gci ht catalogue

92
High Voltage Cable Connecting the World

Upload: mohit-chowdary-n

Post on 23-Nov-2015

31 views

Category:

Documents


1 download

DESCRIPTION

Catalouge

TRANSCRIPT

  • High Voltage Cable

    Connecting the World

  • High Voltage Servicing Utility, Industrial, CommercialAnd Specialty Applications

    This new catalog contains in-depth information on the most comprehensive line of High Voltage Power Cable available today.

    The spec-on-a-page format was developed to meet your needs. It features up-to-the-minute product information, from applications and constructions to detailed technical and specification data. Theres also a glossary of technical terms for additional assistance.

    And, of course, if you need any further data, General Cable's Customer Service staff provides the answer you need quickly and efficiently.

    All information in this catalog is presented solely as a guide product selection and is believed to be reliable. All printing errors are subject to correction in subsequent releases of this catalog. Although General Cable has taken precautions to ensure the accuracy of the product specifications at the time of publication, the specifications of all products contained herein are subject to change without notice.

    E-mail: [email protected]

    General Cable Energy India Pvt LtdCorporate office: Centrum Plaza, Level 3, Tower A, 312 S, Golf Course Road, Sector- 53, Gurgaon-122 002, Haryana. Phone: (0124) 4326000 Fax: (0124) 4326019

    Connecting the WorldConnecting the World

    INTERNATIONALISO 9001:2000CERTIFICATION

  • General Cable Corporation, headquartered in Highland Heights Kentucky, a USD 6.2 billion revenue and over 13000 associates, is a world leader in cable manufacturing with 46 modern production facilities in North America, Europe and rest of the world and provides service to global network of clients.

    General Cable is a leader in the development, design, manufacture, marketing and distribution from power cables to telecommunication cables including electric cables for utility , buildings, data transmission, instrumentation, optic fiber cables, submarine cables, control and special cables and extra high voltage cables for market segments namely Energy, Industrial & Specialty, and Communication.

    General Cable's breadth of products is very extensive, including IS, IEC, IEEE, VDE, and other international standards covering entire range of cable products.

    General Cable has best- in- class research and development, testing and production facilities worldwide. The development of unique compounds designed and tested to meet specific needs and stringent specifications, differentiates General Cable from all others. With superior R&D, engineering and manufacturing, leading logistics capabilities, the broadest product range in all the industry segments, with a strong group of associates seamlessly teaming up to satisfy customers worldwide, makes General Cable as world leader in wire and cable. General Cable bases its activities on a series of Corporate Values which guide all its operations: Customer Satisfaction as an absolute priority; Integrity in all of its actions; People as the main source of value; Teamwork as a path to excellence; speed of delivery as a competitive advantage; and continuous improvement as a constant objective.

    This philosophy can only be assumed by a global company such as General Cable with extremely broad, diversified range, able to meet any requirement, however specific, anywhere on the planet. General Cable India is catering to Indian customer through its state of the art modern facility in 20 acre (Approx 80937 sq. mtrs) situated at the Industrial town of Baddi in the beautiful state of Himachal Pradesh. The range of products manufactured includes low voltage, high voltage, and extra high voltage and specialty cables. General Cable has extensive sales network across India.

    One of the world's biggest companies in the Cable and Wire Industry...

  • Connecting the WorldConnecting the World

    General Cables Global Reach

    General Cable serves customers through a global network of 46 manufacturing facilities in 23 countries

    and sales representatives and distribution centers worldwide. The Company is solely dedicated to the

    production of high-quality energy, industrial, specialty and communications wire and cable products. In

    addition to its breadth of product line and strong brand recognition, the Company offers competitive

    strengths in such areas as technology, manufacturing, distribution and logistics, and sales and customer

    service. This combination enables General Cable to better serve its customers as they expand into new

    geographic markets.

    International CorpNSW

    BRAND

    General Cable Footprint

  • Connecting the WorldConnecting the World

    General Cable is a leader in the development,

    design, manufacture, marketing and

    distribution of copper, aluminum and fiber

    optic wire and cable for the energy, industrial,

    specialty and communications markets.

    Our products inspire progress worldwide......Customers use our value-added products to

    create global infrastructure that improves the

    standard of living for people everywhere.

    Each day were bui lding business

    momentum- developing ideas into innovative

    solutions and industry-leading products,

    expanding geographic access and furthering

    our investment in highly capable associates,

    Lean Manufacturing, material science and

    technology resources.

    General Cable is influencing the world...with more than two-thirds of our sales generated outside North America and more than 13,000 associates in 46 manufacturing facilities throughout 23 countries. As the fifth largest wire and cable manufacturer, we are the One Company Connecting the World.

    Energy CablesOur cables carry energy across the world-through the air, underground and under the sea. Increasing demand for energy is accelerating investment in exploration, extraction, power generation, transmission and distribution- whether based on coal, natural gas, oil, nuclear, wind or water.

    Industrial & Specialty CablesWe have the competitive product mix and global reach to support the production of oil, gas and petrochemical; construction of new factories and maintenance of existing industrial facilities; factory automation; and special applications such as military, nuclear, marine, mining, transit and automotive.

    Communications CablesOur cables keep information flowing- facilitating a non-stop stream of words and images around the world. We meet the high-speed bandwidth needs of global communications networks from fiber optic, submarine communications cables, copper and fiber aerial and underground cables to copper and fiber optic enterprise cables and system solutions.

    India Headquarters General Cable Energy India Pvt LtdCorporate office: Centrum Plaza, Level 3, Tower A, 312 S, Golf Course Road, Sector- 53, Gurgaon-122 002, Haryana. Phone: (0124) 4326000 Fax: (0124) 4326019 E-mail: [email protected]

    World HeadquartersGeneral Cable4 Tesseneer DriveHighland Heights, KY41076-9753 U.S.A

    Directing Traffic without Gridlock

    Building Bridges in the Sky

    Making Contact with the World

  • Connecting the WorldConnecting the World

    Quality is Forethought.General Cable is committed to exceeding our customers expectations for quality and performance.

    We strive to ensure this quality through extensive in-house and third-party testing, with strict adherence

    to our product specification and industry standards. At General Cable, quality is not just a process, it

    is forethought. It is the forethought of using the best materials and proactive prevention. This level of

    quality is best represented in three core steps: Design, Technology and Control.

    General Cable Corporation is committed to developing, producing and marketing products that meet

    the performance, quality, value and safety requirements of our customers by continuously improving all

    areas of our business. We apply Lean Sigma Company-wide, seeking innovative ways to differentiate our

    products and services and to serve as our customers and suppliers most valued business partner.

    DesignDesignControlControl

    TechnologyTechnology

    QualityQuality

    International CorpNSW

  • Connecting the WorldConnecting the World

    Commitment to QualityIndian cable industry is highly saturated with various organised / unorganised cable manufacturers.

    The fierce competition leading to price war, may result into dilution in quality of product.

    Under this scenario General Cable is giving maximum emphasis on quality of its cable products

    and there by ensuring uninterrupted production to industries, safety to equipments and personnel.

    Quality Assurance Guaranteed

    Through an ongoing quality assurance initiative, General Cable ensures the quality of product design,

    manufacture, installation and expected service life, as well as environmentally sound products, processes

    and policies, continuous research and development, combined with process control, quality audits and

    prolonged stringent testing, provide an ever-growing range of specialty materials and designs that meet

    industry approvals and standards.

    Aerial view of General Cable factory at Baddi, H.P., India

    BRAND

  • Connecting the WorldConnecting the World

    Our Green Initiative symbol recognizes our role

    and responsibility in promoting sustainability.

    The symbol also reflects our commitment to achieving

    industry-leading standards and responding

    proactively to environmental global issues.

    IN T I N IE ATE IR VG E

    Commitment To Environment - Green FactoryCompliant to Indian Green Building Council Rating

    Commitment To Environment - Green FactoryCompliant to Indian Green Building Council Rating

    International CorpNSW

  • Products for all

    markets

    Connecting the WorldConnecting the World

    BRAND

  • SM

    Underground High-Voltage and Extra-High-Voltage CablesGeneral Cables complete line of Silec insulatedhigh- and extra-high-voltage underground energycables, from 63kV up to 500kV, and our state-of the-art accessories - such as pre-molded joints and terminals - enable us to provide turnkey design and engineering services for the global, systems engineered, electric utility market.

    Bare Overhead High-Voltage Transmission andDistribution ConductorsOur TransPowr bare aluminum overhead conductors are available in standard ACSR, specialized T-2 designs and high temperature ACSS/TW designs. Our new ACCC/TW conductors feature an innovative composite core construction which possesses high temperature and increased strength characteristics.

    Low- and Medium-Voltage Distribution CablesGeneral Cables extensive line of BICC BrandPowrServ and EmPowr copper and aluminumcables serve the total distribution needs of electric utilities, rural electric co-ops and the public power market for both traditional and renewable energy resources.

    Industrial CablesGeneral Cables industrial instrumentation, powerand control cables serve an extensive range ofmarkets including power generation, refining andpetrochemical, natural gas production, steel, pulp and paper, and factory automation.

    Specialty CablesGeneral Cable manufactures a broad range of specialty cables that meet the exacting specifications for original equipment manufacturers (OEMs), military, transit, offshore and marine shipboard, nuclear, and mining applications. General Cables engineered Brand Rex and Anaconda Brand wire and cable solutions provide great lifecycle performance and reliability - meeting customer applications requirements today, while setting tomorrows standards.

    Energy Cables Industrial & Specialty Cables

  • Specialty Wire HarnessesWe supply application-specific and custom-designed cable, harnesses and assemblies for a wide variety of OEM applications, including business machines, material handling equipment, factory automation, medical equipment and the automotive aftermarket. General Cable is a global leader in the manufacture of automotive wire and cablefrom ignition wire sets and single leads to bulk ignition wire, primary wire and battery starter cable.

    Cord and Cordset ProductsGeneral Cables Carol Brand is the most recognized name in flexible cords for temporary power. Our extensive line includes portable cord, cordsets, portable power cable and premium-grade cable for commercial and industrial applications.

    Electronic CablesOur Carol Brand and Helix/HiTemp products fulfill the complete wire and cable requirements of the fast-changing electronics, sound and security marketplaces. We offer hookup wire; communications cable; computer, coaxial and microphone cables; and special designs for security systems, fire alarms, and audio, video and digital broadcasts.

    Communications CablesData Communications CablesOur GenSPEED Brand products are on the job wherever enhanced performance is criticalfrom Gigabit Ethernet, token ring and broadband applications to patch panels, communications closets and plenum applications.We offer one of the most comprehensive lines of enhanced high-speed Category products, including PanGen structured cabling system solutions.

    Fiber Optic CablesWe provide a full menu of NextGen Brand fiber optic cables for data communications and voice and video networks. Our products range from tight buffer and armored products for military applications to loose tube and hybrid cables for communications networks. We also offer advanced Blolite blown fiber systems for Local Area Networks and campus applications.

    Telecommunications CablesOur broad range of industry-standard General Cable outside plant wire and cable products ensures reliable, cost-effective performance. We provide air core, filled core and specialty wire products for aerial, buried and duct applications.

    Now one industry leader focuses its worldwide resources on delivering maximum value to customers. Its the cost-effective advantage of a single resource, a single company that provides the broadest product range, the highest level of commitment to customer and technical support, the most cost-effective manufacturing and distribution, and the

    most responsive customer-first service. In todays highly competitive worldwide markets, General Cable provides the single-source solution with benefits that go straight to your bottom line. Ask your representative about other General Cable products.

    International Corp NSW

    BRAND

  • CONNECTING THE WORLD

    Making Cables is about Creating Potential

    General Cable products help to illuminate the world, inspire progress and open lines of communication. We connect people with energy, information, ideas and opportunities.

    For more than a century, General Cable has been a leader in the development, manufacture, marketing and distribution ofwire and cable-our sole business. Today, we continue to direct our worldwide resources to deliver maximum value to customers through a powerful combination of product and service innovations.

    At General Cable we aim to add value to our customers businesses by understanding and competitively servicing their needs through customer intimacy operational excellence.

    General Cable provides a single source solutionThe cost effective advantage of a single resource, a single company that provides one of the broadest product ranges, highest levels of customer and technical support and responsive customer-first service.

    THE POWER OF ONEAt General Cable, THE POWER OF ONE embodies our integrated approach to business: one company with the power of our products, expertise, systems and people all focused on one goal - fulfilling our customers needs. It means one source customers can count on for DATA, COMMUNICATION, INDUSTRIAL and ENERGY cables. Most of all, THE POWER OF ONE means one team, well trained and wholly committed to the highest level of customer satisfaction.

  • Manufacturing and logistics

    With superior engineering and manu fac tu r i ng ope ra t i ons , i n d u s t r y - l e a d i n g l o g i s t i c s capabilities, one of the broadest product ranges in the industry, and a strong group of employees seamlessly teaming to satisfy customers, General Cable is strong, diversified and well positioned to meet the challenges of tomorrow.

    Sales and Distribution Network

    General Cable has a distribution network throughout India and a team of people committed to meeting the total needs of our customers- by providing enhanced distribution and warehousing services, and an unprecedented level of technical support.

    Strength, Diversity and Teamwork

    Every product reflects our POWER OF ONE business philosophy. We have become a leading cable supplier in Asla pacific through excellent customer relationships, the quality of our people and the highest standards of service.

    GENERAL CABLE INDIA

    Quality Products, People and Service

    Connecting the WorldConnecting the World

    OUR VISIONStrive for leadership through growth and excellence.

    General Cable India is a leading supplier of cable solutions for energy, industrial, data, communications and specialist applications. As part of the US based General Cable Corporation (one of the worlds largest wire and cable manufacturers) we serve customers through a global network of forty six manufacturing facilities in twenty three countries, with sales and distribution centers worldwide.

    As part of a global business we are able to draw on innovative engineering developments, a comprehensive product range and the best research and technical support available, ensuring our customers are offered a competitive edge.

  • High Voltage Cable

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    PRODUCT SELECTION LOCATOR

    TYPE LETTER CODE REFERENCE STANDARD CABLE DESCRIPTION PAGE NO.HV CABLES

    TECHNICAL INFORMATION 49 - 73

    IS : 7098 Part - 2

    IS : 7098 Part - 2

    IS : 7098 Part - 2

    IS : 7098 Part - 2

    IS : 7098 Part - 2

    IS : 7098 Part - 2

    IS : 7098 Part - 2

    IS : 7098 Part - 2

    IS : 7098 Part - 2

    IS : 7098 Part - 2

    2XWaY

    2XY

    A2XWaY

    A2XY 1 - 43.3 KV, Single Core XLPE

    Power CablesIS : 7098 Part - 2

    5 - 86.6 KV(E), Single Core XLPE Power Cables2XWaYA2XY

    A2XWaY

    2XY

    A2XFY2XFY

    A2XWY2XWY

    A2XFY2XFY

    A2XWY2XWY

    A2XFY2XFY

    A2XWY2XWY

    A2XFY2XFY

    A2XWY2XWY

    A2XFY2XFY

    A2XWY2XWY

    A2XFY2XFY

    A2XWY2XWY

    2XWaY

    2XY

    A2XWaY

    A2XY

    2XWaY

    2XY

    A2XWaY

    A2XY

    2XWaY

    2XY

    A2XWaY

    A2XY

    2XWaY

    2XY

    A2XWaY

    A2XY

    IS : 7098 Part - 2 33 KV(E), Three Core XLPE Armoured Power Cables

    22 KV(E), Three Core XLPE Armoured Power Cables

    11 KV(E), Three Core XLPE Armoured Power Cables

    6.6 KV(E), Three Core XLPE Armoured Power Cables

    3.3 KV, Three Core XLPE Armoured Power Cables

    33 KV(E), Single Core XLPE Power Cables

    22 KV(E), Single Core XLPE Power Cables

    11 KV (E), Single Core XLPE Power Cables

    45 - 48

    41 - 44

    37 - 40

    33 - 36

    29 - 32

    25 - 28

    21 - 24

    17 - 20

    13 - 16

    9 - 12

    11 KV(UE), Three Core XLPE Armoured Power Cables

    11 KV(UE), Single Core XLPE Power Cables

  • General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    Conductor : Round Compact Stranded AluminiumInsulation : Cross - Linked Polyethylene (XLPE)Armour : Round Aluminium Wires Outer Sheath : Black PVC (Type - ST2)

    Construction :I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces #? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    10 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.# Applicable for Screened cables, available upon request.

    Options :

    SINGLE CORE 3.3 KV (E) & (UE) ALUMINIUM CONDUCTOR XLPE INSULATED

    ARMOURED CABLES

    Conductor

    Outer Sheath

    Armour

    Insulation

    1

    25 2.5 1.4 1.24 19.0 350 0.23 0.136 100 90 115 500

    35 2.5 1.4 1.24 20.0 400 0.26 0.130 120 110 140 500

    50 2.5 1.4 1.40 21.0 450 0.29 0.125 140 125 165 500

    70 2.5 1.6 1.40 23.0 600 0.34 0.116 170 155 210 500

    95 2.5 1.6 1.40 25.0 700 0.39 0.110 205 180 250 500

    120 2.5 1.6 1.40 26.5 800 0.43 0.106 230 205 290 500

    150 2.5 1.6 1.40 28.0 900 0.47 0.103 255 225 335 500

    185 2.5 1.6 1.40 29.5 1,050 0.52 0.099 290 255 395 500

    240 2.5 1.6 1.56 32.0 1,250 0.58 0.096 330 295 450 500

    300 2.6 1.6 1.56 34.5 1,500 0.62 0.093 370 330 510 500

    400 2.6 2.0 1.56 38.0 1,850 0.70 0.090 415 370 610 500

    500 2.8 2.0 1.56 42.0 2,250 0.74 0.088 465 425 695 500

    630 3.1 2.0 1.72 46.5 2,800 0.76 0.086 520 480 795 500

    800 3.3 2.0 1.88 52.0 3,500 0.81 0.085 560 520 880 500

    1000 3.6 2.5 2.04 58.5 4,450 0.84 0.085 600 550 980 500

    (Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z

    StandardDeliveryLength

    DIMENSIONS ELECTRICAL PARAMETERS

    Current Rating

    Ground AirDuct

    NominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    MinimumOuter

    SheathThickness

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    Approx.Capacitance

    Approx.Reactance

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    Conductor : Round Compact Stranded Plain CopperInsulation : Cross - Linked Polyethylene (XLPE)Armour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Conductor

    Outer Sheath

    Armour

    Insulation

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces #? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    10 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.# Applicable for Screened cables, available upon request.

    Options :

    SINGLE CORE 3.3 KV (E) & (UE)COPPER CONDUCTOR XLPE INSULATED

    ARMOURED CABLES

    2

    25 2.5 1.4 1.24 19.0 500 0.23 0.136 125 115 145 500

    35 2.5 1.4 1.24 20.0 600 0.26 0.130 150 135 175 500

    50 2.5 1.4 1.40 21.0 750 0.29 0.125 175 155 210 500

    70 2.5 1.6 1.40 23.0 1,000 0.34 0.116 220 190 255 500

    95 2.5 1.6 1.40 25.0 1,250 0.39 0.110 255 230 320 500

    120 2.5 1.6 1.40 26.5 1,500 0.43 0.106 295 260 370 500

    150 2.5 1.6 1.40 28.0 1,750 0.47 0.103 325 290 425 500

    185 2.5 1.6 1.40 29.5 2,100 0.52 0.099 365 325 480 500

    240 2.5 1.6 1.56 32.0 2,650 0.58 0.096 415 375 565 500

    300 2.6 1.6 1.56 34.5 3,250 0.62 0.093 460 420 645 500

    400 2.6 2.0 1.56 38.0 4,100 0.70 0.090 515 470 750 500

    500 2.8 2.0 1.56 42.0 5,150 0.74 0.088 565 520 850 500

    630 3.1 2.0 1.72 46.5 6,550 0.76 0.086 615 575 950 500

    800 3.3 2.0 1.88 52.0 8,250 0.81 0.085 645 600 1030 500

    1000 3.6 2.5 2.04 58.5 10,400 0.84 0.085 675 630 1110 500

    StandardDeliveryLengthGround AirDuct

    DIMENSIONS ELECTRICAL PARAMETERS

    Current RatingNominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    MinimumOuter

    SheathThickness

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    Approx.Capacitance

    Approx.Reactance

    (Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    Conductor : Round Compact Stranded AluminiumInsulation : Cross - Linked Polyethylene (XLPE)Screen : Copper Tape Outer Sheath : Black PVC (Type - ST2)

    Construction :

    Conductor

    Outer Sheath

    Screen

    Insulation

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces #? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    10 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.# Applicable for Screened cables, available upon request.

    Options :

    SINGLE CORE 3.3 KV (E) & (UE) ALUMINIUM CONDUCTOR XLPE INSULATED

    UNARMOURED CABLES

    3

    25 2.2 1.8 16.0 250 0.26 0.125 100 90 110 500

    35 2.2 1.8 17.0 300 0.29 0.119 115 100 135 500

    50 2.2 1.8 18.0 350 0.32 0.114 135 120 160 500

    70 2.2 1.8 19.5 400 0.38 0.105 170 155 195 500

    95 2.2 2.0 22.0 550 0.44 0.102 200 185 250 500

    120 2.2 2.0 23.5 600 0.48 0.098 225 210 280 500

    150 2.2 2.0 25.0 700 0.53 0.095 255 230 325 500

    185 2.2 2.0 26.5 850 0.58 0.092 285 260 370 500

    240 2.2 2.0 29.0 1,000 0.65 0.089 330 300 440 500

    300 2.2 2.0 31.0 1,200 0.72 0.086 375 330 510 500

    400 2.2 2.2 34.5 1,550 0.82 0.084 425 380 600 500

    500 2.4 2.2 38.5 1,900 0.85 0.082 480 430 700 500

    630 2.6 2.2 42.5 2,350 0.90 0.080 540 500 830 500

    800 2.8 2.4 47.5 2,950 0.94 0.079 620 540 950 500

    1000 3.0 2.6 53.0 3,700 0.99 0.078 685 600 1080 500

    StandardDeliveryLengthAirDuctGround

    Approx.Reactance

    Approx.Capacitance

    Approx.Cable

    Wt.

    Approx.OverallCable

    Diameter

    NominalOuter

    SheathThickness

    DIMENSIONS ELECTRICAL PARAMETERS

    Current RatingNominalArea of

    Conductor

    NominalInsulationThickness

    (Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces #? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    10 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.# Applicable for Screened cables, available upon request.

    Options :

    Conductor

    Outer Sheath

    Screen

    Insulation

    SINGLE CORE 3.3 KV (E) & (UE) COPPER CONDUCTOR XLPE INSULATED

    UNARMOURED CABLES

    Conductor : Round Compact Stranded Plain CopperInsulation : Cross - Linked Polyethylene (XLPE)Screen : Copper Tape Outer Sheath : Black PVC (Type - ST2)

    Construction :

    4

    25 2.2 1.8 16.0 400 0.26 0.125 125 115 140 500

    35 2.2 1.8 17.0 500 0.29 0.119 150 140 170 500

    50 2.2 1.8 18.0 600 0.32 0.114 175 160 200 500

    70 2.2 1.8 19.5 800 0.38 0.105 220 200 250 500

    95 2.2 2.0 22.0 1,100 0.44 0.102 260 235 310 500

    120 2.2 2.0 23.5 1,300 0.48 0.098 290 270 360 500

    150 2.2 2.0 25.0 1,550 0.53 0.095 330 300 420 500

    185 2.2 2.0 26.5 1,900 0.58 0.092 370 335 470 500

    240 2.2 2.0 29.0 2,400 0.65 0.089 425 385 560 500

    300 2.2 2.0 31.0 3,000 0.72 0.086 480 430 650 500

    400 2.2 2.2 34.5 3,800 0.82 0.084 540 490 760 500

    500 2.4 2.2 38.5 4,800 0.85 0.082 605 545 870 500

    630 2.6 2.2 42.5 6,100 0.90 0.080 675 600 1000 500

    800 2.8 2.4 47.5 7,750 0.94 0.079 745 660 1140 500

    1000 3.0 2.6 53.0 9,700 0.99 0.078 810 715 1260 500

    StandardDeliveryLengthAirDuctGround

    Approx.Reactance

    Approx.Capacitance

    Approx.Cable

    Wt.

    Approx.OverallCable

    Diameter

    NominalOuter

    SheathThickness

    DIMENSIONS ELECTRICAL PARAMETERS

    Current RatingNominalArea of

    Conductor

    NominalInsulationThickness

    (Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.

    High Voltage Power Cable

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    12 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 6.6 KV (E) ALUMINUM CONDUCTOR XLPE INSULATED

    ARMOURED CABLES

    Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Conductor

    Outer SheathInsulation ShieldConductor Shield

    ArmourInsulation

    5

    25 2.8 1.6 1.40 23.0 500 0.23 0.148 100 90 120 500

    35 2.8 1.6 1.40 24.0 550 0.26 0.141 120 110 145 500

    50 2.8 1.6 1.40 25.0 650 0.28 0.136 140 125 170 500

    70 2.8 1.6 1.40 26.5 750 0.32 0.125 170 155 215 500

    95 2.8 1.6 1.40 28.5 850 0.37 0.119 205 180 260 500

    120 2.8 1.6 1.40 30.0 1,000 0.41 0.114 230 210 300 500

    150 2.8 1.6 1.56 32.0 1,100 0.45 0.111 255 230 340 500

    185 2.8 1.6 1.56 33.5 1,250 0.49 0.107 290 260 390 500

    240 2.8 2.0 1.56 36.5 1,550 0.54 0.104 330 300 460 500

    300 3.0 2.0 1.56 39.0 1,800 0.56 0.101 370 340 520 500

    400 3.3 2.0 1.72 43.0 2,200 0.58 0.098 415 385 600 500

    500 3.5 2.0 1.72 47.0 2,650 0.62 0.095 465 430 690 500

    630 3.5 2.0 1.88 51.0 3,200 0.69 0.092 520 480 815 500

    800 3.5 2.5 2.04 56.5 4,000 0.78 0.091 560 520 890 500

    1000 3.6 2.5 2.20 62.0 4,800 0.85 0.089 600 550 985 500

    DIMENSIONS

    StandardDeliveryLength

    ELECTRICAL PARAMETERS

    Current Rating

    Ground AirDuct

    NominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    MinimumOuter

    SheathThickness

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    Approx.Capacitance

    Approx.Reactance

    (Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.

    High Voltage Power Cable

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    12 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 6.6 KV (E) COPPER CONDUCTOR XLPE INSULATED

    ARMOURED CABLES

    Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Outer Sheath

    Conductor ShieldInsulation Shield

    Insulation

    Conductor

    Armour

    6

    25 2.8 1.6 1.40 23.0 650 0.23 0.148 130 115 155 500

    35 2.8 1.6 1.40 24.0 800 0.26 0.141 155 135 185 500

    50 2.8 1.6 1.40 25.0 900 0.28 0.136 180 155 220 500

    70 2.8 1.6 1.40 26.5 1,150 0.32 0.125 220 195 275 500

    95 2.8 1.6 1.40 28.5 1,400 0.37 0.119 260 230 330 500

    120 2.8 1.6 1.40 30.0 1,650 0.41 0.114 290 265 380 500

    150 2.8 1.6 1.56 32.0 1,950 0.45 0.111 330 295 435 500

    185 2.8 1.6 1.56 33.5 2,350 0.49 0.107 365 330 500 500

    240 2.8 2.0 1.56 36.5 2,950 0.54 0.104 415 380 575 500

    300 3.0 2.0 1.56 39.0 3,600 0.56 0.101 460 425 650 500

    400 3.3 2.0 1.72 43.0 4,450 0.58 0.098 510 470 740 500

    500 3.5 2.0 1.72 47.0 5,550 0.62 0.095 560 525 835 500

    630 3.5 2.0 1.88 51.0 6,950 0.69 0.092 615 575 960 500

    800 3.5 2.5 2.04 56.5 8,800 0.78 0.091 640 600 1020 500

    1000 3.6 2.5 2.20 62.0 10,800 0.85 0.089 675 625 1105 500

    MinimumOuter

    SheathThickness

    StandardDeliveryLength

    DIMENSIONS ELECTRICAL PARAMETERS

    Current Rating

    Ground AirDuct

    NominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    Approx.Capacitance

    Approx.Reactance

    (Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    12 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 6.6 KV (E) ALUMINIUM CONDUCTOR XLPE INSULATED

    UNARMOURED CABLES

    Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)

    Construction :

    InsulationConductor

    Conductor Shield

    Insulation Shield Outer Sheath

    Metallic Insulation Screen

    7

    25 2.8 1.8 20.0 350 0.23 0.137 100 90 115 500

    35 2.8 2.0 21.5 450 0.26 0.132 120 110 140 500

    50 2.8 2.0 22.5 500 0.28 0.127 140 130 165 500

    70 2.8 2.0 24.0 600 0.32 0.116 175 160 210 500

    95 2.8 2.0 26.0 700 0.37 0.111 205 190 255 500

    120 2.8 2.0 27.5 800 0.41 0.107 230 215 295 500

    150 2.8 2.0 29.0 900 0.45 0.104 260 240 335 500

    185 2.8 2.0 30.5 1,000 0.49 0.099 295 275 385 500

    240 2.8 2.2 33.0 1,250 0.54 0.096 340 315 455 500

    300 3.0 2.2 36.0 1,500 0.56 0.095 380 355 525 500

    400 3.3 2.2 39.5 1,800 0.58 0.092 435 405 610 500

    500 3.5 2.4 43.5 2,250 0.62 0.089 495 460 710 500

    630 3.5 2.4 47.5 2,700 0.69 0.087 570 530 840 500

    800 3.5 2.6 52.5 3,350 0.78 0.085 640 600 985 500

    1000 3.6 2.8 57.5 4,100 0.85 0.083 705 660 1110 500

    StandardDeliveryLengthAirDuctGround

    Approx.Reactance

    Approx.Capacitance

    Approx.Cable

    Wt.

    Approx.OverallCable

    Diameter

    NominalOuter

    SheathThickness

    DIMENSIONS ELECTRICAL PARAMETERS

    Current RatingNominalArea of

    Conductor

    NominalInsulationThickness

    (Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    12 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    25 2.8 1.8 20.0 500 0.23 0.137 130 120 150 500

    35 2.8 2.0 21.5 600 0.26 0.132 155 140 180 500

    50 2.8 2.0 22.5 750 0.28 0.127 180 165 215 500

    70 2.8 2.0 24.0 950 0.32 0.116 220 200 270 500

    95 2.8 2.0 26.0 1,250 0.37 0.111 265 240 325 500

    120 2.8 2.0 27.5 1,500 0.41 0.107 300 275 375 500

    150 2.8 2.0 29.0 1,750 0.45 0.104 335 310 430 500

    185 2.8 2.0 30.5 2,100 0.49 0.099 375 350 495 500

    240 2.8 2.2 33.0 2,650 0.54 0.096 435 410 580 500

    300 3.0 2.2 36.0 3,250 0.56 0.095 490 450 670 500

    400 3.3 2.2 39.5 4,050 0.58 0.092 550 515 770 500

    500 3.5 2.4 43.5 5,150 0.62 0.089 615 570 890 500

    630 3.5 2.4 47.5 6,450 0.69 0.087 700 650 1050 500

    800 3.5 2.6 52.5 8,150 0.78 0.085 770 720 1190 500

    1000 3.6 2.8 57.5 10,100 0.85 0.083 840 780 1320 500

    Conductor ShieldInsulation Shield

    Conductor

    Insulation

    Metallic Insulation Screen

    Outer Sheath

    SINGLE CORE 6.6 KV (E) COPPER CONDUCTOR XLPE INSULATED

    UNARMOURED CABLES

    Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)

    Construction :

    8

    StandardDeliveryLengthAirDuctGround

    Approx.Reactance

    Approx.Capacitance

    Approx.Cable

    Wt.

    Approx.OverallCable

    Diameter

    NominalOuter

    SheathThickness

    DIMENSIONS ELECTRICAL PARAMETERS

    Current RatingNominalArea of

    Conductor

    NominalInsulationThickness

    (Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.

    High Voltage Power Cable

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    17 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 11 KV (E) ALUMINIUM CONDUCTOR XLPE INSULATED

    ARMOURED CABLES

    Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Conductor

    Outer SheathInsulation ShieldConductor Shield

    ArmourInsulation

    9

    25 3.6 1.60 1.40 24.5 600 0.19 0.152 100 90 120 500

    35 3.6 1.60 1.40 25.5 650 0.21 0.145 120 110 145 500

    50 3.6 1.60 1.40 26.5 700 0.23 0.139 140 125 170 500

    70 3.6 1.60 1.40 28.5 800 0.27 0.129 170 155 215 500

    95 3.6 1.60 1.40 30.0 950 0.30 0.122 205 185 260 500

    120 3.6 1.60 1.56 32.0 1,100 0.33 0.118 230 210 300 500

    150 3.6 1.60 1.56 33.5 1,200 0.36 0.114 255 230 340 500

    185 3.6 2.00 1.56 36.0 1,450 0.39 0.112 290 260 390 500

    240 3.6 2.00 1.56 38.0 1,650 0.44 0.107 330 300 460 500

    300 3.6 2.00 1.56 40.5 1,900 0.48 0.104 370 335 530 500

    400 3.6 2.00 1.72 43.5 2,250 0.54 0.099 415 380 605 500

    500 3.6 2.00 1.72 47.0 2,650 0.60 0.095 460 430 685 500

    630 3.6 2.00 1.88 51.0 3,200 0.68 0.092 515 485 800 500

    800 3.6 2.50 2.04 57.0 4,000 0.76 0.091 555 520 890 500

    1000 3.6 2.50 2.20 62.0 4,800 0.85 0.089 600 550 990 500

    StandardDeliveryLength

    DIMENSIONS ELECTRICAL PARAMETERS

    Current Rating

    Ground AirDuct

    Approx.Capacitance

    Approx.Reactance

    NominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    MinimumOuter

    SheathThickness

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    (Mtr./Drum)(Amp) (Amp)(Amp)(F/km) Z(Sqmm) (mm) (mm) (mm) (mm) (Kg/km)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.

    High Voltage Power Cable

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    17 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 11 KV (E) COPPER CONDUCTOR XLPE INSULATED

    ARMOURED CABLES

    Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Outer Sheath

    Conductor ShieldInsulation Shield

    Insulation

    Conductor

    Armour

    10

    25 3.6 1.60 1.40 24.5 700 0.19 0.152 130 115 155 500

    35 3.6 1.60 1.40 25.5 850 0.21 0.145 150 135 185 500

    50 3.6 1.60 1.40 26.5 1,000 0.23 0.139 180 160 220 500

    70 3.6 1.60 1.40 28.5 1,200 0.27 0.129 220 200 275 500

    95 3.6 1.60 1.40 30.0 1,500 0.30 0.122 260 230 330 500

    120 3.6 1.60 1.56 32.0 1,750 0.33 0.118 295 265 385 500

    150 3.6 1.60 1.56 33.5 2,050 0.36 0.114 325 300 435 500

    185 3.6 2.00 1.56 36.0 2,500 0.39 0.112 365 330 495 500

    240 3.6 2.00 1.56 38.0 3,050 0.44 0.107 415 380 585 500

    300 3.6 2.00 1.56 40.5 3,650 0.48 0.104 460 425 660 500

    400 3.6 2.00 1.72 43.5 4,500 0.54 0.099 510 470 745 500

    500 3.6 2.00 1.72 47.0 5,550 0.60 0.095 560 525 835 500

    630 3.6 2.00 1.88 51.0 6,950 0.68 0.092 615 570 960 500

    800 3.6 2.50 2.04 57.0 8,800 0.76 0.091 640 590 1030 500

    1000 3.6 2.50 2.20 62.0 10,800 0.85 0.089 670 620 1110 500

    StandardDeliveryLengthGround AirDuct

    NominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    MinimumOuter

    SheathThickness

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    Approx.Capacitance

    Approx.Reactance

    DIMENSIONS ELECTRICAL PARAMETERS

    Current Rating

    (Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    25 3.6 2.0 22.0 450 0.19 0.143 100 90 115 500

    35 3.6 2.0 23.0 500 0.21 0.137 120 110 140 500

    50 3.6 2.0 24.0 550 0.23 0.131 140 130 165 500

    70 3.6 2.0 25.5 650 0.27 0.120 175 160 210 500

    95 3.6 2.0 27.5 750 0.30 0.115 205 190 255 500

    120 3.6 2.0 29.0 850 0.33 0.110 235 220 295 500

    150 3.6 2.0 30.5 950 0.36 0.107 260 240 335 500

    185 3.6 2.2 32.5 1,150 0.39 0.104 295 275 385 500

    240 3.6 2.2 35.0 1,350 0.44 0.100 340 315 455 500

    300 3.6 2.2 37.0 1,550 0.48 0.096 385 360 525 500

    400 3.6 2.2 40.0 1,850 0.54 0.092 435 410 610 500

    500 3.6 2.4 44.0 2,250 0.60 0.090 495 460 710 500

    630 3.6 2.4 47.5 2,750 0.68 0.087 570 530 840 500

    800 3.6 2.6 52.5 3,400 0.76 0.085 640 600 985 500

    1000 3.6 2.8 57.5 4,100 0.85 0.083 710 660 1110 500

    High Voltage Power Cable

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    17 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 11 KV (E) ALUMINIUM CONDUCTOR XLPE INSULATED

    UNARMOURED CABLES

    Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)

    Construction :

    InsulationConductor

    Conductor Shield

    Insulation Shield Outer Sheath

    Metallic Insulation Screen

    11

    Approx.Reactance

    Approx.Capacitance

    Approx.Cable

    Wt.

    Approx.OverallCable

    Diameter

    NominalOuter

    SheathThickness

    DIMENSIONS

    NominalArea of

    Conductor

    NominalInsulationThickness

    StandardDeliveryLengthAirDuctGround

    ELECTRICAL PARAMETERS

    Current Rating

    (Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    17 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 11 KV (E) COPPER CONDUCTOR XLPE INSULATED

    UNARMOURED CABLES

    Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Conductor ShieldInsulation Shield

    Conductor

    Insulation

    Metallic Insulation Screen

    Outer Sheath

    12

    StandardDeliveryLengthDuctGround

    Approx.Reactance

    Approx.Capacitance

    Approx.Cable

    Wt.

    Approx.OverallCable

    Diameter

    NominalOuter

    SheathThickness

    DIMENSIONS ELECTRICAL PARAMETERS

    Current RatingNominalArea of

    Conductor

    NominalInsulationThickness Air

    (Mtr./Drum)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm) (Amp)

    25 3.6 2.0 22.0 600 0.19 0.143 130 120 150 500

    35 3.6 2.0 23.0 700 0.21 0.137 155 140 180 500

    50 3.6 2.0 24.0 800 0.23 0.131 180 165 215 500

    70 3.6 2.0 25.5 1,050 0.27 0.120 220 205 270 500

    95 3.6 2.0 27.5 1,300 0.30 0.115 265 240 325 500

    120 3.6 2.0 29.0 1,550 0.33 0.110 300 275 380 500

    150 3.6 2.0 30.5 1,800 0.36 0.107 335 310 430 500

    185 3.6 2.2 32.5 2,200 0.39 0.104 380 340 495 500

    240 3.6 2.2 35.0 2,750 0.44 0.100 435 410 585 500

    300 3.6 2.2 37.0 3,300 0.48 0.096 490 460 670 500

    400 3.6 2.2 40.0 4,100 0.54 0.092 550 515 770 500

    500 3.6 2.4 44.0 5,150 0.60 0.090 620 570 890 500

    630 3.6 2.4 47.5 6,500 0.68 0.087 700 650 1050 500

    800 3.6 2.6 52.5 8,200 0.76 0.085 770 720 1190 500

    1000 3.6 2.8 57.5 10,100 0.85 0.083 840 780 1320 500

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.

    High Voltage Power Cable

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    28 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 11 KV (UE) ALUMINIUM CONDUCTOR XLPE INSULATED

    ARMOURED CABLES

    Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Conductor

    Outer SheathInsulation ShieldConductor Shield

    ArmourInsulation

    13

    25 5.5 1.60 1.40 28.5 750 0.14 0.162 100 90 120 500

    35 5.5 1.60 1.40 29.5 800 0.16 0.155 120 110 145 500

    50 5.5 1.60 1.56 31.0 900 0.17 0.149 140 125 175 500

    70 5.5 1.60 1.56 32.5 1,050 0.19 0.138 170 155 215 500

    95 5.5 2.00 1.56 34.5 1,150 0.22 0.131 205 185 265 500

    120 5.5 2.00 1.56 36.5 1,400 0.24 0.127 230 210 305 500

    150 5.5 2.00 1.56 38.0 1,500 0.26 0.122 255 235 345 500

    185 5.5 2.00 1.56 39.5 1,650 0.28 0.118 290 270 390 500

    240 5.5 2.00 1.72 42.5 1,950 0.31 0.114 330 310 465 500

    300 5.5 2.00 1.72 44.5 2,200 0.33 0.110 370 340 530 500

    400 5.5 2.00 1.88 48.0 2,600 0.37 0.105 415 390 605 500

    500 5.5 2.00 1.88 51.5 3,000 0.42 0.101 465 440 700 500

    630 5.5 2.50 2.04 56.5 3,750 0.46 0.099 510 480 790 500

    800 5.5 2.50 2.20 61.0 4,450 0.52 0.095 555 520 880 500

    1000 5.5 2.50 2.20 65.5 5,200 0.58 0.092 595 560 970 500

    Approx.Reactance

    StandardDeliveryLength

    DIMENSIONS ELECTRICAL PARAMETERS

    Current Rating

    Ground AirDuct

    NominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    MinimumOuter

    SheathThickness

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    Approx.Capacitance

    (Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.

    High Voltage Power Cable

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    28 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 11 KV (UE) COPPER CONDUCTOR XLPE INSULATED

    ARMOURED CABLES

    Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Outer Sheath

    Conductor ShieldInsulation Shield

    Insulation

    Conductor

    Armour

    14

    25 5.5 1.60 1.40 28.5 900 0.14 0.162 130 115 155 500

    35 5.5 1.60 1.40 29.5 1,000 0.16 0.155 155 140 185 500

    50 5.5 1.60 1.56 31.0 1,200 0.17 0.149 180 160 225 500

    70 5.5 1.60 1.56 32.5 1,450 0.19 0.138 210 200 280 500

    95 5.5 2.00 1.56 34.5 1,700 0.22 0.131 260 240 340 500

    120 5.5 2.00 1.56 36.5 2,050 0.24 0.127 290 270 390 500

    150 5.5 2.00 1.56 38.0 2,350 0.26 0.122 325 300 440 500

    185 5.5 2.00 1.56 39.5 2,750 0.28 0.118 365 335 500 500

    240 5.5 2.00 1.72 42.5 3,350 0.31 0.114 415 385 585 500

    300 5.5 2.00 1.72 44.5 3,950 0.33 0.110 460 430 660 500

    400 5.5 2.00 1.88 48.0 4,850 0.37 0.105 505 470 740 500

    500 5.5 2.00 1.88 51.5 5,900 0.42 0.101 560 520 850 500

    630 5.5 2.50 2.04 56.5 7,450 0.46 0.099 600 560 935 500

    800 5.5 2.50 2.20 61.0 9,200 0.52 0.095 640 600 1020 500

    1000 5.5 2.50 2.20 65.5 11,200 0.58 0.092 675 630 1100 500

    StandardDeliveryLength

    DIMENSIONS ELECTRICAL PARAMETERS

    Current Rating

    Ground AirDuct

    Approx.Capacitance

    Approx.Reactance

    NominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    MinimumOuter

    SheathThickness

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    (Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    28 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 11 KV (UE) ALUMINIUM CONDUCTOR XLPE INSULATED

    UNARMOURED CABLES

    Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)

    Construction :

    InsulationConductor

    Conductor Shield

    Insulation Shield Outer Sheath

    Metallic Insulation Screen

    15

    25 5.5 2.0 26.0 600 0.14 0.154 100 95 120 500

    35 5.5 2.0 27.0 650 0.16 0.147 120 115 145 500

    50 5.5 2.0 28.0 700 0.17 0.141 140 130 170 500

    70 5.5 2.0 29.5 800 0.19 0.130 175 160 215 500

    95 5.5 2.0 31.5 950 0.22 0.123 205 190 260 500

    120 5.5 2.2 33.5 1,050 0.24 0.120 235 215 300 500

    150 5.5 2.2 35.0 1,200 0.26 0.116 260 240 340 506

    185 5.5 2.2 36.5 1,350 0.28 0.111 295 275 390 500

    240 5.5 2.2 38.5 1,550 0.31 0.106 340 320 460 500

    300 5.5 2.2 41.0 1,800 0.33 0.103 385 360 530 500

    400 5.5 2.4 44.5 2,150 0.37 0.099 435 410 615 500

    500 5.5 2.4 47.5 2,550 0.42 0.095 500 470 725 500

    630 5.5 2.6 52.0 3,100 0.46 0.092 570 535 840 500

    800 5.5 2.8 57.0 3,750 0.52 0.090 640 605 975 500

    1000 5.5 2.8 61.5 4,450 0.58 0.087 710 670 1100 500

    StandardDeliveryLengthAirDuctGround

    Approx.Reactance

    Approx.Capacitance

    Approx.Cable

    Wt.

    Approx.OverallCable

    Diameter

    NominalOuter

    SheathThickness

    DIMENSIONS ELECTRICAL PARAMETERS

    Current RatingNominalArea of

    Conductor

    NominalInsulationThickness

    (Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    DIMENSIONS

    StandardDeliveryLengthAirDuctGround

    Approx.Reactance

    Approx.Capacitance

    Approx.Cable

    Wt.

    Approx.OverallCable

    Diameter

    NominalOuter

    SheathThickness

    ELECTRICAL PARAMETERS

    Current RatingNominalArea of

    Conductor

    NominalInsulationThickness

    (Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    28 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 11 KV (UE) COPPER CONDUCTOR XLPE INSULATED

    UNARMOURED CABLES

    Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Conductor ShieldInsulation Shield

    Conductor

    Insulation

    Metallic Insulation Screen

    Outer Sheath

    16

    25 5.5 2.0 26.0 750 0.14 0.154 130 120 150 500

    35 5.5 2.0 27.0 850 0.16 0.147 155 145 185 500

    50 5.5 2.0 28.0 950 0.17 0.141 180 170 220 500

    70 5.5 2.0 29.5 1,200 0.19 0.130 220 205 275 500

    95 5.5 2.0 31.5 1,500 0.22 0.123 265 245 335 500

    120 5.5 2.2 33.5 1,750 0.24 0.120 300 275 385 500

    150 5.5 2.2 35.0 2,050 0.26 0.116 335 310 440 500

    185 5.5 2.2 36.5 2,400 0.28 0.111 380 350 500 500

    240 5.5 2.2 38.5 2,950 0.31 0.106 435 410 590 500

    300 5.5 2.2 41.0 3,550 0.33 0.103 490 460 675 500

    400 5.5 2.4 44.5 4,400 0.37 0.099 555 515 775 500

    500 5.5 2.4 47.5 5,400 0.42 0.095 625 580 910 500

    630 5.5 2.6 52.0 6,850 0.46 0.092 705 660 1050 500

    800 5.5 2.8 57.0 8,550 0.52 0.090 775 730 1185 500

    1000 5.5 2.8 61.5 10,400 0.58 0.087 845 795 1310 500

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.

    High Voltage Power Cable

    StandardDeliveryLength

    DIMENSIONS ELECTRICAL PARAMETERS

    Current Rating

    Ground AirDuct

    NominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    MinimumOuter

    SheathThickness

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    Approx.Capacitance

    Approx.Reactance

    (Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    32 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 22 KV (E) ALUMINIUM CONDUCTOR XLPE INSULATED

    ARMOURED CABLES

    Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Conductor

    Outer SheathInsulation ShieldConductor Shield

    ArmourInsulation

    17

    35 6.0 1.60 1.40 31.0 900 0.15 0.158 120 105 150 500

    50 6.0 1.60 1.56 32.5 1,000 0.16 0.153 140 125 175 500

    70 6.0 1.60 1.56 34.0 1,100 0.18 0.141 170 155 215 500

    95 6.0 2.00 1.56 36.5 1,350 0.21 0.134 200 185 265 500

    120 6.0 2.00 1.56 38.0 1,450 0.22 0.129 230 215 305 500

    150 6.0 2.00 1.56 39.5 1,600 0.24 0.125 255 235 345 500

    185 6.0 2.00 1.56 41.0 1,750 0.26 0.120 285 265 395 500

    240 6.0 2.00 1.72 44.0 2,050 0.29 0.116 325 305 460 500

    300 6.0 2.00 1.72 46.0 2,300 0.31 0.112 365 340 530 500

    400 6.0 2.00 1.88 49.5 2,700 0.35 0.107 410 380 605 500

    500 6.0 2.50 2.04 54.0 3,350 0.39 0.104 450 420 690 500

    630 6.0 2.50 2.04 58.0 3,900 0.43 0.101 500 460 800 500

    800 6.0 2.50 2.20 62.5 4,600 0.48 0.097 545 500 890 500

    1000 6.0 2.50 2.36 67.5 5,400 0.54 0.094 580 540 970 500

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.

    High Voltage Power Cable

    DIMENSIONS ELECTRICAL PARAMETERS

    Current RatingStandardDeliveryLengthGround AirDuct

    NominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    MinimumOuter

    SheathThickness

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    Approx.Capacitance

    Approx.Reactance

    (Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km)

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    32 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 22 KV (E) COPPER CONDUCTOR XLPE INSULATED

    ARMOURED CABLES

    Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundArmour : Round Aluminium WiresOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Outer Sheath

    Conductor ShieldInsulation Shield

    Insulation

    Conductor

    Armour

    18

    35 6.0 1.60 1.40 31.0 1,100 0.15 0.158 150 135 190 500

    50 6.0 1.60 1.56 32.5 1,250 0.16 0.153 175 165 225 500

    70 6.0 1.60 1.56 34.0 1,500 0.18 0.141 220 200 280 500

    95 6.0 2.00 1.56 36.5 1,900 0.21 0.134 255 235 335 500

    120 6.0 2.00 1.56 38.0 2,150 0.22 0.129 290 265 390 500

    150 6.0 2.00 1.56 39.5 2,450 0.24 0.125 320 300 435 500

    185 6.0 2.00 1.56 41.0 2,850 0.26 0.120 360 330 500 500

    240 6.0 2.00 1.72 44.0 3,450 0.29 0.116 405 380 580 500

    300 6.0 2.00 1.72 46.0 4,050 0.31 0.112 455 425 660 500

    400 6.0 2.00 1.88 49.5 4,950 0.35 0.107 500 470 755 500

    500 6.0 2.50 2.04 54.0 6,200 0.39 0.104 545 500 835 500

    630 6.0 2.50 2.04 58.0 7,600 0.43 0.101 590 550 940 500

    800 6.0 2.50 2.20 62.5 9,400 0.48 0.097 630 590 1020 500

    1000 6.0 2.50 2.36 67.5 11,400 0.54 0.094 660 620 1100 500

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    32 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 22 KV (E) ALUMINIUM CONDUCTOR XLPE INSULATED

    UNARMOURED CABLES

    Conductor : Round Compact Stranded AluminiumConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)

    Construction :

    InsulationConductor

    Conductor Shield

    Insulation Shield Outer Sheath

    Metallic Insulation Screen

    19

    Approx.Reactance

    Approx.Capacitance

    Approx.Cable

    Wt.

    Approx.OverallCable

    Diameter

    NominalOuter

    SheathThickness

    Current RatingNominalArea of

    Conductor

    NominalInsulationThickness

    StandardDeliveryLength

    ELECTRICAL PARAMETERSDIMENSIONS

    (Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)

    AirDuctGround

    35 6.0 2.0 28.5 700 0.15 0.151 120 110 145 500

    50 6.0 2.0 29.5 750 0.16 0.145 140 130 170 500

    70 6.0 2.0 31.0 900 0.18 0.133 170 160 210 500

    95 6.0 2.2 33.5 1,050 0.21 0.127 205 190 255 500

    120 6.0 2.2 35.0 1,150 0.22 0.123 235 220 300 500

    150 6.0 2.2 36.5 1,300 0.24 0.118 260 240 340 500

    185 6.0 2.2 38.0 1,450 0.26 0.114 295 275 390 500

    240 6.0 2.2 40.0 1,650 0.29 0.109 335 315 455 500

    300 6.0 2.2 42.5 1,900 0.31 0.105 380 360 535 500

    400 6.0 2.4 46.0 2,250 0.35 0.101 435 410 615 500

    500 6.0 2.6 50.0 2,700 0.39 0.098 495 460 710 500

    630 6.0 2.6 53.5 3,200 0.43 0.094 560 530 850 500

    800 6.0 2.8 58.5 3,900 0.48 0.092 630 600 985 500

    1000 6.0 3.0 63.5 4,650 0.54 0.089 700 660 1110 500

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    High Voltage Power Cable

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(3) Dimensions and weights are subject to industry tolerances.

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    32 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 22 KV (E) COPPER CONDUCTOR XLPE INSULATED

    UNARMOURED CABLES

    Conductor : Round Compact Stranded Plain CopperConductor Shield : Semi-conducting CompoundInsulation : Cross - Linked Polyethylene (XLPE)Insulation Shield : Semi-conducting CompoundMetallic Insulation Screen : Copper TapeOuter Sheath : Black PVC (Type - ST2)

    Construction :

    Conductor ShieldInsulation Shield

    Conductor

    Insulation

    Metallic Insulation Screen

    Outer Sheath

    20

    (Mtr./Drum)(Amp)(Amp)(Amp) (F/km)(Kg/km)(mm)(mm)(Sqmm) (mm)

    StandardDeliveryLengthAirDuctGround

    Approx.Reactance

    Approx.Capacitance

    Approx.Cable

    Wt.

    Approx.OverallCable

    Diameter

    NominalOuter

    SheathThickness

    DIMENSIONS

    Current RatingNominalArea of

    Conductor

    NominalInsulationThickness

    ELECTRICAL PARAMETERS

    35 6.0 2.0 28.5 900 0.15 0.151 155 140 185 500

    50 6.0 2.0 29.5 1,050 0.16 0.145 180 170 220 500

    70 6.0 2.0 31.0 1,300 0.18 0.133 220 205 275 500

    95 6.0 2.2 33.5 1,600 0.21 0.127 260 245 330 500

    120 6.0 2.2 35.0 1,850 0.22 0.123 295 275 385 500

    150 6.0 2.2 36.5 2,150 0.24 0.118 330 310 430 500

    185 6.0 2.2 38.0 2,500 0.26 0.114 375 350 500 500

    240 6.0 2.2 40.0 3,050 0.29 0.109 430 410 580 500

    300 6.0 2.2 42.5 3,650 0.31 0.105 485 465 680 500

    400 6.0 2.4 46.0 4,500 0.35 0.101 550 515 780 500

    500 6.0 2.6 50.0 5,600 0.39 0.098 610 575 900 500

    630 6.0 2.6 53.5 6,950 0.43 0.094 700 655 1050 500

    800 6.0 2.8 58.5 8,700 0.48 0.092 770 730 1190 500

    1000 6.0 3.0 63.5 10,700 0.54 0.089 835 790 1320 500

  • Centrum Plaza, Level 3, Tower A, 312-S, Golf Course Road, Sector-53, Gurgaon-122002, HarayanaPhone : +91 124 432 6000 Fax : +91 124 432 6019

    General Cable Energy India Pvt. Ltd.

    Connecting the WorldConnecting the World

    Note: (1) Electrical Parameters are based on Standard Laying Conditions mentioned in Table-1. (2) Armouring shall constitute the metallic part of insulation screening. (3) Standard delivery Length specified above are for guidance only. Cables can be however supplied in longer lengths as per specific requirement of the Customer.(4) Dimensions and weights are subject to industry tolerances.

    High Voltage Power Cable

    StandardDeliveryLength

    DIMENSIONS ELECTRICAL PARAMETERS

    Current Rating

    Ground AirDuct

    NominalArea of

    Conductor

    NominalInsulationThickness

    NominalArmour

    Wire Diameter

    MinimumOuter

    SheathThickness

    Approx.OverallCable

    Diameter

    Approx.Cable

    Wt.

    Approx.Capacitance

    Approx.Reactance

    (Mtr./Drum)(Amp) (Amp)(Amp)(Sqmm) (mm) (mm) (mm) (mm) (Kg/km) (F/km) Z

    I Normal Operation..................................................90C I Emergency* Operation.........................................130CI Short Circuit Operation.......................................250C

    Temperature Rating :

    * Operation at the emergency overload temperature shall not exceed 100 hours in 12 consecutive months & not more than 500 hours during the lifetime of the cable.

    ? Triple-extruded for clean interfaces? Dry nitrogen cure for enhanced performance? Excellent moisture resistance? High dielectric strength? Low dielectric loss? Excellent resistance to treeing

    Features & Benefits : IS : 7098 Part -2Reference Standard :

    48 KV (AC) for 5 minutes.H.V. Test Voltage :

    Preferably used for Power distribution network. Suitable for exposed in Air, direct burial, open tray & underground duct installation.

    Application :

    FR/FRLS/ZHLS/Flame Spread Resistant type Cables are available upon request.

    Options :

    SINGLE CORE 33 KV (E) ALUM