  • June

    201

    1

    SHARYLANDLOMAALTAHVDCPROJECT

    CONFIDENTIALSTRATEGICPROJECTSB&VENERGY

  • 2

    ContentsHVDCTechnologyCostEstimates&ScheduleConclusions&NextSteps

  • 3

    HVDCTECHNOLOGY

  • 4

    Technology:WhyHVDC?

    Powerflowiscontrollable BypassescongestedACcircuitsw/oinadvertentflow

    BipoleDCperformssimilartodblckt AClineundercontingencies

    Protectsagainstcascadingoutages Powerflowcanbemaintainedatreducedlevelsduringlossofonepolebyswitchingtomonopolewithmetallicreturn

    Cancarrymorepowerwithreducedlossesforagivensizeofconductor

    LowercostperMWofdeliveredcapacity($/MW)forlargesystems

  • 5

    Technology:VoltageSourceConverters VSCmarketedasHVDCLightbyABBandasHVDCPlusbySiemens

    InsulatedGateBipolarTransistor(IGBT)technologydoesnotrequirestrongACsourcesforcommutation

    LowShortCircuitratiorequirements Doesnothaveminimumtransferrequirements Minimalfilteringisrequiredattheterminals Smallerterminalfootprintandeasiertoharden toimprovereliability

    Presenttechnologybeingusedonundergroundandsubmarinelinesbuthaslimiteduseandexperienceonoverheadlines

    Allowsuseofsoliddielectriccabletechnologyforsubmarinecables

  • 6

    Technology:ClassicHVDC

    Extensivetrackrecordupto800kV ConverterterminalstypicallylessexpensivethanVSCterminalsbutreactivecompensationrequirementsdriveupcosts

    ThyristorvalvetechnologyrequiresstrongACsourcesforcommutation

    HigherShortCircuitratiorequirementsoftenresultinginneedforsynchronouscondensersorotherdevices

    Minimumtransferrequirements Filteringrequiredattheterminals Largefootprintrequiredatterminals

  • 7

    Technology:WhyMetallicReturn? Improvedoperationalreliabilityandflexibility Bipoleoperationdoesnotrequireseparatereturnpath;monopoleoperationwillrequirereturnpath

    Sustaineduseofearthreturnduringmonopoleoperationoftennotpermittedforenvironmentalreasons(e.g.impactonotherburiedutilities)

    Plannedevents,suchasplannedmaintenance,requiringsustainedmonopoleoperationmayusemetallicreturn

    MetallicreturnconfigurationachievedbycontrolledswitchingproceduresMetallicreturncanincludeaseparatereturnconductororcanbeimplementedbyswitchingtotheremainingunusedpoleifserviceable

    Unplannedeventsmayuseearthreturnforinitialperiod(minutes)andthenswitchtometallicreturn(hourstoweeks)

  • 8

    Technology:ExampleSubmarineProjects

    ProjectName: CrossSoundLocation: NewYork Conn.Voltage: 150kVHVDCCapacity: 330MWTechnology: ABBHVDCLight(VSC)SeaRoute: 25milesLandRoute: 1mileProjectStatus: Incommercialoperation

    since2002

  • 9

    Technology:ExampleSubmarineProjects

    ProjectName: TransBayLocation: SanFranciscoBayVoltage: 200kVHVDCCapacity: 400MWTechnology: SiemensHVDCPlus(VSC)SeaRoute: 53milesLandRoute: 1mileProjectStatus: Incommercialoperation

    since2010

  • 10

    Technology:ExampleSubmarineProjects

    ProjectName: BorWin1Location: NorthSeaVoltage: 150kVHVDCCapacity: 400MWTechnology: ABBHVDCLight(VSC)SeaRoute: 77milesLandRoute: 46milesProjectStatus: Incommercialoperation

    since2009

  • 11

    Technology:ExampleSubmarineProjects

    ProjectName: DolWin1Location: NorthSeaVoltage: 320kVHVDCCapacity: 800MWTechnology: ABBHVDCLight(VSC)SeaRoute: 46milesLandRoute: 56milesProjectStatus: 2013Completion

  • 12

    Technology:ExampleSubmarineProjects

    ProjectName: SylWin1Location: NorthSeaVoltage: 320kVHVDCCapacity: 864MWTechnology: SiemensHVDCPlus(VSC)SeaRoute: 99milesLandRoute: 28milesProjectStatus: 2014Completion

  • 13

    Technology:ExampleSubmarineProjects

    ProjectName: MAPPLocation: ChesapeakeBayVoltage: 320kVHVDCCapacity: 2000MWTechnology: ABBHVDCLight(VSC)SeaRoute: 39milesLandRoute: 44milesProjectStatus: 2015Completion

  • 14

    Technology:ExampleSubmarineProjects

    ProjectName: AtlanticWindConnection

    Location: MidAtlanticCoastVoltage: 320kVHVDCCapacity: 7000MW(total)

    2000MW(maxperprojectphase)

    Technology: VSCSeaRoute: ~600milesLandRoute: ~50milesProjectStatus: 20162020

    StagedCompletion

  • 15

    Technology:SubmarineCableInstallationCableLaying CableBurialPlowing

  • 16

    COSTESTIMATES&SCHEDULE

  • 17

    OrderofMagnitudeCostEstimates

    Costestimatesinclude:HVDCconverterstationsACsubstationsadjacenttoeachconverterstationSynchronouscondensersatsouthernterminalforHVDCClassicLatticetowerstructuresand2conductorsperpoleonoverheadoption1cableperpoleonunderground/submarineoptionMetallicneutralcable

    Costestimatesdonotinclude:UpgradestoexistingsystemnotincludedinthereportCostofremoteinterconnectionCostofrightofway/siteOwnerscosts Development/permittingcosts

    CCNProcess Financingcosts Constructionmanagement

  • 18

    EstimatedProjectCost OverheadOptionVSC Technology HVDC Classic

    GeneralPeak Delivered Power (MW) 1000 1000Line Voltage +/- 320 kV HVDC +/- 400 kV HVDCMiles of Bipole HVDC Overhead Lines 220 220

    Line RatingLine Losses at Peak Line Loading 3.2% 2.0%Terminal Losses at Peak Load (2 Terminals) 2.0% 1.5%Total Peak Losses 5.2% 3.5%Conductor Rating (MW) 1,052 1,035Conductor Size Per Pole (2) 1943 TWD (2) 1943 TWD

    Total Project Capital CostsBipole HVDC Overhead Lines ($M) $264 $266Two HVDC Converter Stations ($M) $300 $260AC Substations ($M) $40 $40Reactive Compensation [Synch. Cond.] ($M) $0 $60System Impacts ($M) TBD TBD

    Total Capital Cost ($M) $604 $626

    Capital Cost per MW of Delivered Capacity ($/MW) $604,000 $626,000

    Furthercostoptimizationofconverterswouldreduceprojectcost

  • 19

    EstimatedProjectCost SubmarineOptionGeneral

    Peak Delivered Power (MW) 1000Line Voltage +/- 320 kV HVDCMiles of Alignment 160Miles of Bipole HVDC Submarine Lines 150Miles of Bipole HVDC Underground Lines 10

    Line RatingLine Losses at Peak Line Loading 5%Terminal Losses at Peak Load (2 Terminals) 2%Total Peak Losses 7%Cable Rating (MW) 1,070Submarine Cable Size Per Pole (1) 2400 mm CUUnderground Cable Size Per Pole (1) 2500 mm CU

    Total Project Capital CostsBipole HVDC Submarine Lines ($M) $525Bipole HVDC Underground Lines ($M) $45Two HVDC Converter Stations ($M) $300AC Substations ($M) $41System Impacts ($M) TBD

    Total Capital Cost ($M) $911

    Capital Cost per MW of Delivered Capacity ($/MW) $911,000

    Furthercostoptimizationofconverterswouldreduceprojectcost CablecostsbasedonlongestdistancetoNorthernTerminal

  • 20

    HighLevelSchedule OverheadOption

    - - - - -

    - - - - - - - - -

    - - - - - - - - - - -

    - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    Detailed Design

    Equipment & Material Procurement

    Preliminary Design and Studies

    Preliminary Project Approvals

    EIS Activities

    Land Rights

    2 3 4

    Project Definition

    20131 2 3 4 2 3 4

    20151 2 3 4

    20161

    Construction Procurement

    Construction

    20121 2 3 4

    CCN Activities

    20111

    20141 2 3 4

  • 21

    HighLevelSchedule SubmarineOption

    - - - - -

    - - - - - - - - -

    - - - - - - - - - - -

    - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

    20141 2 3 4

    Construction Procurement

    Construction

    20121 2 3 4

    CCN Activities

    2 3 4

    20151 2 3 4

    20161

    20131 2 3 4

    20111 2 3 4

    Project Definition

    Preliminary Design and Studies

    Preliminary Project Approvals

    EIS Activities

    Land Rights

    Detailed Design

    Equipment & Material Procurement

  • 22

    CONCLUSIONS&NEXTSTEPS

  • 23

    Conclusions BothSubmarineandOverheadOptions:

    Providefullycontrollable1,000MWcapability,andabilitytomanagecongestedACcircuits

    Protectsagainstcascadingoutages Cancarrymorepowerwithreducedlossesforagivensizeofconductor

    LowercostperMWofdeliveredcapacity($/MW)forlargesystems

    SubmarineOption:MostreliablealternativetoERCOTforcoastalregionMostreliablealternativetoERCOTforcoastalregionHVDC/VSCisthepreferredchoiceforsubmarinetransferofHVDC/VSCisthepreferredchoiceforsubmarinetransferof1000MW1000MW

    GridconnectedHVDCoptionsatLomaAlta,Pawnee,andCorpusChristiarea(WhitePoint,LasBrisas orBarneyDavis)appeartobeviable

  • 24

    NextSteps

    RecommendERCOTtoperformUPLANbasedeconomicassessment IdentifyproductioncostsavingsfollowingincorporationHVDClinevs.ACsolutions

    ReviewPowerSystemStudiestodetermineoptimalcapacityandperformancerequirements ACpowerflowanalysis Reactivepowerrequirementsofexistingsystem Assessmostviabletechnology(HVDCorHVDClight)forPawneeproject

    DynamicandSSTIAnalysis Performfield/routeconstraintsreviewandupdatepreliminaryrouteandpermittingrequirements

    Updatecostestimates