training on permanent magnt units

Upload: brianhaze

Post on 10-Oct-2015

20 views

Category:

Documents


0 download

DESCRIPTION

Permanent Magnet generators, kohler.

TRANSCRIPT

  • PMG Standby Generator Sets

    MP-5706 9/01a

    Training Manual

  • 2

  • 3Table Of Content

    Introduction ..................................................................................... 3-7

    Basic Safety ..................................................................................... 9

    Alternator ......................................................................................... 11-37

    Alternator Accessories ................................................................... 39-50

    Microprocessor Controller ............................................................. 51-88

    Manual Controller ............................................................................ 89-90

    Gauge Box ....................................................................................... 91-92

    Basic Controller............................................................................... 94-96

    Digital Controller 340 ...................................................................... 97-115

    Controller Accessories ................................................................... 117-132

    Digital 550 Controller ....................................................................... 133-174

    ECM Interface .................................................................................. 175-188

    Glossary ........................................................................................... 189-204

  • 4

    ko49268Notes

  • 5This manual covers operation, and features of Permanent Magnet Generator (PMG).

    This manual is only intended as a training guide and is to be used as a supplement toclassroom material. This is not a service manual and does not contain all available productinformation. Do not attempt to service generator sets without consulting the servicemanual and following all safety warnings.

    Pictures, illustrations, and wiring diagrams in this manual are only representative of thevarious models and may differ slightly even within the same model designation series.

    This manual is not intended as an installation or troubleshooting guide.

    Introduction

  • 6Notes

    6

    ko492686

  • Notes

    7

  • 6Notes

    8

    ko492686

  • Basic Safety

    9

    The safety section is intended to provide basic safety practices that should be followedwhen working on generators. This section is created to allow for the topic of safety to bediscussed in the classroom and should not be interpreted as rules to apply to all situations.Always consult your service manual and read all safety precautions before proceeding withthe operation of the generator set.

    Housekeeping

    1. Keep your work environment clean, this means cleaning up all oil and anti-freeze spills,oily rags or debris.

    2. Have access to safety equipment if necessary such as fire extinguishers, neutralizingsolvents for battery spills, eyewash, and personal protective equipment.

    3. Know where the exit is located, and have an uncluttered path to the exit.4. When working on electrical equipment remove any jewelry.5. Secure loose clothing before working around rotating equipment.

    General Procedures

    1. Before working on a generator set, always disconnect the starting battery. Remove thenegative lead first when disconnecting the battery. Reconnect the negative lead lastwhen connecting the battery.

    2. Always make sure all start signals are removed before connecting batteries.3. Make sure all equipment is electrically grounded before energizing.4. Lockout equipment which may electrically backfeed generator5. Know how your test instruments work. Keep your equipment in good working order.6. Wear insulated safety gloves when working on electrical equipment.7. Assume all conductors are electrically Hot until status is determined.8. Wear splashproof safety goggles, rubber gloves and boots when servicing batteries. If

    battery acid splashes in eyes or on the skin, immediately flush the affected area withlarge quantities of water. Seek medical attention.

    9. Do not allow sparks or flames around the fuel system.10.Never operate the generator if exhaust gas can leak back into an occupied room.

    Carbon monoxide will cause severe nausea, fainting or death.11.Make sure all guards and safety devices are in place before operating the generator.12. Wear hearing protection when near an operating generator.13. USE COMMON SENSE!

  • 10

    ko49268Notes

  • 11

    AlternatorPMG Generators were introduced in 1976 and featured a new concept of fieldexcitation control. Although component design, location and appearance has changed over theyears, the basic concept remains the same on current PMG Generator sets.

    The Microprocessor Controller has also seen many design changes since its introductionon the PMG Generators. The original solid state Mother/Daughter board has since evolved into aMicroProcessor based controller. The manufacturer will continue to offer Generator and Control designs using the latest technologies.

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

  • 12

    AlternatorThe term PMG refers to the generators ability in responding to load changes. Thesegenerators typically recover from voltage transients in .05 seconds compared to a half-second oreven two full seconds for conventional brushless models.

    Conventional brushless generator response time is inherently slow due to a double lag - first, theexciter generator response when the exciter field is energized, then the typical main generatorresponse time.

    The PMG Generator eliminates the exciter lag time by replacing the wound exciter fieldwith permanent magnets. The exciter generator is therefore capable of delivering full excitationdirectly to the Main generator field in the time required to trigger the SCR module.

    Excitation power on conventional generators is dependent on the main generator output. If a circuitconnected to the generator is exposed to a short, exciter voltage as well as line voltage drops. Thisreduction of voltage does not provide sufficient current to trip the breaker connected in the faultcircuit therefore affecting all remaining circuits connected to the system. As the exciter generatorfeatures a permanent magnet field it is not dependent on the main generator output and will supportthe main generator field during a short circuit. The ability to sustain at least 300% of rated currentallows the fault circuit breaker to trip clearing the fault from the system without disruption to theremaining load circuits.

    Response to load change. The oscilloscope record at left shows the prolonged voltage drop of a50 kW conventional brushless generator operating at no load upon one step application of full loadat 0.8 power factor. The record at right shows the recovery time of a 50 kW PMGgenerator operating under the same conditions. The fast recovery (within 2 cycles) aids motorstarting capability and greatly reduces light dimming due to load changes.

    Sustained short circuit performance. A 3-phase symmetrical short circuit of a generator setoperating at full load - a worst case situation - is shown on both oscilloscope screens. The trace atleft follows a conventional brushless generator operating at rated current with a surge current taper-ing to less than the rated level upon application of the short. The trace on the screen at right showsa PMG generator of the same rating operating under identical conditions, with the currentrising above its rated level, enabling it to trip branch circuit breakers.

  • 13

    AlternatorAlternator Designs

    Mechanical alternators or generators that produce an ACoutput are either of the rotating armature or the rotatingfield design and require 3 basic things.

    1. Conductors.2. A magnetic Field.3. Movement between the two.

    1. The Conductors are copper wires wound in slots oflaminated steel referred to as the armature and providethe generated output voltage.2. The Field is the invisible magnetic force producedby electromagnetic pole pieces.3. Movement between the field and conductors isnecessary to create current flow in the armaturewindings and is usually provided by a gas or dieselengine.

    Rotating Armature GeneratorsThe AC generated output power from this type generatoris produced in the rotating component and slip rings andbrushes are required to transfer the current to thecustomers stationary load. The field windings are woundon laminated steel pole pieces located in the stationaryiron shell. Size of these generators are usually limited to20 kW due to the brushes. These generators are notreconnectable between single and three phase voltages.

    Rotating Field GeneratorsAlternators used on most standby generator sets todayare of the Rotating field design. The magnetic polesrotate past the armature windings. As the armaturewindings are stationary, no brushes are required fortransfer of AC power to the customer load. The stationaryarmature also allows for easy reconnection of thewindings to permit various three phase or single phasevoltages.

    These generators usually utilize a small rotating armaturegenerator to produce the excitation power for the maingenerator field windings. This power is converted fromAC to DC by a diode bridge. The armature rotates on thesame shaft as the main field and therefore does notrequire slip rings and brushes. As the field windings forthese exciter generators are stationary, the regulatedcontrol circuit can be directly connected, again eliminatingthe need for brushes and slip rings. A SCR Exciter/Regulator is used to supply a regulated DC supply to thefield. Input power to the SCR circuit is from the mainarmature (stator) output.

  • 14

    AlternatorField Excitation

    Generators supplying the Standby/Prime powermarket are of the salient pole, rotating field type.

    The main AC Power producing components,namely the stator and the Rotor of thesegenerators have changed very little over theyears.

    The excitation circuit, the components supplyingthe main field with the required D.C. power, hashowever seen many design variations, mainlysince the appearance of solid state componentssuch as the SCR.

    A brief description of the most common types ofexcitation systems in use today follows.

    Static Excited (Exciter Regulators)

    This system rectifies AC power from the outputof the generator and sends a controlled DCcurrent to the rotating field through brushes/collector rings. This exciter can be of amagnetic amplifier type; however, it is usually anSCR bridge controlled by a solid state voltageregulator circuit. This system is quite fastoperating and can be designed to have excellentload response and voltage regulation.

    Disadvantages of static excited designs arefound in the rotor collector rings and brushes.These components are subject to routinemaintenance.

  • 15

    AlternatorWound-Field Brushless Excited

    This system uses a wound exciter armature,which rotates on the same shaft as the mainfield. A voltage regulator supplies a regulatedDC to the field of the exciter generator by meansof rectifying a small amount of the AC outputfrom the main generator.

    The system uses a solid state voltage regulatorand is immune from the large power spikesinherent in the static excited-type machine. It isalso completely brushless. It is self-protectingon short circuit or extreme overload, as thegenerator voltage collapses, but leaves loadswithout power.

    The chief disadvantage of this type system isthat it has the inherent time constant of theexciter field, which makes it considerablyslower in recovery time compared to the staticexcited type.

    While this type machine is self-protecting, it willnot selectively trip branch circuit breakersbecause of its collapsing voltage characteristic.

    Pilot PM Brushless Excited

    A brushless wound exciter generator with arotating permanent magnet field pilot generatoris used on generators larger than the PMG generator set series.

    Excitation for the excitergenerator field is suppliedfrom the stator output of thepilot generator. The exciterarmature output is rectifiedand supplies the maingenerator field with excitationpower. Since the onlyconnection to the loadwindings are for regulatorsensing the regulator isimmune to effects of SCRload induced harmonics. Thepermanent magnet pilotgenerator allows thegenerator to support shortcircuit currents for circuitbreaker tripping.

  • 16

    AlternatorPMG

    The PMG excitation system uses apermanent magnet exciter with a rotating SCR(thyristor)-type bridge referred to as the PMGModule. The module controls the DC current fedto the generator field.

    This design uses a voltage regulator, whichsignals the rotating SCR bridge through anoptical coupling.

    The voltage regulator sensesthe output voltage of thegenerator and turns a stationaryLED (light emitting diode) on oroff, depending upon the level ofthe output voltage. Voltagesupply to the regulator is fromthe generator set battery.

    The LED is mounted on the endof the generator shaft opposite aphoto transistor, which rotates onthe shaft. The photo transistorpicks up the signal from the LEDand tells the SCR rotating bridgeto turn on or off depending uponthe need, as dictated by thevoltage regulator.

    This type generator has a voltage recovery timeseveral times faster than the conventionalwound field brushless generator, because itdoes not have the inductance of the exciter fieldto contend with. It combines the fast responsecharacteristics of the static exciter generator withthe short circuit current sustaining capability andrelative immunity to load induced harmonics ofthe pilot exciter design.

    The optional Safeguard Breaker protects thegenerator in the event of extended non-protected overloads by disabling the photo-coupling signal to the SCR module.

  • 17

    Alternator

  • 18

    Alternator

  • 19

    Alternator

    The PMG generator sets have amarketing size code, which pertains to thestator lamination stack length, to the nearestinch, and the air gap bore diameter in inches.

    A Generator model 4S9 is a 4-pole generatorwith a 12 diameter bore and a lamination lengthof approx. 9.

    This Generator would be supplied on most100kW models. (Illustration 4S)

    If a single-phase application is specified anoversized generator (4S13) would be supplied.Also if improved motor starting is required theoversized generator could be specified.

    The Marketing code appears on SpecificationSheets, Price Lists and the Motor StartingGuide.

    Stator

  • 20

    Alternator4UA Alternator(180 - 300)

    The main difference between the 4U and 4UA isa redesign of the end bracket and rotor.

    The end bracket features a grease cavity bothbehind and in front of the bearing. Grease isapplied to both cavities at time of assembly. Azerk fitting and drain plug are provided for theouter cavity.

    A perforated aluminum ring attached to the polepieces allows for precise and easier rotor bal-ancing. The SCR module and a counter balanceplate are also attached to the ring.

    The redesign also allows better airflow forimproved Alternator cooling.

  • 21

    AlternatorPMG generators are of the BroadRange, 12 lead type. The winding is basically athree-phase winding, with each phase wound intwo sections.

    The generator is able to function properly overthe range of 110 to 139 volts per section.

    These stators can be reconnected to various 50/60 Hertz voltage configurations including three-phase Wye, three-phase Delta, and single-phase.

    When the stator windings are connected in a 3phase Wye or Star connection the line voltage(L1 -L2-L3) is equal to the vector summation ofthe phase to neutral voltage. (L1 -L0, L2-L0, L3-L0) or 1.73 times the phase to neutral voltage.

    120X1.73=208 277Xl.73=480 139Xl.73=240

    The phase coils can be connected in either aseries (high) or parallel (low) configuration.Voltages most often encountered in the highWye are; 220/380, 240/416 or 277/480.Common voltages for the low Wye connectionare 110/190, 120/208 or 139/240.

    The most common voltage for the Deltaconnection is 120/240 or 110/220. Half thephase voltage is available between the seriesconnected coils and the line. (L1 -L0)

    The 12-lead generator can be connected tosupply single-phase power. This configuration isreferred to as a dog leg. Both 120 and 240-voltsingle-phase circuits are available with thisconnection.

    When operating at single phase, capacity mustbe derated due to the heating effects inherentwith this connection.

    The generators are not reconnectable to 600volts. Six lead wye connected stators areavailable for these three phase systems.Voltage from line to neutral is 347 volts. Tapsare provided in each phase to provide 120 and240 volts for metering and regulatorconnections.

  • 22

    Alternator

  • 23

    Alternator

    Generators which are used in a system having acombination of single-phase and three-phase loadsare susceptible to load unbalance.

    Three-phase loads are self-balancing; however,single-phase loads must be carefully planned anddistributed between the phases to obtain balancedvoltages and prevent overloading one or two phases.

    This is a fairly simple thing to do for Wye connectedgenerators; however, when the three-phase120/240volt Delta system is used, a compromise must bemade.

    In general, loads should be arranged such that thecurrent rating of the generator is not exceeded on anyphase.

    When calculating three phase systems it is oftenassumed that the loads to be carried will be evenlybalanced. This however is seldom true due to thesingle-phase loads on the system.

    The most glaring example is the 120/240 volt three-phase Delta system used for combinations of 120 and240 volt single-phase loads and 240 volt three-phaseloads.

    It is relatively simple for the system designerconnecting his load to a utility to select three single-phase transformers, one of which is made largeenough to handle the single-phase load.

    The generator set supplier however has a problem inthat the three-phase windings of a generator are allequal in size and he has very little control over theload.

    All the single-phase loading is connected across oneof the phases causing an imbalance. Excessiveunbalance could damage the generator as well asthree-phase motors connected to the load.

    Basic points to remember with three-phase Deltaconnections are:- Balance the 120 volt loads.- Try to keep the single-phase loads too less than50%- Keep the line current at any of the three terminals,particularly terminals L1 and L3, within the currentrating of the generator.

    Load Unbalance

  • 24

    Alternator

    The stators are vacuum impregnated withepoxy varnish - Fungus resistant per Mil-1-24092. They will sustain short circuit currentat 300% of rated current up to 10 seconds.

    Due to the amount of heat produced, mostgenerators furnished today use Class F or Hinsulation in their construction.

    In an ambient of 104 F (40C), Class Finsulation allows a temperature rise of 266F(130C) for standby and 221F (105C)continuous.

    Class H insulation allows a temperature rise of150C standby and 125C for continuous.

    PMG generators are manufacturedwith Class H insulation but is rated accordingto the temperature rise limits of Class FInsulation.

    The Temperature Rise of the windings ismeasured by the resistance method. Theresistance of the windings at the coldtemperature is compared to the resistancewhen the generator has reached stabilizedtemperature.

    If these generators were operated atmaximum ambient temperature and at ratedload continuously, the projected life for thecontinuous rating is 20,000 hours.

    It is obvious that generator winding standardsare very conservative. In fact, generatorsrarely fail when operated under normal ratedload.

    Generator winding failures result fromenvironmental conditions, a weakness in thewinding, continuous overload or loadunbalance.

    Stator Assembly

  • 25

    AlternatorThe purpose for the insulation is to preventshorting between the windings, laminationslots and any conductive material used in thegenerator construction.

    If this insulation deteriorates or breaks down acurrent path can be created between thecopper windings and the frame structure.

    Dirt, grease, chemical fumes, heat, aging andmoisture are some of the contributors toinsulation break down.

    As part of many scheduled maintenanceprograms, insulation deterioration testsbetween the windings and ground are takenfor comparison analysis over the life of thegenerator.

    These resistance values are very high.(Millions of ohms) A Meggerr is the commoninstrument used for taking this measurement.

    Meggers apply a voltage between theinsulated conductor and the material they areinsulated from, usually ground. Theydetermine the resistance from the current flowin or over the insulation.

    Hi-Pots producing high potentials (1000v +)should not be used and can add to thedeterioration of the insulation.

    Prior to operating the Meggerr read and followthe instructions provided with the instrument.Disconnect all loads especially electronicdevices, regulator, diodes, circuit boards etc.from the generator.

    Maintain continuity between all coils per theparticular voltage connection the stator isconnected for. (wye, delta) Isolate the neutralleads from ground and connect the Meggerrbetween the group of neutral leads andground. Record the megohm readings.

    If the insulation resistance is below 1.5megohms the windings must be serviced.This may require a major repair or merelyremoval of moisture by a, drying out, processwhere a current is supplied through thewindings for a period of time.

    Insulation Testing

    ko49268is a registered trademark of Biddle Instruments.

    ko49268R

    ko49268Meggar

  • 26

    AlternatorStator Coils

    Prior to making any stator checks it is importantthat the generator set battery be removed toprevent accidental start-up.

    Customer load must be completely disconnectedfrom the stator leads.

    The resistance value of the stator windings isvery low. Use of a VOM is not recommendedother than for an indication of continuity. Somemay lead the novice technician to assume thewindings are shorted.

    An instrument such as a Kelvin double bridgecapable of indicating accurate readings in themilliohm range must be used if a true resistancevalue is required.

    The V low power leads, (V0, V7, V8, V9) areinternally connected to the main stator coils,therefore their terminal ends must be removedfrom the terminal strip to obtain accuratemeasurements. These leads provide sensingpower for the metering and regulator.

  • 27

    AlternatorStator Coils

    It is not necessary to separate the coils in a Wyeconnected generator to measure coilresistances.

    The total value of the coils connected in series isthe sum of the individual coils.

    Resistance readings can be taken; between Lineto Line, Line to Neutral, or between the 6individual coil groups of a High Wye connectedgenerator.

    In a Low Wye connection the coils in the line toneutral are connected in parallel. The totalresistance of the parallel coils is half the value ofone of the individual coils.

    In a Delta connection it is necessary to open,one of the series coil connections prior tomeasurement to eliminate the series/parallelcircuit.

    NOTE: A considerably higher resistance valuethan specified may be indicated when measuredbetween Line to Line if a loose, corroded orinsufficiently torqued bolted terminal connectionexists.

  • 28

    Alternator

    The exciter generator is of the permanentmagnet rotating armature type. The frameassembly is bolted to the main stator endbracket and is recessed in the stator frame.

    It contains rows of 8 ceramic magnetscemented to the interior circumference.

    Each magnet contains both a north and asouth pole totaling 16 magnetic poles. Theexciter therefore produces a 240 cycle ACoutput @ 1800 RPM.

    The use of a PM exciter field allows theexciter armature to be at maximum excitationvoltage whenever the engine is rotating atrated speed.

    Three sizes of exciter generators are used forthe PMG Generator series. 25-30KW,40-150KW, 180-300KW.

    Magnets may have cracks, provided all piecesare securely fastened to the frame. All loosepieces must be removed. Total volume ofmissing pieces of any one magnet may notexceed 5% of the magnets original volume.

    PM Exciter Field

  • 29

    Alternator

    Three sizes of rotor assemblies match the 4P,4S and 4U code PMG stators.

    The Rotating 4 pole, main field assembly andexciter armature are pressed onto a commonshaft along with a hub assembly which isbolted to drive discs for direct connection tothe engine flywheel.

    The exciter armature end of the shaft issupported in the end bracket with a bearing.

    The laminations of the main field poleassembly are assembled with the polesskewed in relation to the stator slots. Thisimproves the generators output wave shapeby reducing harmonics resulting from the fluxproduced by the armature winding current.

    Amortisseur windings or damper bars areutilized in the rotor laminations. Thesewindings consist of aluminum rods inserted inholes in the laminated pole pieces. Thewindings or rods are short-circuited by weldingthem to the pole end plate.

    The purpose of these windings is to reducethe heating of the rotor by reducing the eddycurrents. These windings also reduce thetendency of the alternator to hunt with loadchanges or when paralleling with otheralternators.

    The field coils are alternately wound on thepole pieces or connected during assembly toproduce alternate magnetic pole polarity. (N- S - N - S)

    Wedges help hold the windings frommovement due to centrifugal forces. Therotors are vacuum impregnated with epoxyvarnish, baked and dynamically balanced.

    The series connected field coils connect to theF+ and F- output terminals of the SCRmodule. Main field resistance can bemeasured at these leads. Nominal rotorresistances are 1 to 3 ohms.

    To insure proper resistance readings with anohmmeter and to prevent damage to theSCRs when checking insulation condition witha Meggerr, first remove the field leads from themodule terminals.

    Rotor Assembly

  • 30

    Alternator

    The exciter armatures are pressed onto themain shaft and provide the excitation voltagefor the main generator field.

    As these exciter armatures use permanentmagnets for their field supply, they perform asa saturated field generator and supplycontinuous maximum output wheneveroperating at rated RPM.

    These rotating armature generators provideoutput power of 1500 to 3500 watts with apotential of 120 - 150 volts AC.

    The armature leads connect to the AC inputterminals on the SCR module.

    Resistance values of the armature windingsare between .2 to .7 ohms.

    Exciter Armature

  • 31

    Alternator

    The SCR Module rectifies the AC output of theExciter Armature and supplies this DC to theGenerator Field (Rotor).

    Three different modules accommodate thethree PMG alternator sizes.

    The Module contains (2) SCRs and (2)Diodes connected in a bridge configuration. Afree wheeling diode and varistor areconnected across the output (F+, F-) toprotect the bridge.

    Controlled gating or triggering signals for theSCRs are received from the Photo-Transistorboard and applied to terminal G. Two currentlimiting resistors protect the gating circuit.

    All components are encapsulated forprotection against the elements and vibration.

    The individual components can be accessedfor bench checking by referring to theschematic drawing.

    When checking components or resistancevalues on modules with stud typeterminals, Install and tighten a nut snugglyagainst the board foil to Insure a goodmechanical connection to the foil circuit.The studs are not soldered to the foil.

    The F- terminal is connected to groundthrough the heatsink and mounting screws.

    Weight plates are attached to the oppositerotor pole piece for counter balance.

    Lead terminal screws are torqued to 8-in. lbs.All leads must be securely tied to the shaft toprevent movement due to centrifugal forces.

    SCR Module

  • 32

    Alternator

    The photo transistor circuit board is thereceiving portion of the photo couplingcircuit and provides the gating signal to theSCR module.

    The frequency of the output signal isdependent on the on-off, light signal itreceives from the stationary light emittingdiode.

    An insulated board and washers aresandwiched between the circuit board andthe speed sensing actuator cup. Theassembly is mounted to the rotor shaft bytwo screws.

    The circuit board leads are fed through adrilling in the shaft and the exciter armaturecore and attached to the SCR moduleterminals.

    Polarity of the G (green) and F3 (red) mustbe observed. G to G, F3 to F+.

    A flashlight can be used as a light source toactivate the photo-transistor for testing ortroubleshooting.

    Do not operate the generator with theprotective cover removed withoutguarding from external stray lightsources that could cause a ceilingoutput voltage from the generator.

    Photo Transistor Board

  • 33

    Alternator

    The LED board provides the light source tothe photo-transistor for triggering of theSCRS. It contains a light emitting diode (D1)and freewheeling diode (D2) as a protectivecomponent.

    The LED is the stationary member of thephoto coupling circuit and is mounted in aprotective cover directly in line with thereceiving photo-transistor.

    The LED emits an infrared signal that isinvisible to the eye but has excellent ability topenetrate any dirt or grime which couldaccumulate over a period of time.

    Wires 3B and 5B are the output leads from thevoltage regulator and terminate at the P1connector of the LED board. A square waveoutput is emitted from the voltage regulator toturn on or off the LED. The amount of On/Offtime is dependent on the generator loadrequirements and the ability of the voltageregulator to maintain the desired output voltage.When the generator is running under light loadconditions the LED will have a longer off time.When the generator is under heavy loadconditions the LED will have a longer on time.

    LED Board

  • 34

    AlternatorThe PMG Voltage Regulator illustrated suppliesthe controlled power to the Light Emitting Diodeand provides +/- 2% regulation.

    The generator set starting battery provides inputpower to the regulator. It will accept both 12 and24-volt battery systems.

    The battery (+) circuit is protected by a 15A fuseand supplied via a normally open K3 controlrelay contact. The controller relay is energizedduring engine crank and run.

    An optional generator overload protection circuitbreaker referred to as the Safe Guard Breakerwill disrupt the regulator input power in the eventof a prolonged overload.

    Regulated output power to the photo couplingLED is 1 - 2 vdc at I00 Ma. Open circuit voltageis approximately 8 vdc.

    The PMG regulator is an average sensingregulator. A nominal single-phase voltagesensing of 190 to 277 volts is monitored atgenerator terminals V7 - V8.

    The regulator can be used for both 50 and 60 Hzoperation depending on a jumper placement; T1to T2 for 60 Hz, T1 to T3 or remove for 50 Hz.

    The regulator is of the volts per hertz design.This feature causes the generator voltage todrop if the frequency falls below a preset level.(8 volts/hertz average). This allows the engine toregain RPM when large one step loads areapplied. Factory cut-in frequency setting is 48for 50 HZ operation and 58 for 60 Hz operation.Settings can be field adjusted if required. Thefeature can be eliminated if necessary by turningthe corresponding pot fully clockwise.

    A Stability adjustment is provided for finetuning and to minimize light flicker.

    The I000 ohm, 1-Watt voltage-adjustingpotentiometer is remotely mounted in the metercabinet.

    1% regulation, RMS, and 3 phase sensingregulators are optional.

    Voltage Regulator

  • 35

    AlternatorA 3-phase voltage sensing regulator is availableas an option for PMG gensets.

    All features and specifications are the same asthe 2% single phase sensing regulators providedas standard on PMG generator sets.

    Three potential transformers are located on theregulator, which sense the generator phase tophase voltage at terminals V7, V8, and V9.

    The 3-phase sensing will improve the generatorperformance in an application of unbalancedloads.

    By monitoring the voltage across all threephases the regulator will sense the average andrespond with more balanced overall regulation.

    Voltage Regulator

    ko49268

  • 36

    Alternator

    ko49268

    ko49268PMG

  • 37

    Alternator

    ko49268

    ko49268PMG

  • 38

    ko49268Notes

  • Alternator Accessories

    39

    The four piece housings provide weatherprotection for the generator assembly. Theyalso support the controller cabinet, containvarious standard and optional controller andgenerator support components and provideisolation protection for the generator outputconnection terminals.

    Customer electrical load connections are madeinside the enclosure either to the generator lineleads, or optional circuit breaker or bus bars.Component location may vary dependent onmodel size.

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

    ko49268

  • Alternator Accessories

    40

    The Line Circuit Breaker provides an automaticdisconnect if a fault in the circuit supplied by thegenerator causes a current demand greater thanthe preselected overcurrent value. (Usually therating of the generator). It also allows formanually isolating the generator from the load.

    The breaker mechanism is spring loaded whenthe contacts are closed and can therefore beeasily tripped to the open position. This springaction also provides for quick making andbreaking of the contacts. The design allows forcontact tripping even if the toggle handle is heldor blocked in the ON position.

    When the mechanism has been tripped theoperator handle will be positioned midwaybetween ON and OFF providing a visualindication of a trip caused by a fault. The handlemust be moved to the off position for resettingbefore it can again be latched in the on position.

    Common methods of activating the tripmechanism are by thermal, magnetic and shuntdevices or combinations of these.

    Thermal Trip

    The thermal portion consists of a bi-metal stripthat reacts to the heat produced from the loadcurrent. Excessive current will cause it to bendsufficiently to trip the mechanism. The trip delayis dependent on the duration and excess ofoverload current. Elements are factorycalibrated.

    Magnetic Trip

    The magnetic trip portion features anelectromagnet in series with the load contactsand a moveable armature to activate the tripmechanism. When a sudden excessive currentsuch as a short circuit occurs the electromagnetattracts the armature resulting in aninstantaneous trip.

    Magnetic elements with either fixed or adjustabletrip points are available.

    Line Circuit Breaker

  • Alternator Accessories

    41

    Thermal Magnetic

    Most breakers utilize both bi-metal andelectromagnetic devices to activate the trippingmechanism.

    A combination of both thermal and magneticallows a delayed trip on an overload and aninstantaneous trip on a short circuit.

    Shunt Trip

    A Shunt trip option provides a 12 or 24vdcsolenoid within the breaker case that whenmomentarily energized from a remote locationwill activate the trip mechanism. This allows thebreaker to be tripped by customer selected faultssuch as a generator overvoltage or overspeed.

  • Alternator Accessories

    42

    The PMG excitation circuit is designed to allow thegenerator to deliver in excess of 600% of ratedoutput amperage and sustain a minimum of300%. This feature allows for tripping of linebreakers feeding an overload or short withoutdisruption to remaining branch circuits.

    If the line protection does not trip in the allottedtime the Safeguard Breaker will provideprotection for the generator.

    As illustrated in the adjoining chart, a faultcausing 400% of rated current to flow will allow 5to 20 seconds for the branch circuit protection toopen prior to tripping of the Safeguard Breaker.

    Current transformers are used for both sensingand supply to the trip elements of the breakers.

    The current transformers supplying the panelammeters are connected in series with thebreaker trip elements. A series of breakers areused to accommodate the PMG sizes. Ratingsrange from 3.0 to 5.0 amperes.

    All three phases of the generator are monitored,the breaker toggles are tied together to allowopening of the breaker contacts if current in anyleg exceeds the trip rating.

    Opening of the breaker contacts removes thebattery supply from the voltage regulator,disrupting the photo coupling circuit, causing themain field to collapse.

    It must be realized that a residual voltage will bepresent at the main generator load terminalswith the safeguard breaker open. This is due tothe magnetism remaining in the rotor iron.

    The safeguard breaker is not a line breaker.

    Breaker contacts are rated at 50 amperes.

    Safeguard Breaker

  • Alternator Accessories

    43

    The circuit breaker used is a viscous dampedmagnetic trip breaker with separate contact andtrip circuits.

    The current being monitored will draw theplunger against the core spring to a proportionalposition in the core tube.

    When current exceeds the trip rating the plungerwill touch the pole piece increasing the magneticflux enough to attract the trip armature and openthe contact circuit.

    The core tube is filled with a silicon fluid, whichdelays the speed of the plunger.

    Delay time is selected by the viscosity of the fluidused.

    Safeguard Breaker

  • Alternator Accessories

    44

    The 6 terminal barrier strip located in thegenerator enclosure provides an interconnectionpoint between the Current Transformersecondary the Voltage regulator battery supplyand the optional Safeguard breaker terminals.

    System battery voltage to the Generator voltageregulator is provided at terminals 70 (+) and 7N(-). This circuit is protected by the 15 Amp fuse. Various optional devicesmay also be found connected to these terminals:

    - Run Relay- Water Level Switch- City Water Cooling Solenoid- Elect. Governor (Gas Models)

    Safeguard BreakerTerminal Strip

    To terminalstrip located incontroller cabinet

    !2 or 24 vdc

    CT1 CT2 CT3

  • Alternator Accessories

    45

    Current Transformers allow the use of lowamperage (5A) meter movements and tripmechanisms when monitoring high ACamperage flow.

    When an AC load carrying conductor is placedthrough the core of a CT a proportionatecurrent will be induced in the secondarywinding surrounding the core.

    Transformers are rated by ratio between theirprimary and secondary and are matched tothe full scale of the ammeter they aresupplying; a transformer with a 100:5 ratio ismatched to a 0-100 Amp full-scale ammeter.A current flow of 100 amps through theprimary will produce 5 amps to the metermovement from the secondary and indicate100 amps (Full Scale) on the meter

    On models featuring the optional SafeguardBreaker, the CTs also provide the current forthe trip elements.

    Polarity markings for both the primary andsecondary are usually indicated by a coloreddot or Hl for the primary and a white lead or Xlindication for the secondary.

    On Three phase units three CTs are requiredand generator leads must be routed throughthe transformer (primary) in the samedirection. The dot or Hl side is toward thegenerator.

    The white or Xl secondary leads connect tothe SG breaker trip elements or Cl, C2 and C3terminals for meter phase selection. Theremaining terminal or black leads are tiedtogether and ground.

    DANGER : Do not operate the generator setunderload with the transformer secondaryterminals disconnected or open circuited. Highvoltage induced into the transformers

    Current Transformer (CT)

  • Alternator Accessories

    46

  • Alternator Accessories

    47

    The Reactive Droop Compensator Kits contain acurrent transformer with a current ratio selectedper the Generator size and a 16 ohm, 100 Wattrheostat common to all kits.

    When generators are connected in parallel,governors control the engine power so eachgenerator carries its proportionate share of thetotal load. The generator field excitation orreactive load however may be less or greater onone unit than another. This is because theindividual voltage regulators all sense the samecommon bus voltage and cannot detectexcitation voltage or reactive loads assumed bythe other generators.

    Imbalance of these reactive loads result incirculating currents (cross current) between thegenerators.

    To minimize this effect a compensation circuit isused to balance the reactive loads by supplyingan error signal to the voltage regulator.

    Generator load current is directed through thetransformer primary. The secondary isconnected across the resistive burden (rheostat)and a generator phase, which is 90 degrees outof phase with the primary. On inductive loadsthe CT secondary will induce a voltage acrossthe resistor which is proportional in magnitudeand in phase with the line current. This voltageis vectorially added to the voltage regulatorsensing voltage to produce an error signalresulting in a droop in output voltage.

    The regulator of another generator connected tothe same load will sense the decrease in voltageand increase its excitation therefore keeping thebus voltage constant.

    On non-inductive loads the transformer primaryand secondary current remain approximately 90degrees out of phase therefore adding very littleincrease to the sensing signal.

    Reactive Droop Compensator(optional)

    ko49268

  • Alternator Accessories

    48

    1. With the compensator rheostat set atminimum resistance (CCW), record the RPMand voltage at 1/4 load steps to full load on unit#1. Repeat for unit #2.

    2. Compare the readings and make finalregulator and governor adjustments so that thevoltage is within 1 volt at each load step and thespeed is within 1 Hz for each unit.

    3. Check Droop Compensation on each unit asfollows:

    a. With unit #1 operating at the correct speedand voltage, apply a lagging power factor load.This load should preferably be 1/2 to full loadand must be inductive.

    b. Observe the voltmeter on unit #1 with therheostat set at minimum. As the rheostat isturned CW the voltmeter should show adecrease in voltage. If a larger voltage isobtained when the rheostat is turned CW, shutdown the system and reverse the direction of thegenerator load line through current transformer,or reverse transformer leads. Recheck droop.

    c. Set the rheostat at a value, which isapproximately 4% of rated voltage at full load.As an example, the voltage will droop (decrease)19.2 v on a 480-volt system at full load or 9.6volts at 1/2 load. To determine droop at otherthan full load, use the following formula:

    Rated voltage x .04 x Actual Load* = voltageDroop

    * (Expressed as a % of full load)

    With full load 0.8 power factor, a droop of 3-5%should be adequate for paralleling.

    d. Repeat Steps a, b, c for unit #2 and becertain the amount of voltage droop is equal atthe same load point as on unit #1.

    e. With this procedure, the two units will sharereactive currents proportionately.

    4. In addition to Steps 1-3, it is desirable to usethe following procedure to check that the unitsare sharing the reactive load correctly.

    a. Parallel the units at one-half to full load.Check the wattmeters to determine that eachunit is carrying equal kW load or a loadproportional to its capacity. If the loads areincorrect, adjust and recheck the governorthrottle control to correctly balance loading.

    b. With the load balanced, check the ammetersto see that equal current is being produced orthe current is proportional according to capacity.If the currents are incorrect, adjust the drooprheostat to reduce the current of the unit that hasthe highest reading. The current should bereduced to an equal division or be proportional.

    As a result of performing Steps a and b, thegovernors have been adjusted to balance loadand the Droop rheostat has been adjusted tobalance current. These setting would beoptimum for parallel operation.

    NOTE

    Voltage must droop on lagging power factorloads (inductive loads). A small change involtage is acceptable on unity power factor loads(resistive loads).

    Reactive Droop Adjustment

  • Alternator Accessories

    49

    Auxiliary Relays (K5 & K6)

    These relays are located in the generatorenclosure when required. The relays areavailable with either 12 or 24 volt coils tomatch the system battery voltage.

    A freewheeling diode is installed across coilterminals 85 and 86 for circuit protection.Polarity direction must be observed per theappropriate diagram.

    Governor Relay (K5)

    The K5 relay is installed on units withElectronic Governors. It controls battery +voltage to the Governor Control.

    The relay is energized during cranking andrunning by the K3 microprocessor controllerrelay.

    Air Damper Relay (K6)

    Damper valves, which block off intakecombustion air for immediate shutdowns areused on various engine models. The damperor linkage is actuated by a momentarilyenergized electric solenoid.

    The K6 relay controls the energizing of thesolenoid.

    A ground output signal from the controllerlogic board due to an Overvoltage,Overspeed or Emergency Stop will energizethe relay.

    Movement of the Solenoid will also activate amicro switch to signal energizing of the AirDamper and Emergency Stop lamps on thecontroller Indicator Panel.

    Once energized the damper will latch closedand must be manually reset prior to restarting.

    The circuit is not energized during normaloperational shutdowns or faults notconsidered emergency.

    ko49268

    ko49268

  • Alternator Accessories

    50

    Run Relay (Optional)

    The Run Relay provides three sets of drycontacts for customer connection of devicesrequired to be energized or deenergized whenthe generator set is being operated. Louvers,Indicator lamps etc.

    The three-pole, double throw contacts of therelay illustrated have an Industrial rating of:3A. 1/3HP, 600vac10A. 1/2HP, 120vac6 2/3A. 1/3HP, 250vacAppliance rated at 10A. 250vac

    Coil voltage is selected to match the Gen. setbattery, (12 or 24vdc) and is supplied duringcranking and running from the 15A controllerfuse. (terminals 70(+) & 7N(-) on the Safeguardterminal strip). The diode connected across thecoil provides protection to the control circuitcomponents and polarity must be observed.

    The relay when specified is located in thegenerator enclosure. On early models the relaywas mounted on the voltage regulator cover. (A)

    Customer connections are made directly to therelay terminals.

  • Controller

    51

    The control cabinet houses the generator setcontrol circuitry and connection terminals.The vibration isolators are symmetricallylocated so the cabinet can be mounted to facethe side or rear.

    The rear panel is hinged to allow easy accessto the microcomputer circuit board andcustomer connection terminals.

    The face of the generator set controllercabinet is lit during operation and contains thegenerator voltage output adjust rheostat, ACmetering system, running time indicator,engine control switches and gauges plus anarray of system condition indicators.

    Meters, gauges and indicator panel areincluded in the controller and provided asstandard on Generator Sets.

    Controller Cabinet

    ko49268

    ko49268

    ko49268

    ko49268

  • Controller

    52

    The Microprocessor Plus controller is availablewith an expanded cabinet if an optionaltachometer, wattmeter or oil temperature gaugeis desired.

    If the application is not as stringent as the Level1 requirements, a Level 2 Microprocessorcontroller is offered in both standard andexpanded cabinets. This controller provides allthe features of the Level 1 but has only 7 statusindicators.

    The AUXILIARY lamp will flash if no generatedAC or low battery voltage is sensed.

    The AUXILIARY lamp will light on EmergencyStop, Overvoltage Shutdown, Low WaterTemperature, or Auxiliary custom supplied devices.

    Optional Controllers are available for manualoperation.

    ko49268

    ko49268

  • Controller

    53

    A 3 dual scale voltmeter is used asstandard for 12 lead generator models.

    Upper scale is 0-600 the lower scale is 0-300.Lamps on the meter selector switch plate willindicate which scale is to be read and is set attime of generator voltage connection.

    The meters are calibrated to read full scale(FS) with 300 volts applied to the terminalsand are rated at 2% FS.

    Voltmeter (600V Models)

    A 0-900 scale voltmeter is supplied on the600-volt non-reconnectable models. Thesemeters also have a 300-volt full-scalemovement and sense the V7-V8-V9 statortaps. A 10W, 10K variable resistor isconnected in series with a meter terminal andis used for calibration during final plant test.

    Frequency Meter

    The standard frequency meter used for both50 and 60 Hertz models as well as 600Vmodels is a 3 1/2, with a scale of 45 to 65 Hz.and a 120-vac .5% movement. The meter isconnected to monitor stator leads V7 - V0.

    Ammeter

    The ammeters are all dual scale meters andselected so one meter will cover all thestandard voltage connections in a specific kWmodel range, except 600v.All ammeters have a 5 amp. full scalemovement and are used in conjunction withcurrent transformers.

    VoltmeterMeters

  • Controller

    54

    Wattmeter (Optional)

    Wattmeters are optional and require anoversized controller to house the transducer andwattmeter.

    Both the AC voltage and current are monitoredand supplied to the transducer, which convertsthe AC power to a proportional DC output.

    Illustrated is a typical 2 element transducerwiring scheme.

    Input power is 120vac / 1 amp. Potentialtransformers are used on Delta and Hi Wyeconnections to provide the 120v.

    Current transformers provide the currentsensing. Polarity and safety precautionsmust be observed. Separate transformers areused from the standard meter CTs.

    Output to the Wattmeter movement is 0 - 1 Madirect current.

    If a field voltage reconnection change is madeon a generator with a wattmeter kit, a transduceror transformer change is required.

    Transducers are selected to match theGenerator kW rating.

    Meters

  • Controller

    55

    The Meter Selector Switch allows monitoring of thegenerator voltage and load amperage as indicatedon the Nameplate.

    Two meter selector switches and nameplatesaccommodate all PMG models.

    The switch terminal numbers and wiring are thesame for both switches, however the internalswitching sequencing differs.

    One switch and nameplate, (A) is used on allPMG generators up to 100 kW (Except 600vmodels) This is to accommodate theSingle-phase models available in thisrange.

    The other switch, (B) is used on allmodels above 100 kW as well as all 600volt models.

    Twelve contacts are enclosed in thetypical rotary switch illustrated. Sixcontacts for the ammeter and six for thevoltmeter.

    Terminals 1 to 12 are make beforebreak contacts and used to switch thesecondary of the CTs to the ammeter.They short the secondary duringswitching between phases preventing thehazardous condition of an open CT secondary.

    Contact terminals 13 to 24 control Line to Line andLine to Neutral sensing to the voltmeter.

    Meter Selector Switch

  • Controller

    56

    Meter Scale Indicators

    Two 1/3-watt neon lamps located in the switchnameplate are connected to a terminal block andindicate which scale is to be read. Placement ofa jumper provides 120 vac and determines thelighting of either the upper or lower indicatorlamp. The lower scale is used on all voltageconnections except 277/480 (220/380), and600v.

    Meter Terminals and Fuses

    Stator coil leads 7, 8 and 9 (V7, V8, V9) aremonitored and protected by 250v 1.5 ampterminal block fuses. Lead 10 is the neutral anddesignated as V0. Terminals C1, C2, and C3are the X1 secondary of the CTs, terminal C0 isthe secondary common and is grounded.

  • Controller

    57

    Emergency Stop Switch (local)

    Depressing the oversized red stop switch asdoes placing the RUN - OFF/RESET - AUTOswitch in the OFF position provides animmediate engine shutdown. It will override the5 minute delayed shutdown which occurs whenthe unit is being controlled remotely and shouldonly be used as an emergency stop switch.

    This switch is standard on all Detroit Dieselpowered units and optional on all other models.

    This three-piece switch consists of a latchingplunger assembly, the mounting housing and thecontact assembly.

    Pressing the plunger button opens the normallyclosed set of contacts. The latching featureholds them in the open position until the button ismanually rotated 1/4 turn clockwise which resetsthe assembly to its normal position.

    The two mounting screws are accessed by firstremoving the contact assembly.

    The switch contacts are wired to terminals 1 and1A of the main control board terminal strip. Ajumper must be placed between these terminalsif a switch is not installed.

  • Controller

    58

    Voltage Adjust

    The 1000 ohm, 1 Watt potentiometer allowscustomer adjustment to the generator outputvoltage a minimum of +/- 10% of the nominalgenerator voltage range.

    The potentiometer is wired to the voltageregulator via an inline 2-pin connector.

    Hourmeter

    The hourmeter is used to record the totaloperating time of the generator set. It isenergized with the engine gauges and panelillumination lamps from the F3, 15-amp fusethrough the K3 control relay.

    The typical style meter illustrated will acceptDC voltages from 8-32 volts. Polarity to itsterminals must be observed.

    Panel Lamps

    Two # 1815, (14v/2.8w) or two #313, (28v/4.8w) miniature bayonet lamps illuminate thestandard front panel. Three lamps are used inthe expanded box panel.

    These lamps are energized whenever thegenerator set is operating and are powered bythe set battery. (12 or 24vdc).

    The circuit is protected by the F3 fuse.

  • Controller

    59

    Control/Status Indicator Panel

    Generator set operational mode selectorswitch, audible alarm and 16 visual indicatorsof system condition are contained on theIndicator panel.

    Programmed decisions of starting andstopping as well as monitoring the systemconditions and channeling the appropriateactions is performed by the Microprocessor control board.

    The Indicator panel is powered by a 12vdcregulated supply from the Processor circuitboard. Interconnection between the twocircuit boards is by a ribbon connector

    - RUN-OFF/RESET-AUTO SW. Selects themode of Engine operation.

    - RUN - Start and run the generator set locally- OFF/RESET - Stop the generator set locally,and reset the system after a fault shutdown.

    - AUTO - Allows Start/Stop commands from aremote location.

    - LAMP TEST SW. Provides a ground to all16 LED indicator input circuits. All indicatorsshould light.

    - ALARM HORN. Provides an audible signalindicating a fault is or was on the system orthe main control switch is not in the Auto,position.

    - ALARM SILENCE SW. Allows the Horn tobe silenced when the Engine control switch isin the Auto position. Horn can not besilenced in the Run or Off/Reset, positions

  • Controller

    60

    Control/Status Indicator PanelCircuit Board

    * Light illuminates when cooresponding terminal is grounded

  • Controller

    61

    Controls/Status Indicators

    A total of 16 LED indicators are provided, 1Green (System Ready) 3 Amber (Prealarm) and12 Red. Not all 16 input senders are standard orfactory wired.

    PMG Standard Features

    - SYSTEM READY - SW. NOT IN AUTO- HIGH ENG. TEMP - LOW OIL PRESS-OVERCRANK -OVERSPEED- LOW COOLANT LEVEL (AUX)

    - EMERGENCY STOP (DDC only)

    SYSTEM READY - Indicator lights when theStart/Selector switch is in the AUTO position andthe system senses no faults. The set is ready tostart on a remote command.

    GENERATOR SWITCH NOT IN AUTO - Lamplights and alarm sounds when Start/Selectorswitch is in RUN or OFF/RESET positionindicating the set cannot be operatedautomatically from a remote location.

    HIGH ENGINE TEMPLOW OIL PRESS - Switches are factoryinstalled and will close when coolanttemperature reaches approximately 225 F(107 C) and Oil Pressure drops toapproximately 5.5 - 10.5 psi (38-72kPa). After 5seconds from switch closure the correspondingIndicator will light, the horn will sound, andengine shutdown will occur.

    PREALARM HIGH ENG. TEMPPREALARM LOW OIL PRESS. - Optionalswitches are required to be installed in theengine block which will activate the indicatorsand horn at temperatures slightly below andpressures slightly above the standard cutoutswitch ratings. No engine shutdown will occur.Wiring is standard and located in the harness.Dual temperature switches may be installed.

  • Controller

    62

    LOW FUEL - Requires customer wiring andtank mounted switch to close at desired fuellevel. Will activate indicator and horn.

    EMERGENCY STOP - Requires switch incontrol panel or optional N.C. remoteswitches. Contact opening provides Lampindication, Horn alarm and an immediateengine shutdown.

    BATTERY CHARGER FAULT - Relay incharger required to provide contact closure oncharger malfunction. Ground Signal will lightindicator if charger malfunctions. (optional)

    LOW BATTERY VOLTAGE - Indicator willlight if battery voltage drops below a presetlevel. Requires ground signal from batterycharger relay contact closure. (optional)

    OVERCRANK - Cranking stops and Indicatorwill light if engine does not start after 45seconds of continuous cranking, 75 secondsof cyclic cranking or 15 seconds of lockedrotor.- OVERCRANK LAMP WILL FLASH IF: Speedsensor signal to microprocessor is absentlonger than one second.

    OVERSPEED - Indicator will light, horn willsound and engine will shut down if governedfrequency exceeds 70 Hz. The signal isprovided to the microprocessor by the SpeedSensor pickup.

    AIR DAMPER - Lamp lights after emergencystop, overspeed or overvoltage fault. Indicatorsignifies the engine air damper is closed.Lamp remains Iit until air damper is manuallyreset. (activated by closure of microswitchcontacts, lead T56 to ground.)

    AUXIUARY PREALARM - Flashing Amberindicator. Activated by customer providedsensing devices. Pre-low fuel, Generatoroverload etc. (lead T27 to ground willactivate.)

    AUXIUARY FAULT - This lamp providesnumerous indications:

    - LAMP WILL LIGHT, HORN WILL SOUND ANDENGINE WILL SHUT DOWN IF:- Overvoltage condition occurs.Activated by optional Overvoltage circuit board(lead 30). on microprocessor-plus controllers

    - LAMP WILL LIGHT, HORN WILL SOUND ANDENGINE WILL SHUT DOWN 5 SECONDSAFTER:- Low Coolant level (standard).- High oil temperature (optional).Feature is inhibited during first 30 seconds afterstartup.

    - LAMP WILL LIGHT AND HORN WILL SOUNDIF:- Optional Emergency Stop switch is reset withthe Engine Start selector switch In the AUTO orRUN position.

    - LAMP WILL FLASH AND HORN WILL SOUNDIF:- No AC output is available (after 10 seconds ofstart-up).- Battery is connected with the Engine Startselector switch In the RUN or AUTO position. -Low battery voltage or hardware reset of theMicroprocessor occurs.

    Control/Status Indicators

  • Controller

    63

  • Controller

    64

  • Controller

    65

    Coolant Level Detector (LWL)

    The liquid sensor is located in the upperradiator tank and detects the presence andabsence of liquid at the probe tip.

    The device will provide a (-) signal via lead 31to the microprocessor board to initiate anengine shutdown, sound the alarm and lightthe AUXIUARY lamp. The shutdown isdelayed for 5 seconds and the circuit isinhibited for 30 seconds on engine start-up.

    Type A (Microprocessor)

    Both 12 and 24v senders are available. Thevoltage rating is stamped in the hex housingand must match the system voltage.A bias voltage must be available for the 3-wiredevice to operate.

    During operation with liquid present at theprobe an open circuit exists between the Blue(output) and Black (ground) leads.

    When liquid is absent from the probe theoutput terminal will go to ground potential.

    Type B (Microprocessor-Plus)

    The sensor used for both 12 & 24 volt systems withMicroprocessor-Plus controls is a 2 wire 12v device.

    Voltage at the sensor terminals during normaloperating conditions when emersed in coolantis 12.5 vdc.

    The resistance value of the device willdecrease when coolant is removed from theprobe. The decrease in resistance will causethe voltage to drop to approximately 7 voltsinitiating an engine shutdown.

  • Controller

    66

    Speed Sensor (Proximity Sensor)

    The Speed Sensor provides the Microcomputercircuit board with digital information on therotating status of the generator set.

    The device when energized will provide anoutput signal when a ferrous metal comes inproximity to its sensing surface.

    Input voltage to the sensor is approximately9.5vdc. During engine cranking and running anaverage of approximately 7vdc will appear at theoutput.

    The Sensor is located on the end bracket andmounted so an air gap of .0201 is between thesensor and actuator. Two signals are providedper revolution of the rotor shaft.

    The microcomputer will monitor and respond tothe sensors output signals.

    - The signal pattern produced at an enginespeed of 750 RPM (25Hz) will be interpreted asengine run speed and the cranking cycle will beterminated.

    - If the engine run signal provided at 750RPM isnot available after a cyclic engine crank totaling75 seconds or after 45 seconds of continuouscranking, the start attempt will be aborted andthe Overcrank indicator will light.

    - If no signal is received after 5 seconds ofcranking the controller will assume the engine isnot rotating and a locked rotor condition exists.After a 5 second rest another 5 second startattempt will be made. If no signal is receivedwithin this 15 second interval the cranking cyclewill terminate and the Overcrank indicator willlight.

    - The signal produced at 2100 RPM (70Hz) andabove will initiate an Overspeed shutdown.

    - If during operation a signal is absent for longerthan 1 second and AC generated voltage isavailable the generator set will continue to run,however the Overcrank indicator will flashindicating a fault has occurred in the sensorcircuit and service is required prior to the nextstart-up.

  • Controller

    67

    Speed Sensor (Proximity Sensor)

    The sensor requires a shielded interconnectioncable to the microprocessor circuit board. Theshield (S2) is grounded through terminal 6 of theP1 connector.

    The device can be bench checked by applying12VDC to the input and observing a DC outputwhen the circuit is triggered by placing a flatpiece of iron or steel at the sensing surface.

  • Controller

    68

    Microprocessor Circuit Board

    The main control circuit board is designedaround a self contained, single-chip digitalmicrocomputer that has memory, logic, databus, control bus and I/O ports in one 40-pinintegrated circuit.

    The control algorithm is provided in ROM(Read-Only-Memory), which maintains datastorage without a power supply ensuring thatprogrammed information is never lost.

    Hardware and software filters protect theboard from electrical noises common togenerator set applications.

    Operating range is from - 40 to 185 F.

    The G-292806 Board illustrated will controlboth 12 and 24 volt engine starting systems.

    Input and output signals are provided at thethree P connectors (P1, P2, P3) and TB 1terminal strip.

    The P3 connector provides the interconnectionfor the 20 conductor ribbon harness and theControl/Status Indicator panel.

    The TB1 barrier strip allows interconnection of

    options such as: remote operation,annunciators, emergency stop switches, anddry contact kits.

    The PI and P2 connectors provide input andoutput connections between the engine,generator and controller.

    Three sealed relays K2, K3, and K4 providethe engine starting, running and stoppingcontrol. LEDs are connected across the relaycoils to indicate voltage has been directed toenergize the relay.

    The K2 relay controls the battery supply to thestarter solenoid on an engine crank command.The F3 fuse protects the output circuit.

    The K3 relay provides battery voltage to theengine run circuit, (Fuel pump/solenoid,Ignition etc.) the meter cabinet componentsand voltage regulator. The F3 Fuse alsoprotects the contact circuit.

    The K4 relay supplies the control logic circuitswith a 12vdc regulated supply. It alsofunctions as the emergency stop relay.

  • Controller

    69

    The 24 terminal barrier strip is provided on theMain Control board for connecting of optionalfeatures.

    It is recommended that stranded wire or theoptional connection kit be used if multipleconnections are made to the terminal strip.Lowering and raising the rear-hinged panelwhen solid conductors are used imposesstress on the circuit board.

    (3 - 4) REMOTE START / STOP

    When the status panel operational selectorswitch is placed in the AUTO position thegenerator set can be remotely started andstopped by a switch or a dry set of contactsconnected across terminals 3 - 4.Do not apply an external voltage.

    Open circuit voltage across 3(-) and 4(+) is12vdc. The circuit draws approximately 42 mawhen completed.

    Two 14 ga. conductors are recommended upto runs of 2000 ft. The conductors should berun in a conduit separate from the conduitsused for generator load cables or batterycharging cables to prevent radiated or inducedsignals to the circuit board.

    When the circuit is opened after operatingfrom a remote start the generator set willcontinue to run for an additional 5 minutes toallow for an Engine Cooldown.

    (1 - 1A) EMERGENCY STOP

    A circuit must be completed between 1 and 1A for the generator set to operate.

    A panel mounted EMERGENCY STOP switch,or optional Break Glass switch provides amaintained set of normally closed contacts. Ifthis circuit is opened during operation animmediate shut down will occur.

    A restart can not be made until both theemergency stop switch and Main operationalcontrol switches are RESET.

    If an emergency stop switch is not installed ajumper is required across the terminals.

    (9 - 2) CRANK MODE

    Cyclic engine cranking of 15 sec. crank with15 sec. rest for a total of 75 seconds isstandard. Placing a jumper between terminals9 and 2 can eliminate the cyclic feature. Thiswill allow a continuous engine crank of 45seconds on a start attempt prior to anovercrank termination.

    (42 - 2) VOLTAGE SUPPLY

    Terminals 42A (+) and 2 (-) provide a 3 ampfused (Fl) systems battery voltage supply foraccessories or optional devices. (12 or 24vdc)

  • Controller

    70

    The following terminals are output only and allowfor connection of optional remote indicators orinputs to dry contact kits. The terminals providea ground (-) output when the fault is activatedand limited to 100 milliampere loads.

    (48) EMERGENCY STOP - E.S.

    (56) AIR DAMPER - A.D.

    (26) AUXILIARY -AUX.

    (12) OVERCRANK - O.C.

    (39) OVERSPEED - O.S.

    (38) LOW OIL PRESSURE - L.O.P

    (36) HIGH ENG. TEMP - H.E.T

    (60) SYSTEM READY - S.R.

    (80) SW. NOT IN AUTO- N.I.A.

    (40) PRE-HIGH ENG. TEMP - PH.E.T

    (41) PRE-LOW OIL PRESSURE - PL.O.P

    (35) LOW WATER TEMP - L.W.T

    (32) COMMON FAULT - C.F.

    The Common Fault terminal 32 will be at ground(-) potential when any of the 10 following faultsoccur:

    - HIGH ENG.TEMP - PRE-HIGH ENG.TEMP

    - LOW OIL PRESS. - PRE-LOW OIL PRESS.- LOW WATER TEMR - OVERCRANK- OVERSPEED - AUXILIARY- LOW FUEL - AIR DAMPER.

    It is used as the input signal for the optionalAudio-Visual Alarm.

    The Common Fault Relay Kit can be used if acustomer desires less or custom combinations ofany of the above.

    TB1 Terminal Strip

  • Controller

    71

    Terminals 61, 62 and 63 can be used asterminating points for both input and outputsignals of optional Battery Charger Fault (61),Low Battery Charger Voltage (62) and LowFuel Level (63).

    A negative (-) signal will energize the StatusPanel indicator as well as optional remoteannunciator indicators connected to theterminal. Terminal 42A is positive, terminal 2 isnegative (-).

    (61) BATTERY CHARGER FAULT

    Terminal 61 can be connected to a relaycontact located in the charger, which isactivated when a fault occurs with the batterycharger. (No AC input or DC output) Closureof the contact will energize the BatteryCharger Fault indicator(s).

    (62) LOW BATTERY VOLTAGE

    Terminal 62 can be connected to a relaycontact located in the battery charger, which isactivated when the battery voltage dropsbelow a preset level for longer than 2seconds. The relay will reset removing thesignal if the voltage rises to a preset levelabove the alarm trip point. The Low BatteryVoltage indicator(s) will light on contactclosure.

    (63) LOW FUEL LEVEL

    Terminal 63 allows for connection of a fuellevel switch and indicator. Contacts of theswitch provide a (-) signal to light theindicator(s) and sound the alarm(s) when thefuel level drops below a preset level.

    TB1 Terminal Strip

  • Controller

    72

    The majority of engine/generator conditioninputs and engine control outputs are providedfrom the harness connector Pl.

    The P2 plug connector provides AC input forvoltage sensing and optional overvoltageshutdown signal as well as DC output to theinstrument panel engine gauges andillumination lamps.

    The signal for the AIR DAMPER, indicator onthe Status Panel is also supplied from the P2connector.

    The P3 20 terminal plug providesinterconnection to the Status Panel switchesand indicators via a ribbon harness. Faultsignals to the P3 are common to the TB1terminals.

    Connectors: P1, P2, P3 Microprocessor

  • Controller

    73

  • 74

    ko49268Notes

  • Controller

    75

    The three fuses are located in holders solderedto the microprocessor circuit board and protectthe wiring and circuit foil from damage in theevent of excessive fault currents.

    The Fl fuse provides overcurrent protection fromaccessories or options powered from terminal42A on the TB1 terminal strip. The 3 Amp fuseis rated at 250 volts.

    The F2 fuse protects the circuits powering themain logic and relay coils on the microcomputerboard as well as the Status/Indicator panel.It is also a 3 Amp, 250-volt fuse.

    The F3 fuse provides circuit protection if faultsoccur on engine electrical components poweredthrough the K2 and K3 relay contacts. Theceramic fuse is rated at 15 amps/ 250v.

    Relays; K2 - K3 - K4 (LEDs 2,3,4)

    The (3) 12vdc sealed relays soldered to thecircuit board provide controlled output power tothe generator sets DC electrical components:Start solenoid, Fuel valves, Governor control,Fuel pump, Ignition, Voltage regulator,Solenoids, Slave relays etc. Red LEDs areconnected across the relay coils to indicatewhen voltage is applied to the coils.

    The K2 relay provides the cranking control to theengine starter crank solenoid (K1). When anengine start command is initiated the logic circuitwill cyclically energize the relay coil, 15 secondson and 15 seconds off for a total time of 75seconds. This cyclic mode can be changed to 75seconds of continuous energizing by placing ajumper between terminals 2 and 9 of the TB1terminal strip.

    The K3 relay provides battery voltage supply (12or 24 vdc) to the engine, generator andcontroller components required for normal runoperation. It remains energized during a start/run command and is deenergized 5 minutesafter a remote stop command or immediately onan emergency stop signal.

    A normally open set of K4 contacts are in serieswith both the K2 and K3 relay coils. The K4

    relay (emergency stop), must be energizedbefore an engine crank and run can occur. If thecircuit to the K4 coil is disrupted both the K2 andK3 relays will be deenergized. The emergencystop switch when used is connected in serieswith the K4 relay coil. (TB1 terminals 1 - 1A)

    Fuse; F1 - F2 - F3

    ko49268(Microprocessor)

    ko49268

  • Controller

    76Microprocessor Controller

  • Controller

    77

  • Controller

    78

    The Plus Controller utilizes the 336415 circuitboard. It was introduced in 1995 and is thestandard microprocessor circuit board on PMGgenerators with serial numbers above 363369.

    The main control circuit board is an enhancedversion of the Microprocessor board design.

    The board will control both 12 and 24 volt enginestarting systems. It features adjustablegenerator Overvoltage shutdown protection anda Prime Power Mode.

    The Prime power feature allows disabling theLED indicators and alarm horn when in theOFF mode to reduce battery drain.

    Input and output signals are provided at thethree P connectors (P1, P2, P3) and TB1 andTB2 terminal strips.

    The P3 connector provides the interconnectionfor the ribbon harness and the Control/StatusIndicator panel.

    The TBI and TB2 barrier strips allowinterconnection of options such as, remoteoperation, annunciators, emergency stopswitches and dry contact kits.

    The P1 and P2 connectors provide input andoutput connections between the engine,generator and controller.

    Three sealed relays K2, K3, and K4 provide theengine starting, running and stopping control.LEDs are connected across the relay coils toindicate voltage has been directed to energizethe relay.

    The K2 relay controls the battery supply to thestarter solenoid on an engine crank command.The F3 fuse protects the K2 output circuit.

    The K3 relay provides battery voltage to theengine run circuit, (Fuel pump/solenoid, Ignitionetc.) the meter cabinet components and voltageregulator. The F3 Fuse protects the K3 outputcircuit.

    The K4 relay supplies the control logic circuitswith a 12vdc regulated supply. It also functionsas the emergency stop relay.

    Microprocessor-Plus Controller

  • Controller

    79

    The 23 terminal barrier strip is provided on theMain Control board for connecting of optionalfeatures.

    It is recommended that stranded wire or theoptional connection kit be used if multipleconnections are made to the terminal strip.Lowering and raising the rear hinged panel whensolid conductors are used imposes stress on thecircuit board.

    (1 - 1A) EMERGENCY STOP

    A circuit must be completed between 1 and 1 Afor the generator set to operate.

    A panel mounted EMERGENCY STOP, switch,or optional Break Glass switch provides amaintained set of normally closed contacts. Ifthis circuit is opened during operation animmediate shut down will occur.

    A restart can not be made until both theemergency stop switch and Main operationalcontrol switches are reset.

    If an emergency stop switch is not installed ajumper is required across the terminals.

    (42 - 2) VOLTAGE SUPPLY

    Terminals 42A (+) and 2 (-) provide a 3 ampfused (Fl) systems battery voltage supply foraccessories or optional devices. (12 or 24vdc)

    (70C) ENGINE COOLDOWN

    Signal is provided for remote annunciationindicating that engine is running in the cooldownmode prior to a normal shutdown.

    (70R) ENGINE RUN

    Signal is provided for remote annunciationindicating the generator set is operating in anormal run condition.

    (61) BATTERY CHARGER FAULT

    (62) LOW BATTERY VOLTAGE

    (63) LOW FUEL LEVEL

    A negative battery (-) signal placed on theterminal will light the corresponding indicator onthe remote annunciator panel.

    Signals are provided by battery charger faultrelays or a fuel level switch.

    ko49268

    ko49268MICROPROCESSOR-PLUS

  • Controller

    80

    The following terminals are output only and allowfor connection to optional remote indicators orinputs to dry contact kits. The terminals providea ground (-) output when the fault is activatedand limited to 100 milliamper loads.

    (56) AIR DAMPER - A.D.

    (48) EMERGENCY STOP - E.S.

    (32A) COMMOM FAULT - LINE 2*

    (26 AUXILIARY - AUX.

    (12) OVERCRANK - O.C.

    (39) OVERSPEED - O.S.

    (38) LOW OIL PRESSURE - L.O.P

    (36) HIGH ENG. TEMP - H.E.T

    (60) SYSTEM READY - S.R.

    (80) SW NOT IN AUTO - N.I.A.

    (41) PRE-LOW OIL PRESSURE - P.L.O.P

    (32) COMMON FAULT -LINE 1 *

    (40) PRE-HIGH ENG. TEMP - PH.E.T

    (35) LOW WATER TEMP - L.W.T.

    * COMMON FAULT is used as an input signal foroptional Audio-Visual Alarms. Two choices ofFault combinations are offered:

    (32) - Terminal will be at ground (-) potentialwhen any of the 10 following faults occur:

    - HIGH ENG.TEMP - PRE-HIGH ENG. TEMP- LOW OIL PRESS. - PRE-LOW OIL PRESS.- LOW WATER TEMR -OVERCRANK- OVERSPEED -AUXIUARY- LOW FUEL -AIR DAMPER.

    (32A) - Terminal will be at ground (-) potentialwhen any of the following 5 faults occur.

    - AUXILIARY - HIGH ENG.TEMP- LOW OIL PRESS. -OVERSPEED- EMERGENCY STOP

    The Common Fault Relay Kit can be used if acustomer desires less or custom combinations ofany of the above.

    TB1 Terminal Strip Microprocessor Plus

  • Controller

    81

    Barrier strip TB2 contains the engine startingcontrol terminals.

    (3 - 4) Remote START/STOP

    When the status panel operational selectorswitch is placed in the AUTO position thegenerator set can be remotely started andstopped by a switch or dry set of contactsconnected across terminals 3 - 4.Do not apply an external voltage.

    Open circuit voltage across 3(-) and 4(+) is12vdc. The circuit draws approximately 42milliamperes when completed.

    Two 14 ga. conductors are recommended up toruns of 2000 ft. The conductors should be run ina conduit separate from the conduits used forgenerator load cables or battery charging cablesto prevent radiated or induced signals to thecircuit board.

    When the circuit is opened after operating from aremote start the generator set will continue torun for and additional 5 minutes to allow for anEngine Cooldown.

    (9 - 9A) Crank Mode

    Cyclic engine cranking of 15 sec. crank with 15sec. rest for a total of 75 seconds is standard.The cyclic feature can be eliminated by placing ajumper between terminals 9 and 9A. This willallow a continuous engine crank of 45 secondson a start attempt prior to an overcranktermination.

    Prime Power Feature

    This feature is provided for applications which donot require a remote automatic start and whenbattery drain must be kept to a minimum when inthe off mode.

    Jumpers must be placed between terminals1P - 2P, 3P - 4P and 3 - 4 to activate thisfeature. Alarm horn, LED indicators and remotestart capabilities will be disabled.An Engine start can only be activated manuallyfrom the local status panel by moving the switchfrom the OFF/RESET to the AUTO position.This will also rearm the alarm and indicator

    TB2 Terminal Strip Microprocessor Plus

  • Controller

    82

    The majority of engine/generator conditioninputs and engine control outputs are providedfrom the harness connector P1.

    The P2 plug connector provides AC input forvoltage sensing and optional overvoltageshutdown signal as well as DC output to theinstrument panel engine gauges and illuminationlamps.

    The signal for the AIR DAMPER indicator on theStatus Panel is also supplied from the P2connector.

    The P3 20 terminal plug providesinterconnection to the Status Panel switches andindicators via a ribbon harness. Fault signals tothe P3 are common to the TBI terminals.

    P1, P2 P3 Connectors

  • Controller

    83

  • Controller

    84

    The three fuses are located in holders solderedto the microprocessor circuit board and protectthe wiring and circuit foil from damage in theevent of excessive fault currents.

    The Fl fuse provides overcurrent protection fromaccessories or options powered from terminal42A on the TB1 terminal strip. The 3 Amp fuseis rated at 250 volts.

    The F2 fuse protects the circuits powering themain logic and relay coils on the microcomputerboard as well as the Status/Indicator panel.It is also a 3 Amp, 250-volt fuse.

    The F3 fuse provides circuit protection if faultsoccur on engine electrical components poweredthrough the K2 and K3 relay contacts. Theceramic fuse is rated at 15 amps/ 250v.

    Relays; K2 - K3 - K4 (LEDs 1,2,3)

    The (3) 12vdc sealed relays soldered to thecircuit board provide controlled output power tothe generator sets DC electrical components:Start solenoid, Fuel valves, Governor control,Fuel pump, Ignition, Voltage regulator,Solenoids, Slave relays etc. Red LEDs areconnected across the relay coils to indicatewhen voltage is applied to the coils.

    The K2 relay provides the cranking control to theengine starter crank solenoid (K1). When anengine start command is initiated the logic circuitwill cyclically energize the relay coil, 15 secondson and 15 seconds off for a total time of 75seconds. This cyclic mode can be changed to75 seconds of continuous energizing by placinga jumper between terminals 9 and 9A of the TB2terminal strip.

    The K3 relay provides battery voltage supply (1 2 or 24vdc) to the engine, generator andcontroller components required for normal runoperation. It remains energized during a start/run command and is deenergized 5 minutesafter a remote stop command or immediately onan emergency stop signal.

    A normally open set of K4 contacts are in serieswith both the K2 and K3 relay coils. The K4relay (emergency stop), must be energizedbefore an engine crank and run can occur. If thecircuit to the K4 coil is disrupted both the K2 andK3 relays will be deenergized. The emergencystop switch when used is connected in serieswith the K4 relay coil. (TB1 terminals 1 - 1 A)

    Fuses; F1, F2, F3 Microprocessor-Plus

  • Controller

    85

    An overvoltage protection circuit is provided onthe Plus circuit board. The feature is factoryadjusted to shut down the generator set if theoutput voltage exceeds 115% of the nominalvoltage setting for longer than 2 seconds*.

    A potentiometer (R41) and Light Emitting Diode(LED4) are provided on the board for fieldadjustment. The LED will indicate when theovervoltage occurs. Clockwise rotation of R41will increase the voltage trip point.

    A shutdown due to an overvoltage condition willcause the Auxiliary indicator on the local andremote status annunciator panels to light.

    NOTE *Equipment sensitive to Voltage specificationsabove this rating requires additional fieldinstalled protective devices.

    Microprocessor-PlusOvervoltage Shutdown

  • Controller

    86Microprocessor Plus Controller

  • Controller

    87

  • Controller

    88

    The seven lamp controller is offered for level 2applications not as stringent as installationsrequiring the NFPA-110 level I (16) lampcontroller.

    This controller incorporates all the componentsof the standard Microprocessor-Plus but provides only 7 indiicator lamps on the status panel. Theseinclude:

    OVERCRANKLOW OIL PRESSUREOVERSPEEDHIGH ENG. TEMPLOW WATER TEMRAUXIUARY *AIR DAMPER

    *The Auxillary lamp will flash if no generated ACor low battery voltage is sensed.

    The Auxillary lamp will light on EmergencyStop, Overvoltage Shutdown, Low WaterLevel, or Auxiliary customer supplied devices.

    Microprocessor-Plus Controller (7 lamp)

  • Controller

    89

    This Manual Controller provides a simplerelay control with full generator meteringand engine condition gauges as well asOverspeed, Low oil pressure, High coolanttemperature and Low coolant level shutdown protection.

    It is designed for local manual starting andstopping of the generator set. Remotestarting capabilities and overcrankprotection are not provided.

    The relay control circuit board featuresLEDs connected across the relay coils fordiagnostic aid when servicing.

    Along with the relay control circuit board acombination Overspeed / Time Delayboard is incorporated.

    The Overspeed (Overfrequency) circuitmonitors the generator AC output and willenergize the stop relay if a generatedfrequency above 70 Hz occurs.

    The TD (time delay) portion of the boardprovides a set of contacts to delayenergizing of the low oil pressureshutdown circuit during cranking and start-up.(5 Sec.)

    The run circuit is interlocked when an ACsignal is available from the generatoroutput. A transformer located in thecontroller cabinet provides 12 vac to thecircuit. A time delay (TD) for engine oilpressure build-up is also provided in theinterlock circuit.

    The common fault lamp will light when the stopcircuit is energized.

    Manual Controller

    ko49268

  • Controller

    90Manual Controller

  • Controller

    91

    This Control cabinet allows the generator set tobe interconnected with switchgear-mountedengine control logic for parallel operation.

    All engine/generator controls and metering aremounted in the switchgear cabinet withexception of an electronic speed switch andemergency stop switch if one is required.

    The governor magnetic pick-up provides theelectronic switch with the flywheel speed signalfor engine crank termination as well asoverspeed shutdown.

    Terminal strips are provided for customerinterconnection of the governor, crank relays,safety shutdown and gauge senders to theswitchgear cabinet.

    Engine Gauge Box

    ko49268

  • Controller

    92Engine gauge Box

  • Controller

    93

    The Basic Controller series provides acost effective controller for applications thatrequire remote or automatic start capability butcompliance with NFPA requirements is notnecessary.

    The Start Selector switch has positions for local(RUN) or remote (AUTO) operation as well aslogic resetting after a fault shut-down.

    A common fault lamp is provided for indication ofa shut-down due to:

    OVERCRANKOVERSPEEDHIGH ENGINE TEMPERATURELOW OIL PRESSURELOW COOLANT LEVEL

    The panel mounted input fuse, running timemeter and voltage regulator adjust are alsostandard on all Basic controllers.

    Terminals 3 - 4 on the TBI strip are provided fordry contact remote starting.

    A 15 amp fuse and K5 relay are also located inthe cabinet and provide controlled batteryvoltage to the engine gauges, fuel system,voltage regulator and battery charging alternatorexcitation circuit.

    The electric governor control is also located inthe controller cabinet.

    Basic Controller

    ko49268Standard Basic

    ko49268

  • Controller

    94

    The logic circuit board contains 4 relays forcontrol of cranking, crank disconnect, run orauto-start and fault indication. LEDs arec