metasys integrator york application
TRANSCRIPT
Metasys Connectivity Technical Manual 629.5Metasys Integrator Section
Application NoteIssue Date 0900
© 2000 Johnson Controls, Inc. 1Code No. LIT-6295540 www.johnsoncontrols.com
lntroduction Page *3
• Application Details *3
• Component Requirements *6
• Vendor Contact Information 7
• Design Considerations *7
Cable Connections 9
• Cable Pinouts 9
• Connecting the Cable 9
Metasys Integrator Setup *11
Point Mapping Tables 15
15
16
*18
20
21
22
24
27
29
• Translator and XL Login
• YT Centrifugal Dual or Mono Shell Chiller
• YK Centrifugal Super Chiller
• YS 125-400 Ton Rotary Screw Chiller
• LS 1000-1250 Ton Rotary Screw Chiller
• YP Absorption Chiller
• C1 U.S. Reciprocating “Intelligent” Chiller - Master
• C3 U.S. Reciprocating “Intelligent” Chiller - Subordinate
• B1 U.K. Basildon Reciprocating “Intelligent” Chiller - Master
• B3 U.K. Basildon Reciprocating “Intelligent” Chiller - Subordinate 31
APPLICATION NOTE
Metasys Integrator York Application
*Indicates those sections where changes have occurred since the last printing.
2 Metasys Integrator—Metasys Integrator York Application
Page 33
35
37
*39
• YR Sunline 3000 Rooftop Chiller
• A1 Air-cooled Screw Chiller - Master
• A3 Air-cooled Screw Chiller - Subordinate
• YI Isoflow Absorption Chiller
• YG Gas Engine Drive Chiller 42
Metasys Network Setup *45
Mapping to a CS Object *45
Custom Integration *47
*Indicates those sections where changes have occurred since the last printing.
Metasys Integrator—Metasys Integrator York Application 3
lntroduction
This document explains Metasys Integrator York applications. Use thisdocument with the Metasys Integrator technical bulletins in the MetasysConnectivity Technical Manual (FAN 629.5), which provide informationon installing and commissioning the Metasys Integrator unit. Forinformation on York equipment, see York documentation (obtainable froma York representative).
Note: If you use a Universal Packaging Module (UPM) enclosure, youmust install the Metasys Integrator 300 Series in a two highenclosure (EN-EWC25-0) rather than the one high enclosure(EN-EWC13-0) as shown in the figures in this application note.
The Metasys Integrator unit allows York Millennium chillers and Sunline 3000 rooftop units to become an integral part of the Metasysand Metasys Companion Networks. Once York controllers are connected to Metasys or Companion Networks via the Metasys Integrator unit, their data is available to the full complement of Metasys Building Automation System (BAS) features, including Change-of-State (COS) monitoring, alarm notification, scheduling, trend, and totalization.
The York YorkTalk Translator and YorkTalk XL are the interfaces between York chiller controllers and non-York devices (such as the Metasys Integrator unit).
Each Metasys Integrator vendor port can connect to one YorkTalk Translator. Each YorkTalk Translator can connect to up to four York chiller controllers. If you use reciprocating chillers, the maximum number of pairs in master/subordinate configuration (C1/C3 or B1/B3) is two. If you use only master reciprocating chillers (C1 or B1), the maximum number of chillers allowed is four. Also, with a YorkTalk Translator interface, reciprocating chillers may not be mixed with other types of chillers due to a difference in baud rates.
Each Metasys Integrator vendor port can connect to one YorkTalk XL, which can then connect to 32 York controllers.
Figure 1 shows York and Metasys System integration. Figure 2 shows York and Metasys Companion integration.
ApplicationDetails
4 Metasys Integrator—Metasys Integrator York Application
N2 Bus
Standard NCU
UNT
N1 LAN
MetasysIntegrator
RS-232
York1
YTChiller
YKChiller
YSChiller
YPChiller
RS-485 ISN Network
LincChiller
LincChiller
LincChiller
YS YI
YorkTalkXL
YorkTalkTranslator
A3 A1
Note: If you use a UPM enclosure, you must install the Metasys Integrator 300Series in a two high enclosure (EN-EWC25-0) rather than the one highenclosure (EN-EWC13-0) as shown in the figures in this application note.
Figure 1: York and Metasys System Integration
Metasys Integrator—Metasys Integrator York Application 5
N2 Bus
UNT
MetasysIntegrator
york2
RS-232
YKChiller
YSChiller
YPChiller
YTChiller
RS-485 ISN Network
YS YI
YorkTalkXL
YorkTalkTranslator
LincChiller
LincChiller
LincChiller
A1
Panel Unit Workstation
Note: A PC version and converter may be substituted for the Panel unit.
A3
Note: If you use a UPM enclosure, you must install the Metasys Integrator300 Series in a two high enclosure (EN-EWC25-0) rather than theone high enclosure (EN-EWC13-0) as shown in the figures in thisapplication note.
Figure 2: York and Metasys Companion Integration
6 Metasys Integrator—Metasys Integrator York Application
To integrate York equipment, you need the following components:
• properly installed York YorkTalk Translator (Revision 1A,firmware Revision 5.00 or above) or YorkTalk XL version andYork chiller controllers
Note: The Metasys Integrator unit supports only the U.S. version ofthe translator, which has two Advanced Processor Cards.Versions with only one Advanced Processor Card (such asthe U.K. version) are not supported.
• RS-232 cable (for connecting the YorkTalk Translator orYorkTalk XL to the Metasys Integrator unit)
• Metasys Integrator unit
• N2 Bus (for connecting the Metasys Integrator unit to the Metasys orCompanion Networks)
• portable Personal Computer (PC) for downloading vendorcommunication tables (.VCT files) and network setup informationinto the Metasys Integrator unit, and for running diagnostics
• cable for connecting portable PC to the Metasys Integrator unit
• the correct vendor communication table (.VCT file) to download intothe Metasys Integrator unit (supplied on Metasys IntegratorCD-ROM)
To integrate York equipment into the Metasys Network, you need:
• Metasys Operator Workstation (OWS) software Release 6.0 or higher
• Metasys Integrator software/firmware Release 8.0 or higher
To integrate York equipment into the Metasys Companion Network, youneed:
• Metasys Companion Release 5.0 or higher
• Metasys Integrator software/firmware Release 8.0 or higher
Integration between the Metasys Integrator unit and York has been testedwith the YorkTalk Translator (Part Number 371-01415-100, Revision 1A)or the YorkTalk XL (Part Number 371-01457-101, Revision 77). Changesto this equipment or integration of York products not discussed in thisdocument will require additional software development and testing bySystems Products. For information on integrating other products, refer tothe Custom Integration section in this document.
ComponentRequirements
MetasysNetwork ReleaseRequirements
MetasysCompanionReleaseRequirements
VendorComponentRequirements
Metasys Integrator—Metasys Integrator York Application 7
York International CorporationApplied SystemsP.O. Box 1592-232ZYork, PA 17405-1592
Phone: (717) 771-7890FAX: (717) 771-7640
When integrating York equipment, consider the following:
• Make sure all York equipment is set up and running properly beforeattempting to integrate with Metasys or Companion Network. (TheYork representative is responsible for operation of YorkTalkTranslator, YorkTalk XL, and controllers.)
• Make sure the YorkTalk Translator or YorkTalk XL baud rate is setto 9600. (The York representative is responsible for setting theYorkTalk baud rate.)
• The York representative must configure the YorkTalk Translator orthe YorkTalk XL to talk to the Metasys Integrator unit, providepasswords, and commission the chillers via YorkTalk. York must alsoconfigure the YorkTalk Translator and the YorkTalk XL to report BIstatuses as Off and On. (The defaults in the Translator at this time areNo and Yes.)
• The YorkTalk Translator or YorkTalk XL must be configured for:trm=4 (cr, prompt)txt=1 (field text)
• The YorkTalk Translator or the YorkTalk XL must have its logonpassword set to 1. Otherwise, the Metasys Integrator unit will not beable to bring it online.
IMPORTANT: Make sure the YorkTalk Translator or YorkTalk XLtable is defined as an N2 address so that the MetasysIntegrator unit can establish the logon procedure. Thiswill ensure the quickest recovery to online status of allYork equipment.
• RS-232 cable distance between the Metasys Integrator unit and theYorkTalk Translator or YorkTalk XL can be a maximum of 50 feet.
• Cable distance between the YorkTalk Translator and the lastcontroller can be a maximum of 5000 feet.
IMPORTANT: The YorkTalk Translator does not provide offlinenotification when the chiller is disconnected from theTranslator.
Vendor ContactInformation
DesignConsiderations
8 Metasys Integrator—Metasys Integrator York Application
• York must configure the YorkTalk XL failure output to report statusesas NOR, and FLT to allow the XL to report if the chiller is offline tothe XL.
• Ensure battery backup is enabled to save baud rate settings on theYorkTalk Translator or YorkTalk XL.
• York chiller model names sometimes differ from the two charactercodes Johnson Controls uses (refer to Table 1).
Table 1: Chiller NamesStandard Name Also Known As:
C1, C3 (B1, B3) YCA, YDA, YEA, YCW, YCR
A1, A3 DYCAS
YI YIA
YP YPC
Metasys Integrator—Metasys Integrator York Application 9
Cable Connections
Use the following cable pinouts for the RS-232 connection between theMetasys Integrator unit and the YorkTalk Translator and XL:
DB-9 Female
Signal Pin
RDTDGND
ScrewTerminal
SignalPinRS-232
Vendor Port A or Bon Metasys Integrator
RS-232 Port on Translator or XL
(50 ft maximum)york3
235
15
1416
TX1
RX1GND1
Figure 3: Cable Pinouts
Connect the female end of the RS-232 cable to either Vendor Port A orVendor Port B on the Metasys Integrator unit. Connect the male end toPort A on the YorkTalk Translator or YorkTalk XL.
MetasysIntegrator
YorkTalkTranslator or XL
RS-232Terminal
Block
Vendor PortA or B
RS-232 Cable
york4
Figure 4: Port-to-Port Connection
Cable Pinouts
Connecting theCable
10 Metasys Integrator—Metasys Integrator York Application
Metasys Integrator—Metasys Integrator York Application 11
Metasys Integrator Setup
To set up the Metasys Integrator unit, use a portable PC connected to theMetasys Integrator Terminal Port. Metasys Integrator setup involves:
• downloading the correct vendor communication table (.VCT file)
• setting up the ports
• assigning network addresses to the controllers
Table 2 provides information specific to York applications. For detailedprocedures, see the Metasys Integrator technical bulletins in the MetasysConnectivity Technical Manual (FAN 629.5).
Table 2: Metasys Integrator Setup for York ControllersVendor Communication Table (.VCT File)Login and Chillers Translator XLLogin YK_TRAN.VCT YK_XL.VCT
YT Chiller (Centrifugal Dual Shell orMono Shell)
YK_YTCH.VCT YK_YTXL.VCT
YK Chiller (Centrifugal “Super Chiller”) YK_YKCH.VCT YK_YKXL.VCT
YS Chiller (125-400 Ton Rotary Screw) YK_YSCH.VCT YK_YSXL.VCT
LS Chiller (1000-1250 Ton Rotary Screw) YK_LSCH.VCT YK_LSXL.VCT
YP Chiller (Absorption Chiller) YK_YPCH.VCT YK_YPXL.VCT
C1 Chiller (U.S. Reciprocating“Intelligent” Chiller-Master)
YK_C1CH.VCT YK_C1XL.VCT
C3 Chiller (U.S. Reciprocating “Intelligent” Chiller-Subordinate)
YK_C3CH.VCT YK_C3XL.VCT
B1 Chiller (U.K. Basildon Reciprocating“Intelligent” Chiller-Master)
YK_B1CH.VCT YK_B1XL.VCT
B3 Chiller (U.K. Basildon Reciprocating “Intelligent” Chiller-Subordinate)
YK_B3CH.VCT YK_B3XL.VCT
YR Chiller (Sunline 3000 Rooftop Chiller) YK_S3000.VCT YK_S30XL.VCT
A1 Chiller (Air-cooled Screw Chiller-Master)
N/A YK_A1XL.VCT
A3 Chiller (Air-cooled Screw Chiller-Subordinate)
N/A YK_A3XL.VCT
YI Chiller (Isoflow Absorption Chiller) N/A YK_YIXL.VCT
YG Chiller (Gas Engine Drive Chiller) N/A YK_YGXL.VCT
Port SetupBaud Rate 9600
Word Length 8
Stop Bits 1
Parity None
Continued on next page . . .
12 Metasys Integrator—Metasys Integrator York Application
Network Setup for Login of Translator or XL (Cont.)
Interface RS-232
Vendor Address 0
Timeout Value 4000 ms
Poll Delay 550 ms
Network Setup for Translator
Vendor Address 1-8
Timeout Value 3000 ms
Poll Delay 50 ms
Network Setup for XLVendor Address* net, node
Timeout Value 3000 ms
Poll Delay 50 ms
Performance Guide
Chillers Translator XLApproximate Scan Time(For a single N2 address)
Login Table 4 seconds 8 seconds
YT Chiller 10 seconds 11 seconds
YK Chiller 11 seconds 11 seconds
YS Chiller 7 seconds 8 seconds
LS Chiller 6 seconds 6 seconds
YP Chiller 8 seconds 9 seconds
C1 Chiller 12 seconds 12 seconds
C3 Chiller 10 seconds 10 seconds
B1 Chiller 12 seconds 12 seconds
B3 Chiller 10 seconds 10 seconds
YR Chiller 11 seconds 12 seconds
A1 Chiller XL N/A 12 seconds
A3 Chiller XL N/A 10 seconds
YI Chiller XL N/A 11 seconds
YG Chiller XL N/A 9 seconds
* Example: If network is 0 and node is 2, then enter 00,02 for the vendor address.The format is two digits each for the network address and the nodeaddress, with leading zeros if necessary.
Metasys Integrator—Metasys Integrator York Application 13
Network Modify/Add/Delete
N2Address Interface Type Vendor Address Port Timeout
PollDelay Retry
0 [ ] [ ] [A] [ ] [ ] [ 3]1 [ ] [ ] [A] [ ] [ ] [ 3]2 [ ] [ ] [A] [ ] [ ] [ 3]3 [YorkTalk Translator] [0 ] [A] [ 4000] [ 550] [ 3]4 [York C1 Chiller ] [1 ] [A] [ 3000] [ 50] [ 3]5 [ ] [ ] [A] [ ] [ ] [ 3]6 [ ] [ ] [A] [ ] [ ] [ 3]7 [ ] [ ] [A] [ ] [ ] [ 3]
Available Vendor Interface Types
YorkTalk Translator York C1 Chiller
F1 Cancel F2 Save F3 More F4 GotoSelect a vendor interface type from the list
Figure 5: Example--Proper Setup of York C1 Chilleron YorkTalk Translator
Network Modify/Add/Delete
N2Address Interface Type Vendor Address Port Timeout
PollDelay Retry
0 [ ] [ ] [A] [ ] [ ] [ 3]1 [YorkTalk XL ] [0 ] [A] [ 4000] [ 550] [ 3]2 [York YT Chiller XL] [00,01 ] [A] [ 3000] [ 50] [ 3]3 [York YT Chiller XL] [00,02 ] [A] [ 3000] [ 50] [ 3]4 [York YT Chiller XL] [00,03 ] [A] [ 3000] [ 50] [ 3]5 [ ] [ ] [A] [ ] [ ] [ 3]6 [ ] [ ] [A] [ ] [ ] [ 3]7 [ ] [ ] [A] [ ] [ ] [ 3]
Available Vendor Interface Types
York Talk XL York YT Chiller XL
F1 Cancel F2 Save F3 More F4 GotoSelect a vendor interface type from the list
Figure 6: Example--Proper Setup of Three York YT Chillerson ISN YorkTalk XL
14 Metasys Integrator—Metasys Integrator York Application
Metasys Integrator—Metasys Integrator York Application 15
Point Mapping Tables
The following tables (one for each application) show the points availablefor mapping in the York controllers:
Table 3: YorkTalk Translator LoginNPT1 NPA2 Unit DescriptionBI 1 Translator Ready 0-no, 1-yes
1 Network Point Type
2 Network Point Address
Table 4: YorkTalk XL LoginNPT1 NPA2 Unit DescriptionBI 1 XL Ready 0-no, 1-yes
1 Network Point Type
2 Network Point Address
Translator andXL Login
16 Metasys Integrator—Metasys Integrator York Application
Table 5: YT Centrifugal Dual or Mono Shell Chiller(Translator and XL Configuration)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
psi
psi
psi
psi
%
Amperes
Amperes
Amperes
Volt
Volt
Volt
DegF
%
Leaving Chill Water Temperature
Entering Chill Water Temperature
Leaving Condenser Water Temperature
Entering Condenser Water Temperature
Evaporator Saturation Temperature
Condenser Saturation Temperature
Discharge Temperature
Oil Temperature
Evaporator Pressure
Condenser Pressure
Oil Differential Pressure
Purge Pressure
% Full Load Amperes
Phase A Amperes
Phase B Amperes
Phase C Amperes
Phase A-B Volts
Phase B-C Volts
Phase C-A Volts
Leaving Water Temperature Actual Setpoint
Current Actual Setpoint Feedback
BI
BI
BI
BI
BI
BI6
BI7
BI8
1
2
3
4
5
6
7
8
Compressor 0-open, 1-made
Vent Solenoid 0-open, 1-made
Chill Water Pump 0-open, 1-made
Start Switch 0-open, 1-made
Flow Switch 0-open, 1-made
ACC Valid Surge Map 0-open, 1-made
ACC New Surge Point 0-open, 1-made
VSD Cooling Pump Running 0-open, 1-made
AO
AO
AO
1*
2
3*
DegF
%FLA
DegC
Leaving Chill Water Setpoint (10 to 70)
Current Limit Setpoint (50 to 100)
Leaving Chill Water Setpoint (-12 to 21)
BO 1 Chiller Start/Stop 0-stop, 1-start
1 Network Point Type
2 Network Point Address
* Points AO1 and AO3 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC.
Continued on next page . . .
YT CentrifugalDual or MonoShell Chiller
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the CondenserPressure point isAI10.
Metasys Integrator—Metasys Integrator York Application 17
NPT1
(Cont.)NPA2 Unit Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Min
Code
Code
Code
Code
Hour
#
#
Volt
kW
MWh
Volt
Amps
#
Hz
%
%
kVA
Deg
Deg
#
Hz
Anti-Recycle Timer
Operational Mode Code
Operational Code
Safety Code
Cycling Code
Runtime Hours
Number Of Starts
Adaptive Capacity Control Frozen Delta p/p
VSD Output Voltage
VSD Input kW
VSD Input MWh
VSD DC Link Voltage
VSD DC Link Current
VSD Surge Count
VSD Output Frequency
VSD Maximum Voltage THD
VSD Maximum Current TDD
VSD Input kVA
VSD Internal Temperature
VSD Converter Heatsink Temperature
ACC PRV Position
ACC Frozen Output Frequency
BD
BD
1
2
VSD IEEE 519 Filter Present 0-Not Installed
Surge Detection Type 0-Delta_p/p, 1-Current
1 Network Point Type
2 Network Point Address
18 Metasys Integrator—Metasys Integrator York Application
Table 6: YK Centrifugal Super Chiller(Translator and XL Configuration)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
psi
psi
psi
%
%
Amperes
Amperes
Amperes
Volt
Volt
Volt
psi
psi
DegF
%
Leaving Chill Water Temperature
Entering Chill Water Temperature
Leaving Condenser Water Temperature
Entering Condenser Water Temperature
Evaporator Saturation Temperature
Condenser Saturation Temperature
Discharge Temperature
Oil Temperature
Evaporator Pressure
Condenser Pressure
Oil Differential Pressure
Refrigerant Level
Full Load Amperes
Phase A Amperes
Phase B Amperes
Phase C Amperes
Phase A-B Volts
Phase B-C Volts
Phase C-A Volts
Low Oil Pressure
High Oil Pressure
Leaving Water Temperature Actual Setpoint
Current Actual Setpoint Feedback
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
Compressor 0-open, 1-made
Vent Solenoid 0-open, 1-made
Chill Water Pump 0-open, 1-made
Start Switch 0-open, 1-made
Flow Switch 0-open, 1-made
ACC Valid Surge Map 0-open 1-made
ACC New Surge Point 0-open 1-made
VSD Cooling Pump Running 0-open 1-made
AO
AO
AO
1*
2
3*
DegF
%FLA
DegC
Leaving Chill Water Setpoint (10 to 70)
Current Limit Setpoint (50 to 100)
Leaving Chill Water Setpoint (-12 to 21)
BO 1 Chiller Start/Stop 0-stop, 1-start
1 Network Point Type
2 Network Point Address
* Points AO1 and AO3 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC.
Continued on next page . . .
YK CentrifugalSuper Chiller
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress).For example, thehardware referencefor the CondenserPressure point isAI10.
Metasys Integrator—Metasys Integrator York Application 19
NPT1
(Cont.)NPA2 Unit Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
Min
Code
Code
Code
Code
Hour
#
#
Volt
kW
MWh
Volts
Amps
#
Hz
%
%
kVA
Deg
Deg
#
Hz
%
Anti-Recycle Timer
Operational Mode Code
Operational Code
Safety Code
Cycling Code
Runtime Hours
Number of Starts
Adaptive Capacity Control Frozen Delta p/p
VSD Output Voltage
VSD Input kW
VSD Input MWh
VSD DC Link Voltage
VSD DC link Current
VSD Surge Count
VSD Output Frequency
VSD Maximum Voltage THD
VSD Maximum Current TDD
VSD Input kVA
VSD Internal Temperature
VSD Converter Heatsink Temperature
ACC PRV Position
ACC Frozen Output Frequency
Refrigerant Level Setpoint
BD
BD
1
2
VSD IEEE 519 Filter Present 0-Not Installed
Surge Detection Type 0-Delta_p/p, 1-Current
1 Network Point Type
2 Network Point Address
20 Metasys Integrator—Metasys Integrator York Application
Table 7: YS 125-400 Ton Rotary Screw Chiller(Translator and XL Configuration)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
psi
psi
psi
psi
%
Amperes
Amperes
Amperes
Volt
Volt
Volt
DegF
%
Leaving Chill Water Temperature
Entering Chill Water Temperature
Leaving Condenser Water Temperature
Entering Condenser Water Temperature
Evaporator Saturation Temperature
Condenser Saturation Temperature
Discharge Temperature
Oil Temperature
Evaporator Pressure
Condenser Pressure
Oil Differential Pressure
Filter Differential Pressure
% Full Load Amperes
Phase A Amperes
Phase B Amperes
Phase C Amperes
Phase A-B Volts
Phase B-C Volts
Phase C-A Volts
Leaving Water Temperature Actual Setpoint
Current Actual Setpoint Feedback
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
Compressor 0-open, 1-made
Oil Solenoid 0-open, 1-made
Chill Water Pump 0-open, 1-made
Start Switch 0-open, 1-made
Flow Switch 0-open, 1-made
Eductor Solenoid 0-open, 1-made
Separator Solenoid 0-open, 1-made
AO
AO
AO
1*
2
3*
DegF
%FLA
DegC
Leaving Chill Water Setpoint (10 to 70)
Current Limit Setpoint (50 to 100)
Leaving Chill Water Setpoint (-12 to 21)
BO 1 Chiller Start/Stop 0-stop, 1-start
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
Min
Code
Code
Code
Code
Hour
#
Anti-Recycle Timer
Operational Mode Code
Operational Code
Safety Code
Cycling Code
Runtime Hours
Number of Starts
1 Network Point Type
2 Network Point Address
* Points AO1 and AO3 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC.
YS 125-400 TonRotary ScrewChiller
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress).For example, thehardware referencefor the DischargeTemperature pointis AI7.
Metasys Integrator—Metasys Integrator York Application 21
Table 8: LS 1000-1250 Ton Rotary Screw Chiller(Translator and XL Configuration)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
DegF
DegF
DegF
DegF
DegF
psi
psi
psi
psi
%
%
%
DegF
%
Leaving Chill Water Temperature
Suction Temperature
Discharge Temperature
Oil Temperature
Separator Temperature
Evaporator Pressure
Condenser Pressure
Oil Pressure
Filter Pressure
% Full Load Amperes
Slide Valve
Liquid Level
Vapor Pressure Ratio
Leaving Water Temperature Actual Setpoint
Current Actual Setpoint Feedback
BI
BI
BI
BI
1
2
3
4
Heater 0-open, 1-made
Oil Pump 0-open, 1-made
Separator Switch 0-open, 1-made
Compressor 0-open, 1-made
AO
AO
AO
1*
2
3*
DegF
%FLA
DegC
Leaving Chill Water Setpoint (38 to 70)
Current Limit Setpoint (50 to 100)
Leaving Chill Water Setpoint (3 to 210)
BO 1 Chiller Start/Stop 0-stop, 1-start
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
Min
Code
Code
Code
Code
Code
Anti-Recycle Timer
Compressor Mode
Slide Mode
Operational Code
Safety Code
Cycling Code
1 Network Point Type
2 Network Point Address
* Points AO1 and AO3 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC.
LS 1000-1250Ton RotaryScrew Chiller
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the DischargeTemperature pointis AI3.
22 Metasys Integrator—Metasys Integrator York Application
Table 9: YP Absorption Chiller(Translator and XL Configuration)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
psi
psi
psi
psi
DegF
DegF
%
Leaving Chill Water Temperature
Entering Chill Water Temperature
Leaving Condenser Water Temperature
Entering Condenser Water Temperature
Leaving Hot Water Temperature
Entering Hot Water Temperature
First Gen 1 Temperature
First Gen 2 Temperature
Refrigerant Temperature
Solution Temperature
First Gen 1 Pressure
First Gen 2 Pressure
Purge Pump Pressure
Purge Tank Pressure
Leaving Water Temperature Actual Setpoint
Leaving Hot Water Temperature Actual Setpoint
Remote Loading Setpoint Feedback
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
Refrigerant Pump 0-open, 1-made
Condenser Pump 0-open, 1-made
Chill Water Pump 0-open, 1-made
Start Switch 0-open, 1-made
Hot Water Pump 0-open, 1-made
Solution Pump 1 0-open, 1-made
Solution Pump 2 0-open, 1-made
Purge Pump 0-open, 1-made
Chill Water Flow Switch 0-open, 1-made
Hot Water Flow Switch 0-open, 1-made
Condenser Water Flow Switch 0-open, 1-made
AO
AO
AO
AO
1*
2*
3*
4*
DegF
DegF
DegC
DegC
Leaving Chill Water Setpoint (42 to 77)
Hot Water Setpoint (90 to 175)
Leaving Chill Water Setpoint (6 to 25)
Hot Water Setpoint (32 to 79)
BO 1 Chiller Start/Stop 0-stop, 1-start
1 Network Point Type
2 Network Point Address
Continued on next page . . .
YP AbsorptionChiller
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the Purge TankPressure point isAI14.
Metasys Integrator—Metasys Integrator York Application 23
NPT1
(Cont.)NPA2 Unit Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Mode
Code
Code
Code
Hour
#
#
#
#
Min
Min
DegF
DegF
%
Operational Mode
Operational Code
Safety Shutdown Code
Cycling Shutdown Code
Accumulated Operating Hours
Accumulated System Starts
Lifetime Purge Count
Max Loading
Seven Day Purge Total
Pulldown Minutes Setpoint
Pulldown Minutes Left
Pulldown Loading Start Setpoint
Pulldown Loading Stop Setpoint
Present Calculated Pulldown Loading
1 Network Point Type
2 Network Point Address
* Points AO1 and AO3 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC. The same is truefor points AO2 and AO4.
24 Metasys Integrator—Metasys Integrator York Application
Table 10: C1 U.S. Reciprocating “Intelligent” Chiller - Master(Translator and XL Configuration)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
DegF
DegF
DegF
DegF
DegF
psi
psi
psi
%FLA
psi
psi
psi
%FLA
DegF
DegF
DegF
DegF
psi
psi
DegF
DegF
DegF
Leaving Chill Water Temperature
Entering Chill Water Temperature
Leaving Condenser Water Temperature
Entering Condenser Water Temperature
Outdoor Air Temperature
Compressor 1 Suction Pressure
Compressor 1 Discharge Pressure
Compressor 1 Oil Pressure
Compressor 1 Full Load Amperes
Compressor 2 Suction Pressure
Compressor 2 Discharge Pressure
Compressor 2 Oil Pressure
Compressor 2 Full Load Amperes
Leaving Chill Water Setpoint Feedback
Low Water Temperature Cutout Feedback
Low Ambient Cutout Feedback
High Ambient Cutout Feedback
Low Pressure Cutout Feedback
High Pressure Cutout Feedback
Remote Temperature Setpoint
Remote Cooling Range
Local Barrel Setpoint
1 Network Point Type
2 Network Point Address
Continued on next page . . .
C1 U.S.Reciprocating“Intelligent”Chiller - Master
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the Outdoor AirTemperature pointis AI5.
Metasys Integrator—Metasys Integrator York Application 25
NPT1
(Cont.)NPA2 Unit Description
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Chiller Run 0-open, 1-made
Chiller Alarm 0-open, 1-made
Evaporator Heater 0-open, 1-made
Evaporator Pump Starter 0-open, 1-made
Condenser Pump Starter 0-open, 1-made
Load Permissive 0-open, 1-made
Comp 1 Liquid Line Valve 0-open, 1-made
Comp 1 Hot Gas Bypass Valve 0-open, 1-made
Comp 1 Condenser Fan Reverse 0-open, 1-made
Comp 2 Liquid Line Valve 0-open, 1-made
Comp 2 Hot Gas Bypass Valve 0-open, 1-made
Comp 2 Condenser Fan Reverse 0-open, 1-made
Sw 1 (0-Comfort Cooling, 1-Brine)
Sw 2 (0-Standard Ambient, 1-Low Ambient)
Sw 3 (0-Local, 1-Remote)
Sw 4 (0-RWT Control, 1-LWT Control)
Sw 5 (0-English Units, 1-Metric Units)
Sw 6 (0-Standard Fan Control, 1-Shared Fan Control)
Sw 7 (0-Manual Lead/Lag, 1-Auto Lead/Lag)
Sw 8 (0- Ambient Pressure Control,1- Discharge Pressure Control)
AO
AO
AO
1*
2
3*
DegF
%FLA
DegC
Leaving Chill Water Setpoint (10 to 70)
% Load Limit Setpoint (50 to 100)
Leaving Chill Water Setpoint (-12 to 21)
BO 1 Chiller Start/Stop 0-stop, 1-start
1 Network Point Type
2 Network Point Address
* Points AO1 and AO3 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC.
Continued on next page . . .
26 Metasys Integrator—Metasys Integrator York Application
NPT1
(Cont.)NPA2 Unit Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Code
Code
#
#
Min
Hour
#
Sec
Code
Code
#
#
Min
Hour
#
Sec
Min
#
#
Compressor 1:
Operational Code
Fault Code
Number of Operating Stages
Condenser Fan Forward
Anti-Recycle Timer
Runtime Hours
Number of Starts
Runtime Seconds
Compressor 2:
Operational Code
Fault Code
Number of Operating Stages
Condenser Fan Forward
Anti-Recycle Timer
Runtime Hours
Number of Starts
Runtime Seconds
Master Anti-Coincidence Timer
Load Steps Available
Lead Compressor
1 Network Point Type
2 Network Point Address
Metasys Integrator—Metasys Integrator York Application 27
Table 11: C3 U.S. Reciprocating “Intelligent” Chiller - Subordinate (Translator and XL Configuration)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
DegF
DegF
DegF
DegF
psi
psi
psi
%FLA
psi
psi
psi
%FLA
DegF
DegF
DegF
DegF
psi
psi
DegF
DegF
DegF
Leaving Chill Water Temperature
Entering Chill Water Temperature
Mixed Chill Water Temperature
Outdoor Air Temperature
Compressor 3 Suction Pressure
Compressor 3 Discharge Pressure
Compressor 3 Oil Pressure
Compressor 3 Full Load Amperes
Compressor 4 Suction Pressure
Compressor 4 Discharge Pressure
Compressor 4 Oil Pressure
Compressor 4 Full Load Amperes
Leaving Chill Water Setpoint Feedback
Low Water Temperature Cutout Feedback
Low Ambient Cutout Feedback
High Ambient Cutout Feedback
Low-Pressure Cutout Feedback
High-Pressure Cutout Feedback
Remote Temperature Setpoint
Remote Cooling Range
Local Barrel Setpoint
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Chiller Run 0-open, 1-made
Chiller Alarm 0-open, 1-made
Evaporator Heater 0-open, 1-made
Evaporator Pump Starter 0-open, 1-made
Condenser Pump Starter 0-open, 1-made
Comp 3 Liquid Line Valve 0-open, 1-made
Comp 3 Hot Gas Bypass Valve 0-open, 1-made
Comp 3 Pressure Equalization Valve 0-open, 1-made
Comp 3 Condenser Reversing Valve 0-open, 1-made
Comp 4 Liquid Line Valve 0-open, 1-made
Comp 4 Hot Gas Bypass Valve 0-open, 1-made
Comp 4 Pressure Equalization Valve 0-open, 1-made
Comp 4 Condenser Reversing Valve 0-open, 1-made
Load Permissive 0-open, 1-made
1 Network Point Type
2 Network Point Address
Continued on next page . . .
C3 U.S.Reciprocating“Intelligent”Chiller - Subordinate
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA(Network Point Address). For example, the hardware reference for the Mixed Chill Water Temperature point is AI3.
28 Metasys Integrator—Metasys Integrator York Application
NPT1
(Cont.)NPA2 Unit Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Code
Code
#
#
Min
hrs
#
Sec
Code
Code
#
#
Min
Hour
#
Sec
Min
#
#
Compressor 3:
Operational Code
Fault Code
Number of Operating Stages Condenser Fan
Forward Anti-Recycle Timer
Runtime Hours
Number of Starts
Runtime Seconds
Compressor 4:
Operational Code
Fault Code
Number of Operating Stages Condenser Fan
Forward Anti-Recycle Timer
Runtime Hours
Number of Starts
Runtime Seconds
Subordinate Anti-Coincidence Timer Load Steps Available
Lead Compressor
1 Network Point Type
2 Network Point Address
Metasys Integrator—Metasys Integrator York Application 29
Table 12: B1 U.K. Basildon Reciprocating “Intelligent” Chiller -Master (Translator and XL Configuration)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
DegF
DegF
DegF
DegF
psi
psi
psi
%FLA
DegF
psi
psi
psi
%FLA
DegF
DegF
DegF
DegF
psi
psi
DegF
DegF
DegF
Leaving Chill Water Temperature
Leaving Condenser Water Temperature
Outdoor Air Temperature
Compressor 1 Oil Temperature
Compressor 1 Oil Pressure
Compressor 1 Suction Pressure
Compressor 1 Discharge Pressure
Compressor 1 Full Load Amperes
Compressor 2 Oil Temperature
Compressor 2 Oil Pressure
Compressor 2 Suction Pressure
Compressor 2 Discharge Pressure
Compressor 2 Full Load Amperes
Leaving Chill Water Setpoint Feedback
Low Water Temperature Cutout Feedback
Low Ambient Cutout Feedback
High Ambient Cutout Feedback
Low Pressure Cutout Feedback
High Pressure Cutout Feedback
Remote Temperature Setpoint
Remote Cooling Range
Local Barrel Setpoint
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Chiller Run 0-open, 1-made
Chiller Alarm 0-open, 1-made
Evaporator Heater 0-open, 1-made
Evaporator Pump Starter 0-open, 1-made
Condenser Pump Starter 0-open, 1-made
Load Permissive 0-open, 1-made
Comp 1 Liquid Line Valve 0-open, 1-made
Comp 1 Hot Gas Bypass Valve 0-open, 1-made
Comp 1 Pressure Equalization Valve 0-open, 1-made
Comp 2 Liquid Line Valve 0-open, 1-made
Comp 2 Hot Gas Bypass Valve 0-open, 1-made
Comp 2 Pressure Equalization Valve 0-open, 1-made
Sw 1 (0-Water Cooling, 1-Brine)
Sw 2 (0-Stand Ambient, 1-Low Ambient)
Sw 3 (0-Local, 1-Remote)
Sw 4 (0-Star/Delta, 1-Part Wind)
Sw 5 (0-English Units, 1-Metric units)
Sw 6 (0-Comm Enable, 1-Comm Disable)
Sw 7 (0-Manual Lead/Lag, 1-Auto Lead/Lag)
Sw 8 (0-R134A Refrigerant, 1-R22)
1 Network Point Type
2 Network Point Address
Continued on next page . . .
B1 U.K.BasildonReciprocating“Intelligent”Chiller - Master
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the Outdoor AirTemperature pointis AI3.
30 Metasys Integrator—Metasys Integrator York Application
NPT1
(Cont.)NPA2 Unit Description
AO
AO
AO
1*
2
3*
DegF
%FLA
DegC
Leaving Chill Water Setpoint (10 to 70)
% Load Limit Setpoint (50 to 100)
Leaving Chill Water Setpoint (-12 to 21)
BO 1 Chiller Start/Stop 0-stop, 1-start
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Mode
Code
#
#
Min
Hour
#
Sec
Code
Code
#
#
Min
Hour
#
Sec
Min
#
#
Compressor 1:
Operational Code
Fault Code
Number of Operating Stages
Condenser Fan Forward
Anti-Recycle Timer
Runtime Hours
Number of Starts
Runtime Seconds
Compressor 2:
Operational Code
Fault Code
Number of Operating Stages
Condenser Fan Forward
Anti-Recycle Timer
Runtime Hours
Number of Starts
Runtime Seconds
Master Panel Anti-Coincidence Timer
Load Steps Available
Lead Compressor
1 Network Point Type
2 Network Point Address
* Points AO1 and AO3 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC.
Metasys Integrator—Metasys Integrator York Application 31
Table 13: B3 U.K. Basildon Reciprocating “Intelligent” Chiller -Subordinate (Translator and XL Configuration)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
DegF
DegF
DegF
DegF
psi
psi
psi
%FLA
DegF
psi
psi
psi
%FLA
DegF
DegF
DegF
DegF
psi
psi
DegF
DegF
DegF
Leaving Chill Water Temperature
Mixed Chill Water Temperature
Outdoor Air Temperature
Compressor 3 Oil Temperature
Compressor 3 Oil Pressure
Compressor 3 Suction Pressure
Compressor 3 Discharge Pressure
Compressor 3 Full Load Amperes
Compressor 4 Oil Temperature
Compressor 4 Oil Pressure
Compressor 4 Suction Pressure
Compressor 4 Discharge Pressure
Compressor 4 Full Load Amperes
Leaving Chill Water Setpoint Feedback
Low Water Temperature Cutout Feedback
Low Ambient Cutout Feedback
High Ambient Cutout Feedback
Low Pressure Cutout Feedback
High Pressure Cutout Feedback
Remote Temperature Setpoint
Remote Cooling Range
Local Barrel Setpoint
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Chiller Run 0-open, 1-made
Chiller Alarm 0-open, 1-made
Evaporator Heater 0-open, 1-made
Evaporator Pump Starter 0-open, 1-made
Condenser Pump Starter 0-open, 1-made
Comp 3 Liquid Line Valve 0-open, 1-made
Comp 3 Hot Gas Bypass Valve 0-open, 1-made
Comp 3 Pressure Equalization Valve 0-open, 1-made
Comp 3 Condenser Reversing Valve 0-open, 1-made
Comp 4 Liquid Line Valve 0-open, 1-made
Comp 4 Hot Gas Bypass Valve 0-open, 1-made
Comp 4 Pressure Equalization Valve 0-open, 1-made
Comp 4 Condenser Reversing Valve 0-open, 1-made
Load Permissive 0-open, 1-made
1 Network Point Type
2 Network Point Address
Continued on next page . . .
B3 U.K.BasildonReciprocating“Intelligent”Chiller - Subordinate
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA(Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is AI3.
32 Metasys Integrator—Metasys Integrator York Application
NPT1
(Cont.)NPA2 Unit Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Code
Code
#
#
Min
Hour
#
Sec
Code
Code
#
#
Min
Hour
#
Sec
Min
#
#
Compressor 3:
Operational Code
Fault Code
Number of Operating Stages Condenser Fan
Forward
Anti-Recycle Timer
Runtime Hours
Number of Starts
Runtime Seconds
Compressor 4:
Operational Code
Fault Code
Number of Operating Stages Condenser Fan
Forward
Anti-Recycle Timer
Runtime Hours
Number of Starts
Runtime Seconds
Subordinate Panel Anti-Coincidence Timer Load Steps Available
Lead Compressor
1 Network Point Type
2 Network Point Address
Metasys Integrator—Metasys Integrator York Application 33
Table 14: YR Sunline 3000 Rooftop Chiller(Translator and XL Configuration)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
DegF
DegF
DegF
DegF
psi
psi
%
%
Hour
Hour
%
%
psi
psi
psi
psi
psi
psi
DegF
DegF
psi
psi
DegF
Space Temperature
Discharge Air Temperature
Return Air Temperature
Outside Air Temperature
Duct Static Pressure
Building Air Pressure
Outside Air Damper Position 0-100%
Heating Coil Valve Position 0-100%
Supply Fan Run Hours
Exhaust Fan Run Hours
Supply Fan Inlet Guide Vane Position 0-100%
Exhaust Fan Inlet Guide Vane Position 0-100%
Compressor 1 Oil Pressure
Compressor 1 Suction Pressure
Compressor 1 Discharge Pressure
Compressor 2 Oil Pressure
Compressor 2 Suction Pressure
Compressor 2 Discharge Pressure
Low Ambient Cutout
High Ambient Cutout
Low Pressure Cutout
High Pressure Cutout
Discharge Air Temperature Cutout
BI
BI
BI
BI
BI
BI
BI
BI
BI
BIBIBIBI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Unit Run Permissive 0-open, 1-made
Air Handling Unit Alarm 0-open, 1-made
Local/Remote Selected 0-local, 1-remote
Supply Fan Run 0-open, 1-made
Return (Exhaust) Fan Run 0-open, 1-made
OA/RA Selected 0-OA, 1-RA
Refrigeration System 1 Locked Out 0-open, 1-made
Compressor 1 Contractor 0-open, 1-made
System 1 Liquid Line Solenoid Valve 0-open, 1-made
Compressor 1 Unloader Solenoid Valve 1 0-open, 1-made
Compressor 1 Unloader Solenoid Valve 2 0-open, 1-made
Compressor 1 Hot Gas Bypass Sol. Valve 0-open, 1-made
Refrigeration System 2 Locked Out 0-open, 1-made
Compressor 2 Contractor 0-open, 1-made
System 2 Liquid Line Solenoid Valve 0-open, 1-made
Compressor 2 Unloader Solenoid Valve 1 0-open, 1-made
Compressor 2 Unloader Solenoid Valve 2 0-open, 1-made
1 Network Point Type
2 Network Point Address
Continued on next page . . .
YR Sunline3000 RooftopChiller
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the Building AirPressure point isAI6.
34 Metasys Integrator—Metasys Integrator York Application
NPT1
(Cont.)NPA2 Unit Description
AO
AO
AO
1*
2
3*
DegF
#
DegC
Return Air Setpoint (10, 70)
0=Vent, 1=Heating, 2=Cooling, 3=Local Setpoints
Return Air Setpoint (-12 to 21)
BO 1 Start/Stop Command 0-stop, 1-start
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Min
Hour
Min
#
Hour
Min
#
Code
Code
Code
Code
Code
#
#
DegF
DegF
DegF
psi
psi
Anti-Coincidence Timer
Compressor 1 Run Hours
Compressor 1 Anti-Recycle Timer
Compressor 1 No. of Operating Stages
Compressor 2 Run Hours
Compressor 2 Anti-Recycle Timer
Compressor 2 No. of Operating Stages
Air Handling Unit Shutdown Code
Compressor 1 Operational Code
Compressor 1 Fault Code
Compressor 2 Operational Code
Compressor 2 Fault Code
Number of Condenser Fans Running
Cooling Load Steps Available
Actual Heating Setpoint
Actual Cooling Setpoint
Actual Discharge Air Temperature Setpoint
Actual Static Pressure Setpoint
Actual Building Pressure Setpoint
1 Network Point Type
2 Network Point Address
* Points AO1 and AO3 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC.
Metasys Integrator—Metasys Integrator York Application 35
Table 15: A1 Air-cooled Screw Chiller - Master(XL Configuration only)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
psi
psi
psi
%FLA
psi
psi
psi
%FLA
%
%
DegF
DegF
DegF
DegF
psi
psi
DegF
DegF
Leaving Chill Water Temperature
Entering Chill Water Temperature
Mixed Chill Water Temperature
Compressor 1 Suction Temperature
Compressor 1 Discharge Temperature
Compressor 1 Saturated Suction Temperature
Compressor 1 Saturated Discharge Temperature
Compressor 1 Oil Temperature
Compressor 2 Suction Temperature
Compressor 2 Discharge Temperature
Compressor 2 Saturated Suction Temperature
Compressor 2 Saturated Discharge Temperature
Compressor 2 Oil Temperature
Outdoor Air Temperature
Compressor 1 Suction Pressure
Compressor 1 Discharge Pressure
Compressor 1 Oil Pressure
Compressor 1 Full Load Amperes
Compressor 2 Suction Pressure
Compressor 2 Discharge Pressure
Compressor 2 Oil Pressure
Compressor 2 Full Load Amperes
Compressor 1 SVCALC %
Compressor 2 SVCALC %
Leaving Chill Water Setpoint
Low Water Temperature Cutout
Low Ambient Temperature Cutout
High Ambient Temperature Cutout
Low Pressure Cutout
High Pressure Cutout
Remote Temperature Setpoint
Local Cooler Barrel Setpoint
1 Network Point Type
2 Network Point Address
Continued on next page . . .
A1 Air-cooledScrew Chiller -Master
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the Outdoor AirTemperature pointis AI14.
36 Metasys Integrator—Metasys Integrator York Application
NPT1
(Cont.)NPA2 Unit Description
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
Chiller Run 0-open, 1-made
Chiller Alarm 0-open, 1-made
Evaporator Heater 0-open, 1-made
Evaporator Pump Starter 0-open, 1-made
Comp 1 Liquid Line Solenoid Valve 0-open, 1-made
Comp 1 Condenser Fan Reverse 0-open, 1-made
Comp 2 Liquid Line Solenoid Valve 0-open, 1-made
Comp 2 Condenser Fan Reverse 0-open, 1-made
Switch 1 (0=Comfort Cooling, 1=Brine Cooling)
Switch 2 (0=Standard Ambient, 1=Low Ambient)
Switch 3 (0=Local, 1=Remote)
Switch 4 (0=eev, 1=Thermal Expansion Valves)
Switch 5 (0=English Units, 1=Metric Units)
Switch 6 (0=x-Line Start, 1=wye delta start)
Switch 7 (0=Manual Lead/Lag, 1=Auto Lead/Lag)
Switch 8 (0=R134a, 1=R22)
Load Permissive 0-open, 1-made
AO
AO
AO
1*
2
3*
DegF
%FLA
DegC
Leaving Chill Water Setpoint (10 to 70)
Load Limit Setpoint (50 to 100)
Leaving Chill Water Setpoint (-12 to 21)
BO 1 Chiller Start/Stop 0-stop, 1-start
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Code
Code
#
Min
Hour
#
Code
Code
#
Min
Hour
#
Min
#
Compressor 1:
Operational Code
Fault Code
Condenser Fan Forward
Anti-Recycle Timer
Runtime Hours
Number of Starts
Compressor 2:
Operational Code
Fault Code
Condenser Fan Forward
Anti-Recycle Timer
Runtime Hours
Number of Starts
Master Anti-Coincidence Timer
Lead Compressor
1 Network Point Type
2 Network Point Address
* Points AO1 and AO3 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC.
Metasys Integrator—Metasys Integrator York Application 37
Table 16: A3 Air-cooled Screw Chiller - Subordinate (XL Configuration only)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
psi
psi
psi
%FLA
psi
psi
psi
%FLA
%
%
DegF
DegF
DegF
DegF
psi
psi
DegF
DegF
Leaving Chill Water Temperature
Entering Chill Water Temperature
Mixed Chill Water Temperature
Compressor 3 Suction Temperature
Compressor 3 Discharge Temperature
Compressor 3 Saturated Suction Temperature
Compressor 3 Saturated Discharge Temperature
Compressor 3 Oil Temperature
Compressor 4 Suction Temperature
Compressor 4 Discharge Temperature
Compressor 4 Saturated Suction Temperature
Compressor 4 Saturated Discharge Temperature
Compressor 4 Oil Temperature
Outdoor Air Temperature
Compressor 3 Suction Pressure
Compressor 3 Discharge Pressure
Compressor 3 Oil Pressure
Compressor 3 Full Load Amperes
Compressor 4 Suction Pressure
Compressor 4 Discharge Pressure
Compressor 4 Oil Pressure
Compressor 4 Full Load Amperes
Compressor 3 SVCALC %
Compressor 4 SVCALC %
Leaving Chill Water Setpoint
Low Water Temperature Cutout
Low Ambient Temperature Cutout
High Ambient Temperature Cutout
Low Pressure Cutout
High Pressure Cutout
Remote Temperature Setpoint
Local Cooler Barrel Setpoint
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
Chiller Run 0-open, 1-made
Chiller Alarm 0-open, 1-made
Evaporator Heater 0-open, 1-made
Evaporator Pump Starter 0-open, 1-made
Comp 3 Liquid Line Solenoid Valve 0-open, 1-made
Comp 3 Condenser Fan Reverse 0-open, 1-made
Comp 4 Liquid Line Solenoid Valve 0-open, 1-made
Comp 4 Condenser Fan Reverse 0-open, 1-made
Load Permissive 0-open, 1-made
1 Network Point Type
2 Network Point Address
Continued on next page . . .
A3 Air-cooledScrew Chiller -Subordinate
To get the hardware reference for mapping points to CS object attributes (via the software model), combine the NPT (Network Point Type) and NPA(Network Point Address). For example, the hardware reference for the Outdoor Air Temperature point is AI14.
38 Metasys Integrator—Metasys Integrator York Application
NPT1
(Cont.)NPA2 Unit Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Code
Code
#
Min
Hour
#
Code
Code
#
Min
Hour
#
Min
#
Compressor 3:
Operational Code
Fault Code
Condenser Fan Forward
Anti-Recycle Timer
Runtime Hours
Number of Starts
Compressor 4:
Operational Code
Fault Code
Condenser Fan Forward
Anti-Recycle Timer
Runtime Hours
Number of Starts
Master Anti-Coincidence Timer
Lead Compressor
1 Network Point Type
2 Network Point Address
Metasys Integrator—Metasys Integrator York Application 39
Table 17: YI Isoflow Absorption Chiller (XL Configuration only)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
psi
psi
psi
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
Leaving Chilled Water Temperature
Entering Chilled Water Temperature
Leaving Condenser Water Temperature
Entering Condenser Water Temperature
Automatic Decrystallization Temperature
Refrigerant Temperature Leaving the Condenser
Steam/Hot Water Supply Temperature
Refrigerant Temperature
Strong Solution Temperature
Generator Shell Pressure
Steam Supply Pressure (Steam Units Only)
Steam/Hot Water Actuator Value Position (0-100%)
Local Leaving Chilled Water Setpoint
Purge Pump Service Interval Setpoint - Hours
Active Leaving Chilled Water Setpoint
Remote Loading Setpoint
Maximum Steam/Hot Water Valve Load Setpoint
Pulldown Demand Setpoint - Minutes
Pulldown Demand Setpoint -Start Load Limit
Pulldown Demand Setpoint -Stop Load Limit
Remote Temperature Range Setpoint
Maximum Entering Condenser Water Temperature Setpoint
1 Network Point Type
2 Network Point Address
Continued on next page . . .
YI IsoflowAbsorptionChiller
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the RefrigerantTemperature pointis AI8.
40 Metasys Integrator—Metasys Integrator York Application
NPT1
(Cont.)NPA2 Unit Description
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
BI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Chilled Water Pump Status 0-Off, 1-On
Condenser Water Pump Status 0-Off, 1-On
Refrigerant Pump Motor Status 0-Off, 1-On
Solution/Absorber Pump Motor Status 0-Off, 1-On
Purge Pump Motor Status 0-Off, 1-On
Generator Pump Motor Status 0-Off, 1-On
Refrigerant and Solution Pump Motor 0-Off, 1-OnCoolant Solenoid Valve Status
Refrigerant Stabilizer Solenoid Valve 0-Off, 1-OnStatus
Refrigerant Level Solenoid Valve 0-Off, 1-OnStatus
Chilled Water Flow Switch Status 0-Open, 1-Closed
Condenser Water Flow Switch Status 0-Open, 1-Closed
Refrigerant Level Float Switch Status 0-Open, 1-Closed
Unit Switch Status 0-Stop, 1-Run
J50 Status 0-AutoRe, 1-Manual
J51 Status 0-LOA, 1-No_LOA
J52 Status 0-Englsh, 1-Metric
J54 Status 0-Limitd, 1-FullCn
J55 Status 0-DiagEn, 1-DiaDis
J57 Status 0-RTCDis,1-RTCEnb
J12 Status(Expansion I/O Board) 0-Englsh 1-German
Dilution Cycle Status 0-Open, 1-Made
Low Entering Condenser Water 0-No, 1-YesTemp Limit Active
Automatic Decrystallization Active 0-No, 1-Yes
Remote Load Limiting Active 0-No, 1-Yes
Pulldown Limiting Active 0-No, 1-Yes
AO
AO
1*
2*
DegF
DegC
Leaving Chill Water Setpoint (10 to 70)
Leaving Chill Water Setpoint (-12 to 21)
BO 1 Chiller Start/Stop 0-Stop, 1-Start
1 Network Point Type
2 Network Point Address
* Points AO1 and AO2 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC.
Continued on next page . . .
Metasys Integrator—Metasys Integrator York Application 41
NPT1
(Cont.)NPA2 Unit Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
8
9
10
11
12
13
Mode
Code
Code
Code
Code
Hour
#
#
#
Min
#
Code
DegF
Operational Mode (0-Service, 1-Local, 2-Remote)
Operational Code
Safety Shutdown Code
Cycling Shutdown Code
Warning Message Code
Total Operating Hours
Total System Starts
Lifetime Purge Count
Weekly Purge Counter
Pulldown Demand - Minutes Left
Pulldown Demand - Present Limit
Dilution Cycle Code
Maximum Steam/Hot Water Valve Unload Setpoint
BD
BD
BD
1
2
3
JP1 Status 0-Steam, 1-Hwater
JP3 Status 0-Stndrd, 1-50Hz
JP1 (Expansion I/O Board) 0-Rotary, 1-Cage
1 Network Point Type
2 Network Point Address
42 Metasys Integrator—Metasys Integrator York Application
Table 18: YG Gas Engine Drive Chiller (XL Configuration only)NPT1 NPA2 Unit DescriptionAI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
AI
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
DegF
DegF
DegF
DegF
DegF
DegF
DegF
DegF
psi
psi
psi
%
%
DegF
rpm
psi
psi
psi
psi
DegF
%
mils
mils
DegF
rpm
Leaving Chill Water Temperature
Entering Chill Water Temperature
Leaving Condenser Water Temperature
Entering Condenser Water Temperature
Evaporator Saturation Temperature
Condenser Saturation Temperature
Discharge Temperature
Oil Temperature
Evaporator Pressure
Condenser Pressure
Oil Differential Pressure
Percent Engine Load
Percent Vanes Open
Engine Jacket Water Temperature
Engine Speed
Engine Oil Pressure
Engine Manifold Pressure
Low Oil Transducer Pressure
High Oil Transducer Pressure
Leaving Water Temperature Actual Setpoint
Remote/Local Actual Engine Load Setpoint
Proximity Sensor - Actual Position
Proximity Sensor - Reference Position
Drain Line Thermocouple Temperature
Delta P over P
Surface Speed
BI
BI
BI
BI
BI
1
2
3
4
5
Engine Panel Shutdown Status 0-open, 1-made
Vent Valve Status 0-open, 1-made
Chilled Water Pump Status 0-open, 1-made
Start Switch Status 0-open, 1-made
Chilled Water Flow Switch Status 0-open, 1-made
AO
AO
AO
1*
2
3*
DegF
%FLA
DegC
Leaving Chill Water Setpoint (10 to 70)
Demand Limit Setpoint (50 to 100)
Leaving Chill Water Setpoint (-12 to 21)
BO 1 Chiller Start/Stop 0-stop, 1-start
1 Network Point Type
2 Network Point Address
* Points AO1 and AO3 are the same point and will have the same value. Two pointsare provided because of the different ranges for DegF and DegC.
Continued on next page . . .
YG Gas EngineDrive Chiller
To get the hardwarereference formapping points toCS object attributes(via the softwaremodel), combine theNPT (Network PointType) and NPA(Network PointAddress). Forexample, thehardware referencefor the EngineSpeed point is AI15.
Metasys Integrator—Metasys Integrator York Application 43
NPT1
(Cont.)NPA2 Unit Description
ADF
ADF
ADF
ADF
ADF
ADF
ADF
1
2
3
4
5
6
7
Min
Code
Code
Code
Code
Hour
#
Anti-Recycle Time Left
Operating Mode
Operation Code
Safety Shutdown Code
Cycling Shutdown Code
Accumulated Operating Hours
Accumulated System Starts
ADI 1 Code Engine Type0-G3408, 1-G3412, 2-G3508, 3-G3512,4-G3516, 5-G3606
1 Network Point Type
2 Network Point Address
44 Metasys Integrator—Metasys Integrator York Application
Metasys Integrator—Metasys Integrator York Application 45
Metasys Network Setup
Metasys Network setup is described in the Metasys Integrator technicalbulletins in the Metasys Connectivity Technical Manual (FAN 629.5). Thissection contains details specific to York applications.
Table 19: Software Model and CS Object DetailsApplication Software Model
(on Tables andModels CD-ROM)
Display Attribute(recommended)
NT CommandAttribute
(recommended)
Login YK_TRAN.DDL BI1 BI1*
YT Chiller YK_YTCH.DDL AI1 BO1
YK Chiller YK_YKCH.DDL AI1 BO1
YS Chiller YK_YSCH.DDL AI1 BO1
LS Chiller YK_LSCH.DDL AI1 BO1
YP Chiller YK_YPCH.DDL AI1 BO1
C1 Chiller YK_C1CH.DDL AI1 BO1
C3 Chiller YK_C3CH.DDL AI1 BI1*
B1 Chiller YK_B1CH.DDL AI1 BO1
B3 Chiller YK_B3CH.DDL AI1 BI1*
YR Chiller YK_S3000.DDL AI1 BO1
A1 Chiller YK_A1XL.DDL AI1 BO1
A3 Chiller YK_A3XL.DDL AI1 BI1*
YI Chiller YK_YIXL.DDL AI1 BO1
YG Chiller YK_YGXL.DDL AI1 BO1
* The NT Command attribute must be defined; it cannot be null. However, since thepoints are not commandable, you will not be able to command the attribute.
Mapping to aCS Object
46 Metasys Integrator—Metasys Integrator York Application
Metasys Integrator—Metasys Integrator York Application 47
Custom Integration
For information on integrating products that are not discussed in thisdocument, first refer to the Metasys Compatible Global Catalog, an onlinelist of released Connectivity products. If this list does not provide theinformation you require, consider using the System Integration ProjectData Sheet to request a custom contract from the System IntegrationTeam.
Both the Metasys Compatible Global Catalog and the System IntegrationProject Data Sheet can be accessed from The Advisor by performing thefollowing steps:
1. Click on the Systems Products button located on the left side of TheAdvisor home page.
2. Click on the Product Literature link.
3. Click on the Manuals-FANS link.
4. Click on the 629.0 Metasys Connectivity Sales Resource Manual link.
5. Find the System Integration Project Data Sheet link in the table ofcontents. Click on this link to view an online copy of the SystemIntegration Project Data Sheet, or click on the Metasys CompatibleGlobal Catalog link below it to view a list of released Connectivityproducts.
The System Integration Project Data Sheet (LIT-6290052) also can befound in the Metasys Connectivity Sales Resource Manual (FAN 629).
If you need further assistance, contact Johnson Controls Field SupportCenter.
48 Metasys Integrator—Metasys Integrator York Application
Notes
www.johnsoncontrols.comControls Group FAN 629.5507 E. Michigan Street Metasys Connectivity Technical ManualP.O. Box 423 Metasys Integrator Release 9.0Milwaukee, WI 53201 Printed in U.S.A.