fermacell special - fire protection with cross laminated timber

16
fermacell special Last updated November 2014 Fire protection with cross laminated timber (CLT)

Upload: dinhkhanh

Post on 12-Feb-2017

228 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: fermacell special - Fire protection with cross laminated timber

fermacell special

Last updated November 2014

Fire protection with cross laminated timber (CLT)

Page 2: fermacell special - Fire protection with cross laminated timber

fermacell at a glanceProducts and solutions

Last updated March 2014

2

1 Jointing 3 Joint design 3

2 Wall 4-11 3 H 12 CLT fermacell Gypsum Fibreboard Wall Lining 4-5 3 H 11 H2O CLT fermacell Powerpanel H2O Wall Lining 6-7 3 H 21 A1 CLT fermacell Firepanel A1 Wall Lining 8-9 3 H 31 A1 CLT fermacell Firepanel A1 Wall Lining 10-11

3 Ceiling 12 2 S 11 fermacell suspended ceiling (fire rated) 12-13 4 K-Class system 14 Fire Strategy 15

Table of contents

Additional information

Website:n www.fermacell.com

Brochure:n fermacell at a glance

Project Eurban Limited – 33 Waterson Street, London

Page 3: fermacell special - Fire protection with cross laminated timber

3

1 Jointing

Note:

Dry butt joints for fire

rated linings are possible

if there are no require-

ments for the surface

finish. Butt joints will be

visible in some finishes.

The installation needs to

follow the instruction as

per approval.

Joint design

Gypsum Fibreboardn fermacell Gypsum Fibreboardn fermacell Firepanel A1

Joint designThere are different options for the jointing of Gypsum Fibreboards. Some specific rules must be followed for fire rated linings. The following details show the different joint options available for fermacell Gypsum Fibreboards or fermacell Firepanels A1.

It is important to choose the appropriate joint design early on in the design process. The following joint options are suitable for fire rated linings.

Dry butt joint – Gap ≤ 1mm fermacell Joint Filler1) – Joint width ½ × panel thickness + max. 3 mm

fermacell Glued Joint1) – Joint width ≤ 1 mm

fermacell Tapered Edge Board1) – fermacell Jointing Tape and fermacell Joint Filler

1) The differential movement of the material must be considered if the Fermacell boards are fixed directly on to the CLT. Joints can open up due to the differential movement of the substrate. This must be specially considered if a wet screed system is being installed or heaters are used for the drying out process.

Page 4: fermacell special - Fire protection with cross laminated timber

4

3 H 12 CLT fermacell Gypsum Fibreboard Wall Lining

A high performance dry lining system with fermacell Gypsum Fibreboards. This is a wall lining system which is used to protect the CLT structure against fire. It also provides a high level of sound insulation.

Material

Material class (EN 13501-1)n A2 s1 d0

Material (regulations/standards)n ETA-03/0050n EN 15283-2

Element

Fire Protection (CR: K-3401/3686-MPA BS)n EI 30

Insulation n not required

Thickness n 46.5 + x + 46.5 mm

Weight n ≈ 2 × 28 kg/m² (without CLT)

Acoustic n ∆Rw ≥ 56 dB incl. glass wool

BenefitsTypical performances of the system:n Fire protection – no insulation requiredn Acoustics - optional insulation for improved sound insulationn Fittings - up to 35 kg per screw - up to 60 kg with cavity dowels / cavity wall anchors.

fermacell Gypsum Fibreboards are used for drylining as:n Lining boardsn Fire boardsn Wet area boards

2 Wall

No fire exposure for the CLT – Lining system provides EI 30 performance – CLT structure protected for 30 min.

Page 5: fermacell special - Fire protection with cross laminated timber

5

3 H 12 CLT fermacell Gypsum Fibreboard Wall Lining

Example of system specification

1 10 mm fermacell Gypsum Fibreboard

2 12.5 mm fermacell Gypsum Fibreboard

3 18–19 mm Diverging Staples (galvanised and resinated) – Spacing ≤ 150 mm

4 15.3 × 35 mm Staples (galvanised and resinated) – Spacing ≤ 250 mm

5 Butt joint – Gap ≤ 1 mm

6 fermacell Jointstick – Width of joints ≤ 1 mm

7 Battens 48 × 24 mm

8 Fixing screw

9 Insulation (optional)

System Specifications

1 823 5 6 94 7

All these system specification options are possible:

Thickness Studs – Substructure fermacell Gypsum Fibre- board lining

Insulation – Mineral wool thickness/ density

Wall lining weight – each side max.

Air-borne sound insulation Rw

Ctraffic factors

mm mm mm mm / kg/m3 kg/m² dB (C100-3150 / C tr100-3150)

72,5 + 10 (gap) CW50 × 0.6 DIN standard studs – metal 12.5 + 10 40/10 without 30 75* (-6, -15)

97,5 + 10 (gap) CW75 × 0.6 DIN standard studs – metal 60/10 > 75* (-6, -15)

ca. 70 CD30-27 Adjustment bracket – metal 60 × 40 studs – timber C24

40/10 66* (-3, -9)

46.5 48 × 24 studs – timber C24 20/10 56* (-3, -13)

22.5 none without 41 (-1, -2)

EI 30

* Standard values, calculated by Sound insulation Software incl. Mineral wool

EI 30

Page 6: fermacell special - Fire protection with cross laminated timber

6

3 H 11 H2O CLT fermacell Powerpanel H2O Wall Lining

Material

Material class (EN 13501-1)n A1

Material (regulations/standards)n ETA-07/0087

Element

Fire Protection (CR: K-3015/439/07-MPA BS)n EI 30

Insulation n 60 mm / 30 kg/m³

Thickness n ≥ 110 + x + 110 mm

Weight n ≈ 2 × 28 kg/m² (without CLT)

Acoustic n ∆Rw ≥ 75 dB incl. mineralwool

A high performance dry wall system with the fermacell Powerpanel H2O boards. This is a wall lining system which is used to protect the CLT structure against fire. It also provides a high level of sound insulation and a high moisture resistance.

BenefitsTypical performances of the system:n Fire protection – A1 classificationn Wet area – high resistance against moisture in wet areasn Concrete like surfacen Fittings – up to 60 kg with cavity dowels / cavity wall anchors

fermacell Powerpanel H2O boards are used for drylining as:n Lining boardsn Fire boardsn Wet area boards for high moisture resistance

No fire exposure for the CLT – Lining system provides EI 30 performance – CLT structure protected for 30 min.

Page 7: fermacell special - Fire protection with cross laminated timber

7

3 H 11 H2O CLT fermacell Powerpanel H2O Wall Lining

Example of system specification

1 12.5 mm fermacell Powerpanel H2O

2 3.9 × 35 mm fermacell Powerpanel H2O Screws – Spacing ≤ 400 mm

3 3.9 × 50 mm fermacell Powerpanel H2O Screws – Spacing ≤ 250 mm

4 Butt joint – Gap ≤ 1 mm

5 fermacell Jointstick – Gap ≤ 1 mm

6 C-Stud CW50-0.6

7 U-Profile UW50-0.6

8 40/60 mm Mineral Wool – 30 kg/m3

System Specifications

1 2 34 5 86 7

Thickness Studs – Substructure fermacell Powerpanel H2O lining

Insulation – Mineral wool thickness/ density

Wall lining weight – each side max.

Air-borne sound insulation Rw

Ctraffic factors

mm mm mm mm / kg/m3 kg/m² dB (C100-3150 / C tr100-3150)

75 + 10 (gap) CW50 × 0.6 DIN standard studs – metal 12.5 + 12.5 40/30 28 75* (-6, -14)

100 + 10 (gap) CW75 × 0.6 DIN standard studs – metal 60/30 > 75* (-6, -14)

Only one system specification option is possible:

EI 30

* Standard values, calculated by Sound insulation Software incl. Mineral wool

EI 30

Page 8: fermacell special - Fire protection with cross laminated timber

8

3 H 21 A1 CLT fermacell Firepanel A1 Wall Lining

A high performance dry wall system with the new fermacell Firepanel A1. This is a wall lining system which is used to protect the CLT structure against fire. It also provides a high level of sound insulation.

Material

Material class (EN 13501-1)n A1

Material (regulations/standards)n EN 15283-2

Element

Fire Protection(CR: KB 3.2/11-035-3) (AS: 3.2/14-276-1)n EI 60 - Lining EI 60 - full loaded CLT

Insulation n not required

Thickness n ≥ 80 + x + 80 mm

Weight n ≈ 2 × 40 kg/m² (without CLT)

Acoustic n ∆Rw ≥ 65 dB incl. glass wool

BenefitsTypical performances of the system:n Fire protection – A1 classification - lean efficient constructions - no insulation requiredn Acoustics - optional insulation for improved sound insulationn Fittings - up to 35 kg per screw - up to 60 kg with cavity dowels / cavity wall anchor

fermacell Firepanels A1 are used for drylining as:n Lining boardsn High performance fire boardsn Wet area boards

No fire exposure for the CLT – Lining system provides EI 60 performance – CLT structure protected for 60 min.

Page 9: fermacell special - Fire protection with cross laminated timber

9

3 H 21 A1 CLT fermacell Firepanel A1 Wall Lining

Example of system specification

1 15 mm fermacell Firepanel A1

2 25–28 mm Diverging Staples (galvanised and resinated) – Spacing ≤ 150 mm

3 15.3 × 40 mm Staples (galvanised and resinated) – Spacing ≤ 250 mm

4 Butt joint – Gap ≤ 1 mm

5 fermacell Jointstick – Gap ≤ 1 mm

6 Lathing 60 × 40 mm

7 Adjustment bracket CD30-27

8 Insulation (optional)

9 Fixings at Adjustment bracket – screws

System Specifications

1 2 94 5 8 367

All these system specification options are possible:

Thickness Studs – Substructure fermacell Firepanel A1 lining

Insulation – Mineral wool thickness/ density

Wall lining weight – each side max.

Air-borne sound insulation Rw

Ctraffic factors

mm mm mm mm / kg/m3 kg/m² dB dB

80 + 10 (gap) CW50 × 0.6 DIN standard studs – metal 15 + 15 40/10 without 40 85* (-7, -15)

105 + 10 (gap) CW75 × 0.6 DIN standard studs – metal 60/10 85* (-7, -15)

ca. 80 CD30-27 Adjustment bracket – metal 60 × 40 studs – timber C24

40/10 65* (-2, -5)

54 48 × 24 studs – timber C24 20/10 55* (-3, -8)

30 none without 43 (-1, -2)

EI 60

* Standard values, calculated by Sound insulation Software incl. Mineral wool

EI 60

Page 10: fermacell special - Fire protection with cross laminated timber

10

3 H 31 A1 CLT fermacell Firepanel A1 Wall Lining

A high performance dry wall system with the new fermacell Firepanel A1. This is a wall lining system which is used to protect the CLT structure against fire. It also provides a high level of sound insulation.

Material

Material class (EN 13501-1)n A1

Material (regulations/standards)n EN 15283-2

Element

Fire Protection(CR: KB 3.2/11-035-4) (AS: 3.2/14-276-1)n EI 90 - Lining EI 90 - full loaded CLT

Insulation n not required

Thickness n ≥ 37.5 + x + 37.5 mm

Weight n ≈ 2 × 47 kg/m² (without CLT)

Acoustic n ∆Rw ≥ 45 dB

Benefits Typical performances of the system:n Fire protection – A1 classification - lean efficient constructions - no insulation requiredn Acoustics - optional insulation for improved sound insulationn Fittings with full thread srews - with a high load carrying ability

fermacell Firepanels A1 are used for drylining as:n Lining boardsn High performance fire boardsn Wet area boards

No fire exposure for the CLT – Lining system provides EI 90 performance – CLT structure protected for 90 min.

Page 11: fermacell special - Fire protection with cross laminated timber

11

3 H 31 A1 CLT fermacell Firepanel A1 Wall Lining

Example of system specification

1 12.5 mm fermacell Firepanel A1

2 21–22 mm Diverging Staples (galvanised and resinated) – Spacing ≤ 150 mm

3 15.3 × 45 mm Staples (galvanised and resinated) – Spacing ≤ 250 mm

4 Butt joint – Gap ≤ 1 mm

5 fermacell Jointstick – Gap ≤ 1 mm

System Specifications

1 245

All these system specification options are possible:

3

Thickness Studs – Substructure fermacell Firepanel A1 lining

Insulation – Mineral wool thickness/ density

Wall lining weight –each side max.

Air-borne sound insulation Rw

Ctraffic factors

mm mm mm mm / kg/m3 kg/m² dB dB

87.5 + 10 (gap) CW50 × 0.6 DIN standard studs – metal 12.5 + 12.5 + 12.5 40/10 without 50 85* (-7, -15)

112.5 + 10 (gap) CW75 × 0.6 DIN standard studs – metal 60/10 85* (-7, -15)

ca. 85 CD30-27 Adjustment bracket – metal 60 × 40 studs – timber C24

40/10 68* (-1, -4)

85.5 48 × 24 studs – timber C24 20/10 59* (-3, -9)

37.5 none without 45 (-1, -3)

EI 90

* Standard values, calculated by Sound insulation Software incl. Mineral wool

EI 90

Page 12: fermacell special - Fire protection with cross laminated timber

12

A high performance suspended ceiling system with the fermacell Gypsum Fibreboards. This is a fire rated suspended ceiling system.

fermacell Gypsum Fibreboards are used for ceilings as:n Lining boardsn Fire boards

n Use - Mechanical resilience - Impact resistance, high resistance against impact forces.

Element

Fire Protection (GA 3368/618/14 MPA BS)(CR: PK2-07-04-008-A-1)n EI 30 – from below

Insulation n not required

Lining n 2 × 10 mm

Ceiling weight n ≥ 28 kg/m²

Construction depth n ≥ 75 mm

Material

Material class (EN 13501-1)n A2 s1 d0

Material (regulations/standards)n ETA-03/0050n EN 15283-2

3 Ceiling

2 S 11 fermacell suspended ceiling (fire rated)

BenefitsTypical performances of the system:n Fire protection – no insulation requiredn Installation - Square Edge board in the first layer with dry Butt Joint < 1 mm - second layer can be fixed directly in the first layer independent of the substructure.

Page 13: fermacell special - Fire protection with cross laminated timber

13

Example of system specification

1 10 mm fermacell Gypsum Fibreboard

2 3.9 x 30 mm fermacell Screws – Spacing ≤ 200 mm

3 18–19 mm Diverging Staples (galvanised and resonated) - Spacing ≤ 120 mm - Row spacing ≈ 350 mm

4 Butt joint – Gap ≤ 1 mm

5 fermacell Jointstick – Gap ≤ 1 mm

6 27 mm CD60-0.6 – Metal profile

7 CD-System connector

8 27 mm CD 60-0.6 – Metal profile

9 CD-Strap hangar

2 S 11 fermacell suspended ceiling (fire rated)

Ceiling type / Construction type

Fire rating Substructure Construction depth Lining Spacing support structure

Insulation – Mineral wool thickness / density

Ceiling weight

mm mm mm mm mm / kg/m3 kg/m2

Suspended ceiling – independently fire rated

from below CD60 × 0.6 75 2 × 10 ≤ 350 Not required or at least A2 insulation

≥ 27

80 2 × 12.5 ≤ 435 ≥ 33

System Specifications

2 34 5 81 679

EI 30

Page 14: fermacell special - Fire protection with cross laminated timber

14

* this class is not included into European Standards - object-specific assassment required

4 K-Class system

Element

Fire Protection (EN 14135) n K260

Classification Report (EN 13501-2) n PCA 10107n PCA 10082n PCA 10161

Insulation n none

Thickness n CLT ≥ 85 mm

Material

Material class (EN 13501-1)n A2 s1 d0

Material (regulations/standards) n ETA-03/0050n EN 15283-2

A high performance dry wall system for the encapsulation of structural elements with the fermacell Gypsum Fibreboards. This is a lining / an encapsulation which is used to protect the CLT structure behind against fire.

K260

T ≤ 270 °C Tm ≤ 250 °C

K260Requirements for K260 class

fermacell Gypsum Fibreboards areused for drylining as:n Fire boards n wet area boards

n External wall alternative – K260 (see page 15): ≥ 12.5 mm fermacell Gypsum Fibreboard + Mineral fibre insulation composite system (Melting point ≥ 1 000 °C, Density ≥ 80 kg/m3, Minimal thickness 60 mm)

1 2

1 18 mm fermacell Gypsum Fibreboard

2 15 mm fermacell Gypsum Fibreboard

BenefitsTypical performances of the system:n Fire protection – directly fixedn high mechanical resistance - economical and efficient solutionn Fittings with full thread srews - with a high load carrying ability

Efficient and economical solution for the fire protection of structural elements especially in conjunction with a project specific fire strategy.

Fire protection linings with fermacell Gypsum Boards

"K classes" according to EN 13501-2

K230 K245* K260 K290*

Lining thickness 1 × 18 mm 2 × 10 mm

2 × 15 mm 15 mm / 18 mm2 × 18 mm 3 × 12.5 mm

3 × 18 mm

Page 15: fermacell special - Fire protection with cross laminated timber

Investor / client

Architect

Main contractor / installer

Call for bids

fermacell

Technical installation fire protection

Organisational fire protection

Fire defence protection

Structural fire protection Clerk of works

Fire protection expert

Material test establishment

Ganzheitliches Brandschutzkonzept

15

isn’t needed. The K260 criteria accord-ing to EN 13501-2[3] is used to assess the fire performance of the lining system. Timber structures which have to fulfil a high performance fire resist-ance need to comply with K260 criteria (K-classes) for the fire lining. The system with the K-class ensures the fire protection of the load bearing structure for 60 minutes and this prevents the self-ignition of the timber element. The self-ignition point of timber is around 300 °C.

Fire Strategy

An early involvement of the whole design team in the fire strategy allows a tailor made solution for a specific project. It can make the whole fire strategy more economical and effi-cient. This is especially important for multi storey buildings with sprinkler systems to make use of all the poten-tial benefits.

Collaboration of the whole design team from the beginning to the end of

a project is necessary to ensure the best and most efficient solution for each project. It also allows a better quality control from design to comple-tion of the project. The fire protection requirements of each individual ele-ment can be specified and optimised to give the most efficient solution. This approach can also enable the reduc-tion of the required K-class for certain elements. For example the reduction from a K260 class to K245/K230, from K290 to K260 or a K2120 to a K290, can result in a much more economical solution.

An individual fire strategy allows the realisation of bigger and more com-plex projects. It takes also project specific or individual requirements into account. It can also compensate for the lack of regulations or guidance for ground breaking projects.

The CLT structures can provide an individual and high performance solution combined together with an individual fire strategy giving a high level of protection and redundancy.

The system solutons with the K-class options describes the fire protective lining of a load bearing timber struc-ture. The lining must consist of non- combustible material to protect the combustible load bearing structure.

This provides a high performance and robust fire protection solution. It is especially suitable for multi storey CLT buildings. Where the fermacell is directly applied it provides a very robust lining which can withstand high impact forces, for example in lift shafts where an acoustic separation

External wall alternative – K260

Fire Strategy – Collaboration and relations in the design team Project Eurban Limited – 33 Waterson Street, London

Page 16: fermacell special - Fire protection with cross laminated timber

For additional information please visit the fermacell website.

Technical modifications subject to changesLast updated: 11/2014

The most recent edition applies.Should you require additional information, please contact our fermacell customer service.

fermacell customer service:E-Mail [email protected]

fermacell® is a registered trademark and a company of the XELLA group.

Fermacell GmbH

Düsseldorfer Landstraße 395

D-47259 Duisburg

www.fermacell.comwww.fermacell-aestuver.com