Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
1
ANNUAL MEETING OF THEREGIONAL OZONE NETWORK
FOR EUROPE & CENTRAL ASIABELGRADE, SERBIA, 10 -13 MAY 2011
Case study:Ammonia as a Refrigerant in the Water
Chiller for apple storage cooling (cold storage capacity is 8000 t)
Dipl.-Ing. Slobodan Pejkovi ć
Filter Frigo - Serbia
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
22
For chilling and storing apples, cooling installationhas been planned with water chiller using Freon 404Aas a refrigerant, and cools secondary fluid, mix of waterand glycol to -6ºC temperature and lower. Advantageof the secondary fluid is the possibility of temperaturecontrol in cold storages with small difference betweenthe air and secondary fluid’s temperature. In this way
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
3
the air and secondary fluid’s temperature. In this wayloss in weight of products is decreased. Besides that, itis also important that the quantity of a refrigerant insuch cooling systems is small.
Necessary cooling capacity for cooling and storing8000 tons of apples is around 1.1 MW.
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
3
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
4Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
4
Freon 404A as three component mixture of arefrigerants R143a / R125 / R134a has high globalwarming potential (GWP=3780). Therefore in theEuropean Union measures are contemplated whichwould lead to decreased use of this refrigerant. Thefirst of the measures introduced by Denmark since2011 is ecological tax for use of Freon 404Aamounting to 79€/kg, which shall be collected during
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
5
amounting to 79€/kg, which shall be collected duringFreon procurement.
That made us think of envisaging some of thenatural refrigerants for this cold storage. The choice
was ammonia.
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
5
Ammonia as a natural refrigerant has GWP=0,meaning that it does not influence global warming ofthe Earth, therefore its use is being stimulated.Advantages in using ammonia with strong smell is thatduring leakage which happens occasionally in coolinginstallations is that you can immediately sense it,
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
6
installations is that you can immediately sense it,remedy the failure and top-up the installation withrefrigerant without stopping. Differently from that,Freons, even R404A are without smell and its leakagefrom the cooling installation can not be observed untilpressure drops, that is, capacity decreases.
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
6
Because R404A is three-component mixture ofdifferent Freons, in case of leakage one mustdischarge the whole quantity from the installation(installation charge is around 300 kg), the failure mustbe remedied, than the installation should be vacuumed
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
7
be remedied, than the installation should be vacuumedand refilled. This procedure requires several hourswork and during that period the cooling installation cannot operate.
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
7
Ammonia as a refrigerant is cheaper. Exploitationcosts and maintenance costs of modern ammoniainstallations are lower than for Freon installations.
Installations with ammonia as a refrigerant aremore energy efficient, meaning that for achieving the
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
8
more energy efficient, meaning that for achieving thesame cooling capacity they shall spend lesselectricity. Due to poor mixing with oils for lubricatingcompressor, ammonia can be used in floodedevaporators at higher evaporating temperatures inrelation to Freons, simultaneously using lesselectricity.
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
8
In order to achieve the necessary glycoltemperature of -6ºC with ammonia as a refrigerant,the compressors can work with evaporationtemperature of -10ºC in flooded plate&shellevaporator and with suction gas superheat of 1K.
In order to achieve the same conditions (glycol
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
9
In order to achieve the same conditions (glycoltemperature and capacity) with Freon R404A as arefrigerant, the installation must have an directexpansion evaporator where the evaporationtemperature can not exceed -12ºC while suction gassuperheat must be from 6 to 10K.
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
9
Bitzerscrew
compressor
Ammonia R717 Freon R404A
Cooling
capacity
[kW]
Power
Consumption
[kW]
Energy Efficiency
Ratio
EER
Cooling
capacity
[kW]
Power
Consumption
[kW]
Energy Efficiency
Ratio
EER
Model OSKA8581-K
324 83.4 3.88 293 94.7 3.09
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
In order to present real difference between the ammonia and Freon404A installations, we shall present table with the cooling capacity and powerconsumption of screw compressor, product of Bitzer.
OSKA8581-K
Bitzerscrew compressor
Ammonia R717 OSKA8581-K
Freon R404A OSKA8581-K
Evaporation Temperature [°C] -10 -12
Condensing Temperature [°C] 35 35
Liquid Subcooling [K] 3 3
Suction Gas Superheat [K] 1 10
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
10
Operating regimes
Tables show that in installations using ammoniaas a refrigerant for the same compressor model,cooling capacity is 10% higher in relation to R404Awith smaller absorbed power for 11.3 kW.
During the first 27 days of work of the coldstorage with full capacity, when the daily apple intakeexceeds 300 t/day, electricity savings during work of4 screw compressors, products of Bitzer, model
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
11
4 screw compressors, products of Bitzer, modelOSKA8581-K with ammonia as a refrigerant would be29 MWh. Simultaneously, these compressors wouldhave 10% higher cooling capacity than the Freonones, and would enable quicker cooling of apples,which is very important for apple quality.
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
11
Analyses of different solutions using ammoniahave been made. One of the solutions was a chillerwith one screw compressor of 1150 kW coolingcapacity. Maximum cooling capacity for this type ofcold storage is necessary during the first 30 days ofwork, from start of apple picking. After that, needs forcooling decrease, as well as the external temperature,
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
12
cooling decrease, as well as the external temperature,and the water chiller has better condensing conditions.Therefore a solution with three water chillers has beendiscussed – chillers in variant 1 with water cooledcondenser, and in the variant 2 with air cooledcondenser. Both solutions have their advantages andshortcomings.
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
12
Advantage of the chiller with air cooledcondenser is installed in the container outside the coldstorage facility, so no special safety measures arerequired. Besides that, apples are stored in the periodfrom October to June, when we don’t have extremely
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
13
from October to June, when we don’t have extremelyhigh air temperatures, and the condensingtemperatures are such that they render sufficiently highEnergy Efficiency Ratio – EER.
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
13
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
14Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
14
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
15Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
15
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
Microchannel Condenser
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
16
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
17
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
AUTOMATIC OIL RECOVERY SYSTEM
For a regular, efficient and continuous operation of a chiller, it’s necessary to guarantee oil recovery to the compressor.
Oil often collects in the bottom part of the
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
18
Oil often collects in the bottom part of the evaporator, with the risk to compromise efficiency and heat exchange of the evaporator. For this reason an oil recovery system has been introduced; thanks to an ejector, oil at low pressure is conveyed from evaporator, with high pressure ammonia to the compressor suction.
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
19
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
20
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
21
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
22
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
23
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
24
Unit prices for the equpment:
� Ammonia water chiller; piston compressor,water cooled condenser - - - - - - - - - - - - - - € 135.000
� R134a water chiller; 2 Turbocor compressors,
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
� R134a water chiller; 2 Turbocor compressors,water cooled condenser - - - - - - - - - - - - - - € 92.000
� R134a water chiller; 2 screw compressors,water cooled condenser - - - - - - - - - - - - - - € 59.000
� Cooling capacity 400 kW
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
25
Price for the cooling system:
� R404a glycol chiller system;cooling capacity – 1.200 kW4 screw compressors,
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
4 screw compressors,1 evaporative condenser
for 4 compressors € 260.000
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling
26
CONCLUSION Advantages of ammonia as a refrigerant:� Ammonia as a natural refrigerant does not influence global warming of
Earth.� Ammonia as a refrigerant is cheaper than Freon.� Exploitation costs and maintenance costs of modern ammonia installations
are lower than for Freon ones.� Installations with ammonia as a refrigerant are more energy efficient.
Roundtable on climate & ozone-friendly technologies in refrigeration & air-conditioning
27
Shortcomings of ammonia as a refrigerant:� Investment costs in making ammonia installations significantly exceed the
costs of making Freon installations.� Safety measures that should be undertook in using ammonia installations
due to its explosiveness cause fear with investors and influence the final price of the installation.
Belgrade, May 10, 2011 Slobodan PejkovićAmmonia as a Refrigerant in the Water Chiller for apple storage cooling