link smp - ss snow melt panels with heat exchangers ... · pdf fileserial #: xxx-xxxx...
TRANSCRIPT
®
LinkHeatwww.heatlink.com
Toll Free: 1-800-661-5332Canada Fax: 1-866-450-1155USA Fax: 1-800-869-6098
Job or Customer :
Location :
Engineer :❏ ❏❏
Complies with Spec❏ Alternate Notes :
Contractor :
HeatLink Rep :
Submitted By : Date :
Approved By : Date :
P.O. Number : Date :
©2012-2017 HeatLink Group Inc.SUBSMP000SSHEX
2017-10-26
SMP - SS Snow Melt Panels with Heat ExchangersSubmittal - Page 1 of 4
Qty Stk. #Nominal Panel Output
see conditions below Primary Circulator Secondary Circulator Heat Exchangers Weight
SMP175SS-HEX 175,000 Btu/hrFerrous, Grundfos
UPS26-99FCFerrous, Grundfos
UPS26-99FC2× Single-wall brazed
plate; FP3×8-2093.5 lb
(42.5 kg)
SMP300SS-HEX 300,000 Btu/hrFerrous, Grundfos
UPS26-99FCFerrous, Grundfos
UPS26-99FC2× Single-wall brazed
plate; FP3×8-30
SMP300SS-HEX-H 365,000 Btu/hrFerrous, Grundfos
UPS26-99FCFerrous, Grundfos
UPS26-150FC3× Single-wall brazed
plate; FP3×8-30
Technical Data Max Ambient Temperature: ................................ 120°F (49°C)Max Water Temperature: ................................... 200°F (93°C)Temperature Control Method: ............................ 3-way Mixing Valve with DDC MotorMixing Valve Size: ............................................. 1-1⁄4"Mixing Valve Cv: ................................................ 11.6Temperature Control Range: ............................. 50-180°F (10-82°C)Power supply: .................................................... 110V(ac); max. current 6AAuxiliary Terminal: ............................................. 1Piping: ................................................................ 1" 304SS TubingPiping Connections: ........................................... 3⁄4" and 1" FNPTMaterial - Backplate: .......................................... Galvanized SteelMaterial - Enclosure: .......................................... Powder Coated Steel
Standards / ListingsCAN/CSA-C22 No.14, UL508cETLus
DescriptionThe SMP175SS-HEX, SMP300SS-HEX, and SMP300SS-HEX-H Snow Melt Panels are operation centers for fully automatic snow melt systems. They are intended for snow melt systems with non-dedicated heat sources, therefore heat exchangers are included to separate the primary loop water from the secondary loop glycol mixture. Standard snow melt control uses Snow/Ice Detector #DRVWSNS-SS (sold separately). Snow melt control can be changed to HeatLink® #31680 Snow/Ice Detector and Melt Control (OPT-SMP-680) which uses Snow/Ice Detector #30090 and Snow/Ice Sensor Socket #30091 (both sold separately).
Options❏ OPT-SMP-680 - replace standard snow melt control with HeatLink® #31680 Snow/Ice Detector and Melt Control (see SUB31680)
Panel Output Conditions SMP175SS-HEX SMP300SS-HEX SMP300SS-HEX-HPrimary Secondary Primary Secondary Primary Secondary
Fluid type Water 50% glycol Water 50% glycol Water 50% glycolEntering fluid temp (°F) 185.0 110.0 185.0 110.0 182.0 110.0Exiting fluid temp (°F) 155.0 141.2 155.0 143.7 152.0 142.8Flow rate (US gpm) 12.0 12.6 20.6 20.0 24.9 24.9Headloss 4.1 – 7.0 – 4.1 –Allowable pressure drop outside of panel (ft head)
– 18 – 10 – 20
®
LinkHeatwww.heatlink.com
Toll Free: 1-800-661-5332Canada Fax: 1-866-450-1155USA Fax: 1-800-869-6098
©2012-2017 HeatLink Group Inc.SUBSMP000SSHEX
2017-10-26
WARNING!!!Consult Manual Before Use
AVERTISSEMENT!!!Consulter le
manual avant l’usage
HeatLink Group Inc.4603E - 13th Street NECalgary, Alberta, CanadaT2E 6M3Phone: (403) 250-3432Fax: (403) 250-1155www.heatlinkgroup.com
Conforms to Std CAN/CSA C22.2 No. 14Conforms to Standard UL 508
MADE IN CANADA
MODEL #: SMP300SS-HEX
D.O.M: Feb 2, 2012
Max Pres: 125psi/862kPa
Volts: 120/24 VAC
Serial #: XXX-XXXX
Phase/Freq: 1/60 Cycles
Max Temp: 100C/212F
Amps: Maximum 15
3189472
SOME UNION NUTS MAYBECOME LOOSE
AND CONSEQUENTLYLEAK THROUGH
TRANSPORTATIONVIBRATION AND
HANDLING. DO NOTOVERTIGHTEN UNION NUTSWHEN CORRECTING THIS.
Any alterations to electrical wiring andcontrols renders warrantynull & void.
Installation must conformto local codes. Check valve(s) if required are theinstallers responsibility.
Before servicing,disconnect powersupply
M A D E I N C A N A D A
CAUTION
HEAT SOURCE
Supply
Return
1 inch Ball Valves
Type UPS 26-99 FC115 V 1 PH60 Hz20 uF
P/N: 52722512 P1 PC: 0939US
IMPEDANCE
PROTECTED
FOR INDOOR USE ONLY
Class F|1/1(A)
P1 (w)
1.301.501.80
150179197
CUS
99K4
ULLISTED
MA
X. FlU
IDTE
MP. 230˚F
99K4LISTED UL
Type UPS 26-99 FC115 V 1 PH60 Hz20 uF
P/N: 52722512 P1 PC: 0939US
IMPEDANCE
PROTECTED
FOR INDOOR USE ONLY
Class F|1/1(A)
P1 (w)
1.301.501.80
150179197
CUS
99K4
ULLISTED
MA
X. FlU
IDTE
MP. 230˚F
99K4LISTED UL
WARNING HOTThis product
may have hot fluidcirculating through it.
DO NOT TOUCH !
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
1 - 1 - 2N - L 3 4 5 6 7 8
ON
ET02ALARM
SMP - SS Snow Melt Panels with Heat ExchangersSubmittal - Page 2 of 4
Panel Components Primary Pump
Secondary Pump
3-Way Mixing Valve and 24V DDC Motor
6' Power Cord
24V(ac) Transformer
Snow Melt Control
Supply Sensor
Return Sensor
Thermometer
Heat Exchanger
Drain and Fill Valve
Pressure Relief Valve
1
2
2
3
3
10 10
12
11
11
4
4
5
5
6
6
7
7
8
8
9
10
11
12
9
9
1
SecondaryReturn
Expansion Tank
Pressure ReliefSecondary
Supply
Primary Supply
Primary Return
SMP300SS-HEX
11
®
LinkHeatwww.heatlink.com
Toll Free: 1-800-661-5332Canada Fax: 1-866-450-1155USA Fax: 1-800-869-6098
©2012-2017 HeatLink Group Inc.SUBSMP000SSHEX
2017-10-26
SMP - SS Snow Melt Panels with Heat ExchangersSubmittal - Page 3 of 4
38.659" (982 mm)
30.504"(775 mm)
®Heat Link
3-7⁄16"
13-3⁄16"
1-3⁄8"
8.0"(203 mm)
12" 3"
1-1⁄2"
5-3⁄4"7-3⁄4"
FT H
D
SMP175SS-HEX
FT HD Outside of Panel
0.0
5.0
10.0
15.0
20.0
25.0
30.0
35.0
40.0
45.0
0.0 5.0 10.0 15.0 20.0 25.0 30.0US GPM
SMP300SS-HEX
SMP300SS-HEX-H
®
LinkHeatwww.heatlink.com
Toll Free: 1-800-661-5332Canada Fax: 1-866-450-1155USA Fax: 1-800-869-6098
©2012-2017 HeatLink Group Inc.SUBSMP000SSHEX
2017-10-26
Technical data
60
Note: Dimensions in inches unless otherwise noted.
TM04
546
3
UPS 26-150 F/SF
TM04
601
4
32
11
23
A
BC
D FD
E
Flow range: 0-53 gpm
Head range: 0-46 feet
Motors: 2-pole, single-phase
Max. liquid temperature: 230 °F (110 °C)
Min. liquid temperature: 36 °F (2 °C)
Max. system pressure: 145 psi (10 bar)
Model Spd Volts Amps Watts Hp Capacitor
UPS 26-150 F/SF
3
115
3.5 370 1/6
40μF/180V2 3.1 335 1/6
1 2.5 265 1/6
3
208
1.7 350 1/6
10μF/400V2 1.5 310 1/6
1 1.2 250 1/6
3
230
1.7 370 1/6
10μF/400V2 1.5 335 1/6
1 1.2 265 1/6
Approvals
Model typeProduct number Dimensions [inches] Connection type
and sizeShipping weight
[lbs]115 V 208 / 230 V A B C D E F
UPS 26-150 F 95906630 95906631 6 1/2 7 1/8 5 7/8 3 7/8 3 3/4 3 1/8 GF 15/26 flange(2) 1/2" dia. bolt holes 17.35
UPS 26-150 SF 95906632 95906633 6 1/2 7 1/8 5 7/8 3 7/8 3 3/4 3 1/8 GF 15/26 flange(2) 1/2" dia. bolt holes 17.35
UPS 26-150 F/SF
UPSeries.book Page 60 Monday, March 21, 2011 8:54 PM
UPS26-99BFC Pump Curve
0
5
10
15
20
25
30
35
0 5 10 15 20 25 30 35Flow (gpm)
Hea
d (fe
et)
1st Speed 2nd Speed 3rd Speed
SMP - SS Snow Melt Panels with Heat ExchangersSubmittal - Page 4 of 4
InstallationInstallation must follow all of HeatLink's instructions and guidelines.
MaintenanceMaintenance must follow all of HeatLink's instructions and guidelines.
Related Documents• SMP000SS Installation, Operation, and Maintenance Manual Instructions (L6SMP000SS)• HeatLink Limited Heating Warranty
UPS 26-150 Pump Curve