areva mbch 12 13 differential protection
TRANSCRIPT
Type MBCH 12, 13, 16Biased Differential Protection forTransformers, Generators and
Generator Transformers
2
Type MBCH 12, 13, 16Biased Differential Protection for Transformers,Generators and Generator Transformers
Features
• Independent single phase relayssuitable for single or three phasetransformer protection schemes
• Fast operating times, typically10ms to 25ms
• Dual slope percentage biasrestraint characteristic withadjustable basic threshold settingof 10% to 50% In, selectable in10% steps
• High stability during throughfaults even under conditions of CTsaturation and with up to 20%ratio imbalance resulting from theeffects of tap changing and CTerrors
• Magnetising inrush restraint over-excitation (over-fluxing) restraint
• Up to six biased inputs
• Transformer phase group and lineCT ratio correction by means ofseparate tapped interposingtransformers where required
• Two isolated change-over trippingcontacts plus one isolatednormally open latching alarmcontact. The individual phaseelements can be interconnectedto provide six isolated change-over tripping contacts for threephase schemes
• Light emitting diode (led) faultindication.
ApplicationThe type MBCH 12, 13 and 16 arehigh-speed, single phase, biaseddifferential relays suitable for theprotection of two- or three-windingpower transformers, auto-transformers, or generator-transformer units. Up to six biasedcurrent inputs can be provided tocater for power transformers withmore than two windings and/ormore than one circuit-breaker
controlling each winding, as in‘mesh’ or ‘one and a half circuit-breaker’ busbar arrangements.Typical applications are shown inFigures 2 to 8.
As a general low impedance biaseddifferential relay, the MBCH mayalso be regarded as an alternativeto the high impedance type relay forthe protection of reactors, motorsand generators.
Models Available
Type Designation No. of Bias ApplicationCircuits
MBCH 12 2 Two-winding power transformerMBCH 13 3 Generally 3 winding power transformer,
where bias is required from each of the 3groups of CTs
MBCH 16 6 For all applications requiring 4, 5 or 6bias circuits
Figure 1:Relay Type MBCH 16withdrawn from case
3
DescriptionThe relay is extremely stable duringthrough faults and provides high-speed operation on internal faults,even when energised via linecurrent transformers of onlymoderate output. Immunity to falsetripping due to large inrush currentson energisation of the powertransformer, and also duringoverfluxing conditions, is providedby the use of a novel feature notinvolving harmonic filter circuits andtheir associated delay.
It can be beneficial to supplementthe differential protection by arestricted earth fault relay,especially where the neutral point ofthe power transformer is earthedvia a current limiting resistor. Therestricted earth fault relay (typeMCAG 14 or MFAC 14) may beconnected into the differentialcircuitry, in association with acurrent transformer in the neutralconnection of the powertransformer, as indicated in Figures3 and 6. Additional line currenttransformers are not required.
For optimum performance, thedifferential scheme should bearranged so that the relay will seerated current when full load currentflows in the protected circuit. Thismay be achieved either byappropriate choice of main linecurrent transformers, or the use ofinterposing current transformers.
When protecting a powertransformer, the differential settingshould not be less than 20% relayrated current, to give stability formoderate transient overfluxing. Themaximum spill current with throughload current should generally bekept below 20% of the relay ratedcurrent, allowing for CT mismatchand possible tap changeroperation. Where higher levels ofspill current exist, the relay settingmay need to be increased.
A tapped interposing transformer isavailable for ratio matching of themain current transformers. The tapsare spaced at intervals of 4% andbetter, allowing matching to wellwithin 2% in most cases. The sameinterposing transformers may also
be used where necessary for powertransformer phase shift correction.
For some applications, no phaseshift correction is necessary, but azero sequence current trap isrequired to prevent zero sequencecurrents, due to external earth faultsbeing seen by the differential relay.Two secondary windings areprovided on the interposingtransformer to allow the creation ofan isolated delta connection for thispurpose.
Each relay case incorporates aterminal block, for externalconnections, into which the moduleis plugged. Removal of the modulefrom the case automatically causesthe incoming line current transformerconnections to be short-circuited,followed by the open circuiting ofthe relay tripping circuit.
Setting adjustment is by means offrontplate mounted switches.Indication of relay operation isprovided by an led, also mountedon the relay frontplate, and which isresettable by a push button operablewith the relay cover in position. Theoutput elements consist of auxiliaryattracted armature relays, thecontacts of which are capable ofcircuit-breaker tripping. Threeelectrically independent contacts,comprising two self-resetting change-over contacts and one hand reset,normally open contact are providedper pole, for circuit breaker trippingand alarm purposes respectively. Byinterconnecting relays as shown inFigure 9, up to six self-resettingchange-over contacts can beprovided for the three-phase trippingof up to six circuit-breakers.
Functional DescriptionThe differential transformerprotection measuring circuit is basedon the well known Merz-Pricecirculating current principle.Figure 10 shows the relay functionalblock diagram. The outputs fromeach bias restraint transformer T3 toT5, proportional to the appropriateprimary line currents, are rectifiedand summed to produce a biasrestraint voltage. Any resultingdifference current is circulatedthrough transformers T1 and T2.
The output from T1 is rectified andcombined with the bias voltage toproduce a signal which is appliedto the amplitude comparator. Thecomparator output is in the form ofpulses which vary in widthdepending on the amplitude of thecombined bias and differencevoltages. Where the measurementof the interval between these pulsesindicates less than a preset time, aninternal fault is indicated and a tripsignal, initiated after a short delay( s), level set by the bias. If, duringthe above mentioned delay, theinstantaneous value of differentialcurrent falls below the threshold andremains below for longer than afurther preset time, ( s) as it wouldduring transformer magnetisinginrush conditions, the trip timer isreset and operation of the relayblocked.
An unrestrained high-set circuit,which monitors the differentialcurrent, will override the amplitudecomparator circuit and operate therelay output element when thedifference current is above the high-set setting.
Variable percentage biasrestraint
Even under normal operatingconditions, unbalanced currents(spill current), may appear. Themagnitude of the spill currentdepends largely on the effect of tapchanging. During through faults thelevel of spill current will rise as afunction of the fault current level. Inorder to avoid unwanted operationdue to spill current and yet maintainhigh sensitivity for internal faults,when the difference current may berelatively small, the variablepercentage bias restraintcharacteristic shown in Figure 11 isused. The setting Is is defined as theminimum current, fed into one of thebias inputs and the differentialcircuit, to cause operation. This isadjustable between 10% and 50%of rated current.
The initial bias slope is 20% fromzero to rated current. This ensuressensitivity to faults whilst allowing a15% current transformer ratiomismatch when the power
1 4f
1 f
4
transformer is at the limit of its taprange, plus 5% for CT ratio error.Above rated current, extra errorsmay be gradually introduced as aresult of CT saturation. The biasslope is therefore, increased to 80%to compensate for this.
At the inception of a through faultthe bias is increased to more than100%. It then falls exponentially tothe steady state characteristic shownin Figure 11. This transient biasmatches the transient differentialcurrents that result from CTsaturation during through faults, soensuring stability.
However, during internal faults thistransient bias is suppressed toensure that no additional delay inoperation is caused.
The transient bias circuits of thethree phases are externallyinterconnected to ensure optimumstability of the protection duringthrough faults.
Magnetising inrush restraint
Particularly high inrush currents mayoccur on transformer energisationdepending on the point on wave ofswitching as well as on themagnetic state of the transformercore.
Since the inrush current flows only inthe energised winding the protectionrelay sees this current as differencecurrent. To avoid unwanted trippingof the power transformer it has beencustomary to incorporate secondharmonic restraint to block theprotection relay. Practice has shownthat this technique may result insignificantly slower operating timesfor internal faults when secondharmonics are introduced into thecurrent waveform by core saturationof line CTs.
In order to overcome the problemsassociated with second harmonic
restraint a new technique has beendeveloped to recognise magnetisinginrush current and restrain the relayduring such periods.
In practice the magnetising inrushcurrent waveform is characterisedby a period during each cycle whenlittle or no current flows, as shown inFigure 12. By measuring thischaracteristic zero period, the relayis able to determine whether thedifference current is due tomagnetising inrush current or togenuine fault current and therebyinhibit operation only during theinrush condition. This newmeasurement technique ensures thatoperating times remain unaffectedeven during periods of significantline CT saturation.
Transformer over-excitation
When a large section of systemload is suddenly disconnected froma power transformer the voltage atthe input terminals of the transformermay rise by 10-20% of rated valuegiving rise to an appreciableincrease in transformer steady stateexciting current. The resultingexciting current may rise to a valuehigh enough to operate thedifferential protection relay, sincethis current is seen by the input linecurrent transformers only. Excitingcurrents of this order are due to theinput voltage exceeding the kneepoint voltage of the powertransformer resulting in amagnetising current wave shape asshown in Figure 13. By detectingthe periods when the currentremains close to or at zero, in asimilar manner to that used toidentify magnetising inrush current,the relay is able to detect andremain insensitive to substantialover-excitation current.
Where extremely large andpotentially damaging over-exciting
currents are possible it isrecommended that an over-fluxingrelay, responsive to V/Hz, shouldbe used. Such relays are designedto operate after a time delay ofseveral seconds
High-set
An unrestrained instantaneous high-set feature is incorporated toprovide extremely fast clearance ofheavy internal faults. Thisinstantaneous feature has an auto-ranging setting, normally low atnormal load through-put, butautomatically rising to a highervalue under heavy through faultconditions. Furthermore, immunityto magnetising current inrush isguaranteed provided the first peakof the waveform is no greater than12 times the rated rms current. Theproblem relating to choice of ahigh-set threshold which avoidstripping on magnetising currentinrush does not, therefore, occurand no user adjustment is required.
Auxiliary interposingtransformer
Auxiliary interposing transformersare available as single or triple unitassemblies as illustrated in Figure15.
A comprehensive tap adjustmentrange is available as indicated bythe details of turns per tap shown inTable 2. All line CT connectionsshould be made to the terminal stripmarked ‘S1 S2 S3 S4 P1 P2’.
Selection of appropriate primarytaps is made using the flexiblejumper leads connected to terminalsP1 and P2. See Figure 16. Thetertiary winding S3-S4 must beused in series with winding S1-S2where a delta output winding isrequired to ensure correct operationof the differential scheme.
5
A
B
C
DY1A
B
C
23 25 27
24 26 28MBCH 12 12
23 25 27
24 26 28MBCH 12 12
23 25 27
24 26 28
12
MBCH 12
Restricted E/Frelay
DY1A
B
C
23 25 27
24 26 28
MBCH 12 12Phase 'A'Relay
23 25 27
24 26 28
MBCH 12 12Phase 'B'Relay
23 25 27
24 26 28 MBCH 12
12Phase 'C'Relay
Figure 3:Typical connection diagram for MBCH 12 relays protecting a DY 1 transformerwith integral restricted earth fault relay
Figure 2:Application diagram: relay type MBCH 12 with two biased inputs
6
A
23 25 27
24 26 28
23 25 27
24 26 28
23 25 27
24 26 28
B
C
Figure 4:Typical connection diagram for MBCH relays protecting a YD 11 transformeron a phase by phase basis
Figure 5:Typical connection diagram for MBCH 12 relays protecting a series reactor
A
B
C
23 25 27
24 26 28
23 25 27
24 26 28
23 25 27
24 26 2812
12
12
7
A
B
C
21 23 25 27
12
22 24 26 28
MBCH 13
21 23 25 27
12
22 24 26 28
MBCH 13
21 23 25 27 12
22 24 26 28
MBCH 13
Y(d)YO
A
B
C
Y(d1) YO
RestrictedE/F relay
21 23 25 27
22 24 26 2812
MBCH 13
21 23 25 27
22 24 26 28 12
MBCH 13
21 23 25 27
22 24 26 28
12
MBCH 13
Figure 7:Typical connection diagram for MBCH 13 relays protecting a Y(d) YO transformer supplied from a ‘mesh’ busbar
Figure 6:Typical connection diagram for MBCH 13 relays protecting a Y(d) YO transformer with integral restricted earth fault relay
8
Figure 8:Typical connection diagram for MBCH 13 relays protecting a generator/transformer unit
Figure 9:Connection for six change-over tripping contacts for three phase tripping ofup to six circuit breakers showing correct connection of the screened lead ona three phase scheme
1
3
5
2
4
6
1
3
5
2
4
6
1
3
5
2
4
6
All output contacts shown areinstantaneously initiated for anyinternal fault condition when terminals No. 10 on each phaseunit are connected togetheras shown.
Correct phase indication is maintained.
Phase 'B'
Phase 'C'
Phase 'A'
14
13
12
10
14
13
12
10
13
14
12
10
+
–
Vx
N.E.R.
Generator
UnitTransformer
22
21 23 25 27
24 26 28
12MBCH 13
21 23 25 27
24 26 28
12MBCH 13
22
21 23 25 27
24 26 28 12MBCH 1322
9
Figure 10:Block diagram: Biased differential protection relay type MBCH 13 with three biased inputs
3
2
1
0 1 2 3 4
Operate
80% Slope
Restrain
20% SlopeAllowable
20% ratio error
Effective bias (xIn) = I1 +I2 +I3 +I4 +I5 +I6
2
Differential current (xIn)
= I1 +I2 +I3 +I4 +I5 +I6
Settingrange(0.1-0.5)
A
B
C
Figure 11:Typical percentage biascharacteristic
Figure 12:Typical magnetisinginrush waveforms
Case earth
13579
111315
17
2468
10121416
18
19
21
23
20
22
24
25 26
27 28
Module terminalblock viewed
from rear
Note 1:
(a) C.T. shorting links makebefore (b) & (c) disconnect
(b) short terminals break before (c)
Note 2:Terminal 12 on each phase assembly should beinterconnected by a screened lead GJO153 001with the screen connected to terminal 14.
21
2223
T5I3
I2
2425
T4
T326
I1
Inputcircuits
IDIFF
T2
T1
27
28
Outputcircuits
RL12
Operate
Reset
RL21
1
35246
RL1-1
RL1-2Trip output
10
13
14
12
Trip other phase
+
–Vx
9
11RL2-1 Alarm
Biassee note 2
Protectivesafetyearth
10
0Figure 13:Magnetising current withtransformer overfluxed
Figure 14:Typical operating timecharacteristic
3
2
1
00.1 0.2 0.5 1 2 5 10 20 50 100
Ope
ratin
g tim
e (c
ycle
s)
Fault current (xIn)
Setting range
Figure 16:Winding arrangement ofsingle pole of auxiliaryinterposing transformer
Figure 15:Outline details of single and triple unit auxiliary interposing transformer assembly
1 2 3 4 5 6 X 7 8 9 1 2 3 4 5 6 X 7 8 9 1 2 3 4 5 6 X 7 8 9Primary taps
M4 terminal screws
119 (1Ø)83.5 (1Ø)
4 off M5clearanceholes
145310 (3Ø)
343 (3Ø)
Earth
S1 S2 S3 S4 P1 P2 S1 S2 S3 S4 P1 P2 S1 S2 S3 S4 P1 P2
117145
11,5
1 2 3 4
Outputto relay
5 6 X 7 8 9Flexiblejumperleads
Input fromline CT's
P2P1S4S3S2S1
11
Technical Data
RatingsAC Current (In) 1A or 5AFrequency 50Hz or 60Hz
Auxiliary dc supply (Vx) Voltage Rating Operating(Vdc) range (Vdc)30 - 34 24 - 4148 - 54 37.5 - 65110 - 125 87.5 - 150220 - 250 175 - 300
Minimum basic settingBiased feature 10%, 20%, 30%, 40%, 50% In
High-set feature 4In up to through bias currents of 9In,thereafter increasing gradually to 8In
at through bias currents of 14In
High-set operation Immunity to magnetising currentinrush is guaranteed provided the firstpeak of the waveform is no greaterthan 12 times the rated rms current.
Accuracy ±10%
Operating characteristic Dual slope, 20% up to In,80% above In.
Operating time Typically 10ms to 25ms
Number of current inputs MBCH 12 - 2 biased inputsMBCH 13 - 3 biased inputsMBCH 16 - 6 biased inputs
AC thermal ratingContinuous MBCH 13,16: 4In
MBCH 12: 2In
Short time, all versions 100In for 1s with amaximum of 400A
DC burdenWith output H/A not picked up
DC voltage Burden at upperrating (V) voltage rating (W)30 - 34 Approx 348 - 54 Approx 3110 - 125 Approx 4220 - 250 Approx 8
With output H/A picked upDC voltage Burden at upperrating (V) voltage rating (W)30 - 34 Approx 448 - 54 Approx 4110 - 125 Approx 7220 - 250 Approx 12
AC burdenThrough current only(per bias circuit) Approx 0.15VA (In = 1A)Ithro - 1 x In Approx 0.30VA (In = 5A)Bias and differential circuit only Approx 2.80VA (In = 1A)Idiff = 1 x In Approx 3.20VA (In = 5A)
12
Contacts Two change-over self-reset trippingcontacts per relay. (For 3 phaseschemes relays can be interconnectedas shown in Figure 9 to provideinstantaneous operation of all threesets of change-over tripping contacts.)
One normally open latching contactper relay.
Make and carry: 7500VA for 0.2swith maxima of 30A and 300V ac or dc.Carry continuously: 5A ac or dcBreak: 1250VA ac or 50W dc resistive,25W, L/R = 0.04s.Subject to maxima of 5A and 300V.
Durability
Loaded contact 10,000 operations minimumUnloaded contact 100,000 operations minimum
Operation indicator Light emitting diode (red), hand reset
Line current transformer requirementsApplication Knee Point Voltage Vk Through Fault Stability
Note: Values to be as givenbelow, with minima of 60 Infor star-connected CTs and100 for delta connected CTs
In X/R If
Transformers Vk / NM 24 In [Rct+2Rl+Rt] 40 15In
GeneratorsGeneratortransformers Vk / 24In [Rct+2Rl+Rt] 40 15InOverall generator-transformer/units Vk / 48In [Rct+2Rl+Rt] 120 15InMotorsShunt reactorsSeries Reactorsalso Transformersconnected to aMesh Corner Vk / 24In [Rct+2Rl+Rt] 40 15Inhaving two sets ofCT’s eachsupplying separate 40 40Inrelay inputs Vk / 48In [Rct+2Rl+Rt]Note: CT’s should 120 15Inbe of equal ratioand magnetisationcharacteristic
Where:
In = Rated line CT secondary current (1A or 5A).Rct = Resistance of line CT secondary winding.Rl = Resistance of a single lead from line CT to relay.Rt = Effective resistance of interposing CT where used.X/R = Maximum value of primary system reactance/resistance ratio.Ιf = Maximum value of through fault current.Table 1: Current Transformer requirements.
13
Auxiliary interposing transformersNominal secondary current rating, In 1A or 5ANominal current ratios selectable in 0.58 - 1.73/14% In steps see Table 1 2.89 - 8.66/1
2.89 - 8.66/5Note: Higher primary currents can be catered for. Refer to publication
R-6077
Rated frequency 50/60Hz
Thermal withstand 4 x In continuous30 x In for 10s100 x In for 1s with 400A maximum
Effective resistance Rt 2.0Ω for 0.58 - 1.73/1ratio0.2Ω for 2.89 - 8.66/5 ratio0.15Ω for 2.89 - 8.66/1ratio
Insulation test voltage 2kV rms 1 minute, 50Hz
Maximum terminal block wire size 84 strand, 0.3mm Ø
Dimensions Outline drawings for single and triplegroup shown in Figure 15
Weight 4kg single unit12kg triple unitNumber of turns
Primary top Transformer ratingterminals 1/1A 5/1A 5/5A
1 – 2 5 1 12 – 3 5 1 13 – 4 5 1 14 – 5 5 1 15 – 6 125 25 25X – 7 25 5 57 – 8 25 5 58 – 9 25 5 5S1 – S2 125 125 25S3 – S4 90 90 18
Table 2: Interposing CTs: number of turns per tap.
High Voltage withstandDielectric withstandIEC 60255-5: 1977 2kV rms for 1 minute between all
terminals and case earth.
2kV rms for 1 minute between allterminals of independent circuits, withterminals on each independent circuitconnected together.
1 kV rms for 1 minute across normallyopen contacts.
High voltage impulseIEC 60255-5: 1977 Three positive and three negative
impulses of 5kV peak, 1.2/50µs, 0.5Jbetween all terminals of the samecircuit (except output contacts),between independent circuits, andbetween all terminals connectedtogether and case earth.
14
Electrical environmentDC supply interruptionIEC 60255-11: 1979 The unit will withstand a 10ms
interruption in the auxiliary supply,under normal operating conditions,without de-energising.
AC ripple on DC supply The unit will withstand 12% ac rippleIEC 60255-11: 1979 on the dc supply
High frequency disturbanceIEC 60255-22-1: 1988 Class III 2.5kV peak between independent
circuits and case.
1.0kV peak across terminals of thesame circuit.
Fast transient disturbanceIEC 60255-22-4: 1992 Class IV 4.0kV, 2.5kHz applied directly to
auxiliary supply.
4.0kV, 2.5kHz applied directly to allinputs.
Surge immunityIEC 61000-4-5: 1995 Level 3 2.0kV peak, 1.2/50µs between all
groups and case earth.
2.0kV peak, 1.2/50µs betweenterminals of each group.
EMC compliance89\336\EEC Compliance with the European
Commission Directive on EMC isclaimed via the Technical ConstructionFile route.
EN5008-2: 1994 Generic Standards were used toEN5008-2: 1995 establish conformity.
Product safety73/23/EEC Compliance with the European
Commission Low Voltage Directive.
EN 61010-1: 1993/A2: 1995 Compliance is demonstrated byEN 60950: 1992 All: 1997 reference to generic safety standards.
Atmospheric environmentTemperatureIEC 60255-6: 1988 Storage and transit -25°C to + 70°C
Operating -25°C to +55°CIEC 60068-2-1: 1990 ColdIEC 60068-2-2: 1974 Dry heat
HumidityIEC 60068-2-3 56 days at 93% RH and 40°C
Enclosure protectionIEC 60529: 1989 IP50 (dust protected)
Mechanical environmentVibrationIEC 60255-21-1: 1988 Response Class 1
SeismicIEC 60255-21-3: 1993 Class 2
15
CasesRelays type MBCH are housed insize 4 cases as shown in Figure 17.
Figure 17:Case outline size 4
Information required with orderNote: 3 single-phase MBCH relays are required for a 3-phase scheme. Pleasestate total number of single-phase relays required.
Rated current In
Rated frequency
Auxiliary dc supply voltage Vx
Number of current bias inputs:
MBCH 12: 2 inputMBCH 13: 3 inputMBCH 16: 6 input
Auxiliary interposing transformerRated current In
Current ratio
Mounting: single or triple unit
Associated PublicationsInterposing matching CTs for use with MBCH relays R6077
MIDOS system R6001
MMLG/MMLB test block/test plug R6004
97
Push buttonprojection 10 max.
4 holes Ø4.452
23.5
159
25 min.
11
157 max.
Flush mountingAll dimensions in mm
Reset
21232
177
77
168
99Panel cut-out:Flush mounting fixing details
St Leonards Works, Stafford, ST17 4LX EnglandTel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: [email protected] Internet: www.alstom.com
©1998 ALSTOM T&D Protection & Control Ltd
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure shouldonly be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.
Publication R-6070L 060010 Printed in England.
ALSTOM T&D Protection & Control Ltd