    contents

    02 ovrviw

    03 Prdu cagry

    03 LW41-126/T4000-40 High Voltage SF6 Circuit Breaker12 High Voltage Disconnector

    14 GW4-27.5DW Single Grounding Once-through Operation Disconnector

    15 GW4-110DW Three-phase Coupled Remodeling Disconnector

    16 GW5-110D (W)/630/ 1250 Outdoor Triple Pole Mounted Disconnector

    17 Medium Voltage Switch

    23 VBP Indoor Solid-sealed Pole Vacuum Circuit Breaker

    32 VK Vacuum Circuit Breaker (Designated Sales Region)

    44 VY Vacuum Circuit Breaker (Designated Sales Region)

    53 ZN85-40.5 Indoor AC High Voltage Vacuum Circuit Breaker

    60 VS1-BYE Indoor High Voltage Vacuum Circuit Breaker

    66 VW Single-phase Vacuum Circuit Breaker (Designated Sales Region)

    67 UVA Vacuum Contactor - Fuse Combination

    70 BYEW1 Series Air Circuit Breaker

    71 BYEM1 Series Molded Case Circuit Breaker

    75 BYEM1LE Series MCCB with Residual Current Protection

    79 BYEM2Z Molded Case Circuit Breaker

    81 BYEM6, BYEM6LE Series Miniature Circuit Breaker

    83 BYQ2 Series Dual Power Supply Automatic Transfer Switch

    86 BYES9 Series Dual Power Supply Automatic Transfer Switch

    88 Vacuum interrupter

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    3/49

    03

    Prdutcategry

    2 High & Lw Vlag swih

    Overview

    Engage in the manufacturing, distribution, design and

    installation of various high, medium and low voltage switch

    assemblies of complete specifications and varieties.

    Products include vacuum circuit breaker and contactor, vacuum

    interrupter, SF6 MV gas insulated switchgear, high voltagedisconnector, various low voltage circuit breakers and switches.

    Toshiba Baiyun Vacuum Interrupters (Jinzhou) Co., Ltd. is a joint

    venture engaged in the manufacturing of vacuum interrupters

    established jointly by Japan Toshiba K.K., Guangzhou Baiyun

    Electric Group Co., Ltd. and Toshiba (China) Co., Ltd. with its

    controlling shares held by Toshiba Group. It's the manufacturing

    base of vacuum switch tubes. It sticks to the strategy of dual

    brands, namely, Toshiba vacuum interrupter and Liaoju vacuum

    interrupter. Its Liaoju vacuum interrupter is one of the top

    four famous brands in China.

    Nanjing Electric (Group) Co., Ltd. (the former name: Nanjing

    Electro-Ceramic Factory) was established in 1936. Through

    merger and acquisition, now it's the wholly owned subsidiary

    of Baiyun Electric Group; it's the manufacturing base of high

    voltage disconnectors; and its Thunderbrand registered in

    1937 is famous at home and abroad.

    Descriptive trademark is Guangzhou Famous Brand and

    Guangdong Province Famous Brand. High, medium and low

    voltage switchgear assembly is Guangdong Famous Brand.

    Besides its proprietary brands, it also manufactures many

    products with joint venture brands.

    It successively established three j oint ventures with Toshiba

    and Mitsubishi, and cooperated with Germany Si emens, France

    Schneider and Switzerland ABB for more than 20 technologies,

    and introduced the world advanced critical technologies

    including 8PT, VK and OKKEN products.

    For a number of years, the company has invested for more

    than 100 million yuan. It respectively introduced more than 50

    (sets) world advanced NC presses, NC shearers, NC benders,

    mechanical machining centers, bus bar machining centers,

    multi-purpose welding equipment and automatic spraying

    production lines etc. from Japan, Switzerland, U.S., Britain, Italy,

    Germany etc., and formed multi-functional metal plate and

    mechanical processing and production lines; its production

    technology and production capacity can represent the highest

    achievement in the fellow sector at home; its annual production

    capacity of high and medium voltage switchgear assemblies is

    6000.

    Its products are mainly used by the key customers in eight

    industries including power grid, rail transportation, power

    plant, petroleum and petrochemical and its market share

    in the construction of Southern Power Grid is 50%. So far,

    the company has participated in 15 provincial level power

    grid construction projects, the construction of more than 80

    power plants, as well as Beijing Metro and Guangzhou Metro,

    becoming one of the 13 qualified suppliers of PetroChina and

    Sinopec.

    It introduces and sets up various management methods and

    systems, including ISO9001, ISO14001, OHSAS18001, 6S, ERP,

    CRM, PLM, JIT, MBO, CEMS etc., which provide high-quality

    guarantee for its products.

    The company has Corporate Technical Center approved by

    Guangdong Province and state approved corporate technical

    center high and low voltage switchgear assemblies research

    sub-center, sets up eight multi-functional research labs in the

    area of switchgear assemblies, has top high and low voltage

    electrical products development and test techniques, and

    possesses more than 80 test and detection equipment with the

    highest level of the industry, and its metering center has been

    approved as State Intermediate Metering enterprise.

    Product Category

    ovrviw

    LW41-126/T4000-40 SF6 Circuit Breaker is outdoor live tank

    circuit breaker, 3 phase, 50Hz, used in 126kV power system for

    cutting off load current, fault current and switching circuit. It is

    capable of 3 phase O/C and auto-reclosing, used to operate,

    control ans protect power system.

    This type of SF6 circuit breaker is self-developed product by our

    company, using SF6 as insulation and arc extinction medium.

    It adopts the latest self-energy arc extinguishing technology in

    the word, with the technical performance reaching international

    advanced level and leading position in China.

    It is featured with reasonable design, compact structure and low

    operating power. Spring mechanism is superior to hydraulic one

    for no leakage of oil and nitrogen. This kind of SF6 circuit breaker

    is the replacement product of SF6 puffer circuit breaker, having

    the advantage of low noise, reliable operation, fast installation

    and easy maintenance.

    Wrkig dii

    n. Im Ui Daa

    1 Ambient temperature0C -30 ~ 50

    2 Wind pressure Pa 700

    3 Altitude m 1000

    4 Seismic intensity Degree 9

    5 Pollution degree of external insulation Class II, III, IV

    6 Static tensile force of horizontal longitudinal terminal N 1250

    7 Static tensile force of transverse horizontal terminal N 750

    8 Static tensile force of vertical terminal N 1000

    LW41-126/T4000-40 High Voltage SF6 Circuit Breaker

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    4/49

    4 05

    Prdutcategry

    High & Lw Vlag swih

    thial daa irui brakr

    Mhaial prpry

    sF6 maagm

    sruurCircuit breaker is composed of three poles, cross-beam, column

    and spring operating mechanism (outline and dimension

    shown in drawing 1). Three poles are on top of the cross-

    beam, and the spring operating mechanism is right below

    the cross-beam. The three poles are mechanical connection,

    with each pole filled with SF6 as insulation and arc-extinction

    medium, connected by pipeline to form a gas circuit system,

    and monitored by pressure pointer type density relay. Electrical

    control system is placed in the spring mechanism box.

    Ar-quhig priipl

    During the opening operation, when the static main contact

    (3) and moving contact (4) separates, the current will transfer

    to static arcing contact (10) and moving arc contact (11) for

    continued flow, and the moving contact will keep up the

    opening operation.

    When breaking high current: during breaking operation,

    SF6 turns into high temperature and pressure gas by the arc

    generated by the separation action of moving arcing contact

    and static arcing contact (10). Before spout (9) laryngeal departs

    with static arcing contact, the gas flows into thermal expansion

    n. Im Ui Daa

    1 Rated voltage kV 126

    2 Rated frequency Hz 50

    3 Insulation

    Rated short time power frequencywithstand voltage (wet, dry)

    Phase to phase, phase to earthkV

    230

    Across the isolating distance 265

    Rated lightning impulse withstandvoltage (positive, negative)

    Phase to phase, phase to earthkV

    550

    Across the isolating distance 630

    4 Rated current A 4000

    5 Rated short-circuit breaking current kA 40

    6 First-pole-to-clear factor 1.5

    7 Rated short time withstand current kA 40

    8 Rated duration of short-circuit s 4

    9 Rated peak withstand current kA 100

    10 Rated short-circuit making current kA 100

    11 Rated operating sequence 0-0.3s-CO-180s-CO

    12 Short-line fault breaking current kA 36; 30

    13 Rated out-of-phase breaking current kA 10

    14 Rated line-charging breaking current A 31.5

    15 Electrical interruptive life of rated short-circuit current time(s) 16

    16 Mechanical life time(s) 3000

    17 Annual leakage ratio (SF6) % 1

    18 Water content in SF6 ppm 150

    n. Im Ui thial daa

    1 Opening time ms 322

    2 Closing time ms 605

    3 Open-close time ms 300

    4 Close-open time ms 805

    5 Opening simultaneity ms 2

    6 Closing simultaneity ms 3

    7 Switch off time ms 60

    sprig mhaim

    n. Im Ui thial daa

    1 Tripping and closing coil voltage/current V/A DC 220/2

    2 Control circuit voltage V DC 220

    3 Rated voltage / power of energy storage motor V/kW AC, DC 220/0.8

    4 Energy storage time at 85-110% rated voltage s

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    5/49

    6 07

    Prdutcategry

    High & Lw Vlag swih

    Fr udai, wigh ad dimi

    1. Pole 2 . Cross-arm 3 . Column 4 . Spring operating mechanism

    5. ON-OFF indicator and density relay 6. Terminal block 7. Mechanism chamber

    Drawing 1 LW-126/T4000-40 AC SF6 Circuit Breaker

    a. ON position b. Break high current c. Break small current d. OFF position

    1. Porcelain sleeve 2. Static main contact pedestal 3. Static main contact 4. Moving main contact 5. Thermal expansion chamber

    6. Pressure chamber 7. Intake valve 8. Moving main contact pedestal 9. Spout 10. Static arcing contact

    11. Moving arcing contact 12. One way valve 13. Piston 14. Pressure relief valve

    Drawing 2 Principle of self-energized arc-extinguishing

    Drawing 3 Circuit breaker installation foundation

    n. Im Ui Daa

    1 Opening force (downward) N 21000

    2 Closing force (upward) N 15000

    3 Total weight including mechanism and gas kg 1400

    4 Dimension (L*W*H) mm 3900*710*4884

    Distancefromthelivepartstoground3230

    Terminalblock

    8-M36-4embeddedanchorbolts

    (Providedby Baiyun)

    150cablehole

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    6/49

    8 09

    Prdutcategry

    High & Lw Vlag swih

    seondaryon

    rolhemaiforLW-126/t4000-40AchighvolagesF6iruibreaker

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    7/49

    0 11

    Prdutcategry

    High & Lw Vlag swih

    ordr irui

    Please clearly state the ollowing items when ordering:

    1. Type, name, quality of circuit breaker;

    2. Rated voltage, rated current, rated short circuit breaking current and rated insulation level;

    3. External insulation pollution degree (or specific creepage distance);

    4. Primary wiring diagram;

    5. Voltage of control circuit, now only DC 220V available;

    6. Voltage of energy storage motor, AC/DC 220V motor available;

    7. If gas processing equipment, SF6 leakage detector, micro-moisture meter required;

    8. Spare parts list: name and quantity.

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    8/49

    2 13

    Prdutcategry

    High & Lw Vlag swih

    High Voltage Disconnector

    ovrviw

    Nanjing Electric (Group) Co., Ltd. was restructured and became

    the wholly owned subsidiary of Baiyun Electric Group and now

    is the manufacture base of high voltage disconnectors.

    Nanjing Electric (Group) Co., Ltd. (Nanjing Electro-Ceramic

    Factory) has been producing high voltage disconnectors for

    more than 40 years; it's one of the important manufacturers

    of high voltage disconnector in our country. Products used forelectrification railway network system and si gnal indication

    include GW4, GW5 and FWZ series of outdoor high voltage

    disconnector, isolation load switch and equipped electric

    mechanism and manual mechanism.

    Rated voltages of products range from 10kV to 220kV, rated

    current includes 630A, 1250A, 1600A, 2000A, 2500A, and

    3150A, specific creepage distance has 16mm/kV, 20mm/kV,

    25mm/kV, and 31mm/kV, which is of complete range of types

    and specifications. The high voltage disconnector has high

    performance and has passed the test by state or provincial test

    center. Now it has tens of thousands machine units running

    in the state power system, among which GW4 series are well

    recognized by users to have reliable structure, flexible machine

    driven system, convenient operation, stable contact resistance

    etc. At present, its products have been sold to all Railway Bureaus

    of the Ministry of Railways. In recent years, its metal accessories

    including rod insulator cap, pedestal switch base frame etc. all

    employ hot galvanizing technology, which greatly improves

    the metalwork's ability to resist tarnishing. The company's

    disconnector and load switches have been successfully used in

    the railway projects including Beijing Kowloon Railway, Beijing

    Shenyang Passenger Railway, Guanghan High-speed Rail,

    Shanghai-Nanjing Intercity High-speed Rail, Guangdong-Hainan

    Cross-sea Railway, Datong-Qinhuangdao Railway, Kowloon-

    Canton Railway etc.

    The product obtains ISO9001 Quality System Authentication.

    Wrkig dii

    1. 2000m or less than 3000m (3000m inclusive) above sea level

    2. Surrounding ambient temperature is not higher than +40C

    or lower than -30C, and not lower than -40C in severe cold

    districts.

    3. Seismic intensity does not exceed grade 8.

    4. Wind pressure for outdoor products shall not exceed 700Pa

    (equivalent to 31m/s).

    5. Ice coating thickness shall not exceed 1mm in general districts

    and not exceed 10mm and 20mm in heavy ice coating districts.

    6. Indoor product temperature: relative temperature: daily

    average value shall not be greater than 95% and monthly

    mean shall not be greater than 90%. Saturated vapor pressure:

    daily average value shall not be greater than 2.210-1MPa, and

    monthly mean value shall not be greater than 1.810-1MPa;

    when temperature drops sharply in the periods with high

    humidity, it may condense.

    7. The product is not applicable in the following places:

    Places with fire or explosion;

    Places with sharp swings, shakes or i mpacts

    Places filled with chemical gases that can easily corrode

    metals and insulation materials

    8. Air pollution classes: no obvious pollution for the use of indoor

    products; pollution classes for operating ambient of outdoor

    products include class 0 (clear area), class I, class II, class III, and

    class IV, which shall be specified by the technical requirements.

    Note:

    Accordingto theregulationsof GB5582-85ExternalInsulationPollution

    Classof HighVoltageElectricPowerEquipment,the minimumnominal

    specific creepage distance is 14.8mm/kV, 16mm/kV for class I, 20mm/

    kV for class II, 25mm/kV for class III and 31mm/kV for class IV. Specific

    creepage distance is the ratio of external insulation creepage distance

    andequipmentmaximumvoltage.

    If the uses requirements are beyond the above standard service

    conditions, please contact with relevant departments of the company

    (factory).

    U

    It can be used for the switch of HV electrification railway

    contact network system without carrying current and

    electrical isolation between the electrical equipment under

    maintenance such as primary busbar and breaker and the

    energized high voltage line.

    Load switch can open the rated current and cut off short-

    circuit current, and has obvious break distance.

    sadard

    1. GB1985 Alternating Current High-voltage Disconnectors

    and Earthing Switches

    2. GB11022 Common Technical Requirements for High Voltage

    Switchgear

    3. Equivalent IEC-129 (1984) publication Alternate Current

    Disconnectors and Earthing Switches by equivalent

    4. Equivalent IEC-694 (1980) General Specifications for High

    Voltage Switchgear and Control Standards

    5. GB311.1 Insulation Coordination for High Voltage Power

    Transmission and Distribution Equipment

    6. GB311.2-311.6 High-voltage Test Techniques

    7. GB3309 Mechanical Test at Ambient Temperature for High

    Voltage Switchgear

    8. GB5582 External Insulation Pollution Class of High VoltageElectric Power Equipment

    9. GB5273 Terminals for Transformers, High Voltage

    Apparatuses and Bushings

    10. GB3804-3.6kV-40.5kV High-voltage Alternating Current

    Switch for Rated Voltage range from 3.6kV to 40.5kV

    11. TB/T3150 High Voltage AC Disconnectors and Earthing

    Switch for Electrification Railway

    12. TB/T3151 High Voltage AC Load Switches for Electrification

    Railway

    ordr irui

    1. Product model, name, rated voltage and rated current

    2. Thermal stable current of the disconnector and grounding disconnector

    3. Grounding disconnector: ungrounded, grounded on the right, grounded on the left, grounded on both sides

    4. Creepage distance

    5. Model and name of operating mechanism, working voltage of power, number of contactors for auxiliary switches, with

    electromagnetic lock or not

    6. Operation mode: triple-pole interlock or single-pole operation, single-pole, double-pole interlocking or triple-pole

    7. Special inclination installation shall be indicated in an order (GW5).

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    9/49

    4 15

    Prdutcategry

    High & Lw Vlag swih

    GW4-27.5DW Single Grounding Once-through Operation Disconnector

    ovrviw

    GW4-27.5DW outdoor AC high voltage disconnector for electrification railway is 50HZ outdoor HV electrical equipment. It can be

    used for the switch of alternate current 27.5kV contact network with voltage and without load as well as the electrical isolation

    between the electrical equipment under maintenance such as HV busbar and circuit breaker and the energized high voltage line. It

    can also be used for breaking and making of low capacitance current and inductive current.

    ovrall Dimi Drawig

    GW4-27.5DW Single Pole Multipack Figure of Single Pole Grounded Once-through Operation Disconnector (matched with CJ11A-G electric mechanism)

    1. GW4- 27.5DW single pole disconnector 2. Upper hoop joint 3. 32 water gas pipelines (prepared by users) 4. Lower hoop joint

    5. CJ11A-G electric-operated mechanism

    Mai hial paramr

    Im Ui GW4-27.5DWRated voltage kV 27.5

    Rated current A 1250~3150Rated withstand current kA 31.5~40

    Rated peak withstand current kA 80~100

    Rated short-circuit period s 4

    Short-time power frequency withstand voltageGrounded

    kV80

    Fracture 90

    Rated lightning impulse withstand voltageGrounded

    kV185

    Fracture 215

    Static tension of terminal

    Horizontal

    N

    750

    Transverse 750Vertical 500

    Creepage distance 1200

    Mechanical life time(s) 10000

    Fitted device Disconnector CJ11Earthing switch CS14

    GW4-110DW Three-phase Coupled Remodeling Disconnector

    ovrviw

    GW4- 110DW three-phase interlock remodeling structure

    Im Ui GW4-40.5DW GW4-126DWRated voltage kV 40.5 126

    Rated current A 1250~3150 1250~3150Rated short time withstand current kA 31.5~40 31.5~50

    Rated peak withstand current kA 80~100 80~100

    Rated short-circuit period s 4 4

    Short-duration power-frequency withstand voltageGrounded distance

    kV80 230

    Fracture 90 300

    Rated lightning impulse withstand voltageGrounded distance

    kV185 550

    Fracture 215 650

    Static tension of terminal

    Horizontal

    N

    750 1250

    Lateral 750 750Vertical 500 1000

    Creepage distance mm 1020~1260 3150~3910

    Mechanical endurance time(s) 10000 10000

    S up pl em en ta ry de vi ce D is co nn ec to r C J1 1 C J1 1Earthing switch CS14 CS14

    GW4 series high voltage disconnector is single-phase dual

    column horizontal open circuit structure; it's mainly composed

    of base frame, rod support insulator, current-carrying part

    and electric Operating device. Each phase has two support

    insulators, which are respectively fixed to the bearing chock

    on both sides of the base frame; they are connected by cross

    member and can rotate horizontally; their intersection angle is

    90. The conduction knife switch is split into halves, which are

    fixed to the support insulator respectively; contact point of the

    contactor is in between two support insulators. The terminal

    employs flexible connection, with simple structure, reliable

    contact and is convenient for repair.

    GW4-126 high voltage disconnector can also be used for high-

    profile layout (namely, operated with the control mechanism

    drawn out). Parts and components for the intermediate driving

    section will be provided along with the disconnector.

    GW4-126 series can be furnished with CS14G manual control

    mechanism or CJ11 electric control mechanism; the earthing

    switch is furnished with CS14G manual control mechanism;

    the manual control mechanism can also be used with DSW4electromagnetic lock.

    It uses slot aluminum as the main conductor; it has large area of

    dissipation, high intensity and is safe and reliable; the earthing

    switch uses flexible configuration and can turn right and left

    conveniently.

    ovrall dimi drawig

    Mai hial paramr

    about

    about

    about

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    10/49

    6 17

    Prdutcategry

    High & Lw Vlag swih

    GW5-110D (W)/630/1250 Outdoor Triple Pole Mounted Disconnector

    ovrviw

    GW5-126II(DW) series disconnector is mainly composed of

    three single poles; each pole is composed of base frame,

    support insulator, right and left contactors, grounded knife

    switch, electric Operating device etc. Two support insulators

    are respectively fixed to the rotary bearings of the pedestal, in V

    type. Intersection angle of axial lines is 50; bevel gear joggle is

    under two bearing chocks; the right and left contactors are fixed

    to the top of support insulator; rotation of the bearing chock will

    drive the synchronous rotation of the support insulator, thereby

    to open and close two contactors; three single poles can be

    interlocked by the interlocking drawbar.

    This series of disconnector can be grounded on one side,

    on both sides or ungrounded. CS17F and CS17D manual

    control mechanism with the angle of rotation being 90are

    used respectively for it. There is mechanical interlocking and

    electromagnetic lock on the control mechanism to make sure

    the operating sequence is right.

    In order to meet user needs, this series of products can beinstalled in five different ways, namely, horizontal installation,

    inclined for 25, inclined for 50, side installation (inclined for 90

    and upside down installation.

    ovrall dimi drawig

    1. Single pole assembly; 2. Universal joint; 3. Pin with hole; 4. water gas pipe (prepared by user);

    5. Locking ring; 8. Joint; 9. Link rod assembly; 10. Water gas pipe (prepared by user);

    11. Supporting rack (prepared by user); 12. Oscillating arm; 13. Bushing; 14.M6 fastening screw;

    15. Grounded knife switch; 16. Split pin; 17.CS17 manual control mechanism;

    GW5-110IID (W)/630,1250 (90transmission) Triple Pole Multipack Figure of Outdoor Disconnector

    Im Ui GW5-40.5DW GW5-126DWRated voltage kV 40.5 126Rated current A 1250~3150 1250~3150

    Rated short time withstand current kA 31.5~40 31.5~50

    Rated peak withstand current kA 80~100 80~100

    Rated short-circuit period S 4 4

    Short-duration power-frequency withstand voltageGrounded distance

    kV80 230

    Fracture 90 300

    Rated lightning impulse withstand voltageGrounded distance

    kV185 550

    Fracture 215 650

    Static tension of terminal

    Horizontal

    N

    750 1250

    Lateral 750 750

    Vertical 500 1000

    Creepage distance mm 1020~1260 3150~3910Mechanical endurance time(s) 10000 10000

    Su pplem ent ar y de vice Dis con nect or CJ11 CJ11

    Earthing switch CS14 CS14

    Mai hial paramr

    Medium Voltage Switch

    VB Vacuum Circuit Breaker

    ovrviw

    Application environmental conditions

    Ambient temperature: upper limit +40C, lower limit - 10C;

    Elevation: not exceeding 1000m;

    Relative humidity: daily average value shall not be greater

    than 95%; monthly average value shall not be greater than 90%;

    Structural feature vacuum: with VEZA: with KYNB: special

    25: 25kA32: 31.5kA40: 40kA50: 50kA

    06: 630A12: 1250A16: 1600A20: 2000A25: 2500A32: 3150A40: 4000A

    12kV

    Rated breaking current

    Type series

    Rated current

    Rated voltage

    Product line VB vacuum circuit breaker

    n. nam (ui) thial paramr

    1 Rated voltage (kV ) 12

    2 Rated cur ren t (A) 630, 1 250, 160 0 2000, 2500, 3150, 4 000

    3 Fr eq ue nc y ( Hz ) 5 0

    4 Rated short-circuit breaking current (kA) 25, 31 .5. 40 40. 50

    5 Rated short-circuit making current (kA) 63, 80, 100 100, 125

    6 4s rated short time withstand current (kA) 25. 31 .5. 40 40. 50

    7 Rated peak withstand current (kA) 63, 80. 100 100. 1258Rated O/C current

    Single capacitor bank current (A) 630 800

    9 Back to back capacitor bank current (A) 400

    10 1min power frequency withstand voltage (kV) 42 (Fracture: 48)

    11 Impulse withstand voltage (kV) 75 (Fracture: 85)

    12 Rated operating procedure O-0, 3s-CO-180s-CO (40, 50kA is O-180s-CO-180s-CO)

    13 Rated short-circuit current operation time(s) 50

    14 Mechanical endurance (times) 30000 20000

    15 Rated breaking time (ms) 60

    16 Trip time (ms) 30

    17 Making time (ms) 45

    18 Rated operating voltage (V) AC/DC 220V/110V

    19 Rated operating current (A ) 2.0/4.0

    20 Single-phase major loop resistance (without primary plug)1N=630A 1N=1250A 1600a1N2000A 1N2500A

    R65 R40 R30 R25

    Places without fire, inflammables, explosion hazards, chemical

    corrosion and sharp vibration;

    Seismic intensity: not exceeding grade 8;

    For special operating ambient, please contact with the

    manufacturer.

    Type specication

    thial paramr

    Electric parameters

    notlessthan1m

    notlessthan2m

    Earthingknife

    Earthingswitchshalf

    (Installatin hole)

    DirectionA

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    11/49

    8 19

    Prdutcategry

    High & Lw Vlag swih

    srial n. nam (ui)chararii paramr

    Brakig urr 40KA Brakig urr = 50kA

    1 Contactor torque (mm) 8.01 9.01

    2 Contacting travel (mm) 30.5

    3 Average closing speed (m/s) 0.4-0.8

    4 Average trip speed (m/s) 0.8-2.0

    5 Jump time of contactor closing (ms) 2

    6 Three-phase asynchronization (ms) 2

    Mechanical parameters ovrall dimi

    Lw urr

    sruur

    Main elements of VB vacuum circuit breaker include the operating device, driven gear, insulating boot, vacuum interrupter

    Closing

    spring

    Hoisting hookFluctuation

    conductor

    Vacuum

    interrupter

    Flexible

    connection

    Insulation

    drawbar

    Contactor

    spring

    Tripspring

    Lever

    Chassis

    Figure 3.1 Sectional View of Disconnector

    Insulatingboot

    Housing

    Vacuum

    interrupter

    Operating

    device Insulation

    cover

    Primary

    plug

    Valvepress

    plateDrivengear

    Chassis

    Trippaddle

    Tripfanningstrip

    Closingspring

    Tripknob

    Closing button

    Closingreleasingslab

    Closingcoil

    Closingwedge Contactorspring

    Tripspring

    Charging

    motorand

    gearbox

    Vacuum

    interrupter

    Tripcoil

    Figure 3.2 Device Module View Figure 3.3 Device Module View

    1.Primaryplug;

    2. Vacuuminterrupter;

    3. Handle;

    4. Counter;

    5. Closingandtrip indication;

    6. Insertingholeof charginghandle;

    7. Secondaryplug;

    8. Springchargingindication;

    9. Closingbutton;

    10. Tripknob

    Figure 4.1.1 Outline Drawing of Low Current Breaker

    chai

    Figure 4.1.2 Chassis Mechanism

    Tripfanningstrip

    Rachet

    Manualcharging

    gearClosinghalf

    shaft

    Counter

    Chargingmotor

    andgearbox

    Triphalfshaft

    Excitationsw itch

    Chargingcamshaft

    Mainshaft

    Contactorspring

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    12/49

    0 21

    Prdutcategry

    High & Lw Vlag swih

    Havy urr

    Figure 4.1.3 Outline Drawing of Heavy Current Breaker

    1.Primaryplug;

    2.Vacuuminterrupter;

    3. Handle;

    4.Counter;

    5.Closingandtripindication;

    6.Insertingholeofcharginghandle

    7.Secondaryplug;

    8.Springchargingindication;

    9.Closingbutton;

    10.Tripknob

    Secondary schematic diagram

    Note:theanti-tripcircuitcanbecancelledaccordingtocustomerrequirements

    TC:(tripcoil)

    CC:(closingcoil)

    M:(chargingmotor)

    LS1~LS5,s

    8,s:(limitswitch)

    a1~a8:(Auxilisrycontact)

    b1~b8:(Auxiliarycontact)

    Y:(auxiliaryrelay)

    X:(Controlrelay)

    F:(Fuse)

    C:(capacitor)

    R1~R4:(resistor)

    D1~D6:(Diode)

    Test position Work position

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    13/49

    2 23

    Prdutcategry

    High & Lw Vlag swih

    Product lectotype

    n.

    VB-12 -------------------------------------

    Maimdl sri

    Widh

    auxiliary

    abi

    opraig

    vlag

    MaidimiAi-

    rip

    trippig

    lur

    Rk-

    i

    oupu

    a

    ovr-

    urr

    rla

    earhig

    mdA B c1 c2 D e F G H J K L M n P W X Y

    1 V B- 1206B25

    A

    W650

    AC/DC110

    220

    528502494 494598

    (608)

    648

    (658)

    436

    (443)637275280

    76

    (81)

    78

    (71)322

    294

    (304)150

    35

    20189

    0:No1:

    Yes

    0:No

    1:Yes

    0:No

    1:Yes

    3:3a3b5:5a5b

    8:8a8b

    0:No

    1:Yes

    0:bothsides

    1:

    bottom

    2 VB-1212B25 49

    3 V B- 1206B25

    W800 685 652 638 638598

    (608)

    648

    (658)

    436

    (443)637275280

    76

    (81)

    78

    (71)322

    294

    (304)210

    35

    28261

    4 V B- 1212B25

    5 V B- 1206B32

    6 V B- 1212B32

    497 V B- 1216B32

    8 V B- 1220B32

    9 V B- 1212B40

    7010 VB-1216B40

    11 VB-1220B40

    12 VB-1225B40

    W1000 880 852 836 840 5 87 637 350

    700

    3 10 2 96 8 5 8 6 3 43 2 62 2 75

    109

    25262

    13 VB-1232B40

    14 VB-1240B4070

    15 VB-1212B50

    74616 VB-1232B50109

    17 VB-1240B50

    e.g. VB-1212B32A/W800DC220V100500

    VBP Indoor Solid-sealed Pole Vacuum Circuit Breaker

    Note: 1. Number in the brackets means special models

    2. Please contact with the manufacturer for other special models needed

    Prdu Lyp Irmai sh

    Procurement

    company

    CompanyAdd.

    Proposing Dept. Promoter Tel:

    Endcustomer

    Model required Quantity

    ModelRated

    voltage

    Rated

    current

    Type

    series

    Ratedbreaking

    current

    Structural

    feature

    Auxiliary

    cabinetwidth

    Operational

    powersupply

    Anti-

    trip

    Closing

    closure

    Rocking-in

    closure

    Output

    contact

    Over-current

    release

    Earthing

    form

    Reference

    value VB - 1 2: 12 kV

    06:630A

    12:1250A

    20:2000A

    25:2500A

    32:3150A

    40:4000A

    B

    25:25kA

    32:31.5kA

    40:40kA

    50:50kA

    Vacuum:

    withVEZ

    A:withKYN

    B:special

    /

    W650

    W800W1000

    AC220V

    AC110V

    DC220V

    DC110V

    0:No

    1:Yes

    0:No

    1:Yes

    0:No

    1:Yes

    3:3A3B

    5:5A5B8:8A8B

    0:No

    1:Yes

    0:both

    sides1:bottom

    VB - 12 B /

    Note:

    1.Standardconfiguration:rockinghandle,charginghandle(1 setforevery3 switches)

    2.Pleasefill inthefollowingcolumnforotherconfigurationorspecialrequirements.

    Otherspecialrequirements

    ovrviw

    VBP indoor solid-sealed pole vacuum circuit breaker is 12kV-

    24kV three-phase alternating current 50Hz indoor high voltage

    switchgear; it's applicable to the control and protective cable,

    overhead line, transformer, current motor, current generator and

    capacitor bank in power transformation and distribution station,

    and can be widely used in power plant, power grid, metallurgy,

    petrochemical, and urban infrastructure construction projects

    such as airports, buildings, metros etc.

    chararii

    High reliability

    Compared with traditional integral type breaker, the number

    of solid-sealed polar pole breaker's parts and components,

    conductor faying surface, and connecting fasteners is greatly

    reduced, which simplifies the assembling of major loop, reduces

    the loop resistance, and greatly improves the reliability of

    connection of major galvanic circle.

    Stable insulating property

    Surface of vacuum interrupter is poured with epoxy, so the

    impact of polar pole's external environment on vacuum

    interrupter is reduced to the minimum; its insulating ability

    can protect the breaker from being affected by dust, moisture,

    beasties, dews and pollution, so it can fully meet the creeping

    distance requirements of class 2 polluted districts specified in

    GB/DL.

    Firmer structure

    Epoxy medium can protect the vacuum interrupter better,

    and protect it from accident mechanical damages during

    assembling and transportation.

    Miniaturization

    The use of epoxy as insulating medium can greatly shorten the

    phase spacing, and reduce the volume of the vacuum breaker

    and its auxiliary switch cabinet.

    Free o maintenance

    The entire polar pole is poured to an integral unit, so the

    vacuum interrupter can be better protected; the maintenance

    free feature of vacuum interrupter enables the breaker to be

    maintenance free.

    1. Dynamicconductingrod

    2. Guidesleeve

    3. Corrugatedtube

    4. Dynamiccoverboard

    5. Shieldcoverofcorrugatedtube

    6. Ceramicpackage

    7. Shieldtube

    8. Contactorsystem

    9. Staticconductingrod

    10. Staticcoverboard

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    14/49

    4 25

    Prdutcategry

    High & Lw Vlag swih

    More environment riendly

    Solid-sealed polar pole breaker can to a certain degree replace

    SF6 gas as protective insulation, so it's more environment

    friendly.

    Satisaction o diferent standards

    VBP indoor solid-sealed pole vacuum breaker can satisfy

    different GB, DL standards.

    Working condition

    Ambient temperature: upper limit +40C, lower limit -15C;

    Elevation: not exceeding 3000m

    Relative humidity: daily average value shall not be greater than

    95%; monthly average value shall not be greater than 90%

    Places: indoor, without fire, inflammables, explosion hazards,

    chemical corrosion and sharp vibration

    Seismic intensity: not exceeding grade 8;

    thial paramr

    Rated short-circuit

    breaking current 25:

    25kA;32:31.5kA; 40:40kA

    Product series

    Rated current

    06: 63A; 12:1250A;

    Rated voltage:

    12:12KV; 24:24KV;

    Solid-sealed polar pole

    Design serial number

    Vacuum circuit breaker

    tabl 1 elri Paramr

    n Im Ui thial paramr

    1 Rated voltage kV 12, 24

    2Rated

    insulation level

    Lightning impulse withstandvoltage

    kV

    To ground 75 (fracture 85), to ground 125 (fracture 145)

    1min power frequency withstandvoltage

    To ground 42 (fracture 48), to ground 65 (fracture 79)

    3 Rated frequency Hz 50

    4 Rated current A 630, 1250, 1600 2000, 3150, 4000

    5 R ated short-circuit break ing current

    kA

    25, 31.5, 40 40

    6 Rated short-circuit making current (peak value) 63, 80, 100 100

    7 Rated peak withstand current 63, 80, 100 100

    8 Rated short time withstand current/ duration kA/s 25/4, 31.5/4, 40/4 40/4

    9 Rated O/Ccurrent

    Single capacitor bank currentA

    630 800

    10 Back t o back capaci to r bank cu rren t 400

    11 Trip time ms 30

    12 Making time 45

    13 Mechanical endurance time(s) 20000

    14 Rated breaking time ms 60

    15 Rated operating voltage V AC/DC 220V/110V

    16 Rated operating current A 2.0/4.0

    17 R ated operating sequence O-0 .3s - C O - 180s-CO

    18 M ajo r loo p resi st an ce ( 20C) M 0 ln =630A60 ln=1250A 40 1600=Sln=s2000A30 3150A=Sln=S4000A25

    For other special requirements beyond the above stated

    application ambient conditions, please contact with the

    manufacturer.

    Mdl dripi

    tabl 2 Mhaial Paramr

    n. Im Uichararii paramr

    Rad vlag 12kV Rad vlag 24kV1 Contactor torque mm 91 131

    2 Contactor overtravel 3.5 0.5 3 0.5

    3 Average closing speed m/s 0.4~0.8 0.6~1.0

    4 Average trip speed 1.0~1.8 1.3~1.7

    5 Closing bounce time ms 2

    6 Asy nchronization of c losing and trip 2

    cirui brakr uid viw

    Heavy current breaker o rated voltage 12kVLow current breaker o rated voltage 12kV

    Low current breaker o rated voltage 24kV Heavy current breaker o rated voltage 24kV

    Secondaryplug

    Trippingbutton

    Closingandtrip

    indicationSpecification

    Counter

    Uppercontactarm

    Solid-sealedpolarpole

    PrimaryplugLowercontactarmInsertingholeofcharginghandleClosingbutton

    Springcharging

    indication

    Insertingholeof

    crankhandle

    Secondaryplug

    Trippingbutton

    Closingandtripindication

    Specification

    Insertingholeof

    crankhandle

    Coolinggrid

    PrimaryplugUppercontactarm

    Solid-sealedpolarpole

    CounterLowercontactarmInsertingholeofcharginghandleClosingbutton

    Springchargingindication

    Secondaryplug

    Counter

    Trippingbutton

    Closingandtrip indication

    Specification

    PrimaryplugUppercontactarm

    Solid-sealedpolarpole

    Lowercontactarm

    Insertingholeof charginghandle

    Closingbutton

    Springchargingindication

    Insertinghole ofcrankhandle

    Secondaryplug

    Tripbutton

    Closingandtripindication

    Specification

    Coolinggrid

    Primaryplug

    Uppercontactarm

    Solid-sealedpolarpole

    LowercontactarmCounter

    Insertingholeof charginghandleClosingbutton

    Springcharging

    indication

    Insertingholeof crank

    handle

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    15/49

    6 27

    Prdutcategry

    High & Lw Vlag swih

    Iral ruur irui brakr

    Circuitboard

    Tripcoil

    Tripspring

    Mainshaft

    Closingcoil

    Rocking-inclosure

    Closingspring

    Auxiliaryswitch

    Springdevice

    Draftgear

    Insertingmouthofcrankhandle

    ovrall dimi irui brak

    Overall dimension low current breaker o rated

    voltage 12kV

    1.Primaryplug; 2.Upperconductingrod; 3.Solid-sealedpolarpole;

    4.Lowerconductingrod; 5.Secondaryplug; 6.Counter; 7.Tripbutton;

    8.Closingandtripindication; 9.Handle; 10.Insertingholeofcharginghandle;

    11.Closingbutton; 12.Springchargingindication

    Overall dimension o rated voltage 24kV heavy current breaker

    1.Tripbutton; 2. Closingbutton; 3. Closingandtripindication; 4. Secondaryplug;

    5. Counter; 6. Insertingholeofcharginghandle; 7. Springchargingindication;

    8.Handle; 9.Primaryplug; 10.Uppercontactarm; 11.Solid-sealedpolarpole;

    12.Lowercontactarm

    1. Tripbutton;

    2. Closingbutton;

    3. Closingandtripindication;

    4. Secondaryplug;

    5. Counter;

    6. Insertingholeofcharginghandle;

    7. Springchargingindication;

    8.Handle;

    9. Primaryplug;

    10. Uppercontactarm;

    11. Solid-sealedpolarpole;

    12. Lowercontactarm

    Overall dimension o rated voltage 24kV low current breaker

    1. Tripbutton;

    2. Closingbutton;

    3. Closingandtripindication;

    4. Secondaryplug;

    5. Counter;

    6. Insertingholeofcharginghandle;

    7. Springchargingindication;

    8.Handle;

    9. Primaryplug;

    10. Uppercontactarm;

    11. Solid-sealedpolarpole;

    12. Lowercontactarm

    Prdu li h

    n.

    Mai dimi

    Mai mdl

    Widh

    auxiliary

    abi

    opraig

    vlag

    Ai-

    rip

    clig

    lur

    Rk-i

    lur

    oupu

    a

    ovr-

    urr

    rla

    earhig

    mdA B c D e F G H J K L M n

    1 VBP-1206B25

    W800

    DC/AC110220

    685 652 638 6 08 4 36 641 280 2 75 76 78 210 304

    0: No1:

    Yes

    0: No1: Yes

    0: No1: Yes

    3:3a3b5:5a5b8:8a8b

    0: No1: Yes

    0: bothsides

    1:bottom

    2 VBP-1212B25

    3 VBP-1212B32

    4 VBP-1212B40

    5 VBP-1216B32

    6 VBP-1216B40

    7 VBP-1220B32

    8 VBP-1220B40

    9 VBP-1232B40

    W1000 885 842

    840 5 87 350 700 296 3 10 85 86 275 29410 VBP-1240B40

    11 VBP-2406B25

    838 747 447 775 326 310 71 126 275 336 454

    12 VBP-2412B25

    13 VBP-2412B32

    14 VBP-2416B32

    15 VBP-2420B32

    16 VBP-2432B32 373 447 775 346 310 71 126 275 336 443

    e.g. VBP-2432B32/W1000 DC220V 100500

    Overall dimension heavy current breaker o

    rated voltage 12kV

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    16/49

    8 29

    Prdutcategry

    High & Lw Vlag swih

    shmai diagram rl lp Iallai ad mmiiig

    Inspection beore installation

    After unpacking the circuit breaker, check whether the

    assemblies are complete according to the packing list; confirm

    there are no damages in its appearance, no water log or

    impurities; make sure the screws are tightened, the major loop

    is firmly fastened and the product can run normally. After the

    inspection, clean the dust on the surface. Check the degree

    of vacuum of the vacuum interrupter using power frequency

    withstand voltage method (trip the breaker and impose power-

    frequency voltage to the fracture).Install the machine after it's

    qualified in inspection.

    Commissioning

    Products which are in good condition after unpacking

    inspection need no commissioning; only the breakers

    which do not meet the technical requirements or whose

    parts and components are changed need commissioning.

    (Commissioning shall be conducted with the help of the

    company's technicians; if detailed product information is

    required, please contact with our company directly)

    First of all, adjust the adjusting nut at the lower end of the

    dynamic conducting rod of vacuum interrupter, so that the

    vacuum interrupter's contactor torque and contactor overtravel

    can reach the specified value of the specification; Then check

    whether all parts of the shaft are correctly connected and

    whether the oil bumper is normal; Finally, adjust the device so

    that it can operate normally; there is be no clamping stagnation

    in manual operation, electro control, charging, closing and

    tripping. After commissioning of the entire breaker, it shall meet

    the requirements of parameters list in table 2.

    oprai ad maia

    Operational readiness inspection

    Check whether the installed base of breaker is level and whether

    the fundamental plane can bear the weight of switch and

    relevant electrical force;

    M:chargingmotor

    CC:closingelectromagnet

    TC:tripelectromagnet

    1WK1-5:limitswitch

    FK:auxiliaryswitch

    Kj:controlrelay

    C1-C2:capacitor

    Rd:fuse

    R1-R4:resistor

    S8-S9:auxiliaryswitch(containedbythechassis)

    D1-D6:diode

    Fj:auxiliaryrelay

    Check whether the connecting line is broken;

    Check whether the breaker is damaged mechanically;

    Conduct power frequency withstand voltage test to the breaker

    to check its insulation level.

    Manual closing and trip

    Manual charging: insert the charging handle from the inserting

    hole of charging handle on the panel to store energy; when the

    device ticktocks, and the charging sign points to the charging

    position, it shows the spring device has finished charging.

    Manual closing: press the closing button on the panel, the

    closing-trip sign will show the closedposition, meaning that it's

    closed.

    Manual trip: press the trip knob on the panel, the closing-trip

    sign will show the tripping position, meaning that it's tripping.

    Electric closing and trip

    Charging operation: connect the control loop of the breaker,

    power on and after the charging signal is sent out, the breaker's

    control wiring is powered on; the motor will be powered on

    through the control loop and then it rotates and drives the

    closing spring to store energy. After the closing spring finishes

    charging, the limit switch will cut off the motor power and the

    charging sign will point to the charging position.

    Closing operation: after the closing instruction is given out,

    the closing coil excites and the iron core moves to hit the

    closing interlocking; the closing spring releases energy and the

    breaker will be switched on; after the closing operation, the

    closing-trip sign will show the closed position, and under suchcircumstances the charging device is in free state.

    Tripping operation: after the tripping instruction is given out, the

    trip coil excites and the iron core moves to separate the tripping

    interlocking; the tripping spring releases energy and the breaker

    will be switched off; after the tripping operation, the closing-trip

    sign will show the switch-off state.

    Test position Working condition

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    17/49

    0 31

    Prdutcategry

    High & Lw Vlag swih

    Maintenance and repair

    The maintenance intervals and contents are changing along

    with the service conditions, on/off times and the level of

    breaking current.

    Normally running breaker shall be maintained regularly; clean

    the dust on the insulation surface, and all moving parts shall be

    poured with lubricating oil regularly;

    Check whether the screws are loosened after operating for

    2000 times; if screws are l oosened, tighten them timely;

    Check immediately when there are closing or tripping faults;

    During maintenance, the vacuum interrupter shall not be hit

    with hard objects (such as tools);

    Mechanical features testing and adjustment of the breaker

    shall only be conducted by professionals.

    srag

    The breaker shall be placed in the room that is dry, ventilated,

    damp proof and has no noxious gas; pay attention to the

    following notes and remember to fi x the dust-proof cover.

    The storage place shall be dry and kept out of the sun;

    Avoid corrosive gas and dust;

    Avoid places with sharp variation in temperature (sharp

    variation in temperature may cause frosting, which may reduce

    the performance or cause defects).

    Aahm papr

    Quality certificate

    Factory inspection report

    Checklist of attachment spares, parts and accessories

    Packing list

    Installation and instruction manual

    Other relevant documents

    ordrig irui

    Type and name of breaker

    Rated voltage (kv)

    Rated current (A)

    Rated short-circuit breaking current ( kA)

    Quantity

    Operating device voltage (AC/DC)

    Accessories

    If users have other special requirements (such as elevation,

    temperature etc.), please make notes before placing orders.

    n. nam U

    1 Manual charg ing handl e For manual charg ing of breaker

    2 R ocking handl e of breaker R ocking in and out of breaker

    3 58-core a ir socket Plug match between secondary socket and vacuum c ircuit breaker

    Li ari

    Prdu Lyp Irmai sh

    Procurement companyCompany Add.

    Proposing Dept. Tel:

    End customer

    Model required

    ModelRated

    voltageRated

    currentTypeseries

    Ratedbreakingcurrent

    Structuralfeature

    Auxiliarycabinetwidth

    Operatio-nal power

    supply

    Anti-trip

    Closingclosure

    Rock-inclosure

    Outputcontact

    Over-currentrelease

    Earthingmode

    Referencevalue

    VBP - 12:12kV

    06:630A12:1250A16:1600A20:2000A25:2500A32:3150A40:4000A

    B25:25kA

    32:31.5kA40:40kA

    Vacuum: withVEZ

    A: with KYNB: special

    W650W800

    W1000

    AC220VAC110VDC220VDC110V

    0: No1: Yes

    0: No1: Yes

    0: No1: Yes

    0: No1: Yes

    0: both sides1: bottom

    VBP - 12 B

    Note:Standard configuration: rocking handle, charging handle (1 set for every 3 switches)Please fill in the following column for other configuration or special requirements.

    Other special requirements

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    18/49

    2 33

    Prdutcategry

    High & Lw Vlag swih

    VK Vacuum Circuit Breaker (Designated Sales Region)

    Miiaurizai dig

    It adopts three-phase insulating boot which can be used

    for inter-phase and phase-ground insulation and support of

    interrupter; it's delicate in appearance, compact in structure,

    small in size and light in weight. Rear part of the insulating boot

    has insulation cap which can realize the omniseal of breaker; it

    can be furnished with a 650 mm wide cabinet.

    Larg rpig dia vauum irrupr

    Surface creeping distance of the corrugated pipe interrupter

    produced by Toshiba Corporation exceeds 240mm, making it

    safer and more reliable in use.

    cld prai

    Bottom of the breaker has a chassis and the use of cabinet can

    realize closed operation, making it safer and more convenient.

    High rliabiliy

    From design to production, VK type vacuum circuit breaker is

    under strict quality control system.

    L maia

    VK vacuum circuit breaker needs no special maintenance;

    besides, with special structural design, it's easy to operate and

    repair.

    Lg rvi li

    Mechanical endurance of Vk vacuum circuit breaker is >20000

    times, and rated short-circuit current opening is >50 times.

    n pllui virm

    Vacuum circuit breaker has no decomposed product and will

    generate no pollution to environment; there is little noise during

    its operation.

    Reliable vacuum circuit breaker

    With the technical support of Toshiba which is most

    experienced in the manufacturing of vacuum equipment

    and the introduction of Toshiba's advanced manufacture and

    monitoring equipment, Guangzhou Toshiba Baiyun Electric

    Equipment Co., Ltd. will provide good quality and highly reliable

    vacuum circuit breakers to the vast customers.

    Toshiba world leading vacuum technique

    Toshiba has been dedicated to improving and developing

    vacuum technique since 1962.

    Now its annual output exceeds 300 million, which is leading

    in the world

    The p roduct has l arge surfac e cre eping distance and

    strong pollution resistance ability, which can meet the market

    demands in China

    Patented technology of longitudinal magnetic field, strong

    ability in opening circuit

    More than 40 years' experience in manufacturing and

    operation, high reliability

    ovrviw

    Product overview

    VK vacuum circuit breaker is produced by Guangzhou Toshiba

    Baiyun Electric Equipment Co., Ltd. through introducing the

    improved technology of Toshiba. The product is of omniseal

    handcart type; its general layout is suspension type; it adopts

    the three-phase integral insulating boot and is used for inter-

    phase and phase-ground insulation and fixed interrupter; It

    uses the charging spring device, has the functions of manual

    charging and electric charging, and has anti-bouncer. The

    operating device has mechanical and electric interlock which

    can prevent maloperation. At its bottom there is chassis for

    closed operation.

    VK type vacuum circuit breaker is 3.6 ~ 12kV three-phase

    alternating current 50Hz indoor high voltage switchgear; it can

    be used for the control or protection of power transmission and

    distribution system in power plants, substations and industrial

    and mining companies, especially for opening circuit in places

    with vital power load and frequent operations.

    Characteristics

    Rliabl brakig prrma

    VK type vacuum circuit breaker adopts the high-performance

    vacuum interrupter produced by Toshiba Corporation; during

    breaking, the electric arc in the vacuum can diffuse at a high

    speed, which can realize arc quenching when the current

    reaches zero for the first time.

    sa ad rliabl

    Vacuum circuit breaker takes vacuum as the arc-extinguishing

    medium which will generate no explosion and fire during

    breaking.

    saiai dir adard

    VK vacuum circuit breaker can meet GB, DL, IEC, and JEC

    standards.

    Working condition

    Ambient temperature: upper limit +40C, lower limit - 15C;

    Elevation: not exceeding 1000m;

    Relative humidity: daily average value shall not be greater than

    95%; monthly average value shall not be greater than 90%;

    Places without fire, inflammables, explosion hazards, chemical

    corrosion and sharp vibration;

    Seismic intensity: not exceeding grade 8;

    For special operating ambient, please contact with the

    manufacturer.

    Model description

    Structural

    feature

    Vacuum:withVEZ

    A:withKYN B:special

    25:25kA; 32:31.5kA

    40:40kA; 50:50kA

    06:630A

    12:1250A

    16:1600A

    20:2500A

    32:3150A

    40:4000A

    12kV

    Ratedbreakingcurrent

    Type series

    Rated current

    Rated voltage

    Product series VKvacuumcircuitbreaker

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    19/49

    4 35

    Prdutcategry

    High & Lw Vlag swih

    Mechanical parameters

    sial viwthial paramr

    Electric parameters

    n. nam (ui) thial paramr

    1 Rated voltage(kv) 12

    2 Rated current(A) 630, 1250, 1600 2000, 2500, 3150, 4000

    3 Frequency (Hz) 50

    4 Rated short-circuit breaking current( kA) 25, 31 .5. 40 40. 50

    5 Rated short-circuit making current ( kA) 63, 80, 100 100, 125

    6 4s rated short time withstand current ( kA) 25. 31 .5. 40 40. 50

    7 Rated peak withstand current ( kA) 63, 80. 100 100. 125

    8 Rated O/Ccurrent

    Single capacitor bank current (A) 630 8009 Back to back capacitor bank current (A) 400

    10 1min power frequency withstand voltage(kV) 42 (fracture: 48)

    1 1 I mp ul se w it hs ta nd v ol ta ge ( k V) 7 5 ( fr ac tu re : 8 5)

    12 R ated operating procedure O-0 .3s-CO-180s-CO (40 , 50kA jO-180s-CO-180s-CO)

    13 R ated short-c ircuit current operation t imes 50

    14 Mechanical endurance (times) 30000 20000

    15 Rated open circuit time (ms) 60

    16 Trip time(ms) 30

    17 Making time(ms) 45

    18 R ated opera ti ng volt age( V) AC/DC 220V/110V

    19 Rated operating current(A) 2.0/4.0

    20 Single-phase major loop resistance (without primary plug)I n=630A In=1250A 1600AI n2000A I n2500A

    R60na R40na R30nD

    n. nam (ui)chararii paramr

    Brakig urr40KA Brakig urr = 50kA

    1 Open contact clearance (mm) 8.01 9.01

    2 Contacting travel (mm) 30.5

    3 Average closing speed (m/s) 0.4-0.8

    4 Average trip speed (m/s) 0.8-2.0

    5 Ju mp ti me of co nt act or clos ing (ms )

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    20/49

    6 37

    Prdutcategry

    High & Lw Vlag swih

    Structure o the operating device

    opraig dvi

    The operating device adopts four-bar structure. During

    closing, the closing spring drives the closing camshaft

    to rotate, and rotation of cam will press the four bars to

    drive the main shaft to close. During tripping, the tripping

    fanning strip rotates and drives the connecting rod to

    activate the four bars, so that the four bars lose balance;

    the quick moving of four bars will drive the rotation of the

    main shaft to open.

    On the device there is a line indicating the abrasion state of

    contactor and the abrasion of contactor can be observed

    from its front side. For details, please refer to the validation

    of contactor abrasion in the maintenance and repair part.

    Lad hararii

    During closing of vacuum circuit breaker, the closing spring

    release energy and draw and press the trip and contractor

    spring respectively; the trip and contactor spring store energy.

    Figure 3.3 Outline drawing of heavy current breaker(2500-4000A)

    Secondaryplugofcontrolloop

    Insertingholeof charginghandle

    Closing/tripi ndication

    (closing:red;trip:green)

    Counter

    Insertingholeof crankhandle

    Tripbutton

    Closingbutton (underneaththe interlocking

    coverboard;thecoverboardis optional)

    Chargingindication

    (white:discharged;yellow:charged)

    Specification

    Primaryplug

    Insulationcover

    Vacuuminterrupter

    Insulatingboot

    Figure 3.4 View of device on the breaker

    Closingspri ng

    Circuitboard

    Auxiliaryswitch

    Closingcoil

    Deviceinterlock

    Contactorabrasion mark

    Electric chassis operationmotor(optional)

    Rockingin interlockelectromagnet

    Rocking-incl osure

    Tripcoil

    Tripspring

    Mainshaft

    Contactorspring

    Draftgear

    Trippingfanningstrip

    Rachet

    Manualcharging gear

    Closinghalfshaft

    Counter

    Chargingmotorandgearbox

    Triphalfshaft

    Limitswitch

    Chargingcamshaft

    Mainshaft

    Contactorspring

    Figure 3.5 Device Module View

    Trippaddle

    Trippingfanningstrip

    Closingspring

    Tripbutton

    Closingbutton

    Closingreleasingslab

    Closingcoil

    Tripcoil

    Vacuuminterrupter

    Chargingmotorandgearbox

    Tripspring

    Closingwedge Contactorspring

    Figure 3.6 Device Module View

    Comparison between VK device and like products :

    The most proper load characteristics Higher calorie running

    Low fusion welding rate of vacuum interru pter contactor

    Figure 3.7 Load characteristics of the device

    During tripping, the trip and contactor spring release energy

    and act together to separate the dynamic & static contactors of

    the vacuum interrupter quickly.

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    21/49

    8 39

    Prdutcategry

    High & Lw Vlag swih

    B Internal structure C Conditions at the arc

    Figure 3.8 Structure of vacuum interrupter and drawing of arc extinction principle

    Staticcontactor

    Ceramicpackage

    Metalbellows

    Shieldcover

    Dynamicc ontactor

    Structure and principle o vacuum interrupter

    The interrupter adopts the longitudinal magnetic field electrode

    technology and controls the electric arc through the magnetic

    field to realize fast arc extinction.

    With the action of the current flowing through the electrode,

    there is longitudinal magnetic field generated between the

    contactors. With the action of the longitudinal magnetic field,

    the electric arc rotates on the electrode surface and diffuse to

    the electrode surface fast, so arc voltage is low and stable and

    there is little contact loss, so that the contactor of interruptercan work for a longer time.

    trippig prai

    Press the trip button and the breaker opens. Then, the closing

    and trip indication shows "open".

    opraial mhd ad ai pifai

    Manual operation

    chargig prai

    See figure 4.1-4.2: insert the charging handle, and shake it

    several times (about 7 times) and it will click. Then the closingspring charging indication changes from white (discharged) to

    yellow (charged), showing that it has entered to the charged

    state.

    clig prai

    Press the closing button and the breaker closes. Then, the

    closing and trip indication shows "closed"; closing charging

    indication shows "white" (discharged).

    A Currentandmagneticfield

    Inserting hole of

    charging handle

    Figure 4.1 Manual operation drawing

    Trip button

    Closing button

    Closing and

    trip indication

    Charging

    indication

    Figure 4.2 Manual operation indication

    Warning

    The following operations may cause breaker defects:

    Press the closing button under closed position.

    Press the closing button while pressing the trip

    button.

    Electric operation

    chargig prai

    Connect the control loop of the breaker and power on,

    the current motor will rotate and the closing spring begins

    charging. When the charging indication changes from "white"

    (discharged) to "yellow" (charged), it means the closing spring

    has finished charging.

    clig prai

    After the closing instruction is given out, the closing coil excites

    and breaker is closed. After it's closed, the current motor

    continues rotating, till the closing spring finishes charging.

    The closing and trip indication will show "closed". The closing

    spring's charging indication shows "yellow" (charged).

    trippig prai

    After the tripping instruction is given out, the trip coil excites

    and breaker is open. Then, the closing and trip indication shows

    "open".

    Action specication

    Ai rl lp

    Note

    Do not operate the breaker when the panel

    is discharged, in case there are damages and

    accidents.

    circumstances, if the closing instruction is given out (impose

    pressure on +HM-N1 point), the breaker will close when the

    closing coil CC excites (about 40ms). When the breaker closes,

    the auxiliary switches b5 and b6 switch and closing coil CC

    terminates excitation. Then the stabilizer Y excites and forms the

    protective circuit of closing and tripping circuit.

    Charging action

    When the breaker closes, the limit switch closes at the same

    time; the control relay X excites and starts the charging function.

    After the control relay excites, the charging circuit is switched

    on; the current motor M rotates and drives the spring to charge;

    after the spring finishes charging (about 4s), the li mit switch LS1-

    LS2 breaks, and control relay X terminates excitation.

    Tripping action

    Only a1, a2 and TC are related to breaker tripping; when

    conditions allow, if the tripping instruction is given out (impose

    pressure on +FM-N2 point), the breaker will open when the

    trip coil excites (about 25ms). When the breaker opens, auxiliary

    switches a1 and a2 switch and trip coil TC terminates excitation.

    Note: refer to section 5.3 Secondary Schematic Diagram for all

    contact points.

    DangerousPlease keep off, for fear of casualties due to

    electric shock.

    Closing action

    After the closing spring finishes charging, if the breaker is in

    open status and meet the requirements for closing of the

    breaker, its control loop is shown in figure 4.3. Under such

    1.Whenthelimit switchLScloses,the closingspringbeginscharging

    2.Whenthelimit switchLSopens,theclosingspringfinishescharging

    3.Closinginstruction; 4.Theclosingactionbegins(thetripspringbeginscharging)

    5.Trippinginstruction; 6.Trippingactionbegins; 7.Breakercloses; 8.Breakeropens

    Figure 4.3 Control Loop Operation

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    22/49

    0 41

    Prdutcategry

    High & Lw Vlag swih

    Dvi ai

    NoteKeep your hands or any part of your body from

    the device, for fear of jammed injuries.

    Closing action

    Figure 4.4 (A) is the illustrative drawing showing the open status

    of the breaker, when the closing spring is charging (waiting for

    closing). Under such circumstances, press the closing button

    or drive the closing wedge through the closing coil, so that the

    cam can rotate fast as shown in figure 4.4 (B), that's the closed

    position.

    Charging action

    The breaker is kept at the closed postion as shown in figure 4.4

    (B); drive the charging crank handle electrically or manually to

    rotate the closing cam and start the charging function. When

    the roller on the closing cam touches the closing wedge, it

    finishes charging.

    Tripping action

    Press the trip button or drive the trip axis through the trip coil

    and the device will return to the open status as shown in figure

    4.4 (A).

    ovrall dimi

    Low current

    1Primaryplug

    2Vacuum interrupter

    3 Handle

    4Counter

    5Closingandtripindication

    6Insertingholeofcharginghandle

    7Secondaryplug

    8Springchargingindication9Closingbutton

    10Tripbutton

    Figure 5.1 Outline Drawing of Low Circuit Breaker

    Figure 4.4 Operation of Device

    A B

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    23/49

    2 43

    Prdutcategry

    High & Lw Vlag swih

    Product selection sheet

    n.

    ------------------------------------- R-

    markMaimdl

    sriW. aux.

    abiU

    Mai dimi Ai-rip

    cliglur

    Rak-ilur

    oupua

    oc.rip

    earhigmd

    elrihaiA B c1 c2 D e F G H J K L M n P W X Y

    1VK-

    1206B25W650

    AC/DC110220

    528502494494608 658 44363729828981 71322 304165

    35

    20189

    0: No1:

    Yes

    0: No1: Yes

    0: No1: Yes

    0:No1:

    Yes

    0: bothsides

    1:bottom

    0: No1: Yes

    WithToshibaVENcabinet

    2VK-

    1212B2549

    3VK-

    1206B25

    W 800 685652638638608 658 44363729828981 71322304200

    35

    38261

    4VK-

    1212B25

    495VK-

    1212B32

    6 VK-1212B40

    7VK-

    1216B4070

    8VK-

    1220B40

    9VK-

    1225B40

    W1000 880 852836840712 762 472746375284 83 86343387275

    109

    25362

    10VK-

    1232B40

    11VK-

    1240B40

    12VK-

    1212B5070

    13VK-

    1232B50109

    14VK-

    1240B50

    15VK-

    1206B25

    A

    W 65 0 5 28 50 24 94 49 4598

    (608)648

    (658)436

    (443)637275280

    76(81)

    78(71)

    322294

    (304)150

    35

    20189

    withKYN28/KYN

    44cabinet

    16VK-

    1212B2549

    17VK-

    1206B25

    W 800 685652638638598

    (608)648

    (658)436(443)

    63727528076

    (81)78

    (71)322

    294(304)

    210

    35

    28261

    18VK-

    1212B25

    4919VK-

    1212B32

    20VK-

    1212B40

    21VK-

    1216B4070

    22

    VK-

    1220B40

    23VK-

    1225B40

    W 1000 880852836840587 637 350

    700

    310296 85 86343262275

    109

    25362

    24VK-

    1232B40

    25VK-

    1240B40

    26VK-

    1212B50

    746

    70

    27VK-

    1232B50109

    28VK-

    1240B50

    e.g.

    Note: 1. Number in the brackets means special models

    2. For other models, please contact with the manufacturer

    Heavy current

    Chassis

    Note1:Chooseonefromthetwo groundingmodes

    Figure 5.2 Chassis Mechanism

    1 Primaryplug

    2 Vacuuminterrupter

    3 Handle

    4 Counter

    5 Closingandtripindication

    6 Insertingholeofcharginghandle

    7 Secondaryplug

    8 Springchargingindication

    9 Closingbutton

    10 Tripbutton

    Figure 5.3 Outline Drawing of Heavy Current Breaker

    Groundingbusbar

    Groundingclamps

    attwosides

    interlockpl ate

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    24/49

    4 45

    Prdutcategry

    High & Lw Vlag swih

    VY Vacuum Circuit Breaker (Designated Sales Region)

    ovrviw

    VY-40 indoor AC high voltage vacuum circuit breaker is mainly

    used in three-phase alternating current 50Hz, 40.5kV power

    system for opening and closing load current, overload and

    short-circuit current; it can be used in the places with frequent

    operation, and is suitable for the control and protection in

    power plants, transformer substations, power equipment and

    power lines.

    The breaker adopts spring charging control mechanism and

    the operational power supply can be DC or AC, which is very

    convenient; the product is characterized by good performance,

    high reliability, convenience in repair and maintenance, and

    long maintenance interval.

    chararii

    The breaker adopts the integral ar rangement structure

    with the vacuum interrupter on the top and the device at the

    bottom, which is convenient for commissioning;

    It adopts the compound insulation structure with air and

    epoxy material, which is compact in design and li ght in weight;

    The inter rupter a dopts l ongitudinal magnetic f ield a rc

    extinction, which is of low closure property and fine asymmetric

    breaking performance;

    Simple spring control mechanism; 10000 times of

    maintenance free operation;

    It adopts the lead screw propelling device, making it labor

    saving, stable, and have good self-locking performance.

    Wrkig dii

    Ambient temperature: upper limit +40C, lower limit - 15C;

    Elevation: not exceeding 1000m;

    Relative humidity: daily average value shall not be greater than

    95%; monthly average value shall not be greater than 90%;

    Places: indoor, without fire, inflammables, explosion hazards,

    chemical corrosion and sharp vibration

    Seismic intensity: not exceeding grade 8;

    Special requirements can be made in orders.

    Mdl dripi

    Irdui ruural ui

    Structure

    VY - 40 indoor AC high voltage vacuum circuit breaker (breaker

    for short hereinafter) adopts the vertical arrangement structure,

    which effectively reduces the depth of breaker. The breaker

    adopts compound insulation structure; the three-phase

    interrupter and conductors are separated by three independent

    epoxy insulating cylinders. Compound insulation reduces the

    size of breaker. With the use of compound insulation structure,

    the breaker can meet the requirements of air i nsulation distance

    and creeping distance in normal operation. The main galvanic

    circle's vacuum interrupter and conductor are installed in the

    insulating cylinder, so the inter-phase distance is only 300mm.

    Electrical connection of the major loop adopts fixed type

    Designseriesnumber

    Ratedshort-circuitbreakingcurrent(kA):25, 31.5

    Ratedcurrent(A):J:63 0,M:1250,N:1600 ,P: 2000

    Ratedvoltage: 40.5kV

    Productseries

    Vacuumcircuit breaker

    connection, which has high reliability.

    The loop resistance of vacuum interrupter under rated contact

    pressure is less than 50u. :

    The control device adopts the spring control mechanism

    especially designed for such new style breaker and is fixed inside

    the framework. Its design characteristics are more suitable for

    such vertical arrangement of the breaker, making it become

    an inseparable part of the entire structure of the breaker. The

    device is simply designed and its output curve can well meet

    the requirements of the interrupter. Its performance can better

    fit the characteristics and requirements of 40.5kV vacuum circuit

    breaker.

    The breaker is generally reasonable in overall arrangement,

    delicate in appearance and simple and flexible in operation;

    it's characterized by reliable electric property, long service life,

    convenient repair and the maintenance free feature. It's suitable

    for various places and can be used in the places with harsh

    operating conditions.

    Circuit breaker outside view

    Figure 1 Panel Appearance

    Counter

    Closingbutton

    Tripbutton

    Chargingindication

    Trippingindication

    Insertingholeof charginghandle

    Specification

    Secondaryplugof

    controlloop

    Handle

    Insertingholeof

    handle

    Operatinginstructi on

    forpropellingdevice

    Emergencytrip button

    Earthinginterlock handle

    Primaryplug

    Contactarm

    Openingpart

    Screwrod

    Figure 2 Circuit Breaker Appearance

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    25/49

    6 47

    Prdutcategry

    High & Lw Vlag swih

    opraig priipl

    Arc extinction principle

    The vacuum interrupter for the breaker has high degree of

    vacuum. When the dynamic and static contactors are charged

    and open when driven by the operating device, vacuum arc

    will be produced between the two contactors. Besides, due

    to the special structure of contactor, there may be proper

    longitudinal magnetic field generated between two contactors.

    As a result, the vacuum arc will be diffused and spread uniformly

    on the surface of the contactor to be combusted, thereby to

    maintain very low arc voltage. When the current reaches zero

    naturally, residual ions, electronics and metallic vapor will be

    compounded or condensed on the contactor surface and

    shield cover within microseconds to extinct the arc; insulation

    strength of the medium at the interrupter fracture will be

    restored fast to realize breaking. The vacuum circuit breaker uses

    longitudinal magnetic field to control the vacuum arc, so it has

    powerful and strong ability for breaking current.

    Staticc ontactor

    Ceramicpackage

    Metalbell ows

    Shieldcover

    Dynamiccontactor

    A Current and magnetic field B Internal structure C Conditions at the arc

    Action

    a) Mr hargig prai

    Connect the control loop of the breaker; power on and the

    motor will start running. When the discharged and charged

    indicationchanges from "discharged" to "charged", the motor

    stops. Then the closing spring is charged.

    b) Maual hargig praiTake the baffle of the handle inserting hole and insert the

    manual charging handle (about 280mm, accessory) to the

    inserting hole; shake the charging handle several times (about

    seven times) and it will snap and become charged. Note) Times

    of action of the operating handle will change along with the

    change of action angles.

    After the device is charged, the breaker will close as long as it

    receives the closing instruction at any time.

    Insertingholeof

    charginghandle

    Figure 3 Manual Operation Drawing

    ) clig prai

    After the device closing spring is charged, such state will be kept

    due to the pressure of the wedge. Gusset of the wedge tends

    to move in the direction of tripping under the driving force of

    the cam roller. Now rotate the closing half shaft clockwise to the

    release position (about 20) and the gusset of wedge that keeps

    the charging state will run fast clockwise; the charging state will

    terminate, and closing spring releases energy fast and drives

    the cam to rotate anticlockwise. Meanwhile, the linkage gear

    will run to the closing position as driven by the cam to close the

    device. Then the travel switch will reset; the motor powers on

    and drives the closing spring to charge again, so that the device

    is closed and charged.

    d) trippig prai

    The closed state of device is kept by the gusset and half shaft

    of linkage gear. The gusset tends to move along the release

    direction under the load of breaker; at such time if the tripping

    half shaft is rotated to the release position anticlockwise

    (about 20), the gusset will run fast anticlockwise, and thus the

    balanced state of linkage gear will be terminated. It will move to

    the tripping positin under load and the device is open.

    ) Ai pifai

    Ai rl lp

    Closing actionAfter the closing spring finishes charging, if the breaker is in

    open status and meets the requirements for closing of the

    breaker, its control loop is shown in figure 4.3. Under such

    circumstances, if the closing instruction is given out (impose

    pressure on +HM-N1 point), the breaker will close when the

    closing coil CC excites (about 40ms). When the breaker closes,

    the auxiliary switches b5 and b6 switch and closing coil CC

    terminates excitation. Then the stabilizer Y excites and forms the

    protective circuit of closing and tripping circuit.

    Warning

    Do not operate the breaker when the panel

    is discharged, in case there are damages and

    accidents.

    DangerousPlease keep off, for fear of casualties due to

    electric shock.

    Charging action

    When the breaker closes, the limit switch LS1 -LS2 closes at the

    same time; the control relay X excites and starts the charging

    function. After the control relay excites, the charging circuit is

    switched on; the current motor M rotates and drives the spring

    to charge; after the spring finishes charging (about 4s), the limit

    switch LS1-LS2 breaks, and control relay X terminates excitation.

    Tripping action

    Only a1, a2 and TC are related to breaker tripping; when

    conditions allow, if the tripping instruction is given out (impose

    pressure on +FM-N2 point), the breaker will open when the

    trip coil excites (about 25ms). When the breaker opens, auxiliary

    switches a1 and a2 switch and trip coil TC terminates excitation.

    Note: refer to the device wiring diagram for the contact points

    Action o control loop

    1. When the limi t switch LS closes, the closing spring begins charging

    2. When the limi t switch LS opens, the closing spring finishes charging

    3. Closing instruction

    4. The closing action begins (the trip spring begins charging)

    5. Tripping instruction

    6. Tripping action begins

    7. Breaker closes

    8. Breaker opens

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    26/49

    8 49

    Prdutcategry

    High & Lw Vlag swih

    thial paramr

    1. Primary plug ; 2. Vacuum interrupter ; 3. Handle ; 4. Counter, charging, closing and tripping indication ; 5. Earthing interlock handle

    6. Inserting hole of charging handle ; 7. Emergent trip button ; 8. Inserting mouth of crank handle ; 9. Closing and trip button ; 10. Specification

    n. Im Ui Paramr valu

    1 Rated voltage

    kV

    40.5

    2 R at ed i ns ul at io n le ve l1min power frequency withstand voltage (effective value) 95

    Lightning impulse withstand voltage (peak value) 185

    3 Rated frequency Hz 50

    4 Rated current A 630 1250 1600 2000

    5 4s rated short time withstand current

    kA

    25, 31.5

    6 Rated peak withstand current 63, 80

    7 Rated short-circuit breaking current 25, 31.5

    8 Rated short-circuit making current 63, 80

    9 Rated operating sequence O-0.3s-CO-180s-CO

    10 Breaking time ms 60

    11 Breaking times of rated short-circuit breaking current time(s) 20

    12 Breaking current of single capacitor bank A

    630

    13 Breaking current of back to back capacitor bank 400

    14 Rated operating voltage V AC110/220, DC 110/220

    15 Mechanical endurance time(s) 10000

    Mhaial aur paramr

    thial paramr r hargig mr rl mhaim

    n. Im Ui Paramr valu

    1 Contactor torque mm 21 1

    2 Contactor overtravelmm

    4 0.5

    3 All owable abrasion thickness of overtrave l contactor 3

    4 Average closing speedm/s

    0.8~1.2

    5 Average trip speed 1.2~17

    6 Making time

    ms

    35-65

    7 Trip time 15~22

    8 Contactor closing bounce time ^5

    9 C lo si ng a sy nc hr on iz at io n o f t hr ee -p ha se c on ta ct or 2

    1 0 T ri p a sy nch ro ni za ti on o f t hr ee -p ha se c on ta ct or 2

    11 Cushion stroke of buffer mm 71

    12 Loop resistance of a ll phases (excl ud ing contact arm) 40

    Rad vlag (V) Rad upu pwr (W) nrmal wrkig vlag

    DC110/AC110 DC220/AC220 70 85%~110% Rated voltage

    thial paramr r lig ad rip il

    Rad wrkig vlag (V) DC110 DC220

    cil hmi valu a 20c () 27.7 10% 126 10%

    cil ur 1700 3880

    Rad praig urr (A) 4 2

    nrmal wrkig vlag rag Reliable tripping at 65%-120% rated working voltage; no tripping lower than 30% rated working voltage

    Li ari

    n. nam U

    1 Manual charging handle For manual charging of breaker

    2 Rocking handle of breaker Rocking in and out of breaker

    3 Air socket Connection of the secondary loop of breaker

    Prdu vrall dimi

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    27/49

    0 51

    Prdutcategry

    High & Lw Vlag swih

    Wiringdiagramofhedevie

    Pakig, rapr, apa hk ad

    rag

    Packing and transport

    VY-40 indoor vacuum circuit breaker is independently packed.

    It's fixed to a wooden stand and covered with plastic paper to

    prevent penetration of water. During packing and transporting,

    the breaker shall be open and the product can't be turned over

    or rolled.

    Acceptance check upon reception

    Check whether the packing is in good condition;

    Consult the packing list and check whether the documents,

    accessories, and spare parts are complete;

    Check whether the technical parameters on the nameplate

    of breaker and quality certificate meet the requirements of

    ordering.

    Storage

    The breaker shall be placed in the room that is dry, ventilated,

    damp proof, shock-resistant and noxious gas proof. If it's placed

    for a long time, spread lubricating oil to the transmission parts

    and check whether the environment meets the requirements

    regularly.

    Weldingpanelof

    printedcircuit

    1 LX Limit switch LXW18-11 1

    2 R4 Resistor RJ-2W-24KQ/6.8KQ 2

    3 R3 Resistor RJ-2W-3KD.750Q 1

    4 R2 Resistor RJ-2W-12KQ/3KQ 2

    5 R1 Resistor R - 2W -1 2

    6 RD Fuse BGXP 250V 2A/4A 1

    7 C2 Capacitor CL11-600V0.1 m F/400V0.1 [iF 1

    8 C1 Capacitor CL11-400V 0.1 M F/200V 0.22 u F 1

    9 D1~D5 Diode 1N5407 800V 3A 5

    10 FJ Auxiliary relay JQX-13F2 DC110V/48V 1

    11 KJ Control relay JQX-13F4DC110V/48V 1

    12 FK Auxiliary switch F10-10II/W2 10a10b 113 1WK1~3 Limit switch LXW16-11 DC220V 16A 3

    14 HQ, FQClosing and tripelectromagnet

    MFH-10 DC220V/110V 2

    15 D Charging motor ZYJ55-1A DC220V/110V rev 10r/min torque 24.5NM 1

    Iallai ad mmiiig

    Inspection beore installation

    Afther unpacking, check whether the parts and components

    of breaker are complete according to the packing list; check

    whether the breaker is wetted and damaged and whether it can

    run normally. After the inspection, clean the dust on the surface.

    Check the degree of vacuum of the vacuum interrupter using

    power frequency withstand voltage method (trip the breaker

    and impose power-frequency voltage to the fracture at 95kV/

    min). Install the machine after it's qualified in inspection.

    Commissioning

    Products which are in good condition after unpacking

    inspection need no commissioning; only the breakers which

    do not meet the technical requirements or whose parts andcomponents are changed need commissioning

    First of all, adjust the height of knuckle bearing and oil bumper

    at the lower end of the dynamic conducting rod of vacuum

    interrupter, so that the vacuum interrupter's contactor torque

    can reach the specified value of the specification; Adjust the

    nuts on the contactor spring properly so that the contactor

    over travel can reach the value specified in the technical

    specification; Then check whether all parts of the shaft are

  • 7/30/2019 Vol. 12-High & Low Voltage Switch

    28/49

    2 53

    Prdutcategry

    High & Lw Vlag swih

    correctly connected and whether the oil bumper is normal. Finally, adjust the device so that it can operate normally; make sure there

    is be no clamping stagnation in manual operation, electro control, energy storage, closing and tripping. After commissioning of the

    entire breaker, it shall comply with the parameters listed in table 2.

    ZN85-40.5 Indoor AC High Voltage Vacuum Circuit Breaker

    Aahm papr

    Quality certificate

    Factory inspection report

    Checklist of attachment spares, parts and accessories

    Packing list

    Installation and instruction manual

    Other relevant documents

    ordrig irui

    Type of breaker

    Quantity

    Rated voltage (kv)

    Operating voltage (AC / DC)

    Rated current (A)

    Accessories

    Rated short-circuit breaking current ( kA)

    ovrviw

    ZN85-40.5 indoor AC high voltage vacuum circuit breaker

    is mainly used in three-phase alternating current 50Hz,

    40.5kV power system for opening and closing load current,

    overload and short-circuit current; it can be used in the places

    with frequent operations, and is suitable for the control and

    protection in power plants, transformer substations, power

    equipment and power lines.

    The breaker adopts spring charging control mechanism and

    the operational power supply can be DC or AC, which is very

    convenient; the product is characterized by good performance,

    high reliability, convenience in repair and maintenance, and

    long maint