qa-es-004 earthing specifications for optical network

Upload: tugerhu-agberia

Post on 03-Apr-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    1/23

    1

    Huawei

    Earthing Specifications forOptical Network Equipment

    Course No.: QA-ES-004

    Prepared by: Engineering CenterService Management Dept.Issue Date: 2004-11-15

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    2/23

    2

    Huawei

    Table of Contents

    1. General Purposes

    2. Basic Earthing Principles

    3. Earthing Optical Network Equipment:

    3.1 Method for Earthing Cabinet-type Optical

    Network Equipment

    3.2 Method for Earthing Case-shape OpticalNetwork Equipment

    4. Earthing Optical Network Equipment Connected

    with Other Communication Equipment

    5. Earthing Cable Distribution Frame DDF or MDF6. Earthing for the Maintenance Terminal7. Selection of the Cross-sectional Area of a Protection

    Earthing Wire

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    3/23

    3

    Huawei

    General Purposes

    1

    This specification is to standardize the lightningprotection & earthing design and the installation method

    of the optical network equipment;

    2 This specification is to ensure that the optical networkequipment has good performances of lightning protection,anti-electric shock and anti-interference;

    3The lightning protection & earthing design of the opticalnetwork equipment should accord with the existingrelative national and industrial standards in addition to

    this specification.

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    4/23

    4

    Huawei

    1The earthing design of the communication bureau (station)should follow the equipotential principle, i.e. the jointearthing mode in which the DC return conductor and theprotection earth (including the shielded layer and thelightning protection earth of the distribution frame) share onegroup of earthing electrodes.

    2The un-energized metal parts of both the cabinet and theauxiliary devices of the optical network equipment should be

    earthed.3Protection earthing wires should be yellow/green interwoven

    and plastic insulated.

    4Earthing wires must be copper wires to reduce the highfrequency impedance. The earthing wires should be as shortand thick as possible and should not be made of aluminum.

    5The connecting points at both ends of an earthing wireshould be in good electrical contact and protected withappropriate anti-corrosion and rustproof measures.

    6Other devices should not be used as part of the electricalconnection of earthing wires.

    Basic Earthing Principles

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    5/23

    5

    Huawei

    Basic Earthing Principles

    7 Earthing wires should not intertwine with signal cables.8Aerial inlead of earthing wires is strictly prohibited. They

    must be buried in the ground or laid indoors.

    9It is strictly prohibited to install switches or fuses along aprotection earthing wire.

    10Protection earthing wires should be no longer than 30m andas short as possible. If a protection earthing wire is longer

    than 30 m, an earthing busbar should be set nearby.11The external conductor of a coaxial cable and the shielded

    layer of a shielded cable should have their two ends in goodelectric contact with the outer surface of the metal shell ofthe connected device.

    12It is strictly prohibited to use neutral wires as protectionearthing wires. Both the cabinet shell and the protectionearth must be insulated from the neutral wires of AC powercables.

    M h d f E hi C bi

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    6/23

    6

    Huawei

    Method for Earthing Cabinet

    Equipment Inside

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    7/237

    Huawei

    Method for Earthing Cabinet

    Equipment Cabinet Earthing 1

    Earthing for Optical Network Equipment

    Powered from our Power Distribution Frame:

    M th d f E thi C bi t

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    8/238

    Huawei

    Method for Earthing Cabinet

    Equipment Cabinet Earthing 2

    Earthing for the Optical Network Equipment

    Powered from users power distribution frame

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    9/239

    Huawei

    e o or ar ng a neEquipment Cabinet Earthing 3

    Earthing for the Optical Network Equipment

    Powered from DC Power Supply

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    10/2310

    Huawei

    e o or ar ng a neEquipment Cabinet Earthing 4

    Following the joint Earthing principle, the 48V DC positive

    busbars of the PDB, users DC power distribution panel orusers DC supply should all be connected to the PGND

    Earthing bar of the equipment room.

    M th d f E thi h

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    11/2311

    Huawei

    Method for Earthing case-shape

    Equipment Inside

    Special whole equipment Earthing terminals should be

    provided on the shell of the case-shape Optical NetworkEquipment.

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    12/2312

    Huawei

    e o or ar ng case-s apeEquipment AC Power Supply 1

    Earthing for the Case-Shape AC Equipment when There Is a Protection

    earthing bus in the Equipment Room

    Method for Earthing case shape

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    13/2313

    Huawei

    Method for Earthing case-shape

    Equipment AC Power Supply 2

    Note: When this mode is adopted, the Earthing reliability of the

    equipment should be ensured with a multimeter after the engineering

    installation.

    E thi h E i t

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    14/2314

    Huawei

    Earthing case-shape Equipment

    DC Power Supply 1

    DC case-shape Equipment

    Protection earthing bar of the equipment room or the earthing bus

    inside the cabinet in/on that the case-shape equipment is installed

    2.5mm2ToPowerSupply

    PGND Earthing terminal of whole

    equipment-48V

    -48VRTN

    Method for Earthing case shape

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    15/2315

    Huawei

    Method for Earthing case-shape

    Equipment DC Power Supply 2

    ToPowerSupply

    DC case-shape Equipment

    -48V

    -48VRTN

    PGND

    Protection earthing bar of the equipment room

    Or the earthing bus inside the cabinet in/on that

    the case-shape equipment is installed

    Earthing Optical Network Equipment

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    16/2316

    Huawei

    Earthing Optical Network Equipment

    Connected with Other Communication Equipment

    To ensure the quality of communication signals, when the optical

    network equipment is connected to other communicationequipment through coaxial cables, the external shield layers of

    both the receiving and sending ends should be connected to

    PGND at the same time, but disconnection should also be

    provided at the receiving end.

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    17/2317

    Huawei

    Earthing the Cable Distribution Frame

    1When being led out of an office (station), TDA audio cablesmust pass the Main Distribution Frame (MDF) with a securityunit, with its shield layer being reliably connected to the

    protection earth of the MDF; the security unit on the MDF

    should have protection against over-voltage and over-current

    and the failure alarm function; the equipment maintenance

    personnel should check periodically to timely check-up andreplace the failed security unit.

    2 The distribution frame (including MDF/DDF) should beprovided with a separate earthing wire with a cross-sectional

    area of no less than 6 mm2 that is as short as possible toconnect its earthing busbar to the protection earthing bus in

    the equipment room.

    Earthing Maintenance Terminal

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    18/2318

    Huawei

    Earthing Maintenance Terminal

    Equipment- with AC Power 1

    Earthing for the Maintenance Terminal Using Network Cables

    for Communication

    Earthing Maintenance Terminal

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    19/2319

    Huawei

    Earthing Maintenance TerminalEquipment- with AC Power 2

    Earthing for the Maintenance Terminal Using a Non Network

    Cable for Communication

    Earthing Maintenance Terminal

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    20/2320

    Huawei

    Earthing Maintenance TerminalEquipment-with AC Power 3

    Earthing for the Maintenance Terminal of

    the Case-Shape AC Equipment

    Earthing Maintenance Terminal

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    21/2321

    Huawei

    Earthing Maintenance TerminalEquipmentwith DC Power

    When the maintenance terminal is powered from a -48 V

    power supply, the shell of the maintenance terminal shouldbe reliably connected to the protection earthing bus in the

    equipment room, or the earthing terminal of the optical

    network equipment or the earthing bus of our power

    distribution frame or users power distribution frame

    powering up the optical network equipment through a

    yellow/green interwoven protection earthing wire with a

    cross-sectional area of no less than 2.5 mm2.

    Selection of the Cross sectional Area

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    22/23

    22

    Huawei

    Selection of the Cross-sectional Area

    of a Protection Earthing Wire

    The major factor to be considered for selecting the Cross-

    sectional area of the PGND wire of the equipment is the

    working current of the equipment.

    Lightning protection requirement: The sectional area of the

    earthing wire should meet the requirement of safely

    discharging the lightning current to the earth. Generally this

    requirement is easy to meet.

    Anti-external force requirement: If the protection earthing wire

    is led from the equipment to the outside, it should not be

    broken due to the accidental contact of people or other objects.

  • 7/29/2019 QA-ES-004 Earthing Specifications for Optical Network

    23/23

    23

    Huawei

    Thanks