specifications historic peacock house and lodge

120
COUNCIL ITEM 7 i OATlr SPECIFICATIONS for the HISTORIC PEACOCK HOUSE AND LODGE STRUCTURE MOVE AND RENOVATION Prepared for The City of Port St. Lucie February 2018 Prepared by: Bender & Associates Architects, P.A. Key West, Florida

Upload: others

Post on 01-Feb-2022

2 views

Category:

Documents


0 download

TRANSCRIPT

COUNCIL ITEM

7 iOATlr

SPECIFICATIONSfor the

HISTORIC PEACOCK HOUSE AND LODGESTRUCTURE MOVE AND RENOVATION

Prepared for

The City of Port St. LucieFebruary 2018

Prepared by:

Bender & Associates Architects, P.A.Key West, Florida

HISTORIC PEACOCK HOUSE AND LODGE

SECTION 00005TABLE OF CONTENTS

INTRODUCTORY PAGES

CITY OF PORT ST. LUCIE BIDDING AND CONTRACT REQUIREMENTS

LEAD BASED PAINT REPORT

MOLD / INDOOR AIR QUALITY REPORT

ASBESTOS SURVEY

GEOTECHNICAL REPORT

00005

TABLE OF CONTENTS

SPECIFICATIONS

DIVISION 1 - GENERAL REQUIREMENTS

01010

SUMMARY OF WORK

01015

CONTRACTOR ' S USE OF THE PREMISES

01045

CUTTING AND PATCHING

01100

ALTERNATES

01340

SUBMITTALS AND SUBSTITUTIONS

01640

PRODUCT HANDLING

01700

CONTRACT CLOSEOUT

01710

CLEANING

DIVISION 2 - SITE WORK

02070

SELECTIVE DEMOLITION

DIVISION 3 - CONCRETE

03300

CAST IN PLACE CONCRETE

TABLE OF CONTENTS

HISTORIC PEACOCK HOUSE AND LODGE

DIVISION 4 - MASONRY

04220

CONCRETE UNIT MASONRY

04500

MASONRY RESTORATION AND CLEANING

DIVISION 5 - METALS

05500

METAL FABRICATIONS

DIVISION 6 - WOOD AND PLASTICS

06100

ROUGH CARPENTRY

06200

FINISH CARPENTRY

DIVISION 7 -THERMAL AND MOISTURE PROTECTION

07310

ASPHALT SHINGLE ROOFING

07317

WOOD SHINGLE ROOFING

07600

FLASHING AND SHEET METAL

07920

SEALANTS AND CAULKING

DIVISION 8 - DOORS AND WINDOWS

08610

WOOD WINDOWS

08800

GLASS AND GLAZING

DIVISION 9 - FINISHES

09900 PAINTING

DIVISION 10 - SPECIALTIES

NOT USED

TABLE OF CONTENTS

HISTORIC PEACOCK HOUSE AND LODGE

DIVISION 11- EQUIPMENT

NOT USED

DIVISION 12 - FURNISHINGS

NOT USED

DIVISION 13 - SPECIAL CONSTRUCTION

NOT USED

DIVISION 14 - CONVEYING SYSTEMS

NOT USED

DIVISION 15 - MECHANICAL

NOT USED

DIVISION 16 - ELECTRICAL

16010 BASIC ELECTRICAL REQUIREMENTS

END OF SECTION

TABLE OF CONTENTS

ENVIRONN TAL SERVICES, LLC

LEAD-BASED PAINT SURVEY REPORT

FOR

FORMER HISTORIC PEACOCK RANCH(PEACOCK HOUSE & BARN - PEACOCK LODGE)

CANAL C-124 & GLADES CUT OFF ROAD (VERANO PROPERTY)PORT ST. LUCIE WEST, FLORIDA

Prepared for

BENDER & ASSOCIATES ARCHITECTS410 ANGELA STREET

KEY WEST, FLORIDA 33040

ATTENTION: MR. BERT BENDER

Prepared by

Hiram A. AguiarEPA Lead Risk Assessor Certificate #FL-R-9781-1

EEEE&G Environmental Services, LLC

5751 Miami Lakes DriveMiami Lakes, Florida 33014

(305) 374-8300www.eeandg.com

December 20, 2017EE&G Project No. 2017-2448 LBP

EEbG: Lead-Based Paint Inspection Report December 20, 2017

CONTENTS

Section

Pacie

1.0 - INTRODUCTION 1

1.1

INTRODUCTION 11.2

OWNER INFORMATION 11.3

EDUCATIONAL MATERIALS 1

2.0 - BUILDING DESCRIPTION 2

3.0 - METHODS AND LIMITATIONS 3

3.1

XRF METHODS 33.2

LIMITATIONS 3

4 .0 - INSPECTION FINDINGS 5

4.1

XRF TESTING RESULTS 5

5.0 - RECOMMENDATIONS 6

5.1

RECOMMENDATIONS FOR LEAD-BASED PAINT 65.2 RECOMMENDATIONS FOR OTHER PAINTS AND COATINGS 65.3

OSHA COMPLIANCE 65.4

DISCLOSURE OF LBP HAZARDS 7

6.0 - SIGNATURE PAGE 8

APPENDICES

APPENDIX A Renovate Right-Important Lead Hazard Information for Families, Child CareProviders, and Schools

APPENDIX B XRF Testing DataAPPENDIX C PhotographsAPPENDIX D Certificates

HISTORIC PEACOCK RANCH LBP REPORT

EEbG: Lead-Based Paint Inspection Report December 20, 2017

SECTION 1.0

INTRODUCTION

1.1

INTRODUCTION

At the request of Bender & Associates Architects (Client), EE&G Environmental Services, LLC(EE&G) conducted Lead-Based Paint (LBP) testing of the historic Peacock House and Ranchlocated at Canal C-124 and Glades Cut of Road in Port St. Lucie West, Florida. The surveywas conducted on December 6, 2017 by Environmental Protection Agency (EPA) Lead-BasedPaint Risk Assessor Hiram Aguiar of EE&G. EE&G's scope of work for this project consisted ofevaluating the subject facility utilizing an X-Ray Fluorescence (XRF) instrument to assess forlead concentrations in selected painted building components in preparation of upcomingrenovations.

1.2 OWNER INFORMATION

CITY OF PORT ST. LUCIEPORT ST. LUCIE, FL

1.3 EDUCATIONAL MATERIALS

A copy of Renovate Riqht: Important Lead Hazard information for Families, Child CareProviders, and Schools has been provided in Appendix A of this report. Federal law requiresthat individuals receive certain information before renovating more than two square feet ofpainted surfaces in housing, child care facilities and schools built before 1978.

• Homeowners and tenants: renovators must give you this pamphlet beforestarting work.

• Child-care facilities, including preschools and kindergarten classrooms, and thefamilies of children under the age of six that attend those facilities: renovatorsmust provide a copy of this pamphlet to child-care facilities and generalrenovation information to families whose children attend those facilities.

Federal law requires contractors that disturb lead-based paint in homes, child care facilities andschools built before 1978 to be certified and follow specific work practices to prevent leadcontamination. Contractors must provide certification prior to renovations.

HISTORIC PEACOCK RANCH LBP REPORT

1

EE&G:Lead-Based Paint Inspection Report

December 20, 2017

SECTION 2.0

BUILDING DESCRIPTION

FORMER HISTORIC PEACOCK HOUSE & BARN

PEACOCK HOUSE

The two-story Victorian-style home was observed to be constructed primarily of wood and metalon concrete footings; interior walls were observed to be finished with painted plaster board;ceilings were finished with painted plaster board and finished wood. Floors were observed to befinished with linoleum, vinyl floor tile, carpet, and ceramic tile on wood. No heating ventilationand air-conditioning (HVAC) system was observed. The exterior walls were observed to bepainted wood. The roof was observed to be finished with asphalt shingles. According to theclient the home also incudes an attached addition built years later. County records for year builtand square footage were not available at the time of this inspection.

PEACOCK BARN

The one-story barn structure was observed to be constructed primarily of wood and metal; nointerior paint was observed on the interior wood walls, ceiling, and doors at time of theinspection. Floors were observed to be unfinished concrete slab. No heating ventilation and air-conditioning (HVAC) system was observed. The exterior walls were observed to be paintedwood. The roof was observed to be finished with asphalt shingles. County records for year builtand square footage were not available at the time of this inspection.

PEACOCK LODGE

The one-story Victorian-style home was observed to be constructed primarily of wood and metal;interior walls were observed to be finished with painted plaster board and finished wood. Theinterior floors and ceilings were finished wood. The heating ventilation and air-conditioning(HVAC) system was insulated fiber-glass sheet metal or fiberglass flex duct. The exterior wallswere observed to be painted wood. The roof was observed to be finished with asphalt shingles.County records for year built and square footage were not available at the time of this inspection.

HISTORIC PEACOCK RANCH LBP REPORT

2

EEbG: Lead-Based Paint Inspection Report

December 20, 2017

SECTION 3.0

METHODS AND LIMITATIONS

3.1 XRF METHODS

The limited inspection was performed based on a modified version of the protocol established inthe "Guidelines for the Evaluation and Control of Lead-Based Paint Hazards in Housing" by theDepartment of Housing and Urban Development (HUD) in June 1995. A portable spectrumanalyzing XRF instrument manufactured by Innov-X Systems (Alpha Series) was utilized toperform a LBP inspection of suspect interior and exterior painted building components. The XRFserial number is 5512.

The XRF instrument performs a self-calibration test on startup. The calibration was then verifiedusing a known standard from the United States Department of Commerce National Institute ofStandards and Technology (NIST). QA/QC measurements were taken with the Level III (1.04mg/cm2) NIST standard at the beginning and end of the inspection. XRF test results expressedlead concentrations in milligram per square centimeter (mg/cm 2). The results were stored in theXRF for later retrieval in a spreadsheet format.

XRF testing locations, or testing combinations, were determined on site by an EPA CertifiedLead-Based paint Inspector and the following factors; location (e.g. Building, Floor, Unit, Room),component (e.g. Wall, Ceiling, Door, Door Frame, Baseboard, etc.), substrate (e.g. Drywall,Concrete, Wood, Metal, etc.), and painting history (if available). An XRF reading was obtainedfrom selected testing combinations.

The United States Environmental Protection Agency (EPA) defines lead based paint (LBP) aspaint or coatings with a result at or greater than 1.0 mg/cm 2 , 0.5 %/Wt. or 5,000 parts per millionwhen measured by Flame AAS. The Occupation Safety and Health Administration (OSHA)considers measurable quantities of lead in paints and coatings to be lead-containing. Due tothe potential for lead dust to be generated or migrate beyond the work area duringrenovation/demolition activities, both the EPA and OSHA criteria were used to interpret data.The EPA's Lead Renovation, Repair and Painting Rule (RRP Rule) guides contractors who willbe conducting activities that will impact LBP but is not intended to be used to abate, mitigate orcompletely remove lead-containing materials. Those activities are regulated in the ToxicSubstances Control Act (TSCA) sections 402/404.

3.2

LIMITATIONS

The limited inspection was conducted to assess painted building components for the presenceof lead. Because of limitations in access this inspection can not be utilized as a Lead-BasedPaint Inspection as defined in the HUD Guidelines, that is beyond the intent and scope of thislimited inspection. The inspected areas are assumed to be representative of the materials usedthroughout the facility. This limited inspection report has been prepared by EE&G in a mannerconsistent with industry standards exercised by members of the profession practicing undersimilar conditions. No other warranty, expressed or implied is made. Under no circumstances isthis limited inspection report to be utilized as a bid proposal or a project specification document,HISTORIC PEACOCK RANCH LBP REPORT

3

EE1G:Lead-Based Paint Inspection Report December 20, 2017

as this is not its intent. The intent of this inspection report is to assist the client in assessing forlead in selected painted building components.

EPA and HUD define lead-based paint (LBP) as; paint or other coatings that contain lead at orgreater than the level of 1.0 mg/cm 2 or 0.5% by weight; however, the US Department of Labor'sOccupational Safety and Health Administration (OSHA) lead regulation, 29 CFR 1926.62, doesnot recognize a concentration of lead in paint that may be safe for workers therefore,measurable amounts of lead are considered to be a potential source of exposure. Thisassessment can be utilized to identify building components that contain lead. However, asOSHA does not recognize the absence of lead through XRF, this assessment can not beutilized for establishing that coatings are lead-free for purposes of OSHA compliance.

EE&G's interpretations and recommendations are based upon the results of the XRF testing,environmental regulations, and quality control and assurance standards. The results,conclusions, and recommendations contained in this report pertain to conditions observed at thetime of the inspection. Other conditions elsewhere at the subject facility may differ from those inthe inspected locations and, such conditions are unknown, may change over time, and have notbeen considered.

This report was prepared solely for the use of EE&G's client, and is not intended for use by thirdparty beneficiaries. The client shall indemnify and hold EE&G harmless against any liability forany loss arising out of or relating to reliance by any third party on any work performed thereunder, or the contents of this report. EE&G will not be held responsible for the interpretation oruse by others of data developed pursuant to the compilation of this report, or for use ofsegregated portions of this report.

HISTORIC PEACOCK RANCH LBP REPORT

4

EEbG:Lead-Based Paint Inspection Report

December 20, 2017

SECTION 4M

INSPECTION FINDINGS

4.1 XRF TESTING RESULTS

HUD defines LBP as; paints or coatings with lead concentrations equal to or greater than 1.0mg/cm2 when measured by XRF. The following components were identified as LBP during thisinspection:

DESCRIPTION:LOCATION:COLORXRF NUMBER:CONDITION:

DESCRIPTION:LOCATION:COLORXRF NUMBER:CONDITION:

DESCRIPTION:LOCATION:COLORXRF NUMBER:CONDITION:

DESCRIPTION:LOCATION:COLORXRF NUMBER:CONDITION:

DESCRIPTION:LOCATION:COLORXRF NUMBER:CONDITION:

DESCRIPTION:LOCATION:COLORXRF NUMBER:CONDITION:

Exterior wood wallsOriginal HouseWhite3, 4, 67, 69Areas with peeling/chalking

Exterior wood ceilingOriginal House - PorchBlue5Areas with peeling/chalking

Paint on Exterior Wood Window/window framesOriginal House - Exterior wood window/window FramesWhite/light green7,8,9,11Peeling/chalking

Paint/glazing on ceramic tileOriginal house - South bathroomWhite35Intact

Paint/glazing on metal sinksHouse Addition - South bathroomsWhite38, 40Intact

Paint/glazing on metal bath tubHouse Addition South bathroomWhite36, 41Intact

HISTORIC PEACOCK RANCH LBP REPORT

5

EEbG:Lead-Based Paint Inspection Report December 20, 2017

DESCRIPTION:

Paint/glazing on ceramic toiletLOCATION:

House Addition - South bathroomCOLOR

WhiteXRF NUMBER:

64CONDITION:

Intact

Additional similar components should be assumed to be LBP. Testing combinations and XRFresults are presented in Appendix B.

HISTORIC PEACOCK RANCH LBP REPORT

EEbG: Lead-Based Paint Inspection Report December 20, 2017

SECTION 5.0

RECOMMENDATIONS

5.1 RECOMMENDATIONS FOR LBP

Lead based paint that has become damaged should be abated. Abatement procedure in whichLBP is disturbed should be conducted by trained personnel and in accordance with federal,state and local regulations, including OSHA's lead regulation 29 CFR 1926.62. Also, prior todisposal, the waste stream from LBP abatement (paint, rags, protective suits, debris, etc.) mustbe characterized by a Toxic Characteristic Leachate Procedure (TCLP) test. The EPA requiresTCLP testing to determine if the waste is considered hazardous.

To comply with OSHA lead regulation 29 CFR 1926.62, the testing results should be madeavailable to personnel that will conduct painting operations of these structures. This regulationconsiders paint that contains lead to be lead-based paint and mandates protective measuresduring painting or renovation project involving the disturbance of LBP components in such away as to cause airborne emissions of lead particulate (sanding, scraping, grinding, etc.). Theseprotective measures include: personnel protection (respirators, protective suits, etc.),engineering controls and personnel air monitoring until results of the personnel monitoringindicate airborne lead concentrations below the Permissible Exposure Limit (PEL) of fifty (50)micrograms per cubic meter as an eight-hour time weighted average (TWA). In lieu of the aboveprotective measures, painting personnel may provide objective historical data from previoussimilar projects to demonstrate that the PEL for lead will not be exceeded.

5.2 RECOMMENDATIONS FOR OTHER PAINTS AND COATINGS

OSHA does not recognize the absence of lead through XRF; therefore, these materials must beconsidered to be lead-containing and a potential source of exposure unless determined to benonlead-containing through laboratory analysis (i.e. Flame AAS, Method SW 846, 7420).

Activities that would release lead dust or fumes must be performed by workers in accordancewith the OSHA standard for removal of lead containing paint. If these materials can remainintact during renovation or demolition, then no other special handling is required.

5.3 OSHA COMPLIANCE

To comply with OSHA lead regulation 29 CFR 1926.62, this report should be made available topersonnel that will conduct painting operations at this facility. This regulation considers coatingsthat contain measurable amounts of lead to be lead-based paint and mandates protectivemeasures when a painting or demolition project involves the disturbance of painted componentsin such a way as to cause airborne emissions of lead particulate (sanding, scraping, grinding,etc.). These protective measures include: hazard communication training, personnel protection(respirators, protective suits, etc.), engineering controls and personnel air monitoring untilresults of the personnel monitoring indicate airborne lead concentrations below the Action Level(AL) of 30 micrograms per cubic meter as an eight-hour time weighted average (TWA). In lieu ofthe above protective measures, painting and or demolition personnel may provide objectiveHISTORIC PEACOCK RANCH LBP REPORT

7

EEbG:Lead-Based Paint Inspection Report December 20, 2017

historical data from previous similar projects to demonstrate that the AL for lead will not beexceeded.

5.4 DISCLOSURE OF LBP HAZARDS

The Residential Lead-Based Paint Hazard Reduction Act of 1992, also known as Title X,Section 1018 requires the disclosure to the purchaser or lessee of any known information onlead-based paint or lead-based paint hazards and provide to the purchaser or lessee any leadhazard evaluation reports available prior to the sale or lease of most housing built prior to 1978.

HISTORIC PEACOCK RANCH LBP REPORT

8

EEIG:Lead-Based Paint Inspection Report December 20, 2017

SECTION 6.0

SIGNATURE PAGE

Hiram AguiarEPA Lead-Based Paint Risk Assessor, EE&G

Jay Sall, C.I.HSenior Technical Advisor, EE&G

HISTORIC PEACOCK RANCH LBP REPORT

EE$-G:Lead-Based Paint Inspection Report December 20, 2017

APPENDIX A

RENOVATE RIGHTEPA PAMPHLET

HISTORIC PEACOCK RANCH LBP REPORT

Federal law requires that individuals receive certain information beforerenovating more than two square feet of painted surfaces in housing,

child care facilities and schools built before 1978.

▪ Homeowners and tenants: renovators must give you this pamphletbefore starting work.

q Child care facilities, including preschools and kindergarten classrooms,and the families of children under the age of six that attend those facilities:renovators must provide a copy of this pamphlet to child-care facilities andgeneral renovation information to families whose children attend those facilities.

Also, beginning April 2010, federal law will require contractors that disturblead-based paint in homes, child care facilities and schools, built before 1978to be certified and follow specific work practices to prevent lead contamination.Therefore beginning in April 2010, ask to see your contractor 's certification.

▪ Is your home, your building, or the child care facility orschool your children attend, being renovated, repaired,or painted?

Was your home, your building, or the child care facilityor school your children under age 6 attend, builtbefore 1978?

If the answer to these questions is YES, there are afew important things you need to know about lead-based paint.

This pamphlet provides basic facts about lead andinformation about lead safety when work is being donein your home, your building or the childcare facility orschool your children attend.

The Facts About Lead

▪ Lead can affect children's brains and developing nervous systems, causingreduced 10, learning disabilities, and behavioral problems, Lead is also harmfulto adults.

▪ Lead in dust is the most common way people are exposed to lead. Peoplecan also get lead in their bodies from lead in soil or paint chips. Lead dust isoften invisible.

▪ Lead-based paint was used in more than 38 million homes until it was bannedfor residential use in 1978.

▪ Projects that disturb lead-based paint can create dust and endanger you andyour family. Don't let this happen to you. Follow the practices described in thispamphlet to protect you and your family.

Who S u

This Pamp

This pamphlet is for you if you:▪ Reside in a home built before 1978,

▪ Own or operate a child care facility, including preschools and kindergartenclassrooms, built before 1978, or

▪ Have a child under six who attends a child care facility built before 1978.

You will learn:

• Basic facts about lead and your health,

▪ How to choose a contractor, if you are a property owner,

▪ What tenants, and parents/guardians of a child in a child care facility orschool should consider,

▪ How to prepare for the renovation or repair job,

• What to look for during the job and after the job is done,

▪ Where to get more information about lead.

This pamphlet is not for:• Abatement projects. Abatement is a set of activities aimed specifically at

eliminating lead or lead hazards. EPA has regulations for certification andtraining of abatement professionals. If your goal is to eliminate lead or leadhazards, contact the National Lead Information Center at 1-800-424-LEAD(5323) for more information.

▪ "Do-it-yourself" projects. If you plan to do renovation work yourself, thisdocument is a good start, but you will need more information to completethe work safely. Call the National Lead Information Center at 1-800-424-LEAD(5323) and ask for more information on how to work safely in a home withlead-based paint.

▪ Contractor education, Contractors who want information about workingsafely with lead should contact the National Lead Information Center at1-800-424-LEAD (5323 for information about courses and resources onlead-safe work practices,

Lead is especially dangerous to childrenunder six years of age.

Lead can affect children's brains anddeveloping nervous systems, causing:

▪ Reduced IQ and learning disabilities.

▪ Behavior problems,

Even children who appear healthy can havedangerous levels of lead in their bodies.

Lead is also harmful to adults. In adults, lowlevels of lead can pose many dangers, including:

▪ High blood pressure and hypertension,

▪ Pregnant women exposed to lead can transferlead to their fetus.

Lead gets into the body when it is swallowedor inhaled.

▪ People, especially children, can swallow lead dust as they eat, play, anddo other normal hand-to-mouth activities,

▪ People may also breathe in lead dust or fumes if they disturb lead-based paint,People who sand, scrape, burn, brush or blast or otherwise disturb lead-basedpaint risk unsafe exposure to lead.

What should I do if I am concerned about my family's exposure to lead?

▪ Call your local health department for advice on reducing and eliminatingexposures to lead inside and outside your home, child care facility or school.

▪ Always use lead-safe work practices when renovation or repair will disturblead-based paint.

▪ A blood test is the only way to find out if you or a family member alreadyhas lead poisoning. Call your doctor or local health department to arrangefor a blood test.

For more information about the health effects of exposure to lead, visitthe EPA lead website at www.epa.gov/lead/pubs/leadinfo.htm or call1-800-424-LEAD (5323).

There are other things you can € o to protect your family ever day.

▪ Regularly clean floors, window sills, and other surfaces.

▪ Wash children's hands, bottles, pacifiers, and toys often.

▪ Make sure children eat a healthy, nutritious diet consistent with the USDA'sdietary guidelines, that helps protect children from the effects of lead.

▪ Wipe off shoes before entering house.

Where D

Dust is the main problem. The most common way to get lead in the body is fromdust. Lead dust comes from deteriorating lead-based paint and lead-contaminatedsoil that gets tracked into your home. This dust may accumulate to unsafe levels.Then, normal hand to-mouth activities, like playing and eating (especially in youngchildren), move that dust from surfaces like floors and windowsills into the body.

Home renovation creates dust. Common renovation activities like sanding,cutting, and demolition can create hazardous lead dust and chips.

Proper work practices protect you from the dust. The key to protecting yourselfand your family during a renovation, repair or painting job is to use lead-safe workpractices such as containing dust inside the work area, using dust-minimizing workmethods, and conducting a careful cleanup, as described in this pamphlet.

Other sources of lead. Remember, lead can also come from outside soil,your water, or household items (such as lead-glazed pottery and lead crystal).Contact the National Lead Information Center at 1-800-424-LEAD (5323) formore information on these sources.

Checking Your Hosead Based

Percentage of Homes Likely to Contain Lead

10

Older homes, child care facilities, and schools are more likely to containlead-based paint. Homes may be single-family homes or apartments. They maybe private, government-assisted, or public housing. Schools are preschools andkindergarten classrooms. They may be urban, suburban, or rural.

You have the following options:You may decide to assume your home, child care facility, or school containslead. Especially in older homes and buildings, you may simply want to assumelead-based paint is present and follow the lead-safe work practices described inthis brochure during the renovation, repair, or painting job.

You or your contractor may also test for lead using a lead test kit. Test kitsmust be EPA-approved and are available at hardware stores. They include detailedinstructions for their use.

You can hire a certified professional to check for lead-based paint. Theseprofessionals are certified risk assessors or inspectors, and can determine if yourhome has lead or lead hazards.▪ A certified inspector or risk assessor can conduct an inspection telling you

whether your home, or a portion of your home, has lead-based paint andwhere it is located. This will tell you the areas in your home where lead-safework practices are needed.

▪ A certified risk assessor can conduct a risk assessment telling you if your homecurrently has any lead hazards from lead in paint, dust, or soil. The risk assessorcan also tell you what actions to take to address any hazards.

▪ For help finding a certified risk assessor or inspector, call the National LeadInformation Center at 1 -800-424-LEAD (5323).

You have the ultimate responsibility for the safety of your family, tenants,or children in your care. This means properly preparing for the renovation andkeeping persons out of the work area (see p. 8). It also means ensuring thecontractor uses lead-safe work practices.

Beginning April 2010, federal law will require that contractors performingrenovation, repair and painting projects that disturb lead-based paint in homes,child care facilities, and schools built before 1978 to be certified and followspecific work practices to prevent lead contamination.

Until contractors are required to be certified, make sure your contractorcan explain clearly the details of the job and how the contractor will minimizelead hazards during the work.

▪ Ask if the contractor is trained to perform lead-safe work practices and tosee a copy of their training certificate.

▪ Ask them what lead-safe methods they will use to set up and perform thejob in your home, child care facility or school.

▪ Ask if the contractor is aware of the lead renovation rules. For example,contractors are required to provide you with a copy of this pamphlet beforebeginning work. A sample pre-renovation disclosure form is provided at theback of this pamphlet. Contractors may use this form to make documentationof compliance easier.

▪ Ask for references from at least three recent jobs involving homes builtbefore 1978, and speak to each personally.

Always make sure the contract is clear about how the work will be set up,performed, and cleaned.

▪ Share the results of any previous lead tests with the contractor.

▪ Even before contractors are required to be certified you should specify in thecontract that they follow the work practices described on pages 9 and 10 ofthis brochure.

▪ The contract should specify which parts of your home are part of the workarea and specify which lead-safe work practices should be used in those areas.Remember, your contractor should confine dust and debris to the work areaand should minimize spreading that dust to other areas of the home.

▪ The contract should also specify that the contractor clean the work area, verifythat it was cleaned adequately, and re-clean it if necessary.

Once these practices are required, if you think a worker is failing to do whatthey are supposed to do or is doing something that is unsafe, you should:

▪ Direct the contractor to comply with the contract requirements,

▪ Call your local health or building department, or

▪ Call EPA's hotline 1-800-424-LEAD (5323).

Tenon s, a.Under Age Sixand Scloo s

e1d Care . Facilities

You play an important role ensuring the ultimatesafety of your family,This means properly preparing for the renovation andstaying out of the work area (see p. 8).

Beginning April 2010, federal law will require thatcontractors performing renovation, repair and paintingprojects that disturb lead-based paint in homes, childcare facilities and schools built before 1978 that a childunder age six visits regularly to be certified and followspecific work practices to prevent lead contamination.

The law will require anyone hired to renovate, repair, ordo painting preparation work on a property built before1978 to follow the steps described on pages 9 and 10unless the area where the work will be done containsno lead-based paint.

Once these practices are required, if you think a worker is failing to do whatthey are supposed to do or is doing something that is unsafe, you should:▪ Contact your landlord,▪ Call your local health or building department, or▪ Call EPA's hotline 1-800-424-LEAD (5323).

If you are concerned about lead hazards left behind after the job is over, you cancheck the work yourself (see page 10).

your areael receives ousing assistance from HUD (or a state or local agencythat uses D funds), you must follow the more stringent requirements of HUD'sLead-safe l ousing Rule and the ones described in this pamphlet.

paring fora Re m

The work areas should not be accessible to occupants while the workoccurs. The rooms or areas where work is being done may be blocked off orsealed with plastic sheeting to contain any dust that is generated. The containedarea will not be available to you until the work in that room or area is complete,cleaned thoroughly, and the containment has been removed. You will not haveaccess to some areas and should plan accordingly.

You may need:▪ Alternative bedroom, bathroom, and kitchen arrangements if work is

occurring in those areas of your home.▪ A safe place for pets because they, too, can be poisoned by lead and can

track lead dust into other areas of the home.▪ A separate pathway for the contractor from the work area to the outside, in

order to bring materials in and out of the home. Ideally, it should not be throughthe same entrance that your family uses.

▪ A place to store your furniture. All furniture and belongings may have to bemoved from the work area while the work is done. Items that can't be moved,such as cabinets, should be wrapped in heavy duty plastic.

▪ To turn off forced-air heating and air conditioning systems while work is done.This prevents dust from spreading through vents from the work area to the restof your home. Consider how this may affect your living arrangements.

You may even want to move out of your home temporarily while allor parts of the work are being done.

Child care facilities and schools may want to consider alternativeaccommodations for children and access to necessary facilities.

Beginning April 2010, federal law will requirecontractors that are hired to perform renovation,repair and painting projects in homes, child carefacilities, and schools built before 1978 that disturblead-based paint to be certified and follow specificwork practices to prevent lead contamination.

Even before contractors are required to be certifiedand follow specific work practices, the contractorshould follow these three simple procedures,described below:

1. Contain the work area. The area should becontained so that dust and debris do not escapefrom that area. Warning signs should be put upand heavy-duty plastic and tape should be usedas appropriate to:▪ Cover the floors and any furniture that cannot be moved.▪ Seal off doors and heating and cooling system vents.

These will help prevent dust or debris from getting outside the work area.

2. Minimize dust. There is no way to eliminate dust, but some methods makeless dust than others, For example, using water to mist areas before sandingor scraping; scoring paint before separating components; and prying andpulling apart components instead of breaking them are techniques thatgenerate less dust than alternatives. Some methods generate large amountsof lead-contaminated dust and should not be used. They are:▪ Open flame burning or torching.

Sanding, grinding, planing, needle gunning, or blasting with power toolsand equipment not equipped with a shroud and HEPA vacuum attachment.

▪ Using a heat gun at temperatures greater than 1100°F.

3. Clean up thoroughly. The work area should be cleaned up daily to keep it asclean as possible. When all the work is done, the area should be cleaned upusing special cleaning methods before taking down any plastic that isolatesthe work area from the rest of the home. The special cleaning methodsshould include:• Using a HEPA vacuum to clean up dust and debris on all surfaces,

followed by• Wet mopping with plenty of rinse water.

When the final cleaning is done, look around. There should be no dust, paint chips,or debris in the work area. If you see any dust, paint chips, or debris, the areashould be re-cleaned.

When all the work is finished, you will want to know if your home, child carefacility, or school has been cleaned up properly. Here are some ways to check.

Even before contractors are required to be certified and follow specific workpractices, you should:

Ask about your contractor's final cleanup check. Remember, lead dust is ofteninvisible to the naked eye. It may still be present even if you cannot see it. Thecontractor should use disposable cleaning cloths to wipe the floor of the work areaand compare them to a cleaning verification card to determine if the work area wasadequately cleaned.

To order a cleaning verification card and detailed instructions visit the EPA leadwebsite at www.epa.govllead or contact the National Lead Information Center at

-800-424-LEAD (5323) or visit their website at www,epa.gov/leadtnllc.htm.

You also may choose to have a lead-dust test. Lead-dust tests are wipesamples sent to a laboratory for analysis.

▪ You can specify in your contract that a lead-dust test will be done. In this case,make it clear who will do the testing.

▪ Testing should be done by a lead professional.

If you choose to do the testing, some EPA-recognized lead laboratories will sendyou a kit that allows you to collect samples and send them back to the lab foranalysis.

Contact the National Lead Information Center at l -800-424-LEAD (5323) for listsof qualified professionals and EPA-recognized lead labs.

If your home, child care facility, orschool fails the dust test, the areashould be re-cleaned and tested again.

Where the project is done by contract, itis a good idea to specify in the contractthat the contractor is responsible forre-cleaning if the home, child carefacility, or school fails the test.

For .Property "l s:.After the Wo k s Done

You may need additional information on how to protect yourself and yourchildren while a job is going on in your home, your building, or childcarefacility.

▪ The National Lead Information Center at I-800-424-LEAD (5323) orwww.epa,gov/lead/nlicnhtm can tell you how to contact your state,local, and/or tribal programs or get general information about leadpoisoning prevention.

® State and tribal lead poisoning prevention orenvironmental protection programs can provideinformation about lead regulations and potentialsources of financial aid for reducing leadhazards. If your State or local government hasrequirements more stringent than thosedescribed in this pamphlet, you must followthose requirements.

® Local building code officials can tell you theregulations that apply to the renovation work thatyou are planning.

® State, county, and local health departmentscan provide information about local programs,including assistance for lead-poisoned childrenand advice on ways to get your home checkedfor lead.

▪ The National Lead Information Center can alsoprovide a variety of resource materials, includingthe following guides to lead-safe work practices.Many of these materials are also available atwww.epa.gov/lead/pubs/bmchure.htm.

• Lead Paint Safety, a Field Guide for Painting,Home Maintenance, and Renovation Work

Reducing Lead Hazards When Remodeling Your Home

Protect Your Family from Lead in Your Home

® Lead in Your Home: A Parent's Reference Guide

For the hearing impaired, call the Federal Information Relay Service at-800-877-8339 to access any of the phone numbers in this brochure.

EPA. Regional Offices

EPA addresses residential lead hazards through several different regulations.EPA requires training and certification for conducting abatement, education abouthazards associated with renovations, disclosure about known lead paint and leadhazards in housing, and sets lead-paint hazard standards.

Your Regional EPA Office can provide further information regarding lead safety andlead protection programs at www,e a.gov/lead.

Region 1 Region 4 Region 7(Connecticut, (Alabama, Florida, (Iowa, Kansas,Massachusetts, Maine, Georgia, Kentucky, Missouri, Nebraska)New Hampshire, Rhode Mississippi, North Carolina, Regional Lead ContactIsland, Vermont) South Carolina, Tennessee) U.S. EPA Region 7Regional Lead Contact Regional Lead Contact 901 N. 5th StreetU.S. EPA Region 1 U.S. EPA Region 4 Kansas City, KS 66101Suite 1100 61 Forsyth Street, SW (913) 551-7003One Congress Street Atlanta, GA 30303-8960Boston, MA 02114-2023 (404) 562-9900 Region 8(888) 372-7341 (Colorado, Montana,

Region 5 North Dakota, SouthRegion 2 (Illinois, Indiana, Dakota, Utah, Wyoming)(New Jersey, New York, Michigan, Minnesota, Regional Lead ContactPuerto Rico, Virgin Islands) Ohio, Wisconsin) U.S. EPA Region 8Regional Lead Contact Regional Lead Contact 999 18th Street, Suite 300U.S. EPA Region 2 U.S. EPA Region 5 Denver, CO 80202-24662890 Woodbridge Avenue 77 West Jackson Boulevard (303) 312-6312Building 209, Mail Stop 225 Chicago, IL 60604-3507Edison, NJ 08837-3679 (312) 886-6003 Region 9(732) 321-6769 (Arizona, California,

Region 6 Hawaii, Nevada)Region 3 (Arkansas, Louisiana, Regional Lead Contact(Delaware, Maryland, New Mexico, Oklahoma, U.S. Region 9Pennsylvania, Virginia, Texas) 75 Hawthorne StreetWashington, DC, Regional Lead Contact San Francisco, CA 94105West Virginia) U.S. EPA Region 6 (415) 947-8021Regional Lead Contact 1445 Ross Avenue,U.S. EPA Region 3 12th Floor Region 101650 Arch Street Dallas, TX 75202-2733 (Alaska, Idaho,Philadelphia, PA (214) 665-6444 Oregon, Washington)19103-2029 Regional Lead Contact(215) 814-5000 U.S. EPA Region 10

1200 Sixth AvenueSeattle, WA 98101-1128(206) 553-1200

CPS

The Consumer Product SafetyCommission (CPSC) protects thepublic from the unreasonable risk ofinjury or death from 15,000 types ofconsumer products under the agency'sjurisdiction. CPSC warns the publicand private sectors to reduce exposureto lead and increase consumerawareness. Contact CPSC for furtherinformation regarding regulations andconsumer product safety.

CPSC4330 East West HighwayBethesda, MD 20814Hotline 1-(800) 638-2772www.cpsc.gov

CDC Childhood LeadPoisoning Prevention BranchThe Centers for Disease Controland Prevention (CDC) assists stateand local childhood lead poisoningprevention programs to provide ascientific basis for policy decisions,and to ensure that health issues areaddressed in decisions about housingand the environment. Contact CDCChildhood Lead Poisoning PreventionProgram for additional materials andlinks on the topic of lead.

CDC Childhood Lead PoisoningPrevention Branch4770 Buford Highway, MS F-40Atlanta, GA 30341(770) 488-3300www.cdc.gov/nceh/lead

HUD Office

lr Homesand Lead Hazard ControlThe Department of Housing andUrban Development (HUD) providesfunds to state and local governmentsto develop cost-effective ways toreduce lead-based paint hazards inAmerica's privately-owned low-incomehousing. In addition, the office enforcesthe rule on disclosure of known leadpaint and lead hazards in housing,and HUD's lead safety regulations inHUD-assisted housing, provides publicoutreach and technical assistance,and conducts technical studies to helpprotect children and their families fromhealth and safety hazards in the home.Contact the HUD Office of HealthyHomes and Lead Hazard Control forinformation on lead regulations, out-reach efforts, and lead hazard controlresearch and outreach grant programs.

U.S. Department of Housingand Urban DevelopmentOffice of Healthy Homesand Lead Hazard Control451 Seventh Street, SW, Room 8236Washington, DC 20410-3000HUD's Lead Regulations Hotline(202) 402-7698www.hud.gov/offices/lead/

Effective until April 2010.

Confirmation of Receipt of Lead Pamphlet

U I have received a copy of the pamphlet, Renovate Right: Important Lead HazardInformation for Families, Child Care Providers and Schools informing me ofthe potential risk of the lead hazard exposure from renovation activity to beperformed in my dwelling unit. I received this pamphlet before the work began.

Printed name of recipient

Date

Signature of recipient

Self-Certification Option (for tenant-occupied dwellings only) -If the lead pamphlet was delivered but a tenant signature was not obtainable,you may check the appropriate box below.

U Refusal to sign - I certify that I have made a good faith effort to deliver thepamphlet, Renovate Right: Important Lead Hazard Information for Families,Child Care Providers and Schools, to the rental dwelling unit listed below at thedate and time indicated and that the occupant refused to sign the confirmationof receipt. I further certify that I have left a copy of the pamphlet at the unit withthe occupant.

U Unavailable for signature - I certify that I have made a good faith effort todeliver the pamphlet, Renovate Right: Important Lead Hazard Information forFamilies, Child Care providers and Schools, to the rental dwelling unit listedbelow and that the occupant was unavailable to sign the confirmation of receipt.1 further certify that I have left a copy of the pamphlet at the unit by sliding itunder the door.

Printed name of person certifying Attempted deliverydate and timelead pamphlet delivery

Signature of person certifying lead pamphlet delivery

Unit Address

Note Regarding Mailing Option - As an alternative to delivery in person, youmay mail the lead pamphlet to the owner and/or tenant, Pamphlet must be mailedat least 7 days before renovation (Document with a certificate of mailing from thepost office),

This sample form may be used by renovation firms to document compliance with theFederal pre-renovation education and renovation, repair, and painting regulations.

Occupant ConfirmationPamphlet ReceiptCI I have received a copy of the lead hazard information pamphlet informing me of the

potential risk of the lead hazard exposure from renovation activity to be performed inmy dwelling unit. I received this pamphlet before the work began.

Owner-occupant Opt-out Acknowledgment13 (A) I confirm that I own and live in this property, that no child under the age of 6

resides here, that no pregnant woman resides here, and that this property is not achild-occupied facility.

Note: A child resides in the primary residence of his or her custodial parents, legalguardians, foster parents, or informal caretaker if the child lives and sleeps most of thetime at the caretaker's residence.

Note: A child-occupied facility is a pre-1978 building visited regularly by the samechild, under 6 years of age, on at least two different days within any week, for at least3 hours each day, provided that the visits total at least 60 hours annually.

If Box A is checked, check either Box B or Box C, but not both.

(B) I request that the renovation firm use the lead-safe work practices requiredby EPA's Renovation, Repair, and Painting Rule; or

LI (C) I understand that the firm performing the renovation will not be required to use thelead-safe work practices required by EPA's Renovation, Repair, and Painting Rule.

Printed Name of Owner-occupant

Signature of Owner-occupant

Signature Date

Renovator's Self Certification Option (for tenant-occupied dwellings only)Instructions to Renovator: If the lead hazard information pamphlet was deliveredbut a tenant signature was not obtainable, you may check the appropriate box below.

LI Declined - I certify that I have made a good faith effort to deliver the lead hazardinformation pamphlet to the rental dwelling unit listed below at the date and timeindicated and that the occupant declined to sign the confirmation of receipt. I furthercertify that I have left a copy of the pamphlet at the unit with the occupant.

Unavailable for signature - I certify that I have made a good faith effort to deliverthe lead hazard information pamphlet to the rental dwelling unit listed below and thatthe occupant was unavailable to sign the confirmation of receipt. I further certify thatI have left a copy of the pamphlet at the unit by sliding it under the door or by (fill inhow pamphlet was left).

Printed Name of Person Certifying Delivery

Attempted Delivery Date

Signature of Person Certifying Lead Pamphlet Delivery

Unit Address

Note Regarding Mailing Option - As an alternative to delivery in person, you may mail thelead hazard information pamphlet to the owner and/or tenant. Pamphlet must be mailed atleast seven days before renovation. Mailing must be documented by a certificate of mailingfrom the post office.

Note: This form is not effective until April 2010.

EEI3sG:Lead-Based Paint Inspection Report December 20, 2017

APPENDIX B

XRF TESTING DATA

HISTORIC PEACOCK RANCH LBP REPORT

PEACOCK RANCH XRF Lead Paint Inspection Results

Reading Date LOCATION FLOOR ROOM OBJECT SUBSTRATE COLOR Pb1 6-Dec-17 Standard Pass2 6-Dec-17 Peacock House Nist Calibrate Wood Red 1.023 6-Dec-17 Peacock House 1 Ext. Porch Wall Wood White 1.14 6-Dec-17 Peacock House 1 Ext. Porch Wall Wood White 1.835 6-Dec-17 Peacock House 1 Ext. Porch Ceiling Wood Blue 1.85

6 6-Dec-17 Peacock House 1 Ext. Porch Floor Wood Grey 0.1

7 6-Dec-17 Peacock House 1 Ext. Porch Window Wood White 1.478 6-Dec-17 Peacock House 1 Ext. Porch Window Wood White 1.21

9 6-Dec-17 Peacock House 1 Ext. Porch Window Frame Wood White 1.4510 6-Dec-17 Peacock House 1 Ext. Porch Window Sill Wood White 0.13

11 6-Dec-17 Peacock House 1 Ext. Porch Window Sill Wood White 1.52

12 6-Dec-17 Peacock House 1 Ext. Porch Door Wood White 0

13 6-Dec-17 Peacock House 1 Ext. Porch Door Wood White 0.19

14 6-Dec-17 Peacock House 1 Ext. Porch D. Casing Wood White 0.37

15 6-Dec-17 Peacock House 1 Ext. Porch D. Casing Wood White 0.22

16 6-Dec-17 Peacock House 1 interior NE RM Wall Wood White 0.18

17 6-Dec-17 Peacock House 1 interior NE RM Wall Wood White 0.13

18 6-Dec-17 Peacock House 1 interior NE RM Wall Wood White 0.11

19 6-Dec-17 Peacock House 1 interior NE RM Ceiling Wood White 0.19

20 6-Dec-17 Peacock House 1 interior SE RM Ceiling Wood White 0.07

21 6-Dec-17 Peacock House 1 interior SE RM Wall Wood White 0.02

22 6-Dec-17 Peacock House 1 interior SE RM Wall Wood White 0.01

23 6-Dec-17 Peacock House 1 interior SE RM Wall Wood Brown 0.03

24 6-Dec-17 Peacock House 1 interior SE RM Wall Wood Brown 0.07

25 6-Dec-17 Peacock House 1 interior SE RM Wall Wood Brown 0.02

26 6-Dec-17 Peacock House 1 interior SE RM Crown Molding Wood Brown 0.03

27 6-Dec-17 Peacock House 1 interior SE RM Crown Molding Wood Brown 0.03

28 6-Dec-17 Peacock House 1 interior SE RM Crown Molding Wood Brown 0.05

29 6-Dec-17 Peacock House 1 interior SW RM Wall Wood Brown 0.23

30 6-Dec-17 Peacock House 1 interior SW RM Door Wood Brown 0.06

31 6-Dec-17 Peacock House 1 interior SW RM Door Casing Wood Brown 0.03

32 6-Dec-17 Peacock House 1 interior SW RM Floor Wood Brown 0.06

PEACOCK RANCH XRF Lead Paint Inspection Results

Reading Date LOCATION FLOOR

ROOM OBJECT SUBSTRATE COLOR Pb

33 6-Dec-17 Peacock House 1 interior SW Bathroom Ceiling Drywall White 0

34 6-Dec-17 Peacock House 1 interior SW Bathroom Window Wood White 0.1

35 6-Dec-17 Peacock House 1 interior SW Bathroom Wall Ceramic Ceramic White 5

36 6-Dec-17 Peacock House 1 interior SW Bathroom Tub Metal White 5

37 6-Dec-17 Peacock House 1 interior SW Bathroom Toilet Ceramic Ceramic White 0

38 6-Dec-17 Peacock House 1 interior SW Bathroom Sink Metal White 1

39 6-Dec-17 Peacock House 1 interior S Bathroom Sink Metal White 1

40 6-Dec-17 Peacock House 1 interior S Bathroom Sink Metal White 1

41 6-Dec-17 Peacock House 1 interior S Bathroom Tub 'Metal White 5

42 6-Dec-17 Peacock House 1 interior

S Bathroom Door Frame Wood White 0.18

43 6-Dec-17 Peacock House 1 interior

S Bathroom Wall Ceramic Ceramic Beige 0

44 6-Dec-17 Peacock House 1 interior

S Bathroom Wall Ceramic Ceramic White 0

45 6-Dec-17 Peacock House 2 interior

S RM Wall Plaster White 0.03

46 6-Dec-17 Peacock House 2 interior

S RM Wall Plaster White 0.03

47 6-Dec-17 Peacock House 2 interior S RM Wall Plaster White 0

48 6-Dec-17 Peacock House 2 interior

S RM Ceiling Plaster White 0.07

49 6-Dec-17 Peacock House 2 interior

S RM Ceiling Plaster White 0.05

50 6-Dec-17 Peacock House 2 interior

S RM Ceiling Plaster White 0.01

51 6-Dec-17 Peacock House 2 interior

S RM Window Wood Brown 0.07

52 6-Dec-17 Peacock House 2 interior

S RM Window Frame Wood Brown 0.1

53 6-Dec-17 Peacock House 2 interior

S RM Baseboard Wood Brown 0.02

54 6-Dec-17 Peacock House 2 interior

N RM Baseboard Wood Brown 0.15

55 6-Dec-17 Peacock House 2 interior

N RM Window Wood Brown 0.03

56 6-Dec-17 Peacock House 2 Exterior S RM Window Wood White 0.07

57 6-Dec-17 Peacock House 2 Exterior S RM Window Wood White 0.05

58 6-Dec-17 Peacock House 2 Exterior

Stairs Wall Wood White 0.08

59 6-Dec-17 Peacock House Exterior

S Wall Wood White 0

60 6-Dec-17 Peacock House Exterior

S Addition Wall Wood White 0

61 6-Dec-17 Peacock House Exterior

S Addition Wall Wood White 0

62 6-Dec-17 Peacock House 2

Bathroom Wall Ceramic Ceramic Beige 0

63 6-Dec-17 Peacock House 2

Bathroom Tub Metal White 5

64 6-Dec-17 Peacock House 2

Bathroom Toilet Ceramic White 1

PEACOCK RANCH XRF Lead Paint Inspection Results

Reading Date LOCATION FLOOR ROOM OBJECT SUBSTRATE COLOR Pb

65 6-Dec-17 Peacock House 2 Bathroom Sink Metal White 0.01

66 6-Dec-17 Peacock House Exterior Exterior Wall Wood White 0.97

67 6-Dec-17 Peacock House Exterior Exterior Wall Wood White 1.16

68 6-Dec-17 Peacock House Exterior Exterior Wall Wood White 0.22

69 6-Dec-17 Peacock House Exterior Exterior Wall Wood White 1

70 6-Dec-17 Peacock House Exterior Exterior Foundation Concrete Green 0

71 6-Dec-17 Peacock House Exterior Exterior Window Wood Green 1.47

72 6-Dec-17 Peacock Garage Exterior Exterior Wall Wood Green 0.13

73 6-Dec-17 Peacock Garage Exterior Exterior Wall Wood Green 0.11

74 6-Dec-17 Peacock Garage Exterior Exterior Wall Wood Green 0.18

75 6-Dec-17 Peacock Garage Exterior Exterior Wall Wood Green 0.13

76 6-Dec-17 Peacock Shed Exterior Exterior Wall Wood Green 0

77 6-Dec-17 Peacock Shed Exterior Exterior Wall Wood Green 0

78 6-Dec-17 Peacock Shed Exterior Exterior Door Wood Green 0

79 6-Dec-17 Peacock Garage Exterior Exterior Door Wood Green 0.15

80 6-Dec-17 Peacock Garage Exterior Exterior Door Wood Green 0.14

81 6-Dec-17 Peacock Garage Exterior Exterior Door Frame Wood Green 0.01

82 6-Dec-17 Peacock Garage Exterior Exterior Header Wood Green 0

83 6-Dec-17 Peacock Lodge Exterior Exterior Wall Wood Green 0.3

84 6-Dec-17 Peacock Lodge Exterior Exterior Wall Wood Green 0.28

85 6-Dec-17 Peacock Lodge Exterior Exterior Wall Wood Green 0.14

86 6-Dec-17 Peacock Lodge Exterior Exterior Wall Wood Green 0.17

87 6-Dec-17 Peacock Lodge Exterior Exterior Wall Wood Green 0.21

88 6-Dec-17 Peacock Lodge Exterior Exterior Wall Wood Green 0.26

89 6-Dec-17 Peacock Lodge Exterior Exterior Wall Wood Green 0.17

90 6-Dec-17 Peacock Lodge Exterior Exterior Window Sill Wood Green 0.15

91 6-Dec-17 Peacock Lodge Exterior Exterior Window Sill Wood Green 0.11

92 6-Dec-17 Peacock Lodge Exterior Exterior Window Sill Wood Green 0.16

93 6-Dec-17 Peacock Lodge Exterior Exterior Window Wood Green 0.09

94 6-Dec-17 Peacock Lodge Exterior Exterior Window Wood Green 0

95 6-Dec-17 Peacock Lodge Exterior Exterior Window Wood Green 0.16

96 6-Dec-17 Peacock Lodge Exterior Exterior Ceiling Wood Green 0.15

PEACOCK RANCH XRF Lead Paint Inspection Results

Reading Date LOCATION FLOOR ROOM OBJECT SUBSTRATE COLOR Pb

97 6-Dec-17 Peacock Lodge 1 Interior Wall Wood Brown 0

98 6-Dec-17 Peacock Lodge 1 Interior Wall Wood Brown 0

99 6-Dec-17 Peacock Lodge 1 Interior Wall Wood Brown 0

100 6-Dec-17 Peacock Lodge 1 Interior Ceiling Wood Brown 0

101 6-Dec-17 Peacock Lodge 1 Interior Ceiling Wood Brown 0

102 6-Dec-17 Peacock Lodge 1 Interior Door Wood Brown 0

103 6-Dec-17 Peacock Lodge 1 Interior Door Frame Wood Brown 0

104 6-Dec-17 Peacock Lodge 1 Interior Door Frame Wood Brown 0

105 6-Dec-17 Peacock Lodge 1 Interior Window Wood Brown 0

106 6-Dec-17 Peacock Lodge 1 Interior Window Wood Brown 0

107 6-Dec-17 Peacock Lodge 1 Interior Window Wood Brown 0

108 6-Dec-17 Peacock Lodge 1 Interior Wall Drywall White 0

109 6-Dec-17 Peacock Lodge 1 Interior Wall Drywall White 0

110 6-Dec-17 Peacock Lodge 1 Interior Bathroom Sink Metal White 0

111 6-Dec-17 Peacock Lodge 1 Interior Bathroom Toilet Concrete White 0

112 6-Dec-17 Peacock Lodge 1 Interior Bathroom Shower Metal White 0

113 6-Dec-17 Peacock Lodge 1 Interior Living Fire Place Concrete Beige 0

114 6-Dec-17 Peacock House Nist Calibrate Wood Red 1.04

EErG:Lead-Based Paint Inspection Report December 20, 2017

APPENDIX C

PHOTOGRAPHS

HISTORIC PEACOCK RANCH LBP REPORT

EErG:Lead-Based Paint Inspection Report

December 20, 2017

Photograph #1: Subject property - Peacock House shown to the left and the attachedaddition to the right of the above picture.

Photograph #2: LBP identified on typical exterior painted wood walls of the originalhouse.

HISTORIC PEACOCK RANCH LBP REPORT

EErG: Lead-Based Paint Inspection Report

December 20, 2017

Photograph #3: LBP identified on typical exterior painted wood porch ceiling of theoriginal house.

Photograph #4: LBP identified on the typical exterior painted wood windows/windowframes.

HISTORIC PEACOCK RANCH LBP REPORT

EEG:Lead-Based Paint Inspection Report

December 20, 2017

Photograph #5: Typical view of the typical the exterior walls, ceiling, and windowsidentified with LBP.

Photograph #6: Typical first floor interior view of the Peacock house.

HISTORIC PEACOCK RANCH LBP REPORT

EEb-G:Lead-Based Paint Inspection Report

December 20, 2017

Photograph #7: Typical second floor interior view of the Peacock house.

Photograph #8: LBP identified on bathroom ceramic tile.

HISTORIC PEACOCK RANCH LBP REPORT

EE$-G: Lead-Based Paint Ins pection Report

December 20, 2017

Photograph #9: LBP identified on bathroom metal bath tub.

Photograph #10: LBP identified on bathroom metal sink.

HISTORIC PEACOCK RANCH LBP REPORT

EEbG:Lead-Based Paint Inspection Report

December 20, 2017

Photograph #11: LBP identified on bathroom toilet.

Photograph #12: Typical view of the Peacock Barn tested for LBP.

HISTORIC PEACOCK RANCH LBP REPORT

EE$G:Lead-Based Paint Inspection Report December 20, 2017

Photograph #13: Typical view of the Peacock Shed tested for LBP.

Photograph #14: Typical view of the Peacock Lodge tested for LBP.

HISTORIC PEACOCK RANCH LBP REPORT

EE}s' G:Lead-Based Paint Inspection Report December 20, 2017

Photograph #15: Typical view of the Peacock Lodge tested for LBP.

Photograph #16: Typical view of the Peacock Lodge tested for LBP.

HISTORIC PEACOCK RANCH LBP REPORT

EEtrG:Lead-Based Paint Inspection Report December 20, 2017

APPENDIX D

CERTIFICATES

HISTORIC PEACOCK RANCH LBP REPORT

Hiram A Aguiar

has fulfilled the requirements of the Toxic Substances Control Act (TSCA) Section 402, and has

received certification to conduct )eod-6mo*dpaint activities pursuant to 40 CFR Part 745.226 as:

All EPA Administered Lead-based Paint Activities Program States, Tribes and Territories

This certification is valid from the date of issuance and expires August 01, 2020

Adrienne Priselac, Manager, Toxics Office

Land Division

[[]P-R-9781-1

Certification #

May 24, 2017

Issued On

se.1

1

IT ; !I ;

F:; 1

n VI !.I - I

[Il TA.1

LlIiL

.1j1I 1 1.11.1.1111 IA Z;

I I

C T:11.j 1 11F.I.'11.1ir:Lf.TFLIE I SfI

I 1±Cl_rr I,

j 71.11117 rl:t

t....

.....

f

1I

ir t11

Tfi. n

71 1i:L 1

41384.4638CERTIPBRARE

900 N .W 5TH Avenue, Fort Lauderdale, Florida 33311 P954) 524-7208

Qio

Processed By:

iii 1111111111

NU 1 11. 1To Authenl!ca Certificat

www.seaguiltraining.con1-800-966-9933

21-Apr-17

TO

21-Apr-17Includes: Arsenic, Barium, Cadmium, Chromium, Lead, Selenium, Silver, & Mercury

YII

11'1.P i'tMetI

AW rt') ft

186sm 1)11

This certificate may be used to obtain a state license, which may be used to obtain an EPA license.IDOL A i

at s)Amu

par.

(IN

Trainer(s): James F. Stump

ii.sc

Training Address: 900 NW 5 AV, Fort Lauderdale, Fl. 33311

"assed the hands-on assessment & completed the course exam on: 21-Apr-17

nes Stump, Training .: na

11111111111111111111111111111This Certificate txpires:

Certificate Number:

7 8 2

SUNSET DATE:

20-Apr-20

III I III

II11

I IIII I!0 4 / 2 0 / 2 0

Course Number: SE1716the actual expiration date v, ill appear on individuai's license. See individual state rules for your state expiration date.

ttrittiiritiril;r

ri

american board of industrial by iene®

organized to improve the practice of industrial hygieneproclaims that

Jay 'W. Sall'having met all requirements of

education, experience and examination, andongoing maintenance,

is hereby certified in the

COMPREHENSIVE PRACTICEof

INDUSTRIAL HYGIENE

and has the right to use the designations

CERTIFIED INDUSTRIAL HYGIENIST

CIH

Certificate Number 5610 CP

Awarded: July 15, 1992

Expiration Date: December 1, 2018

f

xecutive Director ABIH

5751 Miami Lakes DriveMiami Lakes, Florida 33014-2417

Tel (305) 374-8300Environmental Services, LLC

Pax (305) 374-9004vw w.eeandg.com

December 20, 2017EE&G Proposal: 2017-2448

Mr. Bert BenderBender & Associates Architects410 Angela StreetKey West, FL 33040

Subject:

Water-Damaged Building Materials AssessmentFeasibility Study for Relocation/Rehabilitation of Historic StructuresFormer Historic Peacock Ranch House & LodgeCanal C-24 & Glades Cut-off Road (Verano Property)Port St. Lucie West, Florida

Dear Mr. Bender:

EE&G Environmental Services, LLC (EE&G) was retained by Bender & Associates Architects(Client) to provide an assessment for the presence of water damage and mold impacted materials atthe former Historic Peacock Ranch House and Lodge (subject area). The purpose of theassessment was to obtain an understanding of the extent of the water-damaged materials in thesubject area. This report is based on observations made during an assessment performed onDecember 6, 2017, by Sean Nemser E.I. of EE&G.

LIMITATIONS

This report has been prepared by EE&G in a manner consistent with that level of care and skillordinarily exercised by members of the profession currently practicing under similar conditions. Noother warranty, expressed or implied, is made. EE&G's interpretations and recommendations arebased upon the results of sample analyses, as well as investigative work. Other conditionselsewhere in the subject building may differ from those in the inspected/surveyed locations and suchconditions are unknown, may change over time and have not been considered.

Since the dynamics of water intrusion and mold-growth on building materials may involve damage tohidden areas (such as wall cavities and chases), it is possible that this assessment did not result inthe identification of damage to areas not readily accessible. The Client is urged to proceed withrecommendations presented herein with due caution.

The assessment was limited to visual inspection of accessible portions of the subject areas.Accessible areas were defined as those areas that can be accessed without the use of tools orladders. Destructive techniques (test holes) were not installed in walls as a substantial historicalrenovation of the house was implied by the client.

EE&G will not be responsible for the interpretation or use by others of data developed pursuant tothe compilation of this report. This report reflects conditions, operations, and practices as observedon the date and time of the site inspection. The interpretations and recommendations, stated in thisreport, are based on previous environmental studies and research conclusions. EE&G does notwarrant the use of segregated portions of this report.

Miami

Melbourne

Orlando

Tampa

Mr. Bert BenderDecember 20, 2017Page 2

MATERIALS AND METHODS

Visual Inspection and Moisture Testing

A visual assessment was performed in the subject area for the purpose of identifying water-damaged or assumed mold growth (AMG)-impacted building materials. Evidence of water andimpacted AMG damage included materials exhibiting the following characteristics:

• Visible staining on building materials in a pattern that was suggestive of either short-term or long-term contact with water.

• Corrosion, delamination, or deterioration of building materials that was indicative ofcontact with water.

• Visible accumulation of AMG that fits a definite pattern that was associated withwater contact.

For the purposes of this report, surface AMG was defined as having the following characteristics:

Was not associated with water staining.

• Was not associated with water-damage or wet/saturated building materials.

• Had a dust-like appearance and was easily wiped off the surface.

As a means of facilitating the identification of water-damaged materials, EE&G conducted a thermalassessment of the subject area using a FLIR ThermaCAM E6. The assessment consisted of usingthe thermal imager to scan materials suspected of having elevated moisture content. The instrumentused a color spectrum to represent thermal differences between materials. Warmer materials weredisplayed as lighter colors (whites and yellows), and cool materials were displayed as darker colors(blues and reds). Areas of cooler building materials (thermal anomalies), as compared to similaradjacent materials, were suspected as having elevated moisture levels. Testing of materialssuspected of water impacts was performed using a moisture meter in order to determine if thethermal anomalies observed were the result of elevated moisture content or other conditions.

The moisture content of building materials was measured using a Protimeter SurveyMaster SM.This instrument reports results in %Wood-Moisture-Equivalent (WME). Percent WME is themoisture level of a building material other than wood expressed as moisture content of wood. Areading above 20% in a building material was considered a high reading for the purposes of thisreport. High readings indicate an excessive amount of moisture in the tested building material andshould be investigated further. The percent WME was categorized into the following classifications:

▪ Less than 18% WME - The material was in a safe, dry condition. Moisture-relatedproblems of decay and deterioration were not likely to occur.

• From 18% to 20% WME - The material was in a borderline condition. Moisture-related problems of decay and deterioration were possible under certain conditions.

Mr. Bert BenderDecember 20, 2017Page 3

e Greater than 20% WME - The material was in a wet condition. Moisture-relatedproblems of decay and deterioration were likely to occur in time unless the moisturelevel of the material was reduced.

Environmental Parameters Testing

Relative humidity (RH), temperature, and dew point readings were collected using a Model 7525IAQ-Calc indoor air quality meter manufactured by TSI Inc. A thin film capacitive sensor was usedfor RH measurement; results were reported in percent (%). A Thermistor sensor was used fortemperature measurement; results were reported in degrees Fahrenheit (°F). Dew pointmeasurements were calculated by the device based on the current temperature and relativehumidity readings; results were reported in degrees Fahrenheit (°F).

The current American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE)Standard 55-2004 does not provide a specific recommendation for maintaining RH in an indoorenvironment. However, the standard does establish an upper boundary for dew point at 62.2°F.ASHRAE Standard 62.1-2007 provides an additional guideline of 65% or less for RH where airconditioning systems with dehumidification capabilities are used. The upper dew point temperaturecan occur at various combinations of temperature and RH.

The current ASHRAE Standard 55-2004 is intended to provide acceptable thermal comfortguidelines for building occupants and is not intended to be used to maintain conditions that mayprevent indoor microbial growth. It should be noted that no documented RH value exists in thisstandard as a threshold that indicates when mold growth will occur on building materials or surfaces.However, RH values and dew point temperatures are related. At a given temperature, increasingRH produces an increasing dew point temperature and may increase the likelihood of surfacecondensation and the potential for mold growth. Certain building system components can be coolerthan the maximum allowable dew point established by the Standard and therefore, condensationand the potential for mold growth may occur. Furthermore, as RH in an indoor environmentincreases above 60 to 65%, the increased moisture in the air translates into an increase in thespecific water activity of adjacent surfaces. As the specific water activity of a surface increases, thelikelihood of mold growth increases. For the purposes of this report, this data is interpretedaccordingly:

• Temperature - Thermal comfort range is not specified under current ASHRAEguidelines. However, previous standards as well as the general industry recognize arange between 70° and 80°F as being a valid thermal comfort range.

• Relative Humidity - Thermal comfort in the current ASHRAE standard is expressedas a humidity ratio. However, based on previous standards as well as the generalindustry standard, a relative humidity below 60% is considered acceptable forthermal comfort. Concentrations below 65% are considered as advisable for thecontrol of surface mold growth (non-ASHRAE) as described above.

• Dew Point - Below 62.2°F based on ASHRAE 55-2004.

Mr. Bert BenderDecember 20, 2017Page 4

FINDINGS

Visual Assessment

The subject areas included a two-story residential structure (Peacock Ranch House) and a singlestory lodge, both built in 1895. The Ranch House and the Lodge were constructed primarily of woodand metal. Interior walls were finished with painted plaster board. Wood paneling was also installedover plaster board walls in the Lodge. Ceilings were finished with wood, painted plaster board andlay-in tiles. Floors were finished with linoleum, ceramic tile, vinyl floor tile, and carpet over wood.Direct expansion (DX) air handling units (AHUs) serviced the subject areas. Return air was drawnthrough louvered bi-fold doors. Supply air was distributed via externally insulated metal ductworkand flex duct.

Several holes through the building envelop (walls and lower floors) and open doors were observedin both structures. The following was also observed by EE&G:

Peacock Ranch House 1st Floor

• Water damage and AMG was observed on over 75% of the plaster walls and ceilingsof the first floor. The moisture content of the materials tested ranged from 19% to85% WME.

• Water damage and AMG was observed on the ceilings throughout the first floor.The ceiling was observed to be collapsed in some areas due to water impacts (photo4).

• AMG was observed on intact plaster ceiling of the first floor (photos 5).

• Water damage and AMG was observed on the contents throughout the first floor.

Peacock Ranch House2ndFloor

Water damage and AMG were observed on over 75% of the plaster walls and ceilingon the second floor. The moisture content of the materials tested ranged between19% and 87% WME.

• Flooring throughout the second floor was water damaged and was deteriorated,bowing downward and potentially caving in at some locations (photo 6 and Photo 7).

• Plaster ceiling were observed to be collapsed due to water impacts on the secondfloor (photo 8).

• AMG and water damage were observed on walls throughout the second floor.

Mr. Bert BenderDecember 20, 2017Page 5

Peacock Ranch Lodge

Water damage and AMG was observed to have impacted over 50% of the walls and ceiling of thelodge. Wood flooring was water damaged throughout the structure. The moisture content of thematerials tested ranged from 19% to 85% WME. Examples of the damage and impacts observedare presented below. Pictures are attached to this report.

Entrance

Water damage and AMG was observed on the contents and cabinetry throughoutthe first floor (Photo 10).

• Water damage and elevated WME was observed on the walls and ceilings of therooms (photo 11). The flooring was observed to be damaged in several of the roomsdue to water intrusion.

• Water damage and AMG was observed on the ceilings throughout the lodge. (Photo12 and Photo 13).

Environmental Parameter Testinq

The table below presents the findings of the environmental parameter testing.

Location Temperature (°F) Relative Humidity (%) Dew point (°F)Ambient Outdoor 92.0 56.5 77.5

Peacock House 1stFloor

73 .6 81 .9 68 .9

Peacock House 2""Floor

77 1 78 .4 71 .3

Peacock LodgeEntrance

74 .7 85.1 70 .9

Peacock Lodge SeRoom

75 .1 83 .0 70 7

Peacock Lodge SWRoom

74 .4 83 .9 70 .3

ASHRAE 1 Target 70-80°F 60%-65% or below1. Target levels recommended by the American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE).

CONCLUSIONS

• Observations made of the building envelop indicate several sources of moistureintrusion into the structures, including roof leaks, open doors, and holes in the wallsand lower floors, which resulted in water and AMG damage to interior finishes andbuilding materials. The presence of elevated moisture content and significantAMGdamage on the plaster/sheetrock materials of the walls and ceilings indicates thatthe water intrusion through the envelopes was likely ongoing, meaning that damage(decay and deterioration) and microbial growth will likely continue to develop.Additional AMG damage was likely present in wall cavities or areas that were notaccessed during this assessment.

Mr. Bert BenderDecember 20, 2017Page 6

• The environmental parameter testing indicated relative humidity and dew points thatwere at or above the ranges recommended by ASHRAE. These conditions may besupportive of indoor fungal growth. Given the lack of an operational air conditioningsystem and the observed open doors and holes in the building envelopes, it is theopinion of EE&G that humidity-driven AMG will likely continue.

• The potential for elevated relative humidity and observed direct water intrusionresulted in AMG damage which would likely impact the quality of the indoor air.

RECOMMENDATIONS

Based on the conclusions of this assessment, EE&G recommends the following:

• The roof and exterior walls should be assessed by a qualified contractor and repairseffected to prevent water intrusion.

• Once the roof system and walls are made water tight, remediation of impactedinterior materials should be performed. Given the extent of water and mold impactedmaterials observed, as well as the ongoing nature of water intrusion, it is the opinionof EE&G that the house and lodge should be remediated by the complete removal ofinterior finish materials including walls, ceilings and some flooring (where decay anddeterioration is present), including areas of plaster board covered by wood paneling.Finished wood materials (primarily floors and ceilings) may be cleaned and/orsanded to remove AMG damage. Remediation work should be performed by aqualified and licensed mold remediation contractor in accordance with current moldindustry standards and guidelines.

• The wooden floor of the first and second floors of the house and the first floor of thelodge should be evaluated by a qualified engineer as they may require shoring as toaccommodate safe remediation.

• The HVAC system should be assessed by a qualified mechanical contractor for thepurpose of determining if the units can be made operable or should be replaced.

Mr. Bert BenderDecember 20, 2017Page 7

EE&G appreciates the opportunity to assist you with this project. If you have any questions orrequire clarifications please do not hesitate to contact us at (305) 374-8300.

Sincerely,

Reviewed:

Sean Nemser, E.I.Associate Staff ProfessionalEE&G

Jay W. Sall, CIHIH Practice DirectorEE&G

EE6G :Peacock Ranch House & Lodge December20,2017

ATTACHMENT A

PHOTO DOCUMENTATION PAGES

EEG : Peacock Ranch House & Lodge

December 20, 2017

Photo 2: Interior view of the Peacock Ranch House

EEG : Peacock Ranch House & Lodge

December 20, 2017

Photo 3: Water damage and AMG on walls and ceilings

i

Photo 4: Typical water damage and AMG on rafters

EE ,G : Peacock Ranch House & Lodge

December 20, 2017

Photo 6: Second floor of the peacock house

^^̂̂ Eb-G: Peacock Ranch House & Lodge Dmcenlber2O.2U17

Photo 7: Water damage and AMG on the second floor

Photo 8 Water mndAMG on the second floor

EEG : Peacock Ranch House & Lodge

December 20, 2017

Photo 9: Exterior view of the Peacock Ranch Lodge

Photo 10: Interior view of the Peacock Ranch Lodge

EEbG :Peacock Ranch House & Lodge

December 20, 2017

Photo 11: Water damage and AMG

Photo 12: Water damaged ceiling

EErG :Peacock Ranch House & Lodge

December 20, 2017

Photo 13: Water damage and AMG on wood ceiling system

Environmental Services, LLC

5751 Miami Lakes DriveMiami Lakes, Florida 33014

Tel (305) 374-8300Fax (305) 374-9004

www.eeandg.com

December 21, 2017EE&G Project # 2017-2448

Mr. Bert BenderBender & Associates Architects410 Angela StreetKey West, FL 33040

Subject:

Results of Asbestos AssessmentFeasibility Study for Relocation/Rehabilitation of Historic StructuresFormer Historic Peacock Ranch - Ranch House, Lodge & BarnCanal C-24 & Glades Cut-off Road (Verano Property)Port St. Lucie West, Florida

Dear Mr. Bender,

EE&G Environmental Services, LLC (EE&G) was retained by Bender & Associates Architects,(Client) to conduct an asbestos survey at the historic Peacock Ranch House and Lodgecomplex located at the above-referenced address. The survey was performed on December 6,2017, by Mr. Bob Miro of EE&G certified under the Asbestos Hazard Emergency Response Act,(AHERA). The purpose of this asbestos survey was to identify the presence, extent, andcondition of asbestos-containing materials (ACM) that may be impacted as a result of plannedrenovations and/or relocation for compliance with the Environmental Protection Agency (EPA)National Emissions Standards for Hazardous Air Pollutants (NESHAP), Port Saint Lucie Countyand applicable State and Federal Guidelines.

SUMMARY

RANCH HOUSE:

EE&G collected a total of 29 samples of the following materials:

• White drywall system

• Yellow linoleum flooring.

• Gold diamond pattern linoleum

• Beige 12" vinyl floor tile (VFT)

• Light Green linoleum

• Beige linoleum over ceramic tile

• White linoleum

• White exterior window glaze

• Black shingle/paper roof system

Asbestos was found in amounts greater than 1% in various linoleums and floor tiles, andtherefore are considered to be ACM. See attached laboratory results.

Miami

Melbourne

Orlando

Tampa

Mr. Bert BenderDecember 21, 2017Page 2

RANCH LODGE:

EE&G collected a total of 18 samples of the following materials:

White drywall system.Grey linoleum flooring (layered)White 1'x2' ceiling tiles.Beige linoleum.Gray exterior window glaze.Black shingle/paper roof system

Asbestos was not found in amounts greater than 1% in the sampled materials and thereforeare not considered to be ACM. See attached laboratory results.

INSPECTION METHODS

The specified interior/exterior building materials as per the provided plans were inspected forsuspect ACM, unless otherwise noted. Each observed suspect material was described andsampled. Samples were collected according to procedures established by EPA in 40 CFR 763.Samples were sent to AAL Laboratories in Tampa, Florida for analysis. Upon arrival at thelaboratory, the samples were logged-in and stored for analysis. Analyses were performed usingthe polarized light microscopy (PLM) method of asbestos detection using guidelines andprocedures established in the Method for the Determination of Asbestos in Bulk BuildingMaterials (EPA-600/R-93-116 July, 1993). Results were provided as percent (%) asbestos byvolume. Samples found to contain greater than 1% asbestos were considered positive andlisted as ACM.

LIMITATIONS OF SURVEY

This asbestos inspection report has been prepared by EE&G in a manner consistent withindustry standards exercised by members of the profession practicing under similar conditions.No other warranty, expressed or implied is made. The intent of this survey report is to assist theowner or client in locating ACM. Under no circumstances is this survey to be utilized as aproposal or a project specification document without the expressed written consent of EE&G.

The survey was conducted to identify suspect ACM in accessible interior and exterior areas ofthe subject structures as per the Client provided plans. If other areas at this location are to beimpacted during planned or future renovations, a separate asbestos survey of these areas willbe required. Some ACM may not have been discovered due to inaccessibility ormissing/incomplete plans. Suspect materials discovered subsequent to the issue of this surveyreport should be sampled and analyzed to determine asbestos content and to initiateappropriate responses.

Analyses were carried out by PLM. While the most commonly accepted analytical method fordetecting asbestos in bulk materials, PLM is known to have limited resolution and may notdetect extremely small asbestos fibers. Certain materials, notably vinyl floor tiles, may containextremely fine asbestos fibers that are beyond the resolution of PLM.

PEACOCKRANCH COMPLEX SURVEY

Mr. Bert BenderDecember 21, 2017Page 3

EE&G's interpretations and recommendations are based upon the results of sample collectionand analyses in compliance with environmental regulations, quality control and assurancestandards, and the scope of work as indicated in EE&G's proposal. The results, conclusions,and recommendations contained in this report pertain to conditions observed at the time of thesurvey. Other conditions elsewhere in the subject building(s) may differ from those in theinspected/surveyed locations and, such conditions are unknown, may change over time, andhave not been considered.

This report was prepared solely for the use of EE&G's client, and is not intended for use by thirdparty beneficiaries. The client shall indemnify and hold EE&G harmless against liability for lossarising out of or relating to reliance by a third party on work performed thereunder, or thecontents of this report. EE&G will not be held responsible for the interpretation or use by othersof data developed pursuant to the compilation of this report, or for use of segregated portions ofthis report.

SURVEY AREA DESCRIPTION AND OBSERVATIONS

FORMER HISTORIC PEACOCK HOUSE & BARN

PEACOCK HOUSE

The two-story Victorian-style home was observed to be constructed primarily of wood and metalon concrete footings; interior walls were observed to be finished with painted plaster board;ceilings were finished with painted plaster board and finished wood. Floors were observed to befinished with linoleum, vinyl floor tile, carpet, and ceramic tile on wood. No heating ventilationand air-conditioning (HVAC) system was observed. The exterior walls were observed to bepainted wood. The roof was observed to be finished with asphalt shingles. According to theclient the home also incudes an attached addition built years later. County records for year builtand square footage were not available at the time of this inspection.

PEACOCK LODGE

The single-story Victorian-style structure was observed to be constructed primarily of wood andmetal; interior walls were observed to be finished with painted plaster board and finished wood.The interior floors and ceilings were finished wood. The heating ventilation and air-conditioning(HVAC) system was insulated fiber-glass sheet metal or fiberglass flex duct. The exterior wallswere observed to be painted wood. The roof was observed to be finished with asphalt shingles.County records for year built and square footage were not available at the time of this inspection.

PEACOCK BARN/GARAGE

The one-story open-air barn structure was observed to be constructed primarily of wood andmetal; no interior paint was observed on the interior wood walls, ceiling, and doors at time of theinspection. Floors were observed to be unfinished concrete slab. No heating ventilation and air-conditioning (HVAC) system was observed. The exterior walls were observed to be paintedwood. The roof was observed to be finished with asphalt shingles. County records for year builtand square footage were not available at the time of this inspection.

PEACOCKRANCH COMPLEX SURVEY

Mr. Bert BenderDecember 21, 2017Page 4

RESULTS

The results of the PLM analyses and assessment of suspect ACM are as follows:

Asbestos-containinq materials (ACM)

Asbestos was found in amounts greater than 1 percent in the following material and thereforeare considered ACM:

PEACOCK RANCH HOUSE

• Brown Linoleum (20-25% Chrysotile) found in the kitchen, pantry and the hallbathroom (Approx. 330 SF).under the yellow linoleum

• Gold diamond pattern Linoleum (20-25% Chrysotile) found on the floor of the lastroom of the original building (Approx. 60 SF).

• Light Green Linoleum (20-25% Chrysotile) found in foyer next to the stairwell onthe first floor (Approx. 30 SF).

• Yellow Linoleum (20-25% Chrysotile) found under the beige linoleum in the bathroom of the original house

• White Linoleum (20-25% Chrysotile) found on the bath room floor of the 2nd floor

PEACOCK LODGE HOUSE

Asbestos was not found in amounts greater than 1 percent in any of the materials sampledtherefore are not considered ACM:

PEACOCK BARN/GARAGE BUILDING

There where no suspect materials on this structure

Nonasbestos-containing materials

Asbestos was not detected in the following material:

PEACOCK RANCH HOUSEWhite drywall system.

• Beige 12" vinyl floor tiles

• White window caulk.

• Black shingle/paper system.

PEACOCK LODGE HOUSE• White drywall system.

• Grey linoleum flooring (layered)

• White 1'x2' ceiling tiles.

• Beige linoleum.

PEACOCKRANCH COMPLEX SURVEY

Mr. Bert BenderDecember 21, 2017Page 5

▪ Gray exterior window glaze• Black shingle/paper roofing system.

The original laboratory report is attached.

BARN/GARAGE BUILDING

No samples collected

CONCLUSIONS AND RECOMMENDATIONS

RECOMMENDATIONS FOR CATEGORY I NONFRIABLE ACM

The nonfriable ACM brown, gold diamond pattern, light green, yellow and white linoleums werefound to be ACM. These nonfriable materials must be removed prior to renovation activities thatwill crush, abrade, or pulverize its matrix. Removal and disposal of this material must beperformed by a Florida-licensed Asbestos Contractor. However, if these materials are not to beimpacted during the renovation, then no other special handling is required.

If other specific areas at this location are to be impacted during planned renovations, anasbestos survey of these areas will be required. Suspect materials discovered after thisinspection should be sampled and analyzed to determine asbestos content and to initiateappropriate responses.

The Florida Department of Environmental Protection (FDEP) require notification of intent toabate or demolish. Notification must be sent at least 10 working days prior to the start of anydemolition activities. The general contractor should also keep a copy of this survey at thedemolition site during the entire project as proof of compliance with 40 CFR 61 (NESHAP).

EE&G appreciates the opportunity to provide you and your organization with environmentalconsulting services. If you have any questions or require further clarifications, please do nothesitate to contact us at (305) 374-8300.

Sincerely,

Richard GrupenhoffMiami Operations ManagerEE&G

Attachments: Laboratory ReportFiguresPhotographsCertificates

Jay W. Sall, CIHIH Practice Director, EE&GAsbestos Consultant #AX0000011

PEACOCKRANCH COMPLEX SURVEY

Mr. Bert BenderAppendices

PLM LABORATORY RESULTS

PEACOCKRANCH COMPLEX SURVEY

AAL:

American Asbestos Laboratories

SENT RENDER & ASSOCIATES ARCHITECTS

TO 4Itl ANGELA. STREETKEY WESx`, .FL 33040

_BERT RENDER.

P/iutItL. 30-29(-1347

305-29(n2727

^3ftt111:

6lhCntlersa'brIlSnut1mun

Thank you for. yourbusiness.

Analysis; Polarized Light Microscopy (PLA/i) with dispersion staining techniques according to theUnited States (US) Environmental Protection Agency (EPA) 'Method for the Determination ofAsbestos in Bulk Building Materials', EPAJ600/P-93i-116, July 1993.

AAI_,

Asbestos Dep rtmcnt

5005 WEST LAUREL .STREETSUITE

TAMPA, PL 33607NVLAP Lab Code 10.1775

(81 3) 2887- 1 0055

PRE PAREDBY::

.Date inDate put:

Thursday', December 07, 2017

Friday, Dec 15 2017

This report may not be reproduced except in full, without the written approval of AAL, AAL wif( not be held responsitrle for the use of itsreports issued in part to third parties or authorized agents of the client.

Thisreport shall not be used by the client to claim product endorsement by NVLAP nor any agency of the United States Government, AliNVLAP reports displaying NVLAP logo must have at least one signature to be valid.

Due to the small size of asbestos fibers associated with vinyl floor tiles, 1'D46 analysis isecenimeti

for all floor tiles contairnng <1%ar no detectable asbestos by visual estimation.

The following analytical results presented in this report pertain only to the samples analyzed. American Asbestos Laboratories assumasno responsibility tot whether the samples accurately represent tho material to question

ec 15 201''.7i

PM

LABORA TORY K AMPLE A1IFND. 1F . R .,'\ SSOCLATESARC.HITEC'.1S

P Ac :.'OCK RANCE! 'l-IOUSIE LIOLINTY I ROA. El

1.4forh Order: T 71205'9

. T..

'

CLIENT:

PROJECT:Asbestos analysis Of bulk

materialsvia EPA 600/R/93/11 . 6 Method

using Polarized: Light MisottiscOpy (PLM).

01 A KIA

WHITE:DRYWALL

2ND RM ON RHT 1ST FL

: CmmLPIS; NO JOINT COMPOUND ERF5FNT

c1 ,E:....

KIA

1N-F1 1 'LE DR Y WA M SYSTF.M.

ADDITION : 1STFL

j'SIO

DETECTE.DI;,yLl1 NI) AMPS -1 OS

P.D IN WHILE . DRYWAI

: NO ASIJI-SI US DETECTED:IN WHEI.h MINT COMPOUND

C KIA

^ Ill FL L)RFWAI 1 .S .YSTEM

HALL 1S. T FL

No ASHES] OS abi EL FrI2yo . l NO AM=IESTOS DETECTED IN WHITE .DR'y -WAI.

NO AMIES

DEFEL I TEDIN WHITE JOUST COMPOUNDo o2 _____

01 D' NIP

\ HLI . E DRYWALT SY SI EI\T

1.S'T RM ON RHT 1ST FL

"141

NO ASIAENTOS DETECTED IN WHITE DRY -WALT

NU A!"IBLSIDS Dtfl"!''CTED IN WHITE JOUST COMPOUi N3

001 E KIA

\,VLIITE DRYWALL SYSTEM

OFFICE 2ND FL

.liiil-5

I.;;i:.c(E N.0 ASBEtiT.).SDL'I ELl ED IN WHITE DRYWALT.

: ,y n..E7: NO NiiESTOS Dh''rEUED IN Wlil.TE JOINT CONIPOUNa

PF RCFT 7-: i SL?i'::S.T OS FIBERS.

Sample

AMOS CI?OC TRFI;' A,SI T.g 0TH .El?

NON FIR FIBERS222.2 .

. .

NO A . SRES'lUS 1.)f.;:TECHI IE)

(her. gy_ 91?

NO ASBESI QS D1:TF1' 1

CenultVc 10- 1

ONT. S5-90

ASI-IFI-T US DE

.... Report Continued on Next Page

01.hc.iri 80-'90

NO.ASBITS'l- OST)ETEC'FED IN Y1:A1 0W CLUE

Report Con,tinued

Ni Pace; ,

Friday, December $ 5i 2017

Pago 2 of 6

Other- 50- 9O

NO ASBF.TeS

TN YELLOW (3LuE

LABQRATOr.i `B L C SAMPLE ALYS1 ,EPORT CONTINUED :

PERCE,NTASRFSTosrmEA,s,4MOS CI?OC 1R.E.4f ANTM

Ol F KiA

WHITE DRYWALI 81;YSIIM

HALL 2ND'FL

I: NO AfiRFSTOS DETECTED D WHO I: DRYVv".ALI

i 102: NO ASIETI IN WITITEJOINT'COM FOUND

WHITE DRY

L.SYS EM

BR 2ND'FL.

14.'ci . 1 NO ASBFRIOSDETECEA) I WHITE DRYWALL

.NO ASBESIUS D.hl LED IN WHO'EJOINT COMPOUND

NO ASFIFSTOS.DEIELH HD

Oilir. 85- 90

NO ASBESTOS .DE i

HI)

r`ilass 5-10

CiHiiilo,i z- i

07

KV,

YFI oW I

FIJNI BATHROOM HALL J10 2!11 NO ASBESIOS DETECTED Ghis . 5- 10

Ci..iftilosi:7 5- 0

Friday, December r5; 2017

CLIENT:

3&. O r;,}rC ARC^HII.LCTS

PROJECT:

FA{7OCN.RANCH NO1.;.i5L.COV T'i ROAD 709

%e ori`c Order:

1712059

73re:11

T'

c,:C'PIPTICI;,

03 A KIA Iih1

\VN I. INOI.1.7IM

03 B VIA RPLAVN LINO!

-l.NI

04 :A. ,t<IA 0011) IJIAMOND PATTIRN 1 INM..E_:'.!51

05,..A, KIA 'BFI(;i

i? \ 12" vl i

05 B. VIA PF1075 12.1'.X12. " \iF `

05 C - KIA P5100 .12 IXU V1.7

06 KIA [

1.

19( ILPlIM

Pegg 3 of 6

LABORATORY UL K SAM,! - LEr +: S IA L SS REPO RT CONTINUED

!-F•l'^t 77C)^. .Srnnju`r^:^'n,

ADDITION ROOM

PANTRY

N L?

ADDITION ROOM

LA,^T ROOM OF ORIGINAI h 11-12

LAST ROOM CF Qi 1GINAL. 1;444.3

Otis r. 9!3 _

LAST ROOM 'OF ORIGINAL. N ^. A: -k

111,

111;+,x:995

,9

FOYER

N-1 ti.^ 1

)

c,I!ul;-n :„

PERCENT

C'LiiYi'1)1'.S

^,pI,^.'^fi 1-:^S70^S FIRERS

OC' 1/Rf .4 NTH D1I1T'I7

1.01 I A

I LBE.RO

001. 1 95- 99

NO ASBLS I OS DL I I_C 71-D [N S F-I l r1:y` G11 IF

0:111_11,3: [. - 2

1 JHVlIt n P A.1 I IRS) ,DUI ANA) l II I)

C'c I IU.I l i;SZ

!_)IjfiS

NO ;: SBO l OR 1)1- .Trl

Frith y, December 15, 2017

CLIENT:

PROJECT: LABORATORY BULK a5AA/PLE ANA C.Hl:'NDER A A;NOL'I.\II N ARCHIIOIl TS.

L iOUSF, COUNTY RUAl 709

Page 4 „f 6

REPORT `OhlT! t FDWork Order: TI? A-In

Dach PER CENT A:rRES .7 OS 'IRE!?

,t DESCRIPTION 1_OC:4lf0.5 Sawnhf<> b_ 0HR }" A :IIOS Cl? CI0

TEEM

. N J H Ft^ ER,S ,

07 A KIA [ 1IiII- LINO; FLA1 BATHROOM CENTER NO ASBES I ON DE11 U I i-fl

ow,,r . 9`-

vO::ASRIPI(_1ti Dl

lI-t

di-[) Ih ^'1'I:I

)(ii

i!

Don,5

NON

1

C'cl(1dus,c

08 A KIA \ A , .'

I

INC)!

U1; 1 [IATFIROCJlvl (II NT[.H /1.4

ti'IOSD1

III'

I) IYI

_I (P0

^.iIl(I .

00 .A KA 0[ 0

LINOLEUM, BATHROOM CENTER I

-:GR NO ASBESTOS . T.)1 IL•C'i i-;i)

r lin r. 4;_ 91

lhihisc

NO ASBFSIOS DEg ht;!h17 LS.l'FI 1CAN, GLLIP

10 .A

1

10 C

Ii1fs.

KIA

KIA

41'L111 11..11.101.

_?

11111I[

1.1N(ILl(ti5l

VdlltI I INa)I 1100

2NOFI EAIHPP)l)Ivl

2ND FL BATHROOM

7NH FI EA HFIOOM

H4 -

/

4 o

^[t

\S111

0 1 :15

.11

! I,(

I I•.I.1IN ) I.(.I (AV

two]

N 1

0 A l

I I I? S I

I) 'N 111'0 i'

No l

AN 1 i

;ID

ti11(I',-N

IIl/NI I''(NI 01

'VI IIANA! 1[[1!

1

A KIA x`HHEWINDOWt0.A7E . EXTERIOR WINDOWS NO ,\SJ1FSUOS D

lI'E 1. Fn

O h,98 . u`

Report Continued on Next Page:

LABORA TOR BULK SAMPLE ANAL r' J REPORT CONTINUED

AS11E1OS FIFERS

1

%i'lv0A I -ASS

Sainpie Ao,

CH RI A ..IIOS CR00

R!Ijl 1:\'TH OTHER.. INON E713' FIB'E' RS'

NO ASBESTOS DE I EC f FD Crllnlosy

Oilier. 98- 99

NO A'.111141-4101,

11 =1.

.,1'19-,r

OLITL:l Si- 90

H;,19-25'

H49-26

K.4

NO '\ ,cl-31srosbI11-(, ED

Glass i

Ollli°i S5. 911

NO ASBFSFOS UFTEI 10

NC.) ASRESIOS DEFEC'l FD

SBES T OS DL 1 EC I D

00,,r.,1

NO ASBESTOS D: I EGLI I LF

Olh n:r_ 85- 90

NO ASBI T S 1uS DL EC, 11-n

Friday, DOcembor 15, 2017

CLIENT:PROJECT:

BENDER&

REAL:U(1. RNC1.11H01...I S

10141 . 1kiTTS

Y RoAb 7 '7i?

Order:

1:1.7T 91 .059

Dii sh.

I) I:SCR/PITON

11 B K1A WIR-ItE9WINDOW OLI,ZE EXTERIOR WINDOWS

KIA WHITE WINDOW ULA/.R EXTERIOR WINDOWS

.... ,,,..

tll. :D KIAWLIFTE .WrND(W CTLA/..E EXTERIOR WINDOWS

E KIA wHI.LL WINDOW GEA EXTERIOR WINDOWS .

A.. KIA Ni ^;+'K SFIINCTDF BUR ROOF

12 .9a KIA 1II ACK Sll ROOF

.12 C HA RI ACK RobO.

KIA BI

SHINGLF RUR ROOF

Repoli Continued on Next Page

Friday: 00comber 15, 2077

Page 6 of 6

CLIENT:

PROJECT:

Work Order:

sNnre»xxsncWTTsARCM |K r S

pr^rncuRAN( a xnuSi- mw1 o(Ja) :AP)

1-1;N '2050

LABORATORY BULK SAMPLE ANALYSIS REPORT CONMVUEP

Analytical result-, pertain only to the sw^7J^(s)analrzod. All Samples analyzed were acceptable for analysis.ABBxsvIATlONci ANA =*uNysO ASE ~xs^csmm i CHRY=ChqrmleAMos=Amus0,: CRnt=c/m,iomo, TERM =Tv " ,i.iA.#AmTH=»umonxyme:

ACT =Admo|uy AL =mvmmvm': SLK = Brack, .BACK =oarmng BL =n/uy SRN =om*, ; o=WomneCAC = cnfoai e*vmC pr=Cwn*t CM =oemT THE,:

OFM 55 Ceinea 0.0\1= Cover; DEE.= Debris; PG . = Fiberglass; HS = Fibrous; MAS 55i'Masticc MAT = Material; MIC = Micaceous; MVV =Mineral Wnoi; .ORG Orange;.

.. PAI = Pain( .PAP :5= Paper: PL = Plaster, PLAS =..PlastIcc

= Powder . ; RCF 55. Refractory' Ceramic. Fiber; RUB . = Rubber; Sib..=

= Sheet Rock. S =Synthetic;

SUE i=S"»ua"u*; Wr=Te,ureo, Tn=Trara,TnAn=nwo0iii7REM A Tanonq VEnm0 Yo"Woo, vYL= whyL.Yv= \wo|m^*vx uY* Vmiei YeL=YAlaw

ocrCxI rooa

ux\

mx(:]^ sHiVU(/aun

N0x/Io n f'Jxens

NO AM& % WS DH W 41)ROOF

Loc"If 1,10!N ,

WVO

Sample.

^

r" 'vOX-ASRDash

12 E

.BU-LK TES

CHAIN 0.F CUSTODY

CLIENT'

CLIENT CONTACT:

DATE COLLECTED:

DATE SENT:

STOP AT FIRST POSITIVE;

PROJECT:

PROJECT NO./BILL GROUP:

PROJECT PHASE:

DATE VERBAL NEEDED:

DATE WRITTEN NEEDED

CHAIN OF CUSTODY:DATE/TIME

PRINT NAME/SIGNATURE-._

PURPOSE

EE&G Environmental Services, LL5751 Miami .Lakes Drive EastMimi Lakes, Florida 330 .44

CONTINUATION OFULK TRANSMITTAL FORM

CHAIR' OF CUSTODY

CLIENT:

SAMPLE PREFIX PROJECT NO./BILL GROUP:

"SAMPLE NUMBER

COLOR

SAMPLE DESCRIPTION

SAMPLE LOCATION

(,

17...

19

20.

21-.

.22.

23,

24.

25.

26.

27.28.29.30.

31.

32.33.34.35.

CHAIN OF CUSTODY:DATE/TIME

PRINT NAME/SIGNATURE

PURPOSE

T

C T A

C TCollection T'= Transoortat on A- Analysis

;SENT BENDER & ASSOCIATES ARCHITECTS

PREP

TO: 440 ANGELA. STREETKEY WEST, FL 33040BERT BENDER

P/loMt, 305-326-1347

Ftiv

305-226-.272')

Email: blbendir bell utlr,nct

'Thank you for your business.

Analysis: Polarized Light Microscopy (PLM) with dispersion staining techniques according to theUnited States (US) Environmental Protection Agency (EPA) 'Method for the Oetetrnination ofAsbestos in Bulk Building Materials', EPA/600/R-93-116 July 1993.

Sample Type: B1/LA Date in:

# of Samples. : 24 Date out!

Transported:Work Order # Ti712062 Sampled by:AAL Proje 2017-2448 Received by:

Project; PEACOCK RANCH-LODGE

RED AAL

BY: Asbestos D.Departmi ni

50.05 WEST LAt. REL..:STRE T

SUITE 1 i 0

TAMPA. F1., .607NVLAP Leib Code '10177>

(813) 2870 005

Ttitlrsdav, December 07, 2:0 .17

Monday. Dec 18 2017

FEDEX EXPRESS

BOB MIRO

NIA

Due to the small size of bsbestes fibers asSociited with vinyl floor tiles, TEM z naijisis is recommended for all floor tiles containing

of no detectable asbestos by visual estimation.

This report may not be reproduced except in full, without the written approval of AAL, AAL witl natbe held responsible for the use of itsreports issued in part to third parties or authorized agents oftne client.

This report shall not be used by the client to claim product endorsement by NVLAP nor any agency bfth e United StatesGovernment. AllNVLAP reports displaying NVLAP logo must have at least one signature to be valid.

The following analytical results presented in this report pertain only to the samples analyzed. American Asbestos Laboratones as

no responsibility for whether the samples accurately re present the material in vesper!

LABA i' YBULK SAMP ANALY"ft 1 REO

Monday, Dec 18 2.0`17, 1.88 P

BENDER &ASSOCIATES APOllO0F)TS

DESCRIPTION'

LOCATION

WITITO DRYWALL. SYSTf Ail

CHART' ROOM

NO AS13B.S,40S DETECTED

LtycrI; NO ASBESTOS 1711 LCa } D. IN WI f1-IL DRYWALL

Other: 55- 110

Ioyct2: NO ASBESTOS DETECTED 1N WHITE, JOINT CI)MPOi)Ni)

01 B KIA

WHITE.DRYWALI SYSIEEM

CHART ROOM

1 aycr'1 NO ASBESTOS DETECTED IN WHITE DRYWALL

1 a}s:r2t NO ASBESTOS DETECTED IN WHITE JOINT CON POUND

01 C KIA

WIII'IL DRYWAL1 SYSTEM

CHART ROOM

1 aycrl _ dirt ASBESTOS 1)ET I.CIL_-i) IN WI l

DRY ,WAI 1.

Layer2: NO ASBESTOS 1)0 1h.CTI 1) IN WHITE. JOINT COMPOUND

{32 A KIA

GREY I.,1 OLII;I! 1

FRONT ROOM

1'1A2-d

NO 551)1 11)5 DI IFI FF0

Cellulose: l0- 15

Asbestos analysis of bulk inateriois via EPA 600/ 1931116 Methodusing Polarized Light Miscroscopy (PLM).

PEI?(I:N:1 ;-IS1I FSTO S FIRERS

,13105 ow(' 711[';{t A1^`7'11 OTHER

}

NC) ASBESTOS DETEC

Otlict: 05. 00

t:H411Ose t0-15

11-11-3

NO ASB1-Si )5 1)1 1 L t LI)

C f-`liul[se:I

00101 v. 90

02 B KIA

GREY Lit OLEUM

FRONT ROOM.

NO ASBESTos- O CITED

02 C KIA

GREY LiNC?I D . TM

FRONT CHART ROOM-

H ?-6

NO ASBESTOS DETITTED

on,,1 -1)5- O0

(5 liet 05-'1!1

O11

85- 10

(Llli lose. 10- I>

C El)0100.: I0 I5

Report. Continued on Next Page

Monday, De+ ember 18, 2017

CLIENT

BENDER & .AS OI I AI Os ;tit 111 l N i

PROJECT: PEACOCK

Work Order': -H 712062

gays 2 of 4

LABOHATC RY BUL,1 SAMPLE ANAL .Y.SI S RE_ O. `l (0NT/N(JED

03 C KIA

GREY 1>IVEI.INCOMI'OLINI)

FRONT CHAR ROOM

04 A KIA

BLACK MASTIC. ON GREY LEVELING COMPO FRONT ROOM

)l: )?> III

04 B KIA

BLACK MAS 1-ICON CONY LEVOLING CO 'O FRONT (ROOM

hAl2- ^L)

0d C KIA

BLACK MASI It_ ON GREY LE.VL UNJ OOMI>0 FRONT CHART ROOM

/142-61?

05 A ILIA.

WHIFF I'12 t I n tl (.i TILES

EAR. ROOM

11:13-7

M nth y, DecntiSher 18, 201.7

CLIENT:

BENDER & A .OC'(ATI?S ARCl4CII CTS

PROJECT:

Work' Order: x1112552

1'l:Rrili; I tJ 47,'1;,

I4IBI.:17.4

AMOS CROC 7771:,41 ANTI" 0 .11IFIR

NO AtillOS1C)S Dtt iECTFl)

LABORATORY BULK SAMPLE .ANA YSI 3 REP( '0- CON IN - UED.

Page 4 of 4.Monday, Dedei t7ber- 18, 2017

CLIENT:

BENDER ,+.: A sOrIAi t_s ARCLII I ItC ( S

PROJECT:

PE ACOCK R.AN(. II . 1 oDri0

Work Order: 7171206

Analytical results pertain only to the sattiFsle(s).aitalyzed. All Samples analyzed Were acceptable for analysis.AFIBFFE"VIAT"IONJS:

ANA = Analyst; A` l) = AsbeStaS; CHRY = Chryrtatile; AMOS = Ambsite: CRO0 = Croc;idelite; TERM - Term/Act; ANTI-I = Aothol?Iiylit

Al.1 Aclinniite; AL Aluminum; HLK =:Lllac;k BACK = Booking; BL = Blue, 8EN = Brown; C = Cellulose; CALL r..alrcreous; CPT - Garpoi; G I L Oei/mi Tile;

OEM = Cement; COV =Cover; DEB = Debris; F0 Fiberglass; FIB = Fibrous; MAS Mastic; MAT Material; ME; = Mir:ace nrs; MW = INir'ieral Wool; ORG Orange;

PA! Paint; PAP -= Paper; PI = P1/isfer; PLAS - Plastic; EWDR =- Powder; ROE = Refractory Ceramic Fiber; RUB Rubber; SIL = Silver; SR = Sheet Rock; S = Synttirotic;

SUB = Substani^e; J EXT = Textured; TR = Trace; THAN i = Tiansitr . T1:1= M r Tremalite; y/[ EM VernuGUlits; AMYL = Alrnyli W a Wgllastonilo; WH ` W hip:, S [L = Yellow

CHAIN OF CUSTODY:DATE/TIME

PRINT NAME/SIGNATURE

EE&G Envi ownentai Services, LLC5751 Miami Lakes Drive EastMiami Lakes, Florida 33014

CLIENT:

CLIENT CONTACT: . '-

DATE COLLECTED:_

DATE SENT:

STOP AT FIRST POSITIVE: Y,

(circle one)

PROJECT:

PROJECTNO./BILL GROUP

PROJECT PHASE:

DATE VERBAL NEEDED:,

DATE WRITTEN NEEDED

Mr. Bert BenderAppendices

FIGURES

PEACOCKRANCH COMPLEX SURVEY

SCALE I/6" = 1'-0"PRO.IECT

NCRTH

1 PEACOCK 1-LOUSE - EXISTING FIRST FLOOR PLAN

X

P10J No

1728

HOUSEEXISTNGFIRST FLOORPLAND x

12fd0f17

EX1

FFm4A16044(2FB^i

r-

F CORi220.

W421410. ®.

VI' Aff.

/Wa n TWR 2RB£Na

A3401.S 2014412RIXfR44

Q R6R'1-0 HEIE01E

ACM WHITELINOLEUM

r- - -FINR^ 422027

WLWn 42?. La.425' Aft.

40144

AwaT sWF4a=

e-O42E GM.

PEACOCK HOUSE - EXISTING SECOND FLOOR PLAN

X

L-

FOAL CARPET

e-ORI N'

2429 0! m'1415' Aff.861

LJ/

C

SCALE I/8" = I L ORnaoa.T

NORTH

Pt*ctNo.

1728

HOUSE

EXISTNGSECOND

FLOOR PLANDl

12x30117

EX2

0,

Prt oLt No.1728HOUSEEXISTNGROOF PLAN

Deb

1N30117

PROJECTNOR'.

EX3

-----------------------uauur SwHGLE E02512 - - -

RIDGE

II -- ASPHALT SHRCLEROOFINGL.

LINE OF 144LL5-BELOW, TYPICAL

PEACOCK -IOUSE - EXISTING ROOF PLAN

X1

SLOPE

AStNALT SWNGLE ROOFMG

SLOPE-9

ASPHALT %gros R 2fil

I

RIDGE

SLOPE

L

SURE g SLOPE

SCALE I/8" = I'-0

4,2ND FLOOR F.F.

PAINTED WD. BOARDAND BATTEN SIDING

tq 15T FLOOR F.F.

Ct1U FOUNDATION WALL

CQKRETE 4 BRICKSTAIR

11^ ^ PEACOCK HOUSE - SOUTH EXTERIOR ELEVATIONX

SCALE I/8" = 1'-0"

PEACOCK MOUSE - EAST EXTERIOR ELEVATION0

FIDlBCt No.

1728HOUSEEXISTNGEXTERIORELEVATIONSDim

1Nd0117

EX4

SCALE I/8" = I'-0"

PEACOCK I-IOUSE - NEST EXTERIOR ELEVATION

SCALE I/B " = 1 '-0"

^1^ PEACOCK MOUSE - NORTH EXTERIOR ELEVATIONgX

Pm)xtNo.

1728HOUSEEXISTNGEXTERIORELEVATIONSDell

17140/17

EX5SCALE I/B" = I'-0 "

DETERIGRATEDASPHALT SHINGLEROOFING

PAINTED WD. SHINGLE SIDING

PAINTED WD. BOARDAND BATTEN SIDING

,OD,ES

12111 FOUNDATION WALL

1SCALE I/S" = I'-0"

BRICK MASONRYCHNINET

T.O. RODE

C

FAINTED AID.SHINGLE SIDING

• 2NDFLOOR F.F.

t

i9

PAINTED WD. BOARDAND BATTEN SIDING

157 FLOOR F.F.

APPROX. GRADE (VARIES)

1 PEACOCK I-IOUSE - BUILDING SECTION

X

PIDJad ND.

1728

HOUSE

EXISTNGBUILDING

SECTION

Data

12=7

EX6

------------------

QI

CronAFF.

gX

FlKW VWRG VMAD.

FlM1.KEE6R I. VV-MM

4113' WY .

BERKan CCWETMO KTnW W.F.

an Cnncam. ACTWS' W.F.

Fwd aAT

1 a I

I-

RCF AEOlF.

--Ia O/wwa mm

5T00 / ON. 500

----------------------

L ^- JGABEL

`I V-maAW Vau

F K, WRPEFmao V-mao

.1

C'-

Am mass-1- J I ,,,.,.n ma

(n' I I

FILM manCnttN. V-GnO/E

awn.®.A' APF. A

Z

EKGEtLMOO, VLF

CFAIIW V-mAXWawnND' NOV.

r

/ \male

FUOR. VWCOLRY.. VV-444OtE

WORMHD AFF.

tan1.01EK.fitFIWKn

IXCDNIY^ V 42ONE

CYf,F.W.6' AM

SCALE I/8" = 1'-0"PROJECT

MAKIN

EACOCK LODGE - EXISTING FIRST FLOOR PLANP

PmjedNo.

1728

LODGEEXISTNGFIRST FLOORPLANDeli

12130117

EX7

LINE OF WALLSBEIll, TYPICAL i

r-

------------------

pLutsVENT

m-\

J

A' I T

d i RLOFI •

L

ATTICVENT

RIDGE

RIDGE

l5'

PWIDTIG ---

J I j

VENTATTIC

ATTIC

RIDGEVENT

15ASDILAI T `II .I s r+'FI .

PLUMBIVENT I1A

VINTVEN

ATTICVIN

RIDGE

15d

A T O4 .

/T1FI -

PLUMBINGVENT

ATTICVENT

L i

-- -I I

L ^

I

ROOF OVEWIAPIG N I I / ROOF CNERNMY,AT COOK

AT DOOR

SCALE I/8 = 1 1 -01 PEACOCK LODGE - EXISTING ROOF PLAN °PROJECT

NO2TH

Pr*olNo.

1728

LODGEEXISTNGROOF PLAN

Dew

12130117

EX8

-----------------

2 PEACOCK LODGE - SOUTH EXTERIOR ELEVATION

SCALE 1/8° = I'-0 "

X

TYPICAL

1 PEACOCK LODGE - EAST EXTERIOR ELEVATION

SCALE 1/8° = I'-0"

X

Pr*ctNo.

1728LODGEEXISTNGEXTERIORELEVATIONS

Dekt

1W7

EX9

2PEACOCK LODGE - NORTH{ EXTERIOR ELEVATION

X1

WC90OJ0

F edNo.

1716LODGEEXISTNGEXTERIORELEVATIONSMkt

1250111

J

II

PEACOCK LODGE - WEST EXTERIOR ELEVATION

SCALE I/8" = I ' -0"

'I'I1

STUCCO OVER tIA50NNRTCHIMNEY

PANTED WD. ATTICVENT

gTCNENUSAN AD

SCALE 1/8 11 = ILO"

I I fI I f11111

1 1 1 1 1I I I I I I 11

DETERIORATEDLEASPHALT SHMGLEROOFING

PAINTED IND. BRACKET

PEACOCK LODGE - BUILDING SECTION LOOKING WEST

Plajecttk.

1728LODGEEXISTNGBUILDINGSECTION

D

MOM

410 Angela StreetXe1 leeC Ylelda 33040Tel tt:

ET(8611.190.5) WETFacamflie

Elm{& Lienue AAC002022

V-GOON E CYPRESS WALLS

PAINTED YID. DH 111101701-1

PAINED 110. BOARDAND BATTEN 510111.

FIRST FLOOR F.F.

APPROX. GRADE (VARIES)1 1 1 1 1 1 1 1 If I I I I I I I I I I I l I l

I I IICtU FOUNDATION WALL

gm.

Mr. Bert BenderAppendices

INSPECTION PHOTOGRAPHS

PEACOCKRANCH COMPLEX SURVEY

Mr. Bert BenderAppendices

y

''d

Exterior of Peacock Ranch Lodge in Port St. Lucie, Florida.

PEACOCKRANCH COMPLEX SURVEY

Mr. Bert BenderAppendices

Photo #1: Typical ACM linoleum flooring in foyer to stairwells - first floor

PEACOCKRANCH COMPLEX SURVEY

Mr. Bert BenderAppendices

Photo 3: Typical ACM Gold diamond patterned Linoleum

PEACOCKRANCH COMPLEX SURVEY

Photo 5: Beige linoleum over ceramic tile in bathroom

Photo 6: NonACM Exterior window glaze

Mr. Bert BenderAppendices

PEACOCKRANCH COMPLEX SURVEY

Mr. Bert BenderAppendices

APPENDIX D

CERTIFICATES

PEACOCKRANCH COMPLEX SURVEY

Aq,; ;sIttW

4:jB ,-WO4n G'' gAgWO.i-)

SE OR .; VCS ' n i

:15 ORi

s

piiit,j:ft) '5;3jk

. ii i irr?

TflATITAS TPAt4ti4 C

A

CR' intI 7

$`

Flapi,Rl

L,.1

%if

01,41CR4 .itciR OR

tlT

tit

__

As''bb ©8 V©aeur - '

kg,.

_

9 i

900 N 1W. 5'I'lIAvenue, Fort Lauderdale, Florida 33311

his s to C'etify that

VIII IIIII IIIII IIIIIIIIIIIIIIIIIIIII IIIII IIIIIII IIX X X X X- 8 3 0 0

1737 NE 27 DR, Wilton Manors, FL 33334

o Authent

ertificate ,mvvv,seagulltraining.com

1-800-966-9933

11I Ill Illll 11111 Ili 11111 IllCertificate Number:

7 3 4 9 7

1 .3-0q):7

TO

13 -Oct-17

NDAAC Provider #451

Trainer(s): Mauk Knack

TEST SCORE: 88 %

Training Address: 900 NW 5th Ave, Poll Lauderdale, , 33311

Successful course completion based on exam score on, 10/13/17

tries E Stump, Course Spmtsov

Meets state requirements of FL49-0001020/CN-0006273 and UT (6,0 core)

f' If

I 111111111, 111111181

United States Department of CommerceNational Institute of Standards and Technology

Certificate of Accreditation to ISO/IEC 17025:2005NVLAP LAB CODE: 101775-0

American Asbestos Laboratories, Inc.Tampa, FL

is accredited by the National Voluntary Laboratory Accreditation Program for specific services,listed on the Scope of Accreditation, for:

Asbestos Fiber Analysis

This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2005.This accreditation demonstrates technical competence for a defined scope and the operation of a laboratory quality

management system (refer to joint ISO-ILAC-IAF Communique dated January 2009).

2017-04-01 through 2018-03-31

Effective Dates For the National Voluntary i_aboratocy Accreditation Program

STATE OF FLORIDADEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION

ASBESTOS LICENSING UNIT

(850) 487-13952601 BLAIR STONE ROADTALLAHASSEE

FL 32399-0783

SALL, JAY WALTEREE & G ENVIRONMENTAL SERVICES LLC5751 MIAMI LAKES DRIVEMIAMI LAKES

FL 33014

Congratulations! With this license you become one of the nearlyone million Floridians licensed by the Department of Business andProfessional Regulation. Our professionals and businesses rangefrom architects to yacht brokers, from boxers to barbequerestaurants, and they keep Florida's economy strong.

Every day we work to improve the way we do business in orderto serve you better ForInformation about our services, pleaselog onto vytivamyftoridalicense.oom. There you can find moreinformation about our divisions and the regufat ons tttat Impactyou, subscribe to department newsletters and learn more aboutthe Department's initiatives.

Our mission at the Department is: License Efficiently, RegulateFairly. We constantly strive to serve you better so that you canserve your customers. Thank you for doing business in Florida,and congratulations on your new license!

DETACH HERE

RICK SCOTT, GOVERNOR

KEN LAWSON, SECRETARY

STATE OF FLORIDADEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION

ASBESTOS LICENSING UNIT

The ASBESTOS CONSULTANTNamed below IS LICENSEDUnder the provisions of Chapter 469 FS.Expiration date: NOV 30, 2018

SALL, JAY WALTEREE & G ENVIRONMENTAL SERVICES LLC2922 FLAMINGO DRIVEMIAMI BEACH

FL 33140

ISSUED: 10/25/2016

STATE OF FLORIDADEPARTMENT OF BUSINESS ANDPROFESSIONAL REGULATION

AX0000011

ISSUED: 10/25/2016

ASBESTOS CONSULTANTSALL, JAY WALTEREE & C ENVIRONMENTAL SERVICES LLC

IS LICENSED under the provisions of Ch.469 FS,Exo,!3tio^ date : NOV 30. 2018

L1610250005421

Historic Peacock

RelocationPort Saint Lucie, FloridaAmec Foster Wheeler Project lumber: 6784173019

To:

Mr. Bert Bender, RABender and Associates Architects, P.A.

Date: 12/22/2017

From: James L. Brown, P.E.Amec Foster Wheeler Environment & Infrastructure, Inc.

December 22, 2017

Mr. Bert Bender, RABender & Associates Architects, P.A.410 Angela StreetKey West, Florida 33040

Subject:

Report of Geotechnical ExplorationHistoric Peacock House RelocationPort St. Lucie, FloridaAmec Foster Wheeler Project No. 6784173019

Dear Mr. Bender:

Pursuant to your request, Amec Foster Wheeler Environment & Infrastructure, Inc. (Amec FosterWheeler), has completed a geotechnical exploration for the above referenced project. Our serviceswere provided in general accordance with our Amec Foster Wheeler Proposal No.:17PROP.WPB.39 dated November 14, 2017; authorized on November 28, 2017. The purpose ofour work was to obtain site specific subsurface information, evaluate the suitability of the subsurfacematerials to support the proposed construction and to provide to provide recommendations for thegeotechnical aspects of this project. This report describes our field and laboratory testing programs,presents our findings, and offers our evaluation and recommendations for the geotechnical aspectsof the project.

PROJECT INFORMATION

The project involves the relocation of the historic Peacock House and Lodge from western Port St.Lucie to the city park and south of the Port St. Lucie Botanical Gardens. A Site Location Map ispresented as our Figure 1 attached to this report. We understand the city will not be relocating thegarage or extension portion house that was added on in 1968. The surrounding city park land isproposed to be constructed as a new waterfront park that will include a boardwalk, public restrooms,vehicular parking areas, and various public utilities. Our geotechnical exploration services coveredin this report only include the proposed footprint areas of the historic structures.

Both historical structures are to be relocated to an area of the park that has existing vegetation(trees and palmetto bushes) and a short section of asphalt roadway that includes undergrounddrainage structures. This roadway section is located just north of the existing park entrance offSoutheast Westmoreland Boulevard and was originally intended to be an entrance to a homedevelopment project that was previously abandoned. We understand that both historical buildingsare wood-framed structures with the Peacock House being two-story and the Lodge single-story.Pursuant to our conversations with Mr. Mark Keister of Atlantic Engineering Services we understandthat the new foundations are to match the existing historical foundations with perimeter CMU stemwalls and interior CMU piers. The wall loads should not exceed 3 klf and the pier loads should notexceed 25 kips. The building foot prints for the Peacock House and Lodge are approximately 72feet long by 30 feet wide and 94 feet long by 44 feet wide, respectively.

2580 i,Aetrocentre Blvd. Ste. #6 •'.Vest Palm Beach. F6 33407• Ph:(561) 242 7713 • Fax:(561) 242 5591Amec FosterV^dheeler Environment & IntrastruCtare, Inc:.

Historic Peacock House Relocation

December 22, 2017Amec Foster Wheeler Project No. 6784173019

FIELD EXPLORATION

To explore the subsurface conditions throughout the site, five Standard Penetration Test (SPT)borings were performed at the approximate locations shown in Figure 2. The borings wereperformed using a truck-mounted CME 55 drilling rig equipped with an automatic SPT hammer.The borings were terminated at depths of 30 feet below the existing ground surface. The boreholeswere advanced using rotary-wash drilling methods, with SPT sampling performed in generalaccordance with the procedures described in ASTM D-1586. Sampling was performed continuouslythrough the upper 10 feet and at 5 foot intervals from there down. Upon completion of the drillingand testing operations, the boreholes were grouted with a mix of soil and cement. Field TestingProcedures describing the drilling, sampling and testing techniques are attached.

The field exploration was conducted on December 11, 2017. The test locations were determinedin the field in reference to existing features using a measuring wheel and a hand-held GPS. Apreliminary Landscape Plan prepared by Lucido & Associates and revised by Bender & Associateshas been reproduced as our Field Exploration Plan, Figure 2. We estimate that the actual testlocations are within approximately 15 feet of the locations shown in Figure 2.

Proposed grading plans were not provided at the time this investigation was conducted and wehave not been provided with topographic information for this project. Further, the determination ofthe ground surface elevation at the test locations is beyond our scope of services. Thus, the depthsshown and/or referenced in this report and its attachments are with respect to the existing groundsurface elevation at the test location.

LABORATORY TESTING

Soil/rock samples collected during our field exploration were placed in moisture proof containersand transported to our West Palm Beach laboratory. All samples were visually classified anddescribed using nomenclature consistent with the Unified Soil Classification System (USCS). Inaddition, select soil samples were subjected to laboratory testing to aid in their classification. Thelaboratory tests included moisture content (ASTM D-2216), fines content (ASTM D-1140), organiccontent (ASTM D-2974) and particle size (ASTM D-6913) determinations. Descriptions of thelaboratory testing procedures are attached. The results of our laboratory tests are presented in theattached Summary of Laboratory Test Results, and Particle Size Analysis Reports. In addition, themoisture, organic and fines content are noted on the attached Soil Test Boring Records, at thedepths from which the samples were recovered.

The soil/rock samples collected during our field exploration will be kept at our office for a period ofthree months from the date of this report. The samples will then be discarded unless you requestotherwise.

SUBSURFACE CONDITIONS

Graphical representations of the subsurface profiles at the explored locations are presented in theattached Soil Test Boring Records and Generalized Subsurface Profile. They also include SPTpenetration data, detailed descriptions of the subsurface soils and laboratory test data. Thestratification lines and depth designations on the Soil Test Boring Records represent theapproximate boundaries between soil strata, based on our observations during the performance ofthe soil borings and examination of the collected soil samples. Actual transitions between soil stratamay be gradual and indistinct.

Amec Fcstef- 'dlhee!er Environment % Irfrastructu e. Inc.2580 IvIetrrcr.ntr , Blvd. Se. #i . lest Palm Beach. FL 334070 Ph (F31 j 242 7713 0 Fax:(561) 242 5591

Historic Peacock House Relocation

December 22, 2017Amec Foster Wheeler Project No. 6784173019

As shown in the Soil Test Boring Records, the subsurface stratigraphy at the explored locations anddepths consist generally of very loose to medium dense pale brown to dark gray fine sand withvarying amounts of silt and clay (USCS types SP to SM, SP-SC, and SC) from the ground surfaceto the termination depth of the borings at 30 feet. At each boring, a layer of weakly cementedorganically stained silty sand to sand with silt (locally termed "Hardpan") was encountered at a depthof 3.3 to 5.5 feet and thickness of approximately one foot. Boring B-5 was performed first and wasadvanced to a depth of 32 feet as it encountered very loose sand with silt (SP-SM) layer at a depthof 28 to 30 feet that in turn was underlain by a medium dense layer of shell with silt extending to theboring terminus. This very loose sand layer underlain by shell was also encountered in borings B-1and B-3 between depths of 28 to 30 feet.

Groundwater was observed in the boreholes at depths between 3.8 and 6.0 feet below the groundsurface, as noted in the boring logs. Please note that fluctuations in the groundwater level areanticipated at this site in response to seasonal climatic changes and variations in rainfall amongother factors. Groundwater levels somewhat above the levels observed at the time of ourexploration should be expected after periods of heavy rains, particularly at the peak of the rainyseason.

EVALUATION AND RECOMMENDATIONS

Based on our evaluation of the subsurface information obtained from our field exploration program,we consider that the soils underlying the proposed building footprint are generally suitable for theproposed new foundation construction using conventional site preparation procedures andfoundation systems. Following we offer recommendations for generalized site preparationprocedures and the design of new foundations.

We recommend supporting the historical structures on the proposed shallow foundations designedfor a maximum allowable bearing stress of 2,500 pounds per square foot (psf) provided thefoundation system consists of stem walls with a minimum 2 foot wide foundation width and the CMUpiers are a minimum of 3 foot square, also a minimum 1.5 foot embedment below final gradeelevation is recommended for both foundations types. Based upon the boring information andprovided loading conditions, we estimate that the recommended allowable bearing stress willprovide an ample safety factor against a bearing capacity failure. With the subgrade soils and fillcompacted as recommended, we anticipate total and differential settlements of one half of an inchor less.

As previously mentioned, the proposed building footprint areas are located within an existing asphaltroadway section that includes underground drainage structures. We recommend removing theexisting roadway section and drainage structures and casting the new foundations on fill materialmeeting the following recommendations.

The construction areas 3 feet beyond the building footprint slab should be cleared and grubbed toremove all vegetation and topsoil. Any root concentrations, yielding or otherwise unsuitable soils ormaterials detected during the clearing operations should be removed from the proposedconstruction areas. The exposed surface should be recompacted by several passes of a heavyvibratory roller compactor before placing any fill material as required to achieve the planned finalgrade elevations. In addition, bottom of the foundation excavation should be compacted with awalk-behind heavy duty vibratory plate compactor or vibratory rammer. Proofrolling and compactiondensity testing procedures are presented in the following paragraphs.

Amec = os,e iJheeler cnv ronment & Infrastructure. inc.2580 '/etrcce.ntm Blvd. Ste. #b •'V'lest Palm Beach. Ft. 33407s P h.(561) 24? 7713 • Fax: 561) 242 5591

Historic Peacock House Relocation

December 22, 2017Amec Foster Wheeler Project No. 6784173019

Clearing

All vegetation, topsoil and debris should be stripped and removed from the construction areas.Remnants of old pavement and abandoned underground utility lines or other buried features, ifpresent, should be removed entirely from within the construction areas and theirexcavations/depressions backfilled with approved fill material, placed and compacted in lifts asspecified below.

Proofrolling and Initial Compaction

Following the clearing operations, the exposed surface shall be proofrolled using a heavy (10 to 12ton) vibratory roller. The purpose of the proofrolling procedure is to identify near-surfacesoft/yielding soils. Any areas that rut or deflect excessively during the proofrolling process or areaswhere the presence of unsuitable soils has been determined through further exploratory effortsshould be excavated as needed to remove the yielding/unsuitable soils, and subsequently backfilledwith approved fill material, placed and compacted in lifts as specified below. The proofrollingoperations and the replacement of unsuitable soils, if any, shall be witnessed by a qualifiedinspector.

Sufficient passes of the vibratory roller should be provided to produce in-situ dry densities equivalentto at least 95 percent of the Modified Proctor (ASTM D-1557) maximum dry density value of thecompacted materials to depths of 12 inches below the compacted surface.

Placement and Compaction of Fill Material

Once the soils exposed during the clearing operations have been proofrolled and tested to verifythat the specified compaction levels have been attained, the construction areas can be filled to thedesign finish grades. Approved fill material should be placed in thin lifts, 12 inches or less in loosethickness, individually compacted with a heavy vibratory roller. Utility trenches and other areas oflimited access as well as areas located in close proximity to existing structures can be compactedusing light compaction equipment such as vibratory plate tampers or vibratory rammers. Fill to becompacted with light equipment should be placed in thinner lifts, not exceeding 4 inches in loosethickness. Each lift should be thoroughly compacted so as to produce in-situ dry densitiesequivalent to at least 95 percent of the Modified Proctor maximum dry density value of thecompacted materials.

All fill/backfill material should consist of relatively clean sands (USCS types SP, SP-SM, SW), orcrushed limerock, free of organics or otherwise deleterious materials. If crush limerock is used, itshould have a relatively uniform gradation from gravel to silt size, and should have no rocks largerthan 3 inches. Depending of local availability, consideration can be given to the use of silty sands(SM) with fines content of up about 20 percent as fill material. However, it is noted that these soilshave a tendency to retain moisture, which renders them difficult to handle and compact unless verystrict moisture control is exercised.

In order to verify compliance with the above recommendations, the site preparation proceduresshould be monitored and tested by representatives of our Firm. We remain available to provideinspection and testing services as needed.

Amec Foster^^Jheeer Snv^rcnrren & Intrastn.ic(ure. !nr..2580 Metrocentre 31va. Ste. #6 • &iest Palm Seacn. FL 33407+ Pt': 1) 242 7713 • Fax:(561) 242 5591

rnAmos Foster Wheeler Project-No. 678tlf 73019

D ceber 22,Historic Peacoelt House Relocation

CLOSING AND LIMITATIONS

Our professional services have been performed, out-findings obtained and our recommendationsprepared in accordance with generally accepted g eotechnical engineering principles andpractices. We do not guarantee project performance in any respect, only that our work meetsnormal standards of professional care. This company is not responsible for the conclusions,opinions or recommendations made by others based on the data presented in this report.

The analysis and recommendations submitted in this report are based upon the data obtainedfrom the field exploration program and our understanding of the proposed construction describedherein. This report may not account for any variations that may exist between conditions observedin the boring and conditions at locations that were not explored. If any subsoil variations becomeevident during the course of this project, a re-evaluation of the recommendations contained in thisreport will be necessary after we have had an opportunity to observe the characteristics of theconditions encountered, The applicability of the report should also be reviewed in the eventsignificant changes occur in the design, nature or location of the proposed construction.

Assessment of site environmental conditions or the presence of pollutants in the sail Or

groundwater of the site is beyond the scope of this report,

We have enjoyed assisting you on this project and look forward to sewing as your geotechtioalconsultant on the remainder of this project and future projects. Please do not hesitate to contact usshould you have any questions concerning this report.

James A. Baiges, RE.Senior Engineer -- GeotechnicalFlorida License No. 79124

Appendix:

Site Location Map .Field Exploration PlanSoil Test Boring RecordsGeneralized Subsurface ProfileSummary of Laboratory Index Test ResultsParticle Size Distribution Analysis ReportsField and Laboratory Testing Procedures

Respectfully,

Amec Foster Wheeler Environment & infrastructurFlorida Certificate of Authorization No. 5392

It- :orclinical

ens e

Distribut do

Adileredssee

(1}

(2)F

Zw0.

c m c)

Amec Foster Wheeler Project No. 6784173019

Historic Peacock House Relocation

Figure No 1: Site Location Map

Geotechnical Exploration foster DRAWN BY: JLBPort St. Lucie, Florida

amec

CHECKED BY: JAB

DATE: 12/21/2017

SCALE: NTS