SCADAPack Micro 16

Quick Start Guide

CONTROL MICROSYSTEMS SCADA products... for the distance

48 Steacie Drive Telephone: 613-591-1943

Kanata, Ontario Facsimile: 613-591-1022

K2K 2A9 Technical Support: 888-226-6876

Canada 888-2CONTROL

Page 2: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

1

SCADAPack Micro 16 Quick Start Guide

©2000 - 2005 Control Microsystems Inc. All rights reserved. Printed in Canada.

Trademarks

TeleSAFE, TelePACE, SmartWIRE, SCADAPack, TeleSAFE Micro16 and TeleBUS are registered trademarks of Control Microsystems Inc.

All other product names are copyright and registered trademarks or trade names of their respective owners.

Material used in the User and Reference manual section titled SCADAServer OLE Automation Reference is distributed under license from the OPC Foundation.

Page 3: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

2

Table of Contents

1 OVERVIEW .................................................................................................... 3

2 IMPORTANT SAFETY INFORMATION ......................................................... 4

3 QUICK-START PROCEDURE ....................................................................... 5

3.1 1. Connect Input Power ................................................................................ 5

3.2 2. Power Up In Cold Boot Mode .................................................................... 5

3.3 3. Connect Computer to TeleSAFE Micro 16 ................................................ 5

3.4 4. Install TelePACE Software ........................................................................ 6

3.5 5. Configure Computer Serial Port ................................................................ 6

3.6 6. Select Controller Type............................................................................... 7

3.7 7. Configure Register Assignment ................................................................ 7

3.8 8. Configure Controller Serial Ports .............................................................. 8

3.9 9. Program Ladder Logic............................................................................... 9

3.10 10. Configure Monitor List .............................................................................. 9

3.11 11. Write Ladder Logic to the Controller ........................................................ 9

3.12 12. Monitor On Line Mode ............................................................................. 9

4 TROUBLESHOOTING ................................................................................. 11

Page 4: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

3

1 Overview

This document is meant to be a guide to help new users configure, program and operate the

TeleSAFE Micro 16 controller, in a timely fashion. It is not meant as a substitute for the TelePACE

Ladder Logic and TeleSAFE Micro 16 Controller manuals, but rather as a companion to these

manuals. A strong background in both programmable logic controllers (PLC) and personal

computers (PC) using Windows is highly recommended. If any problems arise during the setup, it

may be necessary to then consult the appropriate manual or call the Control Microsystems Technical

Support Department for assistance.

Page 5: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

4

2 Important Safety Information

Power, input and output (i/o) wiring must be in accordance with Class I, Division 2 wiring methods

Article 501-4 (b) of the National Electrical Code, NFPA 70 for installations in the U.S., or as

specified in Section 18-1J2 of the Canadian Electrical Code for installations within Canada and in

accordance with the authority having jurisdiction.

WARNING ! EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY

IMPAIR SUITABILITY FOR CLASS 1, DIVISION 2.

WARNING ! EXPLOSION HAZARD – WHEN IN HAZARDOUS LOCATIONS, TURN

OFF POWER BEFORE REPLACING OR WIRING MODULES.

WARNING ! EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS

KNOWN TO BE NONHAZARDOUS.

Page 6: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

5

3 Quick-Start Procedure

3.1 Connect Input Power

Connect the 16Vrms or 24V wiring to the AC/DC PWR IN terminals on the 5203/5204 board. Do

not apply power to the controller at this time.

3.2 Power Up In Cold Boot Mode

This procedure initializes the serial communication parameters and the I/O database registers to

their default values, erases the Register Assignment, Ladder Logic and C programs, and unlocks

the controller.

Hold down the LED POWER button.

Apply power to the Micro 16 controller.

Continue holding the LED POWER button for 25 seconds until the STAT LED begins to flash

on and off continuously.

Release the LED POWER button.

3.3 Connect Computer to TeleSAFE Micro 16

Connect a null modem cable from the computer serial port to com2 on the TeleSAFE Micro 16

controller board.

LED Power

Button

AC/DC PWR IN

Terminals

Page 7: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

6

3.4 Install TelePACE Software

Insert TelePACE Programming Software Diskette #1 into the computer floppy diskette drive and run

the setup.exe file included on this diskette. Follow the instructions and install the TelePACE

Programming Software to the computer hard drive.

3.5 Configure Computer Serial Port

Open the TelePACE program and select Communications – PC Serial Port Settings from the

pull-down menu bar.

Select the Default button (lower right side of dialog box) and then change the Port (upper right

side of dialog box) to reflect the computer serial port assignment.

Select OK to close the dialog box.

com2

Null Modem

Cable

Page 8: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

7

3.6 Select Controller Type

Select Controller – Type and choose Micro 16.

3.7 Configure Register Assignment

Make a list of all I/O modules that are to be connected to the TeleSAFE Micro 16 controller. Include

5000 Series modules as well as on-board I/O modules.

Select Controller – Register Assignment.

If 5000 Series modules are to be used, select ADD and enter the module which corresponds to

the particular 5000 Series module. Select a module address from the Address box and ensure

that the 5000 Series module’s dipswitch settings correspond to this address. Enter an appropriate

Modbus register address in the Start box. Repeat this step for each 5000 Series module.

If on-board modules are to be used, select ADD and enter the module which corresponds to the

particular on-board module. Enter an appropriate Modbus register address in the Start box.

Repeat this step for each on-board module.

Page 9: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

8

The following example is a completed Register Assignment for a TeleSAFE Micro 16 controller

with an on-board DIN 5203/4 digital inputs module and an AIN 5501 analog input module,

addressed as 0.

3.8 Configure Controller Serial Ports

Select Controller – Serial Ports and modify the settings for com1, if applicable.

The following example shows how com1 would be programmed to communicate via an external

dial-up modem.

Page 10: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

9

Controller serial port com2 is being used to write the ladder logic to the controller. It is

recommended, therefore, that the settings for com2 not be modified at this time. Any changes to the

com2 settings will disrupt the program download and cause a serial communication failure.

3.9 Program Ladder Logic

Program the ladder logic code for your application. Refer to the TelePACE Ladder Logic User

Manual for more information.

3.10 Configure Monitor List

Select Edit – Monitor List and add the registers that are to be monitored to the Monitor Addresses

list on the right side of the dialog. This is accomplished, by either selecting addresses from the

Addresses in Use list, and then selecting the Addresses >> button, or by entering a range of

consecutive registers into the First Register and Last Register boxes, and then selecting the

Range>> button.

A completed Monitor List may appear like this:

3.11 Write Ladder Logic to the Controller

Select Communications – Write to Controller and write the ladder logic to the controller by

selecting Start from the dialog.

3.12 Monitor On Line Mode

Select Activity – Monitor Online and follow the screen prompts:

To Log On to the Controller, select Start.

Page 11: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

10

To Switch to Debug to monitor the program execution, select Yes.

The following Monitor List will appear and display the registers that were added to the Monitor List

in step 11.

The Quick-Start procedure is complete!

Page 12: SCADAPack Micro16 Quick Start

SCADAPack Micro 16 Quick Start Guide

October 19, 2007

11

4 Troubleshooting

If any problems occur at any step in the procedure, review the pertinent steps to ensure that they

have been followed correctly. If you are unable to resolve the problem, please contact the technical

support department at Control Microsystems for further assistance.

Toll Free Technical Support

Users in Canada and the United States may call our technical support department free of charge.

You will be connected to the nearest support center to your time zone.

Telephone: 1-888-226-6876 (1-888-2CONTROL)

Kanata Technical Support Center

Telephone, facsimile and e-mail support are available from 8:00 to 18:30 (North American Eastern

Time Zone) at the following numbers. When calling, please ask for a Technical Support

Representative.

Telephone: 1-613-591-1943

Facsimile: 1-613-591-3145

E-Mail: [email protected]

Mailing Address: Control Microsystems

48 Steacie Drive

Kanata, Ontario, Canada

K2K 2A9