04 - pcs915a busbar protection

218
  PCS-915A Busbar Protection Instruction Manual NR Electric Co., Ltd.

Upload: toing

Post on 02-Nov-2015

37 views

Category:

Documents


2 download

DESCRIPTION

PCS915A Busbar Protection

TRANSCRIPT

  • PCS-915A

    Busbar Protection

    Instruction Manual

    NR Electric Co., Ltd.

  • Preface

    PCS-915A Busbar Protection i

    Date: 2013-06-03

    Preface

    Introduction

    This guide and the relevant operating or service manual documentation for the equipment provide

    full information on safe handling, commissioning and testing of this equipment.

    Documentation for equipment ordered from NR is dispatched separately from manufactured goods

    and may not be received at the same time. Therefore, this guide is provided to ensure that printed

    information normally present on equipment is fully understood by the recipient.

    Before carrying out any work on the equipment, the user should be familiar with the contents of

    this manual, and read relevant chapter carefully.

    This chapter describes the safety precautions recommended when using the equipment. Before

    installing and using the equipment, this chapter must be thoroughly read and understood.

    Health and Safety

    The information in this chapter of the equipment documentation is intended to ensure that

    equipment is properly installed and handled in order to maintain it in a safe condition.

    When electrical equipment is in operation, dangerous voltages will be present in certain parts of

    the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger

    personnel and equipment and cause personal injury or physical damage.

    Before working in the terminal strip area, the equipment must be isolated.

    Proper and safe operation of the equipment depends on appropriate shipping and handling,

    proper storage, installation and commissioning, and on careful operation, maintenance and

    servicing. For this reason, only qualified personnel may work on or operate the equipment.

    Qualified personnel are individuals who:

    Are familiar with the installation, commissioning, and operation of the equipment and of the

    system to which it is being connected;

    Are able to safely perform switching operations in accordance with accepted safety

    engineering practices and are authorized to energize and de-energize equipment and to

    isolate, ground, and label it;

    Are trained in the care and use of safety apparatus in accordance with safety engineering

    practices;

    Are trained in emergency procedures (first aid).

    Instructions and Warnings

    The following indicators and standard definitions are used:

  • Preface

    PCS-915A Busbar Protection ii Date: 2013-06-03

    DANGER!

    It means that death, severe personal injury, or considerable equipment damage will occur if safety

    precautions are disregarded.

    WARNING!

    It means that death, severe personal, or considerable equipment damage could occur if safety

    precautions are disregarded.

    CAUTION!

    It means that light personal injury or equipment damage may occur if safety precautions are

    disregarded. This particularly applies to damage to the device and to resulting damage of the

    protected equipment.

    WARNING!

    The firmware may be upgraded to add new features or enhance/modify existing features, please

    make sure that the version of this manual is compatible with the product in your hand.

    WARNING!

    During operation of electrical equipment, certain parts of these devices are under high voltage.

    Severe personal injury or significant equipment damage could result from improper behavior.

    Only qualified personnel should work on this equipment or in the vicinity of this equipment. These

    personnel must be familiar with all warnings and service procedures described in this manual, as

    well as safety regulations.

    In particular, the general facility and safety regulations for work with high-voltage equipment must

    be observed. Noncompliance may result in death, injury, or significant equipment damage.

    DANGER!

    Never allow the current transformer (CT) secondary circuit connected to this equipment to be

    opened while the primary system is live. Opening the CT circuit will produce a dangerously high

    voltage.

    WARNING!

    Exposed terminals

    Do not touch the exposed terminals of this equipment while the power is on, as the high voltage

    generated is dangerous

  • Preface

    PCS-915A Busbar Protection iii

    Date: 2013-06-03

    Residual voltage

    Hazardous voltage can be present in the DC circuit just after switching off the DC power supply. It

    takes a few seconds for the voltage to discharge.

    CAUTION!

    Earth

    The earthing terminal of the equipment must be securely earthed

    Operating environment

    The equipment must only be used within the range of ambient environment detailed in the

    specification and in an environment free of abnormal vibration.

    Ratings

    Before applying AC voltage and current or the DC power supply to the equipment, check that they

    conform to the equipment ratings.

    Printed circuit board

    Do not attach and remove printed circuit boards when DC power to the equipment is on, as this

    may cause the equipment to malfunction.

    External circuit

    When connecting the output contacts of the equipment to an external circuit, carefully check the

    supply voltage used in order to prevent the connected circuit from overheating.

    Connection cable

    Carefully handle the connection cable without applying excessive force.

    Copyright

    Version: R1.02

    P/N: EN_YJBH5301.0086.0003

    Copyright NR 2013. All rights reserved

    NR ELECTRIC CO., LTD.

    69 Suyuan Avenue. Jiangning, Nanjing 211102, China

    Tel: +86-25-87178185, Fax: +86-25-87178208

    Website: www.nrelect.com, www.nari-relays.com

    Email: [email protected]

    We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and dissemination

    to third parties is strictly forbidden except where expressly authorized.

    The information in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If

    nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.

    We reserve the rights to make technical improvements without notice.

  • Preface

    PCS-915A Busbar Protection iv Date: 2013-06-03

    Documentation Structure

    The manual provides a functional and technical description of this relay and a comprehensive set

    of instructions for the relays use and application.

    All contents provided by this manual are summarized as below:

    1 Introduction

    Briefly introduce the application, functions and features about this relay.

    2 Technical Data

    Introduce the technical data about this relay, such as electrical specifications, mechanical

    specifications, ambient temperature and humidity range, communication port parameters, type

    tests, setting ranges and accuracy limits and the certifications that our products have passed.

    3 Operation Theory

    Introduce a comprehensive and detailed functional description of all protective elements.

    4 Supervision

    Introduce the automatic self-supervision function of this relay.

    5 Measurement and Recording

    Introduce the management function (measurment and recording) of this relay.

    6 Hardware

    Introduce the main function carried out by each plug-in module of this relay and providing the

    definition of pins of each plug-in module.

    7 Settings

    List settings including protection settings, system settings, communication settings, label settings,

    VEBI settings and etc., and some notes about the setting application.

    8 Human Machine Interface

    Introduce the hardware of the human machine interface (HMI) module and a detailed guide for the

    user how to use this relay through HMI. It also lists all the information which can be view through

    HMI, such as settings, measurements, all kinds of reports etc.

    9 Communication

    Introduce the communication port and protocol which this relay can support, IEC60970-5-103,

    IEC61850 and DNP3.0 protocols are introduced in details.

    10 Installation

    Introduce the recommendations on unpacking, handling, inspection and storage of this relay. A

    guide to the mechanical and electrical installation of this relay is also provided, incorporating

  • Preface

    PCS-915A Busbar Protection v

    Date: 2013-06-03

    earthing recommendations. A typical wiring connection to this relay is indicated.

    11 Commissioning

    Introduce how to commission this relay, comprising checks on the calibration and functionality of

    this relay.

    12 Maintenance

    A general maintenance policy for this relay is outlined.

    13 Decommissioning and Disposal

    A general decommissioning and disposal policy for this relay is outlined.

    14 Manual Version History

    List the instruction manual version and the modification history records.

  • Preface

    PCS-915A Busbar Protection vi Date: 2013-06-03

  • 1 Introduction

    PCS-915A Busbar Protection 1-a

    Date: 2012-08-31

    1 Introduction

    Table of Contents

    1 Introduction ..................................................................................... 1-a

    1.1 Application ....................................................................................................... 1-1

    1.2 Function ........................................................................................................... 1-2

    1.3 Feature ............................................................................................................. 1-2

    1.4 Abbreviation .................................................................................................... 1-3

  • 1 Introduction

    PCS-915A Busbar Protection 1-b Date: 2012-08-31

  • 1 Introduction

    PCS-915A Busbar Protection 1-1

    Date: 2012-08-31

    1.1 Application

    PCS-915A is a numerical busbar differential protection intended to be used for protecting and

    monitoring of double busbars with bus coupler arrangement, single busbar arrangement and

    single busbar with single bus section arrangement of various voltage levels. It is capable to protect

    up to 25 bays including bus coupler and bus section (bay 01 is connected with bus coupler (BC),

    the rest bays are taken as feeder 01~24).

    PCS-915A utilizes NRs innovative hardware platform supporting both conventional CT/VT and

    electronic current and voltage transformer (ECVT). It is compliant to several communication

    protocols, such as IEC60870-5-103, IEC61850 and DNP3.0 protocol.

    BB1

    BC

    *

    *

    **

    VT1

    VT2

    PCS-915

    FR50BF 87B

    BB2

    Figure 1.1-1 Typical application-Double busbars with BC arrangement

    Note!

    The bay label of displayed alarm signals, tripping signals, binary input signals, settings and

    sampled values related with each feeder and busbar will change with the corresponding

    description settings. Please refer to Section 7.8 for details.

    For example, if the description setting of feeder 01 i.e. [NameDef_Bay02] is set as Fdr01,

    the three-phase initiating contact of BFP for feeder 01 is [BI_BFI_Fdr01]. If

    [NameDef_Bay02] is set as 0001, the three-phase initiating contact of BFP for feeder 01

    is [BI_BFI_0001].

    In this instruction manual, only take the default settings in Table 7.8-1 as an example to

    introduce.

  • 1 Introduction

    PCS-915A Busbar Protection 1-2 Date: 2012-08-31

    1.2 Function

    PCS-915 provides the following functions

    1. Protection function

    Busbar differential protection (87B)

    Steady-state percentage differential protection

    DPFC percentage differential protection

    Bus coupler protection

    SOTF protection (50)

    End zone fault protection (50DZ)

    Breaker failure protection (50BF)

    Overcurrent protection (50/51)

    Pole discrepancy protection (62PD)

    Feeder breaker failure protection (50BF)

    Note!

    DPFC is the abbreviation of Deviation of Power Frequency Component. When a fault

    occurs in the power system, the fault current consists of three parts: the pre-fault power

    frequency components, the power frequency variables during the fault and the transient

    variables during the fault. DPFC is the power frequency variables during the fault.

    2. Auxiliary protection

    Dynamic busbar replica

    CT circuit failure supervision

    VT circuit failure supervision

    Disconnector position alarm

    1.3 Feature

    1. Protection and Control

    Parallel calculation of double DSP system

    Independent fault detector element

    Accurate measurement which can prevent any undesired trip

  • 1 Introduction

    PCS-915A Busbar Protection 1-3

    Date: 2012-08-31

    Less than 20ms typical trip time for busbar differential protection

    High sensitive percentage restraint differential protection

    Matching to different CT ratios and settable CT adjustment coefficient

    A well proven adaptive weighted anti-saturation algorithm

    Friendly human machine interface

    Comprehensive event recorder

    Multi-language option - English, Chinese and Russian

    2. Time synchronization

    Receiving PPS (pulse per second) and PPM (pulse per minute) via external contact

    Receiving PPS, PPM and IRIG-B signal via RS-485

    Receiving time synchronization message from substation automation system

    3. Event recorder and disturbance recorder

    1024 latest fault reports

    1024 latest self-supervision reports

    1024 latest status change of binary input reports

    32 latest fault waveforms (The file format of disturbance recorder is compatible with the

    international COMTRADE file)

    4. Communication

    2 rear RS-485 communication ports supporting with IEC 60870-5-103 protocol, ModBus

    protocol or DNP3.0 protocol

    4 Ethernet ports at most (depend on the chosen CPU type) supporting with IEC 60870-5-103

    protocol or IEC 61850-8-1 protocol

    1 rear RS-485 communication port for time synchronization

    1 RS-232 communication rear ports for printer

    A front multiplex RJ45 port for local communication with a PC

    1.4 Abbreviation

    Symbol Description

    FD Fault detector

    BBx Busbar No.x, x is the number of each busbar

  • 1 Introduction

    PCS-915A Busbar Protection 1-4 Date: 2012-08-31

    Symbol Description

    feeder xx Feeder No.xx, xx is the number of each feeder

    VCE Voltage controlled element

    BBP Busbar differential protection

    BFP Breaker failure protection

    BFI Breaker failure initiation

    EFP End zone fault protection

    PD Pole disagreement

    SAS Substation automatic system

    RTU Remote terminal unit

    CT Current transformer

    VT Voltage transformer

    DPFC Deviation of power frequency component

  • 2 Technical Data

    PCS-915A Busbar Protection 2-a

    Date: 2013-06-03

    2 Technical Data

    Table of Contents

    2 Technical Data ................................................................................. 2-a

    2.1 Electrical Specifications ................................................................................. 2-1

    2.1.1 Alternating Analog Current................................................................................................... 2-1

    2.1.2 Alternating Analog Voltage ................................................................................................... 2-1

    2.1.3 Power Supply ....................................................................................................................... 2-1

    2.1.4 Binary Input .......................................................................................................................... 2-1

    2.1.5 Binary Output ....................................................................................................................... 2-2

    2.2 Mechanical Specifications ............................................................................. 2-2

    2.3 Ambient Temperature and Humidity Range .................................................. 2-2

    2.4 Communication Port ....................................................................................... 2-3

    2.4.1 EIA-485 Port ........................................................................................................................ 2-3

    2.4.2 Ethernet Port ........................................................................................................................ 2-3

    2.4.3 Optical Fibre Port ................................................................................................................. 2-3

    2.4.4 Print Port .............................................................................................................................. 2-4

    2.4.5 Clock Synchronization Port ................................................................................................. 2-4

    2.5 Type Tests ........................................................................................................ 2-4

    2.5.1 Environmental Tests ............................................................................................................ 2-4

    2.5.2 Mechanical Tests ................................................................................................................. 2-4

    2.5.3 Electrical Tests ..................................................................................................................... 2-4

    2.5.4 Electromagnetic Compatibility ............................................................................................. 2-5

    2.6 Certifications ................................................................................................... 2-6

    2.7 Measurement Scope and Accuracy ............................................................... 2-6

    2.8 Management Function .................................................................................... 2-6

    2.8.1 Clock Performance .............................................................................................................. 2-6

    2.8.2 Fault and Disturbance Recording ........................................................................................ 2-6

  • 2 Technical Data

    PCS-915A Busbar Protection 2-b

    Date: 2013-06-03

    2.8.3 Binary Input Signal............................................................................................................... 2-6

    2.9 Protective Functions ....................................................................................... 2-7

    2.9.1 Busbar Differential Protection .............................................................................................. 2-7

    2.9.2 Switch-onto-fault Protection ................................................................................................. 2-7

    2.9.3 Bus coupler/bus section Overcurrent Protection ................................................................. 2-7

    2.9.4 Bus coupler/bus section Pole Disagreement Protection ..................................................... 2-7

    2.9.5 Bus coupler/bus section Breaker Failure Protection ........................................................... 2-7

    2.9.6 Feeder Breaker Failure Protection ...................................................................................... 2-7

  • 2 Technical Data

    PCS-915A Busbar Protection 2-1

    Date: 2013-06-03

    2.1 Electrical Specifications

    2.1.1 Alternating Analog Current

    Phase rotation ABC

    Nominal frequency (fn) 505Hz, 605Hz

    Rated Current (In) 1A 5A

    Linear to 0.05In~40In

    Thermal withstand

    -continuously

    -for 10s

    -for 1s

    -for half a cycle

    4In

    30In

    100In

    250In

    Burden < 0.15VA/phase @In < 0.25VA/phase @In

    Accuracy 0.5%In

    2.1.2 Alternating Analog Voltage

    Phase rotation ABC

    Nominal frequency (fn) 505Hz, 605Hz

    Rated Voltage (Un) 100V~130V

    Linear to 1V~170V

    Thermal withstand

    -continuously

    -10s

    -1s

    200V

    260V

    300V

    Burden at rated < 0.20VA/phase @Un

    Accuracy 0.5%Un

    2.1.3 Power Supply

    Standard IEC 60255-11:2008

    Rated Voltage 110Vdc/125Vdc, 220Vdc/250Vdc

    Operating Range 80%~120% of rated voltage

    Permissible AC ripple voltage 15% of the nominal auxiliary voltage

    Burden

    Quiescent condition

    Operating condition

  • 2 Technical Data

    PCS-915A Busbar Protection 2-2

    Date: 2013-06-03

    Maximum permissible voltage 120% of rated voltage

    Withstand voltage

    -continously 2000Vac, 2800Vdc

    Response time for logic input

  • 2 Technical Data

    PCS-915A Busbar Protection 2-3

    Date: 2013-06-03

    C)

    Transport and storage temperature

    range -40C to +70C

    Permissible humidity 5%-95%, without condensation

    Pollution degree

    Altitude

  • 2 Technical Data

    PCS-915A Busbar Protection 2-4

    Date: 2013-06-03

    Wave length 1310nm

    Transmission power Min. -20.0dBm

    Minimum receiving power Min. -30.0dBm

    Margin Min +3.0dB

    2.4.3.3 For Synchronization Port

    Characteristic Glass optical fiber

    Connector type ST

    Fibre type Multi mode

    Wave length 820nm

    Minimum receiving power Min. -25.0dBm

    Margin Min +3.0dB

    2.4.4 Print Port

    Type RS-232

    Baud Rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s

    Printer type EPSON 300K printer

    Safety level Isolation to ELV level

    2.4.5 Clock Synchronization Port

    Type RS-485

    Transmission distance

  • 2 Technical Data

    PCS-915A Busbar Protection 2-5

    Date: 2013-06-03

    Overvoltage category

    Insulation resistance

    measurements Isolation resistance >100M@500VDC

    2.5.4 Electromagnetic Compatibility

    1MHz burst disturbance test

    IEC 60255-22-1:2007

    Common mode: class III 2.5kV

    Differential mode: class III 1.0kV

    Electrostatic discharge test

    IEC60255-22-2:2008 class IV

    For contact discharge: 8kV

    For air discharge: 15kV

    Radio frequency interference tests

    IEC 60255-22-3:2007 class III

    Frequency sweep

    Radiated amplitude-modulated

    10V/m (rms), f=80~1000MHz

    Spot frequency

    Radiated amplitude-modulated

    10V/m (rms), f=80MHz/160MHz/450MHz/900MHz

    Radiated pulse-modulated

    10V/m (rms), f=900MHz

    Fast transient disturbance tests

    IEC 60255-22-4:2008

    Power supply, I/O, Earth: class IV, 4kV, 2.5kHz, 5/50ns

    Communication terminals: class IV, 2kV, 5kHz, 5/50ns

    Surge immunity test

    IEC 60255-22-5:2008

    Power supply, AC input, I/O port: class IV, 1.2/50us

    Common mode: 4kV

    Differential mode: 2kV

    Conducted RF Electromagnetic

    Disturbance

    IEC 60255-22-6:2001

    Power supply, AC, I/O, Comm. Terminal: Class III, 10Vrms, 150

    kHz~80MHz

    Power Frequency Magnetic Field

    Immunity

    IEC 61000-4-8:2001

    class V, 100A/m for 1min, 1000A/m for 3s

    Pulse Magnetic Field Immunity IEC 61000-4-9:2001

    class V, 6.4/16s, 1000A/m for 3s

    Damped oscillatory magnetic field

    immunity

    IEC 61000-4-10:2001

    class V, 100kHz & 1MHz100A/m

    Auxiliary power supply performance

    - Voltage dips

    -Voltage short interruptions

    IEC60255-11: 2008

    Up to 500ms for dips to 40% of rated voltage without reset

    100ms for interruption without rebooting

  • 2 Technical Data

    PCS-915A Busbar Protection 2-6

    Date: 2013-06-03

    2.6 Certifications

    ISO9001:2008

    ISO14001:2004

    OHSAS18001:2007

    ISO10012:2003

    CMMI L4

    EMC: 2004/108/EC, EN50263:1999

    Products safety(PS): 2006/95/EC, EN61010-1:2001

    2.7 Measurement Scope and Accuracy

    Item Range Accuracy

    Phase range 0 ~ 360 0.5% or 1

    Frequency fn3Hz 0.01Hz

    Currents from protection measurement current transformers

    Current 0.05 ~ 40.00In 2.5% of rating or 0.02In

    Voltage 0.05 ~ 1.20Un 1.0% of rating or 0.01Un

    2.8 Management Function

    2.8.1 Clock Performance

    Real time clock accuracy 3s/day

    Accuracy of GPS synchronization 1ms

    External time synchronization IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol

    2.8.2 Fault and Disturbance Recording

    Maximum duration 6000 sampled points (24 sampled points per cycle)

    Recording position 2~50 cycles before pickup of trigger element

    2.8.3 Binary Input Signal

    Resolution of binary input signal 1ms

    Binary input mode Potential-free contact

    Resolution of SOE 1ms

  • 2 Technical Data

    PCS-915A Busbar Protection 2-7

    Date: 2013-06-03

    2.9 Protective Functions

    Note!

    The meanings of symbols mentioned in the following sections are given here.

    In -- rated secondary current of reference CT

    U2n -- rated secondary phase-to-phase voltage of VT

    2.9.1 Busbar Differential Protection

    current setting range 0.05In~20.00In

    Tolerance of current setting 2.5%xSetting or 0.02In, whichever is greater

    Accuracy of voltage setting 2.5% or 0.01U2n whichever is greater

    2.9.2 Switch-onto-fault Protection

    Current setting range 0.05In~20.00In

    Tolerance of current setting 2.5% of setting or 0.02In whichever is greater

    2.9.3 Bus coupler/bus section Overcurrent Protection

    Current setting range 0.05In~20.00In

    Tolerance of current setting 2.5% of setting or 0.02In whichever is greater

    Time setting range 0.000~10.000s

    Tolerance of time setting 1%xSetting + 40ms

    2.9.4 Bus coupler/bus section Pole Disagreement Protection

    Residual current setting range 0~20.00In

    Negative-sequence current setting range 0~20.00In

    Tolerance of current setting 2.5% of setting or 0.02In whichever is greater

    Time setting range 0.000~10.000s

    Tolerance of time setting 1%xSetting + 40ms

    2.9.5 Bus coupler/bus section Breaker Failure Protection

    Current setting range 0~20.00In

    Tolerance of current setting 2.5%xSetting or 0.02In, whichever is greater

    Time setting range 0.010~10.000s

    Tolerance of time setting 1%xSetting + 40ms

    2.9.6 Feeder Breaker Failure Protection

    Phase current setting range 0~20.00In

  • 2 Technical Data

    PCS-915A Busbar Protection 2-8

    Date: 2013-06-03

    Residual current setting range 0~20.00In

    Negative-sequence current setting range 0~20.00In

    Tolerance of current setting 2.5%xSetting or 0.02In, whichever is greater

    Time setting range 0.000~10.000s

    Tolerance of time setting 1%xSetting + 40ms

    Undervoltage setting range 01.732U2n

    Residual voltage setting range 0U2n

    Negative sequence voltage setting range 0U2n

    Accuracy of voltage setting 2.5% or 0.01Un whichever is greater

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-a

    Date: 2012-08-31

    3 Operation Theory

    Table of Contents

    3 Operation Theory ............................................................................ 3-a

    3.1 Overview .......................................................................................................... 3-1

    3.2 Busbar Differential Protection ....................................................................... 3-2

    3.2.1 Fault detector (FD) element................................................................................................. 3-3

    3.2.2 Percentage differential element ........................................................................................... 3-4

    3.2.3 Voltage controlled element of busbar differential protection (VCE_BBP) ........................... 3-6

    3.2.4 Faulty busbar zone discrimination ....................................................................................... 3-7

    3.2.5 Backup busbar differential elements ................................................................................... 3-8

    3.2.6 Detection of CT saturation ................................................................................................... 3-8

    3.2.7 External Block Signal ........................................................................................................... 3-9

    3.2.8 Logic scheme ....................................................................................................................... 3-9

    3.3 Bus Coupler/Section (BC/BS) Protection ..................................................... 3-11

    3.3.1 BC/BS switch-onto-fault (SOTF) protection ....................................................................... 3-11

    3.3.2 BC/BS overcurrent protection ............................................................................................ 3-12

    3.3.3 BC/BS breaker failure protection (BFP) ............................................................................ 3-13

    3.3.4 BC/BS end zone fault protection ....................................................................................... 3-14

    3.3.5 BC/BS pole discrepancy protection (PD) .......................................................................... 3-15

    3.4 Feeder breaker Failure Protection (BFP) .................................................... 3-16

    3.4.1 Initiation contact ................................................................................................................. 3-16

    3.4.2 Current criterion ................................................................................................................. 3-17

    3.4.3 Voltage control element of breaker failure protection(VCE) .............................................. 3-17

    3.4.4 Logic scheme ..................................................................................................................... 3-18

    3.5 Identification of disconnector position ....................................................... 3-19

    3.6 VT Circuit Supervision .................................................................................. 3-20

    3.7 CT Circuit Supervision ................................................................................. 3-21

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-b

    Date: 2012-08-31

    3.7.1 CT circuit failure ................................................................................................................. 3-21

    3.7.2 CT circuit abnormality ........................................................................................................ 3-21

    3.8 BC breaker substitution ............................................................................... 3-21

    List of Figures

    Figure 3.1-1 Double-busbar arrangement ................................................................................. 3-2

    Figure 3.2-1 Sketch diagram of double busbars with one bus section arrangement ......... 3-2

    Figure 3.2-2 Operation characteristic of steady-state percentage restraint differential

    element .................................................................................................................................. 3-5

    Figure 3.2-3 Waveform of CT saturation during external fault ............................................... 3-9

    Figure 3.2-4 Logic scheme of busbar differential protection ............................................... 3-10

    Figure 3.3-1 Logic scheme of SOTF protection ..................................................................... 3-12

    Figure 3.3-2 Logic scheme of overcurrent protection........................................................... 3-13

    Figure 3.3-3 The logic scheme of BFP .................................................................................... 3-14

    Figure 3.3-4 The logic scheme of end zone fault protection ................................................ 3-15

    Figure 3.3-5 The logic scheme of pole discrepancy protection ........................................... 3-16

    Figure 3.4-1 The logic scheme of BFP (for the bay that main transformer is not connected)

    .............................................................................................................................................. 3-18

    Figure 3.4-2 The logic scheme of BFP (for the bay that main transformer is connected) 3-19

    Figure 3.8-1 BC breaker substituting through BB2 ............................................................... 3-22

    Figure 3.8-2 BC breaker substituting through BB1 ............................................................... 3-23

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-1

    Date: 2012-08-31

    3.1 Overview

    PCS-915 provides busbar differential protection (BBP), bus coupler/section protection (includes

    overcurrent protection, switch-onto-fault protection, pole disagreement protection, end zone fault

    protection and breaker failure protection), feeder breaker failure protection, CT circuit supervision

    and VT circuit supervision.

    The device can support several busbar arrangements, such as double-busbar arrangement,

    single-busbar arrangement and single busbar with single bus section arrangement. The switch

    method of each busbar arrangement is listed as below:

    System settings

    Busbar arrangement En_SingleBB En_SingleBB_with_SingleBS

    Double-busbar 0 0

    Single-busbar 1 0

    Single busbar with single bus section 0 1

    Please refer to Section 7.1 about detailed description of each system setting. For single busbar

    with bus section arrangement, the system setting [Cfg_DS_BBx] (x=1, 2) is used to indicate which

    busbar zone the feeder is connected to.

    The device has 2 plug-in modules (protection DSP module and fault detector DSP module) to

    perform calculation. The protection DSP module is responsible for calculation of protection

    elements, and fault detector DSP module is responsible for calculation of fault detectors. Any fault

    detector of fault detector DSP module picks up to provide positive supply of output relays. The

    relays will trip only if the fault detector and the corresponding protection element operate

    simultaneously. On the premise of 24 samples per cycle, all data measurement, calculation and

    logic discrimination can be processed within one sampling period. The event recording and

    protection logic calculation are completed simultaneously.

    The following figure shows double busbars arrangement and application mode.

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-2

    Date: 2012-08-31

    *

    BB2

    BB1

    Panel A

    BC

    * * * *

    PCS-915

    VT1

    VT2

    Figure 3.1-1 Double-busbar arrangement

    3.2 Busbar Differential Protection

    In order to be easy to explain the protection function and scheme, the first busbar is defined as

    busbar No.1 (BB1) and the second busbar is defined as busbar No.2 (BB2). In the case of project

    application, the number of each busbar can be set based on on-site case. The polarity marking of

    feeder CT should be on the busbar side and the polarity of BC CT should be on the BB1 side.

    Please refer to the sketch diagram of primary system Figure 3.2-1.

    *

    BB2

    BB1

    BC

    * * * *

    Discriminative

    zone No.2

    Discriminative

    zone No.1Check zone

    Figure 3.2-1 Sketch diagram of double busbars with one bus section arrangement

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-3

    Date: 2012-08-31

    Note!

    The protective device only identifies the physical position of busbar, ignoring the number of

    busbar, takes the busbar arrangement in Figure 3.2-1 as an example, the protective device

    will refer the busbar of which the polarity of BC CT is towards as BB1.

    The primary protection of PCS-915 is phase-segregated percentage restraint differential

    protection. The differential circuits include check zone differential circuit and discriminating zone

    differential circuits of each busbar zone. The check zone differential element is used to distinguish

    between internal and external fault of the overall busbar system, it measures the current from all

    the circuits connected to the busbar system except BC and BS. The discriminating zone

    differential elements are used to select faulty zone by measuring the current of all the circuits

    connected to individual zones of the busbar system separated by BC and BS.

    Discriminating zone No.1 is defined as discriminating differential element of BB1. Discriminating

    zone No.2 is defined as discriminating differential element of BB2.

    3.2.1 Fault detector (FD) element

    PCS-915 provides three independent FD elements for busbar differential protection, which are

    DPFC voltage FD element, DPFC current FD element and differential current FD element. If any of

    these three elements picks up, the positive supply to the output relays is then available and wait

    for the tripping signal from busbar differential protection. The fault detector output signal will last

    for 500ms after the corresponding fault detector element drop off.

    1. DPFC voltage FD element

    When DPFC voltage of any phase of any busbar is larger than the threshold, DPFC voltage FD

    element picks up, the operating criterion is:

    u>UFloat+0.05Un Equation 3.2-1

    Where:

    u: Instantaneous value of phase-to-phase DPFC voltage

    UFloat: Float threshold value, automatically varied with the gradually voltage changing

    0.05Un: Fixed threshold value, Un is the rated secondary phase-to-ground voltage.

    If voltage is not sampled or VT circuit failure is detected, DPFC voltage FD element will quit

    automatically.

    2. DPFC current FD element

    If DPFC check zone restraint current is larger than the threshold, DPFC current fault detector

    element will operate, the operating criterion is:

    si>SIFloat+0.5In Equation 3.2-2

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-4

    Date: 2012-08-31

    Where:

    si: Instantaneous value of DPFC check zone restraint current of any phase (scalar sum of current

    change of all circuits/bays for check zone)

    SIFloat: Float threshold value, automatically varied with the gradually current changing

    0.5In: Fixed threshold value, In is the rated secondary current of reference CT.

    3. Differential current FD element

    When any phase of the check zone differential current is larger than the setting, this element will

    operate. The operating criterion is:

    ID> [I_Pkp_Pcnt_BBP] Equation 3.2-3

    Where:

    ID: Differential phase current of check zone

    [I_Pkp_Pcnt_BBP]: Current setting of busbar differential protection

    3.2.2 Percentage differential element

    The percentage restraint differential element includes steady-state percentage restraint differential

    element and DPFC percentage restraint differential element.

    Steady-state percentage restraint differential element

    The differential current: ID =

    m

    1j

    jI

    The restraint current: IR =

    m

    1j

    jI

    The operating criterion is:

    R

    D

    KI

    ]_Pcnt__[I

    I

    BBPPkpI

    D

    Equation 3.2-4

    Where:

    K: Restraint coefficient of steady-state differential element

    Ij: The current of the j-th feeder (Feeder j) connected

    [I_Pkp_Pcnt_BBP]: Current setting of busbar differential protection

    The operation characteristic is shown as below.

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-5

    Date: 2012-08-31

    [I_Pkp_Pcnt_BBP]

    Operation region

    IR

    ID

    ID=IR

    ID=kIR

    Figure 3.2-2 Operation characteristic of steady-state percentage restraint differential element

    To enhance the sensitivity of steady-state check zone differential element for a fault occurred in

    the weak source bus zone when the BC breaker is open, dual restraint coefficients [0.5, 0.3] and

    [0.6, 0.5] are adopted for steady-state check zone and discriminating zones respectively.

    When one of the following conditions is fulfilled, the busbar steady-state percentage restraint

    differential protection will operate.

    1. Steady-state check zone differential element with high restraint coefficient (0.5) operates and

    steady-state discriminating zone differential element with low restraint coefficient (0.5)

    operates.

    2. Steady-state check zone differential element with low restraint coefficient (0.3) operates and

    steady-state discriminating zone differential element with high restraint coefficient (0.6)

    operates.

    DPFC percentage differential element

    The DPFC percentage restraint differential element is adopted to enhance the performance of

    busbar protection against high impedance fault and the influence of heavy loading condition. The

    busbar DPFC differential protection is formed by DPFC percentage restraint differential element

    and steady-state check zone percentage restraint differential element with fixed restraint

    coefficient 0.2.

    The DPFC differential current: ID =

    m

    1j

    jI

    The DPFC restraint current: IR =

    m

    1j

    jI

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-6

    Date: 2012-08-31

    The operating criterion is:

    R

    /

    D

    RD

    DPickupDFloatD

    IKI

    0.2II

    III

    Equation 3.2-5

    Where:

    K': DPFC restraint coefficient

    Ij: DPFC current of the j-th feeder (Feeder j) connected

    IDFloat: Float threshold value of DPFC check zone differential current

    IDPickup: Fixed threshold value of DPFC check zone differential current, which derives from the

    setting of [I_Pkp_Pcnt_BBP]

    Similar to steady-state percentage restraint differential element, dual restraint coefficients are also

    introduced to DPFC differential element. The restraint coefficients are fixed at [0.65, 0.3] and [0.65,

    0.5] for DPFC check zone and discriminating zones respectively.

    When the steady-state check zone percentage restraint differential element with fixed restraint

    coefficient of 0.2 operates, if one of the following conditions is fulfilled, the busbar DPFC

    percentage restraint differential protection will operate.

    1. DPFC check zone percentage restraint differential element with high restraint coefficient (0.65)

    operates and DPFC discriminating zone percentage restraint differential element with low

    restraint coefficient (0.5) operates.

    2. DPFC check zone percentage restraint differential element with low restraint coefficient (0.3)

    operates and DPFC discriminating zone percentage restraint differential element with high

    restraint coefficient (0.65) operates.

    3.2.3 Voltage controlled element of busbar differential protection (VCE_BBP)

    Voltage controlled element is used as an auxiliary condition.

    The operating criteria are:

    UP [V_UV_VCE_BBP] Equation 3.2-6

    3U0 [V_ROV_VCE_BBP] Equation 3.2-7

    U2 [V_NegOV_VCE_BBP] Equation 3.2-8

    Where:

    UP: Secondary rated phase-to-ground voltage

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-7

    Date: 2012-08-31

    3U0: Residual voltage (calculated internally)

    U2: Negative sequence voltage

    [V_UV_VCE_BBP]: Phase-to-ground voltage setting for blocking BBP

    [V_ROV_VCE_BBP]: Residual voltage setting for blocking BBP

    [V_NegOV_VCE_BBP]: Negative sequence voltage setting for blocking BBP

    Busbar differential protection is always blocked by voltage control element. Busbar differential

    protection can not operate to trip faulty busbar zone unless the voltage of corresponding busbar

    zone met any of above criterions.

    When the protective device is applied to an unearthed system, i.e. the system setting

    [Opt_UnearthedSys_Mode] is set as 1, the criteria of voltage control element will be changed.

    UPP [V_UV_VCE_BBP] Equation 3.2-9

    U2[V_NegOV_VCE_BBP] Equation 3.2-10

    Where:

    UPP: Phase-to-phase voltage

    U2: Negative sequence voltage

    [V_UV_VCE_BBP]: Phase-to-phase voltage setting for blocking BBP

    [V_NegOV_VCE_BBP]: Negative voltage setting for blocking BBP

    3.2.4 Faulty busbar zone discrimination

    The check zone differential element calculates the current from all circuits connected to the entire

    busbar system except BC and BS to distinguish between internal and external fault. The

    discriminating zone differential elements calculate the current of all the circuits connected to

    individual zones via replica image of disconnector position to determine faulty zone.

    When the operation criterion of check zone differential element (steady-state check zone

    differential element is supervised by CT saturation detector 2 and DPFC check zone differential

    element is supervised by CT saturation detector 1, to be described in the following section) and

    any discriminating zone differential element is fulfilled, VCE_BBP of any busbar operates, the

    busbar differential protection will operate to trip all bays connected to the faulty busbar.

    The protection has a feature of inter-connection operation mode, the feature will be effective

    automatically under the following conditions.

    1. The binary input [EBI_IntLink_Mode] is energized or the virtual enable binary input

    [VEBI_IntLink_Mode] is set as 1, it should be done when two bus zones are coupled together

    and unable to detach for a particular system operation condition.

    2. On-load transfer condition (when two busbar disconnectors of one feeder are closed at the

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-8

    Date: 2012-08-31

    same time).

    Under the inter-connection operation mode, the discriminating zone differential elements measure

    the current signals are the same as that of check zone differential element. The coupled busbars

    will be tripped simultaneously when there is a fault.

    3.2.5 Backup busbar differential elements

    If only the check zone percentage restraint differential element (supervised by CT saturation

    detector 2) operates, two stages of backup protection with fixed time delay are applied to trip the

    corresponding circuit breakers. Stage 1 of backup protection will trip BC/BS (when VCE of any

    busbar operates) and the feeders of which CT correction coefficient is not zero and does not have

    disconnector position after 240ms. Stage 2 of backup protection will trip the feeders connected to

    the busbar of which voltage clocking has been released and the feeders with current larger than

    2*In (In: the rated secondary current of reference CT) after 480ms.

    3.2.6 Detection of CT saturation

    Two detectors are used to prevent unwanted tripping caused by severe CT saturation during

    external close up fault. If the differential current is determined to be caused by CT saturation, the

    device will block busbar differential protection to prevent mal-operation.

    CT saturation detector 1

    When DPFC voltage or current FD element operates, the adaptive weighted algorithm for CT

    saturation detector will be activated. In case of busbar fault occurs, DPFC differential element will

    operate almost at the same time with DPFC voltage FD element or DPFC current FD element,

    whereas for external fault, DPFC differential element will not operate before CT saturation at the

    fault incipient stage, it will only operate after DPFC voltage element and DPFC current element in

    case CT is saturated. Adaptive weighted algorithm for CT saturation detector is derived from the

    difference of operating time among these DPFC elements. In coordination with DPFC differential

    element, it has performed excellently to distinguish between internal and external fault with CT

    saturation.

    CT saturation detector 2

    Harmonic restraint element is used in CT saturation detector 2 by analyzing the waveforms of

    differential current harmonics. The detector enables the busbar differential element to remain

    stable for an external fault with CT saturation while to maintain fast tripping for the external fault

    evolved to internal fault on the same phase.

    The blocking signal of CT saturation detector 2 will only last for 500ms. After that the busbar

    differential element is released to operate for complicated fault conditions and minimized affected

    area. In practical cases, CT transient saturation will not be more than 500ms.

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-9

    Date: 2012-08-31

    Figure 3.2-3 Waveform of CT saturation during external fault

    Above figure shows the current waveforms recorded in dynamic simulation with heavy CT

    saturation during external phase-to-phase fault. Protection stability is well achieved in this extreme

    case.

    3.2.7 External Block Signal

    PCS-915 provides a binary input [BI_Blk_BBP] to block BBP through external binary signal. If the

    logic setting [En_BI_Blk_BBP] is set as 1, BBP will be blocked if the binary input [BI_Blk_BBP] is

    energized. However, if the binary input [BI_Blk_BBP] is energized for longer than 1 second,

    PCS-915 will issue an alarm [Alm_Blk_BBP] and the blocking for BBP is released.

    3.2.8 Logic scheme

    Figure 3.2-4 only takes BB1 as an example, the logic scheme of BB2 is similar to it.

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-10

    Date: 2012-08-31

    DPFC voltage FD element

    &

    &

    DPFC current FD element

    DPFC DIF 1

    1

    DPFC DIF

    SP DIF (K=0.2)

    500ms&

    &

    1

    SP DIF 1 (K=0.2)

    HM REL 1

    500ms&

    &

    [En_BBP]

    [EBI_BBP]

    SP DIF 1

    HM REL

    SP DIF

    VCE_BBP 1

    VCE_BBP x

    1

    &

    &

    Op_TrpBB1_Pcnt_BBP

    Op_TrpBC_BBP

    CT

    sa

    tura

    tion

    de

    tecto

    r 1

    240ms[Op_Dly1_Pcnt_BBP]&

    1

    480ms[Op_Dly2_Pcnt_BBP]

    [VEBI_BBP]

    VCE_BBP x & BBx is in service

    & Op_TrpBB1_DPFC_BBP

    SP DIF x

    CT circuit failure

    [BI_Blk_BBP]

    0 1s[En_BI_Blk_BBP]

    &

    1

    Figure 3.2-4 Logic scheme of busbar differential protection

    Please refer to Chapter Settings about the description of each setting.

    Where:

    DPFC current FD element: DPFC current fault detector element, please refer to Section 3.2.1.

    DPFC voltage FD element: DPFC voltage fault detector element, please refer to Section 3.2.1.

    DPFC DIF: DPFC percentage differential element for check zone

    DPFC DIF1: DPFC percentage differential element for bus zone No.1

    SP DIF: Steady-state percentage differential element for check zone

    SP DIF1: Steady-state percentage differential element for bus zone No.1

    SP DIF2: Steady-state percentage differential element for bus zone No.2

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-11

    Date: 2012-08-31

    HM REL: Harmonic release element for check zone

    HM REL1: Harmonic release element for bus zone No.1

    VCE_BBP 1: Voltage controlled element of BBP of BB1 operates

    VCE_BBP x: Voltage controlled element of BBP of any busbar operates

    VCE_BBP x & BBx is in service: VCE_BBP of any energized busbar operates

    Op_Dly1_Pcnt_BBP: Stage 1 of backup busbar differential protection operates

    Op_Dly2_Pcnt_BBP: Stage 2 of backup busbar differential protection operates

    Op_TrpBB1_DPFC_BBP: DPFC percentage differential protection operates to trip BB1

    Op_TrpBB1_Pcnt_BBP: Steady-state percentage differential protection operates to trip BB1

    Op_TrpBC_BBP: BBP operates to trip BC breaker

    3.3 Bus Coupler/Section (BC/BS) Protection

    PCS-915 provides switch-onto-fault protection, breaker failure protection, end zone fault protection,

    pole discrepancy protection and overcurrent protection for BC/BS.

    3.3.1 BC/BS switch-onto-fault (SOTF) protection

    After any busbar has been maintained and before being put into operation, it is needed to close

    BC/BS and make the energizing test firstly. During the energizing process, if any fault occurs in the

    energized busbar, SOTF protection will operate to trip BC/BS to clear the fault.

    SOTF protection will be enabled for 300ms if any of the following conditions is met.

    1. The status of the binary input [BI_52b_BC] changes from 1 to 0.

    2. The binary input [BI_52b_BC] is energized and BC current changes from being smaller than

    0.04IN to being greater than 0.04IN.

    3. The binary input [BI_52b_BC] is energized and BB1 and BB2 are in service.

    The logic scheme of SOTF protection is shown as Figure 3.3-1.

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-12

    Date: 2012-08-31

    Ia_BC>0.04IN

    &

    BB2 is in service

    BB1 is in service

    1

    Ib_BC>0.04IN

    &

    Ic_BC>0.04IN

    Ia_BC>[I_OC_SOTF_BC]

    &

    [En_SOTF_BC]

    Ib_BC>[I_OC_SOTF_BC]

    Ic_BC>[I_OC_SOTF_BC]

    &

    Op_TrpBC_SOTF

    [EBI_SOTF_BC]

    &

    1

    0 300ms

    &

    [VEBI_SOTF_BC]

    [BI_52b_BC]

    [BI_52a_BC]

    &

    Figure 3.3-1 Logic scheme of SOTF protection

    Please refer to Chapter Settings about the description of corresponding settings.

    Where:

    BB1(2) is in service: If busbar phase voltage of BB1(2) is greater than 0.3UN or current of any

    connected bay is larger than 0.04IN, BB1(2) is thought as in service.

    [EBI_SOTF_BC]: The binary input of enabling BC SOTF protection

    [BI_52b_BC]: Normally closed auxiliary contact of BC/BS

    [BI_52a_BC]: Normally open auxiliary contact of BC/BS

    Op_TrpBC_SOTF: BC/BS SOTF protection operates to trip BC/BS breaker

    Ia_BC: Phase A current of BC/BS

    Ib_BC: Phase B current of BC/BS

    Ic_BC: Phase C current of BC/BS

    3.3.2 BC/BS overcurrent protection

    When temporary usage of the BC/BS breaker to substitute a feeder circuit breaker, typically for the

    maintenance of the latter. Overcurrent protection can be provided for this application.

    The logic scheme of overcurrent protection is shown as Figure 3.3-2.

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-13

    Date: 2012-08-31

    Ia_BC>[I_OC_BC]

    Ib_BC>[I_OC_BC]

    Ic_BC>[I_OC_BC]

    1

    3I0_BC>[I_ROC_BC]

    [En_OC_BC]

    [EBI_OC_BC]

    &

    &[t_OC_BC]

    Op_TrpBC_OC

    [VEBI_OC_BC]

    &[t_OC_BC]

    Op_TrpBC_ROC

    Figure 3.3-2 Logic scheme of overcurrent protection

    Please refer to Chapter Settings about the description of corresponding settings.

    Where:

    [EBI_OC_BC]: The binary input of enabling BC/BS overcurrent protection

    Op_TrpBC_OC: Phase overcurrent protection of BC/BS operates to trip BC/BS

    Op_TrpBC_ROC: Zero-sequence overcurrent protection of BC/BS operates to trip BC/BS

    3I0_BC: Residual current of BC/BS

    3.3.3 BC/BS breaker failure protection (BFP)

    When tripping signal has been delivered to BC/BS breaker, while the breaker is failed to open

    since the BC/BS current is still larger than the setting [I_BFP_BC] with a specific time delay, BFP

    will operate to trip all feeders connected to both busbars with the time delay of [t_TrpBB_BFP_BC].

    BC/BS breaker failure protection is blocked by voltage controlled element of BBP (Please refer to

    Section 3.2.3).

    There are several options to initiate BFP:

    1. BBP

    2. Breaker failure initiating binary inputs are energized

    The logic scheme of BC/BS BFP is shown as Figure 3.3-3.

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-14

    Date: 2012-08-31

    Ia_BC>[I_BFP_BC]

    Ib_BC>[I_BFP_BC]

    Ic_BC>[I_BFP_BC]

    1

    BBP Trip BB2

    1

    &

    Op_BFP_BB1

    VCE_BBP 1

    VCE_BBP 2

    [BI_BFI_BC_2]

    [t_TrpBB_BFP_BC]

    1BBP Trip BB1

    BBP Trip BC

    &

    & Op_BFP_BB2[t_TrpBB_BFP_BC]

    &

    [BI_BFI_BC_1]

    Figure 3.3-3 The logic scheme of BFP

    Please refer to Chapter Settings about the description of corresponding settings.

    Where:

    BI_BFI_BC_1: Initiating contact of breaker failure protection for BC/BS

    BI_BFI_BC_2: Any binary input of the binary module located in slot No.09 is energized (in order to

    prevent BC/BS BFP from mal-operation due to hardware fault of the binary input module.

    VCE_BBP 1: voltage controlled element of BBP of BB1, Please refer to Section 3.2.3)

    VCE_BBP 2: voltage controlled element of BBP of BB2, Please refer to Section 3.2.3)

    3.3.4 BC/BS end zone fault protection

    If a fault occurs between BC/BS breaker and BC/BS CT, the fault can not be cleared after busbar

    on the breaker side is tripped. In order to clear the fault quickly, a dedicated end zone fault

    protection is provided.

    After busbar differential protection sends the command to trip BC/BS, if the BC/BS breaker has

    been tripped but the BC/BS current is detected, the end zone fault protection will operate and the

    BC/BS current will be excluded from discriminative zone percentage differential circuit with a time

    delay of 150ms.

    If both busbars are in service and BC/BS breaker is open, in order to prevent both busbars from

    being tripped during end fault, the BC/BS current will be excluded from discriminative zone

    percentage differential circuit in this case.

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-15

    Date: 2012-08-31

    BB No.1

    BC Breaker

    BB No.2

    BC CT

    Dead zone

    The logic scheme of end zone fault protection is shown as Figure 3.3-4.

    &

    BB2 is in service

    BB1 is in service

    &Ia_BC>0.04IN

    Ib_BC>0.04IN

    Ic_BC>0.04IN

    1

    Ia_BC>0.1IN

    Ib_BC>0.1IN

    Ic_BC>0.1IN

    1

    0 400ms

    &

    &

    IBC is excluded from discriminative

    zone percentage differential circuit[BI_52b_BC]

    [BI_52a_BC]

    &

    1

    [EBI_Decoupled_BC]

    &

    SP Trip BC

    SP DIF

    &

    150ms

    Figure 3.3-4 The logic scheme of end zone fault protection

    Please refer to Chapter Settings about the description of corresponding settings.

    BB1(2) is in service: If busbar phase voltage of BB1(2) is greater than 0.3UN or current of any

    connected bay is larger than 0.04IN, BB1(2) is thought as in service.

    SP DIF: Steady-state percentage differential element for check zone

    SP: Steady-state percentage differential element

    3.3.5 BC/BS pole discrepancy protection (PD)

    Pole discrepancy protection is designed for the case that pole discrepancy of BC/BS breaker is

    detected due to one phase of BC/BS breaker is open.

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-16

    Date: 2012-08-31

    Pole discrepancy protection is initiated by series-parallel connected auxiliary contacts of BC/BS

    breaker i.e. the binary input [BI_PD_BC].

    In addition of series-parallel connected auxiliary contacts of BC/BS breaker, residual and negative

    sequence current are used as auxiliary criteria.

    The logic scheme of pole discrepancy protection is shown as Figure 3.3-5.

    &

    [BI_PD_BC]

    3I0_BC>[I_ROC_PD_BC]

    I2_BC>[I_NegOC_PD_BC]

    1

    [EBI_PD_BC]

    [t_PD_BC]

    [En_PD_BC]

    &

    &

    Op_BC_PD

    52b_A 52a_A

    [BI_PD_BC]

    52b_B

    52b_C

    52a_B

    52a_C

    [VEBI_PD_BC]

    Figure 3.3-5 The logic scheme of pole discrepancy protection

    Please refer to Chapter Settings about the description of corresponding settings.

    BI_PD_BC: pole discrepancy binary input of BC/BS

    Op_BC_PD: pole discrepancy protection of BC/BS operates to trip BC/BS breaker

    3I0_BC, I2_BC: Residual and negative sequence current of BC/BS.

    3.4 Feeder breaker Failure Protection (BFP)

    Breaker failure protection is available for each feeder. When a breaker is determined failed to trip,

    the breaker failure protection will trip BC/BS after time delay of [t_TrpBC_BFP] and all feeders

    after time delay of [t_TrpBB_BFP].

    3.4.1 Initiation contact

    For each bay, BFP can be initiated externally via binary inputs by phase-segregated tripping

    contacts or three-phase tripping contacts of protective device for the corresponding bay.

    1. Phase-segregated tripping contact

    [BI_A_BFI_Bayxx]: The binary input for initiating BFP of phase A

    [BI_B_BFI_Bayxx]: The binary input for initiating BFP of phase B

    [BI_C_BFI_Bayxx]: The binary input for initiating BFP of phase C

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-17

    Date: 2012-08-31

    xx=04~13, 16~25.

    2. Three-phase tripping contact

    [BI_BFI_Bayxx]: The binary input for initiating BFP of three phases.

    xx=02~25.

    It is recommended that main transformer should be connected to the bays that only have the

    dedicated opto-coupler used by three-phase tripping contact (bay 02, 03, 14, 15). For each bay

    that main transformer is connected, a binary input for releasing voltage blocking element

    [BI_Rls_VCE_BBP_Trans] is provided. For a transformer, when a fault occurs at the low-voltage

    side but the breaker of the high-voltage side fails, the voltage condition of HV side busbar maybe

    not met, so the other tripping contact can be connected to the the binary input

    [BI_Rls_VCE_BBP_Trans] to release voltage blocking element.

    If the bay is tripped by BBP, the breaker failure protection of this bay will be initiated.

    For the bay that main transformer is connected, BFP operates can initiate intertripping to trip

    breakers of other sides of the main transformer.

    3.4.2 Current criterion

    1. Current criterion 1

    Phase current is greater than the setting [I_OC_BFP_Bayxx]

    2. Current criterion 2

    Residual current is greater than the setting [I_ROC_BFP_Bayxx]

    3. Current criterion 3

    Negative sequence current is greater than the setting i.e. [I_NegOC_BFP_Bayxx]

    3.4.3 Voltage control element of breaker failure protection(VCE)

    Voltage control element is used as an auxiliary condition.

    The criteria are:

    UP[V_UV_VCE_BFP] Equation 3.4-1

    3U0[V_ROV_VCE_BFP] Equation 3.4-2

    U2[V_NegOV_VCE_BFP] Equation 3.4-3

    Where:

    UP: Secondary rated phase-to-ground voltage

    3U0: Residual voltage

    U2: Negative sequence voltage

    [V_UV_VCE_BFP]: Phase voltage setting for blocking BFP

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-18

    Date: 2012-08-31

    [V_ROV_VCE_BFP]: Residual voltage setting for blocking BFP

    [V_NegOV_VCE_BFP]: Negative sequence voltage setting for blocking BFP

    When the protective device is applied to an unearthed system, i.e. the system setting

    [Opt_UnearthedSys_Mode] is set as 1, the criteria of voltage control element will be changed.

    UPP [V_UV_VCE_BFP] Equation 3.4-4

    U2[V_NegOV_VCE_BFP] Equation 3.4-5

    Where:

    UPP: Phase-to-phase voltage

    U2: Negative sequence voltage

    [V_UV_VCE_BFP]: Phase-to-phase voltage setting for blocking BFP

    [V_NegOV_VCE_BFP]: Negative sequence voltage setting for blocking BFP

    3.4.4 Logic scheme

    The logic scheme of BFP is shown as Figure 3.4-1.

    Ia_Bayxx>[I_OC_BFP_Bayxx]

    Ib_Bayxx>[I_OC_BFP_Bayxx]

    Ic_Bayxx>[I_OC_BFP_Bayxx]

    1

    [BI_C_BFI_Bayxx]

    1&

    [BI_A_BFI_Bayxx]

    [BI_B_BFI_Bayxx]

    [En_ROC_BFP_Bayxx]

    &

    &

    VCE 1

    VCE 2

    3I0_Bayxx>[I_ROC_BFP_Bayxx]

    I2_Bayxx>[I_NegOC_BFP_Bayxx]

    [En_NegOC_BFP_Bayxx]

    &

    &

    &

    &BBP operates to trip feeder xx

    1

    1

    &

    1

    Disconnector position of BB1

    Disconnector position of BB2

    &

    &

    &

    &

    &

    [En_BFP]

    [EBI_BFP] &

    [VEBI_BFP]Op_Retrip_Bayxx

    Op_TrpBC_BFP

    Op_BFP_BB1 [t_TrpBB_BFP]

    [t_ReTrp_BFP]

    [t_TrpBC_BFP]

    Op_Retrip_Bayxx

    Op_TrpBC_BFP

    Op_BFP_BB2 [t_TrpBB_BFP]

    [t_ReTrp_BFP]

    [t_TrpBC_BFP]

    [BI_BFI_Bayxx]

    1

    Figure 3.4-1 The logic scheme of BFP (for the bay that main transformer is not connected)

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-19

    Date: 2012-08-31

    Ia_Bayxx>[I_OC_BFP_Bayxx]

    Ib_Bayxx>[I_OC_BFP_Bayxx]

    Ic_Bayxx>[I_OC_BFP_Bayxx]

    1

    1&

    &

    [En_BFP]

    [En_ROC_BFP_Bayxx]

    &

    &

    VCE 1

    VCE 2

    3I0_Bayxx>[I_ROC_BFP_Bayxx]

    I2_Bayxx>[I_NegOC_BFP_Bayxx]

    [En_NegOC_BFP_Bayxx]

    [BI_Rls_VCE_BFP_Trans]

    &

    &

    1

    [EBI_BFP]

    Disconnector position of BB1

    Disconnector position of BB2

    1

    1

    &

    &

    &

    &

    &

    [t_TrpBC_BFP]

    [t_TrpBB_BFP]

    [t_ReTrp_BFP]

    [t_TrpBB_BFP]

    [t_ReTrp_BFP]

    [t_TrpBC_BFP]

    [VEBI_BFP]

    1

    BBP operates to trip feeder xx

    [BI_BFI_Bayxx]

    Op_ReTrp_Bayxx

    Op_TrpBC_BFP

    Op_BFP_BB1

    Op_IntTrp_BFP_Bayxx

    Op_ReTrp_Bayxx

    Op_TrpBC_BFP

    Op_BFP_BB2

    Op_IntTrp_BFP_Bayxx

    Figure 3.4-2 The logic scheme of BFP (for the bay that main transformer is connected)

    Please refer to Chapter Settings about the description of corresponding settings.

    3I0_Bayxx: Residual current of bay xx

    I2_Bayxx: The negative sequence current of bay xx

    Ia_Bayxx: The phase A current of bay xx

    Ib_Bayxx: The phase B current of bay xx

    Ic_Bayxx: The phase C current of bay xx

    Disconnector position of BBx: bay xx is connected to BBx (according to disconnector position of the

    bay)

    3.5 Identification of disconnector position

    In a substation with double busbars layout, feeders may be switched from one busbar to the other

    busbar during operation, and it is necessary to identify real time topology of the busbar correctly.

    Disconnector positions are adopted for this identification and self-diagnosis is carried out

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-20

    Date: 2012-08-31

    simultaneously. If there is current flowing in a bay but the bay has no disconnector positions for

    dual busbars, the protective device can remember the original disconnector position. An

    abnormality of disconnector position is detected and disconnector position alarms [Alm_DS_Bayxx]

    will be issued with a specific time delay in any of the following cases (xx: from 02 to 25).

    1. Disconnector position is changed. The operator should check it and confirm whether it is

    correct. The alarm can be reset by energizing the binary input [BI_ConfirmDS].

    2. If both disconnectors to BB1 and BB2 of a bay are closed, an alarm signal [Alm_IntLink] will

    be issued. The alarm can not be reset by energizing the binary input [BI_ConfirmDS].

    3. There is current detected in a bay but the bay has no disconnector positions for dual busbars.

    The alarm can not be reset by energizing the binary input [BI_ConfirmDS]. In this case, the

    protective device can remember the original disconnector position of the bay, and check its

    validity based on the current distribution of system.

    4. If discriminating zone differential current is greater than 0.04IN due to the wrong disconnector

    position, an alarm will be issued with a time delay and the device can identify the right

    disconnector position based on the current distribution of system.

    Besides, in order to prevent the feeder from missing-operation because the bay has no

    disconnector position, no matter which busbar zone does the fault occur in, the bays whose CT

    correction coefficient is not zero but no disconnector position can be detected will be tripped.

    Note!

    When disconnector position alarm is issued, the operator must check the actual condition

    at first and then energize the binary input [BI_ConfirmDS] to reset the alarm if it is correct.

    Usually a button on the panel is provided, pressing the button will result in energizing the

    binary input [BI_ConfirmDS].

    3.6 VT Circuit Supervision

    1. If three times busbar negative sequence voltage (3U2) is larger than 0.2UN (UN: the secondary

    rated phase-to-ground voltage of VT), an alarm [Alm_VTS_BB1] or [Alm_VTS_BB2] will be

    issued with a time delay of 1.25s.

    2. If any busbar is in service and the sum of the amplitude of busbar three-phase voltage

    (|UA|+|UB|+|UC|) is smaller than UN, an alarm [Alm_VTS_BB1] or [Alm_VTS_BB2] will be

    issued with a time delay of 1.25s.

    3. When the logic setting [Opt_UnearthedSys_Mode] is set as 1, if three times busbar negative

    sequence voltage (3U2) is greater than 0.2UN or any phase-to-phase voltage is smaller than

    0.7UN_PP (UN_PP: the secondary rated phase-to-phase voltage of VT), an alarm

    [Alm_VTS_BB1] or [Alm_VTS_BB2] will be issued with a time delay of 1.25s.

    If the fault detector element picks up due to a disturbance in the system, the VT circuit supervision

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-21

    Date: 2012-08-31

    will be disabled. When VCE of a busbar operates, an alarm [Alm_Pkp_VCE_BB1] or

    [Alm_Pkp_VCE_BB2] will be issued with a time delay of 3s. When the three-phase voltage returns

    to normal condition, the alarm will be reset and the protective device will return to normal operation

    condition automatically with a time delay of 10s.

    3.7 CT Circuit Supervision

    3.7.1 CT circuit failure

    1. If check zone differential current is greater than the setting [I_Alm_CTS], an alarm [Alm_CTS]

    will be issued with a time delay of 5s and BBP will be blocked. The alarm can be reset only by

    pressing reset button on the panel to energize binary input [BI_RstTarg] after the CT circuit

    returns to normal condition.

    2. If check zone differential current is smaller than the setting i.e. [I_Alm_CTS] and both

    discriminating zone currents are greater than [I_Alm_CTS], an alarm [Alm_CTS_BC] will be

    issued with a time delay of 5s and BBP will not be blocked but single busbar mode will be

    enabled automatically. Under this situation, if any internal fault occurs, faulty busbar will not

    be identified. The alarm can be reset only by pressing reset button on the panel to energize

    the binary input [BI_RstTarg] even the CT circuit returns to normal condition.

    When VCE of any busbar operates, CT circuit failure will not be detected.

    3.7.2 CT circuit abnormality

    1. If check zone differential current is greater than the setting i.e. [I_Alm_SensCTS], an alarm

    [Alm_SensCTS] will be issued with a time delay of 5s. The alarm can be reset only by

    pressing reset button on the panel to energize the binary input [BI_RstTarg] after the CT

    circuit returns to normal condition.

    2. If check zone differential current is smaller than the setting [I_Alm_SensCTS] and both

    discriminating zone currents are greater than [I_Alm_SensCTS], an alarm

    [Alm_SensCTS_BC] will be issued with a time delay of 5s. The alarm can be reset only by

    pressing reset button on the panel to energize the binary input [BI_RstTarg] after the CT

    circuit returns to normal condition.

    3. BBP will not be blocked when CT circuit is abnormal.

    3.8 BC breaker substitution

    If BC breaker is used temporarily to substitute one of feeder breakers through transfer bus, the

    binary input [EBI_BT_BC] should be energized. The binary input [EBI_NegPolar_CT_BT] should

    be energized or de-energized according to the busbar arrangement. The polarity mark of feeder

    CT is on the busbar side, if the polarity mark of the substituted BC CT is on the busbar side, the

    binary input [EBI_NegPolar_CT_BT] should be de-energized and BC current will be calculated in

    check zone differential current and discriminating zone differential current. If the polarity mark of

    the substituting BC CT is on the feeder side, the binary input [EBI_NegPolar_CT_BT] should be

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-22

    Date: 2012-08-31

    energized and negative value of BC current will be calculated in check zone differential current

    and discriminating zone differential current.

    If BC breaker is used temporarily to substitute one of feeder breakers, the BC current will be taken

    as the current of the substituted feeder, whether the positive value or the negative value of the

    substituting BC current is calculated in check zone differential current and discriminating zone

    differential current depends on the status of the binary input [EBI_NegPolar_CT_BT].

    If the normally open auxiliary contact of substituting disconnector of BBx [BI_52a_DSBBx_BT] is

    energized, the BC breaker is substituting through BBx, and the BC current will be calculated in

    discriminating zone differential current of BBx.

    When BC breaker is used to substitute any of feeder breakers, some protection elements (such as

    SOTF protection, EFP and BFP) of BC will quit automatically, but overcurrent protection and pole

    disagreement protection are still reserved, which can be used as the protection function of the

    substituted feeder. In addition, some functions for BC breaker is used as a tie breaker connecting

    two busbars are also quit (such as: tripping BC breaker when busbar internal fault happens).

    Note!

    [EBI_NegPolar_CT_BT] should be energized prior to [EBI_BT_BC].

    1. Energizing the binary input [EBI_NegPolar_CT_BT]

    *

    BB2

    BB1

    BC

    * * * *

    Transfer Busbar

    Figure 3.8-1 BC breaker substituting through BB2

    The polarity mark of BC CT is on the feeder side, the binary input [EBI_NegPolar_CT_BT] should

    be energized. Negative value of BC current will be calculated in check zone differential current and

    discriminating zone differential current of BB2.

    2. De-energizing the binary input [EBI_NegPolar_CT_BT]

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-23

    Date: 2012-08-31

    *

    BB2

    BB1

    BC1

    * * * *

    Transfer Busbar

    Figure 3.8-2 BC breaker substituting through BB1

    The polarity mark of BC CT is on the busbar side, the binary input [EBI_NegPolar_CT_BT] should

    not be energized. Positve value of BC current will be calculated in check zone differential current

    and discriminating zone differential current of BB1.

  • 3 Operation Theory

    PCS-915A Busbar Protection 3-24

    Date: 2012-08-31

  • 4 Supervision

    PCS-915A Busbar Protection 4-a

    Date: 2012-08-31

    4 Supervision

    Table of Contents

    4 Supervision ..................................................................................... 4-a

    4.1 Overview .......................................................................................................... 4-1

    4.2 Protective Device Supervision ....................................................................... 4-1

    4.2.1 Hardware supervision .......................................................................................................... 4-1

    4.2.2 Opto-coupler Power Supervision ......................................................................................... 4-1

    4.2.3 Binary output supervision .................................................................................................... 4-1

    4.2.4 Binary input supervision ...................................................................................................... 4-1

    4.2.5 Setting supervision .............................................................................................................. 4-2

    4.2.6 Test Mode Supervision ........................................................................................................ 4-2

    4.2.7 Hardware Configuration Supervision................................................................................... 4-2

    4.3 AC Circuit Supervision ................................................................................... 4-2

    4.3.1 Voltage and current drift supervision and auto-adjustment ................................................. 4-2

    4.3.2 Sample supervision ............................................................................................................. 4-2

    4.4 Secondary Circuit Supervision ...................................................................... 4-2

    4.4.1 Voltage Transformer Supervision (VTS) .............................................................................. 4-2

    4.4.2 Current Transformer Supervision (CTS) ............................................................................. 4-2

    4.4.3 Disconnector position supervision ....................................................................................... 4-3

    4.4.4 BC breaker supervision ....................................................................................................... 4-3

    4.5 Handle Alarm ................................................................................................... 4-3

    4.5.1 List of self-supervision report............................................................................................... 4-3

    4.5.2 Self-Supervision Alarm List.................................................................................................. 4-7

    4.5.3 Repairmen suggestion of self-supervision report ............................................................... 4-11

    Table of Tables

    Table 4.5-1 Self-supervision report ........................................................................................... 4-3

    Table 4.5-2 Equipment self-check alarm list ................................................................................ 4-7

  • 4 Supervision

    PCS-915A Busbar Protection 4-b

    Date: 2012-08-31

    Table 4.5-3 Repairmen suggestion .......................................................................................... 4-11

  • 4 Supervision

    PCS-915A Busbar Protection 4-1

    Date: 2012-08-31

    4.1 Overview

    PCS-915 is a microprocessor based busbar protection which can provide successive automatic

    supervision to the protected object to ensure the power system can quickly restore from any fault

    to normal state. When the device is in energizing process before the LED HEALTHY is lightened,

    operators need to check the device operating state to ensure the automatic supervision function

    can work normally.

    The device will be blocked if there is any severe problem occurs in the hardware module or

    software program. Before reboot the relay, users are recommended to solve the problem or return

    the feedbacks to NR.

    When a failure is detected in the system, the fault message will be displayed on the LCD and the

    corresponding LED will be lightened. Meanwhile, the corresponding alarm output contacts will be

    energized and the failure alarm will be recorded and stored in the device. Users can either view

    the fault report directly on LCD or print out the report.

    The automatic supervision of PCS-915 has advantages in independent operation to the protection

    functions and is capable to identify the fault location when the fault occurs in the system.

    4.2 Protective Device Supervision

    4.2.1 Hardware supervision

    The automatic supervision function can provide monitoring of all chips on protection DSP module

    and fault detector DSP module to prevent any damaged or errors during the normal operation. The

    alarm signals [Alm_DSP_ProtBrd] or [Alm_DSP_FDBrd] will be issued if any damages or errors

    are dectected and the device will be blocked.

    4.2.2 Opto-coupler Power Supervision

    The automatic supervision can continuously monitor the positive power supply of opto-coupler, if a

    failure or damage is detected, then the alarm signal [Alm_Pwr_BI_Bxx] will be issued (xx is the slot

    No. of corresponding binary input module).

    4.2.3 Binary output supervision

    The state of binary outputs of each BO module is continually monitored. If any abnormality is

    detected, the alarm signals [Alm_Output_Bxx] will be issued with device being blocked (xx is the

    slot No. of corresponding BO module).

    4.2.4 Binary input supervision

    The state of binary inputs detected by protection DSP module and fault detector DSP module

    should be the same. Otherwise, the protective device will be blocked.

    If binary input [BI_Blk_BBP] is energized for over 1s, the alarm [Alm_Blk_BBP] will be issued and

    the blocking for BBP will be released.

  • 4 Supervision

    PCS-915A Busbar Protection 4-2

    Date: 2012-08-31

    If any binary input for initiating feeder BFP is energized for over 10s, the alarm

    [Alm_PersistFD_BFP] will be issued with BFP blocked.

    4.2.5 Setting supervision

    PCS-915 has 10 setting groups, while only one group is active at one time. The settings of active

    setting group are checked, if any is out of setting scopes, a corresponding alarm signal

    [Alm_Setting_Out-of-Range] will be issued with the protective device be blocked.

    If the EEPROM on protection DSP module or fault detector DSP module is damaged, it will lead to

    any summation error of all setting groups, the alarms [Alm_Setting] and [Alm_Setting_FDBrd] or

    [Alm_Setting_ProtBrd] will be issued with the protective device blocked.

    4.2.6 Test Mode Supervision

    When protection equipment is set to test mode by configuring the corresponding logic setting, the

    alarm signal [Alm_BO_Test] is issued without blocking equipment.

    4.2.7 Hardware Configuration Supervision