michael krüger © omicron new tools for diagnostic measurements on electical rotating machines

Post on 24-Dec-2015

227 Views

Category:

Documents

8 Downloads

Preview:

Click to see full reader

TRANSCRIPT

Michael Krüger © OMICRON

NEW TOOLS FOR DIAGNOSTIC MEASUREMENTS ON ELECTICAL ROTATING MACHINES

Annual Convention 2014 – Eilat, Israel 2

New Tools for Diagnostic Measurements on Rotating Electrical Machines

• Introduction

• Insulation Resistance and the Polarisation Index (PI)

• Dielectric Response

• Capacitance and Dielectric Dissipation (Power) Factor

• Partial Discharge (PD) Measurement

• Online PD Measurements on a 330MVA Hydro Generator

• PD Location

• Case Study - Measurements on a Hydro Generator

Annual Convention 2014 – Eilat, Israel 3

Sources of Insulation Damages

Source: Brütsch et al. "Insulation Failure Mechanisms of Power Generators", DEIS July/August 2008

Annual Convention 2014 – Eilat, Israel 4

A: small voids on edge

B: delamination: winding – main insulation

C: delamination of tape layers

D: treeing in layers

E: broken strands

G: micro voids

F: slot discharge, semicon paint abrasion

H: Discharges in Cooling Duct

I: Delamination of Insulation in Elbow

J: endwinding surface discharge - contamination

K: Insufficient Spacing, Tracking

L: Connection area between slot corona protection and endwinding corona protection

Electrical Failures

Annual Convention 2014 – Eilat, Israel 7

New Tools for Diagnostic Measurements on Rotating Electrical Machines

• Introduction

• Insulation Resistance and the Polarisation Index (PI)

• Dielectric Response

• Capacitance and Dielectric Dissipation (Power) Factor

• Partial Discharge (PD) Measurement

• Online PD Measurements on a 330MVA Hydro Generator

• PD Location

• Case Study - Measurements on a Hydro Generator

Annual Convention 2014 – Eilat, Israel 8

Insulation Resistance Measurement

Measurement Time Current

U-VWE 60 s25.9809 nA

Measurement Time Current

U-VWE 600s 3.7637 nA

PI = 25.98 / 3.76 = 6.9

Annual Convention 2014 – Eilat, Israel 9

Time Constant

dry

humid

Annual Convention 2014 – Eilat, Israel 10

New Tools for Diagnostic Measurements on Rotating Electrical Machines

• Introduction

• Insulation Resistance and the Polarisation Index (PI)

• Dielectric Response

• Capacitance and Dielectric Dissipation (Power) Factor

• Partial Discharge (PD) Measurement

• Online PD Measurements on a 330MVA Hydro Generator

• PD Location

• Case Study - Measurements on a Hydro Generator

Annual Convention 2014 – Eilat, Israel 11

Dielectric ResponseCombination of PDC and FDS

Cu

rre

nt

[nA

]

Zeit [s]

Trans-formation

Frequency [Hz]

Ve

rlust

fakt

or

0,0010,001

1

1000

10001

100

1

Frequenz [Hz]

Tan

De

lta

1000

1

0,0010,1

1. f > 0,1 Hz

Frequency Domain

2. f < 0,1 Hz

Time Domain

3. Transformation of the Time

Domain Data into the

Frequency Domain

Polarisations- und DepolarisationsstromPDC

Frequency Domain Spectroscopy FDS

Annual Convention 2014 – Eilat, Israel 12

FDS / PDC Measurement

Annual Convention 2014 – Eilat, Israel 13

FDS / PDC Measurement with 2 Channels

Annual Convention 2014 – Eilat, Israel 14

New Tools for Diagnostic Measurements on Rotating Electrical Machines

• Introduction

• Insulation Resistance and the Polarisation Index (PI)

• Dielectric Response

• Capacitance and Dielectric Dissipation (Power) Factor

• Partial Discharge (PD) Measurement

• Online PD Measurements on a 330MVA Hydro Generator

• PD Location

• Case Study - Measurements on a Hydro Generator

Annual Convention 2014 – Eilat, Israel 15

Measurement of Dielectric Losses

Dielectric losses in insulating systems (tan )conducting losses (tan C)

polarization losses (tan P)

partial discharge losses (tan PD)

tan = tan C + tan P + tan PD

Dielectric losses: tan = f (U)

Tip-Up Test according to IEEE 286 ΔTan-Delta Test according to IEC 60894

Annual Convention 2014 – Eilat, Israel 16

Test Setup C-Tan-Delta Measurement

Annual Convention 2014 – Eilat, Israel 17

New Tools for Diagnostic Measurements on Rotating Electrical Machines

• Introduction

• Insulation Resistance and the Polarisation Index (PI)

• Dielectric Response

• Capacitance and Dielectric Dissipation (Power) Factor

• Partial Discharge (PD) Measurement

• Online PD Measurements on a 330MVA Hydro Generator

• PD Location

• Case Study - Measurements on a Hydro Generator

Annual Convention 2014 – Eilat, Israel 18

PD Fault in Head Windings

VATech Hydro Austria

Annual Convention 2014 – Eilat, Israel 19

Cross-Coupling in the Stator Winding

• CORE

CORE

L1 L2

L3 neutral

• 3 2 1 36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 36 35 34 33 32

EE

H

• PD

• Capacitive Coupling• Inductive Coupling• Capacitive & Inductive Coupling• Capacitive Coupling• Inductive Coupling

• Capacitive & Inductive Coupling to the coils of the same phase

Capacitive & Inductive Coupling to the coils of other two phases

Annual Convention 2014 – Eilat, Israel 20

PD Measurement with 3 Synchronous Channels

L1

L2

L3

L1

L2

L3

Inner PD source L1>L2>L3

3PARD

• timeframe 1

µs

Interne TE Quelle in der L1 Wicklung

3PARD = 3 Phase Amplitude Related Diagram

Annual Convention 2014 – Eilat, Israel 21

Synchronous 4-Channel PD Measurement Phase U1-U2

Annual Convention 2014 – Eilat, Israel 22

Channel 1 = U1

Annual Convention 2014 – Eilat, Israel 23

Channel 2 = U2

Annual Convention 2014 – Eilat, Israel 24

Channel 3 = V1

Channel 4 = W1

Annual Convention 2014 – Eilat, Israel 26

Synchronous 4-Channel PD Measurement without Filtering

U1 U2

V W

Annual Convention 2014 – Eilat, Israel 27

3PARD

3PARD = 3 Phase Amplidude Related Diagram

or in this case:

3 Channel Amplitude Related Diagram

U1

U2V

Annual Convention 2014 – Eilat, Israel 28

Synchronous 3-Channel PD Measurment with 3PARD Filtering - Cluster A

A

U1

U2

V

Annual Convention 2014 – Eilat, Israel 29

Synchronous 3-Channel PD Measurment with 3PARD Filtering - Cluster B

B

U1

U2

V

Annual Convention 2014 – Eilat, Israel 30

Simultaneous Measurement of PD, Capacitance and Tan Delta

Annual Convention 2014 – Eilat, Israel 31

Simultaneous Measurement of PD, Capacitance and Tan Delta on U-VWE

C-tanδ und PD Levels + PRPD at 23 Voltage Levels in approx. 6 Minutes

Annual Convention 2014 – Eilat, Israel 32

New Tools for Diagnostic Measurements on Rotating Electrical Machines

• Introduction

• Insulation Resistance and the Polarisation Index (PI)

• Dielectric Response

• Capacitance and Dielectric Dissipation (Power) Factor

• Partial Discharge (PD) Measurement

• Online PD Measurements on a 330MVA Hydro Generator

• PD Location

• Case Study - Measurements on a Hydro Generator

Annual Convention 2014 – Eilat, Israel 33

Measurement SetupCoupling Capacitors

Annual Convention 2014 – Eilat, Israel 34

PD Coupler

Annual Convention 2014 – Eilat, Israel 35

PD Instruments connected to the Couplers

Annual Convention 2014 – Eilat, Israel 37

PD Measurement without Filtering

Annual Convention 2014 – Eilat, Israel 38

PD Measurement with 3PARD Filtering

Annual Convention 2014 – Eilat, Israel 44

New Tools for Diagnostic Measurements on Rotating Electrical Machines

• Introduction

• Insulation Resistance and the Polarisation Index (PI)

• Dielectric Response

• Capacitance and Dielectric Dissipation (Power) Factor

• Partial Discharge (PD) Measurement

• Online PD Measurements on a 330MVA Hydro Generator

• PD Location

• Case Study - Measurements on a Hydro Generator

Annual Convention 2014 – Eilat, Israel 45

Generator

Annual Convention 2014 – Eilat, Israel 46

Dielectric Response with FDS

Annual Convention 2014 – Eilat, Israel 47

Dielectric Response with PDC

Annual Convention 2014 – Eilat, Israel 48

Drying of the Winding with 250A

Annual Convention 2014 – Eilat, Israel 49

Drying of the Winding with 250A

Annual Convention 2014 – Eilat, Israel 50

Winding Resistance Measurement with 100A

0.0Ω

0.005Ω

0.01Ω

0.015Ω

0.02Ω

0.025Ω

0.03Ω

0.035Ω

0.04Ω

0.045Ω

0.05Ω

U

V

W

Annual Convention 2014 – Eilat, Israel 51

Fault: Broken Soldered Joints

Annual Convention 2014 – Eilat, Israel 52

Measurement of the Dielectric Response Before and After Drying (FDS - tanδ)

before drying

after drying

tanδ [%]

Annual Convention 2014 – Eilat, Israel 53

Measurement of the Dielectric Response Before and After Drying (FDS - Capacitance)

before drying

after drying

c‘ [F]before drying: C’ (1mHz) / C (50Hz) = 14.3

after drying: C’ (1mHz) / C (50Hz) = 2.5

Annual Convention 2014 – Eilat, Israel 54

Measurement of the Dielectric Response Before and After Drying (PDC)

before drying

after drying

Annual Convention 2014 – Eilat, Israel 55

Dismounted Rotor

Annual Convention 2014 – Eilat, Israel 56

Dirt in the End Windings

Annual Convention 2014 – Eilat, Israel 57

Dirt in the End Windings

Annual Convention 2014 – Eilat, Israel 58

After Cleaning the End Windings

Annual Convention 2014 – Eilat, Israel 62

PD Test Phase U up to 6400V

Breakdown at 6400V

Annual Convention 2014 – Eilat, Israel 63

Location of the Breakdown (Smoke with 2A)

Annual Convention 2014 – Eilat, Israel 64

Lower or Upper Bar ? (I = 2A)

0.01A

2.04A

Annual Convention 2014 – Eilat, Israel 65

Cutting out the Faulty Coil

Annual Convention 2014 – Eilat, Israel 66

New Soldering Joints

Annual Convention 2014 – Eilat, Israel 67

Insulated Soldering Joint

Annual Convention 2014 – Eilat, Israel 68

Repaired Winding

Annual Convention 2014 – Eilat, Israel 69

FDS Phase U – Before and After Repair

before repair and drying

before repair after drying

after repair

Annual Convention 2014 – Eilat, Israel 70

FDS Phase U – Before and After Repair

before repair and drying

before repair after drying

after repair

michael.krueger@omicron.at

Questions and Remarks?

top related