dunham-bush - db aire installation operation manual

48

Click here to load reader

Upload: cdavidsalazar

Post on 26-Dec-2015

663 views

Category:

Documents


67 download

TRANSCRIPT

Page 1: Dunham-Bush - DB Aire Installation Operation Manual

Form No: MM0704A-1212

R134a

R407C

50Hz 60Hz

INSTALLATION,OPERATION &MAINTENANCEMANUAL

INSTALLATION,OPERATION &MAINTENANCEMANUAL

R410A

PRECISION ENVIRONMENTAL CONTROL UNIT

50/60 Hz

DB-Aire II(Indoor Unit)

DB-Aire II (Outdoor Unit)

DB-Aire II Systems

Page 2: Dunham-Bush - DB Aire Installation Operation Manual

 

- 2 -

 

TABLE OF CONTENTS

Page No GENERAL INFORMATION Nomenclature ....................................................................................................................................................................................... 3 Performance And Technical Data ........................................................................................................................................................ 4 Dual Coils Option ................................................................................................................................................................................. 8 Electrical Data ...................................................................................................................................................................................... 9 Dimensional Data ............................................................................................................................................................................... 11 Remote Air-Cooled Condensers ........................................................................................................................................................ 20 INSTALLATION Inspection ........................................................................................................................................................................................... 21 Transport ............................................................................................................................................................................................ 21 Operating Limits ................................................................................................................................................................................. 21 Locating The Unit And Installation Clearance .................................................................................................................................... 21 Dismantling Unit Frame ...................................................................................................................................................................... 22 Removing Fixed Panels ..................................................................................................................................................................... 23 Removing Filters ................................................................................................................................................................................ 24 Installing Discharge Plenum (Optional) .............................................................................................................................................. 24 Belt Tension Inspection Guide ........................................................................................................................................................... 25 Air-Cooled Piping ............................................................................................................................................................................... 26 Pipe Supports ..................................................................................................................................................................................... 26 Field Provided Piping And Wiring ....................................................................................................................................................... 26 Long Refrigeration Piping ................................................................................................................................................................... 27 Leak Test (System Pressure Test) ..................................................................................................................................................... 29 Vacuum Test And Dehydration .......................................................................................................................................................... 29 Charging ............................................................................................................................................................................................. 29 System Check For Overcharging ....................................................................................................................................................... 30 Water Connections ............................................................................................................................................................................. 30 Humidifier (Optional) .......................................................................................................................................................................... 31 Modulating Hot Gas Reheat For DX System ..................................................................................................................................... 32 Remote Air Cooled Condenser (DBRC) ............................................................................................................................................. 32 Operation ........................................................................................................................................................................................... 32 Dimensional Clearance - Remote Air Cooled Condenser (DBRC) .................................................................................................... 33 OPERATION Electrical Connections ........................................................................................................................................................................ 34 Check For Correct Phasing ................................................................................................................................................................ 34 Under-Floor Water-Detection Probe (Optional) .................................................................................................................................. 34 Alarm Processor ................................................................................................................................................................................. 34 Control Logic ...................................................................................................................................................................................... 35 Piping Schematic ............................................................................................................................................................................... 37 MAINTENANCE INSTRUCTIONS Maintenance ....................................................................................................................................................................................... 40 Troubleshooting Chart ........................................................................................................................................................................ 41 Sample Log Sheet .............................................................................................................................................................................. 43 GUIDE SPECIFICATIONS ................................................................................................................................................................. 44

CAUTION

The manual is to be retained for the entire service life of the unit Read the manual carefully before carrying out any operation on the unit The control is used exclusively for the purpose for which it is intended. Incorrect use of the control shall

release the manufacturer from any liability

This manual is prepared to enable the user to carry out only the operation that can be made with the panels closed. The panel key which is supplied with the unit must be kept by the person responsible for maintenance.

For identification of the unit (model and serial no.) in case of the necessity for assistance or spare parts, locate the identification label on the outside of the unit.

Page 3: Dunham-Bush - DB Aire Installation Operation Manual

 

- 3 -

 

GENERAL INFORMATION NOMENCLATURE INDOOR UNIT

String 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22

D B A D 0 2 P A U D B H G S K P S E V N 1 Q

Outdoor Unit Nomenclature (for Air Cooled DX-System/ Dual Coils System/ DX-System with Hot Gas Reheat )

String 1 2 3 4 5 6 7 8 9 10 11 12 13

D B R C 0 4 P A U A L 1 Q

18 ELECTRIC HEATER OPTION E = Standard Electric Heater

(All models EXCEPT Air-Cooled DX with Hot Gas Reheat i.e. DBRU/D)

N = Electric Heaters Not Furnished (Air-Cooled DX with Hot Gas Reheat i.e. DBRU/D only)

1 & 2 DB-AIRE II

10 DRAIN PAN OPTIONS D = Standard GI Painted T = Stainless Steel

11 DISCHARGE PLENUM OPTION (for Upflow model only) B = Discharge Plenum N = Not Selected

12 HUMIDIFIER OPTION H = Humidifier (water conductivity 75 to 350μS/cm)*** N = Not Selected ***Please consult factory for other water conductivity.

13 HOT GAS BYPASS OPTION G = Hot Gas Bypass N = Not Selected

3 SYSTEM A = Air-Cooled (DX) C = Chilled Water (CW) D = Dual Coils (DX+CW)* R = Air-Cooled DX with Hot Gas Reheat *Model 26 Dual Coils not available

4 CONFIGURATION U = Upflow D = Downflow

5 & 6 MODEL # Std Airflow, ESP Motor hp(kW) CFM(m3/h) (in WG) DX or CW / Dual Coils System 02 1,500 (2,548) 0.3 1.0 (0.75)/1.0 (0.75) 03 1,500 (2,548) 0.3 1.0 (0.75)/1.0 (0.75) 04 2,000 (3,398) 0.3 1.0 (0.75)/ 1.5 (1.1) 05 2,500 (4,247) 0.3 2.0 (1.5)/ 2.0 (1.5) 07 4,000 (6,796) 0.5 2.0 (1.5)/ 2.0 (1.5) 09 5,000 (8,495) 0.5 3.0 (2.2)/ 4.0 (3.0) 11 6,000 (10,194) 0.5 4.0 (3.0)/ 5.5 (4.1) 13 6,500 (11,043) 0.5 5.5 (4.1)/ 5.5 (4.1) 14 8,000 (13,592) 0.5 4.0 (3.0)/ 4.0 (3.0) 16 10,000 (16,989) 0.5 5.5 (4.1)/ 7.5 (5.6) 19 11,000 (18,688) 0.5 7.5 (5.6)/ 7.5 (5.6) 22 11,000 (18,688) 0.5 7.5 (5.6)/ 10.0 (7.5) 26 13,000 (22,086) 0.5 10.0 (7.5)/ Not Applicable

7 REFRIGERANT P = R407C / Dual Coils System / DX with Hot Gas Reheat N = R22 for DX, Dual Coils(DX+CW) & DX with Hot Gas

Reheat/ Chilled Water Unit

8 & 9 VOLTAGE OPTIONS AU = 380~415V/3ph/50Hz AR = 460V/3ph/60Hz CD = 208V/3ph/60Hz** AN = 230V/3ph/60Hz** EF = 380V/3ph/60Hz** Model 02 and 03 Air-Cooled Units 60Hz option not available. **Please consult factory for these special voltages. It requires additional cost and longer lead

time.

21 BMS COMMUNICATION OPTIONS

1 = ModBus RTU RS485**** 2 = ModBus TCPIP 3 = BACnet TCPIP 4 = BACnet MSTP 5 = BACnet PTP 6 = LONworks 7 = GSM Modem 8 = SNMP N = Not Selected **** Standard unit comes with one

ModBus RTU RS485 Communication port.

20 FUTURE OPTION N = Not Selected

19 VFD OPTION V = VFD N = Not Selected

14 EVAPORATOR CONTROL OPTIONS N = Standard Thermal Expansion Valve (TXV) S = Standard Thermal Expansion Valve (TXV) & Liquid Line Solenoid Valve X = Electronic Expansion Valve (EEV)

15 PANEL INSULATION OPTIONS K = Double Skin Panel F = Insulflex Insulation Single Skin Panel N = Not Selected. Standard Fiberglass Insulation Panel

16 UNDER FLOOR WATER DETECTOR OPTION P = Pinhole Probe N = Not selected

17 SMOKE DETECTOR OPTION S = Smoke Detector N = Not selected

22 OTHER SPECIAL OPTION

Q = Special Option N = Not Selected

1,2,3 & 4 AIR COOLED CONDENSER

8 & 9 VOLTAGE OPTIONS AU = 380~415V/3ph/50Hz AR = 460V/3ph/60Hz CD = 208V/3ph/60Hz** AN = 230V/3ph/60Hz** EF = 380V/3ph/60Hz** **Please consult factory for these special voltages. It requires additional cost and longer lead time.

5 & 6 MODEL 04 *with 220~240V/1ph/50,60Hz 06 08 10 11 13 17 20 26 30 34 40 44

7 REFRIGERANT P = R22 / R407C

10 CONDENSER FIN OPTIONS A = Standard Aluminium H = Hydrophilic C = Copper Fin

11 BLACK PAINT (EXTERNAL) OPTION L = Black Paint on Unit External N = Not selected

12 REFRIGERATION CIRCUIT(S) 1 = 1-Circuit (for standard indoor model 02-13) 2 = 2-Circuits (for standard indoor model 14-26)

13 OTHER SPECIAL OPTION Q = Special Option N = Not selected

Page 4: Dunham-Bush - DB Aire Installation Operation Manual

 

- 4 -

 

GENERAL INFORMATION PERFORMANCE AND TECHNICAL DATA Air Cooled Dx System @ 35oC (95oF) Ambient Temperature - With or Without Hot Gas Reheat

Model DBAD/U 02DBRD/U 02

DBAD/U 03DBRD/U 03

DBAD/U 04DBRD/U 04

DBAD/U 05 DBRD/U 05

DBAD/U 07 DBRD/U 07

DBAD/U 09DBRD/U 09

Return Air 80°F/67°F/50% RH (27°C/19°C/50% RH)

Total Cooling Capacity

MBH (kW)

41.0 (12.0)

42.9 (12.6)

51.3 (15.0)

63.8 (18.7)

89.6 (26.3)

131.7 (38.6)

Sensible Cooling Capacity

MBH (kW)

32.2 (9.4)

35.7 (10.5)

44.3 (13.0)

54.7 (16.0)

77.9 (22.8)

111.7 (32.7)

Sensible Heat Ratio (SHR) 0.79 0.83 0.86 0.86 0.87 0.85

Return Air 75°F/62.5°F/50% RH (24°C/17°C/50% RH)

Total Cooling Capacity

MBH (kW)

34.7 (10.2)

38.8 (11.4)

49.7 (14.6)

58.2 (17.1)

80.9 (23.7)

119.3 (35.0)

Sensible Cooling Capacity

MBH (kW)

30.7 (9.0)

35.1 (10.3)

44.8 (13.1)

53.8 (15.8)

75.6 (22.1)

109.8 (32.2)

Sensible Heat Ratio (SHR) 0.90 0.90 0.90 0.93 0.93 0.92

Return Air 72°F/60°F/50% RH (22°C/16°C/50% RH)

Total Cooling Capacity

MBH (kW)

32.7 (9.6)

36.3 (10.6)

46.5 (13.6)

54.6 (16.0)

80.2 (23.5)

118.3 (34.7)

Sensible Cooling Capacity

MBH (kW)

30.0 (8.8)

33.7 (9.9)

43.8 (12.8)

52.6 (15.4)

75.3 (22.1)

108.8 (31.9)

Sensible Heat Ratio (SHR) 0.92 0.93 0.94 0.96 0.94 0.92

Compressor

Number of Compressor(s) 1 1 1 1 1 1

Total Power Input (50Hz) kW 3.4 3.4 4.7 5.2 6.5 10.2

Total Power Input (60Hz) kW N/A N/A 4.4 5.4 6.6 11.2

Hot Gas; Liquid Lines, 50Hz Inch 5/8 ; 1/2 5/8 ; 1/2 5/8 ; 1/2 5/8 ; 1/2 7/8 ; 1/2 7/8 ; 5/8

Hot Gas; Liquid Lines, 60Hz Inch N/A N/A 5/8 ; 1/2 5/8 ; 1/2 7/8 ; 1/2 7/8 ; 1/2

Fan & Motor (Indoor)

Fan Size 10/8 10/8 10/8 10/8 15/15 15/15

Air Volume CFM (m3/h)

1,500 (2,548)

1,500 (2,548)

2,000 (3,398)

2,500 (4,247)

4,000 (6,796)

5,000 (8,495)

External Static Pressure (ESP)

in H2O (Pa)

0.3 (75)

0.3 (75)

0.3 (75)

0.3 (75)

0.5 (125)

0.5 (125)

Motor (Standard Single Coil)

Hp(kW)

1.0 (0.75)

1.0 (0.75)

1.0 (0.75)

2.0 (1.5)

2.0 (1.5)

3.0 (2.2)

Coil (DX)

Face Area ft2(m2)

5.6 (0.5)

5.6 (0.5)

5.6 (0.5)

5.6 (0.5)

12.2 (1.1)

12.2 (1.1)

Face Velocity FPM (m/s)

270 (1.4)

270 (1.4)

360 (1.8)

450 (2.3)

327 (1.7)

409 (2.1)

Condensate Drain O.D Inch 7/8 7/8 7/8 7/8 7/8 7/8

Filters (ASHRAE 52.5 MERV 8)

20" x 20" x 2" Qty 2 2 2 2 N/A N/A

20" x 20" x 4" Qty N/A N/A N/A N/A 4 4

20" x 25" x 4" Qty N/A N/A N/A N/A N/A N/A

Reheat (Electric) N/A for DBRD/U Models

3-Stages (rated at 415V)

MBH (kW)

20.5 (6.0)

20.5 (6.0)

20.5 (6.0)

20.5 (6.0)

41.0 (12.0)

41.0 (12.0)

Steam Humidifier (Optional)

Capacity (max.) lbs/hr (kg/hr)

17 (8.0)

17 (8.0)

17 (8.0)

17 (8.0)

17 (8.0)

17 (8.0)

Power Input (max.) kW 6.0 6.0 6.0 6.0 6.0 6.0

Sound Pressure Level (at 2m distance, free field, downflow) dBA 56 56 57 57 62 63

PHYSICAL DATA

Height H mm(inch)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

Width W mm (inch)

749 (29.5)

749 (29.5)

749 (29.5)

749 (29.5)

1464 (57.6)

1464 (57.6)

Depth D mm (inch)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

Weight DBAD/U kg

(lbs)251

(552) 259

(570) 260

(572) 272

(598) 420

(924) 450

(990)

DBRD/U kg (lbs)

265 (583)

273 (601)

274 (603)

286 (629)

442 (972)

472 (1038)

Notes: 1.) Add 457mm (18inch) to height of unit for Discharge Plenum (optional) – Upflow Models only 2.) Add 32kg (71lbs)- Model 02 to 05; 51kg(112 lbs)-Model 07 to 13; 80kg(176 lbs)- Model 14 to 26 to weight of unit for Discharge Plenum (optional)- Upflow Model only

Page 5: Dunham-Bush - DB Aire Installation Operation Manual

 

- 5 -

 

GENERAL INFORMATION Air Cooled Dx System @ 35oC (95oF) Ambient Temperature - With Or Without Hot Gas Reheat

Model DBAD/U 11DBRD/U 11

DBAD/U 13DBRD/U 13

DBAD/U 14DBRD/U 14

DBAD/U 16DBRD/U 16

DBAD/U 19 DBRD/U 19

DBAD/U 22 DBRD/U 22

DBAD/U 26DBRD/U 26

Return Air 80°F/67°F/50% RH (27°C/19°C/50% RH)

Total Cooling Capacity MBH (kW)

145.7 (42.7)

170.4 (49.9)

190.1 (55.7)

224.3 (65.7)

260.7 (76.4)

288.5 (84.5)

337.3 (98.8)

Sensible Cooling Capacity

MBH (kW)

128.7 (37.7)

145.9 (42.8)

158.3 (46.4)

190.9 (55.9)

226.1 (66.2)

244.3 (71.6)

286.0 (83.8)

Sensible Heat Ratio (SHR) 0.88 0.86 0.83 0.85 0.87 0.85 0.85

Return Air 75°F/62.5°F/50% RH (24°C/17°C/50% RH)

Total Cooling Capacity MBH (kW)

132.5 (38.8)

154.8 (45.4)

182.0 (53.3)

203.1 (59.5)

236.1 (69.2)

262.2 (76.8)

307.4 (90.1)

Sensible Cooling Capacity

MBH (kW)

124.7 (36.5)

143.3 (42.0)

161.2 (47.2)

185.2 (54.3)

222.7 (65.3)

240.0 (70.3)

276.8 (81.1)

Sensible Heat Ratio (SHR) 0.94 0.93 0.90 0.91 0.94 0.92 0.90

Return Air 72°F/60°F/50% RH (22°C/16°C/50% RH)

Total Cooling Capacity MBH (kW)

131.5 (38.5)

145.2 (42.5)

170.2 (49.9)

201.2 (59.0)

234.7 (68.8)

260.1 (76.2)

304.4 (89.2)

Sensible Cooling Capacity

MBH (kW)

125.5 (36.8)

140.0 (41.0)

155.2 (45.5)

184.5 (54.1)

221.2 (64.8)

237.9 (69.7)

278.6 (81.6)

Sensible Heat Ratio (SHR) 0.95 0.96 0.91 0.92 0.94 0.91 0.92

Compressor

Number of Compressor(s) 1 1 2 2 2 2 2

Total Power Input (50Hz) kW 11.1 12.7 14.7 17.1 20.3 21.8 26.1

Total Power Input (60Hz) kW 12.3 13.0 16.3 17.9 22.2 24.2 26.9

Hot Gas; Liquid Lines, 50Hz Inch 7/8; 5/8 7/8; 5/8 7/8(2);

1/2(2) 7/8(2); 1/2(2)

7/8(2); 5/8(2)

7/8(2); 5/8(2)

7/8(2); 5/8(2)

Hot Gas; Liquid Lines, 60Hz Inch 7/8; 5/8 7/8; 5/8 7/8(2);

1/2(2) 7/8(2); 1/2(2)

7/8(2); 1/2(2)

7/8(2); 5/8(2)

7/8(2); 5/8(2)

Fan & Motor (Indoor)

Fan Size 15/15 15/15 15/15 (Twin)

15/15 (Twin)

15/15 (Twin)

15/15 (Twin)

15/15 (Twin)

Air Volume CFM (m3/h)

6,000 (10,194)

6,500 (11,043)

8,000 (13,592)

10,000 (16,989)

11,000 (18,688)

11,000 (18,688)

13,000 (22,086)

External Static Pressure (ESP)

in H2O (Pa)

0.5 (125)

0.5 (125)

0.5 (125)

0.5 (125)

0.5 (125)

0.5 (125)

0.5 (125)

Motor (Standard Single Coil)

Hp (kW)

4.0 (3.0)

5.5 (4.0)

4.0 (3.0)

5.5 (4.0)

7.5 (5.5)

7.5 (5.5)

10.0 (7.5)

Coil (DX)

Face Area ft2(m2)

12.2 (1.1)

12.2 (1.1)

23.9 (2.2)

23.9 (2.2)

23.9 (2.2)

23.9 (2.2)

23.9 (2.2)

Face Velocity FPM (m/s)

491 (2.5)

532 (2.7)

335 (1.7)

419 (2.1)

461 (2.3)

461 (2.3)

544 (2.8)

Condensate Drain O.D Inch 7/8 7/8 7/8 7/8 7/8 7/8 7/8

Filters (ASHRAE 52.5 MERV 8)

20" x 20" x 2" Qty N/A N/A N/A N/A N/A N/A N/A

20" x 20" x 4" Qty 4 4 6 6 6 6 6

20" x 25" x 4" Qty N/A N/A 2 2 2 2 2

Reheat (Electric) N/A for DBRD/U Models

3-Stages (rated at 415V)

MBH (kW)

41.0 (12.0)

41.0 (12.0)

61.4 (18.0)

61.4 (18.0)

61.4 (18.0)

61.4 (18.0)

61.4 (18.0)

Steam Humidifier (Optional)

Capacity (max.) lbs/hr (kg/hr)

17 (8.0)

17 (8.0)

33 (15.0)

33 (15.0)

33 (15.0)

33 (15.0)

33 (15.0)

Power Input (max.) kW 6.0 6.0 11.3 11.3 11.3 11.3 11.3

Sound Pressure Level (at 2m distance, free field, downflow) dBA 66 70 65 65 66 69 73

PHYSICAL DATA

Height H mm(inch)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

Width W mm(inch)

1464 (57.6)

1464 (57.6)

2554 (100.6)

2554 (100.6)

2554 (100.6)

2554 (100.6)

2554 (100.6)

Depth D mm(inch)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

Weight DBAD/U kg

(lbs)460

(1,012) 474

(1,043) 735

(1,617) 754

(1,659) 802

(1,764) 823

(1,811) 835

(1,837)

DBRD/U kg (lbs)

482 (1,060)

496 (1,091)

776 (1,707)

795 (1,659)

843 (1,765)

864 (1,901)

876 (1,927)

Notes: 1.) Add 457mm (18inch) to height of unit for Discharge Plenum (optional) – Upflow Models only 2.) Add 32kg (71lbs)- Model 02 to 05; 51kg(112 lbs)-Model 07 to 13; 80kg(176 lbs)- Model 14 to 26 to weight of unit for Discharge Plenum (optional)- Upflow Model only

Page 6: Dunham-Bush - DB Aire Installation Operation Manual

 

- 6 -

 

GENERAL INFORMATION Chilled Water System @ Water Supply/ Return 7°C/ 12°C (44.6°F/ 53.6°F)

Model DBCD/U 02

DBCD/U 03

DBCD/U 04

DBCD/U 05

DBCD/U 07

DBCD/U 09

Return Air 80F/67F/50% RH (27C/19C/50% RH)

Total Cooling Capacity

MBH (kW)

45.7 (13.4)

62.2 (18.2)

81.4 (23.8)

95.8 (28.1)

147.2 (43.1)

186.5 (54.6)

Sensible Cooling Capacity

MBH (kW)

34.9 (10.2)

44.2 (12.9)

59.3 (17.4)

71.1 (20.8)

109.3 (32.0)

138.6 (40.6)

Sensible Heat Ratio (SHR) 0.76 0.71 0.73 0.74 0.74 0.74

Water Flow Rate GPM (m3/hr)

10.5 (2.4)

14.3 (3.2)

18.7 (4.2)

22.0 (5.0)

33.8 (7.7)

41.9 (9.5)

Water Pressure Drop PSI (kPa) 4.2 (29.3)

10.4 (71.4)

3.7 (25.7)

4.9 (34.1)

5.0 (34.7)

18.3 (125.8)

Return Air 75F/62.5F/50% RH (24C/17C/50% RH)

Total Cooling Capacity

MBH (kW)

31.8 (9.3)

43.0 (12.6)

57.5 (16.9)

67.9 (19.9)

103.8 (30.4)

132.3 (38.8)

Sensible Cooling Capacity

MBH (kW)

29.9 (8.8)

37.1 (10.9)

50.5 (14.8)

61.0 (17.9)

93.2 (27.3)

118.6 (34.8)

Sensible Heat Ratio (SHR) 0.94 0.86 0.88 0.90 0.90 0.90

Water Flow Rate GPM (m3/hr)

7.3 (1.7)

9.9 (2.2)

13.2 (3.0)

15.6 (3.5)

23.8 (5.4)

29.7 (6.7)

Water Pressure Drop PSI (kPa) 2.3 (15.8)

5.5 (38.0)

2.1 (14.3)

2.7 (18.8)

2.7 (18.8)

10.1 (69.6)

Return Air 72F/60F/50% RH (22C/16C/50% RH)

Total Cooling Capacity

MBH (kW)

26.8 (7.9)

35.9 (10.5)

48.1 (14.1)

57.0 (16.7)

86.9 (25.5)

108.9 (31.9)

Sensible Cooling Capacity

MBH (kW)

26.4 (7.7)

32.5 (9.5)

44.4 (13.0)

53.8 (15.8)

82.0 (24.0)

107.8 (31.6)

Sensible Heat Ratio (SHR) 0.99 0.91 0.92 0.94 0.94 0.99

Water Flow Rate GPM (m3/hr)

6.0 (1.4)

8.0 (1.8)

10.7 (2.4)

12.7 (2.9)

19.3 (4.4)

24.2 (5.5)

Water Pressure Drop PSI (kPa)

1.6 (11.1)

3.9 (26.6)

1.4 (9.9)

1.9 (13.2)

1.9 (13.2)

7.1 (49.0)

Fan & Motor (Indoor)

Fan Size 10/8 10/8 10/8 10/8 15/15 15/15

Air Volume CFM (m3/h)

1,500 (2,548)

1,500 (2,548)

2,000 (3,398)

2,500 (4,247)

4,000 (6,796)

5,000 (8,495)

External Static Pressure (ESP)

in H2O (Pa)

0.3 (75)

0.3 (75)

0.3 (75)

0.3 (75)

0.5 (125)

0.5 (125)

Motor hp (kW)

1.0 (0.75)

1.0 (0.75)

1.0 (0.75)

2.0 (1.5)

2.0 (1.5)

3.0 (2.2)

Coil (Chilled Water)

Face Area ft2 (m2)

5.6 (0.5)

5.6 (0.5)

5.6 (0.5)

5.6 (0.5)

12.2 (1.1)

12.2 (1.1)

Face Velocity FPM (m/s)

270 (1.4)

270 (1.4)

360 (1.8)

450 (2.3)

327 (1.7)

409 (2.1)

Condensate Drain O.D inch 7/8 7/8 7/8 7/8 7/8 7/8

Chilled Water Control

3-Way Modulating Valve, Size

DN, mm 25 25 25 25 25 25

Kv, m³/h 10 10 10 10 10 10

Filters (ASHRAE 52.5 MERV 8)

20" x 20" x 2" Qty 2 2 2 2 N/A N/A

20" x 20" x 4" Qty N/A N/A N/A N/A 4 4

20" x 25" x 4" Qty N/A N/A N/A N/A N/A N/A

Reheat (Electric)

3-Stages (rated at 415V)

MBH (kW)

20.5 (6.0)

20.5 (6.0)

20.5 (6.0)

20.5 (6.0)

41.0 (12.0)

41.0 (12.0)

Steam Humidifier (Optional)

Capacity (max.) lbs/hr (kg/hr)

17 (8.0)

17 (8.0)

17 (8.0)

17 (8.0)

17 (8.0)

17 (8.0)

Power Input (max.) kW 6.0 6.0 6.0 6.0 6.0 6.0

Sound Pressure Level (at 2m distance, free field, downflow) dBA 48 50 52 55 52 53

Physical Data

Height H mm(inch)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

Width W mm(inch)

749 (29.5)

749 (29.5)

749 (29.5)

749 (29.5)

1464 (57.6)

1464 (57.6)

Depth D mm(inch)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

Weight

kg(lbs)

205 (451)

212 (466)

219 (482)

229 (504)

365 (803)

374 (823)

Note: 1.) Add 457mm (18 inch) to height of unit for Discharge Plenum (optional) – Upflow Models only 2.) Add 32kg (71lbs)- Model 02 to 05; 51kg(112 lbs)- Model 07 to 13; 80kg(176 lbs)- Model 14 to 26 to weight of unit for Discharge Plenum (optional)- Upflow Model only

Page 7: Dunham-Bush - DB Aire Installation Operation Manual

 

- 7 -

 

GENERAL INFORMATION Chilled Water System @ Water Supply/ Return 7°C/ 12°C (44.6°F/ 53.6°F)

Model DBCD/U 11 DBCD/U 13 DBCD/U 14 DBCD/U 16 DBCD/U 19 DBCD/U 22 DBCD/U 26

Return Air 80F/67F/50% RH (27C/19C/50% RH)

Total Cooling Capacity MBH (kW)

228.1 (66.8)

252.1 (73.9)

291.5 (85.4)

340.7 (99.8)

396.9 (116.3)

447.5 (131.1)

505.1 (148.0)

Sensible Cooling Capacity

MBH (kW)

169.6 (49.7)

185.3 (54.3)

216.8 (63.5)

258.8 (75.8)

297.9 (87.3)

324.0 (94.9)

370.8 (108.6)

Sensible Heat Ratio (SHR) 0.74 0.74 0.74 0.76 0.75 0.72 0.73

Water Flow Rate GPM (m3/hr)

52.3 (11.9)

57.8 (13.1)

66.8 (15.2)

78.1 (17.7)

91.0 (20.7)

102.6 (23.3)

115.8 (26.3)

Water Pressure Drop PSI (kPa)

7.5 (51.7)

15.0 (103.4)

4.2 (28.7)

5.5 (37.7)

4.9 (34.1)

11.7 (81.0)

14.5 (99.8)

Return Air 75F/62.5F/50% RH (24C/17C/50% RH)

Total Cooling Capacity MBH (kW)

162.0 (47.5)

179.7 (52.7)

205.3 (60.2)

240.5 (70.5)

280.9 (82.3)

319.0 (93.5)

360.4 (105.6)

Sensible Cooling Capacity

MBH (kW)

145.3 (42.6)

158.9 (46.6)

184.9 (54.2)

221.9 (65.0)

255.5 (74.9)

277.1 (81.2)

318.1 (93.2)

Sensible Heat Ratio (SHR) 0.90 0.88 0.90 0.92 0.91 0.87 0.88

Water Flow Rate GPM (m3/hr)

37.2 (8.4)

41.2 (9.4)

47.1 (10.7)

55.1 (12.5)

64.4 (14.6)

73.2 (16.6)

82.7 (18.8)

Water Pressure Drop PSI (kPa)

4.1 (28.4)

8.4 (57.7)

2.3 (15.5)

3.0 (20.6)

2.7 (18.5)

6.5 (45.1)

8.1 (55.6)

Return Air 72F/60F/50% RH (22C/16C/50% RH)

Total Cooling Capacity MBH (kW)

136.1 (39.9)

151.1 (44.3)

172.2 (50.5)

202.5 (59.3)

236.4 (69.3)

267.6 (78.4)

303.1 (88.8)

Sensible Cooling Capacity

MBH (kW)

128.4 (37.6)

140.2 (41.1)

163.4 (47.9)

196.3 (57.5)

225.8 (66.2)

243.6 (71.4)

280.0 (82.0)

Sensible Heat Ratio (SHR) 0.94 0.93 0.95 0.97 0.96 0.91 0.92

Water Flow Rate GPM (m3/hr)

30.3 (6.9)

33.6 (7.6)

38.3 (8.7)

45.1 (10.2)

52.6 (11.9)

59.5 (13.5)

67.4 (15.3)

Water Pressure Drop PSI(kPa)

2.9 (19.7)

5.9 (40.7)

1.6 (11.1)

2.1 (14.3)

1.9 (12.9)

4.6 (31.7)

5.7 (39.2)

Fan & Motor (Indoor)

Fan Size 15/15 15/15 15/15 (Twin)

15/15 (Twin)

15/15 (Twin)

15/15 (Twin)

15/15 (Twin)

Air Volume CFM(m3/h)

6,000 (10,194)

6,500 (11,043)

8,000 (13,592)

10,000 (16,989)

11,000 (18,688)

11,000 (18,688)

13,000 (22,086)

External Static Pressure (ESP)

in H2O(Pa)

0.5 (125)

0.5 (125)

0.5 (125)

0.5 (125)

0.5 (125)

0.5 (125)

0.5 (125)

Motor Hp(kW)

4.0 (3.0)

5.5 (4.0)

4.0 (3.0)

5.5 (4.0)

7.5 (5.5)

7.5 (5.5)

10.0 (7.5)

Coil (Chilled Water)

Face Area ft2(m2)

12.2 (1.1)

12.2 (1.1)

23.9 (2.2)

23.9 (2.2)

23.9 (2.2)

23.9 (2.2)

23.9 (2.2)

Face Velocity FPM(m/s)

491 (2.5)

532 (2.7)

335 (1.7)

419 (2.1)

461 (2.3)

461 (2.3)

544 (2.8)

Condensate Drain O.D inch 7/8 7/8 7/8 7/8 7/8 7/8 7/8

Chilled Water Control

3-Way Modulating Valve, Size

DN, mm 40 40 40 40 40 50 50

Kv, m³/h 16 16 16 16 16 25 25

Filters (ASHRAE 52.5 MERV 8)

20" x 20" x 2" Qty N/A N/A N/A N/A N/A N/A N/A

20" x 20" x 4" Qty 4 4 6 6 6 6 6

20" x 25" x 4" Qty N/A N/A 2 2 2 2 2

Reheat (Electric)

3-Stages (rated at 415V)

MBH(kW)

41.0 (12.0)

41.0 (12.0)

61.4 (18.0)

61.4 (18.0)

61.4 (18.0)

61.4 (18.0)

61.4 (18.0)

Steam Humidifier (Optional)

Capacity (max.) lbs/hr(kg/hr)

17 (8.0)

17 (8.0)

33 (15.0)

33 (15.0)

33 (15.0)

33 (15.0)

33 (15.0)

Power Input (max.) kW 6.0 6.0 11.3 11.3 11.3 11.3 11.3

Sound Pressure Level (at 2m distance, free field, downflow) dBA 57 58 52 58 59 60 64

Physical Data

Height H mm(inch)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

1944 (76.5)

Width W mm (inch)

1464 (57.6)

1464 (57.6)

2554 (100.6)

2554 (100.6)

2554 (100.6)

2554 (100.6)

2554 (100.6)

Depth D mm (inch)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

874 (34.4)

Weight

kg(lbs)

398 (876)

410 (902)

602 (1,324)

615 (1,353)

665 (1,463)

678 (1,492)

688 (1,514)

Note: 1.) Add 457mm (18 inch) to height of unit for Discharge Plenum (optional) – Upflow Models only 2.) Add 32kg (71lbs)- Model 02 to 05; 51kg(112 lbs)- Model 07 to 13; 80kg(176 lbs)- Model 14 to 26 to weight of unit for Discharge Plenum (optional)- Upflow Model only

Page 8: Dunham-Bush - DB Aire Installation Operation Manual

 

- 8 -

 

GENERAL INFORMATION DUAL COILS OPTION Air Cooled DX & Chilled Water Systems This system is a combination of the both Direct Expansion (DX) and Chilled Water (CW) system with 2 cooling coil. Cooling capacity and other parameters for DX and CW System are as per stated on respective tables; except for the following.

Model DBDD/U 02 DBDD/U 03 DBDD/U 04 DBDD/U 05 DBDD/U 07 DBDD/U 09

Fan Motor (Indoor) hp (kW)

1.0 (0.75)

1.0 (0.75)

1.5 (1.1)

2.0 (1.5)

2.0 (1.5)

4.0 (3.0)

Sound Pressure Level (at 2m distance, free field, downflow) dBA 56 56 57 57 62 63

Weight kg (lbs)

270 (594)

284 (625)

292 (642)

304 (669)

467 (1,027)

497 (1,093)

Model DBDD/U 11 DBDD/U 13 DBDD/U 14 DBDD/U 16 DBDD/U 19 DBDD/U 22 DBDD/U 26

Fan Motor (Indoor) hp (kW)

5.5 (4.0)

5.5 (4.0)

4.0 (3.0)

7.5 (5.5)

7.5 (5.5)

10.0 (7.5)

N/A Sound Pressure Level (at 2m distance, free field, downflow) dBA 66 70 65 65 66 69

Weight kg (lbs)

523 (1,151)

537 (1,181)

823 (1,811)

842 (1,852)

909 (2,000)

941 (2,070)

Notes: 1.) Add 457mm (18inch) to height of unit for Discharge Plenum (optional) – Upflow Models only 2.) Add 32kg (71 lbs)- Model 02 to 05; 51kg(112 lbs)-Model 07 to 13; 80kg(176 lbs)- Model 14 to 22 to weight of unit for Discharge Plenum (optional)- Upflow Model only

CONDENSER SELECTION Selections are to be based on standard airflow rate and return air temperature of 24°C / 17°C (75°F / 62.5°F) or lesser at sea level.

Model

DX-System DBAD/U 02 DBAD/U 03 DBAD/U 04 DBAD/U 05 DBAD/U 07 DBAD/U 09

Dual Coils System DBDD/U 02 DBDD/U 03 DBDD/U 04 DBDD/U 05 DBDD/U 07 DBDD/U 09

DX-System with Hot Gas Reheat DBRD/U 02 DBRD/U 03 DBRD/U 04 DBRD/U 05 DBRD/U 07 DBRD/U 09

Total Heat Rejection (Nominal)

MBH (kW)

46 (14)

51 (15)

60 (18)

73 (21)

101 (30)

151 (44)

35°C (95°F) Ambient - DBRC04 DBRC04 DBRC04 DBRC06 DBRC08 DBRC10

37.8°C (100°F) Ambient - DBRC04 DBRC04 DBRC06 DBRC06 DBRC08 DBRC13

40.6°C (105°F) Ambient - DBRC04 DBRC06 DBRC06 DBRC08 DBRC11 DBRC17

43°C (110°F) Ambient See Note 1 DBRC06 DBRC06 DBRC08 DBRC11 DBRC17 DBRC20

46°C (115°F) Ambient See Note 1 DBRC08 DBRC11 DBRC17 DBRC17 DBRC26 DBRC34

49°C (120°F) Ambient See Note 2 DBRC11 DBRC11 DBRC17 DBRC20 DBRC26 DBRC34

52°C (125°F) Ambient See Note 3 DBRC13 DBRC13 DBRC20 DBRC26 DBRC30 DBRC40

Model

DX-System DBAD/U 11 DBAD/U 13 DBAD/U 14 DBAD/U 16 DBAD/U 19 DBAD/U 22 DBAD/U 26

Dual Coils System DBDD/U 11 DBDD/U 13 DBDD/U 14 DBDD/U 16 DBDD/U 19 DBDD/U 22 N/A

DX-System with Hot Gas Reheat DBRD/U 11 DBRD/U 13 DBRD/U 14 DBRD/U 16 DBRD/U 19 DBRD/U 22 DBRD/U 26

Total Heat Rejection (Nominal)

MBH (kW)

171 (50)

193 (57)

220 (64)

262 (77)

293 (86)

332 (97)

388 (114)

35°C (95°F) Ambient - DBRC13 DBRC17 DBRC17 DBRC20 DBRC20 DBRC26 DBRC30

37.8°C (100°F) Ambient - DBRC17 DBRC17 DBRC20 DBRC26 DBRC26 DBRC30 DBRC30

40.6°C (105°F) Ambient - DBRC20 DBRC26 DBRC26 DBRC26 DBRC34 DBRC34 DBRC34

43°C (110°F) Ambient See Note 1 DBRC26 DBRC30 DBRC34 DBRC40 DBRC44 DBRC44 DBRC44

46°C (115°F) Ambient See Note 1 DBRC40 DBRC44 DBRC44 DBRC30 x 2 DBRC30 x 2 DBRC40 x 2 DBRC40 x 2

49°C (120°F) Ambient See Note 2 DBRC40 DBRC44 DBRC44 DBRC30 x 2 DBRC34 x 2 DBRC40 x 2 DBRC44 x 2

52°C (125°F) Ambient See Note 3 DBRC44 DBRC44 DBRC26 x 2 DBRC30 x 2 DBRC34 x 2 DBRC44 x 2 DBRC44 x 2

Notes: 1.) Multiply Total Compressor Power Input by 1.05 2.) Multiply Cooling Capacity by 0.9. Multiply Total Compressor Power Input by 1.1 3.) Multiply Cooling Capacity by 0.9. Multiply Total Compressor Power Input by 1.2

Page 9: Dunham-Bush - DB Aire Installation Operation Manual

 

- 9 -

 

GENERAL INFORMATION ELECTRICAL DATA Air Cooled DX & Chilled Water Systems 1.) STANDARD - COOLING & ELECTRIC HEATERS At 35oC (95oF) ambient; Return Air at 24oC/17oC/50 %RH (75oF/62.5oF/50 %RH)

Model DBAD/U 02 DBAD/U 03 DBAD/U 04 DBAD/U 05 DBAD/U 07 DBAD/U 09

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 15.6 18 20 15.7 18 20 17.6 20 25 20.1 22 32 32.7 37 50 39.1 44 60 400V/ 3Ph/ 50Hz 16.0 18 20 16.2 18 20 18.0 20 25 20.5 23 32 33.6 38 50 39.7 44 63 415V/ 3Ph/ 50Hz 16.4 19 20 16.6 19 20 18.4 21 25 21.0 23 32 34.5 39 50 40.3 45 63 460V/ 3Ph/ 60Hz N/A N/A 15.3 17 20 18.0 20 25 28.5 32 40 35.7 40 50

Model DBAD/U 11 DBAD/U 13 DBAD/U 14 DBAD/U 16 DBAD/U 19 DBAD/U 22 DBAD/U 26

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 43.5 49 63 51.6 58 75 58.0 64 75 65.7 71 100 72.1 78 100 77.5 83 100 93.4 100 125 400V/ 3Ph/ 50Hz 44.2 50 63 53.0 60 75 59.1 65 75 66.9 73 100 72.9 79 100 78.5 85 100 96.0 103 125 415V/ 3Ph/ 50Hz 45.3 51 63 55.6 63 80 60.6 67 75 68.7 75 100 73.8 80 100 80.6 87 100 101.0 109 125 460V/ 3Ph/ 60Hz 38.3 43 60 41.4 46 63 53.2 59 63 56.5 62 75 64.5 70 100 67.3 73 100 75.8 81 100

Return Air at 24oC/17oC/50 %RH (75oF/62.5oF/50 %RH)

Model DBCD/U 02 DBCD/U 03 DBCD/U 04 DBCD/U 05 DBCD/U 07 DBCD/U 09

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 9.7 12 16 9.7 12 16 9.7 12 16 11.3 13 16 18.9 23 25 20.3 24 30 400V/ 3Ph/ 50Hz 10.0 12 16 10.0 12 16 10.0 12 16 11.5 14 16 19.6 24 25 20.8 25 30 415V/ 3Ph/ 50Hz 10.2 12 16 10.2 12 16 10.2 12 16 11.7 14 16 20.0 24 25 21.2 25 30 460V/ 3Ph/ 60Hz 6.6 8 10 7.9 9 16 9.1 11 16 10.5 12 16 18.1 22 25 19.2 23 25

Model DBCD/U 11 DBCD/U 13 DBCD/U 14 DBCD/U 16 DBCD/U 19 DBCD/U 22 DBCD/U 26

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 22.0 26 30 23.9 28 32 29.6 35 40 31.5 37 40 34.5 40 50 34.5 40 50 38.0 44 50 400V/ 3Ph/ 50Hz 22.5 26 30 24.2 28 32 30.5 37 40 32.3 38 40 35.1 41 50 35.1 41 50 38.4 44 50 415V/ 3Ph/ 50Hz 22.8 27 30 24.5 29 32 31.2 37 40 32.9 39 40 35.6 42 50 35.6 42 50 38.8 45 50 460V/ 3Ph/ 60Hz 20.5 24 30 22.0 26 30 28.0 34 40 29.5 35 40 31.9 38 50 31.9 38 50 35.8 41 50

2.) STANDARD WITH OPTIONAL HUMIDIFIER At 35oC (95oF) ambient; Return Air at 24oC/ 17oC/50 %RH (75oF/62.5oF/50 %RH)

Model DBAD/U 02 DBAD/U 03 DBAD/U 04 DBAD/U 05 DBAD/U 07 DBAD/U 09

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 24.7 27 32 24.8 27 32 26.7 29 32 29.2 31 40 41.8 46 60 48.2 53 63 400V/ 3Ph/ 50Hz 24.7 27 32 24.9 27 32 26.7 29 32 29.2 31 40 42.2 46 50 48.4 53 63 415V/ 3Ph/ 50Hz 24.8 27 32 25.0 27 32 26.8 29 32 29.3 31 40 42.9 47 50 48.7 53 63 460V/ 3Ph/ 60Hz N/A N/A 22.9 25 30 25.5 27 30 36.0 40 50 43.2 47 63

Model DBAD/U 11 DBAD/U 13 DBAD/U 14 DBAD/U 16 DBAD/U 19 DBAD/U 22 DBAD/U 26

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS 380V/ 3Ph/ 50Hz 52.6 58 75 60.7 68 80 75.1 81 100 82.8 89 100 89.2 95 100 94.6 100 125 110.5 117 150 400V/ 3Ph/ 50Hz 52.8 58 75 61.7 69 80 75.3 81 100 83.1 89 100 89.2 95 100 94.8 101 125 112.3 119 150 415V/ 3Ph/ 50Hz 53.7 59 80 64.0 72 100 76.2 82 100 84.3 91 100 89.5 96 100 96.3 103 125 116.7 124 150 460V/ 3Ph/ 60Hz 45.8 50 63 48.9 54 63 67.3 73 100 70.6 76 100 78.6 84 100 81.4 87 100 89.9 96 100

Return Air at 24oC/17oC/50 %RH (75oF/62.5oF/50 %RH)

Model DBCD/U 02 DBCD/U 03 DBCD/U 04 DBCD/U 05 DBCD/U 07 DBCD/U 09

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 18.8 21 25 18.8 21 25 18.8 21 25 20.4 22 25 28.0 32 40 29.4 33 40 400V/ 3Ph/ 50Hz 18.7 21 25 18.7 21 25 18.7 21 25 20.2 22 25 28.2 32 40 29.5 33 40 415V/ 3Ph/ 50Hz 18.6 21 25 18.6 21 25 18.6 21 25 20.0 22 25 28.4 33 40 29.6 34 40 460V/ 3Ph/ 60Hz 14.2 15 20 15.4 17 20 16.7 19 20 18.1 20 25 25.6 29 40 26.7 30 40

Model DBCD/U 11 DBCD/U 13 DBCD/U 14 DBCD/U 16 DBCD/U 19 DBCD/U 22 DBCD/U 26

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 31.1 35 40 33.0 37 40 46.7 52 60 48.6 54 60 51.6 57 63 51.6 57 63 55.1 61 70 400V/ 3Ph/ 50Hz 31.1 35 40 32.9 37 40 46.7 53 60 48.5 55 60 51.4 57 63 51.4 57 63 54.7 61 70 415V/ 3Ph/ 50Hz 31.2 35 40 32.9 37 40 46.8 53 60 48.5 55 60 51.3 58 63 51.3 58 63 54.5 61 70 460V/ 3Ph/ 60Hz 28.0 32 40 29.5 33 40 42.1 48 50 43.6 49 60 46.0 52 60 46.0 52 60 49.9 56 70

Note : RLA - Rated Load Amps MCA - Minimum Circuit Amps MFS - Maximum Fuse Size

Page 10: Dunham-Bush - DB Aire Installation Operation Manual

 

- 10 -

 

GENERAL INFORMATION ELECTRICAL DATA Air Cooled Dual Coils (DX + CW) & DX With Hot Gas Reheat Systems 1.) STANDARD - COOLING & ELECTRIC HEATERS At 35oC (95oF) ambient; Return Air at 24oC/17oC/50 %RH (75oF/62.5oF/ 50 %RH)

Model DBDD/U 02 DBDD/U 03 DBDD/U 04 DBDD/U 05 DBDD/U 07 DBDD/U 09

Power Supply RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS

380V/ 3Ph/ 50Hz 15.6 9.7 18 20 15.7 9.7 18 20 18.3 10.4 20 25 20.1 11.3 22 30 32.7 18.9 37 40 40.8 22.0 45 60 400V/ 3Ph/ 50Hz 16.0 10.0 18 20 16.2 10.0 18 20 18.6 10.6 21 25 20.5 11.5 23 30 33.6 19.6 38 40 41.4 22.5 46 60 415V/ 3Ph/ 50Hz 16.4 10.2 19 20 16.6 10.2 19 20 19.0 10.8 21 25 21.0 11.7 23 30 34.5 20.0 39 40 41.9 22.8 47 60 460V/ 3Ph/ 60Hz N/A N/A 16.0 9.8 18 20 18.0 10.5 20 25 28.5 18.1 32 40 37.0 20.5 41 50

Model DBDD/U 11 DBDD/U 13 DBDD/U 14 DBDD/U 16 DBDD/U 19 DBDD/U 22

Power Supply RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS

380V/ 3Ph/ 50Hz 45.4 23.9 51 63 51.6 23.9 58 75 58.0 29.6 64 75 68.7 34.5 74 100 72.1 34.5 78 100 81.0 38.0 87 100 400V/ 3Ph/ 50Hz 45.9 24.2 51 63 53.0 24.2 60 75 59.1 30.5 65 75 69.7 35.1 76 100 72.9 35.1 79 100 81.8 38.4 88 100 415V/ 3Ph/ 50Hz 47.0 24.5 53 63 55.6 24.5 63 75 60.6 31.2 67 75 71.4 35.6 78 100 73.8 35.6 80 100 83.8 38.8 90 100 460V/ 3Ph/ 60Hz 39.8 22.0 44 60 41.4 22.0 46 63 53.2 28.0 59 63 58.9 31.9 65 75 64.5 31.9 70 100 71.2 35.8 77 100

2.) STANDARD WITH OPTIONAL HUMIDIFIER At 35oC (95oF) ambient; Return Air at 24oC/17oC/50 %RH (75oF/62.5oF/ 50 %RH)

Model DBDD/U 02 DBDD/U 03 DBDD/U 04 DBDD/U 05 DBDD/U 07 DBDD/U 09

Power Supply RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS

380V/ 3Ph/ 50Hz 24.7 18.8 27 32 24.8 18.8 27 32 27.4 19.5 29 32 29.2 20.4 31 40 41.8 28.0 46 50 49.9 31.1 55 63 400V/ 3Ph/ 50Hz 24.7 18.7 27 32 24.9 18.7 27 32 27.3 19.3 29 32 29.2 20.2 31 40 42.2 28.2 46 50 50.0 31.1 55 63 415V/ 3Ph/ 50Hz 24.8 18.6 27 32 25.0 18.6 27 32 27.4 19.2 29 32 29.3 20.0 31 40 42.9 28.4 47 50 50.3 31.2 55 63 460V/ 3Ph/ 60Hz N/A N/A 23.6 17.4 25 30 25.5 18.1 27 30 36.0 25.6 40 50 44.5 28.0 49 63

Model DBDD/U 11 DBDD/U 13 DBDD/U 14 DBDD/U 16 DBDD/U 19 DBDD/U 22

Power Supply RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS RLA (DX)

RLA (CHW) MCA MFS RLA

(DX) RLA

(CHW) MCA MFS

380V/ 3Ph/ 50Hz 54.5 33.0 60 75 60.7 33.0 68 80 75.1 46.7 81 100 85.8 51.6 92 100 89.2 51.6 95 100 98.1 55.1 104 125 400V/ 3Ph/ 50Hz 54.6 32.9 60 75 61.7 32.9 69 80 75.3 46.7 81 100 86.0 51.4 92 100 89.2 51.4 95 100 98.1 54.7 104 125 415V/ 3Ph/ 50Hz 55.4 32.9 61 75 64.0 32.9 72 80 76.2 46.8 82 100 87.1 51.3 93 100 89.5 51.3 96 100 99.5 54.5 106 125 460V/ 3Ph/ 60Hz 47.3 29.5 52 63 48.9 29.5 54 63 67.3 42.1 73 100 73.0 46.0 79 100 78.6 46.0 84 100 85.3 49.9 91 100

3.) COOLING & HOT GAS REHEAT At 35oC (95oF) ambient; Return Air at 24oC/17oC/50 %RH (75oF/62.5oF/ 50 %RH)

Model DBRD/U 02 DBRD/U 03 DBRD/U 04 DBRD/U 05 DBRD/U 07 DBRD/U 09

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 8.0 9 16 8.1 10 16 10.0 12 20 12.4 15 20 17.4 21 32 23.8 28 40 400V/ 3Ph/ 50Hz 8.0 9 16 8.2 10 16 10.0 12 20 12.5 15 20 17.5 21 32 23.6 28 40 415V/ 3Ph/ 50Hz 8.1 10 16 8.3 10 16 10.1 12 20 12.6 15 20 17.8 21 32 23.7 28 40 460V/ 3Ph/ 60Hz N/A N/A 7.8 9 16 10.5 12 20 13.4 16 25 20.6 25 40

Model DBRD/U 11 DBRD/U 13 DBRD/U 14 DBRD/U 16 DBRD/U 19 DBRD/U 22 DBRD/U 26

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 28.2 34 50 36.3 43 63 35.1 39 50 42.8 47 63 49.2 54 75 54.6 60 75 70.5 77 100 400V/ 3Ph/ 50Hz 28.1 33 50 37.0 44 63 35.0 39 50 42.8 47 63 48.8 54 63 54.4 60 75 71.9 79 100 415V/ 3Ph/ 50Hz 28.6 34 50 39.0 47 75 35.5 39 50 43.7 48 63 48.8 54 63 55.6 61 75 76.0 84 100 460V/ 3Ph/ 60Hz 23.2 28 40 26.3 31 50 30.6 34 40 33.9 37 50 41.9 46 60 44.7 49 63 53.2 58 75

4.) COOLING & HOT GAS REHEAT WITH OPTIONAL HUMIDIFIER At 35oC (95oF) ambient; Return Air at 24oC/17oC/50 %RH (75oF/62.5oF/ 50 %RH)

Model DBRD/U 02 DBRD/U 03 DBRD/U 04 DBRD/U 05 DBRD/U 07 DBRD/U 09

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 17.1 19 25 17.2 19 25 19.1 21 25 21.6 24 32 26.6 30 40 32.9 38 50 400V/ 3Ph/ 50Hz 16.6 19 25 16.8 19 25 18.6 21 25 21.1 23 32 26.1 30 40 32.3 37 50 415V/ 3Ph/ 50Hz 16.4 19 25 16.6 19 25 18.4 21 25 21.0 23 32 26.2 30 40 32.0 37 50 460V/ 3Ph/ 60Hz N/A N/A 15.3 17 20 18.0 20 25 20.9 24 32 28.1 32 40

Model DBRD/U 11 DBRD/U 13 DBRD/U 14 DBRD/U 16 DBRD/U 19 DBRD/U 22 DBRD/U 26

Power Supply RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS RLA MCA MFS

380V/ 3Ph/ 50Hz 37.3 43 63 45.4 52 80 52.2 56 75 59.9 64 80 66.3 71 80 71.7 77 100 87.6 95 125 400V/ 3Ph/ 50Hz 36.7 42 63 45.6 53 80 51.2 55 63 59.0 63 80 65.0 70 80 70.6 76 100 88.1 95 125 415V/ 3Ph/ 50Hz 37.0 43 63 47.3 55 80 51.2 55 63 59.3 64 80 64.5 69 80 71.3 77 100 91.7 99 125 460V/ 3Ph/ 60Hz 30.7 35 50 33.8 39 50 44.7 48 60 48.0 51 63 56.0 60 75 58.8 63 80 67.3 72 100

Note : RLA - Rated Load Amps MCA - Minimum Circuit Amps MFS - Maximum Fuse Size

Page 11: Dunham-Bush - DB Aire Installation Operation Manual

 

- 11 -

 

GENERAL INFORMATION DIMENSIONAL DATA Down Flow - Air Cooled System (With or Without Hot Gas Reheat)

DBAD/ DBRD 02, 03, 04, 05

DBAD/ DBRD 07, 09, 11, 13

DBAD/ DBRD 14, 16, 19, 22, 26

Page 12: Dunham-Bush - DB Aire Installation Operation Manual

 

- 12 -

 

GENERAL INFORMATION Down Flow - Chilled Water System

DBCD 02, 03, 04, 05

DBCD 07, 09, 11, 13

DBCD 14, 16, 19, 22, 26

Page 13: Dunham-Bush - DB Aire Installation Operation Manual

 

- 13 -

 

GENERAL INFORMATION Down Flow - Dual Coils System

DBDD 02, 03, 04, 05

DBDD 07, 09, 11, 13

DBDD 14, 16, 19, 22

Page 14: Dunham-Bush - DB Aire Installation Operation Manual

 

- 14 -

 

GENERAL INFORMATION Up Flow - Air Cooled System (With or Without Hot Gas Reheat)

DBAU/ DBRU 02, 03, 04, 05

DBAU/ DBRU 07, 09, 11, 13

DBAU/ DBRU 14, 16, 19, 22, 26

Page 15: Dunham-Bush - DB Aire Installation Operation Manual

 

- 15 -

 

GENERAL INFORMATION Up Flow - Chilled Water System

DBCU 02, 03, 04, 05

DBCU 07, 09, 11, 13

DBCU 14, 16, 19, 22, 26

Page 16: Dunham-Bush - DB Aire Installation Operation Manual

 

- 16 -

 

GENERAL INFORMATION Up Flow - Dual Coils System

DBDU 02, 03, 04, 05

DBDU 07, 09, 11, 13

DBDU 14, 16, 19, 22

Page 17: Dunham-Bush - DB Aire Installation Operation Manual

 

- 17 -

 

GENERAL INFORMATION Up Flow With Plenum - Air Cooled System (With or Without Hot Gas Reheat)

DBAU/ DBRU 02, 03, 04, 05

DBAU/ DBRU 07, 09, 11, 13

DBAU/ DBRU 14, 16, 19, 22, 26

Page 18: Dunham-Bush - DB Aire Installation Operation Manual

 

- 18 -

 

GENERAL INFORMATION Up Flow With Plenum - Chilled Water System

DBCU 02, 03, 04, 05

DBCU 07, 09, 11, 13

DBCU 14, 16, 19, 22, 26

Page 19: Dunham-Bush - DB Aire Installation Operation Manual

 

- 19 -

 

GENERAL INFORMATION Up Flow With Plenum - Dual Coils System

DBDU 02, 03, 04, 05

DBDU 07, 09, 11, 13

DBDU 14, 16, 19, 22

Page 20: Dunham-Bush - DB Aire Installation Operation Manual

 

- 20 -

 

GENERAL INFORMATION REMOTE AIR-COOLED CONDENSERS Technical Data

Model  Physical Data Electrical Data

Length 'L'

mm (ins)

Fans Approx. Weight

kg(lbs)

Motor

Qty

RPM Motor FLA (3-Phase)

Qty Total L/S

(CFM)

380V

(50Hz)

400V

(50Hz)

415V

(50Hz)

460V

(60Hz) 50Hz 60Hz

DBRC 04 870 (34¼) 1 2030 (4300) 100 (220) 1 900 1075 220~240Vac, 1Ph, 50/60Hz. FLA @ 240V/50Hz = 1.4A; FLA @ 240V/60Hz = 1.5A

DBRC 06 870 (34¼) 1 3210 (6800) 111 (244) 1 925 1110 2.0 1.9 1.8 1.7

DBRC 08 870 (34¼) 1 3210 (6800) 122 (268) 1 925 1110 2.0 1.9 1.8 1.7

DBRC 10 870 (34¼) 1 3210 (6800) 134 (295) 1 925 1110 2.0 1.9 1.8 1.7

DBRC 11 870 (34¼) 1 3210 (6800) 180 (400) 1 925 1110 2.0 1.9 1.8 1.7

DBRC 13 1683 (66¼) 2 6420 (13600) 190 (420) 2 925 1110 4.0 3.8 3.6 3.4

DBRC 17 1683 (66¼) 2 6420 (13600) 204 (450) 2 925 1110 4.0 3.8 3.6 3.4

DBRC 20 1683 (66¼) 2 6420 (13600) 265 (583) 2 925 1110 4.0 3.8 3.6 3.4

DBRC 26 2500 (98¼) 3 9630 (20400) 288 (634) 3 925 1110 6.0 5.7 5.4 5.1

DBRC 30 2500 (98¼) 3 9630 (20400) 320 (700) 3 925 1110 6.0 5.7 5.4 5.1

DBRC 34 2500 (98¼) 3 9630 (20400) 355 (780) 3 925 1110 6.0 5.7 5.4 5.1

DBRC 40 3308 (130¼) 4 12838 (27200) 380 (835) 4 925 1110 8.0 7.6 7.2 6.8

DBRC 44 3308 (130¼) 4 12838 (27200) 410 (900) 4 925 1110 8.0 7.6 7.2 6.8

Notes: 1.) All dimensions are in mm (inches). 2.) * = 889(35”), ** = 972(38.25”) for DBRC-04

Page 21: Dunham-Bush - DB Aire Installation Operation Manual

 

- 21 -

 

INSTALLATION INSPECTION The DB-Aire II unit has been tested and inspected prior to shipment. To ensure that the unit has been received in excellent condition, perform a visual inspection of the outer crating immediately upon delivery, and note any external damage on the freight carrier’s delivery forms. As soon as possible, inspect the unit itself for possible internal damage. File a claim with the shipping company if the shipment is damaged or incomplete. Freight damage claims are the responsibility of the purchaser. TRANSPORT The unit is mounted on skid pallet, packed several times in plastic film and crated. It must always be transported vertically upright on the pallet with a fork lift. The unit can be moved by lifting devices with ropes. For this the ropes have to be fixed at the pallet, and the upper unit edges have to be protected by wooden laths or spreader bars to prevent damage to the unit.

To avoid any damage to the unit during transportation, it is recommended that the unit should only be removed from its packaging when the unit has reached its final destination. It is also essential to make sure that the floor on which the unit is to be installed is capable of supporting its weight. The weight of the unit can be found on the Performance and Technical Data on this manual. OPERATING LIMITS Units are designed to operate within working ranges (See Performance and Technical Data). The limits are referred to new machines which have been correctly installed and serviced. The warranty clauses are no longer valid for any possible damage or malfunction that may occur during or due to operation outside the application values.

Direct Expansion (DX) System Chilled Water (CW) System

Room Condition 68°F(20°C) to 80oF(27oC), 45 to 55% RH

Ambient Condition Min. 66oF(19oC), for DBRC Outdoor Units -

Water Pressure - Max 232PSI (16bar)

LOCATING THE UNIT AND INSTALLATION CLEARANCE Consult local building codes and the national electrical code for special installation requirements. During installation, respect the clearance required for air-flow, wiring, routine and major servicing and maintenance work. The unit may be set directly on top of a raised floor if the raised floor has sufficient load capacity. The unit should not be placed near any corner of the room or at the end of a long, narrow room. For best air distribution, the unit should be centered against the longest wall and as close to the load as possible.

The unit is designed for full front access with hinged and lock type full height doors. Therefore it allows flexible installation by grouping same or differing models and capacities to be installed side by side. No side and rear clearance is required. However, all the fixed panels can be externally removed by the special unit stopper system. This facilitates additional ease of field installation, service and maintenance on the system. Please refer to Removing Fixed Panels section on this manual.

Page 22: Dunham-Bush - DB Aire Installation Operation Manual

 

- 22 -

 

Notes: It is the responsibility of the installing contractor / engineer to check the re-assembled unit structure is correct for each system installation. The warranty clauses are no longer valid for any possible damage or malfunction that may occur due to improper re-assembly of unit and piping work installation.

Removing the Center Frame (model 07 to 26 only) 1. From unit external, remove the cap. 2. From unit internal, unscrew the nut and remove the bolt.

INSTALLATION All piping and wiring connections are designed from unit bottom. Proper openings should have already been cut on the raised floor by others. Minimum Unit Clearance

Model Unit Height H, mm (inch)

Unit Width W, mm (inch)

Unit Depth D,mm (inch)

A, mm (inch) (Recommended)

B, mm (inch)

C, mm (inch)

02 to 05 1944 (76.5)

749 (29.5) 874 (34.4)

Min 305 (12); Max 900 (35.5) Turning vanes is recommended for

downflow (by others) 800 (31.5)

610 (24) Standard Discharge Plenum Height 457

(18) (optional for Upflow Model only) 07 to 13 1464 (57.6) 14 to 26 2554 (100.6)

DISMANTLING UNIT FRAME The unit frame (center and side) can be dismantled. Thus the aluminium profiles can be pulled out. This offers the flexibility of the unit structure especially the unit is needed for site knocked down (SKD) due to site condition. Note that all fixed and access panels as well as the center frame (for model 07 to 26) must be removed prior to dismantle the unit frame. When this situation arises, it is recommended to inform factory upfront in order not to braze all piping joints. All joints, however, can be brazed at site by others.

Removing the Side Frame 1. Remove the first side M6 cap screw on nylon. 2. Remove the screw cover. 3. Remove the other two M6 screws. 4. Pull out the aluminium profiles.

1

3

3

4

Page 23: Dunham-Bush - DB Aire Installation Operation Manual

 

- 23 -

 

INSTALLATION REMOVING FIXED PANELS All fixed panels are externally installed onto the unit cabinet by using special stopper system without using screws. The stopper system facilitates the removable of panels for additional ease of field installation, service and maintenance on the system.

1. Remove the bottom stopper bar.

Gently tap the screw driver flat head into the mating surface between the nylon corner and the stopper bar. Then gradually pull the stopper bar out of its slot as shown.

2. Remove the top stopper bar. Repeat the steps as 1.

3. Remove the left or right side stopper bars respectively.

Repeat the steps as 1. After all four side stopper bars have been pulled out; remove the panel from the unit cabinet.

To reinstall back the fixed panel, reverse the steps. Locate the panel on the frame.

1

Stopper Bars Fixed Panel 

2

3

Note that the left and right side stopper bars have to be inserted prior to the top and bottom stopper bars.

3

Page 24: Dunham-Bush - DB Aire Installation Operation Manual

 

- 24 -

 

INSTALLATION REMOVING FILTERS All units are supplied together with air filters. Follow the below steps to withdraw the filters.

1.

2.

3.

Lift up the filter as shown until it touches filter rack (top).

Tilt the filter (bottom) as shown to allow it coming out from the filter rack and remove it from the unit.

One at a time, slide the other filters to the previous filter location. Follow the above steps to remove the filters from the unit.

Place in the new filters in reverse sequence of the above steps.

INSTALLING DISCHARGE PLENUM (OPTIONAL) Discharge plenum box is supplied separately which to be installed onto the unit by others at field. Follow the below steps to install the discharge plenum. 1.

2.

3.

Place and align the plenum on top of the unit as shown. Make sure the bottom face of the plenum (or top of the unit frame) is adhered with rubber gasket.

Remove the pre-installed tap-screws from the supply air grille. Take out the supply air grille.

Through the grille opening, fasten the plenum onto the unit using tapping screws on the pre-punched holes at all 4 sides. Place back the supply air grilles.

Filter

Fasten the plenum along 4 sides Screws

Page 25: Dunham-Bush - DB Aire Installation Operation Manual

 

- 25 -

 

INSTALLATION BELT TENSION INSPECTION GUIDE When installing or replacing belts, always use a complete set of new belts. Mixing old and new belts will result in the premature wear or breakage of the newer belts. Correct tensioning of V-belts drive is carried out as follows, 1. Fit the belts into the grooves and increase the centre distance until the belts are snug.

(Note: Never lever belts over sheaves) 2. Tighten belts and equalize belt slack so that it is on the same side of belt for all belts. Failure to do so may result

in uneven belt stretching. 3. As shown in figure, measure the span length (mm) of the drive. Determine the deflection at the centre of the

span according to the table below.

Belt Span (mm) Deflection (mm)

250-300 310-360 370-420

4 5 6

430-480 490-540 550-600

7 8 9

4. From table below, find the appropriate deflection force according to belt type. The deflection force for any V-belt should be within the minimum and maximum force shown in the table. When the tension drops to the minimum value, readjust to the maximum value.

Deflection Force (Kg)

Belt Type SPZ SPA SPB

Diam. Of smaller sheave (mm) Min. Max Min. Max Min. Max

63-80 1.2 1.9 - - - -

90-112 1.6 2.4 1.9 2.9 - -

125-160 1.9 2.8 2.6 4.0 3.3 5.0

180-224 1.9 2.9 3.0 4.6 4.3 6.4

250-355 - - 3.2 4.8 5.1 7.7

Note: A new drive should be tensioned to the higher value. After the drive has been running for 30 minutes, the tension should be checked and readjusted to higher value.

Page 26: Dunham-Bush - DB Aire Installation Operation Manual

 

- 26 -

 

INSTALLATION AIR-COOLED PIPING

Direct expansion (DX) system units are shipped pressurized with a nitrogen charge. Remote air-cooled condensers (DBRC) are shipped pressurized with a nitrogen charge.

The interconnecting lines to the remote air-cooled condenser must be installed by a qualified refrigeration mechanic. Prior to connecting the tubes, make sure to apply blind caps or water proof tape to prevent dust or water from getting into the tubes.

Max. Allowable Piping Equivalent Length Elevation Difference between Indoor and Outdoor Units

75 ft (22.9m) 30 ft (9.2m)

PIPE SUPPORTS The table below identifies the maximum distance between pipe supports on horizontal and vertical pipe runs. All pipework should be clamped prior to apply insulation. Clamping over insulation is not acceptable.

Pipe OD (inches) Support Distance (meter)

3/8” to 7/8” 1.0

1-1/8” to 2-1/8” 2.0

FIELD PROVIDED PIPING AND WIRING

1. The required copper pipe diameters for discharge hot gas and liquid lines are shown on Performance and Technical Data. Establish the shortest route for pipework from indoor unit to the outdoor condenser. Try to avoid unnecessary bends on piping as possible to minimize the total charge of refrigerant and the pressure drops. Lay the horizontal gas pipes with 1% downward gradient towards the refrigerant flow.

2. Reduce the number of bends which must be of large radius 3. The liquid line of the system must be insulated if passing through extremely warm places. 4. There must be a minimum separation of 20mm between the hot gas and liquid lines. If this is not possible

insulate both lines. 5. Oil traps are required to be located every 15 to 20ft (4.6 to 6.1m) on hot gas line riser to ensure proper oil

entrapment. 6. Support both horizontal and vertical pipes with vibration damping clamps which should include rubber gaskets.

Notes: Excessive refrigerant line length reduces system capacity and efficiency, as well as system reliability (excessive refrigerant charge). Keep refrigerant lines as short as conditions permit! The pipe sizes/ refrigerant charges quoted are for guidance only. It is the responsibility of the installing contractor/ engineer to check the pipe sizes/ refrigerant charges are correct for each system installation. Split systems may require additional oil which should be added to the low side of each compressor. Design should be in accordance with accepted refrigeration practice to ensure good oil return to the compressor(s) under all normal operating conditions.

Page 27: Dunham-Bush - DB Aire Installation Operation Manual

 

- 27 -

 

INSTALLATION LONG REFRIGERATION PIPING Long refrigeration piping system requires special consideration for the following concerns,

Oil return concerns Minimum pressure drop on liquid line rise Capacity losses Additional refrigerant charge

Outdoor Condenser above Indoor Unit

Outdoor Condenser below Indoor Unit (Liquid Line Vertical Rise)

For long discharge hot gas vertical riser, it is essential that oil separator (field supplied) must be installed in the system. Oil traps are also required to be located every 4m to ensure proper oil entrapment. In addition there should be an oil trap at the exit of the indoor unit before a vertical riser is applied.

Approximate discharge and liquid-line sizing up to 200 equivalent feet (61 meter) are shown in the table on next page.

Discharge check valves are recommended on long pipe runs or in cold climates (not on drawing).

The recommended pressure drop should be between 3 to 6 PSI. Minimum and maximum gas velocity for proper oil return should be 1000 FPM to 3000 FPM.

Careful pipework selection must be done if the liquid line rises. Additional subcooling may be required to prevent flash gas occurring in the liquid line due to excess pressure drop. Careful pipe sizing is recommended to ensure that the liquid line does not have excessive pressure drop. Increasing liquid line pipe size can minimize pipe pressure drop.

Approximate discharge and liquid-line sizing up to 200 equivalent feet (61 meter) are shown in the table on next page.

The recommended pressure drop should be between 2 to 4 PSI. Liquid-line velocity from the condenser to the expansion valve should be between 200 and 300 FPM.

Charging to a minimum of 10F (5.6C) subcooling is recommended to ensure a column of liquid is present at the TXV.

Notes: Excessive refrigerant line length reduces system capacity and efficiency, as well as system reliability (excessive refrigerant charge). Keep refrigerant lines as short as conditions permit! The pipe sizes / refrigerant charges quoted are for guidance only. It is the responsibility of the installing contractor / engineer to check the pipe sizes / refrigerant charges are correct for each system installation. Split systems may require additional oil which should be added to the low side of each compressor. Design should be in accordance with accepted refrigeration practice to ensure good oil return to the compressor(s) under all normal operating conditions.

Discharge Line Riser

Liquid Line

Discharge Line

Liquid Line Riser

Page 28: Dunham-Bush - DB Aire Installation Operation Manual

 

- 28 -

 

INSTALLATION Recommended Line Sizing Up To 200 Equivalent Feet (61 Meter) For Split Air Cooled Systems

MODEL 100 EQUIV FEET [31 METER] 150 EQUIV FEET [46 METER] 200 EQUIV FEET [61 METER]

HOT GAS LIQUID HOT GAS LIQUID HOT GAS LIQUID

02 3/4 [19.1] 1/2 [12.7] 3/4 [19.1] 1/2 [12.7] 3/4 [19.1] 1/2 [12.7]

03 3/4 [19.1] 1/2 [12.7] 3/4 [19.1] 1/2 [12.7] 3/4 [19.1] 1/2 [12.7]

04 3/4 [19.1] 5/8 [15.9] 7/8 [22.2] 5/8 [15.9] 7/8 [22.2] 5/8 [15.9]

05 7/8 [22.2] 5/8 [15.9] 7/8 [22.2] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9]

07 7/8 [22.2] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9]

09 1 1/8 [28.6] 7/8 [22.2] 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]

11 1 1/8 [28.6] 7/8 [22.2] 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]

13 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]

14 7/8 [22.2] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9]

16 7/8 [22.2] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9] 1 1/8 [28.6] 5/8 [15.9]

19 1 1/8 [28.6] 7/8 [22.2] 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]

22 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]

26 1 1/8 [28.6] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2] 1 3/8 [34.9] 7/8 [22.2]

Refrigerant Charge Guide The following table can be used to estimate the refrigerant charge quantity/circuit required in a typical split system installation.

Indoor Unit (Air-Cooled) lbs (kg) / circuit

DBA02 6.9 (3.1)

DBA03 7.2 (3.3)

DBA04 8.0 (3.6)

DBA05 8.2 (3.7)

DBA07 13.3 (6.1)

DBA09 17.0 (7.7)

DBA11 25.5 (11.6)

DBA13 27.9 (12.7)

DBA14 14.6 (6.6)

DBA16 14.6 (6.6)

DBA19 17.0 (7.7)

DBA22 25.5 (11.6)

DBA26 27.9 (12.7)

Additional Liquid Line Refrigerant Charge Guide

Liquid Line Pipe Size kg / meter

3/8” 0.05

1/2" 0.10

5/8” 0.15

3/4" 0.20

7/8” 0.30

1-1/8” 0.50

Page 29: Dunham-Bush - DB Aire Installation Operation Manual

 

- 29 -

 

INSTALLATION LEAK TEST (SYSTEM PRESSURE TEST) 1.) Leak test pressure is at 200psig [1380kPa]. Disconnect or shut off all devices which may be damaged by

200psig [1380 kPa] test pressure.

2.) Open all valves in system so that entire system can be pressurized and connect refrigerant cylinder to charging connection.

3.) Charge in freon vapor to the system until 50psig [345 kPa] and then pressurize with dry nitrogen until 200psig [1380 kPa]. Stop charging gas if noise of escaping gas is heard. Skip to step 6. Caution: Always use inert gas such as nitrogen for testing. Never use other gases such as Oxygen or acetylene which may be inflammable.

4.) With pressure at 200psig [1380kPa], shut off the valve connecting nitrogen cylinder to the system. Disconnect nitrogen cylinder and leave pressure gauge indicating 1380kPa connected to system.

5.) With halide torch or electronic leak detector, leak check every valve, joint, pressure control, coils and headers. Mark every leak and record down as remarks.

6.) When all leaks have been found, blow off charge through tube to outside to prevent refrigerant accumulation around the system.

7.) Repair all leaks (check off on your remarks): If rebrazing is required, feed nitrogen into the system at slightly excessive pressure (leave system open and make sure nitrogen flows through).

8.) After repairing leaks, re-check as per procedure 1 through 7.

9.) When system tight after leak test, keep pressurized at 200psig [1380kPa] and hold for 12 hours. Full in pressure should be negligible (some may be due to temperature change only.)

10.) When system is tight, proceed with vacuum test and dehydration. VACUUM TEST AND DEHYDRATION The purpose of evacuation is to evacuate the system when it is known or suspected that the system has been exposed to atmosphere, and there is a possibility that moisture has entered the system.

1.) Blow-off charge or pump down the refrigerant.

2.) Connect vacuum pump on the liquid line and carefully check the unit piping to ensure all passages are open. (NEVER USE SYSTEM COMPRESSOR TO EVACUATE).

3.) Start vacuum pump operation and pull vacuum to about 2 to 2.5mmHg [0.26 to 0.33 kPa] absolute pressure. During evacuation the pressure may remain steady for sometime at about 0.5” or 12mmHg [1.69 kPa] absolute pressure. This is caused by moisture evaporating in the system. This "boiling off" or "evaporation period" last about the same period of time as it took from initial start to reach this point.

4.) When the "boiling off" period lasts longer that indicated under 3, break vacuum with refrigerant or nitrogen gas to sweep moisture out and evacuate and dryer shells, etc., up to a temperature of 100°F [37.8°C].

5.) Break vacuum with refrigerant or nitrogen gas until pressure is 0psig [0 kPa].

6.) Re-evacuate to 1mmHg [0.133kPa] absolute pressure.

7.) Disconnect vacuum pump and leave system standing for 6 hours. There should be no change in vacuum during this period. If there is a change repeat 1 to 7.

CHARGING 1.) Connect refrigerant cylinder through charging connection to charging valve.

2.) Loosen flare nut on other end of charging connection and blow air out with refrigerant. Tighten flare nut on charging connection.

3.) Weight refrigerant cylinder.

4.) Open charging valve and charge in refrigerant vapor through suction access valve until about 150psig [1034 kPa]. Switch to liquid line access valve and charge in liquid refrigerant. Continue charging with liquid refrigerant until clear glass is observed.

5.) Shut off refrigerant charging valve but keep connected. Check charging valve flare nut for leak. Check and record down discharge and suction pressure. If more than one system to be charged, follow procedure 1 through 4 for each system. After all the systems have been done up to step 4, proceed with 5 and 6.

6.) Shut off the system (compressor, fans, pumps) and leave for 24 hours.

Page 30: Dunham-Bush - DB Aire Installation Operation Manual

 

- 30 -

 

INSTALLATION SYSTEM CHECK FOR OVERCHARGING Because system reliability depends on proper refrigerant charge, it is very important that the system is thoroughly checked for superheat and oil temperature after the unit has stabilized. A final check should be made after the room is stabilized and the unit is fully loaded. WATER CONNECTIONS Chilled Water Piping It will be necessary to install inlet and outlet pipes on unit with chilled water coils. The diameters of the pipes are indicated on the Performance and Technical Data. To ensure proper water circuits installation, it is recommend the following,

1. Use pipes made of copper or steel. Support pipes with suitable brackets. 2. Insulate all pipes with Armaflex type insulation. 3. Install shut-off valves to facilitate maintenance. 4. Install a thermometer on the inlet and outlet pipes. 5. Install a pressure gauge on the inlet and outlet pipes. 6. Install a drain outlet in the lowest part of the circuit.

Use a water or glycol solution where necessary.

Indoor Unit

Page 31: Dunham-Bush - DB Aire Installation Operation Manual

 

- 31 -

 

INSTALLATION HUMIDIFIER (OPTIONAL) General Steam humidifier is an optional item and it is installed and integrated within the function and method of operation of the unit. The humidifier produces non-pressurized steam by means of electrodes immersed in the water contained in the cylinder. The humidifier uses normal main water for the production of steam. The conductivity of the water should be within the range of 75 to 350 µS/cm. The steam is introduced into the airflow by means of distributor via steam hose installed in the unit. The humidifier is necessary to be connected a supply pipe.

Supply Connections The steam humidifier is installed and electrically connected in the unit. Initially the humidifier cylinder is empty. Ensure a water supply is available to the humidifier with the following characteristics,

Pressure between 1 and 8 bar (14.5 and 116psi) Temperature between 1 and 40oC

The water supply connection to the humidifier should have an internal diameter of at least ¼ inch (6mm). A waterline shutoff valve and mechanical filter must be installed (by others) outside the unit to trap any solid impurities and for future disconnection and service.

Replacing the Cylinder

To access the cylinder, Completely drain the water contained in the cylinder Turn the appliance off and open the main power disconnecting switch (safety procedure) Remove the steam hose from the cylinder Disconnect the electrical connections from the top of the cylinder Release the cylinder from the fastening device and lift it up to remove it Fit the new cylinder in the humidifier by performing the previous operations in reverse

Periodical Checks

After 1 hour of operation Check that there are no significant water leaks

Every 15 days or no more than 300 operating hours

Check that there are no significant water leaks and the general condition of the container. Check that during operation there are no arcs or sparks between the electrodes

Every 3 months or no more than 1000 operating hours

Check operation that there are no significant water leaks. If necessary replace the cylinder

Annually or no more than 2500 operating hours

Replace the cylinder

After extended use or alternatively when using water with a high salt content, the solid deposits that naturally form on the electrodes may reach the stage where they also stick to the inside wall of cylinder; in the event of especially conductive deposits, the consequent heat produced may overheat the plastic and melt it, and, in more severe case, puncture the cylinder. As a precaution, check, at the frequency recommended further on, the deposits and the blackening of the wall of the cylinder, and replace the cylinder if necessary.

1. Frame 2. Cylinder 3. Drain Solenoid Valve 4. Drain Connection 5. Supply Tank + Conductivity Meter 6. Cylinder Lock Strap 7. Fill Solenoid Valve 

Humidifier within Unit

Drain 

4 Filter 

Valve 

Supply 

Supply Connection (by others)

Steam Supply 

Warning: The cylinder may be hot. Allow it to cool before touching it or use protective gloves. 

Page 32: Dunham-Bush - DB Aire Installation Operation Manual

 

- 32 -

 

INSTALLATION OPERATION Humidification is provided by an electrode boiler. The sealed humidifier design ensures that only clean sterile steam is supplied to the conditioned area and corrosive salts and minerals are held in the disposable bottle. The humidifier features modulating capacity output control as standard. The system provides continuous modulation of steam output in response to a proportional control signal. The output control range is 20% to 100% of the humidifier rated value and is designed to give an approximate steam output of +/-5%, thus ensuring precise control of the conditioned space. The cylinder operating life time is automatically optimized via the integrated water conductivity sensor which combined with the Vision 2020i controller to monitor and regulate the water refill cycle to reduce excessive salt deposits and the progressive wear of the cylinder. All humidifier parameters and alarms are accessible and adjustable via the microprocessor display keypad unit. The main features include,

Supply water conductivity (μS/cm) Required steam output (kg/h) Actual steam output (kg/h) Required current rating (A) Actual current rating (A)

Status mode (Start Up, Running, Filling or Draining)

MODULATING HOT GAS REHEAT FOR DX SYSTEM Hot gas reheat system is an alternative to electric heating and is only available in the DX-System. The system exploits a part of the heat released to the condenser to reheat the cooled air after it has passed through the evaporator coil destined for the room being conditioned, thereby achieving a worthwhile energy saving. The system incorporates a hot gas reheat coil located downstream of the evaporator coil with modulating valve which is completely integrated to the unit’s microprocessor control. This method of reheating is far more efficient than existing electric heating as no further power input is required over the standard power requirement. For units with two refrigerant circuits, each circuit can operate independently, giving the unit the ultimate flexibility to satisfy space temperature and humidity control. Features and Benefits

When room temperature has reached its set point but room humidity is still above its set point, the hot gas reheat valve will start to modulate the amount of hot refrigerant gas passing through the reheat coil. Since the amount of hot refrigerant gas passing through the reheat coil is modulated, the system delivers only the amount of reheating that is required. Room condition is uniform and consistent because there will be no drastic swings in the supply air temperature and humidity that are inherent with electric heaters on/off staging control. Refrigerant piping, valves and reheat coil are all factory installed. Typical field connection of discharge line and liquid line between the condensing unit and the indoor unit is only required. Controls are factory configured and are adjustable at field to suite site’s requirement and application.

REMOTE AIR COOLED CONDENSER (DBRC)

Rigging Move the unit to the installation location using a crane or fork lift. Each fan section has heavy steel leg supports with lifting holes at the top. Do not lift with a choke sling around the unit. Spreader bars are recommended for lifting multiple fan units. Under no circumstances should the coil headers or piping be used for lifting or moving the unit.

Leg Assembly The legs must be unbolted from the shipping position and extended prior to placing the unit on its pad. Each leg extends down approximately 18 inches [457mm] and reattaches using the same bolts.

Heat Exchanger Piping Connections The inlet connection is located on the top header on all units. The outlet connection is located on the bottom header of all units.

Locating the Unit: In installing the condensing units, considerations should be given to the following, 1.) Installed outside the building or ensure sufficient air to the condenser. 2.) Strong foundation to withstand the unit's weight and vibration. If the base was not leveled, use concrete blocks

as base 3.) Sufficient space for wiring and maintenance as per local legislation. 4.) Location where there is no direct heat source such as near a generator. This is because if the entering air

temperature is high, then the unit will operate at high condensing temperature and subsequently trip on high pressure (during cooling mode).

5.) Location where the unit is not exposed to oily area, salty atmosphere, and sulphide gaseous area. Note: Condenser fans are of the propeller type and not suitable for use with ductwork. The remote heat exchangers must be located in an area that will ensure free air flow into and out of the unit. The unit should not be placed closer than 36 inches [914mm] from any wall or other obstruction. When two or more units are used in the same area, space them apart by a minimum of 48 inches [1219mm].

Page 33: Dunham-Bush - DB Aire Installation Operation Manual

 

- 33 -

 

36 inches (914mm)

36 inches (914mm)

36 inches (914mm)

36 inches (914mm)

36 in

ches

(9

14m

m)

36 in

ches

(9

14m

m)

118

inch

es

(300

0mm

)

INSTALLATION DIMENSIONAL CLEARANCE - REMOTE AIR COOLED CONDENSER (DBRC) (A) Vertical Installation (Recommended) (B) Horizontal Installation

If remote condenser unit should be installed horizontally, additional brackets or supports (where necessary) must be provided to ensure rigid installation by others at field.

Locate the units where air is allowed to circulate. If installing two units together, make sure that the discharge air from one unit were not circuited by the other unit. See figure.

118 inches (3000mm)

36 in

ches

(9

14m

m)

36 in

ches

(9

14m

m)

Page 34: Dunham-Bush - DB Aire Installation Operation Manual

 

- 34 -

 

DBG5 4.3” Color Touch Screen Display

OPERATION ELECTRICAL CONNECTIONS IMPORTANT: Before proceeding with the electrical connections, make certain that the volts, hertz, and phase correspond to that specified on the unit rating plate. Also, check to be sure that the service provided by the utility is sufficient to handle the additional load imposed by this equipment. Refer to the unit rating plate for equipment electrical requirements. The attached typical wiring diagrams show the proper field high and low voltage wiring. Make all electrical connections in accordance with national electrical code and any applicable local code ordinances. Use copper conductors only. WARNING: The unit cabinet must have an uninterrupted electrical ground. An electrical ground wire of adequate size must be connected to the ground lug provided inside the control box. A ground wire is mandatory with microprocessor controls. Supply voltage at the unit must be within 10% of the voltage indicated on the nameplate. Phase-to-phase imbalance must not exceed 3%. Local utility company should be contacted for correction of improper line voltage. Improper electrical power supply may cause premature failures, which will void unit warranties. The computer-room unit and the condenser unit require individual power sources. For auxiliary-equipment control wiring, such as for the remote condenser, bring NEC Class-2 wires to the control box and connect to the terminals indicated on the unit wiring diagram. Wiring terminal numbers will typically be the same in the computer-room unit and the remote heat exchanger. Verify terminal numbers on unit and heat exchanger wiring diagrams before connecting wiring. Verify that properly sized fuses or circuit breakers are installed in the remote-mounted disconnect switch. Fuse size and minimum circuit ampere are listed on the unit nameplate. Check the wiring connections in the unit control panel to ensure that they are tight. Wiring connections may become loose in transit. CHECK FOR CORRECT PHASING The equipment should now be checked for correct phasing through the keypad. Switch the blower manual override to the “ON”, then back to “OFF”, or remove fuses from compressor high voltage circuit and push the “ON/OFF” button located on the front panel. A short start delay will take place as indicated on the screen. The blower motor will start, and it will be possible to determine blower rotation. Compressors, heaters and humidifiers are not affected by phasing. Disconnect power from the unit and reverse two of the three power wires to change rotation. UNDER-FLOOR WATER-DETECTION PROBE (OPTIONAL) This control panel includes a condensate probe, which must be mounted below the unit against the floor area where water may collect. Place it below the unit. ALARM PROCESSOR VISION 2020i Controller

Microprocessor based controller 32 Bit, 44 MHz CPU. Built-in flash memory ( 2 + 2MB ). Non-volatile storage of program & parameters on EEPROM &

Flash Memory. Built-in clock with battery as standard. Add-on communication protocol cards for various supervisory

communications. Touch Screen Display With Led Backlight The unit comes together with a 4.3” Color Touch Screen Display Panel. Graphical screen resolution is 480 X 272 pixels with 65k colors. The screen also has a LED backlight with adjustable brightness control. Display panel is built-in with flash memory 128MB and DDR2 RAM of 256MB with Microsoft Windows CE 6.0 operating system. The monitor displays temperature, humidity, all set points, cooling, humidification, dehumidification, heaters, percentage of chilled-water capacity (valve opening), percentage of cooling capacity (compressors and energy saver), percentage of heating and humidification capacities, average percentage of all capacities for last hour of operation, component run times, alarm history, diagnostics and all alarms listed in alarm section. Manual override of blower, cooling 1, cooling 2, heating 1, heating 2, heating 3, humidification and remote alarm operated via display. Control Switches Touch-button on/off, Touch-button menu, Touch-button alarm silence/program set (See figure above).

Page 35: Dunham-Bush - DB Aire Installation Operation Manual

 

- 35 -

 

OPERATION Standard Alarms High temp, low temp, high humid, low humid, manual override, under floor water detection, no air flow, dirty filters, humidifier failure, low-voltage warning, fire stat, compressor short cycle, power failure restart, humidity-sensor failure, temperature-sensor failure, maintenance required based on programmed run time, high pressure, low pressure, no water flow, smoke alarm, main fan motor overload. On energy-saver units, one programmable local alarm input (#3) is to be used to change from compressor operation to chilled-water operation. Display will switch to energy saver with percentage of valve-opening display on screen. On units with compressors, option input (#1) is used for a high-pressure alarm.

Software Software has menu-driven programming. Password is required. Opening of unit door not required for the following: Temperature set point, temperature dead band, temperature high and low alarm points, temperature sensor calibration, time delay between stages (sequential load activation), unit-start time delay, set tone of alarm buzzer, set DC voltage range for control valve, set hours of operation until appearance of maintenance-required alarm message, set power-failure restart method. Factory settings include periodic chilled-water or energy-saver coil flush, low-voltage dropout point 90%, predictive humidity control, temperature anticipation, automatic lead-lag rotation of compressors and reheat.

Data Collection The microprocessor will log data for the following items: Run times of fan motor, cool 1, cool 2, heat 1, heat 2, heat 3, humidification, dehumidification, chilled-water operation and energy-saver operation. Temperature, humidity and capacity readings will be taken every three minutes and recorded on the unit data base for the past 24 hours. An alarm data base will be maintained for the last 10 alarms and the time since occurrence. All data may be displayed at the unit without any additional equipment.

Communications The unit can communicate over an RS 485 network using a twisted pair of wires in a token ring loop. All data may be transmitted to and displayed at an optional remote-mounted DB-Aire Network. Optional RS 485 or 232 card can be fu-fitted for modem or MODBUS communication protocol.

Diagnostics All electronic circuitry contains built-in diagnostics. No additional external devices are required. Automatic self-diagnostics shall take place when power is applied to the unit. Manual diagnostics will be available with self-prompting instruction displays.

CONTROL LOGIC

Compressor Cooling Logic 1. Maximum frequency of primary compressor starts = 5 minutes start of same stage 2. Primary compressor stage minimum time off = 2 minutes stop to start of same stage 3. Secondary un-loader stage minimum time off = 1 minute stop to start of same stage 4. Compressor staging sequence at each adjustment period:

C1 On at temp set point + temp dead band C2 On at temp set point + temp dead band + 0.3°F C2 Off at temperature set point + temperature dead band C1 Off at temperature set point

Heat Strip Heating Logic 1. Minimum time between heat stage turn on = 1 minute stop to start of same stage or start to start of different

stages. 2. Heat staging sequence:

H1 on at temperature set point -Temperature dead band - 0.3°F H2 on at temperature set point - Temperature dead band - 0.6°F H3 on at temperature set point - Temperature dead band - 0.9°F H3 off at temperature set point - Temperature dead band - 0.6°F H2 off at temperature set point - Temperature dead band - 0.3°F H1 off at temperature set point - Temperature dead band

Humidification Logic 1. All heat Off immediately during humidification 2. Minimum time stop to start = 1 minute 3. Minimum time between humidification / dehumidification changeover = 5 minutes 4. Humidification staging sequence:

H1 on at humidity set point - humidity dead band H1 off at humidity set point - 1%

Page 36: Dunham-Bush - DB Aire Installation Operation Manual

 

- 36 -

 

OPERATION Dehumidification Logic 1. Dehumidification is not governed by the adjustment rate but will not violate compressor short-cycle times. 2. Heating stages are used to reheat the over-cooled but dehumidified air and heating short-cycle time will not be

violated 3. Five minute minimum between humidification and dehumidification cycles 4. One minute minimum between stop to start of dehumidification 5. Dehumidification staging sequence: Energy-saver or chilled-water cooling proportionally increase or

decrease as required, up to maximum valve opening if available. Compressoring units C1 On at humidity set point + humidity dead band C2 On at humidity set point + humidity dead band + 1% C2 Off at humidity set point + humidity dead band C1 Off at humidity set point

Energy-Saver Cooling Logic 1. Energy saver function is always used any time programmable alarm point #3 has been set for energy - saver

operation and is powered. 2. Compressors will not be used with energy saver to hold set point. 3. Energy-saver staging sequence: Water valve is On at temperature set point + temperature dead band. Water valve modulates every 60 seconds to maintain set point. Water valve is Off at temperature set point Chilled-Water Cooling Logic Chilled-water staging sequence: water valve is on at temperature set point + temperature dead band. Water valve modulates every 60 seconds to maintain set point. Water valve is off at temperature set point. Automatic, Periodic Coil-Flush Logic Control will automatically flush chilled water or energy-saver coil and reheat coils. Control valves open 25% every 100 hours of operation for a period of 30 seconds. Humidity Anticipation Logic Control will automatically modify humidity set point to stop unnecessary humidification and dehumidification. Humidity set point is modified based on return air temperature. This prevents humidification and dehumidification if not required based on changing temperature to 70°F. Manual Override Logic Any manual override function will cause all automatic temperature and humidity control by the processor to be discontinued. This will allow installers to easily run each function during start-up. Temperature And Humidity Sensor Failure Logic 1. A temperature-sensor failure will cause the processor to activate all stages of cooling if the unit is operating at the

time of failure. If self-test finds a bad sensor on start-up, the unit will not be allowed to start. 2. A humidity-sensor failure will cause the processor to discontinue all humidification and dehumidification control if

the unit is operating at the time of failure. If self-test finds a bad sensor on start-up, the unit will not be allowed to start.

Compressor Short-Cycle Alarm Logic If the compressor has started 10 times within the last hour, the alarm sounds. The minimum time between primary compressor starts automatically increases from 5 to 6 minutes for the next hour of operation. Power-Failure Restart Alarm Logic Unit restarts based on program selection. No Air Flow Alarm Logic A no air flow alarm will prevent unit operation of cool, heat, humidification or dehumidification, for unit to operate, microprocessor must have proven air flow. Program Selections Operate from front panel with door closed. After 60 seconds without an input, display will return to normal.

Page 37: Dunham-Bush - DB Aire Installation Operation Manual

 

- 37 -

 

OPERATION PIPING SCHEMATIC (A) DX/ Dual Coil System Only (I) Model 02 - 13 (Single Compressor)

(II) Model 14 - 26 (Dual Compressors)

Page 38: Dunham-Bush - DB Aire Installation Operation Manual

 

- 38 -

 

OPERATION (B) DX/ Dual Coil System With EEV (I) Model 02 - 13 (Single Compressor)

(II) Model 14 - 26 (Dual Compressors)

Page 39: Dunham-Bush - DB Aire Installation Operation Manual

 

- 39 -

 

OPERATION (C) DX System With Hot Gas Reheat (I) Model 02 - 13 (Single Compressor)

(II) Model 14 - 26 (Dual Compressors)

Page 40: Dunham-Bush - DB Aire Installation Operation Manual

 

- 40 -

 

MAINTENANCE INSTRUCTIONS MAINTENANCE These units are designed to provide years of services with minimum maintenance. Nonetheless, it is a good practice to carry out regular inspection and checking to ensure the unit's optimum performance.

ITEM MAINTENANCE PROCEDURE RECOMMENDED SCHEDULE

Air Filters

1. Disposable type. 2. The filters should be checked and changed

periodically. When they become dirty, an alarm is activated by the clogged filter switch. If the filters are dirty, they must be changed for efficient operation of the system.

3. To check the alarm indicator, cover approximately 75% of the return air opening; the alarm should energize. If the alarm energizes prematurely or does not energize when it should, adjust the filter switch.

4. All doors to machine should remain closed before determining whether an adjustment is necessary.

Spare filters should be kept in stock. Filters should be checked and replaced monthly or depending upon the condition of the circulated air

Belt

1. Belt tension should be checked every month to assure proper, efficient operation.

2. If retensioning is needed, slightly loosen the four motor-mounting bolts. Turn the adjusting screw (located in the end of the motor mounting channel) until the belt is properly adjusted.

3. Retighten the four mounting bolts.

Every months.

Pulley 1. Make sure the set screws are properly tightened and there is no crack on the pulley. Once every six months.

Blower 1. Turn the blower manually. It should run smoothly and there is no excessive bearing noise. Once every six months.

Bearing and Shaft 1. Check for evidence of wear. Once a year.

Bolts, Screws and Nuts.

1. Tighten any loose components. Once a year.

Coil 1. Check and remove clogged item between fins. Once a year.

Paint 1. Check any evidence of corrosion. Once a year.

Compressor 1. Check if there is any leakage. Every six months.

Electrical 1. Check voltage, current and wiring. 2. Check connections.

Every two months.

Heating Elements 1. The heating elements are finned type and require no maintenance. -

Humidifier 1. Replacement of the humidifier cylinder. See humidifier section or

humidifier manufacturer’s manual for details.

Drain Pan and Pipe 1. Pour some water into the drain pan and let the water run through. If the pipe is clogged, remove the dirt. Every six months.

Piping

1. Inspect all piping for leaks and clearance. 2. Piping must be properly supported and must not be

allowed to vibrate or rub against other pipes or structures.

Every six months.

Glycol

1. Check glycol concentration and inhibiter level. 2. Inhibiter level prevents corrosion and percent of

glycol concentration prevents freezing. 3. Contact a local water-treatment company in the area

for recommendations based on local water conditions.

Every six months.

Page 41: Dunham-Bush - DB Aire Installation Operation Manual

 

- 41 -

 

MAINTENANCE INSTRUCTIONS TROUBLESHOOTING CHART

Page 42: Dunham-Bush - DB Aire Installation Operation Manual

 

- 42 -

 

MAINTENANCE INSTRUCTIONS

Page 43: Dunham-Bush - DB Aire Installation Operation Manual

 

- 43 -

 

MAINTENANCE INSTRUCTIONS SAMPLE LOG SHEET SHEET NO. ..........................

DUNHAM-BUSH PRECISION AIR-COND UNIT UNIT MODEL NO. ........................................................ UNIT NO. .................................... VOLTS: ........................ Hz.....................

UNIT SERIAL NO. .....................................................................................................................

START UP : DATE .......................................... TIME ....................................................

DATE

TIME

COMP. NO.

SUCTION PRESSURE

1.

2.

3.

4.

SUCTION TEMPERATURE

1.

2.

3.

4.

DISCHARGE PRESSURE

1.

2.

3.

4.

DISCHARGE TEMPERATURE

1.

2.

3.

4.

DISCHARGE SUPERHEAT (DISC. TEMP.-SAT. DISCH.)

1.

2.

3.

4.

SUCTION SUPERHEAT (SAT. SUCT .- SUC. TEMP)

1.

2.

3.

4.

RETURN AIR TEMPERATURE – DB/WB

SUPPLY AIR TEMPERATURE – DB/WB

AIR VOLUME

AMBIENT AIR TEMPERATURE

OFF CONDENSER AIR TEMPERATURE

COMPRESSOR AMPS

1.

2.

3.

4.

CONDENSER FAN AMPS

EVAPORATOR FAN AMPS

VOLTS

This log sheet is provided as a recommendation of the readings that should be taken on a periodic basis. The actual readings taken and the frequency will depend upon the units application, hours of use, etc. This type of information can prove very useful in preventing and/ or solving problems that might occur during the life of the unit.

Page 44: Dunham-Bush - DB Aire Installation Operation Manual

 

- 44 -

 

GUIDE SPECIFICATIONS This specification describes requirements for precision air conditioning system. The system shall be designed to maintain precised temperature and humidity conditions for applications such as computer server rooms, telecommunication facilities, clean rooms, laboratories, etc. The precision environmental control system shall be factory assembled, DB-Aire II model vertical floor mounted by Dunham-Bush Industries, Malaysia. DESIGN REQUIREMENTS (A) Direct Expansion (DX) System

The system shall have a total cooling capacity of _____MBH /_____kW and a sensible cooling capacity of _____MBH /_____kW based on an entering air temperature of _____oF /_____oC DB and _____ oF /_____oC WB.

The system shall be designed based on _____oF /_____oC DB ambient temperature. For low ambient application, the system shall also be designed to operate at _____oF/_____oC DB ambient temperature.

The unit shall be supplied with _____/_____/_____(Volt/Phase/Hz) electrical service.

The unit shall be of Upflow / Downflow configured model.

(B) Chilled Water (CW) System

The system shall have a total cooling capacity of _____MBH /_____kW and a sensible cooling capacity of _____MBH /_____kW based on an entering air temperature of _____oF /_____oC DB and _____ oF /_____oC WB.

The system shall be supplied with chilled water with an entering water temperature of _____oF / _____oC and leaving water temperature _____oF /_____oC.

The unit shall be supplied with _____/_____/_____ (Volt/Phase/Hz) electrical service.

The unit shall be of Upflow / Downflow configured model.

(C) Dual Coils (DX + CW) System

The system shall have a total cooling capacity of ______MBH /______kW and a sensible cooling capacity of _____MBH /_____kW based on an entering air temperature of _____°F /_____°C DB and _____°F /_____°C WB.

The DX system shall be designed based on _____°F /_____°C DB ambient temperature. For

low ambient application, the system shall also be designed to operate at _____°F/_____°C DB ambient temperature.

The CW system shall be supplied with chilled water with an entering water temperature of ______°F/______°C and leaving water temperature _____°F / _____°C.

The unit shall be supplied with _____/_____/______ (Volt/Phase/Hz) electrical service.

The unit shall be of Upflow / Downflow configured model.

(D) Direct Expansion (DX) System with hot gas

reheat

The system shall have a total cooling capacity of ______MBH /______kW and a sensible cooling capacity of ______MBH /_____kW based on an entering air temperature of _____oF /_____oC DB and ______ oF /_____oC WB.

The system shall be designed based on _____oF /_____oC DB ambient temperature. For low ambient application, the system shall also be designed to operate at ______oF/______oC DB ambient temperature.

The unit shall be supplied with _____/_____/_____ (Volt/Phase/Hz) electrical service.

The unit shall be of Upflow / Downflow configured model.

1 STANDARD FEATURES (ALL SYSTEMS,

INDOOR UNIT)

1.1 Cabinet The cabinet comprises an anodized aluminium frame of epoxy powder coated black color paint with nylon corners and removable steel sheet panels. All panels shall be externally installed onto the cabinet by using special stopper system without using screws. The stopper system shall also facilitate the removable of panels for additional ease of field installation, service and maintenance on the system. All panels and access doors shall be fabricated from sturdy heavy gauge of 1.0mm steel sheets with epoxy powder coated oven baked black color paint to provide a durable finish. All panels shall be of 25mm (1 inch) thick single skin and lined with minimum 2lbs/ft3 density thermal and acoustical fiberglass insulation with fire resistant of Class O (BS 476 Part 6, 7). The system shall be designed for front access only with hinged and lock type full height doors.

Page 45: Dunham-Bush - DB Aire Installation Operation Manual

 

- 45 -

 

GUIDE SPECIFICATIONS 1.2 Filters

The system shall be provided with 2 inches (50mm) deep (for model 02-05) or 4 inches (100mm) deep (for model 07-26) extended surface pleated disposable type filters rated for MERV8 efficiency to ASHRAE 52.2 standard (equivalent to EU4). Filters shall be withdrawable from the front of the unit.

1.3 Blower Assembly Blowers shall be belt driven double-inlet-double-width (DIDW), statically and dynamically balanced with multiple forward curved blades mounted on a solid steel keyed shaft. Heavy-duty V-belt fan drive (sized for 200% safety factor) with cast iron pulleys keyed and secured to the blower shaft shall be provided.

1.4 Motor Assembly Motors shall be of totally enclosed fan cooled (TEFC) with IP55 enclosure rating. Motors shall be mounted to an adjustable motor frame. Motor pulleys shall be cast iron, keyed and secured to the motor shaft.

1.5 Evaporator Air Discharge

1.5.1 Up-Flow (Front Free Return) The system shall be configured for up-flow pattern with front free evaporator return air and top evaporator air discharge. The system shall be supplied with grilles on the cabinet doors for front return air configuration. Up-flow systems are available with optional Discharge Plenum.

1.5.2 Down-Flow (Top Free or Ducted Return) The system shall be configured for down-flow pattern with top free or ducted evaporator return air and bottom evaporator air discharge through the raised floor.

1.6 Electric Reheat or Hot Gas Reheat

1.6.1 For Direct Expansion (DX) System, Chilled Water (CW) System and Dual Coils (DX+CW) System only. The electric reheat shall be factory installed low watt density finned-tubular nickel plated element heater with overheat safety controls. The electric reheat shall be of three equal stages giving a more accurate controlled response to the room requirement.

1.6.2 For Direct Expansion (DX) System with Hot Gas Reheat only The unit shall incorporate a hot gas reheat

coil located downstream of the evaporator coil with modulating valve which is completely integrated to the unit’s microprocessor control. For units with two refrigerant circuits, each circuit shall operate independently with its own modulating valve.

1.7 Electrical Circuits

The system shall be provided with a factory installed electrical enclosure as per local code requirements. Control voltage of the system shall be 24Vac. The fan motor(s), compressor(s), electric heaters, humidifier (if applicable) shall have their own circuit breaker and contactor. The electrical circuit shall have provision for user to cut off control power during fire / emergency shutdown

1.8 Control System – Vision 2020i Controller

1.8.1 Controller and display

The unit shall be provided with Vision 2020i control system with the following features,

The control algorithm and parameters shall be stored in flash memory and E2PROM of the controller and shall retain even in the event of power failures, without requiring a backup battery 4.3” graphical touch terminal with 65k color display Built in memory for data logging Temperature and humidity controlled Configurable by user Alarm status/display Analog input/output display Digital input/output status Remote start/stop input Digital input for customer input alarm General alarm output (dry contact) Self-diagnostics Security password access with multiple access level for advanced settings Unit status display with following information: • Current room temperature and

temperature setpoint • Current room relative humidity and

relative humidity setpoint • System ON/OFF • Operating mode (cooling/ heating/

humidifying/ dehumidifying)

Page 46: Dunham-Bush - DB Aire Installation Operation Manual

 

- 46 -

 

GUIDE SPECIFICATIONS

1.8.2 Alarm Monitoring When the system is in alarm condition, the system shall activate an audible buzzer and visual alarm message on the terminal display. A digital output (dry contact) shall be closed to indicate the alarm condition. The following alarm conditions shall be monitored by the controller:

High room temperature Low room temperature High supply air temperature High room humidity Low room humidity No air flow/loss of air flow Filter dirty Sensor failure Evaporator fan overload alarm Customer interlock alarm Unit/ Compressor running hours threshold exceeded LAN network disconnected alarm High/Low refrigerant pressure alarm (DX models) Chilled water flow switch alarm (chilled water models) Humidity Alarms Under floor water detector alarm (optional) Smoke detector alarm (optional)

1.8.3 Master-Slave Sequencing Control When more than one unit is present in the system, master-slave or duty-standby control of this group of units shall be done by just connecting controller of each unit in serial and require no additional controller.

1.8.4 BMS communications and remote monitoring ModBus RTU RS485 communication port shall be a standard feature of the controller. On top of that, the following options shall be available for BMS communications and remote monitoring:

ModBus TCPIP BACnet TCPIP / PTP / MSTP LONworks GSM Modem SNMP

2 DIRECT EXPANSION (DX) SPLIT SYSTEMS WITH REMOTE OUTDOOR AIR COOLED CONDENSER (DBRC MODELS)

2.1 Scroll Compressor

Compressor shall be mounted on the base via vibration isolators. Compressor shall be charged with polyolester oil and designed for use with R407C refrigerant.

2.2 Refrigeration Circuits The refrigeration system shall be of the direct expansion type with one (Model 02-13) or two (Model 14-26) hermetic scroll compressors complete with rotalock connections. All refrigeration circuit shall be pre-piped with copper tubing and include expansion valve with external equalizer, filter dryer, sight glass, refrigerant service valves, pressure fittings of manual reset high pressure control/auto reset low pressure safety cutouts and charging/access ports in each circuit.

2.3 Evaporator Coil The evaporator coil shall be of draw through air design for uniform air distribution. The evaporator coil shall be quality construction of seamless copper tube, mechanically bonded to hydrophilic aluminium fins with galvanized coil plates. The coil shall be factory leak and pressure tested to 450psig (31 bar) and the refrigeration system shall be sealed prior to shipment. A galvanized and painted drain pan shall be provided to cover the entire coil area. The drain pan shall be designed to incorporate sloped gutter for complete condensate removal.

2.4 Remote Outdoor Air Cooled Condenser (DBRC Models) The remote condenser shall be constructed from sturdy heavy gauge steel sheets with epoxy powder coated oven baked, factory standard beige color to provide a durable finish.

The remote condenser shall include direct driven propeller fans, condenser coil, fan guard, thermally protected rated IP55 motors, integral factory wired and tested control panel. The condenser coil shall be quality construction of seamless copper tube, mechanically bonded to aluminium fins with galvanized coil plates. The coil shall be factory leak and pressure tested to 450psig (31 bar) and the refrigeration system shall be sealed prior to shipment.

The evaporator and condenser sections shall ship with a dry-nitrogen holding charge ready for field refrigerant charging.

Page 47: Dunham-Bush - DB Aire Installation Operation Manual

 

- 47 -

 

GUIDE SPECIFICATIONS 3 CHILLED WATER (CW) SYSTEMS

3.1 Chilled Water Coil

The evaporator coil shall be of draw through air design for uniform air distribution. The chilled water coil shall be quality construction of seamless copper tube, mechanically bonded to hydrophilic aluminium fins with galvanized coil plates. The coil shall be factory leak and pressure tested to 450psig (31 bar) and sealed prior to shipment. Copper pipe for brazed connection shall be provided as standard. A galvanized and painted drain pan shall be provided to cover the entire coil area. The drain pan shall be designed to incorporate sloped gutter for complete condensate removal.

3.2 Chilled Water Control

The water circuit shall include 3-way forged brass valve and modulating actuators. The microprocessor positions the valve in response to room condition. Cooling capacity shall be controlled by bypassing chilled water around the coil.

4 OPTIONS 4.1 Stainless Steel Drain Pan

A stainless steel condensate drain pan shall be provided for the evaporator/chilled water coil in lieu of standard galvanized and painted drain pan.

4.2 Discharge Plenum (Up-flow Units only)

A discharge plenum box shall be provided for field installation on the top of the up-flow unit. The plenum box shall be 18 inches (457mm) high, insulated and painted to match the color of the indoor unit. The plenum box shall be fitted with double deflection grilles for room discharge of conditioned air.

4.3 Steam Generating Humidifier

Humidifier shall be factory installed inside the unit. The humidification system shall be an electrode cylinder type, complete with fill valve, drain valve, adjustable humidity output and automatic flush cycle activated on demand from the microprocessor control system.

4.4 Hot Gas Bypass (DX Systems only)

The refrigerant circuit(s) shall be provided with a hot gas bypass system for evaporator freeze-protection and capacity modulation during low load conditions.

4.5 Liquid Line Solenoid Valve (DX Systems only)

A factory fitted liquid line solenoid valve shall be provided for each refrigeration circuit as an option.

4.6 Double Skin Panels All panels shall be provided with galvanized internal skin.

4.7 Insulflex Closed Cell Insulation

All panels shall be single skin and lined with Insulflex Closed Celled insulation (in lieu of fiberglass insulation) with fire resistant of Class O (BS476 Part 6) and Class 1 (BS476 Part 7).

4.8 Hydrophilic or Copper Fin for Condenser Coil

(DBRC) Condenser coils shall be provided with hydrophilic or copper fins in lieu of aluminium.

4.9 Black Color Epoxy Powder Coating for

Remote Condenser (DBRC) The remoter condenser DBRC shall be epoxy powder coated oven baked black color paint in lieu of standard beige color.

4.10 Under Floor Water Detector

A remote water leak detector shall be factory provided for field installation. When water leak is detected, cooling mode of the unit is off.

4.11 Smoke Detector

A smoke detector shall be factory supplied at unit’s evaporator return air section. The unit shall shut down when smoke alarm is triggered.

4.12 Variable Frequency Drive (VFD) for Evaporator

Blower Motor A variable frequency drive (VFD) for blower motor shall be factory installed to vary the blower motor speed based on room’s requirement.

4.13 BMS communication cards

BMS communication card shall be factory installed to enable high level interfacing with BMS system. ModBus, BACnet, LONworks, SNMP communication protocols shall be available as option.

4.14 Electronic Expansion Valve (EEV) for

Evaporator Coil The refrigerant circuit(s) shall be provided with an Electronic Expansion Valve (EEV) for evaporator in lieu of standard Thermal Expansion Valve (TXV) to allow an efficient modulation control of refrigeration and consistent energy saving performances.

Page 48: Dunham-Bush - DB Aire Installation Operation Manual

Corporate Head OfficeDUNHAM-BUSH HOLDING BHD

(Formerly known as Dunham-Bush (Malaysia) Bhd) (129358-X)

Lot 5755-6, Kidamai Industrial Park, Bukit Angkat43000 Kajang, Selangor Darul Ehsan, Malaysia.

Tel: 603-8924 9000 Fax: 603-8739 5020E-Mail: [email protected]

www.dunham-bush.com

Manufacturer reserves the right to change specifications w

ithout prior notice. 7001170303