siemens relay configuration

Upload: mohamed-wahid

Post on 03-Jun-2018

260 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/12/2019 Siemens Relay Configuration

    1/28

    SIEMENS RELAY 7SA522 CONFIGURATION

    Select the file and open new. The below display is appeared.

    Now the new file is created for the project.

    Enter name of

    the project and

    select ok.

  • 8/12/2019 Siemens Relay Configuration

    2/28

    Now select the folder right click and select Insert new device and Siprotec devices.

    Now select the Type and Version of the relay and drag it to the folder.

  • 8/12/2019 Siemens Relay Configuration

    3/28

    Now feed the M!" n#mber which is available in the relay Settings$Set#p%

    E&tra$M!" version and then press '(.

  • 8/12/2019 Siemens Relay Configuration

    4/28

    'nce M!" n#mber is done. The relay type and version is displayed.

  • 8/12/2019 Siemens Relay Configuration

    5/28

    Now select the relay type then right click and initiali)e device.

    Select connection type *irect and comm#nication port then press '(.

  • 8/12/2019 Siemens Relay Configuration

    6/28

    Now the +, will comm#nicate with the relay and the following screen will appear.

    Select -ES

  • 8/12/2019 Siemens Relay Configuration

    7/28

    Now enter the +SS/'0* 111111

    Then press '(.

  • 8/12/2019 Siemens Relay Configuration

    8/28

    +ress '(.

  • 8/12/2019 Siemens Relay Configuration

    9/28

    Now right click on the type of the relay and select '+EN '"2E,T.

    The above screen will appear and select *irect and press '(.

  • 8/12/2019 Siemens Relay Configuration

    10/28

    Now the relay is ready for changing the parameters.

    *o#ble click on settings.

  • 8/12/2019 Siemens Relay Configuration

    11/28

    Select the *evice config#ration and do#ble click. !#nctional settings display will be

    opened.

  • 8/12/2019 Siemens Relay Configuration

    12/28

    !or programming "inary inp#ts$"inary o#tp#ts$E*3s select Masking I$'

    ,onfig#ration and do#ble click.

    Select the f#nction and

    change it toEnable$*isable

  • 8/12/2019 Siemens Relay Configuration

    13/28

    Select the f#nction for which "inary o#tp#t has to config#red. 0ight click and select

    ctive with voltage$ctive with o#t voltage.

    Select

    and

    do#bleclick.

  • 8/12/2019 Siemens Relay Configuration

    14/28

    Select the f#nction for which the '#t p#t relay has to config#red4 then right click and

    select atched$5nlatched.

    Select and

    do#ble click.

  • 8/12/2019 Siemens Relay Configuration

    15/28

    Select the f#nction for which the E* has to be config#red4 then right click and select

    for atched$5n latched.

    Select and do#ble click

  • 8/12/2019 Siemens Relay Configuration

    16/28

    ,!, config#ration.

    Then edit the information as per the system re6#irement.

    0ight click here and select Insert

    information.

  • 8/12/2019 Siemens Relay Configuration

    17/28

    'nce this is done. Then this signal has to be config#red for ,!, IN and '5T.

    Same way do it for ,!, o#t.

    Select the type of o#tp#t

    re6#ired for ,!, and drag it .

    Edit the label.

    0ight click and select

    ,onfig#red.

    *rag it to

    this place.

  • 8/12/2019 Siemens Relay Configuration

    18/28

    Then close this window and go to main men# select ,!, and do#ble click.

    0ight click and select

    ,onfig#red.

  • 8/12/2019 Siemens Relay Configuration

    19/28

    *o#ble click here.

    *o#ble click on this.

    Select the page here.

  • 8/12/2019 Siemens Relay Configuration

    20/28

    'nce the f#nction is selected4 Then yo# have to select the n#mber of inp#ts to be #sed

    for the f#nction.

    Select the f#nction.

    *rag it here.

  • 8/12/2019 Siemens Relay Configuration

    21/28

    'nce No. of inp#ts are selected then press '(.

    0ight click on

    this and select

    No. of inp#ts

    Enter No. of

    inp#ts to be

    #sed.

  • 8/12/2019 Siemens Relay Configuration

    22/28

    Now select the page in which ogic gates are available. Then )oom it #ntil

    Inp#t$'#tp#ts appear.

    Now select the inp#t then right click and select the gro#p to be connected.

    Select the page.

    7oom it #ntil the

    f#nction block inp#t

    and o#tp#t appear.

    0ight click on the

    inp#t.

    Select the gro#p

    to be connected

    to the inp#t.

    Select here.

  • 8/12/2019 Siemens Relay Configuration

    23/28

  • 8/12/2019 Siemens Relay Configuration

    24/28

    Select power system data8.

    Select and

    do#ble click.

  • 8/12/2019 Siemens Relay Configuration

    25/28

    Select settings 9ro#p and enter the relay settings.

  • 8/12/2019 Siemens Relay Configuration

    26/28

  • 8/12/2019 Siemens Relay Configuration

    27/28

    fter changing the settings down load in to the relay.

    Select to down

    load settings.

    Enter password

    and press '(.

  • 8/12/2019 Siemens Relay Configuration

    28/28

    Select -ES to save