7+' 52' 729 heinz avenue 0,1 berkeley, ca 94710 0$; · rooftop ac unit typical rooftop ac...

9
DETAILS 7+' 52' 0$; 0,1 PIPE CLAMP WITH CUSHION (TYP.) P1000 2"x6" SUPPORT BLOCKING (TYP.) REFRIGERANT PIPING WITH INSULATION (TYP.) OR ELECTRICAL CONDUIT TYPICAL REFRIGERANT PIPE SUPPORT DETAIL scale: N.T.S. 1 M3.02 OUTDOOR CONDENSING UNIT MOUNTING DETAIL scale: N.T.S. 4 M3.02 TYPICAL CEILING MOUNTED FAN COIL SUPPORT DETAIL scale: N.T.S. 2 M3.02 HEAT PUMP BC CONTROLLER SUPPORT DETAIL scale: N.T.S. 3 M3.02 TYPICAL REFRIGERANT ROOF PIPE SUPPORT DETAIL scale: N.T.S. 5 M3.02 TYPICAL ROOF PIPE PENETRATION CURB scale: N.T.S. 6 M3.02 U-HANGER(TYP.) GALV. METAL BRACKET TYPICAL WOOD ATTACHMENT DETAIL scale: N.T.S. 8 M3.02 TYPICAL SEISMIC BRACING STIFFENER DETAIL scale: N.T.S. 7 M3.02 REVISIONS SHEET NUMBER SHEET TITLE N&T JOB # ISSUE DATE 729 Heinz Avenue Berkeley, CA 94710 tel 510.542.2200 fax 510.542.2201 SEAL APPROVALS 1901 HEARST ST. BERKELEY CA 94704 21603.00 12/19/18 # DATE DESCRIPTION EDDIE PADILLA 274 Devonshire Street CEILING REGISTER GALV. CABLE TIE GALV. CABLE TIE TITUS FEXABOOT SUPPORT ROOM WALL CEILING AIR TRANFER AIR DUC & REGISTERS scale: N.T.S. 9 M3.02 TITUS OMNI

Upload: others

Post on 07-Nov-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

DETAILS

PIPE CLAMP WITH

CUSHION (TYP.)

P1000

2"x6" SUPPORT BLOCKING (TYP.)

REFRIGERANT PIPING WITH

INSULATION (TYP.)

OR ELECTRICAL CONDUIT

TYPICAL REFRIGERANT PIPE SUPPORT DETAIL

scale: N.T.S.

1

M3.02

OUTDOOR CONDENSING UNIT MOUNTING DETAIL

scale: N.T.S.

4

M3.02

TYPICAL CEILING MOUNTED FAN COIL SUPPORT DETAIL

scale: N.T.S.

2

M3.02

HEAT PUMP BC CONTROLLER SUPPORT DETAIL

scale: N.T.S.

3

M3.02

TYPICAL REFRIGERANT ROOF PIPE SUPPORT DETAIL

scale: N.T.S.

5

M3.02

TYPICAL ROOF PIPE PENETRATION CURB

scale: N.T.S.

6

M3.02

U-HANGER(TYP.)

GALV. METAL BRACKET

TYPICAL WOOD ATTACHMENT DETAIL

scale: N.T.S.

8

M3.02

TYPICAL SEISMIC BRACING STIFFENER DETAIL

scale: N.T.S.

7

M3.02

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

CEILING REGISTER

GALV. CABLE TIE

GALV. CABLE TIE

TITUS FEXABOOT SUPPORT

ROOM WALL

CEILING AIR TRANFER AIR DUC & REGISTERS

scale: N.T.S.

9

M3.02

TITUS OMNI

PIPE CLAMP WITH

CUSHION (TYP.)

P1000

2"x6" SUPPORT BLOCKING (TYP.)

TYPICAL PIPE SUPPORT DETAILscale: N.T.S.

3

M3.03

P1000 SUPPORT CHANNEL

PIPE CLAMP WITH

CUSHION (TYP.)U-HANGER(TYP.)

GALV. METAL BRACKET

AIR FLOW

CWS

CWR

NOTES:

1. COORDINATE LEFT OR RIGHT HAND CONNECTION AS REQUIRED.

2. PROVIDE LOW VOLTAGE DDC CONTROLS. PROVIDE 120VAC TO 24VAC TRANSFORMER.

3. PROVIDE GRISWOLD CONTROL 'QUICKSET' CCP-2QIS ASSEMBLY OR BELIMO ASSEMBLY (OR AS PROVIDE BY THE

FAN COIL MANUFACTURER) SHALL INCLUDE QUICK SET MANUAL BALANCING VALVES, ISOLATION BALL VALVES,

UNIONS, DRAIN VALVES WITH HOSE END, PRESSURE TEMPERATURE TEST VALVE AND MANUAL AIR VENT.

CEILING REGISTER

VOLUME DAMPER

NOTES:

1. FLEXIBLE DUCT SHALL SHALL NOT EXCEED 5 FEET IN LENGTH.

2. FLEXIBLE DUCT SHALL BE FLEXIBLE AIR DUCT SHALL BE THERMAFLEX TYPE M-KE REINFORCED INSULATED TYPE RATE AT 4"WC

POSITIVE PRESSURE CLASS.

3. PROVIDE VOLUME DAMPER ON ALL BRANCH OR CONNECTIONS TO AIR DIFFUSERS.

FOUR #12 GAUGE WIRES

SUSPENDED FROM ABOVE PER

SMACNA STANDARDS AND

GUIDELINES FOR SEISMIC

RESTRAINTS

BELL MOUTH WITH WYE

CONNECTION FOR ROUND

PER SMACNA STDS.

16-GA X 1" WIDE SHEET METAL

TYPICAL HEATING COIL PIPING HOOK-UP DETAILscale: N.T.S.

NOTE: THIS DETAILS APPLIES TO FACTORY INSTALLED PIPING PACKAGE BY

FAN COIL MFG.

2

M3.03

2"x6" SUPPORT BLOCKING (TYP.)U-HANGER(TYP.)

AIR DIFFUSER/REGISTER DETAILscale: N.T.S.

4

M3.03

TYPICAL ROOF PIPE SUPPORT DETAILscale: N.T.S.

1

M3.03

BUILT-UP ROOFING

SEE MFR DTL FOR ROOF CURB

DUCT PENETRATION

SET BASE PLATE ON NEOPRENE PAD

SEAL WEATHER TIGHT.

4" FIBER CANT

ROOF CURB BY MFR

INSULATION AND COVER BOARD

FULL GASKETING; INNER AND

OUTER FLANGES

SEE MFR DTLS FOR MOUNTIL

SCREWS

PROVIDE MOUNTING

HARDWARE/BRACKET AS

REQUIRED

TYPICAL ROOFTOP AC UNIT ROOF CURB DETAILscale: N.T.S.

5

M3.03

MITFAB C-PORT C640 28 1/2"WIDE

PIPE SUPPORT

1" THICK SIPLAST OR

APPROVED WALKING PAD

BY ARCHITECT ROOFING SYSTEM

ROOF

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

T S

2-#18 ON/OFF

TO AIR BALANCE KIT

IN CONDUIT RECESS IN WALL

BY. MECH. CONTRACTOR

3-#18

COMM/24V/0-10VDC

TO AIR BALANCE KIT

IN CONDUIT RECESS IN WALL

3-#18

COMM/24V/0-10VDC

TO FAN ECM MOTOR

120 VAC POWER SUPPLY

TCP-1 : COOK FAN

AIR BALANCE KIT VFABK

IN RECESS NEMA 1 ENCLOSURE

PENAIR A10N104 WITH

HINGED COVER AND LATCH.

RECESS MOUNTED FAN COOK

TEMPERATURE CONTROLLER

MODEL VFTC/VFTC-N ON

2"X4" UTILITY ELECT. BOX

AT 48" AFF

RECESS MOUNTED, RECESS

ON/OFF TOGGLE SWITCH ON

2"X4" UTILITY ELECT. BOX.

SWITCH: HUBBELL NP1OW

AT 48" AFF

NOTE: LOW VOLTAGE WIRING AND CONDUIT SHALL BE PROVIDED BY THE

MECHANICAL CONTRACTOR. MECH. CONTRACTOR SHALL PROVIDE THE AIR

BALANCE KIT AND NEMA 1 TCP PANEL, TEMPERATURE CONTROLLER AND

ON/OFF TOGGLE SWITCH.

EXHAUST FAN EF-3 & EF-7 CONTROL DETAILscale: N.T.S.

6

M3.03

FLOOR MOUNTED

FAN COIL

3"X14" WIDE DUCT

(2)3"X14" FOR FC-C

7

M3.03

FRESH AIR INTAKE DETAIL TYPICAL

FOR HEATING WATER FAN COILSscale: NTS

FLOOR

ROOF

WATERPROOFING

SEALANT

BROAN NUTONE 634

ROOF CAP WITH

INSECT SCREENCOUNTER

FLASHING

10X10" DUCT

20 GA GALV. SHT. METAL SHIELD

DUCT FLEXIBLE CONN.(TYP.)

DOUBLE WALL GALV. WITH

2" THICK SUPER 'TUFF R' R-13

INSULATION FOR SUPPLY AND RETURN

AIR DUCT OUTDOOR INSTALLATION.

1 1/4" CONDENSATE DRAIN

TO NEAREST ROOF DRAIN.

DUCT, PIPE OR EQUIPMENT SUPPORT.

SEE SMACNA ARCH. STD. FIG. 4-17D, 6TH

ED. OR UNISTRUT 8DSA DOUBLE BASE

GALV. WITH POLYCARBONATE SUPPORT

BASE. SEE ARCH. DWGS. FOR ROOF

FLASHING.ROOF

PRE-FABRICATED

METAL ROOF CURB

ROOFTOP AC UNIT

TYPICAL ROOFTOP AC UNIT ROOF CURB DETAILscale: N.T.S. (FOR RTU-1, RTU-2 AND RTU-3)

8

M3.03

GALV. CABLE TIE

GALV. CABLE TIE

TITUS FEXABOOT SUPPORT

FRAME WALL

DX FAN COIL (AC UNIT) MOUNTING DETAL AND VENTILATION DETAILscale: N.T.S. (THIS DETAIL APPLIES TO MITSUBISHI FAN COIL (AC) PCFY AND PKFY)

9

M3.02

EXISTING FLOOR JOIST

GYP BD CEILING

PATCH TO MATCH

EXISTING

UNISTRUT P1281 W/ 3/8"

THRU BOLT INTO WOOD

(TYP. 4)

3/8"SUPPORT ROD

W/ STIFFENER

(TYP. 4)

SUPPORT

WOOD BEAMWATERPROOFING

SEALANT

BROAN NUTONE 634 ROOF CAP

WITH INSECT SCREEN O.A. INLETCOUNTER

FLASHING

R2 SERIES HEAT PUMP SYSTEM SCHEMATIC DIAGRAMSCALE: N.T.S.M4.01

1

TB2

TB1r e2c o

G

16-2 AWG(S)

FUSE

~208-230V

TB5 TB15

L1L2 G

FUSE

~208-230V

B15T5BT

L1L2 G

FUSE

~208-230V

16-2 AWG(S)

B15T5BT

L1L2 G

FUSE

~208-230V

B15T5BT

L1L2 G

FUSE

~208-230V

B15T5BT

L1L2 G

FUSE

~208-230V

B15T5BT

L1L2 G

FUSE

~208-230V

B15T5BT

L1L2 G

FUSE

~208-230V

B15T5BT

L1L2 G

FUSE

~208-230V

B15T5BT

L1L2 G

FUSE

~208-230V

B15T5BT

L1L2 G

FUSE

~208-230V

16-2 AWG(S)

BT 3

L1L2L3

)S(

G

208-230V/60Hz3~

FUSE

MA

28~16-2 AWG

MA

28~16-2 AWG

MA

28~16-2 AWG

MA

28~16-2 AWG

MA

28~16-2 AWG

MA

28~16-2 AWG

MA

28~16-2 AWG

MA

28~16-2 AWG

MA

28~16-2 AWG

MA

28~16-2 AWG

REF. PIPE

DISPLAY

DIAGRAM SYMBOL LEGEND

DESCRIPTION

CONTROL WIRE

POWER WIRE

PIPING LIST

SYMBOL BRANCH PIPE MODEL NAME

J1 REDUCER

SYMBOL LIQUID PIPE

P1 1/4" 1/2"

GAS PIPE

P2 3/8" 5/8"

J2 CMB-P1016NU-HA1

P3 7/8" 1-1/8"

208-230V/60Hz

1~

FUSE

PIPING AND CONTROLS

SYMBOL BRANCH PIPE MODEL NAME

J1 CMY-Y62-G-E

SYMBOL LIQUID PIPE

P1 3/8" 5/8"

GAS PIPE

P2 1/4" 1/2"

MA PAR-33MAA-J

S SERIES HEAT PUMP SYSTEM SCHEMATIC DIAGRAMSCALE: N.T.S. SERVES LOUNDGE AREAM4.01

2

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

PROCEDURE FOR INSTALLATION AND TESTING OF SPLIT SYSTEM MITSUBISHI REFRIGERATION SYSTEMS

1. THE FLARE FITTING'S CONTACT SURFACE MUST BE LUBRICATED WITH MANUFACTURER'S RECOMMENDED REFRIGERATION OIL PRIOR TO TIGHTENING FLARE FITTING.

2. FLARING OF COPPER TUBING SHALL BE DONE WITH A FLARE BLOCK WITH SET UP IN DIE PER MANUFACTURER'S INSTRUCTIONS. FLARE DIMENSIONS SHALL BE PER

MANUFACTURER'S DIMENSIONS. SAMPLES OF COPPER TUBING FLARES IN EACH SIZE USED ON PROJECT SHALL BE SUBMITTED FOR REVIEW AND APPROVAL PRIOR TO ON SITE

INSTALLATION OF FLARED CONNECTIONS.

3. ALL FLARE NUTS SHALL BE TORQUED PER MANUFACTURER'S REQUIREMENTS AS LISTED IN THEIR INSTALLATION MANUAL. INSTALLERS MUST HAVE TORQUE WRENCHES ON SITE

AND MUST BE USED DURING INSTALLATION OF FLARE FITTINGS.

4. BRAZING OF COPPER REFRIGERATION PIPING SHALL BE DONE WITH NON-OXIDIZING BRAZING MATERIAL SUCH AS 15% SILFOS. PURGE REFRIGERANT PIPING WITH 1-3 PSIG OF

NITROGEN WHILE BRAZING.

5. EXPANSION VALVES SHALL BE SHIPPED FROM THE MANUFACTURER IN THE OPEN POSITION.

6. SUBMIT CALCULATIONS OF REQUIRED REFRIGERANT CHARGE AS REQUIRED BY THE MANUFACTURER AND SUBMIT ONE COPY, ANOTHER COPY SHALL BE POSTED ON UNIT.

PROVIDE DOUBLE EVACUATION OF REFRIGERATION PIPING. VACUUM MUST BE PULLED ON THE SUCTION AND LIQUID SIDES OF THE OUTDOOR UNIT DURING ALL OF THE VACUUM

TESTING/NITROGEN PURGING PROCESS TO ENSURE THAT ALL OF THE PIPING IS DRY AND UNDER THE PURGE AND VACUUM PROCESS.

1. THE SYSTEM SHALL BE CHARGED WITH COMPRESSED DRY NITROGEN TO A PRESSURE OF 550 PSIG (THE PRESSURE CANNOT EXCEED 575 PSIG). THE CONTRACTOR SHALL VERIFY

THAT THE PRESSURE IS HELD AND REPAIR ANY LEAKS IN SYSTEM PRIOR TO PROCEEDING.

2. THE FIRST EVACUATION SHALL BE TO 1000 MICRONS. VACUUM SHALL BE BROKEN WITH COMPRESSED DRY NITROGEN, THROUGH THE CONDENSER DISCHARGE LINE, THE

CONTRACTOR SHALL VERIFY THAT THE PRESSURE IS HELD AND REPAIR ANY LEAKS IN SYSTEM PRIOR TO PROCEEDING

3. THE SYSTEM SHALL BE CHARGED WITH COMPRESSED DRY NITROGEN TO A PRESSURE OF 550 PSIG (THE PRESSURE CANNOT EXCEED 575 PSIG). . THIS PRESSURE SHALL BE

MARKED BY THE INSPECTOR AND VERIFIED TO HOLD PRESSURE WITH NO PRESSURE LOSS FOR A PERIOD OF A MINIMUM OF ONE (1) HOUR AND A MAXIMUM TEST PERIOD OF 2

HOURS AT THE DIGRESSION OF THE INSPECTOR. ALL VALVES TO THE NITROGEN TANK SHALL BE CLOSED DURING THE TEST. TEST SHALL BE WITNESSED BY OWNER'S

REPRESENTATIVE.

4. THE SECOND EVACUATION SHALL BE TO A MINIMUM VACUUM OF 300 MICRONS. THE VACUUM PUMP SHALL BE TURNED OFF AND ISOLATION VALVES SHUT OFF DURING THE TEST.

THE OWNER'S INSPECTOR SHALL INSPECT AND SIGN OFF ON THIS TEST VERIFYING THAT THE SYSTEM PRESSURE HAS NOT RISEN ABOVE 500 MICRONS AFTER A PERIOD OF AT

LEAST 1 HOUR TO A MAXIMUM TEST PERIOD OF 4 HOURS AT THE DIGRESSION OF THE INSPECTOR.

5. SYSTEM SHALL THEN BE IMMEDIATELY CHARGED WITH REFRIGERANT. CORRECTED REFRIGERANT CHARGE AND CALCULATED CHARGE REQUIREMENT SHALL BE PERMANENTLY

WRITTEN ON A LABEL INSIDE THE UNIT INDICATING DATE AND ACTUAL REFRIGERANT CHARGE WEIGHT INTRODUCED TO SYSTEM.

6. DURING TESTING PROCEDURE, THE TEST RESULT REPORT MUST BE SUBMITTED AND SIGNED OFF BY THE OWNER'S REPRESENTATIVE.

7. ANY FAILURE OF PRESSURE OR VACUUM TESTS AT ANY OF THE PREVIOUSLY MENTIONED STAGES WILL TRIGGER A COMPLETE RETEST OF THE REFRIGERATION SYSTEM

BEGINNING AT FIRST STEP.

ALL FAN COIL SHALL BE PROVIDED WITH HIGH EFFICIENCY DISPOSABLE FILTERS U.L. CLASS ll RATED.1

VOLTS NO.

EXTUNIT

S.P.CFM

MODELMFR

FAN DATA

PHASE

COOLING HEATING

OUTDOORAIR TEMP.

COOLING/HEATING DATA

BTUHCAPACITY

TYPEAREA

SQ. FT.

FILTER DATA

INDOORAIR TEMP. INCH DIA. BRAZED

PIPING CONNECTION

LIQUID GAS

POWER

HI/LO

ALL FAN COIL UNIT SHALL BE PROVIDED WITH CONDENSATE PUMP AND CONTROLS.3

MOISTURE

REMOVAL

GENERAL DATA

PINTS/HR

ENERGY

EFFICIENCY

SEER

SOUND LEVEL

dB(A)

MIN./MAX.

PIPING, WIRING AND SUPPORT INSTALLATION AND TESTING AND COMMISSIONING SHALL PER MANUFACTURER'S RECOMMENDATION.2

PROVIDE LOCAL DISCONNECT SWITCH PER DIV. 16.4

AC

X-X

INPUTMCA

AMPS

MOTOR

OUTPUTWATTS

AC-7

R2 SERIES AC INDOOR UNIT SCHEDULE (DEDUCT ALTERNATE NO.2)

PROVIDE THE FOLLOWING REQUIREMENTS:

DRAIN

ALL INDOOR FAN COIL UNITS SHALL BE PART OF MITSUBISHI CITY MULTI 'R2' SERIES.5

UNIT

MARK

PROVIDE CONDENSATE REMOVAL PUMP FOR FC-9. PUMP SHALL BE REFCO 'GOBI' 3.7 GPH, 65 FT. LIFT, 328 FT. MAX. HORIZONTAL RUN 16

WATTS MOTOR, 208 VOLT/ 1PH DDC CONTROLS, AUTO-SENSING, SAFETY SWITCH, THERMAL OVERLOAD PROTECTION, BUILT-IN

NON-RETURN VALVE, AUTO SHUT-OFF INDOOR AND OUTDOOR AC UNIT WHEN ON PUMP FAILURE. PUMP UNIT SHALL BE UL LISTED. UNIT

SHALL BE 18 dBA NOISE LEVEL MAX..

4

KWCOOLING/HEATING

WEIGHTLBS

REMARKS

REFRIGERANT

AC-8

AC-9

MARK DESCRIPTION REMARKS

CONDENSERMODEL NO.:

NOMINAL TONNAGE:

1 PROVIDE SINGLE POINT POWER CONNECTION 208/3PH

2

3

4

REFRIGERANT HIGH PRESSURE PROTECTION.

6

OVER-HEAT PROTECTION FOR COMPRESSOR.

7

PROVIDE THERMAL SWITCH PROTECTION FOR CONDENSER FAN MOTOR.

LOW AMBIENT CONTROLS

NOMINAL COOLING CAPACITY: 5

INVERTER CIRCUIT: OVER-CURRENT AND OVER-HEAT PROTECTION ON COMPRESSOR AND CONDENSER FAN.

8

DEFROST METHOD: PROVIDE AUTO-REVERSE MODE BY REVERSED REFRIGERANT CYCLE..

9

10 INSTALLER SHALL OBTAIN TRAINING AND CERTIFICATION FROM MITSUBISHI ON INSTALLATION, TEST AND

COMMISSIONING.

11

ALL WIRING AND CONDUIT FROM WEATHERPROOF J-BOX TO INTERIOR LIGHTS AND SWITCHES SHALL BE PROVIDED BY EQUIPMENT

MANUFACTURER.

MITSUBISHI OUTDOOR UNIT

PURY-P144TLMU-A-BS

SUMMER:

12 TONS

OUTDOOR DESIGN CONDITIONS

144,000 BTUH

OPERATING WEIGHT: 695 POUNDS

COOLING:

POWER INPUT NOMINAL

-

GENERAL

COMPRESSOR

CRANKCASE HEATER: -

COMPRESSOR TYPE: VARIABLE SPEED SCROLL HERMITIC

LUBRICANT: MEL32

QUANTITY: 2

REFRIGERANT TYPE: R410A

REFRIGERANT WEIGHT: 23 POUNDS + 2 OZ.

CONDENSER FAN TYPE: PROPELLER

QUANTITY: 2FAN

AIRFLOW RATE: 11,300 CFM

EXTERNAL STATIC PRESSURE: 0.00 INCH W.C.

EXTERNAL UNIT FINISH SHALL BE PRE-COATED GALVANIZED SHEET METAL WITH SEACOAST PROTECTION.

HEAT

EXCHANGER

SALT-RESISTANT CROSS FIN AND COPPER TUBE.

PIPING

CONNECTIONS

LIQUID HIGH PRESSURE: 7/8 INCH O.D. , BRAZED

GAS LOW PRESSURE: 1-1/8 INCHES O.D. , BRAZED

INDOOR:

OUTDOOR:

COOLING

TEMPERATURE RANGE SHALL BE:

CONTROL/DRIVE MECHANISM: DIRECT DRIVE WITH VFD

R2 SERIES OUTDOOR CONDENSING UNIT (DEDUCT ALTERNATE NO.2)

HEATING: -

MINIMUM CIRCUIT AMPACITY: 52 AMP.

MAXIMUM OVER CURRENT: 80

POWER SUPPLY: 208V/3PH/60HZ

SOUND POWER LEVEL: 61 dBA12

EFFICIENCY EER: 12.2

BC CONTROLLER

MODEL NO.: MITSUBISHI R2 SERIES

CMB-P108NU-GA

OPERATING WEIGHT: 122 POUNDS

COOLING:

POWER INPUT NOMINAL

0.112 KW

HEATING: 0.053 KW

MINIMUM CIRCUIT AMPACITY: 0.68 COOLING/0.75 HEATING

MOCP: 15A

POWER SUPPLY: 208V/1PH/60HZ

PROVIDE THE FOLLOWING ADDITIONAL REQUIREMENTS:

BALL VALVE 7/8" FLARE

BALL VALVE 1 1/8" FLARE

PCFY-P24NBMU-E2MITSUBISHI

-1 7127,00024,0001 95/750.0 80/67 3/8" 5/8"0.04/.04 208 -- - 31/370.52 1"494/

636

AC-10

AC-11

REFRIGERANTPCFY-P24NBMU-E2

MITSUBISHI-1 7127,00024,0001 95/750.0 80/67 3/8" 5/8"0.04/.04 208 -- - 31/370.52 1"

494/

636

REFRIGERANTPCFY-P24NBMU-E2

MITSUBISHI-1 7127,00024,0001 95/750.0 80/67 3/8" 5/8"0.04/.04 208 -- - 31/370.52 1"

494/

636

REFRIGERANTPCFY-P24NBMU-E2

MITSUBISHI-1 7127,00024,0001 95/750.0 80/67 3/8" 5/8"0.04/.04 208 -- - 31/370.52 1"

494/

636

REFRIGERANTPCFY-P24NBMU-E2

MITSUBISHI-1 7127,00024,0001 95/750.0 80/67 3/8" 5/8"0.04/.04 208 -- - 31/370.52 1"

494/

636

R410 ONLY

R410 ONLY

R410 ONLY

R410 ONLY

R410 ONLY

NOMINAL HEATING CAPACITY: 160,000 BTUH

AC-12MITSUBISHI

1 95/750.00.04/.04 208258/

328-0.26

PMFY-P12NBMU-E

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

PROVIDE THE FOLLOWING REQUIREMENTS:

1.

PROVIDE MERV 8 (35% EFFICIENCY), ASHRAE RATED.2.

PROVIDE NON-FUSED DISCONNECT SWITCH.3.

PROVIDE AIR INTAKE AND DISCHARGE DUCT CONNECTIONS FOR HORIZONTAL CONCEALED MODEL.4.

POWER SUPPLY SHALL BE 115V/ 1 PHASE.6.

7. PROVIDE ALL FAN COIL WITH MODULATING 2-WAY CONTROL VALVE WITH 'DELUXE' PIPING PACKAGE 'F' OR OTHERWISE NOTED.

10.

PROVIDE 1" THICK FIBERGLESS DUCT ACOUSTICAL LINER FOR 2-FEET AT DISCHARGEAND INLET FOR HORIZONTAL CONCEALED UNIT.

11.

HEATING COIL SHALL BE COPPER TUBE WITH ALUMINUM FINS.

9.

STANDALONE 24V DDCTRACER CN510 CONTROLLER WITH TEMPERATURE SENSOR IN RETURN AIR AND FAN SPEED CONTROL BUILT IN THE UNIT. FAN AND MOTOR ASSEMBLY SHALL REMOVABLE FROM ACCESS PANEL.

13. NOISE GENERATED FROM FAN COILS SHALL NOT EXCEED 30 dbA 3 FEET FROM THE UNIT. OTHER RATINGS SHALL

BE SUBJECT TO REVIEW AND APPROVAL BY THE OWNER.

EXT. SP: FAN COIL SHALL BE PROVIDE WITH STATIC PRESS CAPACITY AS INDICATED MEASURED AT SUPPLY

DISCHARGE AND RETURN AIR DUCT CONNECTIONS. EXT. SP MEASUREMENT EXCLUDING ALL INTERNAL FAN COIL

COMPONENTS INCLUDING COOLING COIL, HEATING COIL, FILTERS AND OTHER ACCESSORIES INTERNAL TO THE

FAN COIL UNIT.

14. FAN COILS SHALL BE DIRECT DRIVEN WITH ECM MOTOR WITH DELUXE SPEED CONTROLLER.

HEATING WATER FAN COIL SCHEDULE (TRANE)

MODEL NUMBER MANUFACTURER

NO.CFM

0.00

(IN.)

WEIGHT-LBS DIMENSIONS

CAP.

BTUH

TOTAL

EXT. S.P.HP

MOTOR

1

QTYFAN

GPM

HEATING WATER COIL DATA

WPDVOLT/PH/HZ

MCAWxLxH

INCHESRATED

CFM

ARI

2.75

DATA TO BE PROVIDED BY THE MANUFACTURER.*

63 125 500 1000 2000 NC250 4000MID FREQ. HZ

-DISCHARGERADIATED 46

8000

CONTROL VALVE

GPM CV

-FC-A 12,130TRANE FORCE-FLO 194

(FT) (IN.)

APD

0.13

L.W.T.E.W.T. L.A.T.E.A.T.

115-ECM0.86 3.5160 130 62.2 97 33x29x10-FFJB04

CABINET

TYPE

VERTICALSLOPED TOP

FAN DATA

-49

-49

-47

-44

-40

-32

-28

-43

0.00 1-FC-B 19,070TRANE FORCE-FLO 296 115-ECM0.99 1.1160 130 62.2 -FFJB06VERTICAL

SLOPED TOP

0.00 1-FC-C 40,000TRANE FORCE-FLO 296 115-ECM2.33 1.67160 130 62.2 -FFJB06VERTICAL

SLOPED TOP

0.00 1-FC-D 19,570TRANE FORCE-FLO 305 115-ECM0.89 3.73160 130 70.0 -FFHB06RESESSED

0.00 1-FC-E 19,570TRANE FORCE-FLO 305 115-ECM1.29 1.78160 130 62.2 -FFHB06

VERTICAL

0.50 1 3.88-FC-F 39,130TRANE FORCE-FLO 500 115-ECM2.61 7.78160 130 34.0 -FFCB06

RESESSEDVERTICAL

CONCEALEDHORIZONLATAL 0.22

-DISCHARGERADIATED 47

125 38x29x10-51

-50

-47

-41

-35

-24

-21

-43

-DISCHARGERADIATED 49

125 39x29x10-51

-50

-47

-41

-35

-24

-21

-43

-DISCHARGERADIATED 49

65 36x30x10-45

-50

-49

-45

-41

-32

-26

-45

-DISCHARGERADIATED 49

81 41x30x10-45

-50

-49

-45

-41

-32

-26

-45

71DISCHARGERADIATED 70

131 47x25x107268

6868

6666

6463

5959

5556

4951

6363

12. FAN AND MOTOR ASSEMBLY SHALL REMOVABLE FROM BOTTOM ACCESS PANEL FOR HORIZONTAL CONCEALED UNTS.

8. PROVIDE MODULATING 3-WAY CONTROL VALVE WITH 'DELUXE' PIPING PACKAGE 'F' FOR REMOTEST FAN COIL IN HALLWAY 146.

15.

118.3

118.3

114.3

117.8

113.4

106.2

ROWS

COIL

2

2

4

2

2

2 500

0.86

0.99

2.33

0.89

1.29

2.61

RPM

850

787

1086

998

1080

1479

0.13

0.13

0.13

0.13

2.75

2.75

2.75

2.75

194

296

296

305

305

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

16. PROVIDE ECONOMIZER AND DDC CONTROLS FOR FC-A, FC-B, FC-C, FC-D AND FC-E.

FC

X

FC

X

NOTATION ON PLAN

FAN COIL

OUTSIDE AIR CFM

WORKSHOP

111

STOR.

112

MECH. RM.

113

ART

SHOP

114

HALL

115

ADMIN

116 A

STOR.

117

ELECT.

118

MANAGERS OFC

119

LOCKER

121

STOR.

122

HALL

123

STOR.

124

125

126

REC.

127

TRASH

128

KITCHEN

129

(N) COFFEE

BAR 131

DINING

ROOM

132

MULTI-PURPOSEROOM

136

STOR

138

LOUNGE

144

WOMEN

161

HALL 142

GAME ROOM B

101GAME ROOM A

102

HEALTH

ROOM

103A

TOILET105

HEALTH

OFFICE 104

HALL

106STOR.

107

STOR.

108

ELEV

EQUIP

109

(N) MEETING RM

103B

FRONT

DESK154

ADVISORY

COUNCIL

OFFICE

155

ENTRY

143

HALL

146

ADMIN

OFC

153

DIRECTOR

OFC

147

COPY

148STOR.

149

STAFF

LOUNGE152

TOILET 151

STOR

141

STAGE

139

MTG RM 156

MEN

157

ELEV

000

OFFICE 2

116 B

OFFICE 3

116 C

JAN

2

FCC

FCA

4FCA

4

FCE

FCA

4

FCC

4

FCF

4

3

EF

16

EF5

10

11

11

11

8D

12D

14D

EF

4

811

9

11 11

11

11

2800

11

8D

8D

12D

14D

12

1212

12

12

12

T

15

12

11

16

16

11 11 11

1655

5

UP

1

1

A

D

5

7

B

C

3 6

42

2

E

F

C.5

UP

UP

FCA

4

FCA

4FCA

4

FCA

4FCA

4

FCC

4

FCC

4

T 13 T

1411 11

1 1 1

2

FCA

4

6D

11

5

T 4

1212

12

12

12

12

12

11

3/4"HWS/R

1"HWS/R

3/4"HWS/R

1/2"HWS/R

UP TO FC-B

ON 2ND FL.

3/4"HWS/R

1/2" CIRCUIT

SETTER

3/4"HWS/R

UP TO (E) EVAP COOLER

3/4"HWS/R

1/2"HWS/R1/2"HWS/R

1/2"HWS/R

3/4"HWS/R

1/2" CIRCUIT

SETTER

1/2"HWS/R

1/2"HWS/R UP

1/2"HWS/R UP

1"HWS/R

1 1/4"HWS/R

1/2"HWS/R

1/2"HWS/R

1/2"HWS/R

1 1/4"HWS/R

(E)1 1/2"HWS/R

POC

17

PIPE ANCHOR

PIPE ANCHOR

EXPANSION

COMPENSATOR

(TYP.) PIPE ANCHOR

PIPE ANCHOR

PIPE ANCHOR

PIPE ANCHOR

PIPE ANCHOR

4

4

4

4

4

4

4

4

4

4

4

4

4

4

44

4

4

4

129

11

8D

11

8X8

28X1428X14

8D

11

11

11

14D

10D24X14

10X8

24X12

12D

10D 10D

10D 10D

10D

12D

10X8

EF7

T

14

18

T

18

18 TCP

12

12 12

12

12

12

3/4"HWS/R 4

3/4"HWS/R TO

2ND FLOOR

60 60

(2)3"X14"0.A.

19

3/4"HWS/R 4

3/4"HWS/R

4

1

M2.21

FIRST FLOOR PLAN HVACscale: 1/8" = 1'-0"

CONSTRUCTION KEYED NOTES:EXISTING BOILERS AND DISTRIBUTION, PIPING AND CONTROLS TO

REMAIN.

EXISTING HEATING WATER RE-CIRCULATION PUMP AND PIPING AND

CONTROLS TO REMAIN. PROVIDE SEISMIC BRACE.

EXISTING POTTERY KILN DRYER: PROVIDE ROOF MOUNTED HEAT

EXHAUST FAN EF-4 AND CEILING MOUNTED AIR REGISTER. PROVIDE

18"X18" EXTERIOR WALL LOUVER 6" ABOVE FLOOR FINISH WITH GRAVITY

BACKDRAFT DAMPER AND INSECT SCREEN.

PROVIDE NEW FAN COIL WITH ASSOCIATED CONTROL VALVE, CONTROLS

AND UNIT MOUNTED TEMPERATURE SENSOR AND FAN SPEED

CONTROLS, ANCHOR AND SUPPORTS. PROVIDE LOCAL POWER

DISCONNECT. PROVIDE NEW HEATING PIPING AND INSULATION AS

INDICATED. PROVIDE NEW HEATING PIPING, INSULATION SUPPORTS AND

ANCHORS. PROVIDE OUTSIDE AIR VENTILATION. SEE DETAIL 7/M3.03.

EXISTING RESTROOM EXHAUST VENTILATION. REPLACE EXISTING

EXHAUST FAN (E-2 )LOCATED ON THE ROOF.PROVIDE NEW EXHAUST FAN

EF-1. TEST AND BALANCE TO AIRFLOW INDICATED .PROVIDE ROOF

MOUNTED SUPPLY AIR FAN AND DUCTWORK. SUPPLY FAN ON/OFF FAN

CONTROL SHALL BE FROM LIGHT SWITCH.TEST AND BALANCE SUPPLY

AIR TO 50 CFM EACH ROOM.

PROVIDE NEW ROOF MOUNTED EXHAUST FAN EF-4 COMPLETE WITH

THERMOSTAT CONTROL. PROVIDE FAN SPEED CONTROLS AND POWER

DISCONNECT POWER DISCONNECT, ROOF CURB SUPPORT AND

ANCHORS. SEE M1.02 FOR SCHEDULED REQUIREMENTS.

PROVIDE NEW ROOF MOUNTED AIR INTAKE VENT, SQUARE LOUVERED

TYPE, 12"X12" NECK WITH INSECT SCREEN AND BACKDRAFT DAMPER,

ROOF CURB SUPPORT AND ANCHORS.

PROVIDE SUPPLY AND RETURN AIR VENTILATION TO EXISTING COPIER

ROOM FROM NEW AC-3 ON ROOF. EXTEND EXISTING DUCT BRANCH AND

PROVIDE NEW AIR REGISTERS.

9

8

7

6

5

4

3

2

1

MECHANICAL ROOM. PROVIDE NEW ROOF MOUNTED EXHAUST

VENTILATION, 200 CFM, 1/4-HP, 115V/1P WITH BIRD SCREEN AND POWER

DISCONNECT.

10

EXISTING KITCHEN ROOF MOUNTED VENTILSTION MAHE-UP AIR UNIT AND

KITCHEN HOOD EXHAUST FAN TO REMAIN.

PROVIDE NEW AIR DISTRIBUTION DUCTWORK, AIR REGISTERS,

BALANCING DAMPERS, SUPPORTS, SEISMIC BRACE ASSOCIATED

ANCHORS AS INDICATED. TEST AND BALANCE TO AIRFLOW INDICATED.

12

11 PROVIDE SUPPLY AIR DIFFUSER, RETURN AND EXHAUST AIR REGISTER.

REFER TO M1.01 FOR SCHEDULED REQUIREMENTS. ADJUST TO AIRFLOW

INDICATED.

LOCATE WALL MOUNTED ROOM THERMOSTAT FOR RTU-1 AT THIS

LOCATION 48" ABOVE FLOOR.13

EXISTING DIFFUSER AND AIR REGISTER TO REMAIN ADJUST TO AIRFLOW

INDICATED.16

LOCATE WALL MOUNTED ROOM THERMOSTAT FOR RTU-2 AT THIS

LOCATION 48" ABOVE FLOOR.14

LOCATE WALL MOUNTED ROOM THERMOSTAT FOR RTU-2 AT THIS

LOCATION 48" ABOVE FLOOR.15

STORAGE RN. 117: PROVIDE ROOF MOUNTED HEAT EXHAUST FAN EF-5

AND CEILING MOUNTED AIR REGISTER. PROVIDE 18"X18" EXTERIOR

WALL LOUVER 6" ABOVE FLOOR FINISH WITH GRAVITY BACKDRAFT

DAMPER AND INSECT SCREEN.

17

1. REFER TO DETAILS M3.01 AND M3.02 FOR DETAILS.

VERIFY EXISTING DUCTS, PIPING AND EQUIPMENT LOCATION PRIOR TO

INSTALLATION OF NEW WORK. COORDINATE CLEARANCES AND ACCESS

WITH ARCHITECTURAL DRAWINGS. REFERENCE TO DETAILS APPLIES TO

ALL MECHANICAL WORK.

2. CONTRACTOR SHALL DETERMINE THE FINAL LOCATION OF THE FAN

COILS. LOCATE FAN COILS TO CLEAR BUILDING STRUCTURE, EXISTING

ELECTRICAL, PIPING AND OTHER OBSTRUCTIONS IN THE CEILING CAVITY.

COORDINATE INSTALLATION WITH ARCHITECTURAL DRAWINGS. PROVIDE

ADEQUATE ACCESS TO FILTERS, MOTORS AND VALVES.

GENERAL NOTES:

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

PROVIDE NEW ROOF MOUNTED EXHAUST FAN EF-7 COMPLETE WITH

THERMOSTAT CONTROL. PROVIDE FAN SPEED CONTROLS AND POWER

DISCONNECT POWER DISCONNECT, ROOF CURB SUPPORT AND

ANCHORS. MOUNT TCP AS HIGH POSSIBLE. SEE M1.02 FOR SCHEDULED

REQUIREMENTS AND DETAIL 6/M3.02 FOR DETAILS.

18

PROVIDE NEW ROOF MOUNTED AIR INTAKE VENT, SQUARE LOUVERED

TYPE, 14"X14" NECK WITH INSECT SCREEN AND BACKDRAFT DAMPER,

ROOF CURB SUPPORT AND ANCHORS. SEE M1.01 FOR DETAILED

REQUIREMENTS.

19

Ventilation Calculation

MULTI-PURPOSE AND DINING: (5X285+.06X4244)/1 = 1680 CFM

ADMIN AREA: (5X16 + 0.12X1442)/1 = 253 CFM

OFFICES 116 & 119: (5X11 + 0.12X1017)/1 = 177 CFM

ART SHOP & WORKSHOP: (10X40 + 0.18X 1830)/1 = 730 CFM

GAME ROOM B: (5X7 + 0.06X344)/1 = 56 CFM

GAME ROOM A:(5X7 + 0.06X366)/1 = 57 CFM

MEETING ROOM: (5X4 + 0.06X182)/1 = 31 CFM

LOUNGE ROOM 144: (5X20 + 0.06X1000 = 160 CFM.

CLASSROOMS A,B & C = (5X115 + 0.12X1685)/1 = 777 CFM

LIBRARY = (5X10 + 0.12X390)/1 = 97 CFM

EF

2

O.A. INTAKE

VENT

EF

1

EF

55

FCF

6D

8D

8D

8D

OPEN TO BELOW

OPEN TO BELOW

1

A

D

5

7

7

B

3 6

42

E

F

C.5

EF

4

10

FCB

4

FC

C4

FCC

4

FCC

4

14D

600 CFM

12x12 A.O.

INTAKE HOOD

ON ROOF

EF6

12

14D6D

6D

6D

6D

6D

EF7

13

EF3

HVAC ROOF OPENING (TYP.)

EXTEND SCREEN

36"x15" TYPICAL FOR RTU-1

& RTU-2 SUPPLY & RETURN

HVAC ROOF OPENING

452

452

452

1

M2.22

SECOND FLOOR PLAN - HVAC DEMOLITIONscale: 1/8" = 1'-0"

PROVIDE NEW 10-TON ROOFTOP AC UNIT, CONTROLS AND ROOM

THERMOSTAT, ROOF CURB AND ANCHORS. PROVIDE LOCAL POWER

DISCONNECT. SEE M1.01 FOR DETAILED REQUIREMENTS.

PROVIDE NEW HEATING WATER FAN COIL, TEMPERATURE CONTROL AND

ANCHORS. MODIFY EXISTING PIPING AS NECESSARY. RESTORE

EXISTING WALL OPENING AND WALL FINISH FOR RECESS FAN COIL.

PROVIDE LOCAL POWER DISCONNECT. SEE M1.01 FOR DETAILED

REQUIREMENTS.

PROVIDE NEW 8-TON ROOFTOP AC UNIT, CONTROLS AND ROOM

THERMOSTAT, ROOF CURB AND ANCHORS. PROVIDE LOCAL POWER

DISCONNECT. SEE M1.01 FOR DETAILED REQUIREMENTS.

PROVIDE NEW 4-TON ROOFTOP AC UNIT CONTROLS AND ROOM

THERMOSTAT, ROOF CURB AND ANCHORS. PROVIDE LOCAL POWER

DISCONNECT. SEE M1.01 FOR DETAILED REQUIREMENTS.

MECHANICAL ROOM VENTILATION: PROVIDE NEW ROOF MOUNTED

EXHAUST FAN EF-2 COMPLETE WITH POWER DISCONNECT, ROOF CURB

SUPPORT AND ANCHORS. SEE M1.01 FOR DETAILED REQUIREMENTS.

PROVIDE NEW ROOF MOUNTED AIR INTAKE VENT, SQUARE LOUVERED

TYPE, 14"X14" NECK WITH INSECT SCREEN AND BACKDRAFT DAMPER,

ROOF CURB, SUPPORTS AND ANCHORS. PROVIDE GREENHECK MODEL

WIH.

PROVIDE NEW EXHAUST FAN EF-1 AND ASSOCIATED DUCTWORK, ROOF

CURB, ANCHORS AND SUPPORTS, LOCAL POWER DISCONNECT. TEST

AND BALANCE TO AIRFLOW INDICATED .

6

8

7

5

1

2

3

4

PROVIDE NEW MECHANICAL ROOM EXHAUST VENTILATION FAN EF-5 AND

ASSOCIATED DUCTWORK, ROOF CURB, ANCHORS AND SUPPORTS,

LOCAL POWER DISCONNECT. SEE M1.01 FOR DETAILED REQUIREMENTS.

PROVIDE NEW AIR DISTRIBUTION DUCTWORK, AIR REGISTERS,

BALANCING DAMPERS, SUPPORTS, SEISMIC BRACE ASSOCIATED

ANCHORS AS INDICATED. TEST AND BALANCE TO AIRFLOW INDICATED.

9

PROVIDE NEW ROOF MOUNTED EXHAUST FAN EF-4 COMPLETE WITH

THERMOSTAT CONTROL FOR ART ROOM. PROVIDE FAN SPEED

CONTROLS AND POWER DISCONNECT POWER DISCONNECT, ROOF CURB

SUPPORT AND ANCHORS. SEE M1.01 FOR SCHEDULED REQUIREMENTS.

10

11PROVIDE NEW ROOM EXHAUST VENTILATION FAN EF-3 AND ASSOCIATED

DUCTWORK, ROOF CURB, ANCHORS AND SUPPORTS, LOCAL POWER

DISCONNECT FOR HALL 201. SEE M1.02 FOR DETAILED REQUIREMENTS.

PROVIDE TEMPERATURE AND FAN SPEED CONTROLS. SEE DETAIL

6/M3.03.

PROVIDE NEW ROOF MOUNTED EXHAUST FAN EF-6 COMPLETE WITH

THERMOSTAT CONTROL FOR STORE ROOM 117. SET THERMOSTAT AT

PROVIDE FAN SPEED CONTROLS AND POWER DISCONNECT

POWER DISCONNECT, ROOF CURB SUPPORT AND ANCHORS. SEE M1.01

FOR SCHEDULED REQUIREMENTS.

12

1"ACOUSTICAL

DUCT LINER

2

M2.22

FRESH AIR INTAKE DETAIL

FOR FAN COIL FC-Fscale: NTS

NOTE: REFER TO 8/M3.01 FOR SUPPORT DETAILS.

ROOF

GREENHECK WIR

AIR INTAKE

FC-F1"ACOUSTICAL

DUCT LINER

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

PROVIDE NEW ROOF MOUNTED EXHAUST FAN EF-7 COMPLETE WITH

THERMOSTAT CONTROL. PROVIDE FAN SPEED CONTROLS AND POWER

DISCONNECT POWER DISCONNECT, ROOF CURB SUPPORT AND

ANCHORS. SEE M1.02 FOR SCHEDULED REQUIREMENTS.

PROVIDE NEW ROOF MOUNTED AIR INTAKE VENT, SQUARE LOUVERED

TYPE, 12"X12" NECK WITH INSECT SCREEN AND BACKDRAFT DAMPER,

ROOF CURB SUPPORT AND ANCHORS. SEE M1.01 FOR DETAILED

REQUIREMENTS.

14

13

1. REFER TO ALL DETAILS ON M3.01, M3.02.

VERIFY EXISTING DUCTS, PIPING AND EQUIPMENT LOCATION PRIOR TO

INSTALLATION OF NEW WORK. COORDINATE CLEARANCES AND ACCESS

WITH ARCHITECTURAL DRAWINGS. REFERENCE TO DETAILS APPLIES TO

ALL MECHANICAL WORK.

2. CONTRACTOR SHALL DETERMINE THE FINAL LOCATION OF THE FAN

COILS. LOCATE FAN COILS TO CLEAR BUILDING STRUCTURE, EXISTING

ELECTRICAL, PIPING AND OTHER OBSTRUCTIONS IN THE CEILING CAVITY.

COORDINATE INSTALLATION WITH ARCHITECTURAL DRAWINGS. PROVIDE

ADEQUATE ACCESS TO FILTERS, MOTORS AND VALVES.

GENERAL NOTES:

R2 SERIES HEAT PUMP SYSTEM SCHEMATIC DIAGRAMSCALE: N.T.S. SERVES CLASSROOMS A,B &C AND LIBRARY (DEDUCT ALTERNATE NO.2)M4.01A

1

REF. PIPE

DISPLAY

DIAGRAM SYMBOL LEGEND

DESCRIPTION

CONTROL WIRE

POWER WIRE

PIPING AND CONTROLD

SYMBOL LIQUID PIPE

P1 3/8" 5/8"

GAS PIPE

P2 7/8" 1 1/8"

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

208-230V/60Hz

3~

FUSE

SYMBOL MODEL NUMBER

MA PAR-33MAA-J

13CU3

EF5

7

BC

CONTROLLER

IN MECH. RM.

REFRIG. PIPING

IN CLG. SPACE

RL&RG PIPING

FROM 1ST FLOOR

SEE M2.21

15

15

15

15

15

EF4

16

EF

3

OPEN TO BELOW

OPEN TO BELOW

1

A

D

5

7

7

B

3 6

42

E

F

C.5

EF2

FCF

6D

8D

8D

8D

14D

600 CFM

12x12 A.O.

INTAKE HOOD

ON ROOF

14D6D

6D

6D

6D

6D

EF7

18

HVAC ROOF OPENING (TYP.)

EXTEND SCREEN

36"x15" TYPICAL FOR RTU-1

& RTU-2 SUPPLY & RETURN

HVAC ROOF OPENING

4"VTR

1

M2.22

SECOND FLOOR PLAN - HVAC DEMOLITIONscale: 1/8" = 1'-0"

PROVIDE NEW 10-TON ROOFTOP AC UNIT, CONTROLS AND ROOM

THERMOSTAT, ROOF CURB AND ANCHORS. PROVIDE LOCAL POWER

DISCONNECT. SEE M1.01 FOR DETAILED REQUIREMENTS.

PROVIDE NEW HEATING WATER FAN COIL, TEMPERATURE CONTROL AND

ANCHORS. MODIFY EXISTING PIPING AS NECESSARY. RESTORE

EXISTING WALL OPENING AND WALL FINISH FOR RECESS FAN COIL.

PROVIDE LOCAL POWER DISCONNECT. SEE M1.01 FOR DETAILED

REQUIREMENTS.

PROVIDE NEW 8-TON ROOFTOP AC UNIT, CONTROLS AND ROOM

THERMOSTAT, ROOF CURB AND ANCHORS. PROVIDE LOCAL POWER

DISCONNECT. SEE M1.01 FOR DETAILED REQUIREMENTS.

PROVIDE NEW 4-TON ROOFTOP AC UNIT CONTROLS AND ROOM

THERMOSTAT, ROOF CURB AND ANCHORS. PROVIDE LOCAL POWER

DISCONNECT. SEE M1.01 FOR DETAILED REQUIREMENTS.

EXISTING KITCHEN HOOD EXHAUST FAN COMPLETE WITH CONTROLS,

AND POWER DISCONNECT TO REMAIN.

EXISTING MAKE-AIR UNIT WITH EVAPORATIVE COOLING, HOT WATER

HEATING COIL, CONTROLS, LOCAL POWER DISCONNECT, GFI OUTLET,

HEATING WATER PIPING AND CONTROL VALVE TO REMAIN.

PROVIDE NEW ROOF MOUNTED EXHAUST FAN EF-2 COMPLETE WITH

POWER DISCONNECT, ROOF CURB SUPPORT AND ANCHORS. SEE M1.02

FOR DETAILED REQUIREMENTS.

PROVIDE NEW ROOF MOUNTED AIR INTAKE VENT, SQUARE LOUVERED

TYPE, 12"X12" NECK WITH INSECT SCREEN AND BACKDRAFT DAMPER,

ROOF CURB SUPPORT AND ANCHORS. SEE M1.01 FOR DETAILED

REQUIREMENTS.

PROVIDE NEW EXHAUST FAN EF-1 AND ASSOCIATED DUCTWORK, ROOF

CURB, ANCHORS AND SUPPORTS, LOCAL POWER DISCONNECT. TEST

AND BALANCE TO AIRFLOW INDICATED .

8

12

11

13

7

6

5

1

2

3

4

PROVIDE NEW MECHANICAL ROOM EXHAUST VENTILATION FAN EF-5 AND

ASSOCIATED DUCTWORK, ROOF CURB, ANCHORS AND SUPPORTS,

LOCAL POWER DISCONNECT. SEE M1.02 FOR DETAILED REQUIREMENTS.

PROVIDE MULTI-CITY AC UNIT (FAN COIL) AND ASSOCIATED DUCTWORK

AND AIR REGISTERS. PROVIDE SUPPORTS, CONTROLS ZONE WALL

MOUNTED THERMOSTAT. REFER FOR SCHEDULED REQUIREMENT ON

DRAWING M1.1. PROVIDE INDEPENDENT UNISTRUT SUPPORT, ANCHORS

AND SEISMIC BRACE PER CBC 2016 AND SMACNA STANDARDS.

PROVIDE REFRIGERATION PIPING BETWEEN DX AC UNIT AND OUTDOOR

CONDENSING UNIT. REFER TO M4.01 FOR PIPE SIZE AND CONTROL FOR

R2-SERIES SYSTEM. PIPE SIZE FOR FAN COIL UNIT SHALL AS INDICATED

ON THE EQUIPMENT SCHEDULE ON M1.01. PIPING SHOWN ARE

INSULATED LINE-SET PAIR FOR EACH FAN COIL AND BETWEEN

CONDENSING UNIT AND BC CONTROLLER. PROVIDE PIPE SUPPORT AND

INSULATION. PROVIDE ALUMINUM JACKET FOR OUTDOOR PIPING

INSULATION. PROVIDE SILICATE INSERTS AT ALL SUPPORT POINTS.

15

9

PROVIDE MITSUBISHI 'CITY MULTI' VARIABLE REFRIGERANT FLOW

ZONING SYSTEM (VRFZ) 'R2' SERIES OUTDOOR CONDENSING UNIT (CU-3).

FIELD VERIFY REQUIRED CLEARANCES AT FINAL LOCATION. PROVIDE BC

CONTROLLER, PIPING FOR REFRIGERANT AND CONDENSATE DRAIN,

PROGRAMMABLE DDC CONTROLS, MOUNTING CURB, ANCHORS,

CONTROLS, POWER DISCONNECT, 120VAC WEATHERPROOF

RECEPTACLE AND PERMANENT LIGHTING ADJACENT TO THE OUTDOOR

CONDENSING UNIT. REFER TO M1.01 FOR SCHEDULED REQUIREMENTS.

PROVIDE NEW AIR DISTRIBUTION DUCTWORK, AIR REGISTERS,

BALANCING DAMPERS, SUPPORTS, SEISMIC BRACE ASSOCIATED

ANCHORS AS INDICATED. TEST AND BALANCE TO AIRFLOW INDICATED.

14

PROVIDE NEW ROOF MOUNTED EXHAUST FAN EF-4 COMPLETE WITH

THERMOSTAT CONTROL FOR ART ROOM. PROVIDE FAN SPEED

CONTROLS AND POWER DISCONNECT POWER DISCONNECT, ROOF CURB

SUPPORT AND ANCHORS. SEE M1.02 FOR SCHEDULED REQUIREMENTS.

16

REVISIONS

SHEET NUMBER

SHEET TITLE

N&T JOB #

ISSUE DATE

729 Heinz AvenueBerkeley, CA 94710

tel 510.542.2200fax 510.542.2201

SEAL

APPROVALS

1901 HEARST ST.

BERKELEY CA 94704

21603.00

12/19/18

# DATE DESCRIPTION

EDDIEPADILLA

274 Devonshire Street

PROVIDE NEW CONDENSATE DRAIN (CD) PIPING FOR ALL FAN COIL

UNITS. SLOPE DRAIN AT 1/8" PER FOOT TOWARDS EXISTING DRAIN

RECEPTOR. PROVIDE CLEANOUT AT EVERY CHANGE OF DIRECTION.

PIPING MATERIAL SHALL BE COPPER DWV TYPE WITH SOLDERED

JOINTS. SUPPORT PIPE AT EVERY 4 FOOT INTERVAL. PIPING SHALL BE IN

COMPLIANCE WITH CPC 2016. INSULATE DRAIN PIPE WITH 1/2"

FIBERGLASS WITH ASJ 6 FT. FROM THE EACH FAN COIL. TERMINATE

CONDENSATE DRAIN TO JANITOR SINK.

10

1. REFER TO DETAILS M3.01 AND M3.02 FOR DETAILS.

VERIFY EXISTING DUCTS, PIPING AND EQUIPMENT LOCATION PRIOR TO

INSTALLATION OF NEW WORK. COORDINATE CLEARANCES AND ACCESS

WITH ARCHITECTURAL DRAWINGS. REFERENCE TO DETAILS APPLIES TO

ALL MECHANICAL WORK.

2. CONTRACTOR SHALL DETERMINE THE FINAL LOCATION OF THE FAN

COILS. LOCATE FAN COILS TO CLEAR BUILDING STRUCTURE, EXISTING

ELECTRICAL, PIPING AND OTHER OBSTRUCTIONS IN THE CEILING CAVITY.

COORDINATE INSTALLATION WITH ARCHITECTURAL DRAWINGS. PROVIDE

ADEQUATE ACCESS TO FILTERS, MOTORS AND VALVES.

GENERAL NOTES:

PROVIDE NEW ROOF MOUNTED EXHAUST FAN EF-3 COMPLETE WITH

POWER DISCONNECT, ROOF CURB SUPPORT AND ANCHORS. SEE M1.02

FOR DETAILED REQUIREMENTS. PROVIDE TEMPERATURE AND SPEED

CONTROLS. REFER TO DETAIL 6/M303.

17

1"ACOUSTICAL

DUCT LINER

2

M2.22 scale: NTS

NOTE: REFER TO 8/M3.01 FOR SUPPORT DETAILS.

ROOF

GREENHECK WIR

AIR INTAKE

FC-F1"ACOUSTICAL

DUCT LINER

PROVIDE NEW ROOF MOUNTED EXHAUST FAN EF-7 COMPLETE WITH

THERMOSTAT CONTROL. PROVIDE FAN SPEED CONTROLS AND POWER

DISCONNECT POWER DISCONNECT, ROOF CURB SUPPORT AND

ANCHORS. SEE M1.02 FOR SCHEDULED REQUIREMENTS.

PROVIDE NEW ROOF MOUNTED AIR INTAKE VENT, SQUARE LOUVERED

TYPE, 12"X12" NECK WITH INSECT SCREEN AND BACKDRAFT DAMPER,

ROOF CURB SUPPORT AND ANCHORS. SEE M1.01 FOR DETAILED

REQUIREMENTS.

18

19