protection instantaneous voltage relayssystemcontrols.co.in/datasheet/vagm high res.pdf ·...

4
1 GRID PROTECTION Customer Benefits Ideal for over voltage / un- der voltage application. Adjustable voltage rating Operation annunciation in the form of flag Draw out type case Completely dust proof by IP5X class protection Type VAGM 22 Instantaneous Voltage Relays

Upload: others

Post on 14-Apr-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PROTECTION Instantaneous Voltage Relayssystemcontrols.co.in/datasheet/VAGM High Res.pdf · 2018-06-15 · 2 Type VAGM 22 Instantaneous Voltage Relays Type VAGM 22 Features • Adjustable

1

GRID

PROTECTION

Customer Benefits• Idealforovervoltage/un-

dervoltageapplication.• Adjustablevoltagerating• Operation annunciation in

theformofflag• Drawouttypecase• Completely dust proof by

IP5Xclassprotection

Type VAGM 22Instantaneous Voltage Relays

Page 2: PROTECTION Instantaneous Voltage Relayssystemcontrols.co.in/datasheet/VAGM High Res.pdf · 2018-06-15 · 2 Type VAGM 22 Instantaneous Voltage Relays Type VAGM 22 Features • Adjustable

2

Type VAGM 22

Instantaneous Voltage Relays

Type VAGM 22

Features

• Adjustablesettingrange• Veryhighdropoff/pickupratio• Unaffectedbynormalvariationinfrequencyofinputvoltage• Simpleandrobustconstruction• Positiveactionwithoutchatter

Application

Instantaneousover–voltageprotectionofgenerators,capaci-tors etc., definite timeundervoltageprotectionof acmotors,automaticvoltagechangeoverschemesandotherinstantane-ousanddefinitetimeundervoltageandovervoltageapplica-tionsrequiringadjustablesettings.

General description

VAGM22isstandardattractedarmaturerelaywithsevenequalsettingadjustableonaplugboard.

Adccoilisusedwithaninternallymountedbridgerectifiertoobtainadropoff/pickupratiooftheorderof90%.Aresistanceconnectedinserieswiththecoilistappedsuitablyandthetapsareconnectedtotheplugboardtoobtainsevenequalsetting.Acapacitorisusedtoserveasafilterunitforthebridgerectifieranditalsoactsasasurgesuppressorforprotectionthediodesofthebridgerectifieragainsthighvoltagetransients.

The dc coil is fittedwith a normally open light duty contactwhichisarragedtoenergiseanauxiliaryunitwhichprovidesthenecessaryoutputcontacts.

TypeVAGM22isasinglepolerelaywithitsauxiliaryunit.

Technical data

Voltage rating and setting

Relaysaresuppliedsuitableforoperationon110volts,50Hzsystemandhavethefollowingstandardsettingranges:

Overvoltagerelay110-140%adjustableinsevenequalsteps

Under-voltagerelay40-80%adjustableinsevenequalsteps

Resetting voltages

Overvoltagerelay:90%ofsettingvoltageUnder–voltagerelayrelay:110%ofsettingvoltage

Operating times

Over-voltagerelay:

0.060secondat110%voltagesetting

Undervoltagerelay:

0.025secondatzerovoltage.Thesetimesareinclusiveoftheopetatingtimeoftheassociatedauxiliaryunit.

VAGM22relaywithdrawnfromcase

Page 3: PROTECTION Instantaneous Voltage Relayssystemcontrols.co.in/datasheet/VAGM High Res.pdf · 2018-06-15 · 2 Type VAGM 22 Instantaneous Voltage Relays Type VAGM 22 Features • Adjustable

3

Type VAGM 22

Burdens (VAG coil)

Over-voltagerelay:

Maximumburdenatnominalvoltageis0.9VA

Under-voltagerelay:Maximumburdenatnominalvoltage(i.e.relaysetatthelow-estsetting)is2.5VA.

Thermal rating

Over–Voltagerelay:

TheVAGunitcanwithstandthreetimesthesettingvoltageonanysettingcontinuously.

Under-voltagerelay:

TheVAGunitcanwithstandtwotimesthepick-up(resetting)voltageonanysettingcontinuously.

Accuracy

Theover-voltageandunderrelaysconformtoerrorclassindexE5.0asperBS142–1966and5.0asperIS3231-1955.

Operation indicator

Therelayscanbefitted,ifrequired,withanoperationindicatorontheauxiliaryunit.Theindicatorishandresetbymeansofapush-rodprotruding through the relaycase.On theunder-voltagerelay,ofreverseoperationindicatorisfittedi.e.itoper-atesondrop-offorlossofvoltage.

Contacts

Uptothreepairsofstandardself-resetcontactscanbeprovidedontheauxiliaryunitoftherelayinanycombinationof‘Make’and ‘Break’. Theauxiliaryunit is alwaysenergizedbyanor-mallyopen,lightdutycontactoftheVAGunitincaseofunder-voltage relay. The auxiliary unit can be fitted with blow-outmagnetcontactsalso,ifrequired,forbreakingheavyorhighlyinductivedcloads.

The normal position, regarding the contacts, is the de-ener-gisedposition.

Contact rating : The contacts of the auxiliary unit of the relay are rated as follows :-Type of contacts Current Make & carry continuously Make & carry for 3.0 sec BreakStandard AC 1250VAwithmaximaof5Aand

660V7500VAwithmaximaof30Aand660V

1250VAwithmaximaof5Aand660V

Standard DC 1250Wwithmaximaof5Aand660V

7500Wwithmaximaof30Aand660V

100W (Resistive) or 50W (in-ductive)withmaximaof5Aand660V

Heavy duty mag-neticblow-out

DC 1250Wwithmaximaof5Aand660V

7500Wwithmaximaof30Aand660V

3¼KWmaximum

Dimensionsandweights

Relay Case size Minimum overall dimensions A p p r o x i m a t e gross weight Kg.Hight mm Widtgh mm Depth* mm

VAGM22 1DVert. 233 170 203 5.5

*Add76mmformaximumlengthofterminalstuds,alternatively,29mmforterminalscrews.Theapproximategrossweightgivenaboveisinclusiveofcartons,mountingappendagesandterminaldetails.Certifieddimensionaldrawingofcaseoutlines,panelcut-outsandmountingdetailsareavailableonrequest.TherelayscomplyfullywiththerequirementsofIS3231–1965andaresuitableforuseinnormaltropicalenvironments.

Page 4: PROTECTION Instantaneous Voltage Relayssystemcontrols.co.in/datasheet/VAGM High Res.pdf · 2018-06-15 · 2 Type VAGM 22 Instantaneous Voltage Relays Type VAGM 22 Features • Adjustable

4

GRID

InsulationTherelaymeetstherequirementsofIS32311965/ICE-255-5SeriesC-2kVfor1minute.

Case and finishRelaysaresuppliedinsinglepole,metaldrawoutcasessuitableforflushmountingarefinishedeggshellblackandtropicalised.Thedrawoutfeatureconsiderablysimplifiesmaintenanceandpermits testing to be carried out easily and quickly. A cradlemountedisolatingswitchisprovidedwhichautomaticallyiso-lates the trip circuitwhen the cradle assembly iswithdrawnfromthecaseformaintenance.Thispreventsanyinadvertenttrippingofthecircuitbreaker.Thecasecanalsobefittedwithswitchestomaintaintheunder–voltagetripcircuitsonwith-drawaloftherelayunitfromthecase.Afilterbreatherisfittedtoequalizepressureinsideandoutsidethecasewithoutadmit-tingdust.

Information required with order1. Typeofrelay(undervoltageorovervoltage)2.NominalVoltagerating.(Ifotherthan110voltsacsuitable

interposingVTswillhavetobeused.)3.Numberandtype(Standardorblowoutmagnet)of‘Make’

and‘Break’contactsrequired.4.Whetheroperationindicatorrequired.Ifsowhetheranyflag

inscriptionisrequired.5. Voltageratingoftheauxiliaryunit(*)6. Typeofmounting–flushorprojection.

(*)Itispreferabletohaveadcorseparateacauxiliaryvoltagesupplyfortheauxiliaryunit.

ALSTOMT&DINDIALIMITEDPallavaramWorks19/1,G.S.T.Road,Pallavaram,Chennai-600043Tel:91-44-22648000Fax:91-44-22640040

ALSTOMT&DWorldwideContactCentre:http://www.alstom.com/contactcentre/Tel.:+44(0)1785250070

www.grid.alstom.com

“Alstom

logoandanyalternativeversionthereofaretradem

arksandservicemarksofA

lstom

.Theothernam

esmentioned,registeredorn

ot,areth

epropertyoftheirrespective

companies.Thetechnicalandotherdatacontainedinth

edocumentareprovidedforinformationonly.NeitherALSTOM,itsofficersnoremployeesacceptresponsib

ilityforor

shouldbetakenasmakinganyrepresentationorwarranty(whetherexpressorimplied)astotheaccuracyorcom

pletenessofsuchdataortheachievementsofanyprojected

perfo

rmancecriteriawhereth

eseareindicated.Noliabilityisacceptedfora

nyrelianceplacedupontheinform

ationcontainedinth

isbrochure.A

lstom

reservesth

erightto

reviseorchangethesedataatanytimewithoutfurthernotice.”

Type VAGM 22