On-Line Dynamic Security Assessment: Its Role and Challenges for Smart Control Centers Lei Wang Powertech Labs Inc. Surrey, BC, Canada [email protected]

Upload: others

Post on 16-Oct-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

On-Line Dynamic Security Assessment: Its Role and Challenges for Smart

Control Centers

Lei WangPowertech Labs Inc.Surrey, BC, [email protected]

Page 2: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

A very simple version of Smart Grid

Hardware / software added to a power system to achieve:

Focused areas:

• A more autonomous responsiveness to events that impact the

electrical power grid

• Optimal day-to-day operational efficiency

of electrical power delivery

Information

technologies

Demand

management

Transmission

grid

Renewable-

based systems

Page 3: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

Smart Transmission Grid

Smarttransmission

network

Smartcontrolcenter

Smartsubstation

• System monitoring and visualization

• Real-time modeling and validation

• Real-time analyses

• Predictive analyses

• Controllability

• Information for dispatchers/operators

• Interactions with power market

Page 4: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

Smart Control Center

• Modernization of control centers involves

development and application of

technologies in many areas

• One of these that is critical to the grid

operation: Dynamic Security

Assessment (DSA)

• This is to answer three basic functions:

– How well a system condition can withstand

credible contingencies (degree of stability)

– What is the maximum secure power transfer

under these contingencies (stability limits)

– What can be done to prevent possible

insecurity (remedial control actions)

Page 5: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

• Assume that a system is operating at a point A– Measured by some system parameters (e.g. interface flows)

What does this mean?

Interface X

Interface Y

X0

Y0A

Stability limit

Stability limit

– Determined to be secure for all credible contingencies

• We need to know what is the secure region within which the system can move

• If the system needs to move to an insecure point for some reason, what needs to be done to ensure the system security– For example, special protection system settings

Extended security region

Page 6: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

Analysis and computation requirements

• Need to work with models of an interconnected power system– The full Eastern US/Canada interconnected system models have

more than 60,000 buses and 8,000 generators

• Use various mathematical techniques– Powerflow

– Time-domain simulations

• Examine a set of contingencies over a range of system conditions– N-1, N-2, N-G outages, etc.

– Different load levels, generator dispatches, power transfers, etc.

• Ensure that a set of security criteria are met– Steady state (thermal, voltage)

– Dynamic (voltage, transient, small signal, frequency)

Page 7: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

Challenges

• DSA has been traditionally performed using off-line

studies

• Problems with this approach:

– Number of possible conditions and contingencies becomes

unmanageable as system complexity increases

– Exact system state is rarely accurately captured by forecast

– Most study results are never used resulting in high wastage

– Conditions which usually cause problems are often not studied

off-line (such as an N-1 event evolving into N-3 event)

Solutions

Avoid using forecasted system conditions for DSA

. . . perform the calculations on-line in real time

Page 8: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

On-line DSA functional overview

Page 9: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

Main benefits

• System security status monitoring

• Stability limit determination

• Recommendations for preventive/corrective control actions

• Impact assessment of renewables on system security

• Verification of Special Protection Systems (SPS)

• Transaction settlements in power market

• Determination of active and reactive power reserves

• Scheduling of equipment maintenance

• Support to PMU/WAMS applications

• Calibration and validation of power system models

• Preparation of models for system studies

• Post-mortem analysis of incidents

• System restoration

Page 10: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

State-of-the-art

• On-line DSA is not new; it has been proposed, discussed, and

developed for over 40 years

– It has matured in the past decade

• This technology has been increasingly included as one of

the advanced network applications in EMS

• Performance

– Real-time models with 13,500 buses and 2,500 generators

– Processing of 3,000 contingencies and 40 stability limits

– Computation cycle within 20 minutes

Page 11: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

Applications of on-line DSA

• At least 7 out of 10 ISO/RTO in North America have, or are

implementing, on-line DSA systems

CAISO

ERCOT

AESO

IESO

MISO

PJM

ISO NE

• On-line DSA systems using Powertech’s DSAToolsTM software have

been implemented in 35 control centers around the world

Page 12: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

Application example – EirGrid

CARRICK-ON-SHANNON

CLOON

GILRA

BLAKE

WOODLAND

FLAGFORD

GALWAYMAYNOOTH

CARLOW

DUNSTOWN

KILTEELNEWBRIDGE

DRUMLINE

ENNIS

TULLABRACK

DALLOW

PORTLAOISE

IKERRIN

LOUTHSHANKILL

NAVANKNOCKUMBER

MULLINGAR

ATHLONE

LANESBORO

CASTLEBAR

RICHMOND

FERBANE

SHANNONBRIDGECASHLA

POLLAPHUCA

RHODE

SOMERSET

ARIGNA

MEATH HILL

THORNSBERRY

KELLIS

TARBERT

DUNMANWAY

RAFFEEN

MOY

TAWNAGHMORE

CAHIR

MUNGRET

LIMERICK

BUTLERSTOWNWATERFORD

ANNER

BANDON

MACROOMCARRIGADROHID

INNISCARRA

TRABEGMARINA

MONETEEN

RATHKEALE

CASTLEFARMAUGHINISH

MONEYPOINT KILKENNY

KILTOY

LETTERKENNY

BELLACORICK

KNOCKRAHA

CATHALEEN'SFALL CLIFF

SLIGO

DUNGARVAN

CRANE

WEXFORD

THURLES

DOONBALLYDINE

GREAT ISLAND

BARRYMORE

MALLOWKNOCKEARAGH

KILLONAN

BRINNY

LISDRUM

MIDLETON

CHARLEVILLE

AHANEPROSPECT

TRIEN

AGHADA

ARDNACRUSHA

BINBANEGOLAGH

TURLOUGHHILL

CARRICKMINESFASSAROE

GRANGEFINGLAS

INCHICORE

NORTHWALLPOOLBEG

SHELLYBANKS

SHELTONABBEY

KILBARRY

TRALEE

RINAWADE

PLATIN

GLASMORE

ARKLOW

DRYBRIDGE

GORTAWEE

OUGHTRAGH

LISHEEN

DUNDALK

ARVA

MULLAGHARLIN

NORTHERNIRELAND

Waringstown

Banbridge

Newry

Tandragee

DungannonOmagh

Enniskillen

MagherafeltNorfil

Antrim

KellsBallymena Larne

B

Ballylumford

Coleraine

LimavadyCOOLKEERAGH

Strabane

Rathgael

EdenCarndonagh

G

CERK

CastlereaghFHannaghstown

Ballynahinch

Drumnakelly

Kilroot

Gobnascale

*

Corraclassy1981

CREA

705207101175810

9002071511

75520 75010

77510

82020

79010

81520

75211

83011

83510

7001185020

86511

87011

87510

88011

89510

90511

Loguestown84511

Lisburn84011

74520TYRONE

90320

77010

81020DG

P.S.W.

Moyle86220

Scotland86221

IRISHTOWN

TRILLICK

CLASHAVOON

CULLENAGH

DALTON

CARRICK-ON-SHANNON

CLOON

GILRA

BLAKE

WOODLAND

FLAGFORD

GALWAYMAYNOOTH

CARLOW

DUNSTOWN

KILTEELNEWBRIDGE

DRUMLINE

ENNIS

TULLABRACK

DALLOW

PORTLAOISE

IKERRIN

LOUTHSHANKILL

NAVANKNOCKUMBER

MULLINGAR

ATHLONE

LANESBORO

CASTLEBAR

RICHMOND

FERBANE

SHANNONBRIDGECASHLA

POLLAPHUCA

RHODE

SOMERSET

ARIGNA

MEATH HILL

THORNSBERRY

KELLIS

TARBERT

DUNMANWAY

RAFFEEN

MOY

TAWNAGHMORE

CAHIR

MUNGRET

LIMERICK

BUTLERSTOWNWATERFORD

ANNER

BANDON

MACROOMCARRIGADROHID

INNISCARRA

TRABEGMARINA

MONETEEN

RATHKEALE

CASTLEFARMAUGHINISH

MONEYPOINT KILKENNY

KILTOY

LETTERKENNY

BELLACORICK

KNOCKRAHA

CATHALEEN'SFALL CLIFF

SLIGO

DUNGARVAN

CRANE

WEXFORD

THURLES

DOONBALLYDINE

GREAT ISLAND

BARRYMORE

MALLOWKNOCKEARAGH

KILLONAN

BRINNY

LISDRUM

MIDLETON

CHARLEVILLE

AHANEPROSPECT

TRIEN

AGHADA

ARDNACRUSHA

BINBANEGOLAGH

TURLOUGHHILL

CARRICKMINESFASSAROE

GRANGEFINGLAS

INCHICORE

NORTHWALLPOOLBEG

SHELLYBANKS

SHELTONABBEY

KILBARRY

TRALEE

RINAWADE

PLATIN

GLASMORE

ARKLOW

DRYBRIDGE

GORTAWEE

OUGHTRAGH

LISHEEN

DUNDALK

ARVA

MULLAGHARLIN

NORTHERNIRELAND

Waringstown

Banbridge

Newry

Tandragee

DungannonOmagh

Enniskillen

MagherafeltNorfil

Antrim

KellsBallymena Larne

B

Ballylumford

Coleraine

LimavadyCOOLKEERAGH

Strabane

Rathgael

EdenCarndonagh

G

CERK

CastlereaghFHannaghstown

Ballynahinch

Drumnakelly

Kilroot

Gobnascale

*

Corraclassy1981

CREA

705207101175810

9002071511

75520 75010

77510

82020

79010

81520

75211

83011

83510

7001185020

86511

87011

87510

88011

89510

90511

Loguestown84511

Lisburn84011

74520TYRONE

90320

77010

81020DG

P.S.W.

Moyle86220

Scotland86221

IRISHTOWN

TRILLICK

CLASHAVOON

CULLENAGH

DALTON

• The Irish national grid company

• Interconnected to Northern Ireland

through AC and to UK through DC

• Small system but with high wind power

penetration

– Maximum wind generation recorded in 2009

supplied 43% of total load (this is 78% of

the installed wind capacity)

– The aim is for 40% of electricity to be produced from renewable

energy sources (mostly wind) in 2020

• The question: what is the highest amount of wind

generation allowed at any given instant of time?

– Subject to thermal, voltage, frequency, and stability criteria

Page 13: On-Line Dynamic Security Assessment: Its Role and ...mydocs.epri.com/docs/PublicMeetingMaterials/1202/MVNQQ2YVLLT… · EirGrid control center as a real-time application –Based

EirGrid’s WSAT application

• A Wind Security Assessment Tool (WSAT) is installed in

EirGrid control center as a real-time application

– Based on Powertech’s DSAToolsTM technology

• Provides max allowable wind generation for

– Real-time condition

– Forecast condition (integrated with wind forecast data)

Wind security assessment results for a 42-hour time window

Actual total wind generation

Wind generation limit

based on real-time data

Forecast total wind generation

Wind generation limit

based on forecast data