International WebEvent on Ductwork Airtightness, 2009-12-16
1
Duct System Leakage TestingMethods, requirements, handing over
Dr. Peter G. Schild
SINTEF Building & Infrastructure
![Page 2: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/2.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
2
Topics
Testing equipmentStandardsTesting procedures – on-site and in laboratoryPractical aspects of on-site testing
![Page 3: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/3.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
3
Measurement apparatus
Manometer(measures leakage flow rate)Manometer
(measures leakage pressure)
Fan(reversible)
Calibrated orifice
Airtight flexible tube
Tested ductwork
— 600 Pa–— 400 Pa–— 200 Pa–— 0 Pa
–20 ℓ/s —
–10 ℓ/s —
–0 ℓ/s —
Speed control
> 2 m
![Page 4: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/4.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
4
Measurement instrumentsAmerican models Scandinavian models
Large leakage flow ratesLarge flexible hoses
Smaller leakage ratesSmaller hoses (50-100 mm)
![Page 5: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/5.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
5
Bladders
![Page 6: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/6.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
6
Leakage localization – smoke tests
![Page 7: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/7.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
7
Swedish VVS AMA 98
Contractual aspects of VVS AMA:Specification guidelines. Voluntarily referenced in building contracts.
Leakage tests (ducts & AHU) must be done by the HVAC contractor as part of the contract. AMA requires the contractor to include the cost of testing in their contract price. Tests can be subcontracted to specialists
The owner’s consultant, is normally also present during the test.
The parts to be measured are chosen by the owner’s consultant.
![Page 8: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/8.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
8
Swedish VVS AMA 98
Test method for leakage testing:Similar to EN 12237 (round) & EN 1507 (rectangular). Separate test of air handling unitA one-pressure measurement, normally at 400 Pa.Minimum duct surface area to be tested:
10 % of total area for round ducts, 20% for rectangular duct systems>10 m² duct surface. (Area is defined as external surface area)Select multiple random test locations, each approx. 25 m²
If the leakage exceeds requirement, repair and repeat on another 10%/20%.If this 2nd test also exceeds requirement, repair and test whole system
![Page 9: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/9.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
9
European StandardsLeakage classification:
EN 1507:2006. Ventilation for buildings - Sheet metal air ducts with rectangular section - Requirements for strength and leakageEN 12237:2003. Ventilation for buildings - Ductwork - Strength and leakage of circular sheet metal ductsEN 1886:2007. Ventilation for buildings - Air handling units - Mechanical performanceEN 1751:1998. Ventilation for buildings - Air terminal devices - Aerodynamic testing of dampers and valves
Leakage requirements, Measurement method, Handing over:EN 13779:2007. Ventilation for non-residential buildings - Performance requirements for ventilation and room-conditioning systemsEN 14239:2004. Ventilation for buildings - Ductwork - Measurement of ductwork surface areaEN 12599:2000. Ventilation for buildings - Test procedures and measuring methods for handing over installed ventilation and air conditioning systems(Corrigendum AC:2002 incorporated)
![Page 10: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/10.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
10
Illustration of VVS AMA Commissioning
Source: AIRWAYS Souce Book
![Page 11: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/11.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
11
European StandardsLeakage classification:
EN 1507:2006. Ventilation for buildings - Sheet metal air ducts with rectangular section - Requirements for strength and leakageEN 12237:2003. Ventilation for buildings - Ductwork - Strength and leakage of circular sheet metal ductsEN 1886:2007. Ventilation for buildings - Air handling units - Mechanical performanceEN 1751:1998. Ventilation for buildings - Air terminal devices - Aerodynamic testing of dampers and valves
Leakage requirements, Measurement method, Handing over:EN 13779:2007. Ventilation for non-residential buildings - Performance requirements for ventilation and room-conditioning systemsEN 14239:2004. Ventilation for buildings - Ductwork - Measurement of ductwork surface areaEN 12599:2000. Ventilation for buildings - Test procedures and measuring methods for handing over installed ventilation and air conditioning systems(Corrigendum AC:2002 incorporated)
![Page 12: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/12.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
12
EN 14239: Area calculation
All length measurements are along centre-linesAll components are thus included in area, e.g. dampers (A), reductions (B), bends (C).Area of reductions (B) are based on largest diameterLength of branch ducts is measured from centre-line of main duct (D)Openings (e.g. branches) shall not be deductedInclude area of end plates
Example of round duct system
Diameter [mm] Length [m] Area, π·D·L [m²]
800 6.5 + 5.2 = 11.7 π×0.8×11.7 = 29.4
600 3 π×0.63×3 = 29.4
400 4.2 + 3.3 = 7.5 π×0.4×7.5 = 29.4
SUM 44.8
![Page 13: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/13.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
13
What the CEN standards sayIn-situ measurements on building site:
at least 10% of total duct system area, and >10 m². Variety of fittingsRatio between joint length and duct area typically: 1 < L/A < 1.5 [m-1]One test pressure: pdesign < ptest < ps,limit, steady for 5 mins, preferably 200, 400 or 1000 Pa.If the leakage exceeds requirement, repair and repeat on another 10%.If this 2nd test also exceeds requirement, repair and test whole system
(for testing of round ducts)
0.001
0.01
0.1
1
10
10 100 1000Duct test pressure, Pa
Air
leak
age,
(
ABCD
![Page 14: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/14.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
14
EN 12237 & EN 1507: Testing of duct (contd.)
Laboratory measurements of duct products:
>10 m², representative variety of duct dimensions and fittings.
Ratio between joint length (L) and duct area (A): L/A > 1 [m-1]
>5 positive & negative pressures: ptest < ps,limit , each for 5 minutes
![Page 15: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/15.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
15
Ratio between joint length (L) and duct area (A)Example system below: L/A = 57 / 34.9 = 1.63 m²
Butt joints
![Page 16: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/16.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
16
On-site measurements
Time & cost for large building: 1 day for 2 persons
Sensible to test as early as possible during construction, before commissioning.
In large buildings, typically many parts of the duct system are tested separately, e.g. a selection of floors
![Page 17: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/17.jpg)
Measurement protocols – See VVS AMA
![Page 18: ASIEPI WP5 WebEvent2 04 TestingMethods](https://reader034.vdocuments.net/reader034/viewer/2022042905/577cc1111a28aba711922812/html5/thumbnails/18.jpg)
International WebEvent on Ductwork Airtightness, 2009-12-16
18
Disclaimer
The ASIEPI project (www.asiepi.eu) has received funding from the Community’s Intelligent Energy Europe programme under the contract EIE/07/169/SI2.466278.
The sole responsibility for the content of this publication lies with the authors. It does not necessarily reflect the opinion of the European Communities. Neither the European Commission nor the authors are responsible for any use that may be made of the information contained therein.
SINTEF’s contribution to the ASIEPI project is funded in part by ENOVA contract SID 06/644