Service & Support Answers for industry. Cover User Rights (Authorizations) in SIMATIC PCS 7 OS V7.1 SIMATIC PCS 7 V7.1 FAQ May 2012

Upload: others

Post on 13-Mar-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

Service & Support

Answers for industry.

Cover

User Rights (Authorizations) in SIMATIC PCS 7 OS V7.1

SIMATIC PCS 7 V7.1

FAQ � May 2012

Page 2: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

Question

2 User Rights PCS 7 OS V7.1

1.0, Item-ID: 60575347

This entry is from the Siemens Industry Online Support. The general terms of use (http://www.siemens.com/terms_of_use) apply.

Clicking the link below directly displays the download page of this document.

http://support.automarion.siemens.com/WW/view/en/60575347

Caution The functions and solutions described in this article confine themselves to the realization of the automation task predominantly. Please take into account furthermore that corresponding protective measures have to be taken up in the context of Industrial Security when connecting your equipment to other parts of the plant, the enterprise network or the Internet. Further information can be found under the Content-ID 50203404.

http://support.automation.siemens.com/WW/view/en/50203404

Question How do user rights (authorizations) work in SIMATIC PCS 7 V7.1?

Answer The instructions and notes listed in this document provide a detailed answer to this question.

Page 3: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

Table of content

User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 3

Table of Content 1 How do user rights work?..............................................................................4

1.1 Where to manage Usernames and Passwords...................................5 1.2 User rights workflow for SIMATIC PCS 7 OS .....................................6 1.3 User rights workflow for SIMATIC PCS 7 OS combined with

Windows............................................................................................8 1.4 User rights workflow for PCS 7 OS Web Option ...............................10 1.5 User rights applied to tags ...............................................................10 1.6 User rights mechanism ....................................................................11

2 Appendix.......................................................................................................13 2.1 Appendix 1 ......................................................................................13 2.2 Appendix 2 ......................................................................................14 2.3 Appendix 3 ......................................................................................14

Page 4: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

1 How do user rights work?

4 User Rights PCS 7 OS V7.1

1.0, Item-ID: 60575347

1 How do user rights work? SIMATIC PCS 7 makes operation secure by means of assigning user rights to users that log on to the system before they can monitor and operate the process.

Levels of user rights

SIMATIC PCS 7 supports the following user rights within the scope of the SIMATIC PCS 7 Operator System (OS).

Table 1-1

No Function Description 1 User Administration Right to create and modify users and groups in the HMI 2 Authorization for Area Right to access and operate the process area and its related

process graphics and tags 3 System Change Right to deactivate the Runtime and gain access to the

Windows desktop 4 Monitoring Right to monitor the process and open other applications (which

will apply user rights within their own scope) for example SIMATIC BATCH Client

5 Process Controlling Right to operate the process and perform normal process adjustments, this includes starting and stopping equipment, opening and closing valves and making setpoint changes to PID loops

6 Higher Process Controlling Right to make adjustments to process critical parameters and tuning parameters like alarm limits, PID algorithm tuning parameters

7 Report System No longer used, left in the system for compatibility reasons 1000 Remote Activation Right to start and stop the runtime for this project from a

different computer, this authorization is not used for SIMATIC PCS 7 OS

1001 Remote Configuration Right to configure and make changes to the project from a different computer, this authorization is not used for SIMATIC PCS 7 OS

1002 Data Monitor(Web Access) – Just Monitor

Right to see process screens in Data Monitor, applicable when the SIMATIC PCS 7 OS project is used as the basis for a Data Monitor Server application, whose Web Client users gain access to live process screens with this user right being set

1100 Highest Process Controlling

Right to operate tag settings that are exceptional like switch a tag to or from simulation (used in APL Function Blocks and Faceplates)

Page 5: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

1 How do user rights work?

User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 5

Area and Station (computer) dependent user rights

The user rights are assigned to individual users or groups of users and can be configured different per process area and operator station.

Within the SIMATIC PCS 7 operator system, process graphics and Tags belong to process areas, the rights of a user within a process area are applicable to all graphics and Tags that are assigned to the process area.

You can also revoke access to specific process areas their process graphics and any Tag that belongs to that process area.

Groups and Users

To make configuration easier and help avoid mistakes, the SIMATIC PCS 7 OS editor “User Administrator” supports Groups and Users. Users must always be member of a Group.

The group configuration can be inherited into a newly created User, but a User can always have a different configuration compared to the group it is member of.

There is an option to manage Usernames and Passwords in Windows and inherit them into the SIMATIC PCS 7 OS. We recommend that method and explain how it works in the next paragraph.

1.1 Where to manage Usernames and Passwords

The standard software function SIMATIC Logon (included in SIMATIC PCS 7 deliverable without a need for a license), offers the possibility to use Usernames and Passwords managed in the Windows operating system environment. The benefits of managing Usernames and Passwords in Windows are:

· Manage Usernames and passwords in one place (for Domain and Workgroup configurations)

· Leverage the Windows password hardening and renewal policies

· Synchronize the SIMATIC PCS 7 OS users with the business environment, apply business user administration rules to the process control environment (e.g. blocking users that should have no access anymore with one action)

If SIMATIC Logon is used to manage Usernames and Passwords then the SIMATIC PCS 7 OS “User Administration” will ignore users that are configured within its environment and apply User rights based on a match between Windows Group membership and that Group being known in the SIMATIC PCS 7 OS. This implies that it is required to create Process Control related groups in the Windows environment that match Groups that are required in the process control environment. The number of groups that needs to be created depends on the granularity of User rights distribution you want to achieve (e.g. you would create levels like Operators, Engineers, Supervisors, but also levels like Operators_Reactors and Operators_Packaging).

Page 6: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

1 How do user rights work?

6 User Rights PCS 7 OS V7.1

1.0, Item-ID: 60575347

1.2 User rights workflow for SIMATIC PCS 7 OS

If the Usernames and Passwords are managed in SIMATIC PCS 7 OS then you must create each individual user on each OS Client. This is a single step activity, open the User Administrator and perform the task.

Adding a new user

There are two possibilities for adding a new user depended on whether single OS Clients can be deactivated or not.

1. Without de-activating the OS Clients To this the new user must be added on all OS Clients and in addition in all offline OS Client projects on the Engineering System (ES).

2. With de-activating the OS Clients To this the new user must be added in all OS Client projects on the Engineering System (ES) and the OS Client projects must be downloaded again, which can only occur by de-activating the runtime OS Client project.

When Usernames and Passwords are managed in the OS client project, the workflow is as follows:

· Add/modify/delete Users in the User Administration of the OS Client project(s) on the ES

· Add/modify/delete Users in the User Administration of the OS Client project(s) on the runtime Operator Systems

· Download the OS Client project(s) from the ES to the runtime Operator System(s)

Page 7: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

1 How do user rights work?

User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 7

User Administration

Figure 1-1

Group

User

No SIMATIC Logon

No Authorization

Process control Monitoring OnlyHigher Process control

Process areas

Page 8: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

1 How do user rights work?

8 User Rights PCS 7 OS V7.1

1.0, Item-ID: 60575347

1.3 User rights workflow for SIMATIC PCS 7 OS combined with Windows

If the Usernames and Passwords are managed in Windows then you must meet the following prerequisites:

· Install SIMATIC Logon on each OS Computer, this includes the ES.

· Identify an existing or configure a new User in Windows and assign that user to the “Logon_Administrator” Group in Windows, this user will be allowed to make changes to settings in SIMATIC Logon itself.

· Create Groups in Windows User Administration (e.g. Operators, Engineers, Supervisors).

· Create identical Groups as in Windows User Administration on the OS Server and OS Clients “User Administration” on the ES and in the OS runtime. Assign User rights to the Groups.

· Check the box “SIMATIC Logon” in the OS “User Administration” in all OS; you can only check/uncheck this box while the OS project is de-activated.

If your Computers are part of a domain, then you will manage the Usernames and Passwords in the domain. Skip the next step.

If your Computers are in a Workgroup, then you must decide if you want to manage the Usernames and Passwords on one Computer or if you want to manage the Usernames and Passwords on each Computer individually. Look in the table below what the consequences are of that choice

Computers are configured in a Workgroup:

Table 1-2

No dedicated Computer to manage the Usernames and Passwords

Dedicated Computer (that runs SIMATIC Logon) is used to manage Usernames and

Passwords

You have to create a Username and Password for each user on multiple Computers

You will create Usernames and Passwords on one Computer only

The ability of a User to access the OS on that Computer is defined if his Username and Password have been defined on that Computer

Users can access the OS on any Computer where the SIMATIC Logon application on that Computer has been configured to use the dedicated Computer as its resource for Usernames and Passwords

You must modify/add/delete Usernames and Passwords each Computer

Users will have authorization as configured on the Computer where they want to have access (these can be configured to be different from Computer to Computer, so, although Usernames and Passwords are configured on one Computer, each Computer can define different user rights for that user its access)

Page 9: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

1 How do user rights work?

User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 9

To add/modify/delete Users in Windows do the following

· Open the Windows User Administration (check Windows documentation if you want to learn how to do this)

– If your Computers are part of a domain you will manage Users in the domain User Administration.

– If your Computers are part of a Workgroup then you will manage Users on each Computer or once on the dedicated Computer for managing Usernames and Passwords.

– If you decide to manage Usernames and Passwords on each Computer then you must repeat the steps below for each of these Computers.

· Create Groups that have an exact name match with the Groups you created in the .OS project(s).

· Create Users, if desired, revoke all Group memberships that the User gets by default, and assign Group membership to one or more Groups that are known both in the Windows User Administration and in the OS “User Administration”.

NOTE Do not create the Users in the OS projects; defining them in the Windows User Administration is sufficient.

SIMATIC Logon Configuration dialog

Figure 1-2

Default User

No change required if a single computer or

on a domain

Select and specify a dedicated computer if

multiple computers are in a Workgroup

Page 10: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

1 How do user rights work?

10 User Rights PCS 7 OS V7.1

1.0, Item-ID: 60575347

1.4 User rights workflow for PCS 7 OS Web Option

Web Client users have to authenticate themselves at the OS Web Server. The configuration of the web users, respectively of SIMATIC Logon is done on the OS Web Server, similar to the normal user configuration.

You can carry out additionally the following adjustments for all web users:

· Display language on the Web Client

· Different start pictures

· Additional user right “Web Access – Monitoring only”

1.5 User rights applied to tags

Once the users have been created they will be assigned the corresponding user Rights every time they log in to a OS runtime on a specific Computer.

Access and ability to operate in a process area has been defined in the OS “User Administration”, if a User has access to a process area, then the scope of his/her ability to operate is defined by specific rights that have been granted to that user.

The rights that have been granted must match the rights that are required for individual actions in the Faceplate of a Tag within the process area.

Note that each user may have different rights depending on the process area he navigates to and that a Tag can demand unique rights for a specific action. However, the viewing of process tag parameters within an authorized plant area is possible anytime.

This means that a user may be able to change an Alarm Limit of a specific measurement while not being able to make changes to Alarm Limits on other measurements.

In Appendix 3 of this document you will find a list of all SIMATIC PCS 7 APL function Blocks, their inputs that can be modified by an Operator and the User Rights required to operate.

Page 11: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

1 How do user rights work?

User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 11

1.6 User rights mechanism

For operation in a Faceplate there are three levels of User Rights that are relevant, these three levels are defined in “levels”. The levels are numbered 1, 2 and 3.

The default User Rights that are assigned to each slot are:

Table 1-3

Level User Right No. Name Description

1 5 Process controlling

Right to operate the process and perform normal process adjustments, this includes starting and stopping equipment, opening and closing valves and making setpoint changes to PID loops

2 6 Higher process controlling

Right to make adjustments to process critical parameters and tuning parameters like alarm limits, PID algorithm tuning parameters

3 1100 Highest process controlling

Right to operate tag settings that are exceptional like switch a tag to or from simulation (used in APL Function Blocks and Faceplates)

Customization of User Rights in a Faceplate

You have three options for customization of User Rights in a Faceplate:

1. Assign a different User Right to a specific level (e.g. assign 1100 to level 2)

– This does not require changing the Faceplate.

– This can be done on an instance specific basis.

– This is done by means of a property of the symbol from where the Faceplate is being opened.

– This can be bypassed (less security if you assigned a higher User right) if the tag Faceplate is being opened from the Tag Directory (selection in the button bar).

2. Change the Faceplate and assign a different level to a specific operation

– Each graphical object that can be operated on in a Faceplate has properties, of which one is the “OperationLevel”, you can change this property to another value, thus changing the required User right to change the value represented by the graphical object.

– This will result in a change to all tags of the type that the Faceplate is defined for (e.g. all MonAnL type tags).

3. Copy the Faceplate to create a new version and, if desired, copy and rename the Function Block in the Controller and make a modification like done under #2, this is the most complicated modification, in essence you are creating a complete new Function Block and Faceplate by copying an existing Function Block and Faceplate.

Page 12: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

1 How do user rights work?

12 User Rights PCS 7 OS V7.1

1.0, Item-ID: 60575347

User Rights adjusted from the symbol

The symbol, from which the Faceplate is being called, can be configured to define a different User Right for each of the three levels.

Each symbol has three properties: “OperationLevel1_backup”, “OperationLevel2_backup”, “OperationLevel3_backup” that have a User Right assigned to them. You can assign a different User Right which will inherit into the Faceplate.

Properties of a Symbol that support modification of a User Right for the three levels:

Figure 1-3

Default settings for Level 1, 2 and 3

Ability to apply a different User Right to each Level

Tag (Symbol) where this setting applies

Page 13: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

2 Appendix

User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 13

2 Appendix 2.1 Appendix 1

The picture below shows the mechanism in a graphical way for users defined in the OS project (uniquely defined for each Operator Station).

Figure 2-1

User Administration

User Group

User Right Area1 Area2 Area3 …

Is member of

Has Applied to

5 X X X …

6 X …

1100 X …

… …

X

Tag AreaIs part of

User User Rightsdefines

for

Tag Faceplate

Are tested byTag Property

Leveldefines As configured in

Symbol

User Rightdefines

Levelfor Applied to

Area specificUser Rights

Together define

Page 14: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

2 Appendix

14 User Rights PCS 7 OS V7.1

1.0, Item-ID: 60575347

2.2 Appendix 2

The picture below shows the mechanism in a graphical way for users defined in Windows.

Figure 2-2

Windows User Administration

User Group

User Right Area1 Area2 Area3 …

Is member of

Has a corresponding Group

Applied to

5 X X X …

6 X …

1100 X …

… …

X

Tag AreaIs part of

User

User Rightsdefines

for

Tag Faceplate

Are tested byTag Property

Leveldefines As configured in

Symbol

User Rightdefines

Levelfor Applied to

Area specificUser Rights

Together define

SIMATIC PCS 7 OS User Administration

Group

Has

Group

Belongs to

2.3 Appendix 3

The enclosed table lists the Levels for all Faceplates that are provided with the SIMATIC PCS 7 APL V7.1 SP5.

Page 15: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objName .#StatusPermanent On 1 5 ~PG_APL_Memo.PDL _CheckBox_BLR .#StatusPermanent Of f 1 5 ~PG_APL_Memo.PDL _CheckBox_BLR

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameConPerMon .Ov sAH_Lim 2 6 High alarm limit f or Ov ershoot [%] ~PG_ConPerMon_Limit.PDL csoIOAnaAHConPerMon .CPI_AL_Lim 2 6 Low alarm limit f or CPI [%] ~PG_ConPerMon_Limit.PDL csoIOAnaALConPerMon .CPI_AlmHy st 2 6 CPI alarm hy steresis [%] ~PG_ConPerMon_Limit.PDL csoIOAnaHy sConPerMon .Ov sWH_Lim 2 6 High warning limit f or Ov ershoot [%] ~PG_ConPerMon_Limit.PDL csoIOAnaWHConPerMon .CPI_WL_Lim 2 6 Low warning limit f or CPI [%] ~PG_ConPerMon_Limit.PDL csoIOAnaWLConPerMon .InitRef Var Initialize 2 6 Initialize Ref Variance, PV_Ref and MV_Ref in steady state of control loop ~PG_ConPerMon_Parameter.PDL csoBtnInitializeConPerMon .MV_Ref 2 6 In/out: MV v alue in ref erence steady state of the control loop ~PG_ConPerMon_Parameter.PDL csoIOAnaMVRefConPerMon .PV_Ref 2 6 In/out: PV v alue in ref erence steady state of the control loop ~PG_ConPerMon_Parameter.PDL csoIOAnaPVRefConPerMon .Ref Variance 2 6 Ref erence v alue f or PV_Variance in proper state of the control loop ~PG_ConPerMon_Parameter.PDL csoIOAnaPVRef VarConPerMon .Ref StdDev #Value 2 6 Value ~PG_ConPerMon_Parameter.PDL csoIOAnaPVRev DevConPerMon .TimeWindow 2 6 length [s] of mov ing time window f or statistical ev aluations ~PG_ConPerMon_Parameter.PDL csoIOAnaTimeWindowConPerMon .BreakSuppress Cancel ev al. 2 6 Break suppression of CPI alarms at the end of closed loop step response ~PG_ConPerMon_Setpoint.PDL csoBtnCancelEv alConPerMon .OnOp On 1 5 Operator input to switch back to serv ice, 1= Block on, i.e. in serv ice ~PG_ConPerMon_Standard.PDL csoBtnModeConPerMon .OosOp Out of serv ice 2 6 Operator input f or Out Of Serv ice, 1= Out Of Serv ice ~PG_ConPerMon_Standard.PDL csoBtnMode

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameCountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAHCountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAHCountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtAHCountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtALCountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtALCountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtALCountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTHCountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTHCountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTHCountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTHCountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTLCountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTLCountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtTLCountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWHCountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWHCountOh .Day sAHLim 2 6 Day s-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWLCountOh .HrsAHLim 2 6 Hours-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWLCountOh .MinsAHLim 2 6 Minutes-High Alarm Limit ~PG_CountOh_Limit.PDL csoIOAnaDtWLCountOh .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountOh_Parameter.PDL csoBtnMaintenanceCountOh .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountOh_Parameter.PDL csoBtnMaintenanceCountOh .PresetEn Preset 2 6 Preset Enable ~PG_CountOh_Parameter.PDL csoBtnPresetCountOh .PresetTime 2 6 Preset Time v alue[Sec]. ~PG_CountOh_Parameter.PDL csoIOAnaPresetDay sCountOh .PresetTime 2 6 Preset Time v alue[Sec]. ~PG_CountOh_Parameter.PDL csoIOAnaPresetHoursCountOh .PresetTime 2 6 Preset Time v alue[Sec]. ~PG_CountOh_Parameter.PDL csoIOAnaPresetMinsCountOh .UpOp Up 1 5 1 = Up Counter ~PG_CountOh_Standard.PDL csoBtnCommand

Page 16: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

CountOh .DnOp Down 1 5 1 = Down Counter ~PG_CountOh_Standard.PDL csoBtnCommandCountOh .Of f Op Of f 1 5 Counter Of f by Operator: 1 = Counter is Of f ~PG_CountOh_Standard.PDL csoBtnCommandCountOh .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_CountOh_Standard.PDL csoBtnModeCountOh .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_CountOh_Standard.PDL csoBtnModeCountOh .Day s 2 6 Operating Day s ~PG_CountOh_Standard.PDL csoIOAnaDay sCountOh .Hours 2 6 Operating Hours ~PG_CountOh_Standard.PDL csoIOAnaHoursCountOh .Minutes 2 6 Operating Minutes ~PG_CountOh_Standard.PDL csoIOAnaMins

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameCountScL .OutAH_Lim 2 6 Out Value High Alarm Limit ~PG_CountScL_Limit.PDL csoIOAnaAHCountScL .OutAL_Lim 2 6 Out Value Low Alarm Limit ~PG_CountScL_Limit.PDL csoIOAnaALCountScL .OutTH_Lim 2 6 Out Value High Tolerance Limit ~PG_CountScL_Limit.PDL csoIOAnaTHCountScL .OutTL_Lim 2 6 Out Value Low Tolerance Limit ~PG_CountScL_Limit.PDL csoIOAnaTLCountScL .OutWH_Lim 2 6 Out Value High Warning Limit ~PG_CountScL_Limit.PDL csoIOAnaWHCountScL .OutWL_Lim 2 6 Out Value Low Warning Limit ~PG_CountScL_Limit.PDL csoIOAnaWLCountScL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountScL_Parameter.PDL csoBtnMaintenanceCountScL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_CountScL_Parameter.PDL csoBtnMaintenanceCountScL .PresetEn Preset 2 6 Preset Out ~PG_CountScL_Parameter.PDL csoBtnPresetCountScL .PresetVal 2 6 Preset Value ~PG_CountScL_Parameter.PDL csoIOAnaPresetValCountScL .UpOp Up 1 5 1 = Up Counter ~PG_CountScL_Standard.PDL csoBtnCommandCountScL .DnOp Down 1 5 1 = Down Counter ~PG_CountScL_Standard.PDL csoBtnCommandCountScL .Of f Op Of f 1 5 Counter Of f by Operator: 1 = Counter is Of f ~PG_CountScL_Standard.PDL csoBtnCommandCountScL .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_CountScL_Standard.PDL csoBtnModeCountScL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_CountScL_Standard.PDL csoBtnModeCountScL .Out 1 5 Counter Value ~PG_CountScL_Standard.PDL csoIOAnaOut

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameDoseL .PV_AH_Lim 2 6 PV - Flow rate high alarm limit (coarse dose) ~PG_DoseL_Limit.PDL csoIOAnaAHCoarseDoseL .CR_AH_Lim 2 6 Creep f low - High alarm limit ~PG_DoseL_Limit.PDL csoIOAnaAHCreepDoseL .PV_AH2_Lim 2 6 PV - Flow rate high alarm limit (f ine dose) ~PG_DoseL_Limit.PDL csoIOAnaAHFineDoseL .PV_AL_Lim 2 6 PV - Flow rate low alarm limit (coarse dose) ~PG_DoseL_Limit.PDL csoIOAnaALCoarseDoseL .PV_AL2_Lim 2 6 PV - Flow rate low alarm limit (f ine dose) ~PG_DoseL_Limit.PDL csoIOAnaALFineDoseL .PV_Hy st 2 6 PV - Flow rate hy steresis (coarse dose) ~PG_DoseL_Limit.PDL csoIOAnaHy sCoarseDoseL .CR_Hy st 2 6 Creep f low - Hy steresis ~PG_DoseL_Limit.PDL csoIOAnaHy sCreepDoseL .PV_Hy st2 2 6 PV - Flow rate hy steresis (f ine dose) ~PG_DoseL_Limit.PDL csoIOAnaHy sFineDoseL .DQ_AH_Tol 2 6 Quantity high alarm tolerance band (ov erdose) ~PG_DoseL_Limit.PDL csoIOAnaOv erdosDoseL .DQ_AL_Tol 2 6 Quantity lower alarm tolerance band (underdose) ~PG_DoseL_Limit.PDL csoIOAnaUnderdoseDoseL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_DoseL_Parameter.PDL csoBtnMaintDoseL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_DoseL_Parameter.PDL csoBtnMaintDoseL .SimOn On 3 1100 Simulation on/of f ~PG_DoseL_Parameter.PDL csoBtnSimuDoseL .SimOn Of f 3 1100 Simulation on/of f ~PG_DoseL_Parameter.PDL csoBtnSimuDoseL .DribbCor On 2 6 Dribbling Correction On/Of f ~PG_DoseL_Parameter.PDL csoChkBoxAutoOnDoseL .DribbCor Of f 2 6 Dribbling Correction On/Of f ~PG_DoseL_Parameter.PDL csoChkBoxAutoOnDoseL .SP_TrkExt On 2 6 1: Internal SPs tracks to external SPs in external mode ~PG_DoseL_Parameter.PDL csoChkBoxSPTrkDoseL .SP_TrkExt Of f 2 6 1: Internal SPs tracks to external SPs in external mode ~PG_DoseL_Parameter.PDL csoChkBoxSPTrkDoseL .DribbMax 2 6 Dribble Value Maximum ~PG_DoseL_Parameter.PDL csoIOAnaDribbMax

Page 17: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

DoseL .RelaxTime 2 6 Relax Time [s] ~PG_DoseL_Parameter.PDL csoIOAnaDribbTimeDoseL .DribbIn 2 6 Dribble Value ~PG_DoseL_Parameter.PDL csoIOAnaDribbValueDoseL .P_DoseTime 2 6 Post dose time [s] ~PG_DoseL_Parameter.PDL csoIOAnaPostTimeDoseL .DCF 2 6 Dribbling Correction Factor [%] ~PG_DoseL_Parameter.PDL csoIOAnaWeightFactDoseL .SP_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaHCoarseDoseL .SP2_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaHFineDoseL .SP_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaLCoarseDoseL .SP2_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaLFineDoseL .SimPV 1 5 PV Simulation Value, tracks when not in simulation ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaPVDoseL .SP_Int 1 5 Flow rate internal setpoint ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaSPCoarseDoseL .SP2_Int 1 5 Flow rate internal setpoint (f ine dose) ~PG_DoseL_Setpoint_Flow.PDL csoIOAnaSPFineDoseL .DQ2_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaHFineDoseL .DQ_HiLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaHTotalDoseL .DQ2_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaLFineDoseL .DQ_LoLim#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaLTotalDoseL .DQ1_SP#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPCoarseDoseL .DQ2_SP#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPFineDoseL .DQ2_Int 1 5 Quantity setpoint f actor internal (f ine dose) ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPFineFactorDoseL .DQ_SP#Value 2 6 Value ~PG_DoseL_Setpoint_Quantity .PDL csoIOAnaSPTotalDoseL .StartMan Start 1 5 1=Start: Start Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommandDoseL .ContMan Continue 1 5 1=Continue: Continue Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommandDoseL .PauseMan Pause 1 5 1=Pause: Pause Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommandDoseL .CancelMan Cancel 1 5 1=Cancel: Cancel Command in Manual Mode ~PG_DoseL_Standard.PDL csoBtnCommandDoseL .AutModOp Automatic 1 5 1=Auto mode: auto mode by operator ~PG_DoseL_Standard.PDL csoBtnModeDoseL .ManModOp Manual 1 5 1=Manual mode: manual mode by operator ~PG_DoseL_Standard.PDL csoBtnModeDoseL .LocalOp Local 1 5 1=Local Mode: Local operation by operator ~PG_DoseL_Standard.PDL csoBtnModeDoseL .OosOp Out of serv ice 2 6 1=Oos mode: Oos mode by operator ~PG_DoseL_Standard.PDL csoBtnModeDoseL .RstOp Reset 1 5 Operator reset signal ~PG_DoseL_Standard.PDL csoBtnResetDoseL .RstDQ_Op Reset 1 5 Operator signal to reset dosed quantity ~PG_DoseL_Standard.PDL csoBtnResetQuantityDoseL .U_AckOp Acknowledge 1 5 Underdose acknowledge operator ~PG_DoseL_Standard.PDL csoBtnResetUnderdoseDoseL .SP_ExtOp External 1 5 Operator Input to Select External Setpoint ~PG_DoseL_Standard.PDL csoBtnSPModeDoseL .SP_IntOp Internal 1 5 Operator Input to Select Internal Setpoint ~PG_DoseL_Standard.PDL csoBtnSPModeDoseL .SimDQ 1 5 Dosing quantity simulation v alue, tracks when not in simulation ~PG_DoseL_Standard.PDL csoIOAnaPVDoseL .DQ_Int 1 5 Quantity setpoint internal ~PG_DoseL_Standard.PDL csoIOAnaSP

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameFmCont .PV_AH_Lim 2 6 PV alarm high limit ~PG_FmCont_Limit.PDL csoIOAnaAHFmCont .PV_AL_Lim 2 6 PV alarm low limit ~PG_FmCont_Limit.PDL csoIOAnaALFmCont .ER_AH_Lim 2 6 ER alarm high limit ~PG_FmCont_Limit.PDL csoIOAnaErrHFmCont .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_FmCont_Limit.PDL csoIOAnaErrHy sFmCont .ER_AL_Lim 2 6 ER alarm low limit ~PG_FmCont_Limit.PDL csoIOAnaErrLFmCont .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_FmCont_Limit.PDL csoIOAnaHy sFmCont .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_FmCont_Limit.PDL csoIOAnaMVHFmCont .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_FmCont_Limit.PDL csoIOAnaMVLFmCont .RbkWH_Lim 2 6 Rbk - High Warning Limit ~PG_FmCont_Limit.PDL csoIOAnaRbkHFmCont .RbkHy st 2 6 Rbk - Hy steresis ~PG_FmCont_Limit.PDL csoIOAnaRbkHy s

Page 18: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

FmCont .RbkWL_Lim 2 6 Rbk - Low Warning Limit ~PG_FmCont_Limit.PDL csoIOAnaRbkLFmCont .SP_InHiLim 2 6 High limit of internal setpoint ~PG_FmCont_Limit.PDL csoIOAnaSPHFmCont .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_FmCont_Limit.PDL csoIOAnaSPLFmCont .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_FmCont_Limit.PDL csoIOAnaTHFmCont .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_FmCont_Limit.PDL csoIOAnaTLFmCont .PV_WH_Lim 2 6 PV warning high limit ~PG_FmCont_Limit.PDL csoIOAnaWHFmCont .PV_WL_Lim 2 6 PV warning low limit ~PG_FmCont_Limit.PDL csoIOAnaWLFmCont .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_FmCont_Parameter.PDL csoBtnMaintFmCont .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_FmCont_Parameter.PDL csoBtnMaintFmCont .SimOn On 3 1100 1 = Simulation activ ated ~PG_FmCont_Parameter.PDL csoBtnSimuFmCont .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_FmCont_Parameter.PDL csoBtnSimuFmCont .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmCont_Parameter.PDL csoChkBoxPVTrkFmCont .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmCont_Parameter.PDL csoChkBoxPVTrkFmCont .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmCont_Parameter.PDL csoChkBoxSPTrkFmCont .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmCont_Parameter.PDL csoChkBoxSPTrkFmCont .BreakTime 2 6 Minimum Break Time [s] ~PG_FmCont_Parameter.PDL csoIOAnaBreakTFmCont .DeadBand 2 6 Width of deadband ~PG_FmCont_Parameter.PDL csoIOAnaDeadBFmCont .Gain#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaGainFmCont .Dif f Gain#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaGainDFmCont .MotorTime 2 6 Motor Actuating Time [s] ~PG_FmCont_Parameter.PDL csoIOAnaMotorTFmCont .PulseTime 2 6 Minimum Pulse Time [s] ~PG_FmCont_Parameter.PDL csoIOAnaPulseTFmCont .TD#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaTDFmCont .TI#Value 2 6 Value ~PG_FmCont_Parameter.PDL csoIOAnaTIFmCont .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmCont_Ramp.PDL csoBtnRampFmCont .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmCont_Ramp.PDL csoBtnRampFmCont .SP_RmpModTime Duration 1 5 1= Use time (SP_RmpTime) f or ramp, 0= Use rates SP_UpRaLim, SP_DnRaLim ~PG_FmCont_Ramp.PDL csoBtnRampModeFmCont .SP_RmpModTime Gradient 1 5 1= Use time (SP_RmpTime) f or ramp, 0= Use rates SP_UpRaLim, SP_DnRaLim ~PG_FmCont_Ramp.PDL csoBtnRampModeFmCont .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmCont_Ramp.PDL csoChkBoxGrdFmCont .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmCont_Ramp.PDL csoChkBoxGrdFmCont .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_FmCont_Ramp.PDL csoIOAnaDurationFmCont .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_FmCont_Ramp.PDL csoIOAnaGrdDownFmCont .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_FmCont_Ramp.PDL csoIOAnaGrdUpFmCont .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_FmCont_Ramp.PDL csoIOAnaTargetSPFmCont .OpenOp Open 1 5 Manual Signal Open by Operation ~PG_FmCont_Standard.PDL csoBtnManipSignalsFmCont .CloseOp Close 1 5 Manual Signal Close by Operation ~PG_FmCont_Standard.PDL csoBtnManipSignalsFmCont .StopOp Stop 1 5 Manual Signal Stop by Operation ~PG_FmCont_Standard.PDL csoBtnManipSignalsFmCont .AutModOp Automatic 1 5 1 = Automatic mode by operator (controlled by ModLiOp = 0) ~PG_FmCont_Standard.PDL csoBtnModeFmCont .ManModOp Manual 1 5 1 = Manual mode by operator (controlled by ModLiOp = 0) ~PG_FmCont_Standard.PDL csoBtnModeFmCont .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_FmCont_Standard.PDL csoBtnModeFmCont .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_FmCont_Standard.PDL csoBtnModeFmCont .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_FmCont_Standard.PDL csoBtnSPModeFmCont .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_FmCont_Standard.PDL csoBtnSPModeFmCont .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_FmCont_Standard.PDL csoIOAnaMVFmCont .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_FmCont_Standard.PDL csoIOAnaPVFmCont .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_FmCont_Standard.PDL csoIOAnaRbkFmCont .SP_Int 1 5 Internal setpoint f or operation ~PG_FmCont_Standard.PDL csoIOAnaSP

Page 19: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameFmTemp .PV_AH_Lim 2 6 PV alarm high limit ~PG_FmTemp_Limit.PDL csoIOAnaAHFmTemp .PV_AL_Lim 2 6 PV alarm low limit ~PG_FmTemp_Limit.PDL csoIOAnaALFmTemp .ER_AH_Lim 2 6 ER alarm high limit ~PG_FmTemp_Limit.PDL csoIOAnaErrHFmTemp .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_FmTemp_Limit.PDL csoIOAnaErrHy sFmTemp .ER_AL_Lim 2 6 ER alarm low limit ~PG_FmTemp_Limit.PDL csoIOAnaErrLFmTemp .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_FmTemp_Limit.PDL csoIOAnaHy sFmTemp .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_FmTemp_Limit.PDL csoIOAnaMVHFmTemp .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_FmTemp_Limit.PDL csoIOAnaMVLFmTemp .RbkWH_Lim 2 6 Rbk - High Warning Limit ~PG_FmTemp_Limit.PDL csoIOAnaRbkHFmTemp .RbkHy st 2 6 Rbk - Hy steresis ~PG_FmTemp_Limit.PDL csoIOAnaRbkHy sFmTemp .RbkWL_Lim 2 6 Rbk - Low Warning Limit ~PG_FmTemp_Limit.PDL csoIOAnaRbkLFmTemp .SP_InHiLim 2 6 High limit of internal setpoint ~PG_FmTemp_Limit.PDL csoIOAnaSPHFmTemp .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_FmTemp_Limit.PDL csoIOAnaSPLFmTemp .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_FmTemp_Limit.PDL csoIOAnaTHFmTemp .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_FmTemp_Limit.PDL csoIOAnaTLFmTemp .PV_WH_Lim 2 6 PV warning high limit ~PG_FmTemp_Limit.PDL csoIOAnaWHFmTemp .PV_WL_Lim 2 6 PV warning low limit ~PG_FmTemp_Limit.PDL csoIOAnaWLFmTemp .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_FmTemp_Parameter.PDL csoBtnMaintFmTemp .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_FmTemp_Parameter.PDL csoBtnMaintFmTemp .SimOn On 3 1100 1 = Simulation activ ated ~PG_FmTemp_Parameter.PDL csoBtnSimuFmTemp .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_FmTemp_Parameter.PDL csoBtnSimuFmTemp .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmTemp_Parameter.PDL csoChkBoxPVTrkFmTemp .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_FmTemp_Parameter.PDL csoChkBoxPVTrkFmTemp .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmTemp_Parameter.PDL csoChkBoxSPTrkFmTemp .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_FmTemp_Parameter.PDL csoChkBoxSPTrkFmTemp .BreakTime 2 6 Minimum Break Time [s] ~PG_FmTemp_Parameter.PDL csoIOAnaBreakTFmTemp .DeadBand 2 6 Width of deadband ~PG_FmTemp_Parameter.PDL csoIOAnaDeadBFmTemp .Gain#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaGainFmTemp .Dif f Gain#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaGainDFmTemp .MotorTime 2 6 Motor Actuating Time [s] ~PG_FmTemp_Parameter.PDL csoIOAnaMotorTFmTemp .PulseTime 2 6 Minimum Pulse Time [s] ~PG_FmTemp_Parameter.PDL csoIOAnaPulseTFmTemp .TD#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaTDFmTemp .TI#Value 2 6 Value ~PG_FmTemp_Parameter.PDL csoIOAnaTIFmTemp .ConZone 2 6 Control zone ~PG_FmTemp_Parameter.PDL csoIOAnaZoneCFmTemp .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmTemp_Ramp.PDL csoBtnRampFmTemp .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_FmTemp_Ramp.PDL csoBtnRampFmTemp .SP_RmpModTime Duration 1 5 1= Use time (SP_RmpTime) f or ramp, 0= Use rates SP_UpRaLim, SP_DnRaLim ~PG_FmTemp_Ramp.PDL csoBtnRampModeFmTemp .SP_RmpModTime Gradient 1 5 1= Use time (SP_RmpTime) f or ramp, 0= Use rates SP_UpRaLim, SP_DnRaLim ~PG_FmTemp_Ramp.PDL csoBtnRampModeFmTemp .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmTemp_Ramp.PDL csoChkBoxGrdFmTemp .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_FmTemp_Ramp.PDL csoChkBoxGrdFmTemp .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_FmTemp_Ramp.PDL csoIOAnaDurationFmTemp .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_FmTemp_Ramp.PDL csoIOAnaGrdDownFmTemp .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_FmTemp_Ramp.PDL csoIOAnaGrdUpFmTemp .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_FmTemp_Ramp.PDL csoIOAnaTargetSP

Page 20: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

FmTemp .OpenOp Open 1 5 Manual Signal Open by Operation ~PG_FmTemp_Standard.PDL csoBtnManipSignalsFmTemp .CloseOp Close 1 5 Manual Signal Close by Operation ~PG_FmTemp_Standard.PDL csoBtnManipSignalsFmTemp .StopOp Stop 1 5 Manual Signal Stop by Operation ~PG_FmTemp_Standard.PDL csoBtnManipSignalsFmTemp .AutModOp Automatic 1 5 1 = Automatic mode by operator (controlled by ModLiOp = 0) ~PG_FmTemp_Standard.PDL csoBtnModeFmTemp .ManModOp Manual 1 5 1 = Manual mode by operator (controlled by ModLiOp = 0) ~PG_FmTemp_Standard.PDL csoBtnModeFmTemp .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_FmTemp_Standard.PDL csoBtnModeFmTemp .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_FmTemp_Standard.PDL csoBtnModeFmTemp .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_FmTemp_Standard.PDL csoBtnSPModeFmTemp .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_FmTemp_Standard.PDL csoBtnSPModeFmTemp .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_FmTemp_Standard.PDL csoIOAnaMVFmTemp .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_FmTemp_Standard.PDL csoIOAnaPVFmTemp .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_FmTemp_Standard.PDL csoIOAnaRbkFmTemp .SP_Int 1 5 Internal setpoint f or operation ~PG_FmTemp_Standard.PDL csoIOAnaSP

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameGainSched .Gain1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGain1GainSched .Gain2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGain2GainSched .Gain3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGain3GainSched .GainOp#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaGainOpGainSched .TD_Op#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD_OpGainSched .TD1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD1GainSched .TD2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD2GainSched .TD3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTD3GainSched .TI_Op#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI_OpGainSched .TI1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI1GainSched .TI2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI2GainSched .TI3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaTI3GainSched .X1#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaX1GainSched .X2#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaX2GainSched .X3#Value 2 6 Value ~PG_GainSched_Parameter.PDL csoIOAnaX3GainSched .ManParOn#Value Automatic 1 5 Value ~PG_GainSched_Standard.PDL csoBtnModeGainSched .ManParOn#Value Manual 1 5 Value ~PG_GainSched_Standard.PDL csoBtnModeGainSched .GainOp#Value 2 6 Value ~PG_GainSched_Standard.PDL csoIOAnaGainGainSched .TD_Op#Value 2 6 Value ~PG_GainSched_Standard.PDL csoIOAnaTDGainSched .TI_Op#Value 2 6 Value ~PG_GainSched_Standard.PDL csoIOAnaTI

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameIntlk02 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk02_Standard.PDL csoBtnBy p1Intlk02 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk02_Standard.PDL csoBtnBy p1Intlk02 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk02_Standard.PDL csoBtnBy p2Intlk02 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk02_Standard.PDL csoBtnBy p2Intlk02 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk02_Standard.PDL csoBtnResetIntlk02 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk02_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameIntlk04 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk04_Standard.PDL csoBtnBy p1

Page 21: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

Intlk04 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk04_Standard.PDL csoBtnBy p1Intlk04 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk04_Standard.PDL csoBtnBy p2Intlk04 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk04_Standard.PDL csoBtnBy p2Intlk04 .By pIn03 Set 2 6 By pass In03 ~PG_Intlk04_Standard.PDL csoBtnBy p3Intlk04 .By pIn03 Reset 2 6 By pass In03 ~PG_Intlk04_Standard.PDL csoBtnBy p3Intlk04 .By pIn04 Set 2 6 By pass In04 ~PG_Intlk04_Standard.PDL csoBtnBy p4Intlk04 .By pIn04 Reset 2 6 By pass In04 ~PG_Intlk04_Standard.PDL csoBtnBy p4Intlk04 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk04_Standard.PDL csoBtnResetIntlk04 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk04_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameIntlk08 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk08_Standard.PDL csoBtnBy p1Intlk08 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk08_Standard.PDL csoBtnBy p1Intlk08 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk08_Standard.PDL csoBtnBy p2Intlk08 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk08_Standard.PDL csoBtnBy p2Intlk08 .By pIn03 Set 2 6 By pass In03 ~PG_Intlk08_Standard.PDL csoBtnBy p3Intlk08 .By pIn03 Reset 2 6 By pass In03 ~PG_Intlk08_Standard.PDL csoBtnBy p3Intlk08 .By pIn04 Set 2 6 By pass In04 ~PG_Intlk08_Standard.PDL csoBtnBy p4Intlk08 .By pIn04 Reset 2 6 By pass In04 ~PG_Intlk08_Standard.PDL csoBtnBy p4Intlk08 .By pIn05 Set 2 6 By pass In05 ~PG_Intlk08_Standard.PDL csoBtnBy p5Intlk08 .By pIn05 Reset 2 6 By pass In05 ~PG_Intlk08_Standard.PDL csoBtnBy p5Intlk08 .By pIn06 Set 2 6 By pass In06 ~PG_Intlk08_Standard.PDL csoBtnBy p6Intlk08 .By pIn06 Reset 2 6 By pass In06 ~PG_Intlk08_Standard.PDL csoBtnBy p6Intlk08 .By pIn07 Set 2 6 By pass In07 ~PG_Intlk08_Standard.PDL csoBtnBy p7Intlk08 .By pIn07 Reset 2 6 By pass In07 ~PG_Intlk08_Standard.PDL csoBtnBy p7Intlk08 .By pIn08 Set 2 6 By pass In08 ~PG_Intlk08_Standard.PDL csoBtnBy p8Intlk08 .By pIn08 Reset 2 6 By pass In08 ~PG_Intlk08_Standard.PDL csoBtnBy p8Intlk08 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk08_Standard.PDL csoBtnResetIntlk08 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk08_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameIntlk16 .By pIn09 Set 2 6 By pass In09 ~PG_Intlk16_Screen2.PDL csoBtnBy p1Intlk16 .By pIn09 Reset 2 6 By pass In09 ~PG_Intlk16_Screen2.PDL csoBtnBy p1Intlk16 .By pIn10 Set 2 6 By pass In10 ~PG_Intlk16_Screen2.PDL csoBtnBy p2Intlk16 .By pIn10 Reset 2 6 By pass In10 ~PG_Intlk16_Screen2.PDL csoBtnBy p2Intlk16 .By pIn11 Set 2 6 By pass In11 ~PG_Intlk16_Screen2.PDL csoBtnBy p3Intlk16 .By pIn11 Reset 2 6 By pass In11 ~PG_Intlk16_Screen2.PDL csoBtnBy p3Intlk16 .By pIn12 Set 2 6 By pass In12 ~PG_Intlk16_Screen2.PDL csoBtnBy p4Intlk16 .By pIn12 Reset 2 6 By pass In12 ~PG_Intlk16_Screen2.PDL csoBtnBy p4Intlk16 .By pIn13 Set 2 6 By pass In13 ~PG_Intlk16_Screen2.PDL csoBtnBy p5Intlk16 .By pIn13 Reset 2 6 By pass In13 ~PG_Intlk16_Screen2.PDL csoBtnBy p5Intlk16 .By pIn14 Set 2 6 By pass In14 ~PG_Intlk16_Screen2.PDL csoBtnBy p6Intlk16 .By pIn14 Reset 2 6 By pass In14 ~PG_Intlk16_Screen2.PDL csoBtnBy p6Intlk16 .By pIn15 Set 2 6 By pass In15 ~PG_Intlk16_Screen2.PDL csoBtnBy p7Intlk16 .By pIn15 Reset 2 6 By pass In15 ~PG_Intlk16_Screen2.PDL csoBtnBy p7Intlk16 .By pIn16 Set 2 6 By pass In16 ~PG_Intlk16_Screen2.PDL csoBtnBy p8

Page 22: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

Intlk16 .By pIn16 Reset 2 6 By pass In16 ~PG_Intlk16_Screen2.PDL csoBtnBy p8Intlk16 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk16_Screen2.PDL csoBtnResetIntlk16 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk16_Screen2.PDL csoBtnResetIntlk16 .By pIn01 Set 2 6 By pass In01 ~PG_Intlk16_Standard.PDL csoBtnBy p1Intlk16 .By pIn01 Reset 2 6 By pass In01 ~PG_Intlk16_Standard.PDL csoBtnBy p1Intlk16 .By pIn02 Set 2 6 By pass In02 ~PG_Intlk16_Standard.PDL csoBtnBy p2Intlk16 .By pIn02 Reset 2 6 By pass In02 ~PG_Intlk16_Standard.PDL csoBtnBy p2Intlk16 .By pIn03 Set 2 6 By pass In03 ~PG_Intlk16_Standard.PDL csoBtnBy p3Intlk16 .By pIn03 Reset 2 6 By pass In03 ~PG_Intlk16_Standard.PDL csoBtnBy p3Intlk16 .By pIn04 Set 2 6 By pass In04 ~PG_Intlk16_Standard.PDL csoBtnBy p4Intlk16 .By pIn04 Reset 2 6 By pass In04 ~PG_Intlk16_Standard.PDL csoBtnBy p4Intlk16 .By pIn05 Set 2 6 By pass In05 ~PG_Intlk16_Standard.PDL csoBtnBy p5Intlk16 .By pIn05 Reset 2 6 By pass In05 ~PG_Intlk16_Standard.PDL csoBtnBy p5Intlk16 .By pIn06 Set 2 6 By pass In06 ~PG_Intlk16_Standard.PDL csoBtnBy p6Intlk16 .By pIn06 Reset 2 6 By pass In06 ~PG_Intlk16_Standard.PDL csoBtnBy p6Intlk16 .By pIn07 Set 2 6 By pass In07 ~PG_Intlk16_Standard.PDL csoBtnBy p7Intlk16 .By pIn07 Reset 2 6 By pass In07 ~PG_Intlk16_Standard.PDL csoBtnBy p7Intlk16 .By pIn08 Set 2 6 By pass In08 ~PG_Intlk16_Standard.PDL csoBtnBy p8Intlk16 .By pIn08 Reset 2 6 By pass In08 ~PG_Intlk16_Standard.PDL csoBtnBy p8Intlk16 .RstBy pOp By passes 2 6 Reset FirstIn (operator) ~PG_Intlk16_Standard.PDL csoBtnResetIntlk16 .RstOp Initial signal 1 5 Reset FirstIn (operator) ~PG_Intlk16_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameModPreCon .SP1DeadBand 2 6 Radius (deadband) f or range control of CV1 ~PG_ModPreCon_Channel1.PDL csoIOAnaDeadBModPreCon .MV1RaLim 2 6 Manipulated v ariable 1 rate limit per sample ~PG_ModPreCon_Channel1.PDL csoIOAnaGradModPreCon .MV1HiLim 2 6 Manipulated v ariable 1 high limit ~PG_ModPreCon_Channel1.PDL csoIOAnaMVHModPreCon .MV1LoLim 2 6 Manipulated v ariable 1 low limit ~PG_ModPreCon_Channel1.PDL csoIOAnaMVLModPreCon .PreFilt1 2 6 Setpoint 1 pref ilter settling time [s] ~PG_ModPreCon_Channel1.PDL csoIOAnaPref ilModPreCon .SP1HiLim 2 6 High limit f or operator setpoint 1 ~PG_ModPreCon_Channel1.PDL csoIOAnaSPHModPreCon .SP1LoLim 2 6 Low limit f or operator setpoint 1 ~PG_ModPreCon_Channel1.PDL csoIOAnaSPLModPreCon .SP2DeadBand 2 6 Radius (deadband) f or range control of CV2 ~PG_ModPreCon_Channel2.PDL csoIOAnaDeadBModPreCon .MV2RaLim 2 6 Manipulated v ariable 2 rate limit per sample ~PG_ModPreCon_Channel2.PDL csoIOAnaGradModPreCon .MV2HiLim 2 6 Manipulated v ariable 2 high limit ~PG_ModPreCon_Channel2.PDL csoIOAnaMVHModPreCon .MV2LoLim 2 6 Manipulated v ariable 2 low limit ~PG_ModPreCon_Channel2.PDL csoIOAnaMVLModPreCon .PreFilt2 2 6 Setpoint 2 pref ilter settling time [s] ~PG_ModPreCon_Channel2.PDL csoIOAnaPref ilModPreCon .SP2HiLim 2 6 High limit f or operator setpoint 2 ~PG_ModPreCon_Channel2.PDL csoIOAnaSPHModPreCon .SP2LoLim 2 6 Low limit f or operator setpoint 2 ~PG_ModPreCon_Channel2.PDL csoIOAnaSPLModPreCon .SP3DeadBand 2 6 Radius (deadband) f or range control of CV3 ~PG_ModPreCon_Channel3.PDL csoIOAnaDeadBModPreCon .MV3RaLim 2 6 Manipulated v ariable 3 rate limit per sample ~PG_ModPreCon_Channel3.PDL csoIOAnaGradModPreCon .MV3HiLim 2 6 Manipulated v ariable 3 high limit ~PG_ModPreCon_Channel3.PDL csoIOAnaMVHModPreCon .MV3LoLim 2 6 Manipulated v ariable 3 low limit ~PG_ModPreCon_Channel3.PDL csoIOAnaMVLModPreCon .PreFilt3 2 6 Setpoint 3 pref ilter settling time [s] ~PG_ModPreCon_Channel3.PDL csoIOAnaPref ilModPreCon .SP3HiLim 2 6 High limit f or operator setpoint 3 ~PG_ModPreCon_Channel3.PDL csoIOAnaSPHModPreCon .SP3LoLim 2 6 Low limit f or operator setpoint 3 ~PG_ModPreCon_Channel3.PDL csoIOAnaSPLModPreCon .SP4DeadBand 2 6 Radius (deadband) f or range control of CV4 ~PG_ModPreCon_Channel4.PDL csoIOAnaDeadBModPreCon .MV4RaLim 2 6 Manipulated v ariable 4 rate limit per sample ~PG_ModPreCon_Channel4.PDL csoIOAnaGrad

Page 23: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

ModPreCon .MV4HiLim 2 6 Manipulated v ariable 4 high limit ~PG_ModPreCon_Channel4.PDL csoIOAnaMVHModPreCon .MV4LoLim 2 6 Manipulated v ariable 4 low limit ~PG_ModPreCon_Channel4.PDL csoIOAnaMVLModPreCon .PreFilt4 2 6 Setpoint 4 pref ilter settling time [s] ~PG_ModPreCon_Channel4.PDL csoIOAnaPref ilModPreCon .SP4HiLim 2 6 High limit f or operator setpoint 4 ~PG_ModPreCon_Channel4.PDL csoIOAnaSPHModPreCon .SP4LoLim 2 6 Low limit f or operator setpoint 4 ~PG_ModPreCon_Channel4.PDL csoIOAnaSPLModPreCon .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1= MS release requirement ~PG_ModPreCon_Parameter.PDL csoBtnMaintModPreCon .MS_RelOp No 3 1100 Operator input f or MS Release, 1= MS release requirement ~PG_ModPreCon_Parameter.PDL csoBtnMaintModPreCon .SimOn On 3 1100 Simulation On/Of f ~PG_ModPreCon_Parameter.PDL csoBtnSimuModPreCon .SimOn Of f 3 1100 Simulation On/Of f ~PG_ModPreCon_Parameter.PDL csoBtnSimuModPreCon .DV_On On 2 6 1 = Activ ate disturbance f eedf orward of DV1 ~PG_ModPreCon_Parameter.PDL csoChkBoxDisturbModPreCon .DV_On Of f 2 6 1 = Activ ate disturbance f eedf orward of DV1 ~PG_ModPreCon_Parameter.PDL csoChkBoxDisturbModPreCon .SP_TrkCV On 2 6 SPs track CVs in manual mode and in tracking mode ~PG_ModPreCon_Parameter.PDL csoChkBoxPVTrkModPreCon .SP_TrkCV Of f 2 6 SPs track CVs in manual mode and in tracking mode ~PG_ModPreCon_Parameter.PDL csoChkBoxPVTrkModPreCon .DV1#Value 2 6 Value ~PG_ModPreCon_Parameter.PDL csoIOAnaDisturbModPreCon .AutModOp Automatic 1 5 Operator input f or automatic mode, 1= Automatic ~PG_ModPreCon_Standard.PDL csoBtnModeModPreCon .ManModOp Manual 1 5 Operator input f or manual mode, 1= Manual ~PG_ModPreCon_Standard.PDL csoBtnModeModPreCon .OosOp Out of serv ice 2 6 Operator input f or Out Of Serv ice, 1= Out Of Serv ice ~PG_ModPreCon_Standard.PDL csoBtnModeModPreCon .SimCV1 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV1ModPreCon .SimCV2 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV2ModPreCon .SimCV3 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV3ModPreCon .SimCV4 1 5 CV Simulation Value, tracks when not in simulation ~PG_ModPreCon_Standard.PDL csoIOAnaCV4ModPreCon .MV1Man 1 5 Manual setting of manipulated v ariable MV1 ~PG_ModPreCon_Standard.PDL csoIOAnaMV1ModPreCon .MV2Man 1 5 Manual setting of manipulated v ariable MV2 ~PG_ModPreCon_Standard.PDL csoIOAnaMV2ModPreCon .MV3Man 1 5 Manual setting of manipulated v ariable MV3 ~PG_ModPreCon_Standard.PDL csoIOAnaMV3ModPreCon .MV4Man 1 5 Manual setting of manipulated v ariable MV4 ~PG_ModPreCon_Standard.PDL csoIOAnaMV4ModPreCon .SP1#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP1ModPreCon .SP2#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP2ModPreCon .SP3#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP3ModPreCon .SP4#Value 1 5 Value ~PG_ModPreCon_Standard.PDL csoIOAnaSP4

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameMonAnL .PV_AH_Lim 2 6 PV - High Alarm Limit ~PG_MonAnL_Limit.PDL csoIOAnaAHMonAnL .PV_AL_Lim 2 6 PV - Low Alarm Limit ~PG_MonAnL_Limit.PDL csoIOAnaALMonAnL .PV_Hy st 2 6 PV - Alarm Hy steresis ~PG_MonAnL_Limit.PDL csoIOAnaHy sMonAnL .PV_TH_Lim 2 6 PV - High Tolerance Limit ~PG_MonAnL_Limit.PDL csoIOAnaTHMonAnL .PV_TL_Lim 2 6 PV - Low Tolerance Limit ~PG_MonAnL_Limit.PDL csoIOAnaTLMonAnL .PV_WH_Lim 2 6 PV - High Warning Limit ~PG_MonAnL_Limit.PDL csoIOAnaWHMonAnL .PV_WL_Lim 2 6 PV - Low Warning Limit ~PG_MonAnL_Limit.PDL csoIOAnaWLMonAnL .GradLLim 2 6 Low alarm limit f or positiv e and negativ e gradient ~PG_MonAnL_Limit.PDL csoIOXAnaGAMonAnL .GradHUpLim 2 6 High alarm limit f or positiv e gradient ~PG_MonAnL_Limit.PDL csoIOXAnaGHMonAnL .GradHDnLim 2 6 High alarm limit f or negativ e gradient ~PG_MonAnL_Limit.PDL csoIOXAnaGLMonAnL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonAnL_Parameter.PDL csoBtnMaintenanceMonAnL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonAnL_Parameter.PDL csoBtnMaintenanceMonAnL .SimOn On 3 1100 Simulation On/Of f ~PG_MonAnL_Parameter.PDL csoBtnSimMonAnL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MonAnL_Parameter.PDL csoBtnSimMonAnL .DeadBand 2 6 Dead band width ~PG_MonAnL_Parameter.PDL csoIOAnaDeadB

Page 24: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

MonAnL .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_MonAnL_Standard.PDL csoBtnModeMonAnL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MonAnL_Standard.PDL csoBtnModeMonAnL .RstOp Reset 1 5 Reset Peak Values ~PG_MonAnL_Standard.PDL csoBtnResetMonAnL .SimPV 1 5 Simulation Value ~PG_MonAnL_Standard.PDL csoIOAnaPV

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameMonAnS .PV_AH_Lim 2 6 PV - High Alarm Limit ~PG_MonAnS_Limit.PDL csoIOAnaAHMonAnS .PV_AL_Lim 2 6 PV - Low Alarm Limit ~PG_MonAnS_Limit.PDL csoIOAnaALMonAnS .PV_Hy st 2 6 PV - Alarm Hy steresis ~PG_MonAnS_Limit.PDL csoIOAnaHy sMonAnS .PV_WH_Lim 2 6 PV - High Warning Limit ~PG_MonAnS_Limit.PDL csoIOAnaWHMonAnS .PV_WL_Lim 2 6 PV - Low Warning Limit ~PG_MonAnS_Limit.PDL csoIOAnaWLMonAnS .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonAnS_Parameter.PDL csoBtnMaintenanceMonAnS .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonAnS_Parameter.PDL csoBtnMaintenanceMonAnS .SimOn On 3 1100 Simulation On/Of f ~PG_MonAnS_Parameter.PDL csoBtnSimMonAnS .SimOn Of f 3 1100 Simulation On/Of f ~PG_MonAnS_Parameter.PDL csoBtnSimMonAnS .DeadBand 2 6 Dead band width ~PG_MonAnS_Parameter.PDL csoIOAnaDeadBMonAnS .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_MonAnS_Standard.PDL csoBtnModeMonAnS .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MonAnS_Standard.PDL csoBtnModeMonAnS .SimPV 1 5 Simulation Value ~PG_MonAnS_Standard.PDL csoIOAnaPV

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameMonDi08 .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonDi08_Parameter.PDL csoBtnMaintenanceMonDi08 .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonDi08_Parameter.PDL csoBtnMaintenanceMonDi08 .Flut1TmIn 2 6 Fluttering Time [s] ~PG_MonDi08_Parameter.PDL csoIOAnaFlutTm1MonDi08 .Flut2TmIn 2 6 Fluttering Time [s] ~PG_MonDi08_Parameter.PDL csoIOAnaFlutTm2MonDi08 .Flut3TmIn 2 6 Fluttering Time [s] ~PG_MonDi08_Parameter.PDL csoIOAnaFlutTm3MonDi08 .Flut4TmIn 2 6 Fluttering Time [s] ~PG_MonDi08_Parameter.PDL csoIOAnaFlutTm4MonDi08 .Flut5TmIn 2 6 Fluttering Time [s] ~PG_MonDi08_Parameter.PDL csoIOAnaFlutTm5MonDi08 .Flut6TmIn 2 6 Fluttering Time [s] ~PG_MonDi08_Parameter.PDL csoIOAnaFlutTm6MonDi08 .Flut7TmIn 2 6 Fluttering Time [s] ~PG_MonDi08_Parameter.PDL csoIOAnaFlutTm7MonDi08 .Flut8TmIn 2 6 Fluttering Time [s] ~PG_MonDi08_Parameter.PDL csoIOAnaFlutTm8MonDi08 .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_MonDi08_Standard.PDL csoBtnModeMonDi08 .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MonDi08_Standard.PDL csoBtnMode

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameMonDiL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonDiL_Parameter.PDL csoBtnMaintenanceMonDiL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonDiL_Parameter.PDL csoBtnMaintenanceMonDiL .SimOn On 3 1100 Simulation On/Of f ~PG_MonDiL_Parameter.PDL csoBtnSimMonDiL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MonDiL_Parameter.PDL csoBtnSimMonDiL .Out_DC 2 6 Out Delay Time Coming [s] ~PG_MonDiL_Parameter.PDL csoIOAnaControlMonMonDiL .FlutFactor 2 6 Fluttering Factor ~PG_MonDiL_Parameter.PDL csoIOAnaFlutFactorMonDiL .FlutTmIn 2 6 Flutter Suppression Time [s] ~PG_MonDiL_Parameter.PDL csoIOAnaFlutTimeMonDiL .Out_DG 2 6 Out Delay Time Going [s] ~PG_MonDiL_Parameter.PDL csoIOAnaRuntimeMonMonDiL .SimIn Activ e 1 5 Simulation Value ~PG_MonDiL_Standard.PDL csoBtnCommandMonDiL .SimIn Inactiv e 1 5 Simulation Value ~PG_MonDiL_Standard.PDL csoBtnCommandMonDiL .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_MonDiL_Standard.PDL csoBtnMode

Page 25: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

MonDiL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MonDiL_Standard.PDL csoBtnMode

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameMonDiS .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonDiS_Parameter.PDL csoBtnMaintenanceMonDiS .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MonDiS_Parameter.PDL csoBtnMaintenanceMonDiS .SimOn On 3 1100 Simulation On/Of f ~PG_MonDiS_Parameter.PDL csoBtnSimMonDiS .SimOn Of f 3 1100 Simulation On/Of f ~PG_MonDiS_Parameter.PDL csoBtnSimMonDiS .Out_DC 2 6 Out Delay Time Coming [s] ~PG_MonDiS_Parameter.PDL csoIOAnaControlMonMonDiS .SimIn Activ e 1 5 Simulation Value ~PG_MonDiS_Standard.PDL csoBtnCommandMonDiS .SimIn Inactiv e 1 5 Simulation Value ~PG_MonDiS_Standard.PDL csoBtnCommandMonDiS .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_MonDiS_Standard.PDL csoBtnModeMonDiS .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MonDiS_Standard.PDL csoBtnMode

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameMotL .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_MotL_Limit.PDL csoIOAnaAHMotL .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_MotL_Limit.PDL csoIOAnaALMotL .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_MotL_Limit.PDL csoIOAnaAVMotL .AV_Hy st 2 6 AV - Hy steresis ~PG_MotL_Limit.PDL csoIOAnaHy sMotL .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_MotL_Limit.PDL csoIOAnaTHMotL .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_MotL_Limit.PDL csoIOAnaTLMotL .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_MotL_Limit.PDL csoIOAnaWHMotL .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_MotL_Limit.PDL csoIOAnaWLMotL .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotL_Parameter.PDL chkMonitorMotL .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotL_Parameter.PDL chkMonitorMotL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotL_Parameter.PDL csoBtnMaintenanceMotL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotL_Parameter.PDL csoBtnMaintenanceMotL .SimOn On 3 1100 Simulation On/Of f ~PG_MotL_Parameter.PDL csoBtnSimMotL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotL_Parameter.PDL csoBtnSimMotL .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotL_Parameter.PDL csoIOAnaDy nMonTimeMotL .MonTiStatic 2 6 Monitoring Time of Feedback [s] ~PG_MotL_Parameter.PDL csoIOAnaStaMonTimeMotL .StartMan Start 1 5 1=Start: Start Command in Manual Mode ~PG_MotL_Standard.PDL csoBtnCommandMotL .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotL_Standard.PDL csoBtnCommandMotL .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_MotL_Standard.PDL csoBtnCommandMotL .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotL_Standard.PDL csoBtnModeMotL .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotL_Standard.PDL csoBtnModeMotL .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_MotL_Standard.PDL csoBtnModeMotL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotL_Standard.PDL csoBtnModeMotL .RstOp Reset 1 5 Operator Reset Signal ~PG_MotL_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameMotRev L .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_MotRev L_Limit.PDL csoIOAnaAHMotRev L .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_MotRev L_Limit.PDL csoIOAnaALMotRev L .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_MotRev L_Limit.PDL csoIOAnaAVMotRev L .AV_Hy st 2 6 AV - Hy steresis ~PG_MotRev L_Limit.PDL csoIOAnaHy sMotRev L .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_MotRev L_Limit.PDL csoIOAnaTHMotRev L .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_MotRev L_Limit.PDL csoIOAnaTL

Page 26: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

MotRev L .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_MotRev L_Limit.PDL csoIOAnaWHMotRev L .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_MotRev L_Limit.PDL csoIOAnaWLMotRev L .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotRev L_Parameter.PDL chkMonitorMotRev L .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotRev L_Parameter.PDL chkMonitorMotRev L .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotRev L_Parameter.PDL csoBtnMaintenanceMotRev L .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotRev L_Parameter.PDL csoBtnMaintenanceMotRev L .SimOn On 3 1100 Simulation On/Of f ~PG_MotRev L_Parameter.PDL csoBtnSimMotRev L .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotRev L_Parameter.PDL csoBtnSimMotRev L .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotRev L_Parameter.PDL csoIOAnaDy nMonTimeMotRev L .MonTiStatic 2 6 Monitoring Time of Feedback [s] ~PG_MotRev L_Parameter.PDL csoIOAnaStaMonTimeMotRev L .FwdMan Forward 1 5 1=Start: Forward Start Command in Manual Mode ~PG_MotRev L_Standard.PDL csoBtnCommandMotRev L .Rev Man Rev erse 1 5 1=Start: Rev erse Start Command in Manual Mode ~PG_MotRev L_Standard.PDL csoBtnCommandMotRev L .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotRev L_Standard.PDL csoBtnCommandMotRev L .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_MotRev L_Standard.PDL csoBtnCommandMotRev L .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotRev L_Standard.PDL csoBtnModeMotRev L .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotRev L_Standard.PDL csoBtnModeMotRev L .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_MotRev L_Standard.PDL csoBtnModeMotRev L .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotRev L_Standard.PDL csoBtnModeMotRev L .RstOp Reset 1 5 Operator Reset Signal ~PG_MotRev L_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameMotS .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotS_Parameter.PDL chkMonitorMotS .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotS_Parameter.PDL chkMonitorMotS .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotS_Parameter.PDL csoBtnMaintenanceMotS .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotS_Parameter.PDL csoBtnMaintenanceMotS .SimOn On 3 1100 Simulation On/Of f ~PG_MotS_Parameter.PDL csoBtnSimMotS .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotS_Parameter.PDL csoBtnSimMotS .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotS_Parameter.PDL csoIOAnaDy nMonTimeMotS .StartMan Start 1 5 1=Start: Start Command in Manual Mode ~PG_MotS_Standard.PDL csoBtnCommandMotS .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotS_Standard.PDL csoBtnCommandMotS .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotS_Standard.PDL csoBtnModeMotS .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotS_Standard.PDL csoBtnModeMotS .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotS_Standard.PDL csoBtnModeMotS .RstOp Reset 1 5 Operator Reset Signal ~PG_MotS_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameMotSpdCL .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaAHMotSpdCL .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaALMotSpdCL .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_MotSpdCL_Limit.PDL csoIOAnaAVMotSpdCL .AV_Hy st 2 6 AV - Hy steresis ~PG_MotSpdCL_Limit.PDL csoIOAnaHy sMotSpdCL .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaTHMotSpdCL .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaTLMotSpdCL .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaWHMotSpdCL .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaWLMotSpdCL .ER_AH_Lim 2 6 ER alarm high limit ~PG_MotSpdCL_LimitRbk.PDL csoIOAnaAHMotSpdCL .ER_AL_Lim 2 6 ER alarm low limit ~PG_MotSpdCL_LimitRbk.PDL csoIOAnaAL

Page 27: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

MotSpdCL .RbkHy st 2 6 Rbk - Hy steresis ~PG_MotSpdCL_LimitRbk.PDL csoIOAnaHy sMotSpdCL .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_MotSpdCL_LimitRbk.PDL csoIOAnaHy sERMotSpdCL .RbkWH_Lim 2 6 Rbk - High Warning Limit ~PG_MotSpdCL_LimitRbk.PDL csoIOAnaWHMotSpdCL .RbkWL_Lim 2 6 Rbk - Low Warning Limit ~PG_MotSpdCL_LimitRbk.PDL csoIOAnaWLMotSpdCL .SP_TrkExt On 2 6 Bumpless Transf er f rom External to Internal ~PG_MotSpdCL_Parameter.PDL chkBumplessMotSpdCL .SP_TrkExt Of f 2 6 Bumpless Transf er f rom External to Internal ~PG_MotSpdCL_Parameter.PDL chkBumplessMotSpdCL .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotSpdCL_Parameter.PDL chkMonitorMotSpdCL .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotSpdCL_Parameter.PDL chkMonitorMotSpdCL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotSpdCL_Parameter.PDL csoBtnMaintenanceMotSpdCL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotSpdCL_Parameter.PDL csoBtnMaintenanceMotSpdCL .SimOn On 3 1100 Simulation On/Of f ~PG_MotSpdCL_Parameter.PDL csoBtnSimMotSpdCL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotSpdCL_Parameter.PDL csoBtnSimMotSpdCL .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotSpdCL_Parameter.PDL csoIOAnaDy nMonTimeMotSpdCL .MonTiStatic 2 6 Monitoring Time of Feedback [s] ~PG_MotSpdCL_Parameter.PDL csoIOAnaStaMonTimeMotSpdCL .SP_RateOn On 1 5 Setpoint changes are rate limited by SP_UpRaLim and SP_DnRaLim ~PG_MotSpdCL_Ramp.PDL chkRampOnMotSpdCL .SP_RateOn Of f 1 5 Setpoint changes are rate limited by SP_UpRaLim and SP_DnRaLim ~PG_MotSpdCL_Ramp.PDL chkRampOnMotSpdCL .SP_RmpModTime Duration 1 5 1: SP ramped ov er SP_RmpTime, 0: SP ramped by rates SP_UpRaLim, SP_DnRaLim ~PG_MotSpdCL_Ramp.PDL csoBtnRampModeMotSpdCL .SP_RmpModTime Gradient 1 5 1: SP ramped ov er SP_RmpTime, 0: SP ramped by rates SP_UpRaLim, SP_DnRaLim ~PG_MotSpdCL_Ramp.PDL csoBtnRampModeMotSpdCL .SP_RmpOn Activ e 1 5 Setpoint is ramped to SP_RmpTarget ~PG_MotSpdCL_Ramp.PDL csoBtnRampOnMotSpdCL .SP_RmpOn Inactiv e 1 5 Setpoint is ramped to SP_RmpTarget ~PG_MotSpdCL_Ramp.PDL csoBtnRampOnMotSpdCL .SP_RmpTime 1 5 Setpoint ramp time [s] ~PG_MotSpdCL_Ramp.PDL csoIOAnaDurationMotSpdCL .SP_DnRaLim 1 5 Downward rate limit f or setpoint changes or ramping [EUs/min] ~PG_MotSpdCL_Ramp.PDL csoIOAnaRampDnMotSpdCL .SP_UpRaLim 1 5 Upward rate limit f or setpoint changes or ramping [EUs/min] ~PG_MotSpdCL_Ramp.PDL csoIOAnaRampUpMotSpdCL .SP_RmpTarget 1 5 Setpoint ramp target ~PG_MotSpdCL_Ramp.PDL csoIOAnaTargetSPMotSpdCL .FwdMan Forward 1 5 1=Start: Forward Start Command in Manual Mode ~PG_MotSpdCL_Standard.PDL csoBtnCommandMotSpdCL .Rev Man Rev erse 1 5 1=Start: Rev erse Start Command in Manual Mode ~PG_MotSpdCL_Standard.PDL csoBtnCommandMotSpdCL .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotSpdCL_Standard.PDL csoBtnCommandMotSpdCL .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_MotSpdCL_Standard.PDL csoBtnCommandMotSpdCL .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnModeMotSpdCL .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnModeMotSpdCL .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_MotSpdCL_Standard.PDL csoBtnModeMotSpdCL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnModeMotSpdCL .RstOp Reset 1 5 Operator Reset Signal ~PG_MotSpdCL_Standard.PDL csoBtnResetMotSpdCL .SP_ExtOp External 1 5 Operator Input to Select External Setpoint ~PG_MotSpdCL_Standard.PDL csoBtnSetpointMotSpdCL .SP_IntOp Internal 1 5 Operator Input to Select Internal Setpoint ~PG_MotSpdCL_Standard.PDL csoBtnSetpointMotSpdCL .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_MotSpdCL_Standard.PDL csoIOAnaRbkOutMotSpdCL .SP_Int 1 5 Setpoint (Internal) ~PG_MotSpdCL_Standard.PDL csoIOAnaSPMotSpdCL .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaAHMotSpdCL .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaALMotSpdCL .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_MotSpdCL_Limit.PDL csoIOAnaAVMotSpdCL .AV_Hy st 2 6 AV - Hy steresis ~PG_MotSpdCL_Limit.PDL csoIOAnaHy sMotSpdCL .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaTHMotSpdCL .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaTLMotSpdCL .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaWHMotSpdCL .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_MotSpdCL_Limit.PDL csoIOAnaWLMotSpdCL .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotSpdCL_Parameter.PDL chkMonitor

Page 28: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

MotSpdCL .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback Monitor ~PG_MotSpdCL_Parameter.PDL chkMonitorMotSpdCL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotSpdCL_Parameter.PDL csoBtnMaintenanceMotSpdCL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_MotSpdCL_Parameter.PDL csoBtnMaintenanceMotSpdCL .SimOn On 3 1100 Simulation On/Of f ~PG_MotSpdCL_Parameter.PDL csoBtnSimMotSpdCL .SimOn Of f 3 1100 Simulation On/Of f ~PG_MotSpdCL_Parameter.PDL csoBtnSimMotSpdCL .MonTiDy namic 2 6 Monitoring Time of Feedback [s] ~PG_MotSpdCL_Parameter.PDL csoIOAnaDy nMonTimeMotSpdCL .MonTiStatic 2 6 Monitoring Time of Feedback [s] ~PG_MotSpdCL_Parameter.PDL csoIOAnaStaMonTimeMotSpdCL .Spd1Man Slow 1 5 ~PG_MotSpdCL_Standard.PDL csoBtnCommandMotSpdCL .Spd2Man Fast 1 5 ~PG_MotSpdCL_Standard.PDL csoBtnCommandMotSpdCL .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_MotSpdCL_Standard.PDL csoBtnCommandMotSpdCL .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_MotSpdCL_Standard.PDL csoBtnCommandMotSpdCL .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnModeMotSpdCL .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnModeMotSpdCL .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_MotSpdCL_Standard.PDL csoBtnModeMotSpdCL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_MotSpdCL_Standard.PDL csoBtnModeMotSpdCL .RstOp Reset 1 5 Operator Reset Signal ~PG_MotSpdCL_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameOpAnL .SP_TrkExt On 2 6 1: SP_Int tracks SP_Ext in External ~PG_OpAnL_Parameter.PDL chkBumplessOpAnL .SP_TrkExt Of f 2 6 1: SP_Int tracks SP_Ext in External ~PG_OpAnL_Parameter.PDL chkBumplessOpAnL .SP_RateOn On 1 5 Setpoint changes are rate limited by SP_UpRaLim and SP_DnRaLim ~PG_OpAnL_Ramp.PDL chkRampOnOpAnL .SP_RateOn Of f 1 5 Setpoint changes are rate limited by SP_UpRaLim and SP_DnRaLim ~PG_OpAnL_Ramp.PDL chkRampOnOpAnL .SP_RmpModTime Duration 1 5 1: SP ramped ov er SP_RmpTime, 0: SP ramped by rates SP_UpRaLim, SP_DnRaLim ~PG_OpAnL_Ramp.PDL csoBtnRampModeOpAnL .SP_RmpModTime Gradient 1 5 1: SP ramped ov er SP_RmpTime, 0: SP ramped by rates SP_UpRaLim, SP_DnRaLim ~PG_OpAnL_Ramp.PDL csoBtnRampModeOpAnL .SP_RmpOn Activ e 1 5 Setpoint is ramped to SP_RmpTarget ~PG_OpAnL_Ramp.PDL csoBtnRampOnOpAnL .SP_RmpOn Inactiv e 1 5 Setpoint is ramped to SP_RmpTarget ~PG_OpAnL_Ramp.PDL csoBtnRampOnOpAnL .SP_RmpTime 1 5 Setpoint ramp time [s] ~PG_OpAnL_Ramp.PDL csoIOAnaDurationOpAnL .SP_DnRaLim 1 5 Downward rate limit f or setpoint changes or ramping ~PG_OpAnL_Ramp.PDL csoIOAnaRampDnOpAnL .SP_UpRaLim 1 5 Upward rate limit f or setpoint changes or ramping ~PG_OpAnL_Ramp.PDL csoIOAnaRampUpOpAnL .SP_RmpTarget 1 5 Setpoint ramp target ~PG_OpAnL_Ramp.PDL csoIOAnaTargetSPOpAnL .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpAnL_Standard.PDL csoBtnModeOpAnL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpAnL_Standard.PDL csoBtnModeOpAnL .SP_ExtOp External 1 5 Operator input to select external setpoint ~PG_OpAnL_Standard.PDL csoBtnSetpointOpAnL .SP_IntOp Internal 1 5 Operator input to select internal setpoint ~PG_OpAnL_Standard.PDL csoBtnSetpointOpAnL .PV_In#Value 1 5 Value ~PG_OpAnL_Standard.PDL csoIOAnaPVOpAnL .SP_Int 1 5 Internal Analog setpoint ~PG_OpAnL_Standard.PDL csoIOAnaSP

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameOpDi01 .SetOp On 1 5 Operator Set Signal ~PG_OpDi01_Standard.PDL csoBtnCommandOpDi01 .RstOp Of f 1 5 Operator Reset Signal ~PG_OpDi01_Standard.PDL csoBtnCommandOpDi01 .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpDi01_Standard.PDL csoBtnModeOpDi01 .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpDi01_Standard.PDL csoBtnMode

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameOpDi03 .SetOp1 On 1 5 Operator Digital Input 1 ~PG_OpDi03_Standard.PDL csoBtnCommand1OpDi03 .SetOp2 On 1 5 Operator Digital Input 2 ~PG_OpDi03_Standard.PDL csoBtnCommand2

Page 29: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

OpDi03 .SetOp3 On 1 5 Operator Digital Input 3 ~PG_OpDi03_Standard.PDL csoBtnCommand3OpDi03 .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpDi03_Standard.PDL csoBtnModeOpDi03 .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpDi03_Standard.PDL csoBtnMode

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameOpStations .In0 Enable 3 1100 1='Enable operator station 1 ~PG_OpStations_Standard.PDL csoChkBoxIn0OpStations .In0 Disable 3 1100 1='Enable operator station 1 ~PG_OpStations_Standard.PDL csoChkBoxIn0OpStations .In1 Enable 3 1100 1='Enable operator station 2 ~PG_OpStations_Standard.PDL csoChkBoxIn1OpStations .In1 Disable 3 1100 1='Enable operator station 2 ~PG_OpStations_Standard.PDL csoChkBoxIn1OpStations .In10 Enable 3 1100 1='Enable operator station 11 ~PG_OpStations_Standard.PDL csoChkBoxIn10OpStations .In10 Disable 3 1100 1='Enable operator station 11 ~PG_OpStations_Standard.PDL csoChkBoxIn10OpStations .In11 Enable 3 1100 1='Enable operator station 12 ~PG_OpStations_Standard.PDL csoChkBoxIn11OpStations .In11 Disable 3 1100 1='Enable operator station 12 ~PG_OpStations_Standard.PDL csoChkBoxIn11OpStations .In12 Enable 3 1100 1='Enable operator station 13 ~PG_OpStations_Standard.PDL csoChkBoxIn12OpStations .In12 Disable 3 1100 1='Enable operator station 13 ~PG_OpStations_Standard.PDL csoChkBoxIn12OpStations .In13 Enable 3 1100 1='Enable operator station 14 ~PG_OpStations_Standard.PDL csoChkBoxIn13OpStations .In13 Disable 3 1100 1='Enable operator station 14 ~PG_OpStations_Standard.PDL csoChkBoxIn13OpStations .In14 Enable 3 1100 1='Enable operator station 15 ~PG_OpStations_Standard.PDL csoChkBoxIn14OpStations .In14 Disable 3 1100 1='Enable operator station 15 ~PG_OpStations_Standard.PDL csoChkBoxIn14OpStations .In15 Enable 3 1100 1='Enable operator station 16 ~PG_OpStations_Standard.PDL csoChkBoxIn15OpStations .In15 Disable 3 1100 1='Enable operator station 16 ~PG_OpStations_Standard.PDL csoChkBoxIn15OpStations .In2 Enable 3 1100 1='Enable operator station 3 ~PG_OpStations_Standard.PDL csoChkBoxIn2OpStations .In2 Disable 3 1100 1='Enable operator station 3 ~PG_OpStations_Standard.PDL csoChkBoxIn2OpStations .In3 Enable 3 1100 1='Enable operator station 4 ~PG_OpStations_Standard.PDL csoChkBoxIn3OpStations .In3 Disable 3 1100 1='Enable operator station 4 ~PG_OpStations_Standard.PDL csoChkBoxIn3OpStations .In4 Enable 3 1100 1='Enable operator station 5 ~PG_OpStations_Standard.PDL csoChkBoxIn4OpStations .In4 Disable 3 1100 1='Enable operator station 5 ~PG_OpStations_Standard.PDL csoChkBoxIn4OpStations .In5 Enable 3 1100 1='Enable operator station 6 ~PG_OpStations_Standard.PDL csoChkBoxIn5OpStations .In5 Disable 3 1100 1='Enable operator station 6 ~PG_OpStations_Standard.PDL csoChkBoxIn5OpStations .In6 Enable 3 1100 1='Enable operator station 7 ~PG_OpStations_Standard.PDL csoChkBoxIn6OpStations .In6 Disable 3 1100 1='Enable operator station 7 ~PG_OpStations_Standard.PDL csoChkBoxIn6OpStations .In7 Enable 3 1100 1='Enable operator station 8 ~PG_OpStations_Standard.PDL csoChkBoxIn7OpStations .In7 Disable 3 1100 1='Enable operator station 8 ~PG_OpStations_Standard.PDL csoChkBoxIn7OpStations .In8 Enable 3 1100 1='Enable operator station 9 ~PG_OpStations_Standard.PDL csoChkBoxIn8OpStations .In8 Disable 3 1100 1='Enable operator station 9 ~PG_OpStations_Standard.PDL csoChkBoxIn8OpStations .In9 Enable 3 1100 1='Enable operator station 10 ~PG_OpStations_Standard.PDL csoChkBoxIn9OpStations .In9 Disable 3 1100 1='Enable operator station 10 ~PG_OpStations_Standard.PDL csoChkBoxIn9

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameOpTrig .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_OpTrig_Standard.PDL csoBtnModeOpTrig .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_OpTrig_Standard.PDL csoBtnModeOpTrig .InOp Set 1 5 Operator Binary Input ~PG_OpTrig_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNamePIDConL .PV_AH_Lim 2 6 PV alarm high limit ~PG_PIDConL_Limit.PDL csoIOAnaAHPIDConL .PV_AL_Lim 2 6 PV alarm low limit ~PG_PIDConL_Limit.PDL csoIOAnaAL

Page 30: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

PIDConL .ER_AH_Lim 2 6 ER alarm high limit ~PG_PIDConL_Limit.PDL csoIOAnaErrHPIDConL .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_PIDConL_Limit.PDL csoIOAnaErrHy sPIDConL .ER_AL_Lim 2 6 ER alarm low limit ~PG_PIDConL_Limit.PDL csoIOAnaErrLPIDConL .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_PIDConL_Limit.PDL csoIOAnaHy sPIDConL .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_PIDConL_Limit.PDL csoIOAnaMVHPIDConL .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_PIDConL_Limit.PDL csoIOAnaMVLPIDConL .RbkWH_Lim 2 6 Rbk warning high limit ~PG_PIDConL_Limit.PDL csoIOAnaRbkHPIDConL .RbkHy st 2 6 Hy steresis f or Rbk warnings ~PG_PIDConL_Limit.PDL csoIOAnaRbkHy sPIDConL .RbkWL_Lim 2 6 Rbk warning low limit ~PG_PIDConL_Limit.PDL csoIOAnaRbkLPIDConL .SP_InHiLim 2 6 High limit of internal setpoint ~PG_PIDConL_Limit.PDL csoIOAnaSPHPIDConL .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_PIDConL_Limit.PDL csoIOAnaSPLPIDConL .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_PIDConL_Limit.PDL csoIOAnaTHPIDConL .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_PIDConL_Limit.PDL csoIOAnaTLPIDConL .PV_WH_Lim 2 6 PV warning high limit ~PG_PIDConL_Limit.PDL csoIOAnaWHPIDConL .PV_WL_Lim 2 6 PV warning low limit ~PG_PIDConL_Limit.PDL csoIOAnaWLPIDConL .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_PIDConL_Parameter.PDL csoBtnMaintPIDConL .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_PIDConL_Parameter.PDL csoBtnMaintPIDConL .SimOn On 3 1100 1 = Simulation activ ated ~PG_PIDConL_Parameter.PDL csoBtnSimuPIDConL .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_PIDConL_Parameter.PDL csoBtnSimuPIDConL .OptimEn On 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConL_Parameter.PDL csoChkBoxOptiPIDConL .OptimEn Of f 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConL_Parameter.PDL csoChkBoxOptiPIDConL .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConL_Parameter.PDL csoChkBoxPVTrkPIDConL .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConL_Parameter.PDL csoChkBoxPVTrkPIDConL .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConL_Parameter.PDL csoChkBoxSPTrkPIDConL .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConL_Parameter.PDL csoChkBoxSPTrkPIDConL .DeadBand 2 6 Width of deadband ~PG_PIDConL_Parameter.PDL csoIOAnaDeadBPIDConL .Gain#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaGainPIDConL .Dif f Gain#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaGainDPIDConL .TD#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaTDPIDConL .TI#Value 2 6 Value ~PG_PIDConL_Parameter.PDL csoIOAnaTIPIDConL .ConZone 2 6 Width of control zone ~PG_PIDConL_Parameter.PDL csoIOAnaZoneCPIDConL .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConL_Ramp.PDL csoBtnRampPIDConL .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConL_Ramp.PDL csoBtnRampPIDConL .SP_RmpModTime Duration 1 5 1= Use time (SP_RmpTime) f or ramp, 0= Use rates SP_UpRaLim, SP_DnRaLim ~PG_PIDConL_Ramp.PDL csoBtnRampModePIDConL .SP_RmpModTime Gradient 1 5 1= Use time (SP_RmpTime) f or ramp, 0= Use rates SP_UpRaLim, SP_DnRaLim ~PG_PIDConL_Ramp.PDL csoBtnRampModePIDConL .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConL_Ramp.PDL csoChkBoxGrdPIDConL .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConL_Ramp.PDL csoChkBoxGrdPIDConL .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_PIDConL_Ramp.PDL csoIOAnaDurationPIDConL .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_PIDConL_Ramp.PDL csoIOAnaGrdDownPIDConL .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_PIDConL_Ramp.PDL csoIOAnaGrdUpPIDConL .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_PIDConL_Ramp.PDL csoIOAnaTargetSPPIDConL .AutModOp Automatic 1 5 1 = Automatic mode by operator (controlled by ModLiOp = 0) ~PG_PIDConL_Standard.PDL csoBtnModePIDConL .ManModOp Manual 1 5 1 = Manual mode by operator (controlled by ModLiOp = 0) ~PG_PIDConL_Standard.PDL csoBtnModePIDConL .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_PIDConL_Standard.PDL csoBtnModePIDConL .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_PIDConL_Standard.PDL csoBtnModePIDConL .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_PIDConL_Standard.PDL csoBtnSPMode

Page 31: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

PIDConL .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_PIDConL_Standard.PDL csoBtnSPModePIDConL .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_PIDConL_Standard.PDL csoIOAnaMVPIDConL .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_PIDConL_Standard.PDL csoIOAnaPVPIDConL .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_PIDConL_Standard.PDL csoIOAnaRbkPIDConL .SP_Int 1 5 Internal setpoint f or operation ~PG_PIDConL_Standard.PDL csoIOAnaSP

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNamePIDConR .PV_AH_Lim 2 6 PV alarm high limit ~PG_PIDConR_Limit.PDL csoIOAnaAHPIDConR .PV_AL_Lim 2 6 PV alarm low limit ~PG_PIDConR_Limit.PDL csoIOAnaALPIDConR .ER_AH_Lim 2 6 ER alarm high limit ~PG_PIDConR_Limit.PDL csoIOAnaErrHPIDConR .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_PIDConR_Limit.PDL csoIOAnaErrHy sPIDConR .ER_AL_Lim 2 6 ER alarm low limit ~PG_PIDConR_Limit.PDL csoIOAnaErrLPIDConR .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_PIDConR_Limit.PDL csoIOAnaHy sPIDConR .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_PIDConR_Limit.PDL csoIOAnaMVHPIDConR .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_PIDConR_Limit.PDL csoIOAnaMVLPIDConR .RbkWH_Lim 2 6 Rbk warning high limit ~PG_PIDConR_Limit.PDL csoIOAnaRbkHPIDConR .RbkHy st 2 6 Hy steresis f or Rbk warnings ~PG_PIDConR_Limit.PDL csoIOAnaRbkHy sPIDConR .RbkWL_Lim 2 6 Rbk warning low limit ~PG_PIDConR_Limit.PDL csoIOAnaRbkLPIDConR .SP_InHiLim 2 6 High limit of internal setpoint ~PG_PIDConR_Limit.PDL csoIOAnaSPHPIDConR .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_PIDConR_Limit.PDL csoIOAnaSPLPIDConR .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_PIDConR_Limit.PDL csoIOAnaTHPIDConR .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_PIDConR_Limit.PDL csoIOAnaTLPIDConR .PV_WH_Lim 2 6 PV warning high limit ~PG_PIDConR_Limit.PDL csoIOAnaWHPIDConR .PV_WL_Lim 2 6 PV warning low limit ~PG_PIDConR_Limit.PDL csoIOAnaWLPIDConR .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_PIDConR_Parameter.PDL csoBtnMaintPIDConR .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_PIDConR_Parameter.PDL csoBtnMaintPIDConR .SimOn On 3 1100 1 = Simulation activ ated ~PG_PIDConR_Parameter.PDL csoBtnSimuPIDConR .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_PIDConR_Parameter.PDL csoBtnSimuPIDConR .OptimEn On 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConR_Parameter.PDL csoChkBoxOptiPIDConR .OptimEn Of f 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDConR_Parameter.PDL csoChkBoxOptiPIDConR .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConR_Parameter.PDL csoChkBoxPVTrkPIDConR .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDConR_Parameter.PDL csoChkBoxPVTrkPIDConR .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConR_Parameter.PDL csoChkBoxSPTrkPIDConR .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDConR_Parameter.PDL csoChkBoxSPTrkPIDConR .DeadBand 2 6 Width of deadband ~PG_PIDConR_Parameter.PDL csoIOAnaDeadBPIDConR .Gain#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaGainPIDConR .Dif f Gain#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaGainDPIDConR .TD#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaTDPIDConR .TI#Value 2 6 Value ~PG_PIDConR_Parameter.PDL csoIOAnaTIPIDConR .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConR_Ramp.PDL csoBtnRampPIDConR .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDConR_Ramp.PDL csoBtnRampPIDConR .SP_RmpModTime Duration 1 5 1= Use time (SP_RmpTime) f or ramp, 0= Use rates SP_UpRaLim, SP_DnRaLim ~PG_PIDConR_Ramp.PDL csoBtnRampModePIDConR .SP_RmpModTime Gradient 1 5 1= Use time (SP_RmpTime) f or ramp, 0= Use rates SP_UpRaLim, SP_DnRaLim ~PG_PIDConR_Ramp.PDL csoBtnRampModePIDConR .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConR_Ramp.PDL csoChkBoxGrdPIDConR .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDConR_Ramp.PDL csoChkBoxGrdPIDConR .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_PIDConR_Ramp.PDL csoIOAnaDuration

Page 32: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

PIDConR .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_PIDConR_Ramp.PDL csoIOAnaGrdDownPIDConR .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_PIDConR_Ramp.PDL csoIOAnaGrdUpPIDConR .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_PIDConR_Ramp.PDL csoIOAnaTargetSPPIDConR .AutModOp Automatic 1 5 1 = Automatic mode by operator ~PG_PIDConR_Standard.PDL csoBtnModePIDConR .ManModOp Manual 1 5 1 = Manual mode by operator ~PG_PIDConR_Standard.PDL csoBtnModePIDConR .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_PIDConR_Standard.PDL csoBtnModePIDConR .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_PIDConR_Standard.PDL csoBtnModePIDConR .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_PIDConR_Standard.PDL csoBtnSPModePIDConR .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_PIDConR_Standard.PDL csoBtnSPModePIDConR .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_PIDConR_Standard.PDL csoIOAnaMVPIDConR .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_PIDConR_Standard.PDL csoIOAnaPVPIDConR .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_PIDConR_Standard.PDL csoIOAnaRbkPIDConR .SP_Int 1 5 Internal setpoint f or operation ~PG_PIDConR_Standard.PDL csoIOAnaSP

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNamePIDStepL .PV_AH_Lim 2 6 PV alarm high limit ~PG_PIDStepL_Limit.PDL csoIOAnaAHPIDStepL .PV_AL_Lim 2 6 PV alarm low limit ~PG_PIDStepL_Limit.PDL csoIOAnaALPIDStepL .ER_AH_Lim 2 6 ER alarm high limit ~PG_PIDStepL_Limit.PDL csoIOAnaErrHPIDStepL .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_PIDStepL_Limit.PDL csoIOAnaErrHy sPIDStepL .ER_AL_Lim 2 6 ER alarm low limit ~PG_PIDStepL_Limit.PDL csoIOAnaErrLPIDStepL .PV_Hy st 2 6 Hy steresis f or PV alarms, warnings and tolerance messages ~PG_PIDStepL_Limit.PDL csoIOAnaHy sPIDStepL .ManHiLim 2 6 High limit f or manipulated v ariable in manual mode ~PG_PIDStepL_Limit.PDL csoIOAnaMVHPIDStepL .ManLoLim 2 6 Low limit f or manipulated v ariable in manual mode ~PG_PIDStepL_Limit.PDL csoIOAnaMVLPIDStepL .RbkWH_Lim 2 6 Rbk warning high limit ~PG_PIDStepL_Limit.PDL csoIOAnaRbkHPIDStepL .RbkHy st 2 6 Hy steresis f or Rbk warnings ~PG_PIDStepL_Limit.PDL csoIOAnaRbkHy sPIDStepL .RbkWL_Lim 2 6 Rbk warning low limit ~PG_PIDStepL_Limit.PDL csoIOAnaRbkLPIDStepL .SP_InHiLim 2 6 High limit of internal setpoint ~PG_PIDStepL_Limit.PDL csoIOAnaSPHPIDStepL .SP_InLoLim 2 6 Low limit of internal setpoint ~PG_PIDStepL_Limit.PDL csoIOAnaSPLPIDStepL .PV_TH_Lim 2 6 PV tolerance message high limit ~PG_PIDStepL_Limit.PDL csoIOAnaTHPIDStepL .PV_TL_Lim 2 6 PV tolerance message low limit ~PG_PIDStepL_Limit.PDL csoIOAnaTLPIDStepL .PV_WH_Lim 2 6 PV warning high limit ~PG_PIDStepL_Limit.PDL csoIOAnaWHPIDStepL .PV_WL_Lim 2 6 PV warning low limit ~PG_PIDStepL_Limit.PDL csoIOAnaWLPIDStepL .MS_RelOp Yes 3 1100 1 = Release f or maintenance by operator ~PG_PIDStepL_Parameter.PDL csoBtnMaintPIDStepL .MS_RelOp No 3 1100 1 = Release f or maintenance by operator ~PG_PIDStepL_Parameter.PDL csoBtnMaintPIDStepL .SimOn On 3 1100 1 = Simulation activ ated ~PG_PIDStepL_Parameter.PDL csoBtnSimuPIDStepL .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_PIDStepL_Parameter.PDL csoBtnSimuPIDStepL .OptimEn On 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDStepL_Parameter.PDL csoChkBoxOptiPIDStepL .OptimEn Of f 2 6 1 = Enable optimization of PID parameters by PID tuner ~PG_PIDStepL_Parameter.PDL csoChkBoxOptiPIDStepL .SP_TrkPV On 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDStepL_Parameter.PDL csoChkBoxPVTrkPIDStepL .SP_TrkPV Of f 2 6 1 = Setpoint f ollows PV in manual mode and in tracking ~PG_PIDStepL_Parameter.PDL csoChkBoxPVTrkPIDStepL .SP_TrkExt On 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDStepL_Parameter.PDL csoChkBoxSPTrkPIDStepL .SP_TrkExt Of f 2 6 1 = Bumpless switchov er f rom external to internal setpoint activ e ~PG_PIDStepL_Parameter.PDL csoChkBoxSPTrkPIDStepL .BreakTime 2 6 Minimum Break Time [s] ~PG_PIDStepL_Parameter.PDL csoIOAnaBreakTPIDStepL .DeadBand 2 6 Width of deadband ~PG_PIDStepL_Parameter.PDL csoIOAnaDeadBPIDStepL .Gain#Value 2 6 Value ~PG_PIDStepL_Parameter.PDL csoIOAnaGainPIDStepL .Dif f Gain#Value 2 6 Value ~PG_PIDStepL_Parameter.PDL csoIOAnaGainD

Page 33: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

PIDStepL .MotorTime 2 6 Motor Actuating Time [s] ~PG_PIDStepL_Parameter.PDL csoIOAnaMotorTPIDStepL .PulseTime 2 6 Minimum Pulse Time [s] ~PG_PIDStepL_Parameter.PDL csoIOAnaPulseTPIDStepL .TD#Value 2 6 Value ~PG_PIDStepL_Parameter.PDL csoIOAnaTDPIDStepL .TI#Value 2 6 Value ~PG_PIDStepL_Parameter.PDL csoIOAnaTIPIDStepL .SP_RmpOn Activ e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDStepL_Ramp.PDL csoBtnRampPIDStepL .SP_RmpOn Inactiv e 1 5 1= Activ ate setpoint ramp to target setpoint SP_RmpTarget ~PG_PIDStepL_Ramp.PDL csoBtnRampPIDStepL .SP_RmpModTime Duration 1 5 1= Use time (SP_RmpTime) f or ramp, 0= Use rates SP_UpRaLim, SP_DnRaLim ~PG_PIDStepL_Ramp.PDL csoBtnRampModePIDStepL .SP_RmpModTime Gradient 1 5 1= Use time (SP_RmpTime) f or ramp, 0= Use rates SP_UpRaLim, SP_DnRaLim ~PG_PIDStepL_Ramp.PDL csoBtnRampModePIDStepL .SP_RateOn On 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDStepL_Ramp.PDL csoChkBoxGrdPIDStepL .SP_RateOn Of f 1 5 1= Activ ate limitation of setpoint gradients by SP_UpRaLim and SP_DnRaLim ~PG_PIDStepL_Ramp.PDL csoChkBoxGrdPIDStepL .SP_RmpTime 1 5 Time f or setpoint ramp [s] f rom current SP up to SP_RmpTarget ~PG_PIDStepL_Ramp.PDL csoIOAnaDurationPIDStepL .SP_DnRaLim 1 5 Downward rate limit of setpoint [PV_Unit/s] ~PG_PIDStepL_Ramp.PDL csoIOAnaGrdDownPIDStepL .SP_UpRaLim 1 5 Upward rate limit of setpoint [PV_Unit/s] ~PG_PIDStepL_Ramp.PDL csoIOAnaGrdUpPIDStepL .SP_RmpTarget 1 5 Target setpoint f or setpoint ramp ~PG_PIDStepL_Ramp.PDL csoIOAnaTargetSPPIDStepL .OpenOp Open 1 5 Manual Signal Open by Operation ~PG_PIDStepL_Standard.PDL csoBtnManipSignalsPIDStepL .CloseOp Close 1 5 Manual Signal Close by Operation ~PG_PIDStepL_Standard.PDL csoBtnManipSignalsPIDStepL .StopOp Stop 1 5 Manual Signal Stop by Operation ~PG_PIDStepL_Standard.PDL csoBtnManipSignalsPIDStepL .AutModOp Automatic 1 5 1 = Automatic mode by operator (controlled by ModLiOp = 0) ~PG_PIDStepL_Standard.PDL csoBtnModePIDStepL .ManModOp Manual 1 5 1 = Manual mode by operator (controlled by ModLiOp = 0) ~PG_PIDStepL_Standard.PDL csoBtnModePIDStepL .Adv CoOn Program 1 5 1 = Enable program mode v ia f aceplate ~PG_PIDStepL_Standard.PDL csoBtnModePIDStepL .OosOp Out of serv ice 2 6 1 = Out of serv ice by OS operation ~PG_PIDStepL_Standard.PDL csoBtnModePIDStepL .SP_ExtOp External 1 5 1 = Select external setpoint (v ia operator) ~PG_PIDStepL_Standard.PDL csoBtnSPModePIDStepL .SP_IntOp Internal 1 5 1 = Select internal setpoint (v ia operator) ~PG_PIDStepL_Standard.PDL csoBtnSPModePIDStepL .Man 1 5 Operator input f or manual setting of manipulated v ariable MV ~PG_PIDStepL_Standard.PDL csoIOAnaMVPIDStepL .SimPV 1 5 Process v alue used f or SimOn = 1 ~PG_PIDStepL_Standard.PDL csoIOAnaPVPIDStepL .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_PIDStepL_Standard.PDL csoIOAnaRbkPIDStepL .SP_Int 1 5 Internal setpoint f or operation ~PG_PIDStepL_Standard.PDL csoIOAnaSP

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameRatio .RatTrkExt On 2 6 Bumpless Transf er f rom External to Internal ~PG_Ratio_Parameter.PDL chkBumplessRatio .RatTrkExt Of f 2 6 Bumpless Transf er f rom External to Internal ~PG_Ratio_Parameter.PDL chkBumplessRatio .SimOn On 3 1100 Simulation On/Of f ~PG_Ratio_Parameter.PDL csoBtnSimRatio .SimOn Of f 3 1100 Simulation On/Of f ~PG_Ratio_Parameter.PDL csoBtnSimRatio .OutHiLim 2 6 Out High Limit ~PG_Ratio_Parameter.PDL csoIOAnaOutHiLimRatio .OutLoLim 2 6 Out Low Limit ~PG_Ratio_Parameter.PDL csoIOAnaOutLoLimRatio .RatHiLim 2 6 Ratio High Limit ~PG_Ratio_Parameter.PDL csoIOAnaRatioHiLimRatio .RatLoLim 2 6 Ratio Low Limit ~PG_Ratio_Parameter.PDL csoIOAnaRatioLoLimRatio .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_Ratio_Standard.PDL csoBtnModeRatio .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_Ratio_Standard.PDL csoBtnModeRatio .RatExtOp External 1 5 Operator Input to Select External Ratio ~PG_Ratio_Standard.PDL csoBtnSetpointRatio .RatIntOp Internal 1 5 Operator Input to Select Internal Ratio ~PG_Ratio_Standard.PDL csoBtnSetpointRatio .SimIn 1 5 In Simulation Value, tracks when not in simulation ~PG_Ratio_Standard.PDL csoIOAnaInRatio .RatioInt 1 5 Ratio (Internal) ~PG_Ratio_Standard.PDL csoIOAnaOf f setRatio .Out#Value 1 5 Value ~PG_Ratio_Standard.PDL csoIOAnaOutRatio .RatioPV#Value 1 5 Value ~PG_Ratio_Standard.PDL csoIOAnaRatioPVRatio .RatioInt 1 5 Ratio (Internal) ~PG_Ratio_Standard.PDL csoIOAnaSP

Page 34: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameSelA16In .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_SelA16In_Standard.PDL csoBtnModeSelA16In .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_SelA16In_Standard.PDL csoBtnModeSelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel1SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel10SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel11SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel12SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel13SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel14SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel15SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel16SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel2SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel3SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel4SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel5SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel6SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel7SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel8SelA16In .SelInt Select 1 5 Select v ia operator input; 1 = select In01; 16 = select In16 ~PG_SelA16In_Standard.PDL csoBtnSel9

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameTotalL .OutAH_Lim 2 6 Out Value High Alarm Limit ~PG_TotalL_Limit.PDL csoIOAnaAHTotalL .OutAL_Lim 2 6 Out Value Low Alarm Limit ~PG_TotalL_Limit.PDL csoIOAnaALTotalL .OutTH_Lim 2 6 Out Value High Tolerance Limit ~PG_TotalL_Limit.PDL csoIOAnaTHTotalL .OutTL_Lim 2 6 Out Value Low Tolerance Limit ~PG_TotalL_Limit.PDL csoIOAnaTLTotalL .OutWH_Lim 2 6 Out Value High Warning Limit ~PG_TotalL_Limit.PDL csoIOAnaWHTotalL .OutWL_Lim 2 6 Out Value Low Warning Limit ~PG_TotalL_Limit.PDL csoIOAnaWLTotalL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_TotalL_Parameter.PDL csoBtnMaintenanceTotalL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_TotalL_Parameter.PDL csoBtnMaintenanceTotalL .SimOn On 3 1100 1 = Simulation activ ated ~PG_TotalL_Parameter.PDL csoBtnSimTotalL .SimOn Of f 3 1100 1 = Simulation activ ated ~PG_TotalL_Parameter.PDL csoBtnSimTotalL .Decr#Value 2 6 Value ~PG_TotalL_Parameter.PDL csoIOAnaDecrTotalL .Incr#Value 2 6 Value ~PG_TotalL_Parameter.PDL csoIOAnaIncrTotalL .PresetVal#Value 2 6 Value ~PG_TotalL_Parameter.PDL csoIOAnaPresetValTotalL .TI 2 6 Integral Time Constant [s] ~PG_TotalL_Parameter.PDL csoIOAnaTITotalL .UpOp Up 1 5 1 = Up Totaliser ~PG_TotalL_Standard.PDL csoBtnCommandTotalL .DnOp Down 1 5 1 = Down Totaliser ~PG_TotalL_Standard.PDL csoBtnCommandTotalL .Of f Op Of f 1 5 Totaliser Of f by Operator: 1 = Totaliser is Of f ~PG_TotalL_Standard.PDL csoBtnCommandTotalL .OnOp On 1 5 1=On Mode: On Mode by Operator ~PG_TotalL_Standard.PDL csoBtnModeTotalL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_TotalL_Standard.PDL csoBtnModeTotalL .RstOp Preset 1 5 1 = Reset Calculation Process ~PG_TotalL_Standard.PDL csoBtnResetTotalL .SimOut 1 5 Process v alue used f or SimOn = 1 ~PG_TotalL_Standard.PDL csoIOAnaOut

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameVlv 2Way L .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_Vlv 2Way L_Parameter.PDL csoBtnMaint

Page 35: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

Vlv 2Way L .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_Vlv 2Way L_Parameter.PDL csoBtnMaintVlv 2Way L .SimOn On 3 1100 Simulation on/of f ~PG_Vlv 2Way L_Parameter.PDL csoBtnSimuVlv 2Way L .SimOn Of f 3 1100 Simulation on/of f ~PG_Vlv 2Way L_Parameter.PDL csoBtnSimuVlv 2Way L .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback monitor ~PG_Vlv 2Way L_Parameter.PDL csoChkBoxMonVlv 2Way L .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback monitor ~PG_Vlv 2Way L_Parameter.PDL csoChkBoxMonVlv 2Way L .MonTiP0Dy namic 2 6 Monitoring time f or expected change of f eedback position 0 [s] ~PG_Vlv 2Way L_Parameter.PDL csoIOAnaControlMonP0Vlv 2Way L .MonTiV0Dy namic 2 6 Monitoring time f or expected change of f eedback FbkV0 [s] ~PG_Vlv 2Way L_Parameter.PDL csoIOAnaControlMonV0Vlv 2Way L .MonTiV1Dy namic 2 6 Monitoring time f or expected change of f eedback FbkV1 [s] ~PG_Vlv 2Way L_Parameter.PDL csoIOAnaControlMonV1Vlv 2Way L .MonTiV2Dy namic 2 6 Monitoring time f or expected change of f eedback FbkV2 [s] ~PG_Vlv 2Way L_Parameter.PDL csoIOAnaControlMonV2Vlv 2Way L .MonTiStatic 2 6 Monitoring time f or unexpected change in any f eedback [s] ~PG_Vlv 2Way L_Parameter.PDL csoIOAnaRuntimeMonVlv 2Way L .Pos0Man Pos0 1 5 1=Pos0: Position 0 command in manual mode. ~PG_Vlv 2Way L_Standard.PDL csoBtnCommandVlv 2Way L .Pos1Man Pos1 1 5 1=Pos1: Position 1 command in manual mode. ~PG_Vlv 2Way L_Standard.PDL csoBtnCommandVlv 2Way L .Pos2Man Pos2 1 5 1=Pos2: Position 2 command in manual mode. ~PG_Vlv 2Way L_Standard.PDL csoBtnCommandVlv 2Way L .AutModOp Automatic 1 5 1=Auto mode: auto mode by operator ~PG_Vlv 2Way L_Standard.PDL csoBtnModeVlv 2Way L .ManModOp Manual 1 5 1=Manual mode: manual mode by operator ~PG_Vlv 2Way L_Standard.PDL csoBtnModeVlv 2Way L .LocalOp Local 1 5 1=Local Mode: Local operation by operator ~PG_Vlv 2Way L_Standard.PDL csoBtnModeVlv 2Way L .OosOp Out of serv ice 2 6 1=Oos mode: Oos mode by operator ~PG_Vlv 2Way L_Standard.PDL csoBtnModeVlv 2Way L .RstOp Reset 1 5 Operator reset signal ~PG_Vlv 2Way L_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameVlv AnL .ER_AH_Lim 2 6 ER alarm high limit ~PG_Vlv AnL_Limit.PDL csoIOAnaErrHVlv AnL .ER_Hy st 2 6 Hy steresis f or ER alarms ~PG_Vlv AnL_Limit.PDL csoIOAnaErrHy sVlv AnL .ER_AL_Lim 2 6 ER alarm low limit ~PG_Vlv AnL_Limit.PDL csoIOAnaErrLVlv AnL .MV_HiLim 2 6 manipulated v ariable High Limit ~PG_Vlv AnL_Limit.PDL csoIOAnaMVHVlv AnL .MV_LoLim 2 6 manipulated v ariable Low Limit ~PG_Vlv AnL_Limit.PDL csoIOAnaMVLVlv AnL .RbkWH_Lim 2 6 Rbk - High Warning Limit ~PG_Vlv AnL_Limit.PDL csoIOAnaRbkHVlv AnL .RbkHy st 2 6 Rbk - Hy steresis ~PG_Vlv AnL_Limit.PDL csoIOAnaRbkHy sVlv AnL .RbkWL_Lim 2 6 Rbk - Low Warning Limit ~PG_Vlv AnL_Limit.PDL csoIOAnaRbkLVlv AnL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_Vlv AnL_Parameter.PDL csoBtnMaintVlv AnL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_Vlv AnL_Parameter.PDL csoBtnMaintVlv AnL .SimOn On 3 1100 Simulation on/of f ~PG_Vlv AnL_Parameter.PDL csoBtnSimuVlv AnL .SimOn Of f 3 1100 Simulation on/of f ~PG_Vlv AnL_Parameter.PDL csoBtnSimuVlv AnL .Monitor On 2 6 1=MonitorV ON, 0=Monitor OFF: Feedback monitor ~PG_Vlv AnL_Parameter.PDL csoChkBoxMonVlv AnL .Monitor Of f 2 6 1=MonitorV ON, 0=Monitor OFF: Feedback monitor ~PG_Vlv AnL_Parameter.PDL csoChkBoxMonVlv AnL .MonitorAuxV On 2 6 1=MonitorAuxV ON, 0=MonitorAuxV OFF: Feedback monitor of auxiliary v alv e ~PG_Vlv AnL_Parameter.PDL csoChkBoxMonAuxVlv AnL .MonitorAuxV Of f 2 6 1=MonitorAuxV ON, 0=MonitorAuxV OFF: Feedback monitor of auxiliary v alv e ~PG_Vlv AnL_Parameter.PDL csoChkBoxMonAuxVlv AnL .MV_TrkExt On 2 6 Bumpless Transf er f rom External to Internal ~PG_Vlv AnL_Parameter.PDL csoChkBoxMVTrkVlv AnL .MV_TrkExt Of f 2 6 Bumpless Transf er f rom External to Internal ~PG_Vlv AnL_Parameter.PDL csoChkBoxMVTrkVlv AnL .MV_TrkRbk On 2 6 Bumpless Transf er f rom tracking to not tracking ~PG_Vlv AnL_Parameter.PDL csoChkBoxRbkTrkVlv AnL .MV_TrkRbk Of f 2 6 Bumpless Transf er f rom tracking to not tracking ~PG_Vlv AnL_Parameter.PDL csoChkBoxRbkTrkVlv AnL .MonTiDy namic 2 6 Monitoring time f or expected change of f eedback [s] ~PG_Vlv AnL_Parameter.PDL csoIOAnaControlMonVlv AnL .MonAuxVTime 2 6 Monitoring time of auxiliary v alv e f or expected change of f eedback [s] ~PG_Vlv AnL_Parameter.PDL csoIOAnaControlMonAuxVlv AnL .MonTiStatic 2 6 Monitoring time f or unexpected change in any f eedback [s] ~PG_Vlv AnL_Parameter.PDL csoIOAnaRuntimeMonVlv AnL .MV_RmpOn Activ e 1 5 manipulated v ariable is ramped to MV_RmpTarget ~PG_Vlv AnL_Ramp.PDL csoBtnRampVlv AnL .MV_RmpOn Inactiv e 1 5 manipulated v ariable is ramped to MV_RmpTarget ~PG_Vlv AnL_Ramp.PDL csoBtnRampVlv AnL .MV_RmpModTime Duration 1 5 1: MV ramped ov er MV_RmpTime, 0: MV ramped by rates MV_UpRaLim, MV_DnRaLim~PG_Vlv AnL_Ramp.PDL csoBtnRampMode

Page 36: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

Vlv AnL .MV_RmpModTime Gradient 1 5 1: MV ramped ov er MV_RmpTime, 0: MV ramped by rates MV_UpRaLim, MV_DnRaLim~PG_Vlv AnL_Ramp.PDL csoBtnRampModeVlv AnL .MV_RateOn On 1 5 manipulated v ariable changes are rate limited by MV_UpRaLim and MV_DnRaLim ~PG_Vlv AnL_Ramp.PDL csoChkBoxGrdVlv AnL .MV_RateOn Of f 1 5 manipulated v ariable changes are rate limited by MV_UpRaLim and MV_DnRaLim ~PG_Vlv AnL_Ramp.PDL csoChkBoxGrdVlv AnL .MV_RmpTime 1 5 manipulated v ariable ramp time [s] ~PG_Vlv AnL_Ramp.PDL csoIOAnaDurationVlv AnL .MV_DnRaLim 1 5 Downward rate limit f or MV changes or ramping [EUs/min] ~PG_Vlv AnL_Ramp.PDL csoIOAnaGrdDownVlv AnL .MV_UpRaLim 1 5 Upward rate limit f or MV changes or ramping [EUs/min] ~PG_Vlv AnL_Ramp.PDL csoIOAnaGrdUpVlv AnL .MV_RmpTarget 1 5 manipulated v ariable ramp target ~PG_Vlv AnL_Ramp.PDL csoIOAnaTargetSPVlv AnL .OpenMan Open 1 5 1=Open: Open Command in Manual Mode ~PG_Vlv AnL_Standard.PDL csoBtnCommandVlv AnL .CloseMan Close 1 5 1=Close: Close Command in Manual Mode ~PG_Vlv AnL_Standard.PDL csoBtnCommandVlv AnL .AutModOp Automatic 1 5 1=Auto mode: auto mode by operator ~PG_Vlv AnL_Standard.PDL csoBtnModeVlv AnL .ManModOp Manual 1 5 1=Manual mode: manual mode by operator ~PG_Vlv AnL_Standard.PDL csoBtnModeVlv AnL .LocalOp Local 1 5 1=Local Mode: Local operation by operator ~PG_Vlv AnL_Standard.PDL csoBtnModeVlv AnL .OosOp Out of serv ice 2 6 1=Oos mode: Oos mode by operator ~PG_Vlv AnL_Standard.PDL csoBtnModeVlv AnL .MV_ExtOp External 1 5 Operator Input to Select External manipulated v ariable ~PG_Vlv AnL_Standard.PDL csoBtnMVModeVlv AnL .MV_IntOp Internal 1 5 Operator Input to Select Internal manipulated v ariable ~PG_Vlv AnL_Standard.PDL csoBtnMVModeVlv AnL .RstOp Reset 1 5 Operator reset signal ~PG_Vlv AnL_Standard.PDL csoBtnResetVlv AnL .MV_Int 1 5 manipulated v ariable (Internal) ~PG_Vlv AnL_Standard.PDL csoIOAnaMVVlv AnL .SimRbk 1 5 Readback v alue used f or SimOn = 1 ~PG_Vlv AnL_Standard.PDL csoIOAnaRbk

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameVlv L .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_Vlv L_Parameter.PDL csoBtnMaintVlv L .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_Vlv L_Parameter.PDL csoBtnMaintVlv L .SimOn On 3 1100 Simulation on/of f ~PG_Vlv L_Parameter.PDL csoBtnSimuVlv L .SimOn Of f 3 1100 Simulation on/of f ~PG_Vlv L_Parameter.PDL csoBtnSimuVlv L .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback monitor ~PG_Vlv L_Parameter.PDL csoChkBoxMonVlv L .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback monitor ~PG_Vlv L_Parameter.PDL csoChkBoxMonVlv L .MonTiDy namic 2 6 Monitoring time f or expected change of f eedback [s] ~PG_Vlv L_Parameter.PDL csoIOAnaControlMonVlv L .MonTiStatic 2 6 Monitoring time f or unexpected change in any f eedback [s] ~PG_Vlv L_Parameter.PDL csoIOAnaRuntimeMonVlv L .OpenMan Open 1 5 1=Open: Open Command in Manual Mode ~PG_Vlv L_Standard.PDL csoBtnCommandVlv L .CloseMan Close 1 5 1=Close: Close Command in Manual Mode ~PG_Vlv L_Standard.PDL csoBtnCommandVlv L .AutModOp Automatic 1 5 1=Auto mode: auto mode by operator ~PG_Vlv L_Standard.PDL csoBtnModeVlv L .ManModOp Manual 1 5 1=Manual mode: manual mode by operator ~PG_Vlv L_Standard.PDL csoBtnModeVlv L .LocalOp Local 1 5 1=Local Mode: Local operation by operator ~PG_Vlv L_Standard.PDL csoBtnModeVlv L .OosOp Out of serv ice 2 6 1=Oos mode: Oos mode by operator ~PG_Vlv L_Standard.PDL csoBtnModeVlv L .RstOp Reset 1 5 Operator reset signal ~PG_Vlv L_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameVlv MotL .AV_AH_Lim 2 6 AV - High Alarm Limit ~PG_Vlv MotL_Limit.PDL csoIOAnaAHVlv MotL .AV_AL_Lim 2 6 AV - Low Alarm Limit ~PG_Vlv MotL_Limit.PDL csoIOAnaALVlv MotL .SimAV 1 5 AV Simulation Value, tracks when not in simulation ~PG_Vlv MotL_Limit.PDL csoIOAnaAVVlv MotL .AV_Hy st 2 6 AV - Hy steresis ~PG_Vlv MotL_Limit.PDL csoIOAnaHy sVlv MotL .AV_TH_Lim 2 6 AV - High Tolerance Limit ~PG_Vlv MotL_Limit.PDL csoIOAnaTHVlv MotL .AV_TL_Lim 2 6 AV - Low Tolerance Limit ~PG_Vlv MotL_Limit.PDL csoIOAnaTLVlv MotL .AV_WH_Lim 2 6 AV - High Warning Limit ~PG_Vlv MotL_Limit.PDL csoIOAnaWHVlv MotL .AV_WL_Lim 2 6 AV - Low Warning Limit ~PG_Vlv MotL_Limit.PDL csoIOAnaWLVlv MotL .V_Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Valv e Feedback Monitor ~PG_Vlv MotL_Parameter.PDL chkMonitor

Page 37: U R (Athorizati) SIMATIC PCS 7 OS V7 - Siemens · 2015-07-14 · 1 How do user rights work? 8 User Rights PCS 7 OS V7.1 1.0, Item-ID: 60575347 1.3 U rig ork SIMATIC PCS 7 OS combi

Vlv MotL .V_Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Valv e Feedback Monitor ~PG_Vlv MotL_Parameter.PDL chkMonitorVlv MotL .M_Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Motor Feedback Monitor ~PG_Vlv MotL_Parameter.PDL chkMonitor1Vlv MotL .M_Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Motor Feedback Monitor ~PG_Vlv MotL_Parameter.PDL chkMonitor1Vlv MotL .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_Vlv MotL_Parameter.PDL csoBtnMaintenanceVlv MotL .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_Vlv MotL_Parameter.PDL csoBtnMaintenanceVlv MotL .SimOn On 3 1100 Simulation On/Of f ~PG_Vlv MotL_Parameter.PDL csoBtnSimVlv MotL .SimOn Of f 3 1100 Simulation On/Of f ~PG_Vlv MotL_Parameter.PDL csoBtnSimVlv MotL .V_MonTiDy namic 2 6 Valv e Monitoring Time of Feedback [s] ~PG_Vlv MotL_Parameter.PDL csoIOAnaDy nMonTimeVlv MotL .M_MonTiDy namic 2 6 Motor Monitoring Time of Feedback [s] ~PG_Vlv MotL_Parameter.PDL csoIOAnaDy nMonTimeMotorVlv MotL .V_MonTiStatic 2 6 Valv e Monitoring Time of Feedback [s] ~PG_Vlv MotL_Parameter.PDL csoIOAnaStaMonTimeVlv MotL .M_MonTiStatic 2 6 Motor Monitoring Time of Feedback [s] ~PG_Vlv MotL_Parameter.PDL csoIOAnaStaMonTime1Vlv MotL .OpenMan Open 1 5 1=Open: Open Command in Manual Mode ~PG_Vlv MotL_Standard.PDL csoBtnCommandVlv MotL .CloseMan Close 1 5 1=Close: Close Command in Manual Mode ~PG_Vlv MotL_Standard.PDL csoBtnCommandVlv MotL .StopMan Stop 1 5 1=Stop: Stop Command in Manual Mode ~PG_Vlv MotL_Standard.PDL csoBtnCommandVlv MotL .RapidStp Rapid stop 1 5 1 = Motor Rapid Stop command ~PG_Vlv MotL_Standard.PDL csoBtnCommandVlv MotL .AutModOp Automatic 1 5 1=Auto Mode: Auto Mode by Operator ~PG_Vlv MotL_Standard.PDL csoBtnModeVlv MotL .ManModOp Manual 1 5 1=Manual Mode: Manual Mode by Operator ~PG_Vlv MotL_Standard.PDL csoBtnModeVlv MotL .LocalOp Local 1 5 1=Local Mode: Local Operation by Operator ~PG_Vlv MotL_Standard.PDL csoBtnModeVlv MotL .OosOp Out of serv ice 2 6 1=Oos Mode: Oos Mode by Operator ~PG_Vlv MotL_Standard.PDL csoBtnModeVlv MotL .RstOp Reset 1 5 Operator Reset Signal ~PG_Vlv MotL_Standard.PDL csoBtnReset

BlockType Tag Text Level User Right IO Comment Picture/Faceplate objNameVlv S .MS_RelOp Yes 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_Vlv S_Parameter.PDL csoBtnMaintVlv S .MS_RelOp No 3 1100 Operator input f or MS Release, 1: MS release requirement ~PG_Vlv S_Parameter.PDL csoBtnMaintVlv S .SimOn On 3 1100 Simulation on/of f ~PG_Vlv S_Parameter.PDL csoBtnSimuVlv S .SimOn Of f 3 1100 Simulation on/of f ~PG_Vlv S_Parameter.PDL csoBtnSimuVlv S .Monitor On 2 6 1=Monitor ON, 0=Monitor OFF: Feedback monitor ~PG_Vlv S_Parameter.PDL csoChkBoxMonVlv S .Monitor Of f 2 6 1=Monitor ON, 0=Monitor OFF: Feedback monitor ~PG_Vlv S_Parameter.PDL csoChkBoxMonVlv S .MonTiDy namic 2 6 Monitoring time f or expected change of f eedback [s] ~PG_Vlv S_Parameter.PDL csoIOAnaControlMonVlv S .OpenMan Open 1 5 1=Open: Open Command in Manual Mode ~PG_Vlv S_Standard.PDL csoBtnCommandVlv S .CloseMan Close 1 5 1=Close: Close Command in Manual Mode ~PG_Vlv S_Standard.PDL csoBtnCommandVlv S .AutModOp Automatic 1 5 1=Auto mode: auto mode by operator ~PG_Vlv S_Standard.PDL csoBtnModeVlv S .ManModOp Manual 1 5 1=Manual mode: manual mode by operator ~PG_Vlv S_Standard.PDL csoBtnModeVlv S .OosOp Out of serv ice 2 6 1=Oos mode: Oos mode by operator ~PG_Vlv S_Standard.PDL csoBtnModeVlv S .RstOp Reset 1 5 Operator reset signal ~PG_Vlv S_Standard.PDL csoBtnReset