    Protection and Substation ControlEV-S_V13_17.07.00- 1

    Line differential relay 7SD52

    Line differential relay for HV andUHV lines/cables with a serialcommunication interface

    7SD52

  • 8/8/2019 Presentation 7sd52 En

    2/17

    Protection and Substation ControlEV-S_V13_17.07.00- 2

    Protection and communication join togetherThree benefits of the 7SD52

    Differential protection for theuniversal use with easy to handle

    settings

    Two up to six line ends , for serial and parallelcompensated lines, handles transformers and

    compensation coils within the protection zone,

    tripping time approx. 15 ms with fast high set element

    Additional functions for very

    long overhead lines and cables

    Considation of local CT errors, chargecurrent compensation (step 2), increased setpoint

    during switching-on conditions

    Direct and modular connection to fibre

    optic and digital communication

    networks

  • 8/8/2019 Presentation 7sd52 En

    3/17

    Protection and Substation ControlEV-S_V13_17.07.00- 3

    Application for a three terminal configuration

    SDHcomms-network

    X21G703.1820 nm

    max.3 km

    eo

    PCMmulti-plexer

    Monomode fibre optic cable up to 35 km with 1300 nm interface

    Distance relay7SA52

    Monomodefibre

    opticcableupto10k

    m

    (1300n

    m

    modul)

    PCMmulti-plexero

    e

    oe

    Comms-converterG703.1: 64 kBitX21: N*64 kBit (1N8)

    Option:

    I-REGB

    timesynchronisation

  • 8/8/2019 Presentation 7sd52 En

    4/17

    Protection and Substation ControlEV-S_V13_17.07.00- 4

    Scope of functions / Hardware options

    Scope of functions

    - Fast high set elementwith charge comparision

    - Sensitive normal tripstage with vectorsummation principle

    - Autoreclosure 1/3 pole- Communication features- Commissioning aid- Overload protection- Backup-/emergencyovercurrent

    - Multiterminal extention- Switch on to faultprotection

    - 4 remote commands24 remote signals

    Relay Hardware

    O

    O1300 nm

    10 kmmonomode

    O 1300 nm35 kmmonomode

    OE

    ElectricalX21G703.1interface

    Options for the Protection Interface

    *19

    internal

    internal

    internal

    1*19External converter

    16 binary inputs24 contacts

    24 binary inputs32 contacts

    Option: 5 fasttrip contacts

    820 nm1,5 / 3 kmmultimode

    820 nm1,5 kmST-connectors

    3Iph , and IE

    4 U8 binary inputs16 contacts1 - 2 protection interfacesSystem interface

    PC-interfaceTime synchronisation

    ST-connector

    ST-

    connector

    FC-connector

  • 8/8/2019 Presentation 7sd52 En

    5/17

    Protection and Substation ControlEV-S_V13_17.07.00- 5

    Hardware option of the comms interfaces

    Protection interface 2Port E

    Synchronous N x 64kB/sec

    7SD5

    2

    Protection interface 1Port D

    Synchronous N x 64kB/sec

    Serial timesync. input GPS-receiver

    Interfacemodul 1

    RS485 or FOor RS232

    service-interface DIGSI 4; also for

    modem connectionand Browser

    local-PCinterface

    DIGSIlocal

    Browser

    Substation controlcommunication modules

    FO (Fibre optic) or RS485or RS232Available ProtocolsIEC - standard

    Interfacemodul 2RS485 or FO

    Subst. control interface

    Plug inmodules

    Remote line end 2

    Remote line end 1

  • 8/8/2019 Presentation 7sd52 En

    6/17

    Protection and Substation ControlEV-S_V13_17.07.00- 6

    Main processorboard of the relay

    Sockets for thecommunicationmodules

    Main board of the relay with itsCommunication - Interfaces

  • 8/8/2019 Presentation 7sd52 En

    7/17

    Protection and Substation ControlEV-S_V13_17.07.00- 7

    Main protection functionFeatures of the differential function

    Phase selective multiend differential protection(2 - 6 ends). Tripping time 15 ms with fast chargecomparison protection.

    Fundamental vector comparison for the sensitive

    trip stage.

    Dynamic increase of differential setpoint during

    switch-on of long lines / cables (settable time) CT saturation detector(only 5 ms saturation free

    time due to external faults necessary)

    Phase selective intertrip within 15 ms

    Settable delay time for single phasefaults (feature for inductive compensatednetworks)

    Option: Inrush 2nd harmonic restraint withvector group adaption. Undelayed trip for highfault currents

    Optional Lockout function

  • 8/8/2019 Presentation 7sd52 En

    8/17

    Protection and Substation ControlEV-S_V13_17.07.00- 8

    Adaptive differential relayingConsideration of CT- errors and comms-errors

    IDiffIN

    I

    IN

    I1 I2

    I3

    IDiff = I1 + I2 + I3Phasor summation:Error summation:

    IDiff>

    I1

    I2 I3

    I1

    I = IDiff> + Linear CT-error ( + Syncronization errorIK)

    Trip, if diff.current exceeds the max. permissible error

    Restraintarea

    Trippingarea

  • 8/8/2019 Presentation 7sd52 En

    9/17

    Protection and Substation ControlEV-S_V13_17.07.00- 9

    To complete the 7SD52Additional functions

    3 stage backup- or emergency O/C protection(Can be activated automatically if the communication withthe remote end is >50 ms interrupted)

    Overload function (Thermal replica with IOperation )

    User definable logic and control functions(AND, OR, NOT, Timer, Flip-Flop)

    4 remote commands via binary input or logic inputs(destination is adressable), 24 remote signals

    Operational values: currents, voltages, power,delay time, differential current - remote end refresh 2s

    Fault recorder with voltages, currents, binary tracesand differential and restraint current per phase

    Fast monitoring functions(Fast broken wire supervision, Current symmetry)

    Switch On to Fault protection

    Option: Three pole and single pole AR (Single pole ARduring 2pole fault without earth possible, adaptive AR)

  • 8/8/2019 Presentation 7sd52 En

    10/17

    Protection and Substation ControlEV-S_V13_17.07.00- 10

    Synchronous data transmission by HDLC- protocol

    Permanent supervision of the data transmission

    Measurement and compensation of signal transmission time (max. 20 ms)

    Counts number of invalid telegrams Blocking the diff.protection if transmission failure rate is too high

    Settings for the data transmission(N*64 kBit/s, N settable from 1 - 8, synchronous HDLC-protocol)

    Communication device addresses (Protection devices are clearly assigned to a defined protection

    section)

    Detection of reflected data in the loops in comms- network

    Step 2: Microsecond exact time synchronisation

    via satellite (civil - IRIG-B) (If signal transmission time depends on the transmission direction,

    Online high resolution fault recorder)

    Familiar with digital communication networks

    Features of the relay to relay communication

  • 8/8/2019 Presentation 7sd52 En

    11/17

    Protection and Substation ControlEV-S_V13_17.07.00- 11

    Ring and Chain topologie

    Closed ring Partial current summation

    I3

    I2

    I1

    side 1

    side 2

    side 3

    I3

    I2

    I1

    side 1

    side 2

    side 3

    I3+I1 I2

    I1+I2 I3

    I3+I1

    I1+I2

    Connection to

    other diff. relays

    Automatic change fromclosed ring to chain, ifone connection is lostor not available

  • 8/8/2019 Presentation 7sd52 En

    12/17

    Protection and Substation ControlEV-S_V13_17.07.00- 12

    Topologies: Chain topology for max. 6 line ends

    1 32

    46 5

    PI - Protection Interface

    PI1 PI1 PI2 PI1

    PI2

    PI1

    PI2PI1PI2PI1

  • 8/8/2019 Presentation 7sd52 En

    13/17

    Protection and Substation ControlEV-S_V13_17.07.00- 13

    Topologies: Ring topology, 6 line ends

    31 2

    46 5

    PI1

    PI2

    PI1

    PI2PI1PI2PI1

    PI2

    PI1

    PI2 PI1 PI2

    PI - Protection Interface

  • 8/8/2019 Presentation 7sd52 En

    14/17

    Protection and Substation ControlEV-S_V13_17.07.00- 14

    IL1_1

    IL3_1

    IL2_1

    IL1_2

    IL2_2

    IL3_2

    Phi1->2

    Signal transmission timeMean value of transmit and receive direction

    Generation of signals for switching test loopsSending of defined telegram patterns looped back to thereceive input of the transmitting relay

    Absolute value and phase measurement of currentsLocal measurement of angle between IL1 , IL2 , IL3

    ,Angle between currents of each phase from remote CB test trip

    Counting of faulty telegrams in % per minute and hour

    Activation of binary inputs and outputs by operatingsoftware DIGSI 4.

    Display of the status of binary inputs

    Test telegrams to the substation control system Automatic Switchover from 3 line to 2 line end

    configuration (while commissioning 3rd line end)

    Complete commissioning support with DIGSI 4 andbrowser based PC-software

    Plug and ProtectCommissiong helps and test features

  • 8/8/2019 Presentation 7sd52 En

    15/17

    Protection and Substation ControlEV-S_V13_17.07.00- 15

    Browser based commissioning aid

  • 8/8/2019 Presentation 7sd52 En

    16/17

    Protection and Substation ControlEV-S_V13_17.07.00- 16

    Comprehensive fault analysis with DIGRA 4

    iEe iL1 iL2 iL3

    t/s-0,075 -0,050 -0,025 0,000 0,025 0,050 0,075 0,100 0,125

    I/A

    -2,00

    -1,50

    -1,00

    -0,50

    -0,00

    0,50

    1,00

    1,50

    uL1 uL2 uL3

    t/s-0,075 -0,050 -0,025 0,000 0,025 0,050 0,075 0,100 0,125

    U/V

    -80

    -60

    -40

    -20

    0

    20

    40

    60

    80

  • 8/8/2019 Presentation 7sd52 En

    17/17

    Protection and Substation ControlEV-S_V13_17.07.00- 17

    Prefault and fault conditions in the vector diagram