    INTRODUCTION TO UNDERGROUND

    CABLESPRESENTED BY:

    ROSHAN PRADHAN

    C.V.RAMAN COLLEGE OF ENGINEERINGBBSR

    C.V.RAMAN GROUP OF INSTITUTIONS. 1

  • 8/10/2019 Roshan new.ppt

    2/42

    UNDERGROUND CABLES

    PRESENTED BY:

    ROSHAN PRADHAN

    REGD NO - 1221227062

    SEC-2, GROUP-C

    SEM-7th,YEAR-4th

    ELECTRICAL ENGINEERING

    C.V.RAMAN GROUP OF INSTITUTIONS 2

  • 8/10/2019 Roshan new.ppt

    3/42

    Introduction

    Since the loads having the trends towards growingdensity. This requires the better appearance, ruggedconstruction, greater service reliability and

    increased safety. An underground cable essentiallyconsists of one or more conductors covered withsuitable insulation and surrounded by a protectingcover. The interference from external disturbanceslike storms, lightening, ice, trees etc. should bereduced to achieve trouble free service. The cablesmay be buried directly in the ground, or may beinstalled in ducts buried in the ground.

    C.V.RAMAN GROUP OF INSTITUTIONS3

  • 8/10/2019 Roshan new.ppt

    4/42

    Introduction

    C.V.RAMAN GROUP OF INSTITUTIONS 4

  • 8/10/2019 Roshan new.ppt

    5/42

    Advantages & Disadvantages

    Advantages Better general appearance

    Less liable to damage through storms or lighting

    Low maintenance cost

    Less chances of faults

    Small voltage drops

    Disadvantages

    The major drawback is that they have greater installation cost and

    introduce insulation problems at high voltages compared with

    equivalent overhead system.

    C.V.RAMAN GROUP OF INSTITUTIONS 5

  • 8/10/2019 Roshan new.ppt

    6/42

  • 8/10/2019 Roshan new.ppt

    7/42

    Construction of Cables

    Metallic SheathA metallic sheath of lead or aluminum isprovided over the insulation to protect the

    cable from moisture, gases or othersdamaging liquids

    Bedding

    Bedding is provided to protect the metallicsheath from corrosion and from mechanicaldamage due to armoring. It is a fibrousmaterial like jute or hessian tape.

    C.V.RAMAN GROUP OF INSTITUTIONS7

  • 8/10/2019 Roshan new.ppt

    8/42

    Construction of Cables

    Armouring

    Its purpose is to protect the cable frommechanical injury while laying it or during thecourse of handling. It consists of one or twolayers of galvanized steel wire or steel tape.

    Serving

    To protect armouring from atmosphericconditions, a layer of fibrous material isprovided.

    C.V.RAMAN GROUP OF INSTITUTIONS 8

  • 8/10/2019 Roshan new.ppt

    9/42

    Properties of Insulating

    Material High resistivity.

    High dielectric strength.

    Low thermal co-efficient.

    Low water absorption.

    Low permittivity.

    Non inflammable.

    Chemical stability.

    High mechanical strength.

    High viscosity at impregnation temperature.

    Capability to with stand high rupturing voltage.

    High tensile strength and plasticity.

    C.V.RAMAN GROUP OF INSTITUTIONS9

  • 8/10/2019 Roshan new.ppt

    10/42

    Insulating Materials for Cables

    Rubber

    It can be obtained from milky sap of tropical trees or

    from oil products.It has the dielectric strength of 30 KV/mm.

    Insulation resistivity of 10 exp 17 ohm.cm

    Relative permittivity varying between 2 and 3.

    They readily absorbs moisture, soft and liable to damage

    due to rough handling and ages when exposed to light.

    Maximum safe temperature is very low about 38 CC.V.RAMAN GROUP OF INSTITUTIONS

    10

  • 8/10/2019 Roshan new.ppt

    11/42

  • 8/10/2019 Roshan new.ppt

    12/42

  • 8/10/2019 Roshan new.ppt

    13/42

    Insulating Materials for Cables

    Polyvinyl chloride (PVC) This material has good dielectric strength, high insulation resistance and high

    melting temperatures.

    These have not so good mechanical properties as those of rubber.

    It is inert to oxygen and almost inert to many alkalis and acids.

    XLPE Cables (Cross Linked Poly-ethene) This material has temperature range beyond 250 300 C

    This material gives good insulating properties

    It is light in weight, small overall dimensions, low dielectric constant and high

    mechanical strength, low water absorption.

    These cables permit conductor temperature of 90 C and 250 C under normal

    and short circuit conditions.

    These cables are suitable up to voltages of 33 KV.

    C.V.RAMAN GROUP OF INSTITUTIONS13

  • 8/10/2019 Roshan new.ppt

    14/42

    CLSSIFICATION OF CABLES

    Low tension (L.T) ----- up to 1000V

    High tension (H.T) ----- up to 11, 000V

    Super tension (S.T) ---- from 22KV to 33KV

    Extra high tension (E.H.T) cables --- from 33KV

    to 66KV

    Extra super voltage cables ------beyond 132KV

    C.V.RAMAN GROUP OF INSTITUTIONS14

  • 8/10/2019 Roshan new.ppt

    15/42

    Extra High Tension Cable

    C.V.RAMAN GROUP OF INSTITUTIONS15

  • 8/10/2019 Roshan new.ppt

    16/42

    Low Tension Cable

    C.V.RAMAN GROUP OF INSTITUTIONS16

  • 8/10/2019 Roshan new.ppt

    17/42

    3- Core CablesBelted Cables

    In these cables the conductors are wrapped with oil impregnatedpaper, and then cores are assembled with filler material. Theassembly is enclosed by paper insulating belt.

    These can be used for voltages up to 11KV or in some cases can

    be used up to 22KV.High voltages beyond 22KV, the tangential stresses becomes an

    important consideration.

    As the insulation resistance of paper is quite small along thelayer, therefore tangential stress set up, hence, leakage current

    along the layer of the paper insulation.This leakage current causes local heating, resulting breaking of

    insulation at any moment

    C.V.RAMAN GROUP OF INSTITUTIONS17

  • 8/10/2019 Roshan new.ppt

    18/42

    3-core belted Cable

    C.V.RAMAN GROUP OF INSTITUTIONS18

  • 8/10/2019 Roshan new.ppt

    19/42

    3- Core Cables

    Screened Cables

    These can be used up to 33kv but in certain

    cases can be extended up to 66kv. These are mainly of two types

    H-type and

    S.L type cables

    C.V.RAMAN GROUP OF INSTITUTIONS19

  • 8/10/2019 Roshan new.ppt

    20/42

    3- Core CablesH-TYPE Cables: Designed by H. Hochstadter.

    Each core is insulated by layer of impregnated paper.

    The insulation on each core is covered with a metallic screenwhich is usually of perforated aluminum foil.

    The cores are laid in such a way that metallic screen makecontact with one another.

    Basic advantage of H-TYPE is that the perforation in themetallic screen assists in the complete impregnation of thecable with the compound and thus the possibility of air

    pockets or voids in the dielectric is eliminated. The metallic screen increase the heat dissipation power of

    the cable.

    C.V.RAMAN GROUP OF INSTITUTIONS 20

  • 8/10/2019 Roshan new.ppt

    21/42

    3- Core Cables (H-Type)

    C.V.RAMAN GROUP OF INSTITUTIONS21

  • 8/10/2019 Roshan new.ppt

    22/42

    3- Core Cables

    S.L - Type:(Separate Lead) Each core insulation is covered by its own lead

    sheath.

    It has two main advantages, firstly the separatesheath minimize the possibility of core-to-corebreakdown. Secondly the, bending of cablesbecome easy due to the elimination of over allsheath.

    The disadvantage is that the lead sheaths of S.L ismuch thinner as compared to H-Type cables,therefore for greater care is required inmanufacturing.

    C.V.RAMAN GROUP OF INSTITUTIONS22

  • 8/10/2019 Roshan new.ppt

    23/42

    3- Core Cables (S.L. Type)

    C.V.RAMAN GROUP OF INSTITUTIONS23

  • 8/10/2019 Roshan new.ppt

    24/42

    3- Core Cables

    Pressurized Type Cables

    In these cables, pressure is maintained

    above atmosphere either by oil or by gas. Gas pressure cables are used up to 275KV.

    Oil filled cables are used up to 500KV.

    C.V.RAMAN GROUP OF INSTITUTIONS24

  • 8/10/2019 Roshan new.ppt

    25/42

    Laying of Underground Cables

    The reliability of underground cable networkdepends to a considerable extent uponproper laying.

    There are three main methods of Layingunderground cables

    a. Direct Laying

    b. Draw in system

    c. Solid system

    C.V.RAMAN GROUP OF INSTITUTIONS25

  • 8/10/2019 Roshan new.ppt

    26/42

    Direct Laying

    This method is cheap and simple and is mostlikely to be used in practice.

    A trench of about 1.5 meters deep and 45 cm

    wide is dug. A cable is been laid inside the trench and is

    covered with concrete material or bricks inorder to protect it from mechanical injury.

    This gives the best heat dissipating conditionsbeneath the earth.

    It is clean and safe method

    C.V.RAMAN GROUP OF INSTITUTIONS26

  • 8/10/2019 Roshan new.ppt

    27/42

    Direct Laying

    C.V.RAMAN GROUP OF INSTITUTIONS 27

  • 8/10/2019 Roshan new.ppt

    28/42

    Disadvantages of Direct Laying

    Localization of fault is difficult

    It can be costlier in congested areas where

    excavation is expensive and inconvenient. The maintenance cost is high

    C.V.RAMAN GROUP OF INSTITUTIONS28

  • 8/10/2019 Roshan new.ppt

    29/42

    Draw in System

    In this conduit or duct of concrete is laid inground with main holes at suitable positionsalong the cable route.

    The cables are then pulled into positions frommain holes.

    C.V.RAMAN GROUP OF INSTITUTIONS 29

  • 8/10/2019 Roshan new.ppt

    30/42

    Advantages of Draw in System

    It is very high initial cost

    Heat dissipation conditions are not good

    This method is suitable for congested areaswhere excavation is expensive andinconvenient

    This is generally used for short lengths cableroute such as in workshops, road crossingswhere frequent digging is costlier andimpossible

    C.V.RAMAN GROUP OF INSTITUTIONS30

  • 8/10/2019 Roshan new.ppt

    31/42

    Solid System

    In this system the cable is laid in open pipes ortroughs dug out in earth along the cable route.

    The troughing is of cast iron or treated wood

    Troughing is filled with a bituminous after cables is

    laid. It provides good mechanical strength

    It has poor heat dissipation conditions

    It requires skilled labour and favorable weatherconditions

    It is very much expensive system

    C.V.RAMAN GROUP OF INSTITUTIONS31

  • 8/10/2019 Roshan new.ppt

    32/42

    Solid System

    C.V.RAMAN GROUP OF INSTITUTIONS32

  • 8/10/2019 Roshan new.ppt

    33/42

    Grading of Cables

    Since the stresses are maximum at surface ofthe conductor or inner most part of thedielectric.

    The stress goes on decreasing as outer mostlayer is reached.

    Since the process of achieving the uniform

    electrostatic stresses on the dielectric ofcables is known as Grading of cables

    C.V.RAMAN GROUP OF INSTITUTIONS

    33

  • 8/10/2019 Roshan new.ppt

    34/42

    Grading of Cables

    The unequal distribution of stresses is

    undesirable because,

    if dielectric is chosen according to maximumstress the thickness of cable increases or either

    this may lead to breakdown of insulation.

    The following are the two main methods of

    grading

    Capacitance grading

    Inter sheath grading

    C.V.RAMAN GROUP OF INSTITUTIONS34

  • 8/10/2019 Roshan new.ppt

    35/42

    Cables are generally laid in the ground or in ductsin the underground distribution system. For thisreason, there are little chances of faults in

    underground cables. However, if a fault doesoccur it is difficult to locate and repair the faultbecause conductors are not visible.Nevertheless, the following are the faults most

    likely to occur in underground cables1) open circuit fault2) short circuit fault3)earth fault

    C.V.RAMAN GROUP OF INSTITUTIONS35

  • 8/10/2019 Roshan new.ppt

    36/42

    The open circuit fault can be checked by megger.For this purpose, the three conductors of the 3-core cable at the far end are shorted and earthed.

    The resistance between each conductor and earthis measured by a megger and it will indicate zeroresistance in the circuit of the conductor that isnot broken.

    However, if the conductor is broken, the megger

    will indicate infinite resistance in its circuit When there is a break in the conductor of a cable,

    it is called open circuit fault.

    C.V.RAMAN GROUP OF INSTITUTIONS36

  • 8/10/2019 Roshan new.ppt

    37/42

    When two conductors of a multi-core cable comein electrical contact with each other due toinsulation failure, it is called a short circuit fault.

    Again, we can seek the help of a megger tocheck this fault.

    For this purpose the two terminals of the meggerare connected to any two conductors.

    If the megger gives zero reading, it indicatesshort circuit fault between these conductors.

    The same steps is repeated for other conductorstaking two a time.

    C.V.RAMAN GROUP OF INSTITUTIONS37

  • 8/10/2019 Roshan new.ppt

    38/42

    EARTH FAULTS

    When the conductor of a cable comes incontact with earth, it is called earth fault orground fault.

    To identify this fault, one terminal of themegger is connected to the conductor andthe other terminal connected to earth.

    If the megger indicates zero reading, it meansthe conductor is earthed. The sameprocedure is repeated for other conductors ofthe cable.

    C.V.RAMAN GROUP OF INSTITUTIONS38

  • 8/10/2019 Roshan new.ppt

    39/42

    Physical Limitations of

    Underground LinesThe main argument against constructingunderground systems is usually financial. But costsare not the only limitation.The laws of physics limit how physically long a powerline can be.

    These limits are relatively unimportant on overheadlines but will severely limit high voltage undergroundcable systems The higher the voltage the shorter the line length

    must be. The limiting effects become very important at

    transmission voltages, especially 100,000 Volts andabove. Limiting effects may also be important for

    subtransmission voltages, 69,000 Volts and 35,000Volts.

    C.V.RAMAN GROUP OF INSTITUTIONS39

  • 8/10/2019 Roshan new.ppt

    40/42

    Physical Limitations: The Effect of

    Capacitanceo Capacitance causes current to flow even when no

    load is connected to the cable. This is called linecharging current.

    o

    Underground line capacitance for power cables is farhigher than overhead line capacitance.o Wires are closer to each othero Wires are closer to the earth (within a few inches).

    o Underground lines have 20-75 times the linecharging current that an overhead line has

    (depending on line voltage).o If a line is long enough the charging current could be

    equal to the total amount of current the line cancarry. This will severely limit its ability to deliverpower.

    C.V.RAMAN GROUP OF INSTITUTIONS40

  • 8/10/2019 Roshan new.ppt

    41/42

    Summary of Costs: Overhead vs.

    Underground

    Transmission: Underground may be 4-20times Overhead.

    Sub transmission: Underground may be 4-20

    times Overhead Distribution: Underground may be 2-10 times

    Overhead

    New underground may be cheaper thanoverhead in special conditions and costs varygreatly from utility to utility and place toplace.

    C.V.RAMAN GROUP OF INSTITUTIONS41

  • 8/10/2019 Roshan new.ppt

    42/42

    THANKS

    PREPARED & PRESENTED BY:

    ROSHAN PRADHAN

    regd no1221227062

    sec-2 , group-c

    sem-7th,year-4th

    ELECTRICAL ENGINEERING