INSTALLATION MANUAL
E-II-YDS-C-0907
DIGITAL SCROLL CENTRAL AIR CONDITIONER (OUTDOOR UNIT) YDS SYSTEM R410A
For correct installation, read this manual before starting installation.Only trained and qualified service personnel should install, repair or service air conditioning equipment. Users
should not install the air conditioner by themselves. All pictures are only sketches. If there is any difference between pictures in this manual and the actual shapeof the air conditioner you purchased, the actual shape shall prevail.
YDMH-252C35B
YDMH-280C35B
YDMH-335C35B
YDMH-400C35B
YDMH-450C35B
Model:
-
7/27/2019 Inst Manual Outdoor252 450C
2/12
INSTALLATION LOCATION
Outdoor unit installation manual
OutlineName
1
2
FunctionQty.
90 elbow
Hole site for fork lift Chassis
1
1
1
1
1
2
PRECAUTIONS
1. This installation manual is for the outdoor unit.2. Refer to the indoor unit installation manual for indoor parts
installation.3. Please read the power source unit installation manual to
install the power source unit .4. Please refer to the refrigerant distributor installation
manual to install the refrigerant distributor.
KEY POINTS IN INSTALLATION
INSTALLATION
Confirm the model and name of your air conditioner to avoid installation mistakes.
REFRIGERANT PIPING
Separately purchased refrigerant distributor (branch joint, branch header pipe) should be used in the processof refrigerant piping.
Charge nitrogen under certain pressure in the refrigerantpiping before welding.Heat insulation should be done to refrigerant piping.
After the installing refrigerant piping, do not electrify theindoor unit before the airtight test and vacuum.
Refrigerant piping should accord with specifieddiameter.
AIRTIGHT TEST
Refrigerant piping must be tested for gas proof 2[3.8MPa(40kgf/cm ) nitrogen.]
VACUUM
Vacuum pump must be used, and vacuuming shouldbe done from the gas side and liquid side
simultaneously.ADD REFRIGERANT
When the actual pipe is longer than the fiducial length,the added refrigerant volume of every outdoor unitdepends on the calculating according to the actual length.Fill the form on the outdoor unit electric control box withthe added volume, length of pipes (actual length) and therelative height drop between outdoor unit and indoor unit.
WIRING
Choose power capacity and wire diameter according tothe design manual. The power cord of the air conditioner
should be wider than the power cord of ordinary motor.
Connect the indoor unit to the power after airtight testand vacuuming.
Do not twist or cross the power cord (380V 3N~)withwiring (low voltage) between indoor and outdoor unit, or mishandling may occur.
Set the address of outdoor unit, see Address dialof outdoor unit
TEST RUNNING
The test running can not begin until the outdoor unit hasbeen connected to the power for 12hr.
Remove six sponges at the back of unit. Please handlewith care to avoid damage to fin, which will decreaseheat exchanging efficiency.
1. Please keep away from the following place, or malfunction of the machine may be caused:
2. The insulation of the metal parts of the building and theair conditioner should comply with the regulation of National Electric Standard.
CAUTION
There is combustible gas leakage.There is much oil (including engine oil) ingredient.
There is salty air surrounding(near the coast)There is caustic gas (the sulfide) existing in the air (near a hotspring).
A place the heat air expelled out from the outdoor unitcan reach your neighbor's window.
A place that the noise interferes your neighbors everyday life.
A place that is too weak to bear the weight of the unit.Uneven place.Insufficient ventilation place.Near a private power station or high frequency equipment.
A place with strong electromagnetic interference.
ACCESSORIES (Outdoor unit)
Outdoor unit owner s manual
Indoor unit owner s manual
Service manual(guaranteeand bar code inside)
Screw bag
Straight screwdriver
(Given to users)
(Given to users)
(Given to users)
This manual
Spare
Dialling
For airtight test
Pipe connecting
Gauge joint
CARRY IN THE OUTDOOR UNIT
Sling the outdoor unit and carry it in with 4 steel wire( 6mm or more)Use soft board to protect the unit surface from scratchand distortion where contact the steel wire.Remove the transportation board after carrying in theoutdoor unit.
1. Carry in with steel wire:
2. Carry in with a fork lift
Protection board
Steel wire
-
7/27/2019 Inst Manual Outdoor252 450C
3/12
Mode Qty. of indoor unit
(Air-in )
(Air-out )
Outdoor unit planform
Installation and maintenance surface
1000mm
1000mm 100mm~ 500mm 1000mm
1000mm
2. When there is obstacle above the outdoor unit:
A
B
C
D
45
1000mm
Airflow deflecto r
Front view
B
A
B
A
C
D
Side view
B
A
100mm~ 500mm
INSTALLATION SPACE
1. Leave enough space for maintenance (see followingpicture) and install power unit on the side of outdoor unit. Refer to power unit installation manual.
2. Keep the modules in one system at the same level.
(Air-in )
300mm
Front view Front view
NOTE: The top of any pile around the outdoor unit should at least 800 mmbelow the top of unit. If not, plea se install mechanical air discharge equipment.
REFRIGERANT PIPE
1. Refrigerant piping connection is inside the outdoor unit, please remove the front clapboard.
2. The piping can be led through the down-left of theoutdoor unit or the soleplate gap.
3. When through the front, piping is led by wiring fromthe panel, then connect branch pipes towards leftor right.
4. When through the soleplate gap, install the branchpipe towards left, right or back.
5. If through the front, please remove the clapboardat corresponding place first.
To prevent the inside of piping from oxidizingwhen welding, it is necessary to charge nitrogen,or oxide may block the circulation.
CAUTION
OUTDOOR UNIT COMBINATION
Mode Qty. of indoor unit
To gas balance pipe
To gas side pipe
Low-pressureball valve
NOTE: No connectionwith gas and oil balancepipes for single module.
1
2
3
Refer to Number 1 in picture below
Pipe between outdoor unit and the firstbranch (Main pipe)
Size of main pipe connecting multi-modulesNumber 2 in picture below
Pipe between branchesNumber 3 in picture below
PIPE SIZE AND CONNECTION
1 23
2 2 2 2 23 3 3 3 3 3 3
1
33 3 3
1 2 2 2 2
3 3 3 33 3
1
2
3
33
Outdoor unit
Outdoor unit
Outdoor unit
Single module
Gas pipe
Liquid pipe
NOTE: Pipe size of model 8HP, 10HP and 12HP:liquid side 12.7, gas side 25.4.Pipe size of model 14HP and 16HP:liquid side 15.88, gas side 35.0.
No connection with gas balance pipes for single module.
To liquid side pipe
To gasbalance pipe(Flaring nut)
(Flaring nut)
(Flaring nut)
-
7/27/2019 Inst Manual Outdoor252 450C
4/12
Gas balance pipe 1, 15.9Gas balance pipe 2, 19.0
C onnection of gas b alance pipes
C onnection of g as balance pipes
capacity
capacity
Four modulescapacity
Liquid pipe 25
Gas p ipe 54 Th ree modulescapa city
Two modules
YDMH-252C35BYDMH-280C35BYDMH-335C35BYDMH-400C35BYDMH-450C35B
YDSA/RD101YDSA/RD101YDSA/RD101YDSA/RD102YDSA/RD102
YDSA/RD102
YDSA/RD102YDSA/RD01
YDSA/RD103
YDSA/RD103YDSA/RD104YDSA/RD104
NOTE: Wrap the valveswith wet cloth when welding,or the valves may bedamaged to cause leakage.
C onnection of g as balance pipes
S ee following chart for size o f T-shaped pipes Zconnecting with ga s pipe.
3- 19.0
(Table2) Pipe size andconnection of single modult andBranch joint
Main pipe(gas sid e/liquid side)
(Table3) Size of Multi-T aiwan pipe and branch pipe
Branch joint
Note: the distance between a outdoor unit and the otherwhich is farthest from it is less than 90 meters.The mainpipe may be the smaller level.
Branch joint Liquid side Y Three Contacts A:
I n s
i d e
d i a m e t e r
I n s
i d e
d i a m e t e r
I n s
i d e
d i a m e t e r
I n s i
d e
d i a m e t e r
I n s i
d e
d i a m e t e r
Gas side Y Three Contacts B:
I n s
i d e
d i a m e t e r
I n s
i d e
d i a m e t e r
I n s
i d e
d i a m e t e r
I n s i
d e
d i a m e t e r
I n s i
d e
d i a m e t e r
Gas s ide Y type three Contacts above :Gas/liquid side
Gas/liquid side
Z
18
32
32
Y
Gas balanc e pipe 1, 15.9Gas balance pipe 2, 19.0
-
7/27/2019 Inst Manual Outdoor252 450C
5/12
1 2
10
3 4 5 6 7
11 12 13 14 15 16 1817
L N
a b8 9c d e f g h i j
12HP 16HP16HP
#1( 5P ) ( 5P ) ( 5P ) ( 5P ) (5P ) (5P )
#2 #3 #4 #5 #6 #7(5P ) (5P ) (4P )
#8 #9
M
150m
175m
40 m
70 m
40 m
15 m
L1+L2+L3+L4+L5+L6
L1+L3+L4+L5+L6+i
L3+L4+L5+L6+i
+a+b+c+d+e+f+g+h+i30HP 3 5 0 m
5 0 0 m30HP
Table 4Size of main pipe
A: Cap aci ty of all the indoo r uni ts. A(horsepower) A 1212 A 1616 A 2828 A 3434 A 4848 A 64
22.0 / 9.53
Take (16+16+12)HP outdoor unit as example:
parallel outdoor unit:
1. Branch pipes: NoL,M,N the size is 25.0/ 12.7 / 15.9 35.0/According to the cor respondin g outdoor units ability.
2..1# pipe , total HP is 16+12=28HP pipe size is 0/
3.model of branch joint: a ,type YDSA/RD101 ,b choose YDSA/RD01.Room inside:
1). Branch pipes are 10--18,refer to table 5,the size is: 15.9/ 9.532). Subordinate indoor units of pipe 9 are 8#, 9#, total HP is 5+4=9P 12P
, pipe 9# size is 22.0/ , model of branch joint j :YDSA/RD101
3). Subordinate indoor units of pipe 8 are 7#,8#,9#, totel HP is 5+5+4=14P
16P,pipe size is / 12.7, model of branch joint I : YDSA/RD102
4).Subordinate indoor units of pipe 7 are 6#~9#, totel HP is 5+5+5+4=19P
28P,pipe size is 35.0/ , model of branch joint h : YDSA/RD102
5).Subordinate indoor units of pipe 6 are 5#~9#, totel HP is5+5+5+5+4=24P 28P
pipe size is 35.0/ , model of branch joint g ::YDSA/RD102
6).Subordinate indoor units of pipe 5 are 4#~9#, totel HP is5+5+5+5+5+4=29P
34P,pipe5 size is .0/ , model of branch joint f ::YDSA/RD102
7).Subordinate indoor units of pipe 4are 3#~9#, totel HP is5+5+5+5+5+5+4=34P
34P,pipe4size is .0/ , model of branch joint e :: YDSA/RD102
8).Subordinate indoor units of pipe 3are 2#~9#, totel HP is5+5+5+5+5+5+5+4=39P
48P,pipe3size is .0/ , model of branch joint d :: YDSA/RD103
9).Pipe2 is the main pipe,the size of pipe2 and branchc refer to the outdoor unit.
pipe3size is .0/ model of branch j oint c ::YDSA/RD103
9.5312.7
0.060kg0.110kg
19.022.0
0.250kg0.350kg
25.0 0.520kg
15.9 0.170kg
28.6 0.680kg
Main pipe(gas side/liquid side) Branch joint
Note: the first branch pipe is according to the total ability of theoutdoor unit, the others could not larger than it.
Length and Drop Height Permitted of the R efrigerant piping
Permitted value
Total Pipe Length (Actual)
Max Piping (L)
Indoor Unit to Indoor Unit Drop Height(h)
Indoor-Outdoor UnitDrop Height(H)
Piping (farthestfrom the first linepipebranch) Equivalent Length (l)
Actual LengthEquivalent Length
Outdoor Unit UpOutdoor Unit Down
P i p e
L e n g
t h
D r o p
H e
i g h t
Piping
Make sure there is no any dirt or water beforeconnecting the piping to the outdoor units.Wash thepipingwith high pressure nitrogen,neveruserefrigerant of theoutdoor unit.
Remove Dirt or Water in the Piping
Airtight Test1. C onnect piping on h i-pressur e sid e with hi-pressur e
va lve. (For multi-modules pa rallel connection, pleaseco nnect gas and oil balance v alves.)
2. W eld the piping on l ow-press ure s ide with gauge joint.3. C harge nitrogen from hi-pressur e va lve c ore a nd gaugejo int.
4. After airtight test, weld low-pressur e ba ll valve a ndpiping on low--pressur e side.
CAUTION21.Pres sured n i trogen [3.8MP a (40kg /cm ) shou ldbeu sed in the
air tigh t test.
3. The air tight test should never use any ox ygen, f lammablegasor po isonous gas.
2. Do not c onnect piping on low-pressure s ide and low -pressure ballvalve be fore charg ing nitrogen.
4. W rap low-press ure valve and balance valves w ithwet cloth while welding.
Do vacuum with vacuum pump instead of refrigerant.
Vacuum with vacuum pump
Vacuuming should be done from liquid and gas sidesimultaneously. The pressure should be lower than30Pa.
Open all valves
Refrigerant Amount to be AddedCalcu late the added ref rigerant according to the diameterand the length of the liquid sidep ipe oftheou tdoor/indoorunit connection. T he refrigerant is .R410A
Pipe siz e on liquid s ide Re frigerant to be Added per meter6.35 0.022kg
Table5size and connection of branch pipes
Note:Y type branch joint a,b must be the level laying ,otherwise can causethe cold intermediary assignment to be uneven!And multi-Taiwan paralleloutdoor unit must be in the identical altitude.
Gas balance valve
Hi-pressure valve
Gauge joint
Indoor unit and branch joint
Low-pressure valve
Outdoor Unit (one or more outdoor units)
D
r o p H e i g h t b e t w e e n I n d o o r
u n i t a n d o u t d o o r U n i t H
7 0 m
First branch
Indoor Unit
Max Piping EquivalentLength L 125m7
(From the first branch)Max piping EquivalentLength l 40m
Indoor Unit
I n d o
o r
U n
i t t o I n d
o o r
U n
i t
D r o p
H e
i g h t
Gas balance valve
YDSA/RD101YDSA/RD101YDSA/RD102YDSA/RD102YDSA/RD103YDSA/RD103
28 ~ 45 (4-way cassette)
56 ~ 112 (4-way cassette)
22 ~ 36 (duct type) / ceiling de floor
45 ~ 71 (duct type)
22 ~ 56 (wall mounted)
12,7 (Flaring nut)
16,0 (Flaring nut)
12,7 (Flaring nut)
16,0 (Flaring nut)
12,7 (Flaring nut)
6,35 (Flaring nut)
9,53 (Flaring nut)
6,35 (Flaring nut)
9,53 (Flaring nut)
6,35 (Flaring nut)
R410A
/ ceiling de floor
28.6 / 12.7 35.0 / 15.9 38.0 / 19.0 42.0 / 22.0 45.0 / 22.0
-
7/27/2019 Inst Manual Outdoor252 450C
6/12
QUERY DESCRIPTION
Address dial of outdoor unit
The address dial of outdoor unit is shown below:when outdoor unit is on,namely examines outdoor scheme quantity, and determines the main unitor auxiliary unit according to outdoor unit address.
Address 0: outdoor main unit; Address 1: outdoor auxiliary unit; Address 2: outdoor auxiliary unit; Address 3: outdoor auxiliary unit; Address higher than 3: ineffective address, error occurs.
Distance between ground bolt is shown below: (Note: Outdoor units inthe same system should be located in the same level.)
Outdoor unit
Through hole(15X20 longhole)
Sw4 query instructions:Display content Note
Normal displayNormal display ADDR of outdoor unitCap. of outdoor unitQty. of outdoor unitTotal cap. of outdoor unitsCap. REQT. of indoor unitsCap. REQT. of main unit (after correction)Running mode Actual running cap. of outdoor unitFan speed
Discharge temp, inverter compressor Discharge temp, No.1 fixed compressor Discharge temp, No.2 fixed compressor Current, inverter compressor Current, No.1 fixed compressor Current, No.2 fixed compressor Opening degree, electronic expansion valveAOpening degree, electronic expansionvalveBQty. of indoor unitThe last error or protection code
T2 averageT3 pipe tempT4 ambient temp
Actual value Actual value Actual value Actual value Actual value Actual value Actual value Actual value Actual value
Actual value
Actual value 8 Actual value 8
Effective to main unit
Effective to main unitEffective to main unit
No protection or error, display 00End of query
table2 functional description
Current protector, used for Digital Scroll compressor
Current protector, used for No.2 fixed compressor (Reserved )
Current protector, used for No.1 fixed compressor
Reserved
Transformer input, 220V AC
Reserved
Reserved
load output
Electric expansion valve drive port
Electric expansion valve drive port
Communication between indoor/outdoor units, RS-485 signal
T3 sensor port
Low pressuredetect portHigh pressure detect port
No.1 Fixed compressor discharge temperature detect port
Reserved
communication between outdoor units, RS-485 signal
T4 sensor port
Transformer output
load output
Digital scroll compressor discharge temperature detect port
Digital scroll compressor discharge temperature detect port
Phase C Power
load output
Reserved
Reserved
Reserved
No.2Fixed compressor discharge temperature detect port
Please establish the address of indoor and outdoor unit before debugging!!!High-voltage in the electrically controlled box,do not move if not professional!!!
Normal display:Display qty. of indoor units which communicate with outdoor unit onstandby mode. In case of cap. requirement, display running frequencyof compressor.Running mode:OFF: 0--OFF,1--FAN, 2-- COOL, 3-- HEAT, 4-- Constraint cool
Fan speed: 0--OFF, 1-- LOW, 2--HIGH
PWV opening: pulse count=displayed value 8
Sw1, Sw2: network ADDR setting switchSw4: query button
The outdoor unit of 8Hp, 10Hp and 12Hp exclude the part in broken
line circle and relevant wiring (including the wiring with CT2 currentinductor and HEAT2) on nameplate.
Sw3: constraint cool buttonSw5:Set lock mode switch
Patternlocking
-
7/27/2019 Inst Manual Outdoor252 450C
7/12
2 2 0 9 5 5 0 1 7 8
O u t d o o r A d d r e s s
d i a l s w i t c h
O u t d o o r P o w e r
d i a l s w i t c h
M o d e L o c k
d i a l s w i t c h
F o r c e d
c o o l i n g
P o i n t
C h e c k
( T a
b l e 2 )
-
7/27/2019 Inst Manual Outdoor252 450C
8/12
( R e s e r v e
d )
D i g i t a l c o m p r e s s o r
F i x e
d c o m p r e s s o r
F a n
C a p a c
i t o r ,
f a n
M a i n
4 - w a y v a
l v e
A u x
i l . 4 - w a y v a
l v e
C o n
t a c t o r
R e l a y
W i r i n g p l a c e
L o w - p r e s s u r e s w
i t c h
H i - p r e s s u e s w
i t c h
E l e c t r o n i c e x p a n s i o n v a l v e
M i d d l e
t e r m
i n a l
M i d d l e
t e r m
i n a l
P i p e
t e m p s e n s o r
O u t
d o o r
t e m p s e n s o r
d i s c
h a r g e
t e m p e r a
t u r e s e n s o r ,
D i g i t a l c o m p r e s s o r (
i n d o o r
)
d i s c
h a r g e
t e m p e r a
t u r e s e n s o r ,
D i g i t a l c o m p r e s s o r ( o u
t d o o r )
D i s c h a r g e
t e m p s e n s o r ,
f i x e
d c o m p r e s s o r
C u r r e n t
i n d u c t o r
P o w e r
t r a n s f o r m e r
S o l e n o i
d v a
l v e
C r a n k c a s e h e a t e r
O u t
d o o r u n
i t C O M M e r r o r
P h a s e p r o t e c
t i o n
C O M M e r r o r w
i t h i n d o o r u n
i t
T 3 e r r o r w
i t h w a r m s e n s o r
O u
t d o o r
t e m p s e n s o r e r r o r
E r r o r w
i t h D i g i t a l d i s c h a r g e
t e m p e r a
t u r e s e n s o r
O u t
d o o r u n
i t a d
d r e s s e r r o r
C h i p
C O M M e r r o r
C h i p
C O M M e r r o r
Q t y o
f o u t d o o r u n i t d e c r e a s e s
Q t y o
f o u
t d o o r u n
i t i n c r e a s e s
H i - p r e s s u r e p r o t e c
t i o n
L o w - p r e s s u r e p r o t e c
t i o n
C o m p r e s s o r c u r .
P r o
t e c
t i o n
C o m p r e s s o r d i s c h a r g e t e m p p r o t e c t i o n
O u t d o o r c o n d e n s e r h i t e m p p r o t e c t i o n
C u r r e n t p r o t e c t i o n
, N o
. 1 f i x e d c o m p r e s s o r
C u r r e n
t p r o
t e c t
i o n
, N o
. 2 f i x e
d c o m p r e s s o r
3 - p
h a s e p o w e r s u p p l y
C o n n e c t
i n d o o r
C o n n e c t o u
t d o o r
M a i n c o n t r o l b o a r d
M a i n u n i t A u x
i l . u n
i t 1
A u x
i l . u n
i t 2
A u x
i l . u n
i t 3
S w
1 c a p a c i
t y s e
t t i n g
( u n c
h a n g e a
b l e )
A d d r e s s s e
t t i n g
C a p a c
i t y s e
t t i n g
M o
d e
l o c k
i n g
O
u t d o o r u n i t
w i r i n g n a m a p l a t e
L o a d p a t c h b o a r d
-
7/27/2019 Inst Manual Outdoor252 450C
9/12
16(29) 1625 (46)35 (78)60 50
380V 3N~
50Hz80 70
a
b
b
a
OUTDOOR UNIT INSTALLATION
I n s nowy a rea s, f acilities s hould be insta lled top revent sn ow. (S ee the chart be low)(defectivef acilities m ay cau se malfunction.) Pleas e lift theb rac ket higher an d install s now shed at the airi nlet and a ir outlet.
Snow sh ed for air inlet Snow shed for air outlet
Sn ow sh ed for air inlet
ELECTRIC WIRING
CAUTION
Please select power supply for indoor unit andoutdoor unit separately.
The power supply should have speci ed branchcircuit with leakage protector and manual switch.
Please pu t the conne ctive wiring system be tweenindoor unit and outdoor unit with refrigeran t pipingsystem tog ether.
Pleas e comply with relevant Natio nal E lectric Stan dard.Power w iring sho uld be done by profess ional ele ctrician.
The power s upply, lea kage protector and manual o f allthe indoor units connecting to the sam e outdoor unitshould be universal . (Pl eas e se t all the indoor unit powersupply of one sy stem into the sam e cir cuit.)
It is su ggested to use 2 -core shielded wire as s ignalwire between indoor and outdoor units, mu lti-core wireis una vailab le.
POWER WIRING
Separate Power Supply (without power facility)(See table below)
Model
ItemPowersupply
Min. Power wire diametermmWiring of mental and synthetic resin
2 Manual switch(A) Leakage
protectorGroundingwire CapacityFuse
100mA0.1sec orless
Size Size
380V 3N~50Hz
16(29)25 (46)
35 (78)16
Note: S elect po wer cord for these ve models separa telya ccording to rele vant sta ndard.
Note: The wiring diameter and the l ength in the table indicatethe c ondition that the voltage dropping range is within
2 %. If the length exceeds t he ab ove figure, please se lectthe wire diameter according to relevant standard.
380V 3N~
50Hz
Outdoor unitpower supply
Leakageprotector
Manualswitch
Lea kageprotectorManualsw itch
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Outdoor unit
GND
GND
GND
GND
GND
GNDBranch box
GND
GND
GND
GND
GND
GND
With power facilities Power facilities(with leakage protector)
Branch box
Lea kageprotectorManualsw itch
Outdoor unit
Outdoor unit
Select the wire diameterPowe r wiring re fer to the m ain w ire (a ) con necting tobranch box and the wiring (b) be tween branch box a ndpower faci lities. Plea se se lect the wire diameter ac cordingto the following requirement.
(1) Di amete r of main wire (a)Depends on the total horsepo wer of outdoor unit andfollowing ta ble.E.g In syste m:(5H p 1unit+8Hp 1unit+10Hp 1unit)Total H p=23H p ( Table ) siz e of w ire=70mm ( within50m)(2) W iring(b) between branch box a nd power equipmentDepends on the number of combined outdoor unit. If fewerthan 5, th e dia meter is t he s ame as t hat of ma in wire (a);if more than6, there will be 2 el ectric co ntrol boxes, a nd thediameter of wiring depends on the total horsepower of outdoor connecting to andfollowing table.
units each elec tric control box
2
Select wire diameter ( ) (table) (unit :mm) 2
Y DM H-25 2C 35 B Y DM H-28 0C 35 B
Y DM H-33 5C 35 B Y DM H-40 0C 35 B
YDMH-450C35B
YDMH-252C35BYDMH-280C35BYDMH-335C35B
YDMH-400C35B
YDMH-450C35B
-
7/27/2019 Inst Manual Outdoor252 450C
10/12
2.530m
3.550m
1.6mm30 15
Single-phase220V~ 50Hz
380V 3N~50Hz
10~1415~1819~28
29~3637~4748~50
100100150
200300300
75100150
200250300
-
7/27/2019 Inst Manual Outdoor252 450C
11/12
-
7/27/2019 Inst Manual Outdoor252 450C
12/12
DE - COMMISSIONING DISMANTLING & DISPOSALThis product contains refrigerant under pressure, rotating parts, and electrical connections which
may be a danger and cause injury! All work must only be carried out by competent persons using suitable protective clothing and safety precautions.
1. Isolate all sources of electrical supply to theunit including any control system supplies switched by theunit. Ensure that all points of electrical and gasisolation are secured in the OFF position. The supply cables and gas pipework may then be disconnected and removed. For pointsof connection referto unit installation instructions.
2. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then bere-used, if appropriate, or returned to the manufacturer for disposal. Under No circumstances should refrigerant be vented to atmosphere. Whereappropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to local laws and regulations governingdisposal of oily wastes.
3. Packaged unit can generally be removed in one piece after disconnection as above.Any fixing down bolts should be removed and then unit lifted fromposition using the points provided and equipment of adequate lifting capacity. Reference MUST be made to the unit installation instructions for unitweight and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and disposed of as described above.
4. After removal from position the unit parts may be disposed of according to local laws and regulations.
dellortnoc y letomersitinUkcohscirtcelefoksiRlaunaMehtdaeRand may start without warning
ENGLISH