SUBMITTAL DATA SHEET Non-Ducted Wall Mount Indoor Unit FEATURES: ● Removable front panel for easy cleaning. ● Optional wireless controller and built-in wireless sensor ● Optional condensate pump 0.7 RT TIWM008B22S ACCESSORY: Strainer Kit: MSF-NP63A 1 © 2018 Johnson Controls, Inc. version 201910 Tonnage 0.7 Ton Model TIWM008B22S Indoor Unit Power Supply AC 1Phase, 208/230V, 60Hz Nominal Cooling Capacity 1 Btu/h (kW) Nominal Heating Capacity 1 Btu/h (kW) dB Outer Dimensions Height in. (mm) 11-13/16 (300) Width in. (mm) 31-1/8 (790) Depth in. (mm) 9-1/16 (230) Net Weight lbs. (kg) 22 (10) Refrigerant R410A Indoor Fan cfm Airflow Rate (Hi2-Hi-Me-Lo) (m 3 /min.) Motor Nominal Output W Connections Refrigerant Piping Flare-Nut Connection (with Flare Nuts) Liquid Line in. (mm) 1/4 (6.35) Gas Line in. (mm) 1/2 (12.70) Condensate Drain OD in. (mm) 7/8 (22) Sound Pressure Level 2 (Overall A Scale) 8,000 (2.3) 9,000 (2.6) 39-35-32-30 353-282-247-229 (10-8-7-6.5) 38 *1 Nominal capacity is based on combinations within the VRF system and the following conditions; Cooling Operation Conditions Heating Operation Conditions Indoor Air Inlet Temperature: 80 o F (26.7 o C)DB Indoor Air Inlet Temperature: 70 o F (21.1 o C)DB Outdoor Air Inlet Temperature: 47 o F (8.3 o C)DB 43 o F (6.1 o C)WB 67 o F (19.4 o C)WB Outdoor Air Inlet Temperature: 95 o F (35.0 o C)DB Piping Length: 24.6in. (7.5m) Piping Lift: 0ft. (0m) *2 Sound pressure level is based on following conditions; 3.3ft (1m) Front of the Unit and 3.3ft (1m) Below the Unit.. The above data was measured in an anechoic chamber so that reffected sound should be taken into consideration in the field. NOTES: Specifications subject to change. Job Name: Location: Purchaser: Order No: Engineer: GC: Submitted To: Approval: Submitted By: Date: Unit Designation: Schedule/Model No:

Upload: others

Post on 09-Aug-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SUBMITTAL DATA SHEET submittal.pdf · (Hi2-Hi-Me-Lo) (m3/min.) Motor Nominal Output W Connections Refrigerant Piping Flare-Nut Connection (with Flare Nuts) Liquid Line in. (mm) 1/4

SUBMITTAL DATA SHEETNon-Ducted Wall Mount Indoor Unit

FEATURES:● Removable front panel for easy cleaning.● Optional wireless controller and built-in

wireless sensor● Optional condensate pump

0.7 RT TIWM008B22S

ACCESSORY:Strainer Kit: MSF-NP63A

1© 2018 Johnson Controls, Inc.version 201910

Tonnage 0.7 TonModel TIWM008B22SIndoor Unit Power Supply AC 1Phase, 208/230V, 60HzNominal Cooling Capacity 1 Btu/h

(kW)Nominal Heating Capacity 1 Btu/h

(kW)

dBOuter Dimensions

Height in. (mm) 11-13/16 (300)Width in. (mm) 31-1/8 (790)Depth in. (mm) 9-1/16 (230)

Net Weight lbs. (kg) 22 (10)Refrigerant R410AIndoor Fan

cfmAirflow Rate(Hi2-Hi-Me-Lo) (m3/min.)

Motor Nominal Output WConnections

Refrigerant Piping Flare-Nut Connection (with Flare Nuts)Liquid Line in. (mm) 1/4 (6.35)Gas Line in. (mm) 1/2 (12.70)

Condensate DrainOD in. (mm) 7/8 (22)

Sound Pressure Level 2(Overall A Scale)

8,000(2.3)

9,000(2.6)

39-35-32-30

353-282-247-229(10-8-7-6.5)

38

*1 Nominal capacity is based on combinations within the VRF system and the following conditions;Cooling Operation Conditions Heating Operation Conditions

Indoor Air Inlet Temperature: 80oF (26.7oC)DB Indoor Air Inlet Temperature: 70oF (21.1oC)DBOutdoor Air Inlet Temperature: 47oF (8.3oC)DB

43oF (6.1oC)WB67oF (19.4oC)WB

Outdoor Air Inlet Temperature: 95oF (35.0oC)DBPiping Length: 24.6in. (7.5m)

Piping Lift: 0ft. (0m)

*2 Sound pressure level is based on following conditions;3.3ft (1m) Front of the Unit and 3.3ft (1m) Below the Unit..The above data was measured in an anechoic chamber so that reffected sound should be taken into consideration in the field.

NOTES:

Specifications subject to change.

Job Name: Location: Purchaser: Order No: Engineer: GC: Submitted To: Approval: Submitted By: Date: Unit Designation: Schedule/Model No:

Page 2: SUBMITTAL DATA SHEET submittal.pdf · (Hi2-Hi-Me-Lo) (m3/min.) Motor Nominal Output W Connections Refrigerant Piping Flare-Nut Connection (with Flare Nuts) Liquid Line in. (mm) 1/4

2© 2018 Johnson Controls, Inc.

version 201910

Opening Direction Option 2:

Opening Direction Option 1:

NOTES:1. Attach strainer kit to refrigerant pipe closest to the unit when integrating wall mount type indoor unit into VRF system. The

strainer kit is an option. However, if the installation environment is not clean, then the strainer kit is required.2. Install condensate piping from either the left or right side of the knockout holes on the unit.

In case of the left side, mount a condensate hose to condensate pipe connection of the left side.3. Pay attention to a gap of center position of the bracket and the unit.

Mount them according to the figure “Dimension of Mounting Plate”.4. Taking out of refrigerant pipe from the right bottom side and right side of the unit are not available.

Unit: inch (mm)Non-Ducted Wall Mount Indoor Unit Model: TIWM008B22S

System Dimensions

Specifications subject to change.

Page 3: SUBMITTAL DATA SHEET submittal.pdf · (Hi2-Hi-Me-Lo) (m3/min.) Motor Nominal Output W Connections Refrigerant Piping Flare-Nut Connection (with Flare Nuts) Liquid Line in. (mm) 1/4

Item TIWM008B22S

a 25-1/8 (638)b 15-9/16 (395)c 17-11/16 (450)d 22-3/8 (568)e 1-3/4 (45)f 4-3/16 (107)g 2-9/16 (65)h 1/4 (6.35)j 1/2 (12.7)

Refrigerant Liquid Pipe Connection

Exterior Contour for Indoor Unit

Hole for Piping and Wiring

Hole for Piping

Condensate Pipe Connection VP16(Outer Diamater ɸ7/8 (22)) c

b

d

e

fa

gg

e

(ɸh With Flare Nut)

Refrigerant Gas Pipe Connection(ɸ j With Flare Nut)

TIWM008B22S

View from Front Side for Indoor Unit

For the pipe installation embedded in the wall

Unit: inch (mm)

Piping Connection Dimensions

Unit: Inch (mm)

Item TIWM008B22SLiquid Piping Gas Piping

a 17-11/16 (450) 15-9/16 (395)b 4-3/16 (107) 4-3/16 (107)

Securing Plate

Do not bend here.

Hold herewhen bending.

Refer to “For the pipe installation embedded in the wall” in the previouspage for fitting the pipe within therange of the hole.

Securing Plate

Do not bend here.

Bend the refrigerantpipe after putting intostraight position.

Cabinet

ab

For the rear side installation