as eave loads.

Figure 5.3. (a) Top view of a four-bay building showing individual elements and applied hori-zontal loads. Encircled numbers identify frame elements, other numbers identify diaphragm elements. (b) Corresponding spring model.

k1 k2 k3 k4 k5

Ch1 Ch2 Ch3 Ch4

r1 r2 r3 r4 r5

1 2 3 4

1 2 3 4 5

(a)

(b)

Page 45: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-4

5.3 Frame Stiffness, k 5.3.1 Definition. To be compatible with a model in which nodes represent points along the eave line (figure 5.3b), frame element stiffness, k, must equal the force required for a unit dis-placement of the frame at the eave (figure 5.4). In equation form: k = P / ∆ (5-1) where: k = frame stiffness, lbf/in (N/mm) P = load applied at eave, lbf (N) ∆ = lateral displacement at eave result-

ing from applied load P, in (mm)

Figure 5.4. Definition of frame stiffness, k. 5.3.2 Calculation. Frame stiffness is generally obtained with a plane-frame structural analysis program, e.g., PPSA (Purdue Research Foun-dation, 1993), METCLAD (Gebremedhin, 1987b), and SOLVER (Gebremedhin, 1987a). For post-frames in which (1) all posts are as-sumed to be pin-connected to the truss (or raf-ters), and (2) there are no special members (e.g., knee braces) connecting posts to the truss, frame stiffness can be calculated as: n

k = Σ kp,i (5-2) i = 1 where: kp,i = stiffness of post i, lbf/in (N/mm) n = number of posts in the post-frame

Post stiffness, kp, is graphically defined in figure 5.5. For a post with a constant flexural rigidity (E x I) that is assumed to be fixed at the base, post stiffness is given as: kp = 3 E I / Hp

3 (5-3) where: kp = stiffness of post that is fixed at the

base and pinned at the top, lbf/in (N/mm)

E = modulus of elasticity of post, lbf/in2 (N/mm2)

I = moment of inertia of post, in4 (mm4) Hp = post height from fixed base to truss

connection post (see figure 5.5), in (mm)

Figure 5.5. Definition of post stiffness, kp. 5.3.3 Shearwalls. End shearwalls and interme-diate shearwalls, like post-frames, are modeled as frame elements (see Section 5.2.3). Conse-quently, their stiffness, like that for post-frames, is defined as the ratio of a horizontal force, P, applied at the eave of the wall, to the resulting horizontal eave displacement, ∆. The stiffness of shearwalls can be obtained us-ing validated structural models, or from tests of functionally equivalent assemblies. ASAE EP558 (1999b) gives laboratory test procedures that can be used to determine the stiffness of functionally equivalent walls. This topic is also discussed in Section 6.5.

P

k = P / ∆ P∆

kp = P / ∆

Post -to-truss connection pointHp

Page 46: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-5

Technical Note Embedded Post Analogs When a post is embedded in the soil, calculated post stiffness (and consequently calculated frame stiffness) is highly dependent on how the embedded portion is modeled. Traditionally, en-gineers have ignored soil properties and have modeled embedded posts using the analogs shown in figures 5.6a and 5.6b. An inherent de-ficiency of these analogs is that the pin supports used to fix the post below grade do not allow the post to naturally displace. For this reason, post stiffness values predicted using the analogs should be applied with caution. It should also be noted that the analogs in figures 5.6a and 5.6b produce a reduced post stiffness when depth of embedment, d, is increased. In reality, anytime a post is embedded deeper into the ground, the stiffness associated with the post increases. To accurately model post movement below grade requires accounting for soil stiffness. Bohnhoff (1992) developed equations for pre-dicting post stiffness assuming soil stiffness in-creased linearly with depth below grade and inversely with post width. Bohnhoff also as- sumed that the post had infinite flexural stiffness

below grade. Meador (1997) developed similar equations, but unlike Bohnhoff, Meador as-sumed that soil stiffness was not a function of post width. Meador also investigated the as-sumption of infinite post stiffness below grade, and established limits for applicability of the equations he developed. McGuire (1998) used the work of both Bohnhoff and Meador to pro-pose an analog where soil is modeled as a se-ries of linear springs whose stiffness increases linearly below grade (figure 5.6c). McGuire veri-fied Bohnhoff’s results and also showed that for the case of non-constrained posts, analogs like those shown in figure 5.6a may incorrectly pre-dict the sense of base moment (see Chapter 8). Current impediments to the wide spread adop-tion of analogs that account for soil stiffness in-clude: (1) complexity of equations, and (2) unre-alistically low post stiffness values obtained us-ing published soil stiffness data. It is important for the post-frame designer to re-alize that fixing the post at grade (figure 5.5) generally produces conservative values for post base moments, especially for the non-constrained post case. Conversely, forces calcu-lated in the diaphragm using this model might be non-conservative.

Figure 5.6. Structural analog traditionally used for (a) non-constrained and (b) constrained posts. (c) A more realistic non-constrained post analog that accounts for soil stiffness.

Hp

d

Ground surface

0.34 d

0.1 d

Hp

d0.7 d

Floor slab

Hp

dSprings used to

model soil stiffness

(b)(a) (c)

Page 47: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-6

5.4 Diaphragm Stiffness, Ch 5.4.1 Definition. As shown in figure 5.7, the stiffness of a diaphragm element is the horizon-tal load required to cause a unit shift (in a direc-tion parallel to the trusses/rafters) of the roof/ceiling assembly over a frame spacing (a.k.a. bay width), s. This stiffness is commonly referred to as the total horizontal shear stiffness, Ch, of the diaphragm.

Figure 5.7. (a) Top view of a four-bay building. (b) Definition of diaphragm stiffness, Ch, for a single diaphragm element. 5.4.2 Calculation. The total horizontal shear stiffness of a diaphragm element is simply equal to the sum of the horizontal shear stiffness val-ues of the diaphragm sections that comprise the element. In equation form: n

Ch = Σ ch,i (5-4) i = 1 where:

Ch = total horizontal shear stiffness of diaphragm element, lbf/in (N/mm)

ch,i = horizontal shear stiffness of dia-phragm section i (from Section 6.4.4), lbf/in (N/mm)

n = number of diaphragm sections comprising the diaphragm element

5.5 Eave Loads, R 5.5.1 Definition. For diaphragm design, build-ing loads are replaced by an equivalent set of horizontally acting, concentrated (i.e., point) loads. These loads are located at the eave of each frame element (i.e., post-frame and end shearwall, and intermediate shearwall) and therefore are referred to as eave loads. Eave loads and applied building loads are equivalent when they horizontally displace the eave an equal amount.

Figure 5.8. Typical structural analog for obtain-ing eave load, R. 5.5.2 Calculation by Plane-Frame Structural Analysis. A horizontal restraint (vertical roller) is placed at the eave line as shown in figure 5.8 and the structural analog is analyzed with all external loads in place. The horizontal reaction at the vertical roller support is numerically equal to the eave load, R. The vertical roller should always be placed at the same location that hori-zontal load P was placed when determine frame stiffness (see figure 5.4). The value of R is very dependent on the magnitude of forces with

R

Roof Gravity Loads

Ceiling Gravity Loads

s x q

w w

s x qwr s x qlr

s x q

l w

1 2 3 4

(a)

(b)

s1 s2 s3 s4

si

s2

P

P

iC h,i = P / ∆

Page 48: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-7

horizontal components (i.e., wind and stored materials). 5.5.3 Calculation Using Frame-Base Fixity Factors. When: (1) posts are assumed to be pin-connected to trusses/rafters, (2) the only applied loads with horizontal components are due to wind, and (3) wind pressure is uniformly distributed on each wall and roof surface, then eave load, R, can be estimated as: R = s (hwr qwr – hlr qlr + hww fw qww – hlw fl qlw) (5-5) where: R = eave load, lbf (N) s = frame spacing for interior post-

frames and shearwalls, ft (m) = one-half the frame spacing for end-

walls, ft (m) hwr = windward roof height, ft (m) hlr = leeward roof height, ft (m) hww = windward wall height, ft (m) hlw = leeward wall height, ft (m) qwr = design windward roof pressure,

lbf/ft2 (N/m2) qlr = design leeward roof pressure, lbf/ft2

(N/m2) qww = design windward wall pressure,

lbf/ft2 (N/m2) qlw = design leeward wall pressure lbf/ft2

(N/m2) fw = frame-base fixity factor, windward

post fl = frame-base fixity factor, leeward

post Inward acting wind pressures have positive signs, outward acting pressures are negative (figure 5.8). In buildings with variable frame spacings, set s equal to the average of the frame spacings on each side of the eave load. Frame-base fixity factors, fw and fl, determine how much of the total wall load is transferred to the eave, and how much is transferred directly to the ground. The greater the resistance to ro-tation at the base of a wall, the more load will be attracted directly to the base of the wall. For substantial fixity against rotation at the ground-line, set the frame-base fixity factor(s) equal to 3/8. For all other cases, set the frame-base fixity factor(s) equal to 1/2.

For symmetrical base restraint and frame ge-ometry, equation 5-5 reduces to: R = s [hr (qwr – qlr) + hw f (qww – qlw)] (5-6) where: hr = roof height, ft (m) hw = wall height, ft (m) f = frame-base fixity factor for both lee-

ward and windward posts 5.6 Load Distribution 5.6.1 General. The distribution of horizontal loads to frames, shearwalls, and various dia-phragm sections can be determined after stiff-ness values have been assigned to each frame and diaphragm element, and eave loads have been established. 5.6.2 Analysis Tools. Any finite element or plane-frame structural analysis program can be used to analyze the structural model shown in figure 5.3b. However, to expedite this process, computer program DAFI was developed (Bohnhoff, 1992). Once eave loads and frame and diaphragm element stiffness values are in-put, DAFI calculates eave displacements, frame element loads and diaphragm element shear forces. DAFI can be downloaded at no cost from the NFBA web site (http://www.postframe.org/). An iterative method for hand-calculating load distribution was developed by Anderson and others (1989). This method, which is referred to as the force distribution method, is procedurally identical to the classical method of moment dis-tribution. 5.6.3 mS and mD Tables. Forces in the most highly loaded diaphragm and frame elements, can be calculated using tables 5.1 and 5.2 when all five of the following conditions exist: (1) all diaphragm elements have the same stiffness Ch, (2) all interior frame elements have the same stiffness, k, (3) both exterior frame elements (i.e., the two elements representing the end-walls) have the same stiffness, ke, (4) eave load, R, is the same at each interior frame, and (5) the eave load for each exterior frame is equal to one-half that for an interior frame. These five requirements are generally met in buildings with a fixed bay spacing, endwalls that are virtually identical in construction, and interior frames that

Page 49: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-8

don’t vary in overall design. When tables 5.1 and 5.2 are applicable, the analysis tools discussed in Section 5.6.2 are generally not needed. Input parameters required for tables 5.1 and 5.2 include: number of frame elements (i.e., the number of interior frames + 2); ratio of dia-phragm element to interior frame element stiff-ness, Ch / k; and ratio of exterior to interior frame element stiffness, ke / k. The most highly loaded diaphragm element (in any building that meets the preceding five condi-tions) is the element located adjacent to the endwalls. The maximum shear force in this dia-phragm element, Vh, is equal to the appropriate shear modifier value, mS, from table 5.1, multi-plied by the eave load, R, for an interior frame. In equation form: Vh = R mS (5-7) where: Vh = maximum diaphragm element shear

force, lbf (N) mS = shear force modifier from Table 5.1 R = eave load at interior frame, lbf (N) The value obtained from equation 5-7 is simply equal to one-half of the total horizontal eave load that is not carried by the interior frames. The most highly loaded interior frame element (in any building that meets the preceding five conditions) is the element located closest to the building midlength. Because of diaphragm ac-tion, the total horizontal load that this critical frame must resist is reduced from that which it would have to resist without diaphragm action. The magnitude of this reduction is referred to the horizontal restraining force because in real-ity, it is a restraining force applied to the frame by the roof (and/or ceiling) diaphragms. Numeri-cally, the horizontal restraining force, Q, is equal to the product of the eave load R, and the ap-propriate sidesway restraining force factor, mD from table 5.2. In equation form: Q = R mD (5-8) where:

Q = sidesway restraining force, lbf (N) mD = sidesway restraining force factor

from Table 5.2 R = eave load at interior frame, lbf (N) 5.6.4 In-Plane Shear Force in a Diaphragm Section, Vp. The analysis tools discussed in Section 5.6.2 (and equation 5-7) output dia-phragm element forces. In most cases, each element is comprised of two or more diaphragm sections. The in-plane shear force in each of these diaphragm sections is calculated as: Vp,i = (ch,i / Ch) Vh / (cos θ i) (5-9) where: Vp,i = in-plane shear force in diaphragm

section i, lbf (N) Vh = horizontal shear force in the dia-

phragm element, lbf (N) ch,i = horizontal shear stiffness of dia-

phragm section i, lbf/in. (N/mm) θ i = slope of diaphragm section i 5.6.5 Forces Applied to Frames by Individual Diaphragms. The horizontal movement of most building frames is resisted by roof/ceiling dia-phragms. The total horizontal resisting force ap-plied to an individual frame by the roof/ceiling diaphragms was previously defined as the side-sway restraining force, Q. To accurately model a frame with the resisting forces applied by the roof and ceiling diaphragms, requires that the sidesway restraining force, Q, first be divided up between the individual diaphragms (e.g., dia-phragms a, b, and c in figure 5.2b). This is ac-complished using the following equation: Q i = Q (ch,i / Ch) (5-10) where: Q i = sidesway resisting force due to dia-

phragm i, lbf (N) Q = total sidesway resisting force acting

on the frame, lbf (N) Ch = horizontal shear stiffness for a width

s of the roof/ceiling assembly, lbf/in. (N/mm)

ch,i = horizontal shear stiffness of dia-phragm i with width s, lbf/in. (N/mm)

Page 50: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-9

Table 5.1. Shear Force Modifier (mS) Number of frames (endwalls are counted as frames) ke / k Ch / k

3 4 5 6 7 8 9 10 11 12 13 14 15 16

5 5 0.88 1.14 1.33 1.45 1.53 1.59 1.62 1.65 1.66 1.67 1.68 1.68 1.68 1.68 5 10 0.89 1.19 1.42 1.59 1.72 1.82 1.89 1.94 1.98 2.00 2.02 2.04 2.05 2.06 5 20 0.90 1.22 1.48 1.68 1.85 1.98 2.08 2.16 2.23 2.29 2.33 2.36 2.39 2.41 5 50 0.91 1.24 1.51 1.74 1.93 2.10 2.23 2.35 2.45 2.53 2.60 2.67 2.72 2.77 5 100 0.91 1.24 1.53 1.76 1.97 2.14 2.29 2.42 2.53 2.63 2.72 2.80 2.87 2.93 5 200 0.91 1.25 1.53 1.77 1.98 2.16 2.32 2.46 2.58 2.69 2.79 2.87 2.95 3.02 5 500 0.91 1.25 1.54 1.78 1.99 2.18 2.34 2.48 2.61 2.73 2.83 2.92 3.01 3.08 5 1000 0.91 1.25 1.54 1.78 2.00 2.18 2.35 2.49 2.62 2.74 2.84 2.94 3.02 3.10 5 10000 0.91 1.25 1.54 1.79 2.00 2.19 2.35 2.50 2.63 2.75 2.86 2.95 3.04 3.12

10 5 0.91 1.23 1.46 1.62 1.73 1.81 1.86 1.89 1.91 1.92 1.93 1.93 1.94 1.94 10 10 0.93 1.29 1.58 1.81 1.99 2.13 2.23 2.31 2.36 2.40 2.44 2.46 2.48 2.49 10 20 0.94 1.33 1.66 1.94 2.17 2.36 2.52 2.66 2.76 2.85 2.92 2.98 3.03 3.06 10 50 0.95 1.35 1.70 2.02 2.30 2.55 2.76 2.96 3.12 3.27 3.40 3.51 3.61 3.70 10 100 0.95 1.36 1.72 2.05 2.35 2.62 2.86 3.08 3.27 3.45 3.61 3.76 3.89 4.01 10 200 0.95 1.36 1.73 2.07 2.37 2.65 2.91 3.14 3.36 3.56 3.74 3.90 4.06 4.20 10 500 0.95 1.36 1.74 2.08 2.39 2.68 2.94 3.19 3.41 3.62 3.82 4.00 4.17 4.32 10 1000 0.95 1.36 1.74 2.08 2.40 2.68 2.95 3.20 3.43 3.64 3.84 4.03 4.20 4.37 10 10000 0.95 1.36 1.74 2.08 2.40 2.69 2.96 3.21 3.45 3.66 3.87 4.06 4.24 4.41

20 5 0.93 1.28 1.54 1.73 1.85 1.94 2.00 2.03 2.06 2.07 2.09 2.09 2.10 2.10 20 10 0.95 1.35 1.68 1.95 2.16 2.33 2.45 2.55 2.62 2.67 2.71 2.74 2.76 2.78 20 20 0.96 1.39 1.76 2.09 2.38 2.62 2.83 3.00 3.14 3.25 3.35 3.43 3.49 3.54 20 50 0.97 1.41 1.82 2.20 2.54 2.85 3.14 3.39 3.62 3.83 4.01 4.17 4.32 4.44 20 100 0.97 1.42 1.84 2.23 2.60 2.95 3.26 3.56 3.83 4.09 4.32 4.54 4.74 4.92 20 200 0.97 1.42 1.85 2.25 2.63 2.99 3.33 3.65 3.95 4.24 4.50 4.75 4.99 5.21 20 500 0.98 1.43 1.86 2.27 2.65 3.02 3.38 3.71 4.03 4.33 4.62 4.90 5.16 5.41 20 1000 0.98 1.43 1.86 2.27 2.66 3.03 3.39 3.73 4.06 4.37 4.66 4.95 5.22 5.48 20 10000 0.98 1.43 1.86 2.27 2.67 3.04 3.40 3.75 4.08 4.40 4.70 5.00 5.28 5.55

50 5 0.95 1.31 1.59 1.79 1.93 2.03 2.09 2.14 2.16 2.18 2.19 2.20 2.20 2.21 50 10 0.97 1.38 1.74 2.04 2.28 2.46 2.61 2.72 2.80 2.86 2.91 2.94 2.97 2.99 50 20 0.98 1.43 1.83 2.20 2.52 2.80 3.04 3.25 3.41 3.55 3.67 3.77 3.84 3.91 50 50 0.99 1.45 1.90 2.32 2.71 3.08 3.42 3.73 4.01 4.26 4.50 4.70 4.89 5.06 50 100 0.99 1.46 1.92 2.36 2.78 3.18 3.57 3.93 4.27 4.60 4.90 5.18 5.45 5.69 50 200 0.99 1.47 1.93 2.38 2.82 3.24 3.65 4.04 4.42 4.79 5.14 5.47 5.79 6.09 50 500 0.99 1.47 1.94 2.40 2.84 3.28 3.70 4.12 4.52 4.91 5.29 5.66 6.02 6.37 50 1000 0.99 1.47 1.94 2.40 2.85 3.29 3.72 4.14 4.55 4.96 5.35 5.73 6.11 6.47 50 10000 0.99 1.47 1.94 2.40 2.86 3.30 3.74 4.16 4.58 5.00 5.40 5.80 6.19 6.57

100 5 0.95 1.32 1.61 1.82 1.96 2.06 2.13 2.17 2.20 2.22 2.23 2.24 2.24 2.25 100 10 0.97 1.40 1.76 2.07 2.32 2.51 2.67 2.78 2.87 2.93 2.98 3.02 3.05 3.06 100 20 0.98 1.44 1.86 2.24 2.58 2.87 3.12 3.34 3.52 3.67 3.79 3.89 3.98 4.05 100 50 0.99 1.47 1.92 2.36 2.77 3.16 3.52 3.85 4.16 4.43 4.69 4.91 5.12 5.30 100 100 0.99 1.48 1.95 2.40 2.85 3.27 3.68 4.07 4.44 4.79 5.13 5.44 5.73 6.01 100 200 0.99 1.48 1.96 2.43 2.89 3.33 3.77 4.19 4.61 5.00 5.39 5.76 6.12 6.46 100 500 1.00 1.48 1.97 2.44 2.91 3.37 3.83 4.27 4.71 5.14 5.56 5.98 6.38 6.78 100 1000 1.00 1.48 1.97 2.45 2.92 3.39 3.85 4.30 4.75 5.19 5.62 6.05 6.48 6.89 100 10000 1.00 1.49 1.97 2.45 2.93 3.40 3.86 4.32 4.78 5.23 5.68 6.12 6.56 7.00

1000 5 0.95 1.33 1.63 1.84 1.99 2.09 2.16 2.20 2.23 2.25 2.27 2.27 2.28 2.28 1000 10 0.98 1.41 1.78 2.10 2.36 2.56 2.72 2.84 2.93 3.00 3.05 3.09 3.12 3.14 1000 20 0.99 1.45 1.88 2.28 2.63 2.93 3.20 3.43 3.62 3.78 3.91 4.02 4.11 4.18 1000 50 1.00 1.48 1.95 2.40 2.83 3.24 3.62 3.97 4.30 4.60 4.87 5.12 5.34 5.54 1000 100 1.00 1.49 1.97 2.45 2.91 3.36 3.79 4.21 4.61 4.99 5.35 5.69 6.02 6.32 1000 200 1.00 1.49 1.99 2.47 2.95 3.42 3.89 4.34 4.78 5.22 5.64 6.05 6.44 6.83 1000 500 1.00 1.50 1.99 2.49 2.98 3.46 3.95 4.42 4.90 5.37 5.83 6.29 6.74 7.18 1000 1000 1.00 1.50 2.00 2.49 2.98 3.48 3.97 4.45 4.94 5.42 5.90 6.37 6.85 7.31 1000 10000 1.00 1.50 2.00 2.50 2.99 3.49 3.98 4.48 4.97 5.47 5.96 6.45 6.94 7.43

10000 5 0.96 1.33 1.63 1.84 1.99 2.09 2.16 2.21 2.24 2.26 2.27 2.28 2.28 2.29 10000 10 0.98 1.41 1.79 2.10 2.36 2.57 2.72 2.85 2.94 3.01 3.06 3.10 3.12 3.14 10000 20 0.99 1.45 1.89 2.28 2.63 2.94 3.21 3.43 3.63 3.79 3.92 4.03 4.12 4.19 10000 50 1.00 1.48 1.95 2.40 2.84 3.25 3.63 3.98 4.31 4.61 4.89 5.14 5.36 5.57 10000 100 1.00 1.49 1.98 2.45 2.92 3.37 3.80 4.22 4.62 5.01 5.37 5.72 6.05 6.35 10000 200 1.00 1.50 1.99 2.48 2.96 3.43 3.90 4.35 4.80 5.24 5.66 6.08 6.48 6.87 10000 500 1.00 1.50 2.00 2.49 2.98 3.47 3.96 4.44 4.92 5.39 5.86 6.32 6.78 7.23 10000 1000 1.00 1.50 2.00 2.50 2.99 3.49 3.98 4.47 4.96 5.44 5.93 6.41 6.88 7.36 10000 10000 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 4.99 5.49 5.99 6.49 6.98 7.48

Page 51: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-10

Table 5.1. Shear Force Modifier (mS), cont. Number of frames (endwalls are counted as frames) ke / k Ch / k

17 18 19 20 21 22 23 24 25 26 27 28 29 30

5 5 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 1.69 5 10 2.06 2.07 2.07 2.07 2.07 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 2.08 5 20 2.43 2.44 2.46 2.46 2.47 2.48 2.48 2.49 2.49 2.49 2.49 2.49 2.50 2.50 5 50 2.81 2.84 2.87 2.89 2.92 2.94 2.95 2.97 2.98 2.99 3.00 3.01 3.01 3.02 5 100 2.98 3.03 3.07 3.11 3.14 3.18 3.20 3.23 3.25 3.27 3.29 3.30 3.32 3.33 5 200 3.09 3.14 3.19 3.24 3.28 3.32 3.36 3.39 3.42 3.45 3.48 3.50 3.52 3.54 5 500 3.15 3.22 3.28 3.33 3.38 3.43 3.47 3.51 3.55 3.58 3.61 3.64 3.67 3.70 5 1000 3.18 3.24 3.30 3.36 3.41 3.46 3.51 3.55 3.59 3.63 3.66 3.70 3.73 3.75 5 10000 3.20 3.27 3.33 3.39 3.45 3.50 3.54 3.59 3.63 3.67 3.71 3.74 3.78 3.81

10 5 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 1.94 10 10 2.50 2.50 2.51 2.51 2.51 2.52 2.52 2.52 2.52 2.52 2.52 2.52 2.52 2.52 10 20 3.09 3.12 3.14 3.15 3.16 3.17 3.18 3.19 3.19 3.20 3.20 3.20 3.21 3.21 10 50 3.77 3.84 3.89 3.94 3.99 4.02 4.06 4.09 4.11 4.13 4.15 4.17 4.18 4.19 10 100 4.12 4.21 4.30 4.38 4.45 4.52 4.58 4.63 4.68 4.72 4.76 4.80 4.83 4.86 10 200 4.33 4.45 4.56 4.66 4.76 4.84 4.92 5.00 5.07 5.13 5.19 5.25 5.30 5.35 10 500 4.47 4.61 4.74 4.86 4.97 5.08 5.18 5.27 5.36 5.44 5.52 5.60 5.67 5.73 10 1000 4.52 4.66 4.80 4.93 5.05 5.16 5.27 5.37 5.47 5.56 5.65 5.73 5.81 5.88 10 10000 4.57 4.72 4.86 4.99 5.12 5.24 5.36 5.47 5.57 5.67 5.76 5.86 5.94 6.03

20 5 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 2.10 20 10 2.79 2.80 2.80 2.81 2.81 2.81 2.82 2.82 2.82 2.82 2.82 2.82 2.82 2.82 20 20 3.58 3.62 3.64 3.66 3.68 3.69 3.71 3.71 3.72 3.73 3.73 3.74 3.74 3.74 20 50 4.56 4.65 4.74 4.82 4.88 4.94 4.99 5.03 5.07 5.11 5.14 5.16 5.18 5.20 20 100 5.08 5.24 5.38 5.51 5.62 5.73 5.83 5.91 5.99 6.07 6.13 6.20 6.25 6.30 20 200 5.42 5.61 5.80 5.97 6.13 6.28 6.42 6.55 6.67 6.79 6.90 7.00 7.09 7.18 20 500 5.65 5.88 6.09 6.30 6.50 6.69 6.87 7.04 7.20 7.36 7.51 7.65 7.78 7.91 20 1000 5.73 5.97 6.20 6.42 6.64 6.84 7.03 7.22 7.40 7.58 7.74 7.90 8.06 8.21 20 10000 5.81 6.06 6.30 6.54 6.77 6.98 7.20 7.40 7.60 7.79 7.97 8.15 8.33 8.50

50 5 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 2.21 50 10 3.00 3.01 3.02 3.02 3.03 3.03 3.03 3.03 3.03 3.04 3.04 3.04 3.04 3.04 50 20 3.96 4.00 4.03 4.06 4.08 4.10 4.11 4.12 4.13 4.14 4.14 4.15 4.15 4.16 50 50 5.20 5.33 5.45 5.55 5.64 5.72 5.79 5.85 5.90 5.95 5.99 6.03 6.06 6.08 50 100 5.92 6.13 6.33 6.51 6.67 6.83 6.97 7.10 7.21 7.32 7.42 7.51 7.59 7.67 50 200 6.39 6.66 6.93 7.18 7.41 7.64 7.85 8.05 8.24 8.42 8.59 8.75 8.90 9.04 50 500 6.71 7.04 7.36 7.67 7.97 8.26 8.54 8.81 9.07 9.32 9.57 9.80 10.03 10.25 50 1000 6.83 7.18 7.52 7.85 8.18 8.50 8.80 9.10 9.40 9.68 9.96 10.23 10.50 10.75 50 10000 6.94 7.31 7.68 8.03 8.38 8.72 9.06 9.39 9.72 10.04 10.35 10.66 10.97 11.27

100 5 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 2.25 100 10 3.08 3.09 3.10 3.10 3.11 3.11 3.11 3.11 3.11 3.12 3.12 3.12 3.12 3.12 100 20 4.10 4.14 4.18 4.21 4.23 4.25 4.27 4.28 4.29 4.30 4.30 4.31 4.31 4.31 100 50 5.46 5.61 5.74 5.85 5.95 6.04 6.12 6.19 6.24 6.30 6.34 6.38 6.42 6.45 100 100 6.26 6.50 6.72 6.93 7.12 7.29 7.45 7.60 7.74 7.86 7.98 8.08 8.18 8.27 100 200 6.79 7.10 7.41 7.69 7.97 8.23 8.48 8.72 8.94 9.15 9.35 9.54 9.72 9.89 100 500 7.16 7.54 7.91 8.27 8.62 8.96 9.29 9.62 9.93 10.24 10.53 10.82 11.10 11.37 100 1000 7.30 7.70 8.10 8.49 8.87 9.24 9.61 9.97 10.33 10.67 11.01 11.35 11.68 12.00 100 10000 7.43 7.85 8.28 8.69 9.11 9.51 9.92 10.32 10.72 11.11 11.50 11.88 12.27 12.64

1000 5 2.28 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 1000 10 3.15 3.16 3.17 3.18 3.18 3.18 3.19 3.19 3.19 3.19 3.19 3.19 3.19 3.19 1000 20 4.24 4.29 4.32 4.36 4.38 4.40 4.42 4.43 4.44 4.45 4.46 4.46 4.47 4.47 1000 50 5.72 5.88 6.02 6.15 6.26 6.36 6.44 6.52 6.59 6.65 6.70 6.74 6.78 6.81 1000 100 6.61 6.87 7.12 7.35 7.57 7.77 7.95 8.12 8.28 8.43 8.56 8.68 8.79 8.89 1000 200 7.20 7.56 7.90 8.23 8.55 8.85 9.14 9.41 9.68 9.93 10.17 10.39 10.61 10.81 1000 500 7.62 8.05 8.48 8.89 9.30 9.70 10.10 10.48 10.86 11.22 11.58 11.93 12.27 12.61 1000 1000 7.78 8.24 8.69 9.15 9.59 10.04 10.47 10.91 11.33 11.75 12.17 12.58 12.99 13.39 1000 10000 7.92 8.41 8.90 9.39 9.87 10.36 10.84 11.33 11.81 12.29 12.77 13.25 13.73 14.20

10000 5 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 2.29 10000 10 3.16 3.17 3.18 3.19 3.19 3.19 3.19 3.20 3.20 3.20 3.20 3.20 3.20 3.20 10000 20 4.25 4.30 4.34 4.37 4.40 4.42 4.43 4.45 4.46 4.46 4.47 4.48 4.48 4.48 10000 50 5.75 5.91 6.05 6.18 6.29 6.39 6.48 6.56 6.62 6.68 6.73 6.78 6.82 6.85 10000 100 6.64 6.91 7.17 7.40 7.62 7.82 8.01 8.18 8.34 8.49 8.62 8.74 8.86 8.96 10000 200 7.24 7.60 7.95 8.29 8.61 8.92 9.21 9.49 9.76 10.01 10.26 10.49 10.71 10.91 10000 500 7.67 8.11 8.54 8.96 9.38 9.78 10.18 10.57 10.96 11.33 11.70 12.06 12.41 12.75 10000 1000 7.83 8.30 8.76 9.22 9.67 10.12 10.57 11.01 11.44 11.88 12.30 12.72 13.14 13.55 10000 10000 7.98 8.47 8.97 9.46 9.96 10.45 10.94 11.44 11.93 12.42 12.91 13.40 13.89 14.38

Page 52: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-11

Table 5.2. Sidesway Restraining Force Modifier (mD) Number of frames (endwalls counted as frames) ke / k Ch / k

3 4 5 6 7 8 9 10 11 12 13 14 15 16

5 5 0.75 0.64 0.52 0.43 0.34 0.28 0.22 0.18 0.14 0.12 0.09 0.08 0.06 0.05 5 10 0.78 0.69 0.59 0.52 0.44 0.39 0.33 0.28 0.24 0.21 0.18 0.15 0.13 0.11 5 20 0.80 0.72 0.64 0.58 0.51 0.46 0.41 0.37 0.33 0.30 0.26 0.24 0.21 0.19 5 50 0.81 0.74 0.67 0.62 0.56 0.52 0.48 0.44 0.41 0.38 0.35 0.32 0.30 0.28 5 100 0.81 0.74 0.68 0.63 0.58 0.54 0.50 0.47 0.44 0.41 0.38 0.36 0.34 0.32 5 200 0.82 0.75 0.69 0.64 0.59 0.55 0.52 0.48 0.46 0.43 0.41 0.38 0.36 0.35 5 500 0.82 0.75 0.69 0.64 0.60 0.56 0.52 0.49 0.47 0.44 0.42 0.40 0.38 0.36 5 1000 0.82 0.75 0.69 0.64 0.60 0.56 0.53 0.50 0.47 0.45 0.42 0.40 0.39 0.37 5 10000 0.82 0.75 0.69 0.64 0.60 0.56 0.53 0.50 0.47 0.45 0.43 0.41 0.39 0.37

10 5 0.83 0.73 0.60 0.51 0.41 0.34 0.27 0.22 0.17 0.14 0.11 0.09 0.07 0.06 10 10 0.86 0.79 0.70 0.63 0.54 0.48 0.41 0.36 0.30 0.26 0.22 0.19 0.16 0.14 10 20 0.88 0.83 0.76 0.70 0.64 0.58 0.52 0.48 0.43 0.39 0.35 0.31 0.28 0.25 10 50 0.90 0.85 0.80 0.75 0.71 0.66 0.62 0.58 0.55 0.51 0.48 0.45 0.42 0.39 10 100 0.90 0.86 0.81 0.77 0.73 0.70 0.66 0.63 0.60 0.57 0.54 0.51 0.49 0.46 10 200 0.90 0.86 0.82 0.78 0.75 0.71 0.68 0.65 0.63 0.60 0.57 0.55 0.53 0.51 10 500 0.90 0.86 0.82 0.79 0.75 0.72 0.70 0.67 0.64 0.62 0.60 0.58 0.56 0.54 10 1000 0.90 0.86 0.83 0.79 0.76 0.73 0.70 0.67 0.65 0.63 0.61 0.59 0.57 0.55 10 10000 0.91 0.86 0.83 0.79 0.76 0.73 0.70 0.68 0.66 0.63 0.61 0.59 0.58 0.56

20 5 0.87 0.78 0.65 0.56 0.45 0.38 0.30 0.25 0.19 0.16 0.13 0.10 0.08 0.07 20 10 0.91 0.85 0.76 0.69 0.60 0.54 0.46 0.41 0.35 0.30 0.26 0.22 0.19 0.16 20 20 0.93 0.89 0.83 0.78 0.72 0.66 0.60 0.55 0.50 0.46 0.41 0.37 0.33 0.30 20 50 0.94 0.91 0.87 0.84 0.80 0.76 0.72 0.69 0.65 0.62 0.58 0.55 0.51 0.48 20 100 0.95 0.92 0.89 0.86 0.83 0.80 0.77 0.75 0.72 0.69 0.66 0.64 0.61 0.58 20 200 0.95 0.92 0.90 0.87 0.85 0.83 0.80 0.78 0.76 0.73 0.71 0.69 0.67 0.65 20 500 0.95 0.93 0.90 0.88 0.86 0.84 0.82 0.80 0.78 0.76 0.74 0.72 0.71 0.69 20 1000 0.95 0.93 0.91 0.88 0.86 0.84 0.82 0.81 0.79 0.77 0.75 0.74 0.72 0.71 20 10000 0.95 0.93 0.91 0.89 0.87 0.85 0.83 0.81 0.80 0.78 0.76 0.75 0.73 0.72

50 5 0.89 0.81 0.68 0.59 0.48 0.40 0.32 0.26 0.21 0.17 0.13 0.11 0.09 0.07 50 10 0.93 0.88 0.80 0.73 0.65 0.58 0.50 0.44 0.38 0.33 0.28 0.24 0.21 0.18 50 20 0.96 0.93 0.88 0.83 0.77 0.72 0.66 0.61 0.55 0.51 0.46 0.41 0.37 0.34 50 50 0.97 0.95 0.93 0.90 0.87 0.84 0.80 0.77 0.73 0.70 0.66 0.63 0.59 0.56 50 100 0.98 0.96 0.94 0.93 0.90 0.88 0.86 0.84 0.81 0.79 0.76 0.74 0.71 0.69 50 200 0.98 0.97 0.95 0.94 0.92 0.91 0.89 0.88 0.86 0.84 0.82 0.81 0.79 0.77 50 500 0.98 0.97 0.96 0.95 0.94 0.92 0.91 0.90 0.89 0.88 0.86 0.85 0.84 0.83 50 1000 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.86 0.85 50 10000 0.98 0.97 0.96 0.95 0.94 0.93 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.87

100 5 0.90 0.82 0.69 0.60 0.48 0.41 0.32 0.27 0.21 0.17 0.14 0.11 0.09 0.07 100 10 0.94 0.90 0.82 0.75 0.66 0.59 0.51 0.45 0.39 0.34 0.29 0.25 0.21 0.18 100 20 0.97 0.94 0.89 0.85 0.79 0.74 0.68 0.63 0.57 0.52 0.47 0.43 0.39 0.35 100 50 0.98 0.97 0.94 0.92 0.89 0.86 0.83 0.80 0.76 0.73 0.69 0.66 0.62 0.59 100 100 0.99 0.98 0.96 0.95 0.93 0.91 0.89 0.87 0.85 0.83 0.80 0.78 0.75 0.73 100 200 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.91 0.90 0.88 0.87 0.85 0.84 0.82 100 500 0.99 0.98 0.98 0.97 0.96 0.96 0.95 0.94 0.93 0.92 0.91 0.90 0.89 0.88 100 1000 0.99 0.98 0.98 0.97 0.97 0.96 0.95 0.95 0.94 0.93 0.93 0.92 0.91 0.91 100 10000 0.99 0.99 0.98 0.98 0.97 0.97 0.96 0.96 0.95 0.95 0.94 0.94 0.93 0.93

1000 5 0.91 0.83 0.70 0.61 0.49 0.41 0.33 0.27 0.22 0.18 0.14 0.11 0.09 0.07 1000 10 0.95 0.91 0.83 0.76 0.67 0.60 0.52 0.46 0.40 0.35 0.30 0.26 0.22 0.19 1000 20 0.98 0.95 0.91 0.87 0.81 0.76 0.70 0.65 0.59 0.54 0.49 0.45 0.40 0.36 1000 50 0.99 0.98 0.96 0.94 0.91 0.89 0.86 0.83 0.79 0.76 0.72 0.69 0.65 0.62 1000 100 0.99 0.99 0.98 0.97 0.95 0.94 0.92 0.90 0.88 0.86 0.84 0.82 0.79 0.77 1000 200 1.00 0.99 0.99 0.98 0.98 0.97 0.96 0.95 0.94 0.93 0.91 0.90 0.88 0.87 1000 500 1.00 1.00 0.99 0.99 0.99 0.99 0.98 0.98 0.97 0.97 0.96 0.95 0.95 0.94 1000 1000 1.00 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.98 0.98 0.98 0.97 0.97 0.97 1000 10000 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.99 0.99

10000 5 0.91 0.83 0.70 0.61 0.49 0.42 0.33 0.27 0.22 0.18 0.14 0.11 0.09 0.07 10000 10 0.95 0.91 0.83 0.76 0.68 0.61 0.53 0.46 0.40 0.35 0.30 0.26 0.22 0.19 10000 20 0.98 0.95 0.91 0.87 0.81 0.76 0.70 0.65 0.59 0.54 0.49 0.45 0.40 0.37 10000 50 0.99 0.98 0.96 0.94 0.92 0.89 0.86 0.83 0.79 0.76 0.72 0.69 0.65 0.62 10000 100 1.00 0.99 0.98 0.97 0.96 0.94 0.93 0.91 0.89 0.87 0.84 0.82 0.80 0.77 10000 200 1.00 1.00 0.99 0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.90 0.89 0.87 10000 500 1.00 1.00 1.00 0.99 0.99 0.99 0.98 0.98 0.98 0.97 0.96 0.96 0.95 0.95 10000 1000 1.00 1.00 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.99 0.98 0.98 0.98 0.97 10000 10000 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00

Page 53: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-12

Table 5.2. Sidesway Restraining Force Modifier (mD), cont. Number of frames (endwalls counted as frames) ke / k Ch / k

17 18 19 20 21 22 23 24 25 26 27 28 29 30

5 5 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00 0.00 0.00 5 10 0.09 0.08 0.07 0.06 0.05 0.04 0.04 0.03 0.03 0.02 0.02 0.02 0.01 0.01 5 20 0.17 0.15 0.13 0.12 0.11 0.10 0.09 0.08 0.07 0.06 0.06 0.05 0.04 0.04 5 50 0.26 0.24 0.22 0.21 0.19 0.18 0.17 0.16 0.14 0.13 0.12 0.12 0.11 0.10 5 100 0.30 0.29 0.27 0.26 0.24 0.23 0.22 0.20 0.19 0.18 0.17 0.17 0.16 0.15 5 200 0.33 0.31 0.30 0.29 0.27 0.26 0.25 0.24 0.23 0.22 0.21 0.20 0.19 0.19 5 500 0.35 0.33 0.32 0.31 0.29 0.28 0.27 0.26 0.25 0.25 0.24 0.23 0.22 0.21 5 1000 0.35 0.34 0.33 0.31 0.30 0.29 0.28 0.27 0.26 0.25 0.25 0.24 0.23 0.23 5 10000 0.36 0.35 0.33 0.32 0.31 0.30 0.29 0.28 0.27 0.26 0.26 0.25 0.24 0.24

10 5 0.05 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00 0.00 10 10 0.12 0.10 0.09 0.08 0.06 0.06 0.05 0.04 0.03 0.03 0.03 0.02 0.02 0.02 10 20 0.23 0.20 0.18 0.16 0.15 0.13 0.12 0.11 0.09 0.08 0.08 0.07 0.06 0.05 10 50 0.36 0.34 0.32 0.30 0.28 0.26 0.24 0.23 0.21 0.20 0.18 0.17 0.16 0.15 10 100 0.44 0.42 0.40 0.38 0.36 0.34 0.33 0.31 0.29 0.28 0.27 0.25 0.24 0.23 10 200 0.49 0.47 0.45 0.43 0.42 0.40 0.39 0.37 0.36 0.34 0.33 0.32 0.31 0.30 10 500 0.52 0.50 0.49 0.47 0.46 0.44 0.43 0.42 0.40 0.39 0.38 0.37 0.36 0.35 10 1000 0.53 0.52 0.50 0.49 0.47 0.46 0.45 0.43 0.42 0.41 0.40 0.39 0.38 0.37 10 10000 0.54 0.53 0.51 0.50 0.49 0.47 0.46 0.45 0.44 0.43 0.42 0.41 0.40 0.39

20 5 0.05 0.04 0.03 0.03 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.01 0.00 0.00 20 10 0.14 0.12 0.10 0.09 0.07 0.06 0.05 0.05 0.04 0.03 0.03 0.03 0.02 0.02 20 20 0.27 0.24 0.22 0.20 0.17 0.16 0.14 0.13 0.11 0.10 0.09 0.08 0.07 0.06 20 50 0.45 0.42 0.40 0.37 0.35 0.33 0.30 0.28 0.27 0.25 0.23 0.22 0.20 0.19 20 100 0.56 0.53 0.51 0.49 0.47 0.45 0.43 0.41 0.39 0.37 0.35 0.34 0.32 0.31 20 200 0.63 0.61 0.59 0.57 0.55 0.53 0.52 0.50 0.48 0.47 0.45 0.44 0.42 0.41 20 500 0.67 0.66 0.64 0.63 0.61 0.60 0.59 0.57 0.56 0.55 0.53 0.52 0.51 0.50 20 1000 0.69 0.68 0.66 0.65 0.64 0.62 0.61 0.60 0.59 0.58 0.57 0.55 0.54 0.53 20 10000 0.71 0.69 0.68 0.67 0.66 0.65 0.64 0.63 0.62 0.61 0.60 0.59 0.58 0.57

50 5 0.06 0.05 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00 50 10 0.15 0.13 0.11 0.10 0.08 0.07 0.06 0.05 0.04 0.04 0.03 0.03 0.02 0.02 50 20 0.30 0.27 0.24 0.22 0.20 0.18 0.16 0.14 0.13 0.11 0.10 0.09 0.08 0.07 50 50 0.52 0.49 0.46 0.44 0.41 0.38 0.36 0.34 0.31 0.29 0.27 0.26 0.24 0.22 50 100 0.66 0.64 0.61 0.59 0.56 0.54 0.52 0.50 0.47 0.45 0.43 0.41 0.40 0.38 50 200 0.75 0.73 0.71 0.69 0.68 0.66 0.64 0.62 0.60 0.59 0.57 0.55 0.54 0.52 50 500 0.81 0.80 0.79 0.78 0.76 0.75 0.74 0.73 0.71 0.70 0.69 0.68 0.67 0.65 50 1000 0.84 0.83 0.82 0.81 0.80 0.79 0.78 0.77 0.76 0.75 0.74 0.73 0.72 0.71 50 10000 0.86 0.85 0.84 0.84 0.83 0.82 0.81 0.81 0.80 0.79 0.79 0.78 0.77 0.77

100 5 0.06 0.05 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00 100 10 0.16 0.13 0.11 0.10 0.08 0.07 0.06 0.05 0.04 0.04 0.03 0.03 0.02 0.02 100 20 0.31 0.28 0.25 0.23 0.20 0.18 0.16 0.15 0.13 0.12 0.11 0.09 0.08 0.08 100 50 0.55 0.52 0.49 0.46 0.43 0.41 0.38 0.36 0.33 0.31 0.29 0.27 0.25 0.24 100 100 0.70 0.68 0.65 0.63 0.60 0.58 0.56 0.53 0.51 0.49 0.47 0.45 0.43 0.41 100 200 0.80 0.78 0.77 0.75 0.73 0.71 0.69 0.68 0.66 0.64 0.62 0.61 0.59 0.57 100 500 0.87 0.86 0.85 0.84 0.83 0.82 0.81 0.80 0.79 0.77 0.76 0.75 0.74 0.73 100 1000 0.90 0.89 0.88 0.88 0.87 0.86 0.85 0.84 0.84 0.83 0.82 0.81 0.80 0.80 100 10000 0.92 0.92 0.91 0.91 0.90 0.90 0.90 0.89 0.89 0.88 0.88 0.87 0.87 0.86

1000 5 0.06 0.05 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00 1000 10 0.16 0.14 0.12 0.10 0.09 0.07 0.06 0.05 0.05 0.04 0.03 0.03 0.02 0.02 1000 20 0.33 0.29 0.26 0.24 0.21 0.19 0.17 0.15 0.14 0.12 0.11 0.10 0.09 0.08 1000 50 0.58 0.55 0.52 0.49 0.46 0.43 0.40 0.38 0.35 0.33 0.31 0.29 0.27 0.25 1000 100 0.74 0.72 0.69 0.67 0.64 0.62 0.60 0.57 0.55 0.53 0.50 0.48 0.46 0.44 1000 200 0.85 0.84 0.82 0.80 0.79 0.77 0.75 0.74 0.72 0.70 0.68 0.66 0.65 0.63 1000 500 0.93 0.93 0.92 0.91 0.90 0.89 0.88 0.87 0.86 0.85 0.84 0.83 0.82 0.81 1000 1000 0.96 0.96 0.95 0.95 0.94 0.94 0.93 0.93 0.92 0.92 0.91 0.90 0.90 0.89 1000 10000 0.99 0.99 0.99 0.99 0.99 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98

10000 5 0.06 0.05 0.04 0.03 0.02 0.02 0.02 0.01 0.01 0.01 0.01 0.01 0.00 0.00 10000 10 0.16 0.14 0.12 0.10 0.09 0.07 0.06 0.05 0.05 0.04 0.03 0.03 0.02 0.02 10000 20 0.33 0.30 0.26 0.24 0.21 0.19 0.17 0.15 0.14 0.12 0.11 0.10 0.09 0.08 10000 50 0.58 0.55 0.52 0.49 0.46 0.43 0.40 0.38 0.36 0.33 0.31 0.29 0.27 0.25 10000 100 0.75 0.72 0.70 0.67 0.65 0.62 0.60 0.58 0.55 0.53 0.51 0.49 0.47 0.45 10000 200 0.86 0.84 0.83 0.81 0.79 0.78 0.76 0.74 0.72 0.71 0.69 0.67 0.65 0.64 10000 500 0.94 0.93 0.92 0.92 0.91 0.90 0.89 0.88 0.87 0.86 0.85 0.84 0.83 0.82 10000 1000 0.97 0.96 0.96 0.96 0.95 0.95 0.94 0.94 0.93 0.93 0.92 0.91 0.91 0.90 10000 10000 1.00 1.00 1.00 1.00 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99

Page 54: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-13

FRAME FRAME APPLIED HORIZONTAL LOAD RESISTED FRACTION OF NUMBER STIFFNESS LOAD DISPLACEMENT BY FRAME APPLIED LOAD --------------------------------------------------------------------- 1 10000.00 500.0 .1946696 1946.7 3.8934 2 100.00 1000.0 .3393392 33.9 .0339 3 100.00 1000.0 .3874022 38.7 .0387 4 100.00 1000.0 .3393392 33.9 .0339 5 10000.00 500.0 .1946696 1946.7 3.8934 DIAPHRAGM DIAPHRAGM SHEAR SHEAR NUMBER STIFFNESS DISPLACEMENT LOAD -------------------------------------------- 1 10000.00 .1446696 1446.7 2 10000.00 .0480630 480.6 3 10000.00 .0480630 480.6 4 10000.00 .1446696 1446.7

Figure 5.9. Sample output from computer program DAFI.

When requirements for use of tables 5.1 and 5.2 are met, equation 5-8 can be used to calculate the total sidesway resisting force, Q. In all other cases, analysis tools such as DAFI must be used to obtain Q. A copy of output from program DAFI for a 4-bay building with Ch fixed at 10000, ke at 10000, k at 100, and R at 1000 is shown in figure 5.9. Although the sidesway resisting force for each frame is not given in the DAFI output, it is numerically equal to the difference between the load applied to the frame, and the load re-sisted by the frame – two values that are listed in the program’s output. For example, Q for the critical middle frame (frame 3 in figure 5.9), would be equal to the difference between 1000.0 and 38.7 or 961.3. Since diaphragm construction typically doesn‘t change from one side of a frame to the other side of the frame, Ch and ch,i values associated with either of the two diaphragm elements (that are adjacent to the frame) can be used in equa-tion 5-9. Horizontal restraining forces calculated for the three diaphragms in figure 5.2b, are graphically illustrated in figure 5.10a. For post-frame com-ponent stress analysis, these restraining forces should be applied as in-plane forces as shown in figure 10b. In-plane forces are calculated from the horizontal forces as follows:

Qp,i = Q i / (cos θ i) or q p,i = Q i / (d i cos θ i) (5-11) where: Q pi = in-plane force applied to frame by

diaphragm i, lbf (N) Q i = sidesway resisting force due to dia-

phragm i, lbf (N) θ i = slope of diaphragm i q p,i = in-plane force applied to the frame

per unit length of diaphragm i, lbf/ft (N/m)

d i = slope length of diaphragm i, ft (m) 5.6.6 Simple Beam Analogy Equations. McGuire (1998) presented the concept of mod-eling the diaphragm as a simple beam with an applied load inversely proportional to deflection. This analogy resulted in the following equations for calculating diaphragm shear forces and lat-eral displacements for the special case when: (1) all diaphragm elements have the same stiff-ness Ch, (2) all interior frame elements have the same stiffness, k, (3) both exterior frame ele-ments (i.e., the two elements representing the endwalls) have the same stiffness, ke, and (4) eave load, R, is the same at each interior frame.

Page 55: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-14

Figure 5.10 (a) Frame with diaphragm resisting forces. (b) Resisting forces applied as uniformly distributed in-plane loads for frame component stress analysis. Vh = Chαs[A sinh(α x) + B cosh(α x)] (5-12) y = A cosh(α x) + B sinh(α x) + R/k (5-13) ye = R / [ k (1 – D)] (5-14) where: Vh = diaphragm shear force, lbf (N) x = distance from endwall, in. (mm) R = eave load, lbf (N)

s = frame spacing, in. (mm) y = lateral displacement of diaphragm at

a distance x from the endwall, in. (mm)

ye = lateral displacement of the endwall, in. (mm)

k = stiffness of interior frames, lbf/in. (N/mm)

ke = stiffness of endwall frames (or shearwalls), lbf/in. (N/mm)

Ch = horizontal shear stiffness for a width s of the diaphragm, lbf/in. (N/mm)

L = Distance between endwalls, in. (mm)

sinh = hyperbolic sine cosh = hyperbolic cosine

( k / Ch )1/2 α = s A = ye – R/k

A ( 1 – cosh(α L)) B = sinh(α L)

ke sinh(α L) D =

α Ch s (1 - cosh(α L)) 5.7 Component Design 5.7.1 General. All building components must be checked to ensure that actual loads do not ex-ceed allowable design values. In this section, special attention is given to components that are involved in load transfer by diaphragm action. 5.7.2 Diaphragms. The maximum shear in a diaphragm section, Vp,i, cannot exceed the al-lowable shear strength of the section, va,i, multi-plied by the diaphragm length. Vp,i < va,i d i (5-15) where: Vp,i = in-plane shear force in diaphragm

section i from equation 5-9 lbf (N) va,i = allowable in-plane shear strength of

diaphragm i (see Section 6.3.3), lbf/ft (N/m)

d i = slope length of diaphragm i, ft (m)

Q b

Roof Gravity Loads

Ceiling Gravity Loads

s x q

w w

s x qwr s x qlr

s x q

l w

Q a

Q c

Roof Gravity Loads

Ceiling Gravity Loads

s x q

w w

s x qwr s x qlr

s x q

l w

q p,a q p,b

q p,c

(a)

(b)

Page 56: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-15

5.7.3 Diaphragm Chords. In addition to shear forces, a roof/ceiling diaphragm assembly must also resist bending moment. The magnitude of this bending moment is dependent on a number of factors. For design, this bending moment is assumed to be no greater than: Md = Vh L / 4 (5-16) where: Md = diaphragm bending moment, lbf-ft

(N m) Vh = maximum total shear in roof/ceiling

diaphragm assembly, lbf (N) L = distance between shearwalls, ft (m) Equation 5-16 treats the roof/ceiling assembly as a uniformly loaded beam that is simple sup-ported by two shearwalls spaced a distance L apart. Each shearwall is assumed to be sub-jected to a force that is equal to the maximum total shear in the roof/ceiling assembly, Vh. The maximum total shear in the roof/ceiling assem-bly, Vh, can be obtained from computer output (e.g. figure 5.9), or equation 5-7 or 5-12 if appli-cable. The uniform load on the roof/ceiling as-sembly (w in figure 5.11a) is set equal to 2Vh/L. This quantity is multiplied by L2/8 to obtain Md.

The bending moment applied to a roof/ceiling diaphragm assembly is resisted by axial forces (a.k.a. chord forces) in members orientated per-pendicular to trusses/rafters. This includes roof purlins and analogous framing members in the ceiling diaphragm. For bending moment calcula-tions, these members are referred to as dia-phragm chords (figure 5.11a). Any connection in the chords, either between intermediate chord members or where they are connected to the endwalls, must be designed to resist the calcu-lated axial force. If the roof/ceiling assembly behaves as a single beam in resisting bending moment, the maxi-mum chord force (which is located in the edge chords) can be calculated as: Pe = Md α / b (5-17) where: Pe = axial force in edge chord, lbf (N) Md = diaphragm bending moment from

equation 5-16, lbf-ft (N m) α = reduction factor dependent on chord

force distribution b = horizontal distance between edge

chords, ft (m)

Figure 5.11. (a) Plan view of a diaphragm under a uniform load, w. Chord force distribu-tions when (b) moment resisted by edge chords only, (b) chord force distribution is linear, and (c) chord force distribution is linear, but diaphragm halves assumed to act independ-ently in resisting moment.

Vh

w

(a)(b) (c)

Trusses/raftersChords(d)

Vh

L

Shearwall

Page 57: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-16

The axial force in an edge chord is dependent on chord force distribution as indicated by the presence of α in equation 5-17. The current ASAE EP484 diaphragm design procedure (ASAE, 1999a) assumes that edge chords act alone in resisting bending moment (figure 5.11b). For this case, α is numerically equal to one (1). This is a conservative approach. Alter-natively, many engineers assume a linear distri-bution of chord forces as shown in figure 5.11c. When a linear distribution is assumed, the re-duction factor α is a function of chord location. If chords are evenly spaced, then α is given as:

(n – 1 )2 α =

n / 2

Σ (n – 2 i + 1)2 i =1

when n is even

(n – 1 )2

α =

(n-1)/2

Σ (n – 2 i + 1)2 i =1

when n is odd

where: α = reduction factor when chords are

evenly spaced and chord forces are linearly distributed

n = number of chord rows, including the two rows of edge chords

The preceding equations were used to calculate the values given in table 5.3. If a linear distribution of chord force is assumed (figure 5.11c), and interior chords are evenly spaced, the load in an interior chord, Pi, is given as: Pi = 2 Pe x i / b (5-18) where: Pi = axial force for chord in row i, lbf (N) Pe = axial force in edge chord from equa-

tion 5-17, lbf (N) b = horizontal distance between edge

chords, ft (m) x i = horizontal distance from center of

diaphragm to chord row i.

Table 5.3. Reduction Factor, α, for Axial Force in Edge Chords

n* α n* α 2 1.000 22 0.249 3 1.000 23 0.239 4 0.900 24 0.230 5 0.800 25 0.222 6 0.714 26 0.214 7 0.643 27 0.206 8 0.583 28 0.200 9 0.533 29 0.193 10 0.491 30 0.187 11 0.455 31 0.181 12 0.423 32 0.176 13 0.396 33 0.171 14 0.371 34 0.166 15 0.350 35 0.162 16 0.335 36 0.158 17 0.314 37 0.154 18 0.298 38 0.150 19 0.284 39 0.146 20 0.271 40 0.143 21 0.260 41 0.139

* n is the number of chord rows, including the two rows of edge chords

Technical Note Chord Forces The axial force induced in an individual chord by applied building loads is a function of many complex, interacting design variables. For this reason, designers have had to rely on simplify-ing assumptions in order to approximate chord forces. One common assumption is that the roof/ceiling assembly acts as a large deep beam that is simply supported by two end shearwalls. This assumption is used to calculate the maximum in-plane bending moment to which a diaphragm is subjected. This assumption is conservative in that it neglects the resistance to in-plane bend-ing contributed by sidewalls. Sidewalls help re-sist (and thereby reduce) in-plane bending mo-ments in two ways. First they brace endwalls

Page 58: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-17

and other shearwalls, which limits rotation of the diaphragm at these shearwalls. Second, they resist a change in eave length (and hence changes in eave chord forces) by virtue of their own in-plane shear stiffness. Because of the influence of sidewalls, the distri-bution of in-plane bending moment will not follow that for a typical simple supported beam (i.e., zero moment at the supports, and maximum moment at midspan). For this reason, Pollock and others (1996) recommend modeling the roof/ceiling assembly as a deep beam with fixed supports. Because of uncertainty surrounding variation in in-plane bending moment with building length, some designers will assign the maximum calcu-lated in-plane bending moment (Md from equa-tion 5-16) to every location along the length of the building. This is obviously a conservative approach. Another major assumption that a designer must make involves the distribution of chord forces across a building. Three different chord force distributions are shown in figure 5.11b, 5.11c, and 5.11d. Whether or not edge chords resist virtually all of the in-plane bending moment (fig-ure 5.11b), or a linear distribution of axial forces exists in chords between edge chords (figure 5.11c) is a question that is at the heart of ongo-ing research. In reality, the distribution of chord forces lies somewhere in between these two extremes, exactly where being dependent on specifics of the design and on the magnitude of the applied load (Note: at higher load levels, load distributions change due to geometric and material nonlinearities). Presently, there is very little research data to support one specific de-sign procedure/assumption. The most extensive investigation of chord forces was by Niu and Gebremedhin (1997) who strain gauged purlins in a full-scale building and in a diaphragm test assembly. The data collected in this study does not strongly support any particular hypotheses regarding chord force distribution. The only other research of significance to chord force dis-tribution was the comprehensive finite element analyses of diaphragm assemblies by Wright (1992) and Williams (1999). Both of these re-searchers found that in-plane bending

moment in their models was resisted almost en-tirely by the edge purlins. Bohnhoff and others (1999) showed that as the shear stiffness of cladding is increased, interior purlins get more involved in resisting in-plane bending moments. Chord force distribution has also been shown to depend on the degree of interaction between individual diaphragms. Figure 5.11d illustrates the distribution of chord forces when there is no interaction between individual diaphragms on both sides of a ridge. Note that interaction be-tween individual diaphragms on opposites sides of a ridge is highly dependent on: (1) the spac-ing between ridge purlins, and (2) the rigidity of the ridge cap and other elements joining the two diaphragms. 5.7.4 Shearwalls. End and intermediate shear-walls must have sufficient strength to transmit forces from roof and ceiling diaphragms to the foundation system. In equation form: va > Vs / (W – DT) (5-19) where: va = allowable shear capacity of shear-

wall, lbf/ft (N/m) Vs = force induced in shearwall, lbf (N) W = building width, ft (m) DT = total width of door and window

openings in the shearwall, ft (m) The allowable shear capacity of end and inter-mediate shearwalls, va, is obtained from vali-dated structural models, or from tests as out-lined in ASAE EP558 (see Section 6.5). The total force in the shear wall, Vs, is obtained from computer output (e.g. figure 5.8), or equation 5-7 or equation 5-12 if applicable. The total width of door and window openings, DT, generally varies with height as shown in fig-ure 5.12. At locations where DT is the greatest (section b-b in figure 5.12) additional reinforcing may be required to ensure that the allowable shear stress is not exceeded. The structural framing over a door or window opening will act as a drag strut transferring

Page 59: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-18

shear across the opening. The header over the opening shall be designed to carry the force in tension and/or compression across the opening.

Figure 5.12. Shearwall showing variations in opening width, DT, with height. Shearwall strength can easily be increased when the applied load exceeds shearwall capac-ity. For example, the density of stitch screws can be increased and additional fasteners can be added in panel flats (on both sides of each ma-jor rib is the most effective). If only one side of the wall has been sheathed, add wood paneling or metal cladding to the other side. Metal diago-nal braces can also be added beneath any wood paneling or corrugated metal siding. 5.7.5 Shearwall Connections. Connections that fasten (1) roof and ceiling diaphragms to a shearwall, and (2) shearwalls to the foundation system, must be designed to carry the appropri-ate amount of shear load. The design of these connections may be proved by tests of a typical connection detail or by an appropriate calcula-tion method. At end shearwalls it is not uncommon to use the truss top chord to transfer load from roof clad-ding to endwall cladding. Sidewall steel is fas-tened directly to the truss chord, as is the roof steel when purlins are inset. In buildings with top-running purlins, roof cladding can not be fastened directly to the truss. In such cases, blocking equal in depth to the purlins is placed between the purlins and fastened to the truss. Roof cladding is then attached directly to this blocking.

5.7.6 Shearwall Overturning. Diaphragm load-ing produces overturning moment in shearwalls. This moment induces vertical forces in shear-wall-to-foundation connections that must be added to vertical forces resulting from tributary loads. In the case of embedded posts, increases in uplift forces may require an increase in em-bedment depth, and increases in downward force may require an increase in footing size (see Chapter 8). 5.8 Rigid Roof Design 5.8.1 General. When diaphragm stiffness is considerably greater than the stiffness of interior post frames, the designer may want to assume that the diaphragm and shearwalls are infinitely stiff. Under this assumption, 100% of the applied eave load, R, is transferred by the diaphragm to shearwalls, and none of the applied eave load is resisted by the frames. Because all eave load is assumed to be transferred to shearwalls, no special analysis tools or design tables are re-quired to determine load distribution between diaphragms and post-frames. This simplifies the entire diaphragm design process. This simplified procedure is referred to as rigid roof design (Bender and others, 1991). 5.8.2 Calculation. When (1) the shearwalls and roof/ceiling diaphragm assembly are assumed to be infinitely rigid, (2) the only applied loads with horizontal components are due to wind, and (3) wind pressure is uniformly distributed on each wall and roof surface, then the maximum shear force in the diaphragm assembly is given as: Vh = L (hwr qwr – hlr qlr + hww fw qww – hlw fl qlw) / 2 (5-20) where: Vh = maximum diaphragm element shear

force, lbf (N) L = building length, ft (m) hwr = windward roof height, ft (m) hlr = leeward roof height, ft (m) hww = windward wall height, ft (m) hlw = leeward wall height, ft (m)

W

a

b

c

a

b

c

Page 60: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-19

qwr = design windward roof pressure, lbf/ft2 (N/m2)

qlr = design leeward roof pressure, lbf/ft2 (N/m2)

qww = design windward wall pressure, lbf/ft2 (N/m2)

qlw = design leeward wall pressure lbf/ft2 (N/m2)

fw = frame-base fixity factor, windward post

fl = frame-base fixity factor, leeward post

Inward acting wind pressures have positive signs, outward acting pressures are negative (figure 5.8). As previously noted, frame-base fixity factors, fw and fl, determine how much of the total wall load is transferred to the eave, and how much is transferred directly to the ground. The greater the resistance to rotation at the base of a wall, the more load will be attracted directly to the base of the wall. For substantial fixity against rotation at the groundline, set the frame-base fixity factor(s) equal to 3/8. For all other cases, set the frame-base fixity factor(s) equal to 1/2. For symmetrical base restraint and frame ge-ometry, equation 5-20 reduces to: Vh = L [hr (qwr – qlr) + hw f (qww – qlw)] / 2 (5-21) where: hr = roof height, ft (m) hw = wall height, ft (m) f = frame-base fixity factor for both lee-

ward and windward posts 5.8.3 Application. The Vh value calculated us-ing equation 5-20 (or 5-21) is always a conser-vative estimate of the actual maximum shear force (due to wind) in a diaphragm assembly. This estimate becomes increasingly conserva-tive as the amount of load resisted by interior post-frames increases. It follows that equations 5-20 and 5-21 are most accurate when dia-phragm stiffness is considerably greater than interior post-frame stiffness. This tends to be the case in buildings that are relatively wide and/or high, and in buildings where individual posts offer no resistance to rotation (i.e., the posts are more-or less pin-connected at both the floor and eave lines).

Output from a DAFI analysis of a building with relatively high diaphragm and shearwall stiffness values is presented in figure 5.9. This output shows less than 3% of the total horizontal eave load being resisted by the interior frames. Although rigid roof design expedites calculation of maximum diaphragm shear forces, the design procedure does not provide estimates of sides-way restraining force for interior post-frame de-sign. 5.9 References Anderson, G.A., D.S. Bundy and N.F. Meador. 1989. The force distribution method: procedure and application to the analysis of buildings with diaphragm action. Transactions of the ASAE 32(5):1781-1786. ASAE. 1999a. EP484.2 Diaphragm design of metal-clad wood-frame rectangular buildings. ASAE Standards, 46th Ed., ASAE, St. Joseph, MI. ASAE. 1999b. EP558.1 Load tests for metal-clad wood-frame diaphragms. ASAE Standards, 46th Ed., ASAE, St. Joseph, MI. Bender, D. A., T. D. Skaggs and F. E. Woeste. 1991. Rigid roof design for post-frame buildings. Applied Engineering in Agriculture 7(6):755-760. Bohnhoff, D. R., P. A. Boor, and G. A. Anderson. 1999. Thoughts on metal-clad wood-frame dia-phragm action and a full-scale building test. ASAE Paper No. 994202, ASAE, St. Joseph, MI. Bohnhoff, D. R. 1992. Expanding diaphragm analysis for post-frame buildings. Applied Engi-neering in Agriculture 8(4):509-517. Gebremedhin, K.G. 1987a. SOLVER: An inter-active structures analyzer for microcomputers. (Version 2). Northeast Regional Agricultural En-gineering Service. Cornell University, Ithaca, NY. Gebremedhin, K.G. 1987b. METCLAD: Dia-phragm design of metal-clad post-frame build-ings using microcomputers. Northeast Regional Agricultural Engineering Service. Cornell Uni-versity, Ithaca, NY.

Page 61: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

5-20

McGuire, P.M. 1998. One equation for compati-ble eave deflections. Frame Building News 10(4):39-44. Meader, N.F. 1997. Mathematical models for lateral resistance of post foundations. Trans of ASAE, 40(1):191-201. Niu, K.T. and K.G. Gebremedhin. 1997. Evalua-tion of interaction of wood framing and metal-cladding in roof diaphragms. Transactions of the ASAE 40(2):465-476. Pollock, D. G., D. A. Bender and K. G. Gebre-medhin. 1996. Designing for chord forces in post-frame roof diaphragms. Frame Building News 8(5):40-44. Purdue Research Foundation. 1986. Purdue plane structures analyzer. (Version 3.0). De-partment of Forestry and Natural Resources. Purdue University, West Layfette, IN. Williams, G. D. 1999. Modeling metal-clad wood-framed diaphragm assemblies. Ph.D. diss., University of Wisconsin-Madison, Madi-son, WI. Wright, B.W. 1992. Modeling timber-framed, metal-clad diaphragm performance. Ph.D. diss. The Pennsylvania State University, University Park, PA.

Page 62: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

6-1

Chapter 6: METAL-CLAD WOOD-FRAME DIAPHRAGM PROPERTIES

6.1 Introduction 6.1.1 General. One of the first steps in dia-phragm design is to establish in-plane shear strength and stiffness values for each identified diaphragm section. In most post-frame build-ings, these diaphragm sections consist of corru-gated metal panels that have been screwed or nailed to wood framing. Behavior of these metal-clad wood-frame (MCWF) diaphragms is com-plex, and consequently, has been the subject of considerable research during the past 20 years. In addition to improving overall design, this re-search has led to improved methods for predict-ing metal-clad wood-frame diaphragm strength and stiffness. 6.1.2 Predicting Diaphragm Behavior. There are essentially three procedures for predicting the strength and stiffness of a building dia-phragm. First, an exact replica of the building diaphragm (a.k.a. a full-size diaphragm) can be built and tested to failure. Second, a smaller, representative section of the building diaphragm can be built and laboratory tested. The strength and stiffness of this test assembly are then ex-trapolated to obtain strength and stiffness values for the building diaphragm. Lastly, diaphragm behavior can be predicted using finite element analysis software. The latter requires that the strength and stiffness properties of individual component (e.g., wood framing, mechanical connections, cladding) be known. Of the three procedures for predicting metal-clad wood-frame diaphragm properties, only the sec-ond one – extrapolation of diaphragm test as-sembly data - is commonly used. This is be-cause testing full-size diaphragms is simply not practical (a new test would have to be con-ducted every time overall dimensions changed), and finite element analysis of MCWF dia-phragms is, for practical purposes, still in a de-velopmental stage. The later can be attributed to the fact that the large number of variables affect-ing diaphragm structural properties, as well as the nonlinear behavior of some variables, has thus far precluded the development of a quick and reasonably accurate closed-form approxi-

mation of diaphragm strength and stiffness. 6.1.3 ASAE EP558 and EP484. Construction specifications and testing procedures for dia-phragm test assemblies are given in ASAE EP558 Load Test for Metal-Clad Wood-Frame Diaphragms (ASAE, 1999b). EP558 also gives equations for calculating diaphragm test assem-bly strength and stiffness. These calculations along with construction specifications and test-ing procedures from EP558 are outlined in Sec-tion 6.3: Diaphragm Assembly Tests. For addi-tional details and further explanation of testing procedures, readers are referred to the ASAE EP558 Commentary (ASAE, 1999b). ASAE EP484, which was introduced in detail in Chapter 5, contains the equations for extrapolat-ing diaphragm test assembly properties for use in building design. These calculations are pre-sented in Section 6.4: Building Diaphragm Properties. 6.2 Design Variables 6.2.1 General. Many variables affect the shear stiffness and strength of a structural diaphragm, including: overall geometry, cladding character-istics, wood properties, fastener type and loca-tion, and blocking. A short description of each of these variables follows. 6.2.2. Geometry. Geometric variables include: spacing between secondary framing members (e.g. purlins), spacing between primary framing members (e.g., trusses/rafters), and overall di-mensions. With respect to overall dimensions, diaphragm depth is measured parallel to primary frames, diaphragm length is measured perpen-dicular to primary frames. In most structures, the overall length of a roof diaphragm is equal to the length of the building. 6.2.3 Cladding. Cladding type (e.g., wood, metal, fiberglass, etc.) is a significant design variable. Coverage (and examples) in this de-sign manual is limited to corrugated metal clad-ding. Important design characteristics of this type of cladding include: base metal (e.g., steel,

Page 63: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

6-2

aluminum), base metal thickness, panel profile, and individual sheet width and length. 6.2.4 Wood Framing. The species, moisture content and specific gravity of wood used in the framing system will not only affect the structural properties of the wood members, but also the shear stiffness and strength of mechanical con-nections between wood members and between wood members and cladding. 6.2.5 Mechanical Connections. Type (screw or nail), size, and relative location of mechanical fasteners used to join components significantly impact diaphragm properties. Fasteners are primarily defined by what they connect. Major categories include purlin-to-rafter, sheet-to-purlin, and sheet-to-sheet (see figure 6.1). Sheet-to-sheet fasteners are more commonly referred to as stitch or seam fasteners. Remov-ing stitch fasteners can dramatically reduce the

shear strength and stiffness of a diaphragm. Sheet-to-purlin fasteners are also defined by their location (i.e., end, edge, and field). A sheet-to-purlin fastener may be located in a rib or in the flat of a corrugated metal panel. Locat-ing fasteners in the flat generally produces stronger and stiffer diaphragms. The nonlinear nature of fastener performance is one of the more complex variables affecting diaphragm stiffness. 6.2.6 Blocking. When secondary framing members are installed above primary framing (e.g. top running purlins) or below primary fram-ing (e.g. bottom-running ceiling framing), clad-ding can only be fastened directly to the secon-dary framing (see figure 6.1). In such cases, blocking is often placed between the cladding and primary framing to increase shear transfer between the components. This is commonly done at locations where diaphragms and shear-walls intersect.

Figure 6.1. Components of a metal-clad wood-frame roof diaphragm.

Sheet-to-Purlin Fasteners (Field)Stitch Fastener

Sidelap Seam

Sheet-to-Purlin Fasteners (End)

Corrugated Metal Cladding

Purlin Rafter/Truss Top Chord

Purlin-to-Rafter Fastener

Blocking between purlins Rake Board

Sheet-to-Purlin Fastener (Edge)

Page 64: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

6-3

(a)

(b)

Figure 6.2. (a) Cantilever test configuration, and (b) Simple beam test configuration for diaphragm test assemblies.

Dire

ctio

n of

C

orru

gatio

ns

Cladding

a = Test assembly width

1. Force P may be alternately applied at point H2. Locate gages 2 and 4 on the edge purlins3. Locate gages 1 and 3 on the rafter / truss chord

E

F G

H

Applied force, P

Purlins

Rafter / Truss chord

Deflection gage location and direction of measured

deflection (typ.)

Notes:

b =

Test

ass

embl

y le

ngth

1 3

4

2

b =

Test

ass

embl

y le

ngth

Dire

ctio

n of

co

rruga

tions

Cladding

3a = Test assembly width

1. The applied forces may alternately be applied at points J and L2. Locate gages 1, 2, 3 and 4 on the rafters/ truss chords

E

G

H

Applied force, P/2

Purlins

Rafter / Truss chord

Deflection gage location and direction of measured deflection (typ.)

Notes:

F I K

J L

Applied force, P/2

12 3

4

Page 65: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

6-4

6.3 Diaphragm Test Assemblies 6.3.1 Construction. With the exception of overall length and width, a diaphragm test as-sembly is required to be identical to the dia-phragm in the building being designed. Specifi-cally, frame members must be of identical size, spacing, species and grade; metal cladding must be identical in composition, profile and thickness; and fastener type and location must be the same. ASAE EP558 has established minimum sizes for diaphragm test assemblies to ensure that there is not too great a difference between the size of a diaphragm test assembly and the actual building diaphragm. 6.3.2 Test Configurations. ASAE EP558 al-lows for two different testing configurations: a cantilever test and a simple beam test (figures 6.2a and 6.2b, respectively). In both figures 6.2a and 6.2b, variable “a” represents the spacing between rafters/trusses (a.k.a. the frame spac-ing). This spacing should be equal to, or a multi-ple of, the frame spacing in the building being designed. 6.3.3 Shear Strength. The allowable design shear strength, of a diaphragm test assembly is equal to 40% of the ultimate strength of the as-sembly. In equation form: Cantilever test: va = 0.40 Pu / b (6-1) Simple beam test: va = 0.40 Pu / (2b) (6-2) where: va = allowable design shear strength,

lbf/ft (N/m) Pu = ultimate strength, lbf (N) = total applied load at failure b = assembly length, ft (m) (see figure

6.2) If one or more of the test assembly failures were initiated by lumber breakage or by failure of the fastenings in the wood, then the allowable de-sign shear stress must be adjusted to account for test duration. To adjust from a total elapsed testing time of 10 minutes to a normal load dura-tion of ten years, divide va by a factor of 1.6.

When this reduction is not applied (as would be the case when test assembly failure is not initi-ated by wood failure), the NDS load duration factor, CD, can not be used to increase the al-lowable design shear strength during building design. Completely separate of the load duration factor adjustment is the 30% increase in allow-able strengths allowed by most codes for wind loadings (see Section 3.9.4). 6.3.4 Shear Stiffness. The procedure for de-termining the effective shear modulus of a test assembly begins with calculation of the adjusted load-point deflection, DT. This value takes into account rigid body rotation/translation during assembly test and is calculated as follows: Cantilever test: DT = D3 – D1 – (a/b) (D2 + D4) (6-3) Simple beam test: DT = (D2 + D3 – D1 – D4) / 2 (6-4) where: DT = adjusted load point deflection, in.

(mm) D1, D2, D3, and D4 = deflection measure-

ments, in. (mm) (see figure 6.2) a = assembly width, ft (m) b = assembly length, ft (m) The effective in-plane shear stiffness, c, for a diaphragm test assembly is defined as the ratio of applied load to adjusted load point deflection at 40% of ultimate load. In equation form: Cantilever test: c = 0.4 Pu / DT,d (6-5) Simple beam test: c = 0.2 Pu / DT,d (6-6) where: c = effective in-plane shear stiffness,

lbf/in. (N/mm) DT,d = adjusted load-point deflection, DT, at

0.4 Pu, in. (mm) The in-plane shear stiffness for the diaphragm test assembly, c, is converted to an effective shear modulus for the test assembly, G, as:

Page 66: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

6-5

G = c (a/b) (6-7) where: G = effective shear modulus of the test

assembly, lbf/in (N/mm) 6.4 Building Diaphragm Properties 6.4.1 General. As described in Chapter 5, each building diaphragm is sectioned for analysis. Each of these sections must be assigned a hori-zontal stiffness value, ch, and an allowable load, va. 6.4.2 Shear Strength The allowable design shear strength of a build-ing diaphragm is equal to that calculated for the diaphragm test assembly. Consequently, to cal-culate the total in-plane shear load that a build-ing diaphragm can sustain, simply multiply the allowable design shear strength, va, by the slope length of the building diaphragm. 6.4.3 In-Plane Shear Stiffness. The in-plane shear stiffness, cp, of a building diaphragm sec-tion is calculated from the effective shear modulus, G, of the diaphragm test assembly using the following equation:

G bs cp = s (6-8)

or G bh cp = s cos(θ) (6-9)

where: G = effective shear stiffness of test as-

sembly, lbf/in (N/mm) bS = slope length of building diaphragm

section being modeled, ft (m) s = width of the building diaphragm sec-

tion being modeled, ft (m) bh = horizontal span length of building

diaphragm section, ft (m) θ = slope of the building diaphragm sec-

tion, degrees Implicit in equation 6-8 is the assumption that the total shear stiffness of a building diaphragm is a linear function of length.

6.4.4 Horizontal Shear Stiffness. The horizon-tal shear stiffness, ch, of a building diaphragm section is related to its in-plane shear stiffness as follows: ch = cp cos2(θ) (6-10) or ch = G bh cos(θ) / s (6-11) 6.5 Building Shearwall Properties 6.5.1 General. The same procedure used to determine the strength and stiffness of building diaphragms is used to determine the strength and stiffness of building shearwalls. That is, rep-resentative test assemblies are loaded to failure, to determine their shear strength and stiffness. These properties are then linearly extrapolated to obtain strength and stiffness values for the building shearwall(s). 6.5.2 Shearwall Test Assemblies. ASAE EP558 also contains guidelines for construction and testing of shearwall test assemblies. With the exception of overall length and width, a shearwall test assembly is required to be identi-cal to the shearwall in the building being de-signed. Specifically, frame members must be of identical size, spacing, species and grade; clad-ding must be identical; and fastener type and location must be the same. 6.6 Tabulated Data 6.6.1 Sources. Testing replicate samples of diaphragm test assemblies can get expensive. For this reason, a designer may choose not to conduct his/her own diaphragm tests, relying instead on designs that have been previously tested by others. Information on many tested designs is available in the public domain. Clad-ding manufacturers may have additional test information on assemblies that feature their own products. 6.6.2 Example Tabulated Data. Table 6.1 con-tains design details and engineering properties for roof diaphragm tests assemblies. The infor-mation in this table represents a small percent-age of available data.

Page 67: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

6-6

Table 6.1. Steel-Clad Roof Diaphragm Assembly Test Data Test Assembly Number 1 2 3 4 Test Configuration Cantilever Cantilever Cantilever Cantilever Cladding

Manufacturer/Trade Name Wick Agri Panel

Wick Agri Panel

Wick Agri Panel

Midwest Manu-facturing.

Base Metal Thickness Gauge 28 28 29 29 Major Rib Spacing, inches 12 12 12 12 Major Rib Height, inches 0.75 0.75 0.75 1.0 Major Rib Base Width, inches 1.25 1.25 1.25 2.5 Major Rib Top Width, inches 0.375 0.375 0.375 0.5 Yield Strength, ksi 50 50 80 80

Overall Design Width, feet 9 9 9 6 Length, b , feet 12 12 12 12 Purlin Spacing, feet 2 2 2 2 Rafter Spacing, feet 9 9 9 6 Purlin Location Top running Top running Top running Top running Purlin Orientation On edge On edge On edge On edge Number of Internal Seams 2 2 2 2

Wood Properties Purlin Size 2- by 4-inch 2- by 4-inch 2- by 4-inch 2- by 4-inch Purlin Species and Grade No.1 & 2 SPF No.1 & 2 SPF No.1 & 2 SPF No.2 SYP Rafter Species and Grade No. 1 SYP No. 1 SYP No. 1 SYP No. 1 SYP

Stitch Fastener Type None Screw Screw EZ Seal Nail Length, inches 1.0 1.0 2.5 Diameter #10 #10 8d On Center Spacing, inches 24 24 24

Sheet-to-Purlin Fasteners Type Screw Screw Screw EZ Seal Nail Length, inches 1.0 1.0 1.0 2.5 Diameter #10 #10 #10 8d Location in Field In Flat In Flat In Flat Major Rib Location on End In Flat In Flat In Flat In Flat Avg. On-Center Spacing in Field, in. 12 12 12 12 Avg. On-Center Spacing on End, in. 6 6 6 12

Purlin-to-Rafter Fastener 60d Threaded Hardened Nail

60d Threaded Hardened Nail

60d Threaded Hardened Nail

60d Threaded Hardened Nail

Engineering Properties Ultimate Strength, Pu, lbf. 2140 3390 3220 1930 Allowable Shear Strength, va, lbf/ft 71 113 107 64 Effective In-Plane Stiffness, c ,lbf/in 1625 2720 2720 1590 Effective Shear Modulus, G, lbf/in 1220 2040 2040 795

Reference Anderson, 1989

Anderson, 1989

Anderson, 1989

Wee & Ander-son, 1990

Page 68: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

6-7

Table 6.1. cont., Steel-Clad Roof Diaphragm Assembly Test Data Test Assembly Number 5 6 7 8 Test Configuration Cantilever Cantilever Cantilever Cantilever Cladding

Manufacturer/Trade Name Midwest Manu-facturing Grandrib 3 Grandrib 3 Walters

STR-28 Base Metal Thickness Gauge 29 29 29 28 Major Rib Spacing, inches 12 12 12 12 Major Rib Height, inches 1.0 0.75 0.75 0.94 Major Rib Base Width, inches 2.5 1.75 1.75 Major Rib Top Width, inches 0.5 0.5 0.5 Yield Strength, ksi 80 80 80 80

Overall Design Width, feet 6 9 9 9 Length, b , feet 12 12 12 16 Purlin Spacing, feet 2 2 2 2 Rafter Spacing, feet 6 9 9 9 Purlin Location Top running Top running Top running Top running Purlin Orientation On edge On edge On edge On edge Number of Internal Seams 2 2 2 2

Wood Properties Purlin Size 2- by 4-inch 2- by 4-inch 2- by 4-inch 2- by 4-inch Purlin Species and Grade No.2 SYP No.2 DFL No.2 SPF No.2 SYP Rafter Species and Grade No. 1 SYP No. 2 DFL No. 2 SPF 1950f1.7E SYP

Stitch Fastener Type EZ Seal Nail None None Screw Length, inches 2.5 1.5 Diameter 8d #10 On Center Spacing, inches 24 24

Sheet-to-Purlin Fasteners Type Screw Screw Screw Screw Length, inches 0.75 1.0 1.0 1.5 Diameter #12 #10 #10 #10 Location in Field In Flat In Flat In Flat In Flat Location on End In Flat In Flat In Flat In Flat Avg. On-Center Spacing in Field, in. 6 12 12 12 and 18 Avg. On-Center Spacing on End, in. 6 6 6 12

Purlin-to-Rafter Fastener 60d Threaded Hardened Nail

1-60d Spike + 2-10d Toenails

1-60d Spike + 2-10d Toenails

60d Threaded Hardened Nail

Engineering Properties Ultimate Strength, Pu, lbf. 3995 3300 2775 4884 Allowable Shear Strength, va, lbf/ft 133 110 93 122 Effective In-Plane Stiffness, c ,lbf/in 2980 2920 2950 3890 Effective Shear Modulus, G, lbf/in 1490 2190 2210 2190

Reference Wee & Ander-son, 1990

Lukens & Bundy, 1987

Lukens & Bundy, 1987

Bohnhoff and others, 1991

Page 69: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

6-8

Table 6.1. cont., Steel-Clad Roof Diaphragm Assembly Test Data Test Assembly Number 9 10 11 12 Test Configuration Simple Beam Cladding

Type Regular Leg Extended Leg Regular Leg Extended Leg Base Metal Thickness Gauge 29 Major Rib Spacing, inches 9 Major Rib Height, inches 0.62 Major Rib Base Width, inches 1.75 Major Rib Top Width, inches 0.75 Yield Strength, ksi 80

Overall Design Width, feet 36 Length, b , feet 12 Purlin Spacing, feet 2 Rafter Spacing Pair of rafters every 12 feet (each pair spaced 6 in. apart) Purlin Location Top running and lapped Inset Purlin length, ft 13.2 and 12.0 11.25

Purlin Attachment To special blocking nailed be-tween each pair of rafters

To joist hanger attached to raf-ters

Purlin Orientation On edge Number of Internal Seams 11

Wood Properties Purlin Size 2- by 6-inch Purlin Species and Grade No.2 DFL and 1650f DFL Rafter Species and Grade No. 2 DFL

Stitch Fastener* Type None Screw* None Screw* Length, inches 1.5 1.5 Diameter #10 #10 On Center Spacing, inches 24 24

Sheet-to-Purlin Fasteners Type Screw Length, inches 1.5 Diameter #10 Location in Field In Flat Location on End In Flat Avg. On-Center Spacing in Field, in. 9 Avg. On–Center Spacing on End, in. 9

Engineering Properties Ultimate Strength, Pu, lbf. 6950 7850 6400 6950 Allowable Shear Strength, va, lbf/ft 116 131 107 116 Effective In-Plane Stiffness, c ,lbf/in 4700 7500 3700 4400 Effective Shear Modulus, G, lbf/in 4700 7500 3700 4400

Reference NFBA, 1996 * Because of the extended leg, screws installed in the flat at overlapping seams function as stitch fasteners.

Page 70: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

6-9

Table 6.1. cont., Steel-Clad Roof Diaphragm Assembly Test Data Test Assembly Number 13 14 15 Test Configuration Simple Beam Simple Beam Simple Beam Cladding

Manufacturer/Trade Name Metal Sales Pro Panel II

Metal Sales Pro Panel II

McElroy Metal Max Rib

Base Metal Thickness Gauge 30 30 29 Major Rib Spacing, inches 9.0 9.0 9.0 Major Rib Height, inches 0.75 Major Rib Base Width, inches 1.75 Major Rib Top Width, inches Yield Strength, ksi 104 104 80

Overall Design Width, feet 24 24 24 Length, b , feet 12 12 12 Purlin Spacing, feet 2.33 2.33 2

Rafter Spacing, feet Pair of rafters every 12 feet (each pair spaced 6 in. apart)

Pair of rafters every 12 feet (each pair spaced 6 in. apart)

8

Purlin Location Top running Top running Top running Purlin Orientation On edge On edge NA Number of Internal Seams 8 8 7

Wood Properties Purlin Size 2- by 6-inch 2- by 6-inch

Purlin Species and Grade 1650f 1.5E SPF 1650f 1.5E SPF

Mac-Girt steel hat section: 1.5 in. tall, 3.2 in. wide, 18 ga.

Rafter Species and Grade 1650f 1.5E SPF 1650f 1.5E SPF 2250f 1.9E SP Stitch Fastener

Type Screw None None Length, inches 0.625 Diameter #12 On Center Spacing, inches 9

Sheet-to-Purlin Fasteners Type Screw Screw Screw Length, inches 1.5 1.5 1.0

Diameter #10 #10 in field #14 in ends #14

Location in Field In Flat In Flat In Flat Location on End In Flat In Flat In Flat Avg. On-Center Spacing in Field, in. 9 9 18 (3 screws/sheet) Avg. On-Center Spacing on End, in. 4.5 4.5 9 (4 screws/sheet)

Purlin-to-Rafter Fastener Two - #12 x 1.6 in. screws/joint

Engineering Properties Ultimate Strength, Pu, lbf. 9600 6600 8645 Allowable Shear Strength, va, lbf/ft 160 110 144 Effective In-Plane Stiffness, c ,lbf/in 7680 7100 10700 Effective Shear Modulus, G, lbf/in 7680 7100 7130

Reference Townsend, 1992 Townsend, 1992 Myers, 1994

Page 71: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

6-10

6.7 Example Calculations A designer wishes to find ch and va for roof diaphragm sections in a gable-roofed building with roof slopes of 4-in-12. Distance between eaves is 36 feet, and post-frame spacing, s, is 10 feet. A cantilever test of a representative diaphragm test assembly with a width, a, of 10 feet and a length, b, of 12 feet, yields an ultimate strength, Pu of 3900 lbf and an effective in-plane stiffness, c, of 4000 lbf/in. The test assembly failure was not wood related, there-fore the ultimate strength was not adjusted for load duration. Equation 6-1: va (test assembly) = 0.40 Pu / b va (test assembly) = 0.40 (3900 lbf) /12 ft = 130 lbf/ft Equation 6-7: G = c (a/b) G = (4000 lbf/in) (10 ft/12 ft) = 3333 lbf/in. Equation 6-11: ch = G bh cos(θ) / s ch = (3333 lbf/in) (36 ft / 2) (cos 18.4°) / 10 ft = 5690 lbf/in. The horizontal stiffness, ch of 5690 lbf/in represents a single diaphragm section that

runs from eave to ridge and has a width of 10 feet. va (diaphragm) = 1.30 va (test diaphragm) = 1.3 (130 lbf/ft) = 169 lbf/ft As described in Section 3.9.4, the allowable strength of a diaphragm can generally

be increased by 30% when wind or seismic loads are acting in combination with other loads.

6.8 References Anderson, G.A. 1989. Effect of fasteners on the stiffness and strength of timber-framed metal-clad roof sections. ASAE Paper No. MCR89-501. ASAE, St. Joseph, MI. ASAE. 1999a. EP484.2: Diaphragm design of metal-clad, wood-frame rectangular buildings. ASAE Standards, 46th Edition. St. Joseph, MI. ASAE. 1999b. ASAE EP558: Load tests for metal-clad wood-frame diaphragms. ASAE Standards, 46th edition. ASAE, St. Joseph, MI. Anderson, and P.A. Boor. 1991. Influence of insulation on the behavior of steel-clad wood frame diaphragms. Applied Engineering in Agri-culture 7(6):748-754.

Lukens, A.D., and D.S. Bundy. 1987. Strength and stiffnesses of post-frame building roof pan-els. ASAE Paper No. 874056. ASAE, St. Jo-seph, MI. Myers, N.C. 1994. McElroy Metal Post Frame Roof Diaphragm Test. Test Report 94-418. Pro-gressive Engineering, Inc., Goshen, IN. NFBA. 1996. 1996 Diaphragm Test. National Frame Builders Association, Inc., Lawrence, KS. Townsend, M. 1992. Alumax test report: dia-phragm loading on roofs and end wall sections. Alumax Building Products, Perris, CA. Wee, C.L. and G.A. Anderson. 1990. Strength and stiffness of metal clad roof section. ASAE Paper No. 904029. ASAE, St. Joseph, MI.

Page 72: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

7-1

Chapter 7: POST PROPERTIES 7.1 Introduction 7.1.1 Types. Several different post types are currently used in post-frame construction. The most common of these are laminated lumber posts. Solid-sawn posts are still used by most builders, but not to the extent they were a dec-ade ago. Parallel strand lumber (PSL) and laminated veneer lumber (LVL) products are gaining in popularity. Use of these and other engineered lumber products as posts in post-frame buildings can only be expected to in-crease as the relative cost of these products decreases. 7.1.2 Preservative Treatment. If posts are to be embedded, they must be preservative treated to avoid decay. General issues of preservative treatment have already been presented in Chapter 4. Discussion in this chapter will focus on the structural aspects of post selection and design. 7.2 Solid-Sawn Posts 7.2.1 Size. Post size varies considerably with building geometry and design loads. The most common sizes are 6- by 6-inch, 6- by 8-inch, and 4- by 6-inch. Although both S4S (Surfaced on 4 Sides) and rough sawn posts are available, most rough sawn posts are not graded and therefore are generally only used in code ex-empt applications. 7.2.2 Wood Species. Species of wood used in posts depends on local availability and on preservative treatment needs. Commonly used species includes Southern Pine, Douglas Fir and Ponderosa Pine. 7.2.3 Design Properties. NDS design values for species and grades typically used in post-frame construction are given in table 7.1. These values have been adjusted for conditions of use in which wood moisture content exceeds 19% for extended time periods, as is the case for embedded posts. To apply the values in table

7.1, a post must be graded by an approved grading agency and stamped accordingly. 7.2.4 Current Demand. Solid-sawn post use in post-frame construction is on the decline, pri-marily because posts of acceptable size, length and quality are increasingly difficult to obtain. The scarcity of long posts in structural sizes has made laminated posts more price competitive. Additionally, laminated post prices are typically constant on a per-foot basis regardless of length, while the cost of solid-sawn posts in-creases exponentially with length. 7.3 Laminated Lumber Posts 7.3.1 General. Laminated lumber posts are posts that are fabricated by joining together individual pieces of dimension lumber, most commonly 2- by 6-inch, 2- by 8-inch and 2- by 10-inch members. Structural properties of the finished product vary significantly depending on the means of lamination and the presence or absence of joints in individual layers. Laminates are either glued together or joined together with mechanical fasteners (i.e., nails, screws, bolts, shear transfer plates, metal plate connectors). 7.3.2 Advantages. By combining individual laminates to build up a desired cross-section, the statistical probability that a strength-reducing characteristic of wood (such as a knot) would exist through the entire cross section is greatly diminished. Consequently, laminated posts have more uniform strength and stiffness properties than solid-sawn posts. This increased reliability results in higher allowable design values.

7.3.3 Laminate Orientation. Laminated post strength is dependent on orientation of individual laminates with respect to the principal load direction. If a post is designed (and positioned within the structure) to resist loads acting on the edge, or narrow face, of the laminates, the post is said to be vertically-laminated (figure 7.1a). If a post is oriented such that the applied load acts on the wide face of the laminates, the post is said to be horizontally-laminated (figure 7.1b).

Page 73: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

7-2

Table 7.1. Design Stresses for Selected Species and Grades of Solid-Sawn Posts *

Design Values in Pounds per Square Inch (psi) Species and

Grade Bending, Fb

Tension Parallel to Grain, Ft

Shear Parallel to Grain, Fv

Compression Perpendicular to Grain, Fc┴

Compression Parallel to Grain, Fc

Modulus of Elasticity, E

Douglas Fir-Larch Sel Str 1500 1000 85 420 1045 1,600,000 No. 1 1200 825 85 420 910 1,600,000 No. 2 750 475 85 420 430 1,300,000 Northern Pine Sel Str 1150 800 65 290 820 1,300,000 No. 1 950 650 65 290 730 1,300,000 No. 2 500 375 65 290 340 1,000,000 Ponderosa Pine Sel Str 1000 675 65 360 730 1,100,000 No. 1 825 550 65 360 635 1,100,000 No. 2 475 325 65 360 295 900,000 Southern Pine Sel Str 1500 1000 110 375 950 1,500,000 No. 1 1350 900 110 375 825 1,500,000 No. 2 850 550 100 375 525 1,200,000 * From the National Design Specifications (NDS) for wood under wet-use conditions, AF&PA (1997b).

Values are for lumber in the size category “Posts and Timbers”.

Figure 7.1. (a) Vertically laminated, and (b) horizontally laminated post cross-sections.

7.4 Glued-Laminated (Glulam) Posts 7.4.1 Advantages. For a given species and grade of lumber, glued-laminated posts have higher allowable design values than solid-sawn posts and most spliced mechanically-laminated posts (see Section 7.6). Glued-laminated posts exhibit complete composite action, that is, the glue interface is of sufficient integrity that it is assumed that there is no slip between laminates regardless of load level. With no slip between layers, glued-laminated posts behave much like solid-sawn posts, and are very effective in carrying biaxial bending loads. 7.4.2 Vertical Lamination. Glued-laminated posts that have a rather square cross-section are typically designed as vertically-laminated components; that is, they are designed to resist primary bending moments about an axis per-pendicular to the wide faces of individual lamina-tions (Axis V-V, figure 7.1b). This class of posts

H

H

VV HH

V

V

Load

(a) (b)

Load

Page 74: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

7-3

(cross-sectional aspect ratios less than 1.5) are commonly used as posts in post-frame build-ings. 7.4.3 Horizontal Lamination. In contrast to the glued-laminated posts commonly used in post-frame construction, deep glulam beams (e.g. door headers) are generally designed as hori-zontally laminated components (figure 7.1a). Lumber is used more efficiently in these assem-blies by placing higher grade lumber in outer laminates where bending stresses are higher, and using lower grade lumber near the center where bending stresses are low. In addition, horizontal lamination facilitates the manufacture

of curved members. 7.4.4 Design Properties. Design properties for both horizontally- and vertically-laminated glu-lams are published by American Institute of Timber Construction (AITC, 1985) and AF&PA (1997b). Values for selected vertically-laminated assemblies are listed in table 7.2. These values are for dry-use conditions and normal load duration. In actual application, glulam design values must be adjusted by applicable factors involving curvature, volume, beam stability and column stability. These factors (and direction regarding their application) can also be found in the two references cited in this paragraph.

Table 7.2. Design Values for Vertically Glued Laminated Posts a

Extreme Fiber in Bending, psi Bending about

V-V Axis.

Compression Parallel to Grain, psi AITC

Combination

Symbol

Lumber Grade MOE, million

psi 3 Lams

4 or More Lams

Bending about

H-H Axis.

Tension Parallel to Grain,

psi 2 or 3 Lams

4 or More Lams

Douglas Fir- Larch

13 Dense Sel Str 2.0 2300 2400 2200 1600 1950 2300 12 Sel Str 1.8 1950 2100 1900 1400 1650 1950 11 No. 1 Dense 2.0 2100 2300 2100 1500 1700 2300 10 No. 1 1.8 1750 1950 1750 1300 1450 1950 9 No. 2 Dense 1.8 1800 1850 1600 1150 1350 1800 8 No. 2 1.6 1550 1600 1350 1000 1150 1550

Hem-Fir

21 Sel Str 1.6 1650 1750 1500 1100 1350 1450 20 No. 1 1.6 1500 1550 1350 975 1250 1450 19 No. 2 1.4 1300 1350 1150 850 975 1300

Southern Pine

52 Dense Sel Str 1.9 2300 2400 2100 1500 1850 2200 51 Sel Str 1.7 1950 2100 1750 1300 1600 1900 50 No. 1 Dense 1.9 2100 2100 b 1800 b 1550 1700 2300 49 No. 1 1.7 1750 1850 b 1550 b 1350 1450 2100 48 No. 2 Dense 1.7 1800 1850 b 1600 b 1400 1350 2200 47 No. 2 1.4 1550 1600 b 1350 b 1200 1150 1900

Wet Service Factor, CM

c 0.833 0.80 0.80 0.80 0.80 0.73 0.73 a From the National Design Specifications (NDS), AF&PA (1997b). b Values reflect the removal of the more restrictive slope-of-grain requirements. c The tabulated values are applicable when in-service moisture content is less than 16%. To obtain

wet-use values, multiply the tabulated values by the factors shown.

Page 75: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

7-4

7.4.5 Manufacturing Requirements. For glu-lam design values apply, tight quality control must be maintained during the laminating proc-ess. The AITC has published standards for the design (AITC, 1985) and manufacturing (AITC, 1988) of glued-laminated members. Fabrication procedures for the members must conform to an additional standard (AITC, 1983), which covers physical construction issues as well as quality control, testing and marking procedures. The rigorous requirements for construction, as well as the planing that must be performed (individ-ual laminates prior to lamination, and the fin-ished member after lamination completion), combine to essentially eliminate the possibility of on-site fabrication. These factors also increase product price, however, for many applications, higher design properties justify the higher cost. 7.4.6 End Joints. Posts of any length can be created by end-joining individual laminates. The most common glued end joint is the finger joint. Although finger joining is a common manufactur-ing process, only a few manufacturing facilities have the capability of producing finger joints that meet AITC quality standards for structural joints (i.e., the type of joints required in glulams). Joints that do not meet criteria established for structural joints are likely to fail when subjected to design level stresses. 7.4.7 Glulams for Post-Frame Buildings. A handful of companies now manufacture and market glulams specifically for use in post-frame buildings. These posts are intended for soil embedment, with pressure preservative treated wood on one end, and non-treated wood on the other. Fabrication of such posts requires special resins and procedures for joining and laminating treated wood to non-treated wood. 7.5 Unspliced Mechanically- Laminated Posts 7.5.1 General. The majority of posts used in post-frame construction with an overall length less than 18 feet are unspliced, mechanically-laminated posts. An unspliced post is any lami-nated post that does not contain end joints. This means that each layer is comprised of a single uncut piece of dimension lumber. 7.5.2 Fasteners. As previously noted, a me-chanically laminated post is a laminated post in

which nails, screws, bolts, and/or shear transfer plates (STPs) have been used to join individual laminates. Nails are the most commonly used mechanical fastener and posts that only feature nails are often referred to as nail-laminated posts. STPs are medium-gage metal plates that are stamped such that teeth protrude from both surfaces. Mechanical fasteners that connect preservative treated lumber should be AISI type 304 or 316 stainless steel, silicon bronze, copper, hot-dipped galvanized (zinc-coated) steel nails or hot-tumbled galvanized nails. 7.5.3 Advantages. Unspliced mechanically-laminated posts generally cost less than solid-sawn posts, and they are stronger than similarly sized solid-sawn posts when bent around axis V-V (figure 7.1a). As previously noted, this is due to the fact that strength reducing defects are spread out in laminated assemblies. Also, pressure preservative treatment retention is more uniform in the narrower laminates of a mechanically-laminated post than it is in wide solid-sawn posts. 7.5.4 Disadvantages. When mechanically-lami-nated posts are bent around axis H-H (figure 7.1b), there can be considerable slip between laminates. For this reason, the bending strength and stiffness of mechanically-laminated assem-blies bent about axis H-H is relatively low. To compensate for this weakness, mechanically-laminated posts are generally only used where: (1) there is adequate weak axis support (i.e., the posts are part of a sheathed wall), (2) cover plates can be added to increase bending strength and stiffness about axis H-H (figure 7.2), or (3) the bending moment about axis H-H is relatively low or non-existent.

Figure 7.2. Cover plates used to increase the bending capacity of a mechanically laminated post about axis H-H.

Page 76: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

7-5

7.5.5 Bending About Axis V-V. Allowable design stresses for bending of unspliced me-chanically-laminated posts about axis V-V are calculated in accordance with ANSI/ASAE EP559 Design Requirements and Bending Properties for Mechanically Laminated Columns (ASAE, 1999). The procedure outlined in ANSI/ASAE EP559 is identical to procedures outlined in the NDS (AF&PA, 1997a) with the exception of two adjustment factors: the repeti-tive member factor, Cr, and the beam stability factor, CL.

7.5.5.1 Repetitive Member Factor. ANSI/ ASAE EP559 allows the use of the repetitive member factors in Table 7.3 when: (1) each lamination is between 1.5 and 2.0 inches, (2) all laminations have the same depth (face width), (3) faces of adjacent lamina-tions are in contact, (4) the centroid of each lamination is located on the centroidal axis of the post (axis V-V in figure 7.1a), that is, no laminations are offset, (5) all laminations are the same grade and species of lumber, (6) concentrated loads are distributed to the individual laminations by a load distributing element, and (7) the mechanical fasteners joining the individual layers meet the criteria in table 7.4. Note that if one or more of these criteria are not met, the NDS repetitive member factor of 1.15 should be used if it applies.

7.5.5.2 Beam Stability Factor. The beam stability factor, CL, is a function of the slen-derness ratio, RB, which in turn, is a function of: beam thickness, b; depth, d; and effec-tive span length, Le. ANSI/ASAE EP559 states that for mechanically-laminated posts being bent about axis V-V, thickness, b, shall be equated to 60% of the actual post thickness, and depth, d, to the actual face width of a lamination. The effective span length, Le, is a function of the unsupported length, Lu. The unsupported length shall be set equal to the on-center spacing of bracing that keeps the post from buckling laterally.

7.5.5.3 Design Values. Tables 7.5a and 7.5b contain design values for assemblies fabricated from visually graded and machine stress rated dimension lumber, respectively. The design bending stresses have been ad-justed for repetitive member use. They must be further adjusted to account for stability,

wet use, load duration, temperature, and in certain cases, special preservative and fire treatments.

Table 7.3. Repetitive Member Factors*

Number of laminations

3 4 Visually graded 1.35 1.40 Mechanically graded 1.25 1.30 * For mechanically-laminated dimension lumber

assemblies with minimum interlayer shear capacities as specified in Table 7.4. From ANSI/ASAE EP559 (ASAE, 1999).

Table 7.4. Minimum Required Interlayer Shear Capacities*

Nominal face width of lamina-

tions, inches

Minimum required interlayer shear capacity

per interface per unit length of post, lb/in.

6 12 8 15 10 19 12 24

* For unspliced mechanically-laminated posts. From ANSI/ASAE EP559 (ASAE, 1999).

7.5.6 Bending About Axis H-H. When all laminates are the same size, species and grade of lumber, the allowable design bending strength about axis H-H is conservatively taken as the sum of the bending strengths of the individual layers. The bending strength of an individual layer is equated to the product of the “flatwise” section modulus of an individual laminate and the NDS adjusted design bending stress. For flatwise bending, the NDS adjusted design bending stress, Fb’, is equal to tabulated design bending stress, Fb, multiplied by the appropriate flat use factor, a repetitive member factor of 1.15, and all other applicable factors. Note that the beam stability factor is equal to 1.0 for flatwise bending.

Page 77: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

7-6

Table 7.5a Design Values for Unspliced Mechanically-Laminated Posts in Bending About Axis V-V. Extreme Fiber Bending Stress*, psi

Nominal Width of Individual Layers, inches 6 8 10 12

Number of laminations Grade 3. 4. 3. 4. 3. 4. 3. 4.

Modulus of

Elasticity, x 106 psi

Douglas Fir-Larch Sel Str 2540 2640 2350 2440 2150 2230 1960 2030 1.9 No. 1 & Better 2020 2090 1860 1930 1710 1770 1550 1610 1.8 No. 1 1760 1820 1620 1680 1490 1540 1350 1400 1.7 No. 2 1540 1590 1420 1470 1300 1350 1180 1230 1.6 Hem Fir Sel Str 2460 2550 2270 2350 2080 2160 1890 1960 1.6 No. 1 & Better 1840 1910 1700 1760 1560 1620 1420 1470 1.5 No. 1 1670 1730 1540 1600 1410 1460 1280 1330 1.5 No. 2 1490 1550 1380 1430 1260 1310 1150 1190 1.3 Southern Pine Dense Sel Str 3650 3780 3310 3430 2900 3010 2770 2870 1.9 Sel Str 3440 3570 3110 3220 2770 2870 2570 2660 1.8 Non-Dense SS 3170 3290 2840 2940 2500 2590 2360 2450 1.7 Dense No. 1 2360 2450 2230 2310 1960 2030 1820 1890 1.8 No. 1 2230 2310 2030 2100 1760 1820 1690 1750 1.7 Non-Den. No. 1 2030 2100 1820 1890 1620 1680 1550 1610 1.6 Dense No. 2 1960 2030 1790 1960 1620 1680 1550 1610 1.7 No. 2 1690 1750 1620 1690 1420 1470 1320 1370 1.6 Non-Den. No.2 1550 1610 1490 1540 1280 1330 1220 1260 1.4 * For dry posts under normal load duration. Size and repetitive member factors applied. For other appli-

cable modification factors, see NDS (AF&PA, 1997a). Table 7.5b Design Values for Unspliced Mechanically-Laminated Posts in Bending About Axis V-V.

Extreme Fiber Bending Stress*, psi Extreme Fiber Bending Stress*, psiGrade 3 Laminates 4 Laminates

Grade 3 Laminates 4 Laminates

900f-1.0E 1130 1170 1950f-1.5E 2440 2540 900f-1.2E 1130 1170 1950f-1.7E 2440 2540 1200f-1.2E 1500 1560 2100f-1.8E 2630 2730 1200f-1.5E 1500 1560 2250f-1.6E 2810 2930 1350f-1.3E 1690 1760 2250f-1.9E 2810 2930 1350f-1.8E 1690 1760 2400f-1.7E 3000 3120 1450f-1.3E 1810 1890 2400f-2.0E 3000 3120 1500f-1.3E 1880 1950 2550f-2.1E 3190 3320 1500f-1.4E 1880 1950 2700f-2.2E 3380 3510 1500f-1.8E 1880 1950 2850f-2.3E 3560 3710 1650f-1.4E 2060 2150 3000f-2.4E 3750 3900 1650f-1.5E 2060 2150 3150f-2.5E 3940 4100 1800f-1.6E 2250 2340 3300f-2.6E 4130 4290 1800f-2.1E 2250 2340

* For dry posts under normal load duration. Repetitive member factors applied. For other applicable modification factors, see NDS (AF&PA, 1997a).

Page 78: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

7-7

7.5.7 Flexural Rigidity. To calculate deflections due to bending requires that the flexural rigidity of the member be known. The flexural rigidity of a solid-sawn member is equal to its modulus of elasticity times its moment of inertia about the axis it is being bent. The flexural rigidity of an unspliced laminated post when bent around axis V-V is simply equal to the sum of the flexural rigidities of the individual laminates about axis V-V. In other words, the flexural rigidity about axis V-V is not dependent on the properties of the mechanical fasteners. This is not the case with respect to bending about axis H-H. The bending stiffness about axis H-H axis is highly dependent on the shear stiffness of the mechanical connec-tions between the individual laminates. A high bound for flexural rigidity about axis H-H is obtained by assuming complete composite action between layers (no interlayer slip). A lower bound is obtained by assuming no com-posite action (no interlayer connections). In the latter case, the total flexural rigidity is equal to the sum of the flexural rigidities of the individual laminates. Special analysis procedures, such as that developed by Bohnhoff (1992) are available for more accurate estimates of deformation due to bending about axis H-H. Use of these pro-grams requires knowledge of the shear stiffness properties of the mechanical connections. 7.5.8 Compressive Properties. The allowable compressive load for an unspliced mechanically laminated post is typically calculated by treating the individual laminates as discrete columns. This method conservatively assumes no com-posite action between laminates. An allowable compressive stress is first calculated for each laminate for buckling about axis V-V. This allow-able stress is then multiplied by the cross-sectional area of the laminate to obtain an allowable load for buckling about axis V-V. This calculation is repeated for each layer, and the resulting individual laminate loads are summed to obtain a total allowable column load for buck-ling about axis V-V. The entire process is re-peated to obtain a total allowable load for buck-ling about axis H-H. The NDS (AF&PA, 1997a) presents methods for calculating a compressive load capacity that accounts for some composite action; however, connectors used in fastening the laminations must meet criteria outlined in the NDS.

7.5.9 Field Fabrication. A distinct advantage of mechanically-laminated posts is that fabrication can be performed using tools and equipment readily available on the job site. With unspliced posts that will be embedded in the ground, it is common to construct the post so that an interior laminate is left shorter than the surrounding laminates. When the post is installed with this feature located on the top of the post, the truss can be set in the resulting pocket, enabling a double shear connection between the post and truss. The interior laminate is generally signifi-cantly shorter (approximately 1 foot) than needed to accommodate the truss. This is done to compensate for varying depths of embed-ment. After posts are installed, a spacer (or block) of the same cross-sectional size as the shortened laminate is placed in between the shortened laminate and the truss. A schematic of this procedure is shown in Figure 7.3.

Figure 7.3. On-site truss placement in a me-chanically laminated post. 7.6 Spliced Mechanically-Laminated Posts 7.6.1 Types. A spliced post is any post in which at least one laminate contains one or more end-joints (i.e., is comprised of two or more individual pieces of lumber). Major end-joint types used in spliced mechanically-laminated posts include: simple butt joints, reinforced butt joints, and glued finger joints. Butt joints are generally reinforced by pressing metal plate connectors into one or both sides of each joint.

1. Post set, bottom of truss marked, and block height measured

Block Height

2. Truss set on block and bolted into place.

3. Block nailed into place and top of outer layers cut off.

Block

Page 79: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

7-8

Figure 7.4. (a) Treated portions of 3-layer spliced posts are embedded in the soil. (b) Top of treated portions cut so that tops at same elevation. (c) Untreated post portions spliced to treated portions.

7.6.2 Use. Virtually all mechanically-laminated posts with overall lengths exceeding 20 foot are spliced posts. 7.6.3 Advantages. Splicing enables the fabrica-tion of long posts from shorter, less expensive lengths of dimension lumber. Splicing also enables the construction of posts with preserva-tive treated lumber on only one end. This re-duces the quantity of treated lumber used in a building, which in turn reduces the number of special corrosion-resistant fasteners needed to join treated lumber. With simple butt joints, the attachment of non-treated lumber to treated lumber is sometimes done in the field. This attachment is done after the treated pieces have been laminated and embedded in the ground (figure 7.4a). Prior to attaching the untreated top-portion of each post, the embedded treated portions are all cut so that their tops are at the same elevations (note: because of differing depths-of-embedment, the top of each embedded section is generally at a different height above grade). With the embed-ded portions at the same elevation (figure 7.4b),

the upper portions will have the same overall length (figure 7.4c). This eliminates cutting and blocking like that associated with the special construction shown in figure 7.3. 7.6.4 Disadvantages. Spliced mechanically-laminated posts have the same disadvantages as unspliced mechanically-laminated posts (see Section 7.5.4). In addition, a simple (non-reinforced) butt joint can significantly reduce bending strength and stiffness in the vicinity of the joint. If a post contains a simple butt joint in each laminate, and these joints are all located within 1 or 2 feet of each other, engineers will often model that portion of the post as a hinge connection. 7.6.5 Design Properties. Design properties for spliced mechanically-laminated posts are highly dependent on the type and relative location of end joints, and on the type and relative location of mechanical fasteners, especially those lo-cated in the vicinity of end joints. Procedures for designing and determining the bending strength and stiffness of spliced nail-laminated posts are outlined in ANSI/ASAE EP559 (ASAE, 1999).

(a) (b) (c)

Level line of sight

Page 80: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

7-9

The design portion of EP559 includes require-ments for joint arrangement, overall splice length, nail strength, nail density, nail diameter, and nail location. If these design requirements are followed, the bending strength and stiffness of the nail-laminated post can be calculated using the equations in the EP. It is important to note that the intent of the EP559 design re-quirements is to maximize the bending strength of the splice region, while minimizing overall splice length. Overall splice length is defined as the distance between the two farthest removed end joints in a post that contains one end joint in each laminate. Reducing overall splice length generally reduces the amount of preservative treated lumber used in a post. 7.6.6 Laboratory Tests. Engineers must gen-erally rely on laboratory tests to determine design properties for spliced posts that do not meet the design requirements of ANSI/ASAE EP559. In recognition of this, a laboratory test procedure specifically for spliced mechanically laminated posts is outlined in ANSI/ASAE EP559. 7.6.7 Computer Modeling. Discontinuities at butt joints result in a post with a varying bending stiffness along its length. If the overall splice length is rather short (i.e., all joints are located within a distance equal to 1/4th the post length), the post is generally sectioned into three ele-ments for computer frame analysis: a middle element that contains all the joints, and two “joint-free” outer elements. The joint-free ele-ments are treated like unspliced mechanically-laminated posts with flexural rigidities calculated as described in Section 7.5.7. The element containing the joints is assigned an effective flexural rigidity that will cause it to deform like actual laboratory tested posts. A procedure for “backing-out” an effective flexural rigidity from bending test data is given in ANSI/ASAE EP559. The EP also contains an equation for calculating the flexural rigidity of the splice region of any nail-laminated post that meets the design re-quirements of the EP. 7.7 References American Forest and Paper Association (AF&PA). 1997a. National Design Specifications for Wood Construction (NDS). American Forest and Paper Association, Washington, D.C.

American Forest and Paper Association (AF&PA). 1997b. NDS Supplement - Design values for wood construction. American Forest and Paper Association, Washington, D.C. American Institute of Timber Construction (AITC). 1983. Structural glued laminated timber. ANSI/AITC A190.1-1983. Englewood, CO. American Institute of Timber Construction (AITC). 1985. Design standard specifications for structural glued laminated timber of softwood species. AITC 117.85. Englewood, CO. American Institute of Timber Construction (AITC). 1988. Manufacturing standard specifica-tions for structural glued laminated timber of softwood species. AITC 117.88. Englewood, CO. ASAE. 1999. ANSI/ASAE EP559: Design re-quirements and bending properties for mechani-cally laminated columns. ASAE Standards, 46th edition. ASAE, St. Joseph, MI. Bohnhoff, D.R. 1992. Modeling horizontally nail-laminated beams. ASCE Journal of Strucutral Engineering 118(5):1393-1406.

Page 81: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

7-10

Page 82: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 1

Chapter 8 - POST FOUNDATION DESIGN 8.1 Introduction 8.1.1 General. A distinct advantage of post-frame construction is the opportunity to transfer structural loads to the soil via embedded posts, thereby eliminating the need for a traditional foundation. 8.1.2 Post Loads. Post loads (i.e., structurally induced shear, bending moment and axial loads) are obtained using procedures presented in Chapter 5. Most post foundation design equa-tions require that post loads be specified at the ground surface. 8.1.3 Post Foundation Classification. Based on their depth, post foundations are categorized as shallow foundations. Shallow foundations exhibit behavior quite different from that of deeper systems such as pilings. Specifically, post deformation below grade is relatively insig-nificant compared to the deformation of the soil around the post. Soil deformation around a post is a three-dimensional phenomena. Figure 8.1 shows the lines of constant soil pressure (in a horizontal plane of soil) that form when a post moves laterally. The greater the distance be-tween two posts, the less influence one post will have on the soil pressure near the other. For design purposes, individual embedded posts are considered isolated foundations when post spacing is six times greater than post width. Higher allowable lateral soil bearing pressures are justified for a foundation featuring isolated posts instead of a continuous foundation wall. 8.1.4 Design Variables. Factors that influence the strength and stiffness of a post foundation include: embedment depth, post constraint (Sec-tion 8.2), soil properties (Section 8.3), footing size (Section 8.4), collar size (Section 8.5), backfill properties (Section 8.6), and post di-mensions (Section 8.7). 8.1.5 Design Guides. The first design manual for post foundations was originally published by the American Wood Preservers Institute (Patter-son, 1969). The basic design approach and guidelines for post embedment analysis have been accepted by several major building codes.

The most comprehensive current design guide-line is ASAE EP486 (ASAE, 1999a). The mate-rial in this chapter is largely based on this engi-neering practice.

Figure 8.1. Constant Pressure Lines in a Hori-zontal Plane of Soil. 8.2 Post Constraint 8.2.1 Nonconstrained Post. The most basic type of post foundation consists of a post simply embedded in the ground, with no attachments or additional support (figure 8.2). If the rotation and lateral displacement of the post are resisted solely by the soil, the post foundation is said to be non-constrained. 8.2.2 Constrained Post. If a post bears on (or is attached to) an additional “immovable” struc-tural element such that the lateral displacement at some point at or above the ground surface is essentially equal to zero, the post foundation is said to be constrained. An example of a con-strained post foundation would be when the post is installed immediately adjacent to a concrete slab floor in the building (figure 8.3).

CLB/2 B/2

1.0B 1.0B1.5B 1.5B2.0B 2.0B

2.0B

1.5B

1.0B

0.5B

2.5B

3.0B

3.5B

0.1q

0.2q

0.3q

0.4q0.5q

0.7q

0.6q

0.8q

0.9q

q

Post

Page 83: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 2

8.2.3 Varying Constraint. It is important to note that a single post can be both constrained or non-constrained, depending on the load case. Using the previous example of a slab floor, and assuming that the post is not attached to the slab, if the wind loading was such that the post

was pushing on the slab, the post would be con-sidered constrained. However, if the wind were blowing in the opposite direction, the post would not be supported by the slab; hence, the post would be analyzed for that load case as non-constrained.

Figure 8.2. Free body diagrams of non-constrained post foundations. Load Case A: groundline shear and moment both cause clockwise rotation of embedded portion of post. Load Case B: groundline shear and moment cause clockwise and counter clock-wise rotation, respectively, of embedded portion of post.

Figure 8.3. Free body diagram of a constrained post foundation.

Ma

Va

Footing

Post

Ground Level

d

Soil Forces

Floor

R

Resultant Soil Force

Footing

Rotation Axis

Post

Ground Level

d

do

Soil Forces

Ma

Va

Resultant Soil Force

Resultant Soil Force

Footing

Rotation Axis

Ground Level

d

do

Ma

Va

LOAD CASE BLOAD CASE A

Page 84: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 3

8.3 Soil Properties 8.3.1 General. The capability of a soil to handle loads transmitted to it by a post depend on such characteristics as: particle size and size distribu-tion (a.k.a. soil classification), moisture content, density, and depth below grade. These soil characteristics control the allowable vertical and lateral soil pressures. 8.3.2 Soil Classification. Soil is classified by the size of individual particles and the distribu-tion of sizes within the sample. There are four major particle (grain) sizes: gravel, sand, silt, and clay. The most popular classification system in the U.S. (i.e., the Unified Soil Classification (USC) system) classifies gravels as grains be-tween 0.2 and 3.0 inches, sands as particles between 0.003 and 0.2 inches, silts as grains between 0.003 and 0.00008 inches, and clays as all particles finer than 0.00008 inches. The distribution of these particles within a given soil has a major impact of soil behavior. A soil with a wide distribution of particle sizes is referred to as a well-graded soil. A poorly graded soil is comprised of similar sized particles. The best soils for foundation design are gravels and sands, with well-graded gravels and sands, bet-ter than poorly graded gravels and sands. Or-ganic silt, peat and soft clay soils are not suit-able for post foundations, as they have neither the strength nor the stability to support structural loads. 8.3.3 Soil Moisture Content. The effective shear strength of a soil can be reduced signifi-cantly when soil is allowed to saturate with wa-ter. To avoid water saturation of soils around posts, install rain gutters, and slope the finish grade away from the building. A minimum 2% slope for a distance of at least 6 ft (2 m) from the building walls is recommended. 8.3.4 Soil Density and Depth. Allowable verti-cal and lateral soil pressures increase with in-creases in soil density and depth. This is be-cause soil confinement pressures increase as both of these variables increase. 8.3.5 Tabulated Design Values. Table 8.1

contains soil properties as tabulated in ASAE are referred to as presumptive values and should only be used if there is no active building code in effect, and site-specific soil properties are unavailable. The vertical soil pressures given in table 8.1 are for the first foot (300 mm) of footing width and first foot below grade. A twenty percent increase in allowable soil pressure is allowed for each additional foot (300 mm) of foundation width or depth, up to a maximum of three times the origi-nal value. The lateral soil pressure values in table 8.1 are per unit depth. To obtain the allowable lateral pressure at a point below grade, SL, multiple the lateral soil pressure value, S, by the distance below grade of the point in question. For exam-ple, the lateral pressure per unit depth, S, for a firm sandy gravel is 300 lbm/ft2 per foot of depth. This equates to an allowable pressure of 1200 lbf/ft2 (4 ft x 300 lbm/ft2 per ft x 1lbf/lbm) for points four feet below grade. [Note: use of variable SL to represent S when adjusted for depth, is unique to this design manual, and is done to avoid confusion between values that have and have not been adjusted for depth. It is important to realize that SL and S have different units.] 8.3.6 Soil Tests. Site-specific soil test results are often used to determine allowable soil pres-sures. Such calculations generally result in higher allowable design values than would be obtained using table 8.1. This is because pre-sumptive values are the lowest values associ-ated with a broad classification of soils, each at their minimum strength conditions. 8.3.7 Soil Sampling. Soil samples should be gathered from the applicable location in the soil profile: one-third the foundation depth for lateral soil pressure calculations for non-constrained posts; and at footing depth for lateral soil pres-sure calculations for constrained posts and for vertical soil pressure calculations. From each soil sample, the cohesion, c, angle of internal friction φ, and bulk density, w, must be deter-mined.

Page 85: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 4

Table 8.1. Presumed Soil Properties for Post Foundation Design (ASAE, 1999). For use in ab-sence of codes or test.

Lateral Pressure Per Unit Depth, S

Vertical Pressure, Sv ↓ Density, w ±

Class of Material

Density or Con-sistency

← lbf/ft2 per ft

kPa per m

Lateral Sliding Coeffi-cient → lbf/ft2 kPa

Friction Angle,

degrees ° lbm/ft2 kg/m3

1. Massive crystalline bedrock - 1200 180 0.79 4000 200 - - -

2. Sedimentary and foliated rock - 400 60 0.35 2000 100 - - -

3. firm 300 45 - - - 38 120 2000

Sandy gravel and/or gravel (GW and GP) loose 200 30 0.35 2000 100 32 90 1500

4. firm 200 30 - - - 30 105 1750

Sand, silty sand, clayey sand, silty gravel and clayey gravel (SW, SP, SM, SC, GM, and GC) loose 150 22.5 0.25 1500 75 26 85 1400

5. medium 130 20 ″ - - 15 120 2000

Clay, sandy clay, silty clay and clayey silt (CL, ML, MH and CH) soft 100 15 - 1000 50 10 90 1500

← Firm consistency of class 4 and the medium consistency of class 5 can be molded by strong finger pressure, and the firm con-

sistency of class 3 is too compact to be excavated with a shovel. ↑ The hydrostatic increase in lateral pressure per unit depth has been included in the equations of this chapter. Source: Table 29-

B UBC modified with the addition of firm and medium values from Hough (1969). → Sliding resistance source: Table 29-B UBC. ↓ Allowable foundation pressures are for footings at least 1 ft (300 mm) wide and 1 ft (300 mm) deep into natural grade. Pressure

may be increased 20% for each additional 1 ft (300 mm) of width and/or depth to a maximum of three times the tabulated value. Source: Table 29-B UBC.

° Soil friction angle varies from soft to medium density for clay materials, and from loose to firm for sand and gravel materials. Source: Merritt (1976).

± Soil density varies from soft to medium density for clay materials, and from loose to firm for sand and gravel materials. Source: Hough(1969).

″ Multiply an assumed lateral sliding resistance of 130 lbf/ft2 (6 kPa) by the contact area. Use the lesser of the lateral sliding resis-tance and one-half the dead load.

8.3.8 Allowable Vertical Soil Pressure From Soil Test Data. The allowable vertical soil pressure for round or square footings, Sv, can be estimated from site-specific soil test as: Sv = SBC / FS (8-1) where: Sv = allowable vertical soil pressure,

lbf/ft2 (kPa) FS = factor of safety (2.3 to 3.0) SBC = ultimate soil bearing capacity, lbf/ft2

(kPa) SBC = 0.6 g w b (Nq + 1) tan φ + (Nq - 1+ Nq tan φ)(g w y + c/tanφ) (8-2) Nq = eπ tanφ tan2(φ/2 + 45)

c = soil cohesion, lbf/ft2 (Pa) φ = soil angle of internal friction, de-

grees w = soil bulk density, lbm/ft3 (kg/m3) g = gravitational constant, 1 lbf/lbm

(0.00981 kPa m2/kg) y = depth where soil allowable pressure

is calculated, ft (m) b = footing diameter or length of one

side, ft (m) For shallow foundations, a factor of safety be-tween 2.3 and 3.0 is typically applied to vertical soil pressure (Whitlow, 1995). Equation 8.2 is a modified Terzaghi-Meyerhoff equation taken from Whitlow (1995). Values compiled in table 8.2 can be used to facilitate calculation of the ultimate soil bearing capacity, SBC.

Page 86: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 5

Table 8.2. Ultimate Bearing Capacity* SBC = 0.6 w b T1 +

T2(w y + c T3) φ deg. Nq

T1 T2 T3 10 2.471 0.612 1.907 5.671 12 2.974 0.845 2.606 4.705 14 3.586 1.143 3.480 4.011 16 4.335 1.530 4.578 3.487 18 5.258 2.033 5.966 3.078 20 6.399 2.693 7.729 2.747 22 7.821 3.564 9.981 2.475 24 9.603 4.721 12.879 2.246 26 11.854 6.269 16.636 2.050 28 14.720 8.358 21.547 1.881 30 18.401 11.201 28.025 1.732 32 23.177 15.107 36.659 1.600 34 29.440 20.532 48.297 1.483 36 37.752 28.155 64.181 1.376 38 48.933 39.012 86.164 1.280 40 64.195 54.705 117.061 1.192 42 85.374 77.771 161.244 1.111 44 115.308 112.317 225.659 1.036 46 158.502 165.169 321.635 0.966 50 319.057 381.429 698.295 0.839

* See Equation 8.2 for variable descriptions. 8.3.9 Allowable Lateral Soil Pressure From Soil Test Data. The allowable lateral pressure per foot of depth, S, can be estimated from site-specific soil test data as: S = SRP / FS (8-3) where: S = allowable lateral soil pressure, lbf/ft2

per ft, (kPa per m) FS = factor of safety (1.5 to 2.0) SRP = Rankine passive pressure for

drained, cohesiveless soils, lbf/ft2 per ft, (kPa per m).

SRP = w g tan2(45 + φ/2) (8-4) w = soil bulk density, lbm/ft3 (kg/m3) φ = soil angle of internal friction, de-

grees g = gravitational constant, 1 lbf/lbm

(0.00981 kPa m2/kg)

For lateral earth pressures in drained soils, a factor of safety between 1.5 and 2.0 is typical (Whitlow, 1995). Equation 8-2 assumes drained soils (i.e., the water table is located below the top of the footing). Equation 8-2 does not ac-count for soil cohesion, therefore the equation is conservative for clays. Values for the Rankine passive pressure are given in table 8.3. Table 8.3. Rankine Passive Soil Pressures for Drained, Cohesiveless Soils

SRP, lbf/ft2 per ft Soil Density, lbm/ft3 φ

deg. 95 100 105 110 115 120

10 135 142 149 156 163 170 12 145 152 160 168 175 183 14 156 164 172 180 188 197 16 167 176 185 194 203 211 18 180 189 199 208 218 227 20 194 204 214 224 235 245 22 209 220 231 242 253 264 24 225 237 249 261 273 285 26 243 256 269 282 295 307 28 263 277 291 305 319 332 30 285 300 315 330 345 360 32 309 325 342 358 374 391 34 336 354 371 389 407 424 36 366 385 404 424 443 462 38 399 420 441 462 483 504 40 437 460 483 506 529 552 42 479 504 530 555 580 605 44 527 555 583 611 638 666 46 582 613 643 674 704 735 50 717 755 793 830 868 906

8.3.10 Adjustment to Allowable Vertical Pressure. Most codes allow for a 33% increase in the allowable vertical pressure values, Sv, when post loads result from wind and seismic forces acting alone or in combination with verti-cal forces (see Section 3.9.4). This adjustment would apply directly to the Sv value from equa-tion 8-1, and is cumulative with the adjustments described in Section 8.3.5 for the presumptive Sv values listed in table 8.1. In this manual, a prime (‘) will be used to denote an allowable Sv value that has been adjusted (i.e., Sv Sv’). 8.3.11 Adjustment to Allowable Lateral Pressure. In addition to the 33% increase gen-erally allowed when post loads result from wind

Page 87: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 6

and seismic forces (acting alone or in combina-tion with vertical forces), the allowable lateral pressure, S, can be doubled when posts have a spacing at least six times their width. This in-crease is due to the multi-dimensional nature of pressure distribution in the soil around isolated posts as depicted in figure 8.1, and described in Section 8.1.3. In this manual, a prime (‘) will be used to denote an allowable S value that has been adjusted (i.e., S S’). 8.4 Footings 8.4.1 General. Typically, the soil is not able to resist applied vertical loads when those loads are transferred through the post alone. There-fore, the post is set on some type of footing, which is installed in the hole prior to post place-ment. Footings in post-frame construction are usually poured concrete. This type of footing is depicted in Figure 8.4. Generally there is no mechanical attachment of the footing to the post. 8.4.2 Friction. A footing is assumed to only re-sist vertical loads; the friction between the foot-ing and the post is assumed to be negligible

when assessing the post lateral load resistance capabilities. Also, the friction between the post (and/or collar) and the surrounding soil are as-sumed to be negligible when assessing the ver-tical load-carrying capability of a given post foundation design. 8.5 Collars 8.5.1 General. When lateral soil pressures ex-ceed allowable values, additional lateral surface area can be obtained by increasing post depth, or by adding a structural element called a collar. A collar is typically either concrete cast around the base of the post (and considered to be at-tached to the post) or built-up wood attached to the post. These structural elements are repre-sented in figure 8.4. 8.5.2 Location. The collar increases the lateral load resistance capability of the post foundation by increasing the bearing area in the region of the post where lateral soil capability is relatively high. Collars are typically not placed at the top of the post foundation (at the surface of the ground) due to the possibility of frost heave.

Figure 8.4. Examples of common post foundation elements with (a) a poured concrete collar, and (b) a built-up wood collar.

Ground level

Post

Original excavated post hole and backfill region

Poured concrete collar

Built-up wood collar

Footing

(a) (b)

Page 88: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 7

8.5.3 Attachment. Whether poured concrete or wood, the collar must be attached to the post in a manner sufficient to carry the structural loads involved. As with any wood structural element exposed directly to the soil, appropriate pre-servatives and fastener systems must be em-ployed to maintain structural integrity over the design life of the building. 8.6 Backfilling 8.6.1 General. The details of backfilling are of-ten overlooked by the designer, and with poten-tially dire consequences. After the footing and post are installed (and the collar, if required), the hole that was dug or drilled is backfilled. Essen-tially, the material used for backfill is the medium through which some, if not all, transverse loads are passed from the post to the virgin soil. Back-fill material is subjected to higher pressures than the surrounding virgin soil due to its proximity to the post. Therefore, material used for backfill and its installation are critically important for the successful performance of a post foundation design. 8.6.2 Materials. Typical materials for backfill include concrete, well-graded granular aggre-gate, gravel, sand, or soil initially excavated from the post hole. These alternatives are listed in the order of decreasing stiffness. 8.6.3 Concrete. While concrete is the stiffest backfill material, it is also the most expensive. Concrete backfill essentially increases post width, b. It must be installed with attention to the possibility of frost heave (discussed later). 8.6.4 Excavated Soil. The most common back-fill material is the excavated soil. If used as backfill, it should be free of topsoil and organic matter. Silt- or clay-based soils should be moist (not wet) and well packed. 8.6.5 Compaction. Backfill materials should be tamped or vibrated upon backfill in maximum layers (a.k.a. lifts) of 8 inch (400 mm). 8.7 Post Dimensions 8.7.1 Effective Width. Design equations for lateral loading (Section 8.7) are a function of

effective post width, b, which in turn, is a func-tion of post size and shape. For posts whose narrow face is pushing on the soil: b = 1.4 B (8-5) where: b = effective post width, ft (m) B = width of post face pushing on the

soil, ft (m) For posts whose wide face is pushing on the soil, b is equal to the diagonal dimension of the post. For poles, the effective post width, b, is equal to the pole diameter. 8.7 Design for Lateral Loadings 8.7.1 General. Bending moments and post shears cause lateral movement of the post foundation. Designers must insure that this movement does not induce soil stresses that exceed allowable lateral soil pressures. If the allowable lateral soil pressure is exceeded, the designer must increase the lateral soil bearing area by adding a collar, by increasing embed-ment depth, d, and/or by increasing effective post width, b. In the majority of cases, the most economical way to increase bearing area is to increase post depth. For this reason, embed-ment depth, d, is the dependent variable in most design equations. Occasionally a designer will add an extra laminate to the embedded portion of a laminated post to increase effective width. More often, designers will backfill all or a portion of the hole with concrete, which is akin to adding a concrete collar. 8.7.2 Assumptions. Equations in 8.7.3 and 8.7.4 assume that only the post (and not the footing) resists lateral loads. This is because variations in vertical post loads make it impossi-ble to rely on post-to-footing friction for lateral load resistance. 8.7.3 Required Embedment Depth for Non-Constrained Posts Without Collars. Two dif-ferent load cases for a non-constrained, non-collared post are shown in figure 8.2: The first

Page 89: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 8

load case (a.k.a. Load Case A ) represents con-ditions where groundline shear and groundline bending moment both cause the embedded por-tion of the post to rotate in the same direction. Load Case B represents conditions where groundline bending moment causes the embed-ded portion of the post to rotate in an opposite direction than the rotation caused by groundline shear. Minimum post embedment depth, d, for both Load Case A & B is calculated using one of the following equations. From ASAE EP486 (1999a), AWPI (Patterson, 1969), and the UBC (ICBO, 1994):

7.02 Va + 7.65 Ma / d

d 2 = S’ b (8-6)

From ASAE EP486.2 (1999b):

6 Va + 8 Ma / d

d 2 = S’ b (8-7)

where: d = minimum embedment depth, ft (m) Va = shear force applied to foundation at

ground surface, lbf (N) Ma = bending moment applied to founda-

tion at ground surface, ft-lbf (N-m) S’ = adjusted allowable lateral soil pres-

sure, lbf/ft per ft (kPa/m per m) b = effective post width, ft (m), see Sec-

tion 8.7.1 Equations 8-6 and 8-7 must be solved by itera-tion. For Load Case B, Va and Ma must be input with opposing signs. Note that equation 8-6 is in a slightly different form than appears in any of the three referenced documents. See the follow-ing technical note on equation development for additional information. Technical Note Non-Constrained Post Equations Equation 8-6 for the embedment depth, d, of non-constrained, non-collared posts appears in most code documents as: d = 0.5 A [1 + (1 + 4.36 h / A)1/2] (T-1)

where: A = 2.34 P / (SL’ b) b = effective post width, ft (m) d = post embedment depth, ft (m) P = applied lateral force, lbf (N) h = distance from ground surface to

point of application of force P, ft (m) SL’ = adjusted allowable lateral soil pres-

sure at one-third the embedment depth, lbf/ft2 (kPa)

Equation T-1 was developed for point-loaded posts that behave as pure cantilevered beams. Unfortunately, posts in post-frame buildings are not point-loaded, and embedded posts are sup-ported in such a way that they behave more like propped cantilevers. To adjust equation T-1 so that it can be applied to posts subjected to a variety of loadings and “above-grade” constraint conditions, load P is replaced with an equivalent shear force and bending moment located at the ground surface. Using predefined nomenclature: Va is substi-tuted into equation T-1 for P, and Ma is substi-tuted for the product of P and h. In addition, the adjusted allowable lateral soil pressure at one-third the embedment depth, SL’, is replaced by the quantity S’ d / 3. This substitution eliminates having to recalculate SL’ every time the embed-ment depth changes. With these substitutions, equation T-1 appears in ASAE EP486 (1999a) as: d 2 = 3.51Va/(S’ b)[1+(1+(0.62 Ma S’ b d)/ Va

2)1/2] Because it is somewhat confusing, the ASAE EP486 equation was rewritten for this design manual in the form of Equation 8-6. The first major revision to ASAE EP486 (due for release in 2000) will contain several changes, including a switch from equation 8-6 to equation 8-7. Equation 8-7 is based on five common as-sumptions: (1) only the post (and not the footing) resists lateral loads, (2) the post behaves as a rigid body below grade (3) soil type remains constant, (4) at a given depth, soil resisting pressure, q, is equal to the product of soil stiff-ness, k, and lateral post movement at that depth, and (5) soil stiffness, k, at a distance, y,

Page 90: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 9

below grade is equal to the product of the hori-zontal subgrade reaction, nh, and the distance below grade, y. In equation form, the soil resist-ing pressure, q, for a non-constrained, non-collared post is given by Meador (1997) as: q = nh ∆ (y – y2/do) (T-2) where: q = actual soil pressure at a depth y

below grade, lbf/ft2 (kPa) nh = constant of horizontal subgrade re-

action, lbf/ft4 (N/m4) ∆ = lateral post deflection at grade, ft

(m) y = depth below grade, ft (m) do = distance from surface to point of

post rotation in soil, ft (m), (see fig-ure 8.2)

Equation T-2 is a parabolic function that pro-duces the soil pressure profile shown in figure 8.2. If a summation of the horizontal forces in figure 8.2 is set equal to zero, and the bending moment around any point is equated to zero, the following two equations can be obtained for the grade deflection ∆, and distance to post rotation point, do. ∆ = (24 Ma + 18 Va d)/(d 3 nh b) (T-3) do = (3 Va d + 4 Ma)/(4 Va + 6 Ma /d) (T-4) Examination of equation T-4 shows that the point of post rotation is two-thirds the embed-ment depth when there is no shear in the post at the ground surface (Va = 0). When there is no moment in the post at the ground surface (Ma = 0), the point of post rotation is located at three-quarters of the embedment depth. If both Va and Ma are positive and non-zero, the point of rota-tion is between two-thirds and three-fourths of the embedment depth. Substitution of equation T-3 into equation T-2 yields the following equation for soil pressure: q = (18 Va + 24 Ma/d)(y – y 2/do)/(d 2 b) (T-5) Typically, a designer selects a value for d, such that for all points below the surface, the actual

soil pressure, q, does not exceed the adjusted allowable lateral soil pressure, SL’ = S’ y. It can be shown that every time a designer does this, the depth at which the actual soil pressure is closest to the allowable pressure is right at the surface. In other words, for a non-constrained post, the designer does not need to compare S’ y and q from equation T-5 at every value of y, instead, the designer only needs to check it at y = 0. It follows that the embedment depth, d, needed to ensure that the actual soil pressure does not exceed the allowable soil pressure at the surface (or any point below the surface) is given as: d 2 = (18 Va + 24 Ma / d )/(S’ b) (T-6) Equation T-6 is not used in practice as field and laboratory tests have shown that it is extremely conservative for non-constrained posts. This is because when actual soil pressures at the sur-face equal the allowable soil pressure, the ac-tual soil pressure at points below the surface are below (and in most cases substantially below) allowable soil pressures. Consequently, non-constrained post foundations are no where near failure when allowable soil pressures near the surface are exceeded. A more realistic embed-ment depth is obtained by replacing S’ in equa-tion T-6 with 3S’. The resulting equation is equa-tion 8-7. Note that when this equation is used, actual soil pressure will exceed allowable soil pressure for points between y = 0 and y = 2do/3, and for points deeper than y = 4do/3. For an in-depth discussion and greater detail on non-constrained post foundation equation de-velopment see Meador (1997). 8.7.4 Required Embedment Depth for Con-strained Posts Without Collars. A free body diagram of a constrained, non-collared post is shown in figure 8.3. Minimum post embedment depth, d, for the constrained, non-collared case is calculated using one of the following equa-tions. From ASAE EP486 (1999a), AWPI (Patterson, 1969), and the UBC (ICBO, 1994):

4.25 Ma1/3

d = S’ b (8-8)

Page 91: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 10

From ASAE EP486.2 (1999b):

4 Ma 1/3 d = S’ b (8-9)

where: d = minimum embedment depth, ft (m) Ma = bending moment applied to founda-

tion at ground surface, ft-lbf (N-m) S’ = adjusted allowable lateral soil pres-

sure, lbf/ft per ft (kPa/m per m) b = effective post width, ft (m), see Sec-

tion 8.7.1 Note that equation 8-8 is in a slightly different form than appears in any of the three referenced documents. See the following technical note on equation development for additional information.

Technical Note Constrained Post Equations Equation 8-8 for the embedment depth, d, of constrained, non-collared posts appears in most code documents as: d = [4.25 P h / (SL’ b)]1/2 (T-1) where: d = post embedment depth, ft (m) P = applied lateral force, lbf (N) h = distance from ground surface to

point of application of force P, ft (m) SL’ = adjusted allowable lateral soil pres-

sure at the full embedment depth, lbf/ft2 (kPa)

b = effective post width, ft (m) Equation 8-8 is derived from equation T-1 by substituting bending moment, Ma, for the product of P and h, and replacing SL’ with the quantity S’d. This latter substitution eliminates having to recalculate SL’ every time the embedment depth changes. As described in the previous technical note on non-constrained posts, the first major revision to ASAE EP486 will contain several changes. One

of these is a switch from equation 8-8 to equa-tion 8-9. Equation 8-9 is based on the same as-sumptions as described for equation 8-7. These assumptions result in the following equation for actual soil resisting pressure, q, for a con-strained, non-collared post (Meador, 1997): q = nh y2 ∆ / d (T-2) where: q = actual soil pressure at a depth y

below grade, lbf/ft2 (kPa) nh = constant of horizontal subgrade re-

action, lbf/ft4 (N/m4) ∆ = lateral movement of post at a depth

y = d, ft (m) y = depth below grade, ft (m) Equation T-2 is a parabolic function that pro-duces the soil pressure profile shown in figure 8.3. If the bending moment around any point in figure 8.3 is equated to zero, the following equa-tion is obtained for the lateral movement, ∆, of the post at a depth, d. ∆ = 4 Ma /(d 3 nh b) (T-3) Substitution of equation T-3 into equation T-2 yields the following equation for soil pressure: q = 4 Ma y 2/(d 4 b) (T-4) The actual soil pressure increases at an increas-ing rate as y increases. The allowable lateral soil pressure, SL’, increases at a constant rate as y increases (note: SL’ = S’ y). This means that if a designer ensures that the actual soil pres-sure, q does not exceed the allowable pressure at a depth, y = d, then the actual stress will be less than the allowable for all points between the ground surface and y = d. In equation form: S’ y > q = 4 Ma y 2/(d 4 b) for y = d (T-5) Equation T-5 becomes equation 8.9 after it is rearranged so that d is the dependent variable. For an in-depth discussion and greater detail on constrained post foundation equation develop-ment see Meador (1997).

Page 92: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 11

8.7.5 Required Embedment Depth for Posts With Collars. This design manual does not con-tain embedment equations for posts with collars. For such equations, see ASAE EP486 (1999a, 1999b) and Meador (1997). 8.8 Design for Downward Loadings 8.8.1 Required Footing Area. Downward forces are resisted by the footing. The footing area, A, required to resist these forces is: A = P / SV’ (8-10) where: A = required footing area, ft2 (m2) P = vertical foundation load, lbf (N) SV’ = adjusted allowable vertical soil

pressure, lbf/ft2 (kPa) (see Section 8.3.10)

8.9 Design for Uplift Loadings 8.9.1 General. If the net vertical force acting on a post is upward, either the footing or a collar must be attached to the post. When the footing or a collar is attached to the post, upward movement of the post foundation cannot occur without displacing a cone-shaped mass of soil. The mass of this of soil depends on foundation depth, footing (or collar) size, soil density, and soil internal friction angle. 8.9.2 Skin Friction. An attached footing or col-lar is required to resist uplift forces because skin friction between a post and backfill cannot be relied on to resist such forces. 8.9.3 Concrete Backfill. Concrete cast against undisturbed soil and mechanically fastened to the post adds uplift resistance of both the con-crete mass and the skin friction between the concrete and soil. Note that this practice is not recommended in soils with a high susceptibility to frost heave 8.9.4 Volume of Displaced Soil. The volume of soil that must be displaced when pushed up-ward by a footing or collar is dependent on the shape of the footing or collar. Figures 8.5 and 8.6 show configurations for circular and rectan-gular foundation elements, respectively.

Figure 8.5. Schematic of relevant uplift resis-tance components for post foundation with an attached circular collar.

Figure 8.6. Schematic of relevant uplift resis-tance components for post foundation with an attached rectangular collar.

φ dT

Ground Level

Post

Ap

Collar

Footing

r / tan φ

2r

dT

l2l1

Ground Level

Post

AP

Collar

Unattached Footing

φ

Page 93: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 12

The volume of displaced soil, VS, is calculated using the following equations: For circular footings and collars: VS = π dT [r 2 + dT r tanφ + dT

2 tan2φ / 3] – dT Ap For rectangular footings and collars: VS = dT (l1 l2 - Ap) + dT

2 tanφ (l1 + l2) + dT 3π tan2φ / 3 where: VS = volume of displaced soil, ft3 (m3) dT = distance from ground surface to top

of collar, or to top of footing if collar is not present, ft (m)

r = radius of collar, or footing if collar is not present, ft (m)

φ = angle of internal soil friction Ap = post cross-sectional area, ft2 (m2) l1, l2 = length and width of a rectangular

collar or footing, ft (m) 8.9.5 Uplift Resistance, U. The resistance to uplift, U, is calculated as: U = g ( MF+ w VS ) (8-11) where: U = uplift resisting force, lbf (N) MF = mass of all foundation elements that

are attached to the post, lbm (kg) w = soil density, lbm/ft3 (kg/m3) dT = distance from ground surface to top

of collar, or to top of footing if collar is not present, ft (m)

VS = volume of displaced soil, ft3 (m3) g = gravitational constant, 1 lbf/lbm

(9.81 N/kg) 8.10 Frost Heave Considerations 8.10.1 General. Freezing temperatures in the soil result in the formation of ice lenses in the spaces (a.k.a. pores) between soil particles. Under the right conditions, these ice lenses will continue to attract water and increase in size. This expansion of the ice lenses increases soil volume. If this expansion occurs under a footing, or alongside a foundation element with a rough surface, that portion of the foundation will be

forced upward. 8.10.2 Problems. Frost heave can induce large differential movements in the foundation. This differential movement can crack building finishes, and induce significant stress in struc-tural connections and components. When ice lenses thaw, soil moisture content increases dramatically. The soil is generally in a saturated state with reduced strength. As soil water drains from the soil, effective soil stresses increase and the foundation will generally settle. 8.10.3 Minimizing Frost Heave. Frost heave can be minimized by: (1) avoiding clays and silts, (2) extending footings below the frost line, and (3) providing good drainage.

8.10.3.1 No Silts and Clays. Fine grained soils such as clays and silts are more sus-ceptible to frost heave because (1) water is drawn upward by the fine pores which func-tion as capillaries, and (2) there is much more surface area in a unit volume of fine grained soil, and therefore more surface area for water adsoprtion. 8.10.3.2 Footing Depth. The most sure fire way to avoid frost heave problems is to locate the footing where water never freeze. It is for this reason that codes require foun-dations to be located below the frost line. Exceptions include footings on rock and floating foundation systems. A floating foun-dation is reinforced so that it can float as a monolithic unit as the soil swells and shrinks. 8.10.3.3 Water Drainage. Proper surface and subsurface drainage can reduce frost heave. Drainage of surface waters from a builder is enhanced by installing rain gutters, adequately sloping the finish grade away from the building, and raising the building elevation to a level above that of the sur-rounding area. Subsurface drainage is achieved with the placement of drain tile or coarse granular material below the maxi-mum frost depth, with drainage to an outlet. Such drainage lowers the water table and interrupts the flow of water moving both ver-tically and horizontally through the soil.

Page 94: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 13

8.10.4 Concrete Floors. If the ground beneath a concrete floor can freeze, the floor should be installed such that its vertical movement is not restricted by embedded posts or by structural elements attached to embedded posts. While concrete shrinkage may break bonds between a floor and surrounding components, more proac-tive measures will ensure independent vertical behavior. For example, plastic film can be placed against surrounding surfaces prior to pouring the floor. 8.10.5 Concrete Backfill. The use of poured concrete as a backfill material may actually in-crease the likelihood of frost heave. The rough soil-to-concrete backfill interface provides the potential for significant vertical uplift forces due to frost heave. Also, the placement of concrete in holes that decrease in diameter with depth provide additional risk for frost heave. 8.10.6 Top Collars. Although common in past years, placement of collars at the ground sur-face (to increase lateral load resistance) has all but been abandoned due to frost heave consid-erations. 8.11 References ASAE. 1999a. ASAE EP486: Post and pole foundation design. Shallow post foundation de-sign. ASAE Standards, 46th Edition. ASAE,. St. Joseph, MI ASAE. 1999b. ASAE EP486.2: Shallow post foundation design. In review. ASAE. St. Joseph, MI. Hough, B.K. 1969. Basic Soils Engineering, 2nd Edition. Ronald Press Co. Table 7-2, p. 249. International Conference of Building Officials (ICBO). 1994. Uniform Building Code, 1994 Edi-tion. ICBO, Whittier, CA McGuire, P. M. 1998. Overlooked assumption in nonconstrained post embedment. ASCE Prac-tice Periodic on Structural design and Construc-tion, 3(1):19-24. Meador, N.F. 1997. Mathematical models for lateral resistance of post foundations. Trans of ASAE, 40(1):191-201.

Merritt, F.S. 1976. Standard Handbook for Civil Engineers, pp. 7-53. Patterson, D. 1969. Pole Building Design. American Wood Preservers Institute (AWPI), Washington D.C. Whitlow, R. 1995. Basic Soil Mechanics. 3rd edi-tion. John Wiley & Sons, Inc. New York, NY

Page 95: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

8 - 14

Page 96: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

9-1

Chapter 9: DESIGN EXAMPLE 9.1 Introduction 9.1.1 General. Structurally efficient post-frame buildings utilize the roof as a diaphragm to resist horizontal wind forces. This chapter presents an example of diaphragm design following the five steps outlined in Section 5.1.4. 9.1.2 Building Specifications. Table 9.1 lists design parameters for the example building. Table 9.1. Example Building Specifications

Width (truss length) 36 ftLength (along ridge) 60 ftHeight at post bearing 12 ftRoof slope 4/12 (18.43°)Bay spacing 10 ftNumber of frames (including end walls) 7

Post embedment depth 4 ftPost grade & species No.2 S. PinePost size Nom. 6- by 6-in.Roof snow load 30 psfRoof dead load 5 psfConcrete slab? YesCeiling? No

9.1.3 Wind Loads. It is assumed that the ex-ample building is located in a jurisdiction that has adopted the 1994 Uniform Building Code. Design wind loads calculated according to this code are presented in Table 9.2 Table 9.2. Wind Loads

Wind speed 80 mphExposure category BWindward wall, qww 8.13 psfLeeward wall, qlw -5.08 psf *Windward roof, qwr 3.05 psfLeeward roof, qlr -7.12 psf *

* Negative loads act away from the surface in question. Positive loads act toward the sur-face in question.

9.2 Step 1: Modeling 9.2.1 General. The structural model for this ex-ample building follows that in Section 5.2. The frames are numbered from one to seven begin-ning on the left end. That portion of the roof dia-phragm between each frame is broken into two discrete segments labeled 1a, 1,b, …6a, 6b. See Figure 9.1.

Figure 9.1. Identification of frame elements and roof diaphragm segments. 9.3 Step 2: Stiffness Properties 9.3.1 Frame Stiffness, k. One reliable way to determine frame stiffness is to use a plane-frame analysis program such as the PPSA pro-gram mentioned in Section 5.3.2. In this exam-ple, all posts will be considered fixed at the grade line and pin connected to trusses (figure 5.5). Consequently, the stiffness of each em-bedded post can be calculated using equation 5-3 which is given as: kp = 3 E I / Hp

3 For the nominal 6- by 6-inch No. 2 Southern Pine posts: E = 1.2 x 106 lbf/in.2 (No adjustment for

wet conditions is necessary for Southern Pine timbers. It is gener-ally required for laminated posts.)

I = 76.26 in.4 Hp = 144 in. Thus, kp = 91.9 lbf/in.

1a

1b

2a

2b

3a

3b

4a

4b

1 2 4 5 73 6

5a

5b

6a

6b

Page 97: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

9-2

Frame stiffness, k, is obtained by summing indi-vidual post stiffness values (equation 5-2). This summation yields: k = 184 lbf/in. 9.3.2 Diaphragm Stiffness, Ch. The diaphragm assembly used in this example is Test Assembly 11 in Table 6.1. Its properties are summarized in Table 9.3. Table 9.3. Diaphragm Properties

Metal thickness 29 gageAssembly width, 3 x a 36 ftAssembly length, b 12 ftAllowable shear strength, va 107 lbf/ftEffective in-plane shear stiffness, c 3700 lbf/in.

Effective shear modulus, G 3700 lbf/in. In-plane shear stiffness for a single diaphragm section is calculated using equation 6-9, which is given as.

G bh cp = s cos(θ)

Substitution of appropriate values yields:

(3700 lbf/in.)(18 ft) cp = (10 ft)(cos(18.43))

cp = 7020 lbf/in.

The horizontal shear stiffness, ch, of a single diaphragm section is calculated using equation 6-10 which is given as: ch = cp cos2

(θ) Substitution of appropriate values yields: ch = (7020 lbf/in.) cos2(18.43°) = 6320 lbf/in. Total horizontal shear stiffness of a diaphragm element, Ch, is found by summing the stiffness values of the two sections that comprise each diaphragm element (see equation 5-4). Ch = 6320 + 6320 = 12,640 lbf/in.

9.3.3 Shearwall Stiffness, ke. There are no large doors in the endwalls of the example build-ing. Lacking a specific tested endwall assembly, the 12 ft high endwalls will be assumed to have the same shear stiffness as an 8 ft section of the roof diaphragm; that is, ke will be set equal to Ch or 12,640 lbf/in. 9.4 Step 3: Eave Loads 9.4.1 Windward Roof Pressures. As noted in Section 9.1.3, this example uses wind loads cal-culated in accordance with the 1994 UBC. Pres-sure coefficients (from UBC table 16-H) for windward roof slopes between 2/12 and 9/12 are -0.9 (outward) and 0.3 (inward). It is impor-tant to recognize the significant impact that wind direction (inward or outward) has on calculated eave loads. The 3.05 psf design windward roof pressure listed in table 9.2 was calculated using the 0.3 pressure coefficient. When combined with the negative pressure of 7.12 psf on the leeward roof, the net lateral roof pressure is 10.17 psf. If the –0.9 pressure coefficient would have been used, the net lateral roof pressure would have been –2.03 psf. 9.4.2 Fixity Factors, f. Based on the assump-tion of a post fixed at the groundline (see Sec-tion 9.3.1), a fixity factor of 3/8 is appropriate for this example. 9.4.3 Eave Load, R. Since this example uses symmetrical base restraint and frame geometry, equation 5-6 may be used. R = s [hr (qwr – qlr) + hw f (qww – qlw)] where: hr = (36 ft /2) (4/12) = 6 ft hw = 12 ft s = 10 ft f = 0.375 or R = 10 ft [6 ft (3.05 psf + 7.12 psf) + 12 ft (.375)(8.13 psf + 5.08 psf)] R = 1205 lbf

Page 98: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

9-3

For later calculations, it is convenient to calcu-late R in terms of its components – roof, wind-ward wall and leeward wall. RR = 10(6)(3.05 + 7.12) = 610.2 lbf RW = 10(12)(.375)(8.13) = 365.8 lbf RL = 10(12)(.375)(-5.08) = -228.6 lbf RR + RW – RL = 1205 lbf 9.5 Step 4: Load Distribution 9.5.1 Introduction. For this example problem, diaphragm shear stiffness, Ch, frame stiffness, k, endwall stiffness, ke, and eave load, R, are all constant. Consequently, in addition to analysis methods such as DAFI, load distribution can be determined using the ANSI/ASAE EP484.2 ta-bles (Section 5.6.3) and the simple beam anal-ogy equations (Section 5.5.6). For comparison purposes, all three methods are demonstrated here (Sections 9.5.2 – 9.5.4). The information obtained from these analyses is then used to determine the maximum diaphragm shear force (Section 9.5.6) and maximum post forces (Sec-tion 9.5.7). 9.5.2 ANSI/ASAE EP484.2 Tables. In this de-sign manual, the ANSI/ASAE EP484.2 tables are tables 5.1 and 5.2. Table 5.1 contains shear force modifiers or “mS” values. The product of this modifier and eave load, R, is the maximum shear force in the diaphragm, Vh. Table 5.2 con-tains sidesway restraining force modifiers or “mD” values. The product of this modifier and eave load, R, is referred to as the horizontal re-straining force, Q, which is the amount of eave load transferred away from the center post-frame(s) by the diaphragm. Use of tables 5.1 and 5.2 requires two ratio: ke/k and Ch/k. For this example analysis, both ratios are equal to 69 (12640/184). Using linear inter-polation, the mS value from table 5.1 is 2.77, and the mD value from table 5.2 is 0.90. The maximum diaphragm shear force, Vh, which occurs adjacent to each endwall, is given as: Vh = mS R = 2.77(1205 lbf) = 3340 lbf The horizontal restraining force, Q, that must be applied to the center post frame (i.e., frame 4 in figure 9.1) is given as:

Q = mD R = 0.90(1205 lbf) = 1085 lbf The difference between eave load, R, and the horizontal restraining force, Q, is the amount of the eave load that is transferred by the center post-frame to the foundation. R – Q = 120 lbf The eave deflection, ∆, for a post-frame with stiffness, k, subjected to an eave load, R, and horizontal restraining force, Q, is given as: ∆ = (R – Q) / k Eave deflection for the center post-frame is given as: ∆ = (1205 lbf – 1085 lbf) / 184 lbf/in. ∆ = 0.652 in. 9.5.3 Simple Beam Analogy Equations. As previously noted, the simple beam analogy equations for diaphragm shear force, Vh, and diaphragm displacement, y, can be used when R, k, ke and Ch are constant. These two equa-tions are given in Section 5.6.6 as: Vh = Ch α s [A sinh(α x) + B cosh(α x)] y = A cosh(α x) + B sinh(α x) + R/k Input parameters and calculated equation con-stants for the simple beam analogy equations have been compiled for this example analysis in Table 9.4. Maximum diaphragm shear is calculated by set-ting x = 0 in., or: Vh = 12,640 lbf/in.(1.0054x10-3 in.-1) •(120 in.)[-6.286 in.(0) + 2.181 in.(1)] Vh = 3326 lbf Maximum diaphragm displacement is calculated by setting x = L/2 = 360 in. , or: y = -6.286 in.( 1.0662) + 2.181 in.( 0.3699) + 1205 lbf/(184 lbf/in.) y = 0.6535 in.

Page 99: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

9-4

Table 9.4. Parameters for Simple Beam Anal-ogy Equations

R 1205 lbf s 120 in.L 720 in.ke 12,640 lbf/in.k 184 lbf/in.R / k 6.549 in.Ch 12,640 lbf/in.α 1.0054x10-3 in.-1 *α L 0.7239cosh(α L) 1.2737sinh(α L) 0.7888D -23.890 *ye 0.2631 in. *A -6.286 in. *B 2.181 in. *cosh(0) 1sinh(0) 0cosh(α 360 in.) 1.0662sinh(α 360 in.) 0.3699

* Equations for calculation of these values are given in Section 5.6.6.

The force transferred to the foundation by the center frame (frame 4) is equal to the product of eave displacement, y, and frame stiffness, k, or: y k = 0.6535 in. (184 lbf/in.) = 120.2 lbf The horizontal restraining force, Q, for the frame 4 is equal to the difference between the eave load, R, and the 120.2 lbf, or Q = 1205 lbf – 120.2 lbf = 1084.8 lbf Note that ye in table 9.4 is the eave displace-ment of the endwall. 9.5.4 DAFI. As previously mentioned, DAFI is a computer program specifically written for deter-mining load distribution between diaphragms and frames. DAFI can be downloaded free from the NFBA web site (www.postframe.org). The maximum shear force in the diaphragm. Vh, is numerically equal to the load resisted by the endwall frame. In figure 9.2, this value is given as 3353.2 lbf. Note that this value is more pre-cise than the 3340 lbf value calculated from the mS values in table 5.1 because the values in table 5.1 are only given to three significant fig-ures. It is important to note that the shear load

FRAME FRAME APPLIED HORIZONTAL LOAD RESISTED FRACTION OF NUMBER STIFFNESS LOAD DISPLACEMENT BY FRAME APPLIED LOAD --------------------------------------------------------------------- 1 12640.00 602.5 .2652868 3353.2 5.5655 2 184.00 1205.0 .4829074 88.9 .0737 3 184.00 1205.0 .6122254 112.6 .0935 4 184.00 1205.0 .6551232 120.5 .1000 5 184.00 1205.0 .6122254 112.6 .0935 6 184.00 1205.0 .4829074 88.9 .0737 7 12640.00 602.5 .2652867 3353.2 5.5655 DIAPHRAGM DIAPHRAGM SHEAR SHEAR NUMBER STIFFNESS DISPLACEMENT LOAD -------------------------------------------- 1 12640.00 .2176206 2750.7 2 12640.00 .1293180 1634.6 3 12640.00 .0428978 542.2 4 12640.00 .0428979 542.2 5 12640.00 .1293180 1634.6 6 12640.00 .2176206 2750.7

Figure 9.2. Output from computer program DAFI for example building.

Page 100: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

9-5

listed for each diaphragm in the DAFI output is essentially an average shear load in the dia-phragm. For example, the average shear load in diaphragm 1 is listed as 2750.7 lbf. To calculate the maximum shear load in each diaphragm element, simply add the quantity R/2 to the av-erage value. For this example analysis, half the eave load is 602.5 lbf. Adding this to the aver-age shear load in diaphragm 1 yields the ex-pected maximum shear force in the diaphragm of 3353.2 lbf. The amount of eave load transferred to the foundation by each frame is listed in figure 9.2 under the column heading “load resisted by frame.” The difference between this value and the eave load, R, is the horizontal restraining force, Q. The load resisted by the most heavily loaded frame (i.e., frame 4) is 120.5 lbf. This equates to a horizontal restraining force for frame 4 of 1084.5 lbf (1205 lbf – 120.5 lbf). 9.5.5 Comparison of Methods. The ANSI/ ASAE EP484.2 tables (tables 5-1 and 5-2), sim-ple beam analogy equations, and program DAFI yield identical values for maximum diaphragm shear, horizontal restraining force, and eave deflections. Again, it is important to note that the ANSI/ASAE EP484.2 tables and the simple beam analogy equations are restricted to de-signs with fixed values of Ch, k, R, and ke. Al-though DAFI is more versatile, a DAFI analysis requires computer access. The simple beam analog equations can be quickly solved with a hand calculator that supports hyperbolic trigo-nometric functions. 9.5.6 Diaphragm Shear. The maximum in-plane shear force, Vp, in a diaphragm section is calculated from the maximum horizontal shear force, Vh, in the diaphragm elements using equation 5-9 which is given as: Vp,i = (ch,i / Ch) Vh / (cos θ i) For this example analysis, all six diaphragm elements have the same Ch, and all twelve of the diaphragm sections shown in figure 9.1 have the same horizontal stiffness, ch and slope, θ, that is: Ch = 12,640 lbf/in. ch,i = 6320 lbf/in. θ = 18.43°

Diaphragm elements 1 and 6 are both subjected to the maximum horizontal shear, Vh, of 3350 lbf. Consequently, the in-plane shear force in diaphagm sections 1a, 1b, 6a and 6b is given as:

6320 lbf/in (3350 lbf) Vp = 12,640 lbf/in (cos 18.43°) Vp = 1766 lbf Dividing the in-plane shear force by the slope length of a diaphragm section yields the in-plane shear force on a unit length basis, vp. vp = 1766 lbf /(18 ft / cos (18.43°)) vp = 93.1 lbf/ft 9.5.7. Post Forces. The most critical posts from a design perspective are those associated with the most heavily loaded frame. In the example building this is the center post-frame (a.k.a. frame 4). There are two basic methods for determining post forces. The first is to analyze the frame with a plane-frame structural analysis program, the second is to assume the truss is rigid and then use a series of equations to calculate post forces. A structural analog for a plane-frame structural analysis of frame 4 is shown in figure 9.3a. Post forces obtained with this analog are given in fig-ure 9.3b. For this example analysis, the load combination of “full dead + full wind + ½ snow “ was used, with a roof dead load of 5 psf and a roof snow load of 30 psf (Note: in practice, the building designer must check all applicable load cases). The force applied to the frame by the diaphragm, qp, was applied as a force of 30.12 lbf per foot of top chord. This force was obtained by first combining equations 5-10 and 5-11 into the following equation: q p,i = Q (c h,i / Ch ) / b i (9-1) where: Q is the horizontal restraining force (1084.5 lbf for frame 4); ch,i is the horizontal stiffness of diaphragm segment i (6320 lbf/in); Ch is the horizontal stiffness of diaphragm element i (12,640 lbf/in); and bi is the horizontal span of diaphragm segment i (18 ft).

Page 101: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

9-6

Figure 9.3. (a) Structural analog for frame 4 of the example building (s = 10 ft). (b) Re-sulting forces on post ends. Lateral deflection at the top of the windward and leeward posts were 0.572 and 0.735 inches, respectively.

Figure 9.4. Resultant of forces applied to truss of frame 4. In lieu of a computer analysis, post axial forces for a two-post frame can be obtained by drawing a free-body diagram of the truss and summing forces about each truss-to-post connection. Such a free-body diagram for frame 4 of the ex-ample building is shown in figure 9.4. The axial forces (Pw and Pl) obtained in this manner are identical to those obtained via the computer analysis (figure 9.3).

To obtain post shears and bending moments without reliance on a computer is a straight for-ward process if the truss is assumed to be com-pletely rigid. When this assumption is made, the lateral movement, ∆, of all posts at their truss attachment point will be equal to that obtained using the methods outlined in Sections 9.5.2, 9.5.3 and 9.5.4. Post shear and post bending

9 ft 9 ft 9 ft 9 ft

Roof dead + 1/2 snow = 7200 lbf

Vertical component of leeward roof pressure = -1281.6 lbf

+Vertical component of diaphragm

restraining force = -180.75 lbf

Vertical component of windward roof pressure = 549 lbf

+Vertical component of diaphragm

restraining force = 180.75 lbf

3 ft

3 ft

Horizontal component of windward roof pressure = 183 lbf

+Horizontal component of diaphragm

restraining force = -542.25 lbf

3 ft

3 ft

Horizontal component of leeward roof pressure = -427.2 lbf

+Horizontal component of diaphragm

restraining force = 542.25 lbf

Pl = 2646 lbfPw = 3821 lbf

Vtw Vtl

s x (5 psf + 30 psf /2)

s x 8.

13 p

sf

s x 3.05 psfs x 7.12 psf

s x 5.

08 p

sf

30.12 lbf/ft 30.12 lbf/ft

(a)

3820 lbf

0 in.-lbf313 lbf

662 lbf

3821 lbf

25100 in.-lbf

2650 lbf

161 lbf

449 lbf

2646 lbf

20700 in.-lbf

Windward post

Leeward post

(b)

0 in.-lbf

Page 102: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

9-7

moment can then be calculated using the follow-ing equations which assume zero bending mo-ment at the top of the post. Vy = kp ∆ – R i + s q (Hp – y) (9-2) My = (s q / 2)(Hp – y)2 + Vt (Hp – y) (9-3) Mmax = - Vt

2 / (2 s q) (9-4) where: Vy = post shear at distance y from base,

lbf (N) kp = post stiffness, lbf/in. (N/mm) ∆ = lateral movement of post top, in.

(mm) R i = contribution of wall pressure to eave

load, lbf (N) = RW for windward wall = RL for leeward wall s = frame spacing q = wall pressure, lbf/ft2 (N/m2) Hp = post height, ft (m) y = distance from post base, ft (m) My = bending moment in post at distance

y from base, lbf-ft (N-m) Vt = Vy at y = Hp, lbf (N) Mmax = bending moment at y = Hp + Vt /(sq)

(i.e., at the point of zero post shear) Positive sign conventions for the preceding vari-ables are illustrated in figure 9.5.

Figure 9.5. Positive sign convention for vari-ables used in equations 9-2 and 9-3.

Using equation 9-2, the shears at the top, Vt, and bottom, Vb, of the windward post of frame 4 are: Vt = (91.9 lbf/in.)(0.655 in.) – 365.8 lbf + (10 ft)(8.13 psf) (12 ft – 12 ft) Vt = –305.6 lbf Vb = (91.9 lbf/in.)(0.655 in.) – 365.8 lbf + (10 ft)(8.13 psf) (12 ft – 0 ft) Vb = 670.0 lbf and the shears at the top, Vt, and bottom, Vb, of the leeward post of frame 4 are: Vt = (91.9 lbf/in.)(0.655 in.) – 228.6 lbf + (10 ft)(5.08 psf) (12 ft – 12 ft) Vt = –168.4 lbf Vb = (91.9 lbf/in.)(0.655 in.) – 228.6 lbf + (10 ft)(5.08 psf) (12 ft – 0 ft) Vb = 441.2 lbf Equation 9-3 yields bending moments at the base of the windward and leeward posts of 26200 and 19640 lbf-in., respectively. The dif-ference between these values and those in fig-ure 9.3b are due to the rigid truss assumption. According to equation 9-4, bending moments at the point of zero shear in the windward and lee-ward posts are 6890 and 3350 lbf-in., respec-tively. 9.6 Step 5: Check Allowable Values 9.6.1 Diaphragm Shear. The actual maximum diaphragm shear stress of 93.1 lbf/ft (Section 9.5.6) is less than the allowable of 107 lbf/ft (ta-ble 9.3) so the diaphragm has sufficient strength.

9.6.2 Windward Post Stresses. Posts are sub-ject to combined bending and compression and must be checked per the requirements of the 1997 NDS Section 3.9.2 and NDS equation 3.9-3. This equation, simplified for uniaxial bending is:

Hps x q

yVy

My

Vy

Page 103: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

9-8

CSI = ( fc / Fc’ )2 + f b / {Fb’ [ 1 – ( fc / FcE)]} < 1.0 (9-5) where: CSI = combined stress index fc = actual compressive stress f b = actual bending stress Fc’ = allowable compressive stress = Fc •CD •CM •CF •Ci •CP Fb’ = allowable bending stress = Fb •CD •CM •CF •Ci •CL•Cr •Cf •CV FcE = critical buckling design stress = K E’ I / ( le / d )2 and: Fc = tabulated compressive stress Fb = tabulated bending stress CD = load duration factor CM = wet service factor CF = size factor Ci = incising factor CP = column stability factor CL = beam stability factor Cr = repetitive member factor Cf = form factor CV = volume factor E’ = E •CM •Ci I = moment of inertia le /d = slenderness ratio K = 0.3 for visually graded lumber = 0.384 for machine evaluated lumber Actual stresses for the windward post are: fc = PW / A = 3821 lbf / (30.25 in.2) = 126 lbf/in.2 f b = M / S = 26200 lbf-in. / (27.73 in.3) = 945 lbf/in.2 (at the base) f b = 6890 lbf-in. / (27.73 in.3) = 248 lbf/in.2 (at point of zero shear) For No. 2 Southern Pine timber, the tabulated compression and bending stresses and modulus of elasticity are: Fb = 850 lbf/in.2 Fc = 525 lbf/in.2 E = 1,200,000 lbf/in.2 Applicable adjustment factors are:

CD = 1.60 since the shortest duration load

in the combination of loads is wind CM = 1.00 for modulus of elasticity, com-

pression and bending of Southern Pine timber regardless of moisture content

CF = 1.00 for nominal 6- by 6-inch No.2 Southern Pine

Ci = 1.00 since Southern Pine does not need to be incised for pressure treatments

CL = 1.00 since post is square Cr = 1.00 because post spacing exceeds

24 inches. Note that this value is non-zero for mechanically laminated posts

Cf = 1.00 since posts are rectangular CV = 1.00 since posts are not glued-

laminated CP = 1.00 at the base of the post where

support is provided in both direc-tions

CP = is less than 1.00 at locations re-moved from supports that keep the post from buckling. For such cases, CP is calculated using NDS equation 3.7-1.

It follows that at the base of both the windward and leeward posts: Fc’ = ( 525 lbf/in.2)(1.60) = 840 lbf/in.2 Fb’ = ( 850 lbf/in.2)(1.60) = 1360 lbf/in.2 FcE = A very large number if the effective

buckling length, le, is assumed to be very small because of support at the base. As a result, the ratio fc / FcE in equation 9-5 is assumed to equal zero.

and at the base of the windward post: CSI = ( 126 / 840 )2 + ( 945 / 1360 ) = 0.02 + 0.70 = 0.72 < 1.0 OK The other critical location to check the combined stress index (CSI) is at the point of maximum bending moment (point of zero shear) in the up-per portion of the post. At this location, the col-umn stability factor is generally based on an ef-fective column buckling length of 0.8 Hp (see

Page 104: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

9-9

NDS Appendix G), which results in the following slenderness ratio: le / d = 0.8 (144 in.) / 5.5 in. = 20.9 thus: FcE = 0.3 (1200000 lbf/in.2) / (20.9)2 = 820 lbf/in.2 The ratio of FcE / Fc is 0.976. This yields a Cp of 0.682, resulting in the following allowable com-pressive stress, Fc’. Fc’ = ( 525 lbf/in.2)(1.60)(0.682) = 573 lbf/in.2 The CSI at the point of maximum moment in the upper portion of the post is: CSI = ( 126 / 573 )2 + 248 / [1360 (1 - 126/820)] = 0.05 + 0.22 = 0.27 < 1.0 OK 9.6.3 Windward Post Embedment. The wind-ward post is constrained by the floor slab. Since our example building is in an UBC jurisdiction, embedment depth will be checked using equa-tion 8-8 which is given as:

4.25 Ma 1/3 d = S’ b

For this example, the soil is assumed to be a firm silty sand which puts it in class 4 (firm) of Table 8.1 – a soil with a tabulated lateral soil pressure of 200 lbf/ft per foot of depth. In accor-dance with the UBC, the tabulated lateral pres-sure can be adjusted for wind loading by a factor of 1.33. Since the posts are more than six di-ameters apart, the allowable lateral pressure can also be doubled for isolated conditions. Thus, the allowable lateral soil bearing pressure is: S' = (200 lbf / ft2 / ft)(1.33)(2) = 532 lbf / ft2 / ft As previously calculated, the moment at grade is 26200 lbf-in or 2180 lbf-ft. The effective width of the post, b, is: b = (1.4)(5.5 in)/12 = 0.64 ft

The minimum embedment depth, d, is:

4.25 (2180 lbf-ft) 1/3 d = (532 lbf/ft3) (0.64 ft)

d = 3.00 ft < 4 ft OK 9.6.4 Leeward Post Stresses. Because (1) the axial force and maximum bending moments as-sociated with the leeward post are all less than those for the windward post, (2) the windward and leeward posts are similarly supported, and (3) the windward post is not overstressed, there is not need to check stresses in the leeward post. 9.6.5 Leeward Post Embedment. Unless the post-frame designer makes special provisions to tie the base of the leeward post to the floor slab, it will be non-constrained. Since this is a UBC jurisdiction, embedment depth will be checked using equation 8-6, which is given as follows:

7.02 Va + 7.65 Ma / d

d 2 = S’ b Solution of this equation is an iterative process. The values for S’ and b are as determined for the windward post. Leeward post base shear and bending moment where previously calcu-lated as 441 lbf and 1640 lbf-ft, respectively

7.02(441 lbf) + 7.65(1640 lbf-ft)/dd 2 = (532 lbf/ft3) (0.64 ft) d = 4.22 ft > 4 ft At this point, the post-frame designer must apply engineering judgement. It is important to re-member that the analogs in this example pro-duce conservative values for base moments and shears, especially for the non-constrained case. The designer must also consider what is known about the soil type and its variability on the build-ing site. If an embedment of 4 ft rather than 4.22 ft satisfies uplift requirements as calculated elsewhere (not included in this example) an ex-perienced post-frame designer could validly judge that an embedment of 4 ft. is OK.

Page 105: Post-Frame Building Design Manual

National Frame Builders Association Post-Frame Building Design Manual

9-10

9.7 Example Summary There are many items that the post-frame de-signer must still check. These include but are not limited to: • The interconnection between diaphragms

and shearwalls • Diaphragm chords • Footings for gravity loads • Uplift checks for embedded posts • All secondary members and headers • The connections of all members, especially

truss to post • End wall posts • Diaphragms and shearwalls for wind against

the endwall This example has focused solely on those items that are unique to post-frame. The post-frame designer should be able to perform the remain-ing checks and designs using commonly ac-cepted practices and techniques.