Page 1: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

88

Page 2: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

89

Page 3: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

90

Page 4: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

91

Page 5: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

92

Page 6: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

93

Page 7: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

94

Note: WI amendment for this section

Page 8: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

95

Page 9: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

96

Page 10: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

97

Page 11: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

98

Page 12: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

99

Page 13: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Boaraa

100

Page 14: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

101

Page 15: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

102

Page 16: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

103

Page 17: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

104

Page 18: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

105

Page 19: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

106

Page 20: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Corridor Fire-Resistance Rating IBC Table 1026.1

• Note that Table 1026.1 does not allow for corridors to be constructed in various non-sprinklered occupancies

– This is an important fact for those buildings having an R-2 occupancy which do not have an automatic sprinkler system installed per NFPA 13 or 13R See footnote c.

107

Page 21: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Corridors & Elevator LobbiesIBC 3006.2 vs 1020.6

• IBC 3006.2 requires that elevator lobbies be provided unless a listed exception is met—Review IBC 3006.3

• Note that even if the exception for application of IBC 3006.2 is met, the Designer must construct the corridor so as to meet the requirements of IBC 1020.6

108

Page 22: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

• Additionally, note that if the elevator opens into a fire rated corridor, then there shall be actions to either:

– 1) isolate the elevator shaft openings from directly opening into a rated corridor, or else…

– 2) install smoke protection on the doors of the elevator in order to fulfill the requirements of IBC 1020.6.

109

Corridors & Elevator LobbiesIBC 3006.2 vs 1020.6

Page 23: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Corridor ProtectionIBC 1020.6

• Example 1 recognizes the inclusion of an elevator lobby/corridor with 20 minute smoke and draft control assembly in the doors located between the elevator lobby and the fire rated corridor

110

Page 24: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

111

IBC 2015 Code & Commentary

Page 25: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Corridor ProtectionIBC 1020.6

• Example 2 recognizes the use of 20 minute smoke and draft control assemblies placed over the elevator entry points which require 1-1/2 hour fire protection rated assemblies

112

Page 26: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

113

IBC 2015 Code & Commentary

Page 27: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

114

Won-Door Fire & Security Solutions

Page 28: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Corridor ProtectionIBC 1020.6

• Example 3 allows a fire rated corridor to extend to 20 minute fire rated smoke and draft control door assemblies which allows one to enter an elevator lobby. The lobby could be entered by multiple fire rated corridors. Note that enclosed elevator lobbies as permitted by Item 1 of Section 1016.2 shall not be construed as intervening rooms.

115

Page 29: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

116

IBC 2015 Code & Commentary

Page 30: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

117

Page 31: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

118

Page 32: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

119

Page 33: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

120

Page 34: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

121

Page 35: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

122

Page 36: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

123

Page 37: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

124

Page 38: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

125

Page 39: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

126

Page 40: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

127

Page 41: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

128

Page 42: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

129

Page 43: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Posting of Occupant Load

• Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place near the main exit or exit access doorway from the room or space.

• Must be of approved legible permanent design and be maintained by owner or their agent

130

Page 44: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

131

Page 45: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Openings in a Interior Exit Stairway IBC 1023.4

• Openings in interior exit stairways and ramps, other than unprotected exterior openings, shall be limited to those necessary for exit access to the enclosure from normally occupied spaces and for egress from the enclosure

132

Page 46: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Openings in a Interior Exit Stairway IBC 1023.4

• Examples of spaces that are not allowed to open into the Interior Exit Stairway:

– Laundry Rooms

– Closets

– Toilet Rooms

– Janitor Closets

– Mechanical Rooms

– Electrical Rooms133

Page 47: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

134

Mechanical Room

“Corridor”Fire Rated Stairwell

One way to meet the intent of the code is to create a corridor between these spaces and fire rated stairwell

Page 48: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

135

Storage access from within the fire rated stairwell is not allowed

Page 49: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

136

Page 50: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

137

Storage access from within the fire rated stairwell is not allowed

Page 51: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Openings in an Interior Exit Stairway IBC 1023.4 & 3002.7

• Elevators shall not open into interior exit stairways and ramps

– Exception: Open parking garages.

138

Page 52: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Enclosures Under Interior Stairways IBC 1011.7.3

• The walls and soffits within enclosed usable spaces under enclosed and unenclosed stairways shall be protected by 1-hr fire resistance rated construction or the fire resistance rating of the stairway enclosure, whichever is greater. Access to the enclosed space shall not be directly from within the stairway enclosure.

139

Page 53: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

140

Page 54: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

141

Page 55: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

142

Avar

Page 56: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

What are your

thoughts?

143Inhabitat.com

Page 57: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

No storage under lowest landing, but at least it's sprinklered, and has a “guard” !!

144

Page 58: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Enclosures Under Exterior Stairways IBC 1011.7.4

• No usable space under exterior exit stairways unless the space is completely enclosed in 1 hr fire resistance rated construction. The open space under exterior stairways shall not be used for any purpose.

145

Page 59: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

A

146Aber Fence

Page 60: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

147Artistic Stairs

Page 61: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

148

Page 62: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

149

Page 63: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Stairway Identification Signs

• A sign shall be provided at each floor landing in an interior exit stairway and ramp connecting more than 3 stories designating the floor level, the terminus of the top and bottom of the interior exit stairway and ramp and the identification of the stairway or ramp.

150

Page 64: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Discharge IdentificationIBC 1023.8

151Randy Dahmen

Page 65: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Discharge IdentificationIBC 1023.8

• An interior exit stairway and ramp shall not continue below its level of exit discharge unless an approved barrier is provided at the level of exit discharge to prevent persons from unintentionally continuing into levels below.

152

Page 66: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

153Pacific Stair Corporation

Page 67: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

154Pacific Stair Corporation

Page 68: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

155

Page 69: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

156

Page 70: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

157

Page 71: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

158

Page 72: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

159

Page 73: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

160

Page 74: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

161

Page 75: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

162

Page 76: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Luminous Egress Path Markings IBC 1025

• Approved luminous egress path marking delineating the exit path shall be provided in high-rise buildings(occupied floor located more than 75 ft above the lowest level of fire dept. access) of Group A, B, E, I, M and R-1 occupancies

163

Page 77: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Luminous Egress Path Markings IBC 1025

• Steps –

– Req’r solid and continuous stripe applied to horizontal leading edge of each step and extend for the full length of the step.

– Outlining stripes to be 1” min. or 2” maximum

• Exception

164

Page 78: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Luminous Egress Path Markings IBC 1025

• Handrails & Handrail Extensions –

– Marked with a solid and continuous stripe with minimum width of 1”

– Stripe shall be placed on the top surface of the handrail for the entire length of the handrail, extensions & newel post caps.

• Exception

165

Page 79: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

166

Page 80: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Luminous Egress Path Markings IBC 1025

• Perimeter Demarcation Lines –

– Stair landings & other floor areas within interior exit stairways, interior exit ramps and exit passageways, with exception of the sides of steps, shall be provided with solid and continuous demarcation lines on the floor or on the walls or both

– Outlining stripes to be 1” min. or 2” maximum

• Exception

167

Page 81: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Luminous Egress Path Markings IBC 1025

• Wall-Mounted Demarcation Lines

– Perimeter demarcation lines shall be placed on the wall with the bottom edge of the stripe not more than 4” above the finished floor

– Where the wall line is broken by a door, demarcation lines on the walls shall continue across the face of the door or transaction the floor and extend across the floor in front of such door.

168

Page 82: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Luminous Egress Path Markings IBC 1025

169

Luminous Tape

Randy Dahmen

Page 83: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Luminous Egress Path Markings IBC 1025

• Obstacles

– Obstacles at or below 6’ 6” in height and projecting more than 4” into the egress path shall be outlined with markings not less than 1” in width, comprised of a pattern of alternating equal bands in width, consisting of luminous material and black. With alternating bands not more than 2” thick and angled at 45o

– Could include standpipes, hose cabinets, wall projections and restricted height areas.

170

Page 84: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

171

Such markings cannot conceal any required information or indicators including, and not be limited to, instructions to occupants for the use of the standpipes

Page 85: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

172

Page 86: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

173

Page 87: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Emergency Power for IlluminationSection 1008.3

• Item of discussion

– Where is emergency lighting required to be installed in an enclosed parking area requiring a minimum of 2 exits?

174

Page 88: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Interior Parking Ramp

175

Page 89: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Emergency Power for IlluminationSection 1008.3

• Item of discussion

– IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way of complying with IBC section 1008.1 and assuring the means of egress is illuminated when the space served is occupied?

176

Page 90: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Emergency Power for IlluminationSection 1008.3

177

Answer: Yes, the use of automatic controls, like occupancy sensors, is an acceptable way of conserving energy while also assuring the lights will be on during normal use of the spaces. When employing such automatic controls, their use must be incorporated into the design such that they will be overridden by the emergency power system upon loss of normal power. In essence, the switch controllers must be equipped for fail-safe operation. – Review UL 924 listed sensors (May 1, 2018)

Eaton

Page 91: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

178

Page 92: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Emergency lighting is required to be extended from the required bldg exit to exit discharge where there are 2

ways of travel. In this case, that location is at the bottom of the exterior ramp.

179

Page 93: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

180

Emergency lighting is required to be extended from the required bldg exit to exit discharge where there are 2

ways of travel. In this case, that location is at the bottom of the exterior ramp.

Page 94: 2015 IBC Means of Egress 1 - BIANEWbianew.org/yahoo_site_admin/assets/docs/2015_IBC... · – IBC 1008.1, 1008.3 and 2702.2.11: Is the use of occupancy sensors permitted as a way

Any Questions?