LSIS Susol Low voltage switchgear provides optimized solution to meet various customer's needs.

Susol Low voltage switchgear is designed and produced to construct high quality power system such as plants and buildings. It realizes compact size and also secures customer's convenience and safety. Susol Low voltage switchgear is a high performance & high quality product that comply with IEC 61439-1&2, so it can be used all kinds of industrial field.

Low Voltage Switchgear & Motor Control Center

Features

Specifications

Unit

Internal form of separation

Multi function wall

Susol LV Switchgear structure

4

5

6

9

10

11

Contents

LV Switchgear

Page 3: Susol LV Switchgear - LSIS

3

Page 4: Susol LV Switchgear - LSIS

4

Features

Stability and reliability

• Designed to meet the IEC61439-1&2 standard

• Protection degree: IP43 (Up to 54)

• Form 4b structure- Prevention fault spread by metal partitions

Compact size

• Reduce installation space- Save space by 29% compared to the conventional model

• Adopted ½ unit construction

• Flexible design for installation space

Adopted LSIS ACB & MCCB

• Secures high reliability by applying LSIS MCCB and ACB

Safety and convenience for user

• Usability improvement through 3-way unit withdrawal type (ASTA certification)

• Independent modular structure for maintenance

• Screw type in/out assembly

• Structure and various options for user safety - Segregation of the busbars by applying multi function wall - Gear device indicator padlock - Draw in/out interlock

• Easy unit position change

Features

Save space by 29%

Single line diagram

ACB4P6300AW / OCR

ACB4P

630AW / OCR

ACB4P

2000AW / OCR MCCB

4P100AF / 100AT

3P4W 690V 100kA/1sec 5000A 50/60Hz

MCCB4P

250AF / 250AT

MCCB4P

630AF / 630AT

INCOMINGFEEDER

(ACB 2 of units)FEEDER(MCC)

Page 5: Susol LV Switchgear - LSIS

5

Specifications

Description Main Feeder MCC

Rated operating voltage Up to 690V Up to 500V

Rated current

Main Up to 5000A

Distribution Up to 5000A Up to 1500A

Phases 3P4W

Rated frequency 50/60Hz

Rated short time withstand current Up to 100 kA/1sec.

Arc fault containment (IEC TR 61641) Up to 100kA/0.3sec (85kA/0.5sec)

Rated insulated voltage 1000V 750V

Rated impulse withstand voltage 12kV 8kV

Degree of protection Up to IP54

Form of Internal separation Form 4b

Size (W×D×H) 1200×1000×2250 1150×1000×2250

(Double front type) 1000×1000×2250

(Single front type) 1000×650×2250

Standard IEC 61439-1 & 2

Page 6: Susol LV Switchgear - LSIS

6

Unit

■Withdrawable unit's height is adjustable from 150 mm up to 750 mm.

■Unit's height can be adjusted by 50 mm pitch.

■�MCCB, magnetic contactors, protective relays, auxiliary relay, timer, CT, ZCT and fuse are attached horizontally from the front of the unit case.

■Primary and secondary plug of main circuit and control circuit plug are attached at the back of the unit case.

Unit withdrawal (3-way type)

1 Unit ½ Unit

Position window Space for unit

Unit withdrawal (Screw type)

½ Unit configuration

• ½ unit configuration provides expanded working space and allows optimal space management

Safety embedded design for operators

• Padlock-equipped gear device indicator

• Unit withdrawal/insertion disabled when circuit breaker is on

• Interior shaft prevents negligent accidents

[ Screw type ]

[ Screw type + Push interlock ] [ OP-Handle type + 5 position ]

Unit configuration

Page 7: Susol LV Switchgear - LSIS

7

➌➎

➊ ➌➎

➊ ➌➎

➌➎

➌➎

➊ ➌➎

➊ ➌➎

➌➎

➌➎

➊ ➌➎

➊ ➌➎

➌➎

➌➎

➊ ➌➎

➊ ➌➎

➌➎

Position handle

Position Mechanical status Electrical status

½, 1 Unit StatusModule

interlockedPadlock possible

Withdrawablecontact

Mainswitch

Controlcircuit

1 Position Service

2 Position Test

3 Position Disconnected ISO

4 Position Moving -

Service positionThis means that if unit's locking device is at locked position, primary & secondary plug of main circuit, control circuit plug are connected to respective circuit.

Disconnected positionControl circuit plug, primary & secondary plug of main circuit are disconnected. However, the unit cannot be withdrawn from the MCC by mechanical mechanism.

Test positionAt test position, only control circuit plug and socket are connected and you can check all control unit output signal.

Withdrawable positionPlug and socket of control unit, primary & secondary plug of main circuit, mechanical mechanism are disconnected. So the unit can be completely withdrawn from the MCC.

Unit's location

➊ Vertical busbar

➋ Primary plug of main circuit

➌ N phase busbar

➍ N phase primary plug of main circuit

➎ Secondary fixed plug of main circuit

➏ Secondary movable plug of main circuit

➐ Control circuit plug

➑ Control circuit socket

➒ Withdrawal unit

Page 8: Susol LV Switchgear - LSIS

8

Unit

➊ MCCB handle

➋ Position interlock

➌ Control board

➍ Door handle

➊ Unit base plate

➋ Gear interlock

➌ Primary plug of main circuit

➍ Secondary plug of main circuit

➎ 24 poles control circuit plug

➏ Control board

Control board

Unit structure

➊ ➍

Page 9: Susol LV Switchgear - LSIS

9

Internal form of separation

Prevention fault spread by metal partitions (Up to form 4b type 7)

Form 4b structure

• Separation of busbar from the functional units

• Separation of functional units from one another

• Separation of terminals of functional units

• Terminals are not in the same compartment as functional unit

Susol LV Switchgear form 4b type 5 & 7 structure

Type 7

Type 5

• Busbar separation is by metallic or non-metallic rigid barriers or partitions.

• The termination for each functional unit has its own integral glanding facility.

• Busbar separation is by metallic or non-metallic rigid barriers or partitions.

• Terminals are separated by insulated coverings.

Page 10: Susol LV Switchgear - LSIS

10

Multi function wall

Multi function wall structure

Multi function wall has modularized and standardized structure and high level of safety

Features

• Simple structure by integration of components and functions

• Separation of phase to phase each busbar

• Rated short circuit current: up to 100kA/1s, 85kA/3s

Busbar systems

Exist system (Clamp)

New system (Multi function wall)

• Separation of phase to phase each busbar (➊)

• Support the middle of busbar (➋)

• Support the end of busbar’s top and bottom (➌)

× 13EA

× 10EA

× 8EA

× 12EA

× 2EA

• Separation of phase to phase each busbar ( A )

• Support the middle of busbar ( A )

• Support the end of busbar’s top and bottom ( B )

A

B

Page 11: Susol LV Switchgear - LSIS

11

Susol LV Switchgear structure

❶ Channel base

❷ Bottom plate

❸ Cable compartment

❹ Corner piece

❺ Multi function wall

❻ Right side plate

❼ Main busbar clamp

❽ Frame

❾ Pressure relief cover

❿ Top plate

MCCB operate handle

Position window

Unit barrier

Main busbar

Vertical busbar

Finger proof barrier

Safety shutter

Left side plate

Primary plug of main circuit

Secondary plug of main circuit

Control circuit plug

Lamp plate

Gear unit

Interlock unit

Unit ass’y (300mm)

Page 12: Susol LV Switchgear - LSIS

2019. 04 ⓒ2016. 12 LSIS Co.,Ltd. All rights reserved. / English (03) 2019. 04 Staffcom

www.lsis.com

Specifications in this catalog are subject to change without notice due to continuous product development and improvement.

Overseas Branches• LSIS Shanghai Office (China)

Tel: 86-21-5237-9977 Fax: 86-21-5237-7189

• LSIS Beijing Office (China)Tel: 86-10-5761-3127 Fax: 86-10-5761-3128 E-Mail: [email protected]

• LSIS Guangzhou Offce (China) Tel: 86-20-8326-6784 Fax: 80-20-8326-6287 E-Mail: [email protected]

• LSIS Qingdao Office (China)Tel: 86-532-8501-6058 Fax: 86-532-8501-6057 E-Mail: [email protected]

• LSIS Chengdu Office (China)Tel: 86-28-8670-3200 Fax: 86-28-8670-3203 E-Mail: [email protected]

• LSIS ShenYang Office (China)Tel: 86-24-2321-9050 Fax: 86-24-8386-7210 E-Mail: [email protected]

• LSIS Jinan Office (China)Tel: 86-531-8699-7826 Fax: 86-531-8697-7628 E-Mail: [email protected]

• LSIS Co., Ltd. Tokyo Office (Japan)Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: [email protected]

• LSIS Co., Ltd. Rep. Office (Vietnam)Tel: 84-28-3823-7890 E-Mail: [email protected]

• LSIS Moscow Office (Russia)Tel: 7-499-682-6130 E-Mail: [email protected]

• LSIS Jakarta Office (Indonesia)Tel: 62-21-2933-7614 E-Mail: [email protected]

• LSIS Bangkok Office (Thailand)Tel: 66-90-950-9683 E-Mail: [email protected]

Head Quarter127 LS-ro (Hogye-dong) Dongan-gu, Anyang-si,Gyeonggi-Do, 14119, KoreaTel. 82-2-2034-4848, 4671, 4429 Fax: 82-2-2034-4555

Overseas Subsidiaries• LSIS(Dalian) Co., Ltd. (Dalian, China)

Tel: 86-411-8730-7510 Fax: 86-411-8730-7560 E-Mail: [email protected]

• LSIS(Wuxi) Co., Ltd. (Wuxi, China) Tel: 86-510-8534-6666-8005 Fax: 86-510-8534-4078 E-Mail: [email protected]

• LS VINA Industrial Systems Co., Ltd (Hanoi, Vietnam)Tel: 84-24-3882-0222 Fax: 84-24-3882-0220 E-Mail: [email protected]

• LSIS Middle East FZE (Dubai, U.A.E.)Tel: 971-4-886-5360 Fax: 971-4-886-5361 E-Mail: [email protected]

• LSIS Europe B.V. (Amsterdam, Netherlands)Tel: 31-20-654-1420 Fax: 31-20-654-1429 E-Mail: [email protected]

• LSIS Japan Co., Ltd. (Tokyo, Japan)Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: [email protected]

• LSIS USA Inc. (Chicago, U.S.A)Tel: 1-800-891-2941 Fax: 1-847-383-6543 E-Mail: [email protected]