Direct Two-Way Or Punching Shear Force: The direct shear force, V u , to be resisted by the slab- column connection can be calculated as the total factored load on the area bounded by panel centerlines around the column less the load applied within the area defined by the critical shear perimeter. This is to be calculated both at the column perimeter and at the perimeter of drop panel, if present, using the critical section defined in Figs. 12.18 and 12.19.

Upload: saulat-jillani

Post on 04-Jun-2018

219 views

Category:

Documents


1 download

TRANSCRIPT

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 1/44

Direct Two-Way Or Punching Shear Force:

The direct shear force, V u, to be resisted by the slab-

column connection can be calculated as the totalfactored load on the area bounded by panel centerlines

around the column less the load applied within the area

defined by the critical shear perimeter.

This is to be calculated both at the column perimeter

and at the perimeter of drop panel, if present, using the

critical section defined in Figs. 12.18 and 12.19.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 2/44

Edge Of Slab

d / 2

lesser than1) b2 / 2

2) 4h

b2

b1

Fig. 12.19. Critical Section For Edge Column.

Eccentric Punching Shear Force:

According to ACI 11.2.6.2, the shear stress resulting from

moment transfer by eccentricity of shear shall be assumed

to vary linearly about the centroid of the critical section.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 3/44

bo = 2c1 + 2c2 + 4d 

V u = qu [l1l2 –  b1 b2]

C

C

C

AD

B

b1 = c1 + d 

b2

=c2

+ d 

c1

c2

Centroid

al axis

+

c

=

γf  M u

γν M u

a) Slab-Column Connection

 b) Critical Section For Shear 

C

Cv =

Applied direction

of forces is shown.

c1 + d 

c2 + d 

c) Direct Shear 

d) Eccentric Shear 

e) Resultant Shear 

Fig. 12.20. Two-Way Shear Acting on CriticalSlab Section Around Column.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 4/44

The resultant shear stress acting on the critical perimeter,

considering moment acting from both the directions, may be written as follows:

vu at face AB =   ± ±c

u

 A

V    ( )

1

2

1

1

c

uu

 J 

b

 M     

 

 

 γ    ( )

2

2

2

2

c

uu

 J 

b

 M     

 

 

 γ 

Where, Ac and J c are calculated for the faces of a box-like shape defined by the assumed vertical failure

section.

 Ac = perimeter area of the critical section

=   bod  = 2(b1 + b2) d 

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 5/44

 J c = torsional constant, like polar moment of

inertia of the area Ac

=   I x + I y

Torsional Constant For Interior Column:

The critical area subjected to punching shear is a three

dimensional area and hence the calculation of itstorsional constant is not as simple as for any planar area.

In order to get a reasonably good estimate, the width ofthe area may be squeezed to zero but maintaining the

original area.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 6/44

Centroidal axis of

the critical area

Moment in b1

direction

b2

b1

z

x

y

A

B

C

D

(a)Critical Perimeter Section OverInterior Column.

 y

 x

 A = b2 d   A = b2 d 

 A = 2b1 d 

(b)2-D Area Equivalent to Area in (a)Looking From z-Direction.

Fig. 12.21. Critical Section For Two-Way Shear Over Interior Column.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 7/44

 J c

=  I x

for faces AD and BC +  I x

for faces AB and CD

+   I y for faces AD and BC +   I y for faces AB and CD

= 2 × + 0 + 2 × + 2 ×

+ 012

3

1d b

+ 0

12

3

1db

( )

 

 

 

 2

1

2 2

b

d b

=266

2

12

3

1

3

1   bdbdbd b++

Torsional Constant For Edge Column:

 x1 = =( )d bd b

bd b

21

11

222

+ 21

2

1

2   bbb+

 Ac = (2b1 + b2) d 

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 8/44

z

y

x

C.A.

x1

 b1

 y

 x

 A = b2 d  A = 2b1 d 

(b)2-D Area Equivalent to Area in (a)

Looking From z-Direction.

Fig. 12.22. Critical Section For Two-Way Shear Over Edge Column.

 J c

=   ( )( )2

12

2

11

1

3

1

3

1

212122   xd b x

bd b

dbd b+

 

  

 −++×

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 9/44

Torsional Constant For Corner Column:

 y

 x

 A = b2 d  A = b1 d 

(b)2-D Area Equivalent to Area in (a)

Looking From z-Direction.

z

y

x

C.A.

x1

 b1

 b2

Fig. 12.23. Critical Section For Two-Way Shear Over Corner Column.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 10/44

 x1 = =( )d bd b

bd b21

11 2+ 21

2

1

2   bbb+

 Ac = (b1 + b2) d 

 J c =   ( )( )2

12

2

11

1

3

1

3

1

21212

 xd b xb

d bdbd b

+

 

 

 

 −++

Concrete Punching Shear Strength (V c):

According to ACI 11.12.2.1, for non-prestressed slabsand footings, V c shall be the smallest of:

a)   V c =   bod c f  ′ 

 

 

 

+  β 

2

16

1

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 11/44

 β   = of column, concentrated load, or section area.sideshort

sidelong

bo = perimeter of critical section for slabs and footings.

 b)  V c =   bod 

where   α    = 40 for interior columns= 30 for edge columns

= 20 for corner columns

c

o

 s  f b

d ′

 

  

 + 2

12

1   α 

c) V c =   bod c f  ′

3

1

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 12/44

For design, maximum shear stress due to the factored

shear force and moment   ≤ φ vn

where φ vn =

V s = 0, when no shear reinforcement in slabs

in the form of shear heads.

( ) ( )d bV V  o sc +φ 

Shear Head To Improve Strength

Against Punching Shear:

Four types of shear heads, shown in Figs. 12.24 and

12.25, may be designed over the top of columns in case

the concrete strength alone is not sufficient to resist theapplied punching shear.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 13/44

d / 2

≤ d / 2

d / 2

Critical

Section

lv − c1/2

¾ (lv − c1/2)

(a) Stirrup Shear Reinforcement.(b) Large Interior Shear Head of

Channel Sections.

Fig. 12.24. Typical Shear Heads.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 14/44

lv − c1/2

¾ (lv − c1/2)d / 2

d / 2

(a) Small Interior Shear Head of

Channel Section. (b) Shear Head of Stud Connectors.

Fig. 12.25. More Examples of Shear Heads.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 15/44

According to ACI 11.12.3, shear reinforcement consisting of bars,

wires, single leg stirrups and double leg stirrups may be provided

in slabs and footings with effective depth greater than or equal to

greater of 150 mm and 16 times the shear reinforcement bar

diameter.

This reinforcement must engage the longitudinal flexural

reinforcement in the direction being considered.

To calculate the shear strength with shear reinforcement, themaximum value of  V c is taken equal to bod and V s is not to be

taken greater than   bod .c f  ′6/1

c f  ′3/1

In other words, the maximum two-way shear strength cannotexceed bod , even if shear reinforcement is provided.c f  ′2/1

The area of shear reinforcement, Av, is equal to area of all legs of

reinforcement on one perimeter of the column section.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 16/44

• The distance between the column face and the first lineof stirrup legs that surround the column must not exceed

d /2.

• The spacing parallel to the column face between thestirrups in this first line must not exceed 2d .

• The spacing between successive lines of shearreinforcement that surround the column must not exceedd /2 measured in a direction perpendicular to the columnface.

• Structural steel I− and channel−shaped sections are alsoallowed in the slabs.

• Arms of the shear-head must not be interrupted within

the column sections.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 17/44

• The section should not be a depth greater than 70

times the web thickness of the steel shape.• All compression flanges of the structural shapes

are to be located within 0.3d of compression

surface of the slab and these sections may be

considered to be effective in resisting the

moments besides providing the shear strength.• The ratio (a

v) between the flexural stiffness of

each shear-head arm and that of the surroundingcomposite cracked slab section of width (c

2+ d )

must not be less than 0.15.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 18/44

Example 12.1: Perform check for punching

shear of a two-way slab system (Fig. 12.26) at thegiven edge column. The panel size is 6m × 8m and

all conditions of direct design method are satisfied.The other related data is as under:

qu = 11,000 Pa M 

u(unbalanced)= 200 kN-m

 f c′ = 25 MPah = 230 mm

d  = 190 mm

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 19/44

Solution:

 β  = longer / shorter sides ratio for the column = 2.0

600mm

1200mm 8 m

3.5 m

Direction of

unbalanced

moment

200mm

Fig. 12.26. Slab System For Example 12.1.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 20/44

b1

= 600 + 190/2 + 200 = 895 mm

b2

= 1200 + 190 = 1390 mm

bo

= 2 b1

+ b2

= 3180 mm

α s = 30 for the edge column

vc

= the least out of the following

i) = = 1.667 MPac f  ′

 

 

 

 +

 β 

21

6

125

0.2

21

6

1

 

 

 

  +

ii) = = 1.580 MPac

o

 s  f b

d ′

 

  

 + 2

12

1   α 252

3180

19030

12

1

 

  

  +×

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 21/44

iii) = = 1.667 MPac f  ′

3

125

3

1

φ vc

= 0.75 × 1.580 = 1.185 MPa

Ac

=   bo × d  = 3180 × 190 = 604,200 mm2

 x1 = = = 252 mm21

2

1

2   bb

b

+ 13908952

8952

 J c

= ( )( )2

12

2

11

1

3

1

3

1

21212

2   xd b xb

d bdbd b

+

 

  

 −++×

=

 

  

  −××+×

×233

2522

895190895

12

895190

12

1908952

( )( )22521901350 ×+

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 22/44

 J c

= 5,349,563 × 104 mm4

γ f 

  = = = 0.651

2

1

3

21

1

b

b+

1390

895

3

21

1

+

γ f 

= 1 − γ f 

= 0.349

More flexural steel is to be provided near the column, ina width of c2 + 3h, to transfer 65.1% of moment.

Direct shear force, V u =   qu [length × width –  b1 b2]

= = 294.3 kN( )( ) ( )( )[ ]390.1895.085.31000

000,11−

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 23/44

Direct shear stress = V u / Ac = 294.3 × 1000 / 604,200

= 0.487 MPaEccentric shear =

c

u

 J 

 x M  1ν γ 

= = 0.329 MPa4

6

10563,349,5

25210200349.0

××××

Total applied shear, ν u   = 0.486 + 0.329 = 0.815 MPa

ν u   ≤   φν c   ⇒ The slab is safe against two-way shear .

If ν u > φν c , following solutions are possible:

* Design a shear head.

* Provide drop panels or column capitals.

* Slightly increase the depth of slab if the differenceof  ν u and φν c is smaller .

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 24/44

Example 12.2: Design reinforcement for the interior

 panel of the flat plate floor system, shown in Fig. 12.27.Assume that direct design method is applicable and the

depth criterion is satisfied using a depth of 220 mm.

Check the depth of slab for shear considering the effect ofeccentric shear equal to 15% of the direct shear for this

interior panel. The other related data is as under:

Live load = 300 kgs/m2

Floor finish and partitions = 150 kgs/m2

 M u (unbalanced) = 200 kN-m f c′ = 25 MPa

 f y = 300 MPa

h = 220 mm

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 25/44

750 mm φ Columns

6m

8m

Fig. 12.27. Typical Interior Panel of Slab System For Example 12.2.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 26/44

Solution:

Equivalent square column side, h =4

π (750) = 665 mm

qL = 300 N/m2

qD = 0.220 × 2400 + 150 = 678 N/m2

qu

= [1.2(qD

) + 1.6(qL

)] × 9.81 / 1000

= [1.2(678) + 1.6(300)] × 9.81 / 1000

= 12.69 kN/m2

The column and middle strips are shown in Fig. 12.28.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 27/44

665mm square2.5m

1.5m

1.5m = Half 

Middle Strip

Column

Strip

1.5m

1.5m

1.5m

Fig. 12.28. Equivalent Columns And Column And Middle Strips.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 28/44

1. E−W Span

l1 = 8ml2 = 6m

ln

= 8.0 – 0.665 = 7.335 m

l2w = 6.0 m

 M o =   qu 8

2

2   nw  ll

= (12.69)

( )( )8

335.70.62

= 512.1 kN-m

 Support Section (Top steel, E–W Direction)

 M

= 0.65 M o = 0.65 (512.1) = 332.9 kN-m A = l2/l1 = 0.75

α  f1 = 0 (no beam), D = 0

%age CS moment out of positive moment = 75%%age CS moment out of positive moment = 60%

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 29/44

Column Strip: 0.75 (332.9) = 249.7 kN-m

Middle Strip: 0.25 (332.9) = 83.2 kN-m

 Mid Span Section (Bottom steel, E–W Direction)

 M +

= 0.35 M o= 0.35 (512.1) = 179.2 kN-mColumn Strip = 0.60 (179.2) = 107.6 kN-m

Middle Strip = 0.40 (179.2) = 71.6 kN-m

2.0 N – S Span

l1 = 6m

l2 = 8m

ln = 6.0 – 0.665 = 5.335m

l2w = 8m

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 30/44

 M o = (12.69) = 361.2 kN-m( )( )

8

335.50.82

 Support Section (Top steel, N–S Direction)

 M − = 0.65 M o = 0.65 (361.2)= 234.8 kN-m

Column Strip = 0.75 M − = 0.75 (234.8) = 176.1 kN-m

Middle Strip = 0.25 M − = 0.25 (234.8) = 58.7 kN-m

 Mid Span Section

 M + = 0.35 M o = 0.35 (361.2) = 126.4 kN-m

Column Strip = 0.60 (126.4) = 75.8 kN-m

Middle Strip = 0.40 (126.4) = 50.6 kN-m

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 31/44

3m

3m

3m

3m′3m 5m

176.1

176.1

176.1

176.1

249.7 249.7

249.7 249.7

75.8 75.8

83.2 83.2

58.7

58.7

107.6

107.6

71.6

50.6

Fig. 12.29. Moments Across Full Width of Strips For Example 12.2.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 32/44

 smax = 2h = 440 mm

d  = 220 − 20 − 16 − 6 = 178 mm(lesser value for the inner steel)

 ρ min   = 0.0020 , As,min  = 0.002 × 1000 × 220

= 440 mm2/m width

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 33/44

Table 12.12. Calculation of Slab Steel For Example 12.2.

Design

Frame

Location Strip Width

mm

Mu

kN-m

= M u/bd 2

  As

mm2

Steel

E-W Support

Top steel

CS 3000 249.7 2.627 0.0106 1887 #19@150mm c/c

MS 3000 83.2 0.875 0.0033 587 #13@200mm c/c

E-W Mid-span

Bot. steel

CS 3000 107.6 1.132 0.0046 819 #13@150mm c/c

MS 3000 71.6 0.753 0.0029 516 #13@250mm c/c

 N-S Support

Top steel

CS 3000 176.1 1.853 0.0076 1353 #19@200mm c/c

MS 5000 58.7 0.371 0.0025 445 #10@160mm c/c

 N-S Mid-span

Bot. steel

CS 3000 75.8 0.797 0.0033 587 #13@200mm c/c

MS 5000 50.6 0.319 0.0025 445 #10@160mm c/c

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 34/44

Table 12.13. Curtailment of Slab Steel For Example 12.2.

Design

Frame

Span Lengths Column Strip

+ ½ Eq. Column Size

Middle Strip

+ ½ Eq. Column Size

l1

(mm)

ln

(mm)

0.30  ln

(mm)

0.20  ln

(mm)

0.22  ln

(mm)

0.15  ln

(mm)

E-W 8000 7335 2540 1800 1950 1430

 N-S 6000 5335 1940 1400 1510 1130

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 35/44

1400

1940

#10@160 (alt.)

150mm lap

Full tension

splice

1130

1510

1510

#19@200 (alt.)

#13@200 (alt.)

#10@160

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 36/44

150mm lap

Full tension

splice

1430 Each

2540

1950 1950

#13@250 (alt.)

#13@150 (alt.) #13@200

#19@150 (alt.)

25401800 Each

Fig. 12.30. Detailing For Slab of Example 12.2.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 37/44

Example 12.3: Calculate the design moments for the

exterior panel of the flat plate system given in Fig. 12.31, perpendicular to the edge. The other related data is as

under:

Clear cover = 20 mm

Grade of steel = 420 MPa

Superimposed qD = 150 kgs/m2

Live load qL = 300 kgs/m2

 f c′ = 20 MPa

Solution:

Longer  ln = (6000 – 375) / 1000 = 5.625 m

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 38/44

375mm×375mm Columns

l2=5.5m

l1=6.0m

l2=5.5m

Fig. 12.31. Flat Slab of Example 12.3.

hmin.

  ≅   ln

/ 30 for  f y

= 420 MPa   ≥ 120 mm

= (5.625×1000) / 30 = 187.5 mm ≥ 120 mm

OK 

Try   h = 200 mm

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 39/44

Total Static Moment

qD = 0.2 × 2400 + 150 = 630 kgs/m2

qL = 300 kgs/m2

qu = [1.2(630) + 1.6(300)] × 9.81 / 1000

= 12.13 kN/m2

l2w = 5.5 m

 M o = =

= 263.8 kN-m8

2

2   nwuq   ll

8

625.55.513.12 2××

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 40/44

Longitudinal Distribution Of Moments

Mo = 263.8

Int. M    =0.70Mo = −184.7kN-m

M+ = 0.52Mo = +137.2kN-m

Ext. M    =0.26Mo = −68.6kN-m

Torsional Member

There is no edge beam and 375mm width of slab may be

assumed to act as a torsion member, as shown in Fig.12.32.

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 41/44

L-section in l2 direction

 x = 200mm

 y = 375mm

X-section inl

1direction

8″

5500mm

Fig. 12.32. Torsion Member For Example 12.3.

C  = = 66,400 × 104 mm4

363.01

3 y x

 y

 x∑  

 

  

 −

 I s = = 366,667 × 104 mm4

12

2005500 3×

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 42/44

 β t

=

= = 0.09

 scs

cb

 I  E 

C  E 

2

( )( )4

4

10667,3662

10400,66

×

×

 A =   l2 / l1 = 5.5 / 6.0 = 0.917

 B =   β t = 0.09

α f1   = 0   ⇒   D = = 0

1

21

l

l

 f α 

Transverse Distribution Of Moments

The column strip moment percentages are calculated asunder:

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 43/44

Int. M − = 75 + 30(1− A) D = 75%

Ext. M − = 100 − 10 B + 12 BD(1 − A) = 99.1%

 M + = 60 + 15(3−2 A) D = 60%

Mo = 263.8

Int. M  =0.70Mo = −184.7kN-m

M+ = 0.52Mo = +137.2kN-m

Ext M  =0.26Mo = −68.6kN-m

CS = 0.75(−184.7) = 138.5kN-m

MS = 0.25(−184.7) = 46.2kN-m

CS = 0.60(137.2) = 82.3kN-m

MS = 137.2−82.3 = 54.9kN-m

CS = −68.0k-ft (99.1%)

MS = very small

8/13/2019 M.sc-rC-7 Direct Design Method 2

http://slidepdf.com/reader/full/msc-rc-7-direct-design-method-2 44/44