gci ht catalogue
DESCRIPTION
CatalougeTRANSCRIPT
-
High Voltage Cable
Connecting the World
-
High Voltage Servicing Utility, Industrial, CommercialAnd Specialty Applications
This new catalog contains in-depth information on the most comprehensive line of High Voltage Power Cable available today.
The spec-on-a-page format was developed to meet your needs. It features up-to-the-minute product information, from applications and constructions to detailed technical and specification data. Theres also a glossary of technical terms for additional assistance.
And, of course, if you need any further data, General Cable's Customer Service staff provides the answer you need quickly and efficiently.
All information in this catalog is presented solely as a guide product selection and is believed to be reliable. All printing errors are subject to correction in subsequent releases of this catalog. Although General Cable has taken precautions to ensure the accuracy of the product specifications at the time of publication, the specifications of all products contained herein are subject to change without notice.
E-mail: [email protected]
General Cable Energy India Pvt LtdCorporate office: Centrum Plaza, Level 3, Tower A, 312 S, Golf Course Road, Sector- 53, Gurgaon-122 002, Haryana. Phone: (0124) 4326000 Fax: (0124) 4326019
Connecting the WorldConnecting the World
INTERNATIONALISO 9001:2000CERTIFICATION
-
General Cable Corporation, headquartered in Highland Heights Kentucky, a USD 6.2 billion revenue and over 13000 associates, is a world leader in cable manufacturing with 46 modern production facilities in North America, Europe and rest of the world and provides service to global network of clients.
General Cable is a leader in the development, design, manufacture, marketing and distribution from power cables to telecommunication cables including electric cables for utility , buildings, data transmission, instrumentation, optic fiber cables, submarine cables, control and special cables and extra high voltage cables for market segments namely Energy, Industrial & Specialty, and Communication.
General Cable's breadth of products is very extensive, including IS, IEC, IEEE, VDE, and other international standards covering entire range of cable products.
General Cable has best- in- class research and development, testing and production facilities worldwide. The development of unique compounds designed and tested to meet specific needs and stringent specifications, differentiates General Cable from all others. With superior R&D, engineering and manufacturing, leading logistics capabilities, the broadest product range in all the industry segments, with a strong group of associates seamlessly teaming up to satisfy customers worldwide, makes General Cable as world leader in wire and cable. General Cable bases its activities on a series of Corporate Values which guide all its operations: Customer Satisfaction as an absolute priority; Integrity in all of its actions; People as the main source of value; Teamwork as a path to excellence; speed of delivery as a competitive advantage; and continuous improvement as a constant objective.
This philosophy can only be assumed by a global company such as General Cable with extremely broad, diversified range, able to meet any requirement, however specific, anywhere on the planet. General Cable India is catering to Indian customer through its state of the art modern facility in 20 acre (Approx 80937 sq. mtrs) situated at the Industrial town of Baddi in the beautiful state of Himachal Pradesh. The range of products manufactured includes low voltage, high voltage, and extra high voltage and specialty cables. General Cable has extensive sales network across India.
One of the world's biggest companies in the Cable and Wire Industry...
-
Connecting the WorldConnecting the World
General Cables Global Reach
General Cable serves customers through a global network of 46 manufacturing facilities in 23 countries
and sales representatives and distribution centers worldwide. The Company is solely dedicated to the
production of high-quality energy, industrial, specialty and communications wire and cable products. In
addition to its breadth of product line and strong brand recognition, the Company offers competitive
strengths in such areas as technology, manufacturing, distribution and logistics, and sales and customer
service. This combination enables General Cable to better serve its customers as they expand into new
geographic markets.
International CorpNSW
BRAND
General Cable Footprint
-
Connecting the WorldConnecting the World
General Cable is a leader in the development,
design, manufacture, marketing and
distribution of copper, aluminum and fiber
optic wire and cable for the energy, industrial,
specialty and communications markets.
Our products inspire progress worldwide......Customers use our value-added products to
create global infrastructure that improves the
standard of living for people everywhere.
Each day were bui lding business
momentum- developing ideas into innovative
solutions and industry-leading products,
expanding geographic access and furthering
our investment in highly capable associates,
Lean Manufacturing, material science and
technology resources.
General Cable is influencing the world...with more than two-thirds of our sales generated outside North America and more than 13,000 associates in 46 manufacturing facilities throughout 23 countries. As the fifth largest wire and cable manufacturer, we are the One Company Connecting the World.
Energy CablesOur cables carry energy across the world-through the air, underground and under the sea. Increasing demand for energy is accelerating investment in exploration, extraction, power generation, transmission and distribution- whether based on coal, natural gas, oil, nuclear, wind or water.
Industrial & Specialty CablesWe have the competitive product mix and global reach to support the production of oil, gas and petrochemical; construction of new factories and maintenance of existing industrial facilities; factory automation; and special applications such as military, nuclear, marine, mining, transit and automotive.
Communications CablesOur cables keep information flowing- facilitating a non-stop stream of words and images around the world. We meet the high-speed bandwidth needs of global communications networks from fiber optic, submarine communications cables, copper and fiber aerial and underground cables to copper and fiber optic enterprise cables and system solutions.
India Headquarters General Cable Energy India Pvt LtdCorporate office: Centrum Plaza, Level 3, Tower A, 312 S, Golf Course Road, Sector- 53, Gurgaon-122 002, Haryana. Phone: (0124) 4326000 Fax: (0124) 4326019 E-mail: [email protected]
World HeadquartersGeneral Cable4 Tesseneer DriveHighland Heights, KY41076-9753 U.S.A
Directing Traffic without Gridlock
Building Bridges in the Sky
Making Contact with the World
-
Connecting the WorldConnecting the World
Quality is Forethought.General Cable is committed to exceeding our customers expectations for quality and performance.
We strive to ensure this quality through extensive in-house and third-party testing, with strict adherence
to our product specification and industry standards. At General Cable, quality is not just a process, it
is forethought. It is the forethought of using the best materials and proactive prevention. This level of
quality is best represented in three core steps: Design, Technology and Control.
General Cable Corporation is committed to developing, producing and marketing products that meet
the performance, quality, value and safety requirements of our customers by continuously improving all
areas of our business. We apply Lean Sigma Company-wide, seeking innovative ways to differentiate our
products and services and to serve as our customers and suppliers most valued business partner.
DesignDesignControlControl
TechnologyTechnology
QualityQuality
International CorpNSW
-
Connecting the WorldConnecting the World
Commitment to QualityIndian cable industry is highly saturated with various organised / unorganised cable manufacturers.
The fierce competition leading to price war, may result into dilution in quality of product.
Under this scenario General Cable is giving maximum emphasis on quality of its cable products
and there by ensuring uninterrupted production to industries, safety to equipments and personnel.
Quality Assurance Guaranteed
Through an ongoing quality assurance initiative, General Cable ensures the quality of product design,
manufacture, installation and expected service life, as well as environmentally sound products, processes
and policies, continuous research and development, combined with process control, quality audits and
prolonged stringent testing, provide an ever-growing range of specialty materials and designs that meet
industry approvals and standards.
Aerial view of General Cable factory at Baddi, H.P., India
BRAND
-
Connecting the WorldConnecting the World
Our Green Initiative symbol recognizes our role
and responsibility in promoting sustainability.
The symbol also reflects our commitment to achieving
industry-leading standards and responding
proactively to environmental global issues.
IN T I N IE ATE IR VG E
Commitment To Environment - Green FactoryCompliant to Indian Green Building Council Rating
Commitment To Environment - Green FactoryCompliant to Indian Green Building Council Rating
International CorpNSW
-
Products for all
markets
Connecting the WorldConnecting the World
BRAND
-
SM
Underground High-Voltage and Extra-High-Voltage CablesGeneral Cables complete line of Silec insulatedhigh- and extra-high-voltage underground energycables, from 63kV up to 500kV, and our state-of the-art accessories - such as pre-molded joints and terminals - enable us to provide turnkey design and engineering services for the global, systems engineered, electric utility market.
Bare Overhead High-Voltage Transmission andDistribution ConductorsOur TransPowr bare aluminum overhead conductors are available in standard ACSR, specialized T-2 designs and high temperature ACSS/TW designs. Our new ACCC/TW conductors feature an innovative composite core construction which possesses high temperature and increased strength characteristics.
Low- and Medium-Voltage Distribution CablesGeneral Cables extensive line of BICC BrandPowrServ and EmPowr copper and aluminumcables serve the total distribution needs of electric utilities, rural electric co-ops and the public power market for both traditional and renewable energy resources.
Industrial CablesGeneral Cables industrial instrumentation, powerand control cables serve an extensive range ofmarkets including power generation, refining andpetrochemical, natural gas production, steel, pulp and paper, and factory automation.
Specialty CablesGeneral Cable manufactures a broad range of specialty cables that meet the exacting specifications for original equipment manufacturers (OEMs), military, transit, offshore and marine shipboard, nuclear, and mining applications. General Cables engineered Brand Rex and Anaconda Brand wire and cable solutions provide great lifecycle performance and reliability - meeting customer applications requirements today, while setting tomorrows standards.
Energy Cables Industrial & Specialty Cables
-
Specialty Wire HarnessesWe supply application-specific and custom-designed cable, harnesses and assemblies for a wide variety of OEM applications, including business machines, material handling equipment, factory automation, medical equipment and the automotive aftermarket. General Cable is a global leader in the manufacture of automotive wire and cablefrom ignition wire sets and single leads to bulk ignition wire, primary wire and battery starter cable.
Cord and Cordset ProductsGeneral Cables Carol Brand is the most recognized name in flexible cords for temporary power. Our extensive line includes portable cord, cordsets, portable power cable and premium-grade cable for commercial and industrial applications.
Electronic CablesOur Carol Brand and Helix/HiTemp products fulfill the complete wire and cable requirements of the fast-changing electronics, sound and security marketplaces. We offer hookup wire; communications cable; computer, coaxial and microphone cables; and special designs for security systems, fire alarms, and audio, video and digital broadcasts.
Communications CablesData Communications CablesOur GenSPEED Brand products are on the job wherever enhanced performance is criticalfrom Gigabit Ethernet, token ring and broadband applications to patch panels, communications closets and plenum applications.We offer one of the most comprehensive lines of enhanced high-speed Category products, including PanGen structured cabling system solutions.
Fiber Optic CablesWe provide a full menu of NextGen Brand fiber optic cables for data communications and voice and video networks. Our products range from tight buffer and armored products for military applications to loose tube and hybrid cables for communications networks. We also offer advanced Blolite blown fiber systems for Local Area Networks and campus applications.
Telecommunications CablesOur broad range of industry-standard General Cable outside plant wire and cable products ensures reliable, cost-effective performance. We provide air core, filled core and specialty wire products for aerial, buried and duct applications.
Now one industry leader focuses its worldwide resources on delivering maximum value to customers. Its the cost-effective advantage of a single resource, a single company that provides the broadest product range, the highest level of commitment to customer and technical support, the most cost-effective manufacturing and distribution, and the
most responsive customer-first service. In todays highly competitive worldwide markets, General Cable provides the single-source solution with benefits that go straight to your bottom line. Ask your representative about other General Cable products.
International Corp NSW
BRAND
-
CONNECTING THE WORLD
Making Cables is about Creating Potential
General Cable products help to illuminate the world, inspire progress and open lines of communication. We connect people with energy, information, ideas and opportunities.
For more than a century, General Cable has been a leader in the development, manufacture, marketing and distribution ofwire and cable-our sole business. Today, we continue to direct our worldwide resources to deliver maximum value to customers through a powerful combination of product and service innovations.
At General Cable we aim to add value to our customers businesses by understanding and competitively servicing their needs through customer intimacy operational excellence.
General Cable provides a single source solutionThe cost effective advantage of a single resource, a single company that provides one of the broadest product ranges, highest levels of customer and technical support and responsive customer-first service.
THE POWER OF ONEAt General Cable, THE POWER OF ONE embodies our integrated approach to business: one company with the power of our products, expertise, systems and people all focused on one goal - fulfilling our customers needs. It means one source customers can count on for DATA, COMMUNICATION, INDUSTRIAL and ENERGY cables. Most of all, THE POWER OF ONE means one team, well trained and wholly committed to the highest level of customer satisfaction.
-
Manufacturing and logistics
With superior engineering and manu fac tu r i ng ope ra t i ons , i n d u s t r y - l e a d i n g l o g i s t i c s capabilities, one of the broadest product ranges in the industry, and a strong group of employees seamlessly teaming to satisfy customers, General Cable is strong, diversified and well positioned to meet the challenges of tomorrow.
Sales and Distribution Network
General Cable has a distribution network throughout India and a team of people committed to meeting the total needs of our customers- by providing enhanced distribution and warehousing services, and an unprecedented level of technical support.
Strength, Diversity and Teamwork
Every product reflects our POWER OF ONE business philosophy. We have become a leading cable supplier in Asla pacific through excellent customer relationships, the quality of our people and the highest standards of service.
GENERAL CABLE INDIA
Quality Products, People and Service
Connecting the WorldConnecting the World
OUR VISIONStrive for leadership through growth and excellence.
General Cable India is a leading supplier of cable solutions for energy, industrial, data, communications and specialist applications. As part of the US based General Cable Corporation (one of the worlds largest wire and cable manufacturers) we serve customers through a global network of forty six manufacturing facilities in twenty three countries, with sales and distribution centers worldwide.
As part of a global business we are able to draw on innovative engineering developments, a comprehensive product range and the best research and technical support available, ensuring our customers are offered a competitive edge.
-
High Voltage Cable
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
PRODUCT SELECTION LOCATOR
TYPE LETTER CODE REFERENCE STANDARD CABLE DESCRIPTION PAGE NO.HV CABLES
TECHNICAL INFORMATION 49 - 73
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
IS : 7098 Part - 2
2XWaY
2XY
A2XWaY
A2XY 1 - 43.3 KV, Single Core XLPE
Power CablesIS : 7098 Part - 2
5 - 86.6 KV(E), Single Core XLPE Power Cables2XWaYA2XY
A2XWaY
2XY
A2XFY2XFY
A2XWY2XWY
A2XFY2XFY
A2XWY2XWY
A2XFY2XFY
A2XWY2XWY
A2XFY2XFY
A2XWY2XWY
A2XFY2XFY
A2XWY2XWY
A2XFY2XFY
A2XWY2XWY
2XWaY
2XY
A2XWaY
A2XY
2XWaY
2XY
A2XWaY
A2XY
2XWaY
2XY
A2XWaY
A2XY
2XWaY
2XY
A2XWaY
A2XY
IS : 7098 Part - 2 33 KV(E), Three Core XLPE Armoured Power Cables
22 KV(E), Three Core XLPE Armoured Power Cables
11 KV(E), Three Core XLPE Armoured Power Cables
6.6 KV(E), Three Core XLPE Armoured Power Cables
3.3 KV, Three Core XLPE Armoured Power Cables
33 KV(E), Single Core XLPE Power Cables
22 KV(E), Single Core XLPE Power Cables
11 KV (E), Single Core XLPE Power Cables
45 - 48
41 - 44
37 - 40
33 - 36
29 - 32
25 - 28
21 - 24
17 - 20
13 - 16
9 - 12
11 KV(UE), Three Core XLPE Armoured Power Cables
11 KV(UE), Single Core XLPE Power Cables
-
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
Conductor : Round Compact Stranded AluminiumInsulation : Cross - Linked Polyethylene (XLPE)Armour : Round Aluminium Wires Outer Sheath : Black PVC (Type - ST2)
Construction :I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces #? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
10 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.# Applicable for Screened cables, available upon request.
Options :
SINGLE CORE 3.3 KV (E) & (UE) ALUMINIUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor
Outer Sheath
Armour
Insulation
1
25 2.5 1.4 1.24 19.0 350 0.23 0.136 100 90 115 500
35 2.5 1.4 1.24 20.0 400 0.26 0.130 120 110 140 500
50 2.5 1.4 1.40 21.0 450 0.29 0.125 140 125 165 500
70 2.5 1.6 1.40 23.0 600 0.34 0.116 170 155 210 500
95 2.5 1.6 1.40 25.0 700 0.39 0.110 205 180 250 500
120 2.5 1.6 1.40 26.5 800 0.43 0.106 230 205 290 500
150 2.5 1.6 1.40 28.0 900 0.47 0.103 255 225 335 500
185 2.5 1.6 1.40 29.5 1,050 0.52 0.099 290 255 395 500
240 2.5 1.6 1.56 32.0 1,250 0.58 0.096 330 295 450 500
300 2.6 1.6 1.56 34.5 1,500 0.62 0.093 370 330 510 500
400 2.6 2.0 1.56 38.0 1,850 0.70 0.090 415 370 610 500
500 2.8 2.0 1.56 42.0 2,250 0.74 0.088 465 425 695 500
630 3.1 2.0 1.72 46.5 2,800 0.76 0.086 520 480 795 500
800 3.3 2.0 1.88 52.0 3,500 0.81 0.085 560 520 880 500
1000 3.6 2.5 2.04 58.5 4,450 0.84 0.085 600 550 980 500
(Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
StandardDeliveryLength
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground AirDuct
NominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
MinimumOuter
SheathThickness
Approx.OverallCable
Diameter
Approx.Cable
Wt.
Approx.Capacitance
Approx.Reactance
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
Conductor : Round Compact Stranded Plain CopperInsulation : Cross - Linked Polyethylene (XLPE)Armour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath
Armour
Insulation
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces #? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
10 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.# Applicable for Screened cables, available upon request.
Options :
SINGLE CORE 3.3 KV (E) & (UE)COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
2
25 2.5 1.4 1.24 19.0 500 0.23 0.136 125 115 145 500
35 2.5 1.4 1.24 20.0 600 0.26 0.130 150 135 175 500
50 2.5 1.4 1.40 21.0 750 0.29 0.125 175 155 210 500
70 2.5 1.6 1.40 23.0 1,000 0.34 0.116 220 190 255 500
95 2.5 1.6 1.40 25.0 1,250 0.39 0.110 255 230 320 500
120 2.5 1.6 1.40 26.5 1,500 0.43 0.106 295 260 370 500
150 2.5 1.6 1.40 28.0 1,750 0.47 0.103 325 290 425 500
185 2.5 1.6 1.40 29.5 2,100 0.52 0.099 365 325 480 500
240 2.5 1.6 1.56 32.0 2,650 0.58 0.096 415 375 565 500
300 2.6 1.6 1.56 34.5 3,250 0.62 0.093 460 420 645 500
400 2.6 2.0 1.56 38.0 4,100 0.70 0.090 515 470 750 500
500 2.8 2.0 1.56 42.0 5,150 0.74 0.088 565 520 850 500
630 3.1 2.0 1.72 46.5 6,550 0.76 0.086 615 575 950 500
800 3.3 2.0 1.88 52.0 8,250 0.81 0.085 645 600 1030 500
1000 3.6 2.5 2.04 58.5 10,400 0.84 0.085 675 630 1110 500
StandardDeliveryLengthGround AirDuct
DIMENSIONS ELECTRICAL PARAMETERS
Current RatingNominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
MinimumOuter
SheathThickness
Approx.OverallCable
Diameter
Approx.Cable
Wt.
Approx.Capacitance
Approx.Reactance
(Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
Conductor : Round Compact Stranded AluminiumInsulation : Cross - Linked Polyethylene (XLPE)Screen : Copper Tape Outer Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer Sheath
Screen
Insulation
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces #? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
10 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.# Applicable for Screened cables, available upon request.
Options :
SINGLE CORE 3.3 KV (E) & (UE) ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
3
25 2.2 1.8 16.0 250 0.26 0.125 100 90 110 500
35 2.2 1.8 17.0 300 0.29 0.119 115 100 135 500
50 2.2 1.8 18.0 350 0.32 0.114 135 120 160 500
70 2.2 1.8 19.5 400 0.38 0.105 170 155 195 500
95 2.2 2.0 22.0 550 0.44 0.102 200 185 250 500
120 2.2 2.0 23.5 600 0.48 0.098 225 210 280 500
150 2.2 2.0 25.0 700 0.53 0.095 255 230 325 500
185 2.2 2.0 26.5 850 0.58 0.092 285 260 370 500
240 2.2 2.0 29.0 1,000 0.65 0.089 330 300 440 500
300 2.2 2.0 31.0 1,200 0.72 0.086 375 330 510 500
400 2.2 2.2 34.5 1,550 0.82 0.084 425 380 600 500
500 2.4 2.2 38.5 1,900 0.85 0.082 480 430 700 500
630 2.6 2.2 42.5 2,350 0.90 0.080 540 500 830 500
800 2.8 2.4 47.5 2,950 0.94 0.079 620 540 950 500
1000 3.0 2.6 53.0 3,700 0.99 0.078 685 600 1080 500
StandardDeliveryLengthAirDuctGround
Approx.Reactance
Approx.Capacitance
Approx.Cable
Wt.
Approx.OverallCable
Diameter
NominalOuter
SheathThickness
DIMENSIONS ELECTRICAL PARAMETERS
Current RatingNominalArea of
Conductor
NominalInsulationThickness
(Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces #? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
10 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.# Applicable for Screened cables, available upon request.
Options :
Conductor
Outer Sheath
Screen
Insulation
SINGLE CORE 3.3 KV (E) & (UE) COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain CopperInsulation : Cross - Linked Polyethylene (XLPE)Screen : Copper Tape Outer Sheath : Black PVC (Type - ST2)
Construction :
4
25 2.2 1.8 16.0 400 0.26 0.125 125 115 140 500
35 2.2 1.8 17.0 500 0.29 0.119 150 140 170 500
50 2.2 1.8 18.0 600 0.32 0.114 175 160 200 500
70 2.2 1.8 19.5 800 0.38 0.105 220 200 250 500
95 2.2 2.0 22.0 1,100 0.44 0.102 260 235 310 500
120 2.2 2.0 23.5 1,300 0.48 0.098 290 270 360 500
150 2.2 2.0 25.0 1,550 0.53 0.095 330 300 420 500
185 2.2 2.0 26.5 1,900 0.58 0.092 370 335 470 500
240 2.2 2.0 29.0 2,400 0.65 0.089 425 385 560 500
300 2.2 2.0 31.0 3,000 0.72 0.086 480 430 650 500
400 2.2 2.2 34.5 3,800 0.82 0.084 540 490 760 500
500 2.4 2.2 38.5 4,800 0.85 0.082 605 545 870 500
630 2.6 2.2 42.5 6,100 0.90 0.080 675 600 1000 500
800 2.8 2.4 47.5 7,750 0.94 0.079 745 660 1140 500
1000 3.0 2.6 53.0 9,700 0.99 0.078 810 715 1260 500
StandardDeliveryLengthAirDuctGround
Approx.Reactance
Approx.Capacitance
Approx.Cable
Wt.
Approx.OverallCable
Diameter
NominalOuter
SheathThickness
DIMENSIONS ELECTRICAL PARAMETERS
Current RatingNominalArea of
Conductor
NominalInsulationThickness
(Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
12 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 6.6 KV (E) ALUMINUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer SheathInsulation ShieldConductor Shield
ArmourInsulation
5
25 2.8 1.6 1.40 23.0 500 0.23 0.148 100 90 120 500
35 2.8 1.6 1.40 24.0 550 0.26 0.141 120 110 145 500
50 2.8 1.6 1.40 25.0 650 0.28 0.136 140 125 170 500
70 2.8 1.6 1.40 26.5 750 0.32 0.125 170 155 215 500
95 2.8 1.6 1.40 28.5 850 0.37 0.119 205 180 260 500
120 2.8 1.6 1.40 30.0 1,000 0.41 0.114 230 210 300 500
150 2.8 1.6 1.56 32.0 1,100 0.45 0.111 255 230 340 500
185 2.8 1.6 1.56 33.5 1,250 0.49 0.107 290 260 390 500
240 2.8 2.0 1.56 36.5 1,550 0.54 0.104 330 300 460 500
300 3.0 2.0 1.56 39.0 1,800 0.56 0.101 370 340 520 500
400 3.3 2.0 1.72 43.0 2,200 0.58 0.098 415 385 600 500
500 3.5 2.0 1.72 47.0 2,650 0.62 0.095 465 430 690 500
630 3.5 2.0 1.88 51.0 3,200 0.69 0.092 520 480 815 500
800 3.5 2.5 2.04 56.5 4,000 0.78 0.091 560 520 890 500
1000 3.6 2.5 2.20 62.0 4,800 0.85 0.089 600 550 985 500
DIMENSIONS
StandardDeliveryLength
ELECTRICAL PARAMETERS
Current Rating
Ground AirDuct
NominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
MinimumOuter
SheathThickness
Approx.OverallCable
Diameter
Approx.Cable
Wt.
Approx.Capacitance
Approx.Reactance
(Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
12 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 6.6 KV (E) COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)
Construction :
Outer Sheath
Conductor ShieldInsulation Shield
Insulation
Conductor
Armour
6
25 2.8 1.6 1.40 23.0 650 0.23 0.148 130 115 155 500
35 2.8 1.6 1.40 24.0 800 0.26 0.141 155 135 185 500
50 2.8 1.6 1.40 25.0 900 0.28 0.136 180 155 220 500
70 2.8 1.6 1.40 26.5 1,150 0.32 0.125 220 195 275 500
95 2.8 1.6 1.40 28.5 1,400 0.37 0.119 260 230 330 500
120 2.8 1.6 1.40 30.0 1,650 0.41 0.114 290 265 380 500
150 2.8 1.6 1.56 32.0 1,950 0.45 0.111 330 295 435 500
185 2.8 1.6 1.56 33.5 2,350 0.49 0.107 365 330 500 500
240 2.8 2.0 1.56 36.5 2,950 0.54 0.104 415 380 575 500
300 3.0 2.0 1.56 39.0 3,600 0.56 0.101 460 425 650 500
400 3.3 2.0 1.72 43.0 4,450 0.58 0.098 510 470 740 500
500 3.5 2.0 1.72 47.0 5,550 0.62 0.095 560 525 835 500
630 3.5 2.0 1.88 51.0 6,950 0.69 0.092 615 575 960 500
800 3.5 2.5 2.04 56.5 8,800 0.78 0.091 640 600 1020 500
1000 3.6 2.5 2.20 62.0 10,800 0.85 0.089 675 625 1105 500
MinimumOuter
SheathThickness
StandardDeliveryLength
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground AirDuct
NominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
Approx.OverallCable
Diameter
Approx.Cable
Wt.
Approx.Capacitance
Approx.Reactance
(Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
12 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 6.6 KV (E) ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)
Construction :
InsulationConductor
Conductor Shield
Insulation Shield Outer Sheath
Metallic Insulation Screen
7
25 2.8 1.8 20.0 350 0.23 0.137 100 90 115 500
35 2.8 2.0 21.5 450 0.26 0.132 120 110 140 500
50 2.8 2.0 22.5 500 0.28 0.127 140 130 165 500
70 2.8 2.0 24.0 600 0.32 0.116 175 160 210 500
95 2.8 2.0 26.0 700 0.37 0.111 205 190 255 500
120 2.8 2.0 27.5 800 0.41 0.107 230 215 295 500
150 2.8 2.0 29.0 900 0.45 0.104 260 240 335 500
185 2.8 2.0 30.5 1,000 0.49 0.099 295 275 385 500
240 2.8 2.2 33.0 1,250 0.54 0.096 340 315 455 500
300 3.0 2.2 36.0 1,500 0.56 0.095 380 355 525 500
400 3.3 2.2 39.5 1,800 0.58 0.092 435 405 610 500
500 3.5 2.4 43.5 2,250 0.62 0.089 495 460 710 500
630 3.5 2.4 47.5 2,700 0.69 0.087 570 530 840 500
800 3.5 2.6 52.5 3,350 0.78 0.085 640 600 985 500
1000 3.6 2.8 57.5 4,100 0.85 0.083 705 660 1110 500
StandardDeliveryLengthAirDuctGround
Approx.Reactance
Approx.Capacitance
Approx.Cable
Wt.
Approx.OverallCable
Diameter
NominalOuter
SheathThickness
DIMENSIONS ELECTRICAL PARAMETERS
Current RatingNominalArea of
Conductor
NominalInsulationThickness
(Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
12 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
25 2.8 1.8 20.0 500 0.23 0.137 130 120 150 500
35 2.8 2.0 21.5 600 0.26 0.132 155 140 180 500
50 2.8 2.0 22.5 750 0.28 0.127 180 165 215 500
70 2.8 2.0 24.0 950 0.32 0.116 220 200 270 500
95 2.8 2.0 26.0 1,250 0.37 0.111 265 240 325 500
120 2.8 2.0 27.5 1,500 0.41 0.107 300 275 375 500
150 2.8 2.0 29.0 1,750 0.45 0.104 335 310 430 500
185 2.8 2.0 30.5 2,100 0.49 0.099 375 350 495 500
240 2.8 2.2 33.0 2,650 0.54 0.096 435 410 580 500
300 3.0 2.2 36.0 3,250 0.56 0.095 490 450 670 500
400 3.3 2.2 39.5 4,050 0.58 0.092 550 515 770 500
500 3.5 2.4 43.5 5,150 0.62 0.089 615 570 890 500
630 3.5 2.4 47.5 6,450 0.69 0.087 700 650 1050 500
800 3.5 2.6 52.5 8,150 0.78 0.085 770 720 1190 500
1000 3.6 2.8 57.5 10,100 0.85 0.083 840 780 1320 500
Conductor ShieldInsulation Shield
Conductor
Insulation
Metallic Insulation Screen
Outer Sheath
SINGLE CORE 6.6 KV (E) COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)
Construction :
8
StandardDeliveryLengthAirDuctGround
Approx.Reactance
Approx.Capacitance
Approx.Cable
Wt.
Approx.OverallCable
Diameter
NominalOuter
SheathThickness
DIMENSIONS ELECTRICAL PARAMETERS
Current RatingNominalArea of
Conductor
NominalInsulationThickness
(Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
17 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 11 KV (E) ALUMINIUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer SheathInsulation ShieldConductor Shield
ArmourInsulation
9
25 3.6 1.60 1.40 24.5 600 0.19 0.152 100 90 120 500
35 3.6 1.60 1.40 25.5 650 0.21 0.145 120 110 145 500
50 3.6 1.60 1.40 26.5 700 0.23 0.139 140 125 170 500
70 3.6 1.60 1.40 28.5 800 0.27 0.129 170 155 215 500
95 3.6 1.60 1.40 30.0 950 0.30 0.122 205 185 260 500
120 3.6 1.60 1.56 32.0 1,100 0.33 0.118 230 210 300 500
150 3.6 1.60 1.56 33.5 1,200 0.36 0.114 255 230 340 500
185 3.6 2.00 1.56 36.0 1,450 0.39 0.112 290 260 390 500
240 3.6 2.00 1.56 38.0 1,650 0.44 0.107 330 300 460 500
300 3.6 2.00 1.56 40.5 1,900 0.48 0.104 370 335 530 500
400 3.6 2.00 1.72 43.5 2,250 0.54 0.099 415 380 605 500
500 3.6 2.00 1.72 47.0 2,650 0.60 0.095 460 430 685 500
630 3.6 2.00 1.88 51.0 3,200 0.68 0.092 515 485 800 500
800 3.6 2.50 2.04 57.0 4,000 0.76 0.091 555 520 890 500
1000 3.6 2.50 2.20 62.0 4,800 0.85 0.089 600 550 990 500
StandardDeliveryLength
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground AirDuct
Approx.Capacitance
Approx.Reactance
NominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
MinimumOuter
SheathThickness
Approx.OverallCable
Diameter
Approx.Cable
Wt.
(Mtr./Drum)(Amp) (Amp)(Amp)(F/km) Z(Sqmm) (mm) (mm) (mm) (mm) (Kg/km)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
17 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 11 KV (E) COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)
Construction :
Outer Sheath
Conductor ShieldInsulation Shield
Insulation
Conductor
Armour
10
25 3.6 1.60 1.40 24.5 700 0.19 0.152 130 115 155 500
35 3.6 1.60 1.40 25.5 850 0.21 0.145 150 135 185 500
50 3.6 1.60 1.40 26.5 1,000 0.23 0.139 180 160 220 500
70 3.6 1.60 1.40 28.5 1,200 0.27 0.129 220 200 275 500
95 3.6 1.60 1.40 30.0 1,500 0.30 0.122 260 230 330 500
120 3.6 1.60 1.56 32.0 1,750 0.33 0.118 295 265 385 500
150 3.6 1.60 1.56 33.5 2,050 0.36 0.114 325 300 435 500
185 3.6 2.00 1.56 36.0 2,500 0.39 0.112 365 330 495 500
240 3.6 2.00 1.56 38.0 3,050 0.44 0.107 415 380 585 500
300 3.6 2.00 1.56 40.5 3,650 0.48 0.104 460 425 660 500
400 3.6 2.00 1.72 43.5 4,500 0.54 0.099 510 470 745 500
500 3.6 2.00 1.72 47.0 5,550 0.60 0.095 560 525 835 500
630 3.6 2.00 1.88 51.0 6,950 0.68 0.092 615 570 960 500
800 3.6 2.50 2.04 57.0 8,800 0.76 0.091 640 590 1030 500
1000 3.6 2.50 2.20 62.0 10,800 0.85 0.089 670 620 1110 500
StandardDeliveryLengthGround AirDuct
NominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
MinimumOuter
SheathThickness
Approx.OverallCable
Diameter
Approx.Cable
Wt.
Approx.Capacitance
Approx.Reactance
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
(Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
25 3.6 2.0 22.0 450 0.19 0.143 100 90 115 500
35 3.6 2.0 23.0 500 0.21 0.137 120 110 140 500
50 3.6 2.0 24.0 550 0.23 0.131 140 130 165 500
70 3.6 2.0 25.5 650 0.27 0.120 175 160 210 500
95 3.6 2.0 27.5 750 0.30 0.115 205 190 255 500
120 3.6 2.0 29.0 850 0.33 0.110 235 220 295 500
150 3.6 2.0 30.5 950 0.36 0.107 260 240 335 500
185 3.6 2.2 32.5 1,150 0.39 0.104 295 275 385 500
240 3.6 2.2 35.0 1,350 0.44 0.100 340 315 455 500
300 3.6 2.2 37.0 1,550 0.48 0.096 385 360 525 500
400 3.6 2.2 40.0 1,850 0.54 0.092 435 410 610 500
500 3.6 2.4 44.0 2,250 0.60 0.090 495 460 710 500
630 3.6 2.4 47.5 2,750 0.68 0.087 570 530 840 500
800 3.6 2.6 52.5 3,400 0.76 0.085 640 600 985 500
1000 3.6 2.8 57.5 4,100 0.85 0.083 710 660 1110 500
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
17 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 11 KV (E) ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)
Construction :
InsulationConductor
Conductor Shield
Insulation Shield Outer Sheath
Metallic Insulation Screen
11
Approx.Reactance
Approx.Capacitance
Approx.Cable
Wt.
Approx.OverallCable
Diameter
NominalOuter
SheathThickness
DIMENSIONS
NominalArea of
Conductor
NominalInsulationThickness
StandardDeliveryLengthAirDuctGround
ELECTRICAL PARAMETERS
Current Rating
(Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
17 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 11 KV (E) COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)
Construction :
Conductor ShieldInsulation Shield
Conductor
Insulation
Metallic Insulation Screen
Outer Sheath
12
StandardDeliveryLengthDuctGround
Approx.Reactance
Approx.Capacitance
Approx.Cable
Wt.
Approx.OverallCable
Diameter
NominalOuter
SheathThickness
DIMENSIONS ELECTRICAL PARAMETERS
Current RatingNominalArea of
Conductor
NominalInsulationThickness Air
(Mtr./Drum)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm) (Amp)
25 3.6 2.0 22.0 600 0.19 0.143 130 120 150 500
35 3.6 2.0 23.0 700 0.21 0.137 155 140 180 500
50 3.6 2.0 24.0 800 0.23 0.131 180 165 215 500
70 3.6 2.0 25.5 1,050 0.27 0.120 220 205 270 500
95 3.6 2.0 27.5 1,300 0.30 0.115 265 240 325 500
120 3.6 2.0 29.0 1,550 0.33 0.110 300 275 380 500
150 3.6 2.0 30.5 1,800 0.36 0.107 335 310 430 500
185 3.6 2.2 32.5 2,200 0.39 0.104 380 340 495 500
240 3.6 2.2 35.0 2,750 0.44 0.100 435 410 585 500
300 3.6 2.2 37.0 3,300 0.48 0.096 490 460 670 500
400 3.6 2.2 40.0 4,100 0.54 0.092 550 515 770 500
500 3.6 2.4 44.0 5,150 0.60 0.090 620 570 890 500
630 3.6 2.4 47.5 6,500 0.68 0.087 700 650 1050 500
800 3.6 2.6 52.5 8,200 0.76 0.085 770 720 1190 500
1000 3.6 2.8 57.5 10,100 0.85 0.083 840 780 1320 500
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
28 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 11 KV (UE) ALUMINIUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer SheathInsulation ShieldConductor Shield
ArmourInsulation
13
25 5.5 1.60 1.40 28.5 750 0.14 0.162 100 90 120 500
35 5.5 1.60 1.40 29.5 800 0.16 0.155 120 110 145 500
50 5.5 1.60 1.56 31.0 900 0.17 0.149 140 125 175 500
70 5.5 1.60 1.56 32.5 1,050 0.19 0.138 170 155 215 500
95 5.5 2.00 1.56 34.5 1,150 0.22 0.131 205 185 265 500
120 5.5 2.00 1.56 36.5 1,400 0.24 0.127 230 210 305 500
150 5.5 2.00 1.56 38.0 1,500 0.26 0.122 255 235 345 500
185 5.5 2.00 1.56 39.5 1,650 0.28 0.118 290 270 390 500
240 5.5 2.00 1.72 42.5 1,950 0.31 0.114 330 310 465 500
300 5.5 2.00 1.72 44.5 2,200 0.33 0.110 370 340 530 500
400 5.5 2.00 1.88 48.0 2,600 0.37 0.105 415 390 605 500
500 5.5 2.00 1.88 51.5 3,000 0.42 0.101 465 440 700 500
630 5.5 2.50 2.04 56.5 3,750 0.46 0.099 510 480 790 500
800 5.5 2.50 2.20 61.0 4,450 0.52 0.095 555 520 880 500
1000 5.5 2.50 2.20 65.5 5,200 0.58 0.092 595 560 970 500
Approx.Reactance
StandardDeliveryLength
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground AirDuct
NominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
MinimumOuter
SheathThickness
Approx.OverallCable
Diameter
Approx.Cable
Wt.
Approx.Capacitance
(Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
28 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 11 KV (UE) COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)
Construction :
Outer Sheath
Conductor ShieldInsulation Shield
Insulation
Conductor
Armour
14
25 5.5 1.60 1.40 28.5 900 0.14 0.162 130 115 155 500
35 5.5 1.60 1.40 29.5 1,000 0.16 0.155 155 140 185 500
50 5.5 1.60 1.56 31.0 1,200 0.17 0.149 180 160 225 500
70 5.5 1.60 1.56 32.5 1,450 0.19 0.138 210 200 280 500
95 5.5 2.00 1.56 34.5 1,700 0.22 0.131 260 240 340 500
120 5.5 2.00 1.56 36.5 2,050 0.24 0.127 290 270 390 500
150 5.5 2.00 1.56 38.0 2,350 0.26 0.122 325 300 440 500
185 5.5 2.00 1.56 39.5 2,750 0.28 0.118 365 335 500 500
240 5.5 2.00 1.72 42.5 3,350 0.31 0.114 415 385 585 500
300 5.5 2.00 1.72 44.5 3,950 0.33 0.110 460 430 660 500
400 5.5 2.00 1.88 48.0 4,850 0.37 0.105 505 470 740 500
500 5.5 2.00 1.88 51.5 5,900 0.42 0.101 560 520 850 500
630 5.5 2.50 2.04 56.5 7,450 0.46 0.099 600 560 935 500
800 5.5 2.50 2.20 61.0 9,200 0.52 0.095 640 600 1020 500
1000 5.5 2.50 2.20 65.5 11,200 0.58 0.092 675 630 1100 500
StandardDeliveryLength
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground AirDuct
Approx.Capacitance
Approx.Reactance
NominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
MinimumOuter
SheathThickness
Approx.OverallCable
Diameter
Approx.Cable
Wt.
(Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
28 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 11 KV (UE) ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)
Construction :
InsulationConductor
Conductor Shield
Insulation Shield Outer Sheath
Metallic Insulation Screen
15
25 5.5 2.0 26.0 600 0.14 0.154 100 95 120 500
35 5.5 2.0 27.0 650 0.16 0.147 120 115 145 500
50 5.5 2.0 28.0 700 0.17 0.141 140 130 170 500
70 5.5 2.0 29.5 800 0.19 0.130 175 160 215 500
95 5.5 2.0 31.5 950 0.22 0.123 205 190 260 500
120 5.5 2.2 33.5 1,050 0.24 0.120 235 215 300 500
150 5.5 2.2 35.0 1,200 0.26 0.116 260 240 340 506
185 5.5 2.2 36.5 1,350 0.28 0.111 295 275 390 500
240 5.5 2.2 38.5 1,550 0.31 0.106 340 320 460 500
300 5.5 2.2 41.0 1,800 0.33 0.103 385 360 530 500
400 5.5 2.4 44.5 2,150 0.37 0.099 435 410 615 500
500 5.5 2.4 47.5 2,550 0.42 0.095 500 470 725 500
630 5.5 2.6 52.0 3,100 0.46 0.092 570 535 840 500
800 5.5 2.8 57.0 3,750 0.52 0.090 640 605 975 500
1000 5.5 2.8 61.5 4,450 0.58 0.087 710 670 1100 500
StandardDeliveryLengthAirDuctGround
Approx.Reactance
Approx.Capacitance
Approx.Cable
Wt.
Approx.OverallCable
Diameter
NominalOuter
SheathThickness
DIMENSIONS ELECTRICAL PARAMETERS
Current RatingNominalArea of
Conductor
NominalInsulationThickness
(Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
DIMENSIONS
StandardDeliveryLengthAirDuctGround
Approx.Reactance
Approx.Capacitance
Approx.Cable
Wt.
Approx.OverallCable
Diameter
NominalOuter
SheathThickness
ELECTRICAL PARAMETERS
Current RatingNominalArea of
Conductor
NominalInsulationThickness
(Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
28 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 11 KV (UE) COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)
Construction :
Conductor ShieldInsulation Shield
Conductor
Insulation
Metallic Insulation Screen
Outer Sheath
16
25 5.5 2.0 26.0 750 0.14 0.154 130 120 150 500
35 5.5 2.0 27.0 850 0.16 0.147 155 145 185 500
50 5.5 2.0 28.0 950 0.17 0.141 180 170 220 500
70 5.5 2.0 29.5 1,200 0.19 0.130 220 205 275 500
95 5.5 2.0 31.5 1,500 0.22 0.123 265 245 335 500
120 5.5 2.2 33.5 1,750 0.24 0.120 300 275 385 500
150 5.5 2.2 35.0 2,050 0.26 0.116 335 310 440 500
185 5.5 2.2 36.5 2,400 0.28 0.111 380 350 500 500
240 5.5 2.2 38.5 2,950 0.31 0.106 435 410 590 500
300 5.5 2.2 41.0 3,550 0.33 0.103 490 460 675 500
400 5.5 2.4 44.5 4,400 0.37 0.099 555 515 775 500
500 5.5 2.4 47.5 5,400 0.42 0.095 625 580 910 500
630 5.5 2.6 52.0 6,850 0.46 0.092 705 660 1050 500
800 5.5 2.8 57.0 8,550 0.52 0.090 775 730 1185 500
1000 5.5 2.8 61.5 10,400 0.58 0.087 845 795 1310 500
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
StandardDeliveryLength
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground AirDuct
NominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
MinimumOuter
SheathThickness
Approx.OverallCable
Diameter
Approx.Cable
Wt.
Approx.Capacitance
Approx.Reactance
(Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
32 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 22 KV (E) ALUMINIUM CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)
Construction :
Conductor
Outer SheathInsulation ShieldConductor Shield
ArmourInsulation
17
35 6.0 1.60 1.40 31.0 900 0.15 0.158 120 105 150 500
50 6.0 1.60 1.56 32.5 1,000 0.16 0.153 140 125 175 500
70 6.0 1.60 1.56 34.0 1,100 0.18 0.141 170 155 215 500
95 6.0 2.00 1.56 36.5 1,350 0.21 0.134 200 185 265 500
120 6.0 2.00 1.56 38.0 1,450 0.22 0.129 230 215 305 500
150 6.0 2.00 1.56 39.5 1,600 0.24 0.125 255 235 345 500
185 6.0 2.00 1.56 41.0 1,750 0.26 0.120 285 265 395 500
240 6.0 2.00 1.72 44.0 2,050 0.29 0.116 325 305 460 500
300 6.0 2.00 1.72 46.0 2,300 0.31 0.112 365 340 530 500
400 6.0 2.00 1.88 49.5 2,700 0.35 0.107 410 380 605 500
500 6.0 2.50 2.04 54.0 3,350 0.39 0.104 450 420 690 500
630 6.0 2.50 2.04 58.0 3,900 0.43 0.101 500 460 800 500
800 6.0 2.50 2.20 62.5 4,600 0.48 0.097 545 500 890 500
1000 6.0 2.50 2.36 67.5 5,400 0.54 0.094 580 540 970 500
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
DIMENSIONS ELECTRICAL PARAMETERS
Current RatingStandardDeliveryLengthGround AirDuct
NominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
MinimumOuter
SheathThickness
Approx.OverallCable
Diameter
Approx.Cable
Wt.
Approx.Capacitance
Approx.Reactance
(Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
32 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 22 KV (E) COPPER CONDUCTOR XLPE INSULATED
ARMOURED CABLES
Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)
Construction :
Outer Sheath
Conductor ShieldInsulation Shield
Insulation
Conductor
Armour
18
35 6.0 1.60 1.40 31.0 1,100 0.15 0.158 150 135 190 500
50 6.0 1.60 1.56 32.5 1,250 0.16 0.153 175 165 225 500
70 6.0 1.60 1.56 34.0 1,500 0.18 0.141 220 200 280 500
95 6.0 2.00 1.56 36.5 1,900 0.21 0.134 255 235 335 500
120 6.0 2.00 1.56 38.0 2,150 0.22 0.129 290 265 390 500
150 6.0 2.00 1.56 39.5 2,450 0.24 0.125 320 300 435 500
185 6.0 2.00 1.56 41.0 2,850 0.26 0.120 360 330 500 500
240 6.0 2.00 1.72 44.0 3,450 0.29 0.116 405 380 580 500
300 6.0 2.00 1.72 46.0 4,050 0.31 0.112 455 425 660 500
400 6.0 2.00 1.88 49.5 4,950 0.35 0.107 500 470 755 500
500 6.0 2.50 2.04 54.0 6,200 0.39 0.104 545 500 835 500
630 6.0 2.50 2.04 58.0 7,600 0.43 0.101 590 550 940 500
800 6.0 2.50 2.20 62.5 9,400 0.48 0.097 630 590 1020 500
1000 6.0 2.50 2.36 67.5 11,400 0.54 0.094 660 620 1100 500
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
32 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 22 KV (E) ALUMINIUM CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)
Construction :
InsulationConductor
Conductor Shield
Insulation Shield Outer Sheath
Metallic Insulation Screen
19
Approx.Reactance
Approx.Capacitance
Approx.Cable
Wt.
Approx.OverallCable
Diameter
NominalOuter
SheathThickness
Current RatingNominalArea of
Conductor
NominalInsulationThickness
StandardDeliveryLength
ELECTRICAL PARAMETERSDIMENSIONS
(Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)
AirDuctGround
35 6.0 2.0 28.5 700 0.15 0.151 120 110 145 500
50 6.0 2.0 29.5 750 0.16 0.145 140 130 170 500
70 6.0 2.0 31.0 900 0.18 0.133 170 160 210 500
95 6.0 2.2 33.5 1,050 0.21 0.127 205 190 255 500
120 6.0 2.2 35.0 1,150 0.22 0.123 235 220 300 500
150 6.0 2.2 36.5 1,300 0.24 0.118 260 240 340 500
185 6.0 2.2 38.0 1,450 0.26 0.114 295 275 390 500
240 6.0 2.2 40.0 1,650 0.29 0.109 335 315 455 500
300 6.0 2.2 42.5 1,900 0.31 0.105 380 360 535 500
400 6.0 2.4 46.0 2,250 0.35 0.101 435 410 615 500
500 6.0 2.6 50.0 2,700 0.39 0.098 495 460 710 500
630 6.0 2.6 53.5 3,200 0.43 0.094 560 530 850 500
800 6.0 2.8 58.5 3,900 0.48 0.092 630 600 985 500
1000 6.0 3.0 63.5 4,650 0.54 0.089 700 660 1110 500
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
High Voltage Power Cable
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
32 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 22 KV (E) COPPER CONDUCTOR XLPE INSULATED
UNARMOURED CABLES
Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)
Construction :
Conductor ShieldInsulation Shield
Conductor
Insulation
Metallic Insulation Screen
Outer Sheath
20
(Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)
StandardDeliveryLengthAirDuctGround
Approx.Reactance
Approx.Capacitance
Approx.Cable
Wt.
Approx.OverallCable
Diameter
NominalOuter
SheathThickness
DIMENSIONS
Current RatingNominalArea of
Conductor
NominalInsulationThickness
ELECTRICAL PARAMETERS
35 6.0 2.0 28.5 900 0.15 0.151 155 140 185 500
50 6.0 2.0 29.5 1,050 0.16 0.145 180 170 220 500
70 6.0 2.0 31.0 1,300 0.18 0.133 220 205 275 500
95 6.0 2.2 33.5 1,600 0.21 0.127 260 245 330 500
120 6.0 2.2 35.0 1,850 0.22 0.123 295 275 385 500
150 6.0 2.2 36.5 2,150 0.24 0.118 330 310 430 500
185 6.0 2.2 38.0 2,500 0.26 0.114 375 350 500 500
240 6.0 2.2 40.0 3,050 0.29 0.109 430 410 580 500
300 6.0 2.2 42.5 3,650 0.31 0.105 485 465 680 500
400 6.0 2.4 46.0 4,500 0.35 0.101 550 515 780 500
500 6.0 2.6 50.0 5,600 0.39 0.098 610 575 900 500
630 6.0 2.6 53.5 6,950 0.43 0.094 700 655 1050 500
800 6.0 2.8 58.5 8,700 0.48 0.092 770 730 1190 500
1000 6.0 3.0 63.5 10,700 0.54 0.089 835 790 1320 500
-
Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019
General Cable Energy India Pvt. Ltd.
Connecting the WorldConnecting the World
Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.
High Voltage Power Cable
StandardDeliveryLength
DIMENSIONS ELECTRICAL PARAMETERS
Current Rating
Ground AirDuct
NominalArea of
Conductor
NominalInsulationThickness
NominalArmour
Wire Diameter
MinimumOuter
SheathThickness
Approx.OverallCable
Diameter
Approx.Cable
Wt.
Approx.Capacitance
Approx.Reactance
(Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z
I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C
Temperature Rating :
* Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.
? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing
Features & Benefits : IS : 7098 Part -2Reference Standard :
48 KV (AC) for 5 minutes.H.V. Test Voltage :
Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.
Application :
FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.
Options :
SINGLE CORE 33 KV (E) ALUM