  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    1/18

    SECTION XUL EX-4510 4-1-05 Page 10-1

    REV. 1

    Electronic data processing involves storage, recall and useof information via electronic equipment. Electronic data pro-

    cessing equipment is found in almost every industry today.

    The equipment is very sensitive and operates within minute

    tolerances. Additionally, many computer installations are

    designed with a subfloor area containing data and power

    cable bundles.

    Because of the high dollar valve of the equipment, the data

    managed by that equipment and the productivity provided

    by electronic data processing, rapid detection and efficient

    fire protection are imperative. Time lost to cleanup and ven-

    tilation of a computer room means lost time throughout the

    company, so these areas require a clean, no residue gas

    agent that disperses easily.

    The computer room and subfloor space can be protected

    with an SAPPHIRE suppression system, even when the

    computer room is normally occupied.

    Fires can occur within the computer electrical insulation and

    in the cable bundles in the subfloor. Paper debris that has

    been allowed to accumulate in the subfloor is also a source

    of fuel.

    Computer room/subfloor protection can be accomplished by

    installation of a total flood SAPPHIRE system. The

    system is designed in accordance with the ANSUL design,

    installation manual and NFPA Standard 2001, Standard for

    Clean Agent Fire Extinguishing Systems. It is importantthat an effective agent concentration not only be achieved,

    but shall be maintained for a sufficient period of time to

    allow effective emergency action by trained personnel.

    The SAPPHIRE system consists of a tank(s), a piping

    arrangement and discharge nozzles located in the comput-

    er room, storage room, and subfloor space.

    Occasionally, drainage is installed in the subfloor area.

    Provisions must be made for making the drain piping a

    closed system unless water is present to assist in assuring

    the necessary concentration.

    When the computer room is normally occupied, personnel

    safety is of first concern. Alarms or warning devices mustbe located in the room to provide sufficient annunciation of

    agent discharge. The rooms and subfloor must be tight to

    prevent loss of agent.

    All air handling equipment must be shut down and

    dampered prior to system discharge.

    Smoke detectors, operated by an electronic control panel,

    are usually employed with a SAPPHIRE system to provide

    detection and thus suppression of a fire before it has a

    chance to do serious damage.

    The authority having jurisdiction may have additiona

    requirements.

    HAZARD

    A computer room having dimensions of 33 ft. x 15 ft. x

    10 ft.

    A storage room having dimensions of 12 ft. x 12 ft. x 10 ft

    A subfloor having dimensions of 33 ft. x 15 ft. x 1 ft.

    No unclosable openings.

    Ventilation to be shut down at system actuation.

    Example Computer Room,Storage Room, and Subfloor

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    2/18

    SECTION XUL EX-4510 12-1-03 Page 10-2

    Example Computer Room, Storage Room, and Subfloor

    10 FT.

    10 FT.

    12 FT.

    33 FT.

    1 FT.

    12 FT.

    006891

    15 FT.

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    3/18

    SECTION XUL EX-4510 12-1-03 Page 10-3

    Example Computer Room, Storage Room, and Subfloor

    006905a

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    4/18

    SECTION XUL EX-4510 12-1-03 Page 10-4

    Example Computer Room, Storage Room, and Subfloor

    006905b

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    5/18

    SECTION XUL EX-4510 12-1-03 Page 10-5

    Example Computer Room, Storage Room, and Subfloor

    006905c

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    6/18

    SECTION XUL EX-4510 12-1-03 Page 10-6

    Example Computer Room, Storage Room, and Subfloor

    006905d

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    7/18

    SECTION XUL EX-4510 4-1-05 Page 10-7

    REV. 1

    Example Computer Room, Storage Room, and Subfloor

    006905e

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    8/18

    SECTION XUL EX-4510 12-1-03 Page 10-8

    Example Computer Room, Storage Room, and Subfloor

    006905f

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    9/18

    SECTION XUL EX-4510 12-1-03 Page 10-9

    Example Computer Room, Storage Room, and Subfloor

    006905g

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    10/18

    SECTION XUL EX-4510 12-1-03 Page 10-10

    Example Computer Room, Storage Room, and Subfloor

    006906a

    John M KehoeOne Stanton Street

    Marinette WI 54143-2542Phone: 715-735-7411

    Sapphire Designer ProgramProject: Example

    File Name: Manual1.FLC

    Customer InformationCompany Name: Ansul Incorporated

    Address:

    Phone:

    Contact:

    Title:

    John M. Kehoe

    Project DataProject Name: Example

    Designer:

    Number:

    Account:

    Location:

    Description:

    Anywhere, USA

    Computer Room, Subfloor and Storage Room

    Consolidated Report

    Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated

    Page: 1 9of

    Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    11/18

    SECTION XUL EX-4510 12-1-03 Page 10-11

    Example Computer Room, Storage Room, and Subfloor

    006906b

    Consolidated Report

    Elevation: 4000 ft (relative to sea level)

    Atmospheric Correction Factor: 0.86

    Enclosure Information

    Enclosure Number: 1

    Name: Computer Room

    Enclosure Temperature...

    Minimum: 60 F

    Maximum: 80 F

    Maximum Concentration: 4.388 %

    Design Concentration...

    Adjusted: 4.216 %

    Minimum:

    Minimum Agent Required:

    Width:

    Length:

    Height:

    Volume:

    Non-permeable:

    Total Volume:

    Adjusted Agent Required:

    Number of Nozzles:

    4.200 %

    165.2 lbs

    33.0 ft

    15.0 ft

    10.0 ft

    4950.0 cubic ft

    0.0 cubic ft

    4950.0 cubic ft

    165.8 lbs

    2

    Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated

    Page: 2 9of

    Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    12/18

    SECTION XUL EX-4510 12-1-03 Page 10-12

    Example Computer Room, Storage Room, and Subfloor

    006906c

    Consolidated Report

    Elevation: 4000 ft (relative to sea level)

    Atmospheric Correction Factor: 0.86

    Enclosure Information

    Enclosure Number: 2

    Name: Storage Room

    Enclosure Temperature...

    Minimum: 60 F

    Maximum: 80 F

    Maximum Concentration: 4.386 %

    Design Concentration...

    Adjusted: 4.213 %

    Minimum:

    Minimum Agent Required:

    Width:

    Length:

    Height:

    Volume:

    Non-permeable:

    Total Volume:

    Adjusted Agent Required:

    Number of Nozzles:

    4.200 %

    48.1 lbs

    12.0 ft

    12.0 ft

    10.0 ft

    1440.0 cubic ft

    0.0 cubic ft

    1440.0 cubic ft

    48.2 lbs

    1

    Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated

    Page: 3 9of

    Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    13/18

    SECTION XUL EX-4510 12-1-03 Page 10-13

    Example Computer Room, Storage Room, and Subfloor

    006906d

    Consolidated ReportAgent Information

    Agent: Novec / Propellant N2

    (Novec is a trademark of 3M)

    Adjusted Agent Required: 214.0 lbs

    Container Name: 390 lb Cylinder Assemby

    Container Part Number: 570640

    Number of Main Containers:

    Number of Reserve Containers:

    1

    0

    Manifold: No Manifold

    HorizontalPipe Take Off Direction:

    Agent Per Container: 214.0 lbs

    Fill Density: 41.2 lbs / cubic ft

    Container Empty Weight: 198.2 lbs

    Weight, All Containers + Agent: 412.2 lbs

    Floor Area Per Container: 1.40 square ft

    Floor Loading Per Container: 295 lbs / square ft

    360 psigStarting Pressure:

    Pipe NetworkPart 1 - Pipe

    Description Start End Type Diameter Length Elevation

    Pipe

    Main Cyl. X 1 0 1 2 in 4.44 ft 4.44 ft

    Flex Hose 1 2 2 in 0.39 ft 0.00 ft

    Flex Hose 2 3 2 in 1.71 ft 1.71 ft

    Pipe 3 4 40T 2 in 4.45 ft 4.45 ft

    Pipe 4 5 40T 1-1/4 in 2.25 ft 0.00 ftPipe 5 6 40T 1-1/4 in 1.50 ft 0.00 ft

    Pipe 6 7 40T 1-1/4 in 17.00 ft 0.00 ft

    Pipe 7 8 40T 1-1/4 in 1.25 ft 0.00 ft

    Pipe 8 9 40T 1 in 8.25 ft 0.00 ft

    Pipe/E1-N1 9 10 40T 1 in 0.75 ft -0.75 ft

    Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated

    Page: 4 9of

    Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    14/18

    SECTION XUL EX-4510 12-1-03 Page 10-14

    Example Computer Room, Storage Room, and Subfloor

    006906e

    Consolidated ReportPart 1 - Pipe

    Description Start End Type Diameter Length Elevation

    Pipe

    Pipe 8 11 40T 1 in 8.25 ft 0.00 ft

    Pipe/E1-N2 11 12 40T 1 in 0.75 ft -0.75 ft

    Pipe 5 13 40T 3/4 in 1.00 ft 0.00 ft

    Pipe 13 14 40T 3/4 in 4.25 ft 0.00 ft

    Pipe 14 15 40T 3/4 in 4.50 ft 0.00 ft

    Pipe/E2-N1 15 16 40T 3/4 in 0.75 ft -0.75 ft

    Part 2 - Equivalent LengthStart End 90 45 Thru Side Union Other Added Total

    0 1 0 0 0 0 0 0.00 ft 35.0 ft

    1 2 0 0 0 0 0 2inFlexN1 0.00 ft 0.4 ft

    2 3 1 0 0 0 0 2inFlexN2 0.00 ft 17.2 ft

    3 4 0 0 0 0 0 0.00 ft 4.5 ft

    4 5 1 0 0 0 0 0.00 ft 6.0 ft

    5 6 0 0 1 0 0 0.00 ft 3.8 ft

    6 7 1 0 0 0 0 0.00 ft 20.7 ft

    7 8 1 0 0 0 0 0.00 ft 5.0 ft

    8 9 0 0 0 1 0 0.00 ft 14.0 ft

    9 10 1 0 0 0 0 0.00 ft 3.6 ft

    8 11 0 0 0 1 0 0.00 ft 14.0 ft

    11 12 1 0 0 0 0 0.00 ft 3.6 ft

    5 13 0 0 0 1 0 0.00 ft 5.5 ft

    13 14 1 0 0 0 0 0.00 ft 6.5 ft

    14 15 1 0 0 0 0 0.00 ft 6.7 ft

    15 16 1 0 0 0 0 0.00 ft 3.0 ft

    Part 3 - Nozzles

    Start End Flow Name Size Type Nozzle Area0 1 214.0 lbs

    1 2 214.0 lbs

    2 3 214.0 lbs

    3 4 214.0 lbs

    4 5 214.0 lbs

    5 6 165.8 lbs

    Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated

    Page: 5 9of

    Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    15/18

    SECTION XUL EX-4510 12-1-03 Page 10-15

    Example Computer Room, Storage Room, and Subfloor

    006906

    Consolidated ReportPart 3 - Nozzles

    Start End Flow Name Size Type Nozzle Area

    6 7 165.8 lbs

    7 8 165.8 lbs

    8 9 82.9 lbs

    9 10 82.9 lbs E1-N1 1 in 16 Port - BR 0.2963 square in

    8 11 82.9 lbs

    11 12 82.9 lbs E1-N2 1 in 16 Port - BR 0.2963 square in

    5 13 48.2 lbs

    13 14 48.2 lbs

    14 15 48.2 lbs

    15 16 48.2 lbs E2-N1 3/4 in 16 Port - BR 0.2524 square in

    Parts Information

    Total Agent Required: 214.0 lbs

    Container Name: 390 lb Cylinder Assemby (Part: 570640)

    Number Of Containers: 1

    Field1

    Nozzle Type Diameter Nozzle Area Part Number

    E1-N1 16 Port - BR 1 in 0.2963 square in 570517

    E1-N2 16 Port - BR 1 in 0.2963 square in 570517

    E2-N1 16 Port - BR 3/4 in 0.2524 square in 570516

    Nozzle Drill Diameter Drill Size

    E1-N1 0.1535 inches 3.90 mm

    E1-N2 0.1535 inches 3.90 mm

    E2-N1 0.1417 inches 3.60 mm

    Pipe: Type Diameter Length

    40T 3/4 in 10.50 ft

    40T 1 in 18.00 ft

    40T 1-1/4 in 22.00 ft

    40T 2 in 4.45 ft

    Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated

    Page: 6 9of

    Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    16/18

    SECTION XUL EX-4510 4-1-05 Page 10-16

    REV. 1

    Example Computer Room, Storage Room, and Subfloor

    006906g

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    17/18

    SECTION XUL EX-4510 12-1-03 Page 10-17

    Example Computer Room, Storage Room, and Subfloor

    006906h

    Consolidated ReportMinimumAgent

    RequiredNozzle

    AdjustedAgent

    Required

    PredictedAgent

    Delivered

    NozzlePressure(Average)

    E2-N1 48.1 lbs 48.2 lbs 48.9 lbs 142 psig

    Drawing View: 1

    Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated

    Page: 8 9of

    Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM

  • 8/12/2019 SAPPHIRE Engineered Clean-Agent Manual (PN570590) - Typical Example

    18/18

    SECTION XUL EX-4510 12-1-03 Page 10-18

    Example Computer Room, Storage Room, and Subfloor

    006906i

    Consolidated ReportDrawing View: 5

    Drawing View: 9

    Copyright (c) Hughes Associates, Inc. Licensed to: Ansul Incorporated

    Page: 9 9of

    Calculation Date/Time: Monday, October 20, 2003, 11:35:09 AM