Page 1: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

PNOZ m EF 8DI4DO

Operating Manual­1002661­EN­02

Configurable Control System PNOZmulti

Page 2: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

PrefaceThis document is a translation of the original document.

All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be madefor internal purposes. Suggestions and comments for improving this documentation will begratefully received.

Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®,SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarksof Pilz GmbH & Co. KG in some countries.

 SD means Secure Digital

Page 3: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Content

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

3

Section 1 Introduction 41.1 Validity of documentation 41.2 Retaining the documentation 41.3 Definition of symbols 4

Section 2 Overview 62.1 Scope of supply 62.2 Unit features 62.3 Front view 7

Section 3 Safety 83.1 Intended use 83.2 System requirements 83.3 Safety regulations 83.3.1 Use of qualified personnel 83.3.2 Warranty and liability 83.3.3 Disposal 93.3.4 For your safety 9

Section 4 Function description 104.1 Integrated protection mechanisms 104.2 Functions 104.3 System reaction time 104.4 Block diagram 10

Section 5 Installation 115.1 General installation guidelines 115.2 Dimensions 115.3 Connecting the base unit and expansion modules 11

Section 6 Commissioning 126.1 Wiring 126.2 Download modified project to the PNOZmulti safety system 126.3 General wiring guidelines 126.4 Connection 12

Section 7 Operation 157.1 Messages 15

Section 8 Technical details 168.1 Safety characteristic data 19

Section 9 Supplementary data 209.1 Permitted ambient temperature Tamb dependent on the total current Isum 20

Section 10 Order reference 21

Page 4: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Introduction

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

4

1 Introduction

1.1 Validity of documentationThis documentation is valid for the product PNOZ m EF 8DI4DO. It is valid until new docu­mentation is published.

This operating manual explains the function and operation, describes the installation andprovides guidelines on how to connect the product.

1.2 Retaining the documentationThis documentation is intended for instruction and should be retained for future reference.

1.3 Definition of symbolsInformation that is particularly important is identified as follows:

DANGER!

This warning must be heeded! It warns of a hazardous situation that posesan immediate threat of serious injury and death and indicates preventivemeasures that can be taken.

WARNING!

This warning must be heeded! It warns of a hazardous situation that couldlead to serious injury and death and indicates preventive measures that canbe taken.

CAUTION!

This refers to a hazard that can lead to a less serious or minor injury plusmaterial damage, and also provides information on preventive measuresthat can be taken.

NOTICE

This describes a situation in which the product or devices could be dam­aged and also provides information on preventive measures that can betaken. It also highlights areas within the text that are of particular import­ance.

Page 5: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Introduction

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

5

INFORMATION

This gives advice on applications and provides information on special fea­tures.

Page 6: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Overview

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

6

2 Overview

2.1 Scope of supply} Expansion modulePNOZ m EF 8DI4DO

} Jumper 779 260

2.2 Unit featuresUsing the product PNOZ m EF 8DI4DO:

Expansion module for connection to a base unit from the configurable control systemPNOZmulti 2 .

The product has the following features:

} Can be configured in the PNOZmulti Configurator

} Semiconductor outputs:

4 safety outputs Depending on the application, up to PL e of EN ISO 13849­1 and up to SIL CL 3 of ENIEC 62061

} 8 inputs for connecting, for example:

– E­STOP pushbutton

– Two­hand button

– Safety gate limit switch

– Start button

– Light beam devices

– Scanner

– Enabling switch

– PSEN

– Operating mode selector switch

} LED for:

– Error messages

– Diagnostics

– Supply voltage

– Output circuits

– Input circuits

} Test pulse outputs used to monitor shorts across the inputs

} Monitoring of shorts between the safety outputs

} Plug­in connection terminals:Either spring­loaded terminal or screw terminal available as an accessory (see orderreference)

} Please refer to the document "PNOZmulti System Expansion" for the PNOZmulti baseunits that can be connected

Page 7: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Overview

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

7

2.3 Front view

Key:

} 0 V, 24 V: Supply connections

} Inputs I0 – I7

} Outputs O0 – O3

} LEDs:

– POWER

– Run

– Diag

– Fault

– I Fault

– O Fault

Page 8: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Safety

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

8

3 Safety

3.1 Intended useThe expansion module may only be connected to a base unit from the configurable controlsystem PNOZmulti 2 (please refer to the document "PNOZmulti System Expansion" for de­tails of the base units that can be connected).

The configurable control system PNOZmulti 2 is used for the safety­related interruption ofsafety circuits and is designed for use in:

} E­STOP equipment

} Safety circuits in accordance with VDE 0113 Part 1 and EN 60204­1

3.2 System requirementsPlease refer to the "Product Modifications" document in the "Version overview" section fordetails of which versions of the base unit and PNOZmulti Configurator can be used for thisproduct.

3.3 Safety regulations

3.3.1 Use of qualified personnelThe products may only be assembled, installed, programmed, commissioned, operated,maintained and decommissioned by competent persons.

A competent person is someone who, because of their training, experience and current pro­fessional activity, has the specialist knowledge required to test, assess and operate thework equipment, devices, systems, plant and machinery in accordance with the generalstandards and guidelines for safety technology.

It is the company’s responsibility only to employ personnel who:

} Are familiar with the basic regulations concerning health and safety / accident preven­tion

} Have read and understood the information provided in this description under "Safety"

} And have a good knowledge of the generic and specialist standards applicable to thespecific application.

3.3.2 Warranty and liabilityAll claims to warranty and liability will be rendered invalid if

} The product was used contrary to the purpose for which it is intended

} Damage can be attributed to not having followed the guidelines in the manual

} Operating personnel are not suitably qualified

} Any type of modification has been made (e.g. exchanging components on the PCBboards, soldering work etc.).

Page 9: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Safety

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

9

3.3.3 Disposal} In safety­related applications, please comply with the mission time tM in the safety­re­

lated characteristic data.

} When decommissioning, please comply with local regulations regarding the disposal ofelectronic devices (e.g. Electrical and Electronic Equipment Act).

3.3.4 For your safetyThe unit meets all necessary conditions for safe operation. However, you should always en­sure that the following safety requirements are met:

} This operating manual only describes the basic functions of the unit. Information on theadvanced functions can be found in the online help for the PNOZmulti Configurator andin the PNOZmulti technical catalogue. Only use these functions after you have read andunderstood the documentation. All necessary documentation can be found on thePNOZmulti Configurator CD.

} Do not open the housing or make any unauthorised modifications.

} Please make sure you shut down the supply voltage when performing maintenancework (e.g. exchanging contactors).

Page 10: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Function description

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

10

4 Function description

4.1 Integrated protection mechanismsThe relay conforms to the following safety criteria:

} The circuit is redundant with built­in self­monitoring.

} The safety function remains effective in the case of a component failure.

4.2 FunctionsThe expansion module provides additional inputs and additional semiconductor outputs.

The function of the inputs and outputs on the control system depends on the safety circuitcreated using the PNOZmulti Configurator. A chip card is used to download the safety cir­cuit to the base unit. The base unit has 2 microcontrollers that monitor each other. Theyevaluate the input circuits on the base unit and expansion modules and switch the outputson the base unit and expansion modules accordingly.

The online help on the PNOZmulti Configurator contains descriptions of the operatingmodes and all the functions of the PNOZmulti control system, plus connection examples.

4.3 System reaction timeCalculation of the maximum reaction time between an input switching off and a linked out­put in the system switching off is described in the document "System Expansion".

4.4 Block diagram

Page 11: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Installation

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

11

5 Installation

5.1 General installation guidelines} The unit should be installed in a control cabinet with a protection type of at least IP54.

} Fit the safety system to a horizontal mounting rail. The venting slots must face upwardand downward. Other mounting positions could damage the safety system.

} Use the locking elements on the rear of the unit to attach it to a mounting rail.

} In environments exposed to heavy vibration, the unit should be secured using a fixingelement (e.g. retaining bracket or end angle).

} Open the locking slide before lifting the unit from the mounting rail.

} To comply with EMC requirements, the mounting rail must have a low impedance con­nection to the control cabinet housing.

} The ambient temperature of the PNOZmulti units in the control cabinet must not exceedthe figure stated in the technical details, otherwise air conditioning will be required.

CAUTION!

Damage due to electrostatic discharge!

Electrostatic discharge can damage components. Ensure against dischargebefore touching the product, e.g. by touching an earthed, conductive sur­face or by wearing an earthed armband.

5.2 Dimensions

22,5

(0.88")

5.3 Connecting the base unit and expansion modulesConnect the base unit and the expansion modules as described in the operating manualsfor the base modules.

} The terminator must be fitted to the last expansion module

} Install the expansion module in the position configured in the PNOZmulti Configurator.

Page 12: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Commissioning

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

12

6 Commissioning

6.1 WiringThe wiring is defined in the circuit diagram of the PNOZmulti Configurator.

Please note:

} Information given in the "Technical details" must be followed.

} Use copper wire that can withstand 75°C.

6.2 Download modified project to the PNOZmulti safety systemAs soon as an additional expansion module has been connected to the system, the projectmust be amended using the PNOZmulti Configurator. Proceed as described in the operat­ing instructions for the base unit.

NOTICE

For the commissioning and after every program change, you must checkwhether the safety devices are functioning correctly.

6.3 General wiring guidelinesThe wiring is defined in the circuit diagram of the PNOZmulti Configurator.

Please note:

} Information given in the "Technical details" must be followed.

} Use copper wire that can withstand 75°C.

6.4 Connection

Supply voltage DC

24 V + 24 V DC

0 V 0 V

Supply voltage

Page 13: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Commissioning

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

13

Input circuit Single­channel Dual­channel

Example:E­STOPwithout detection of shorts acrosscontacts

S1

I0 L+

Example:E­STOPwith detection of shorts acrosscontacts

I0

T0

S1 S1

T1

I1

T0

I0

Connection examples for the input circuit

Redundant output

K2L-

O0 (O2)

O1 (O3)

K1L-

Single output

K3L-

K4

O0 (O2)

O1 ( O3)

K1L-

K2

Single output with advanced faultdetection*

K1

L+

L-K2

O0 (O2)

i0

Connection examples for semiconductor outputs

*Two loads may be connected to each safety output with advanced fault detection, even onapplications in accordance with EN IEC 62061, SIL CL 3. Prerequisite: Feedback loop isconnected, shorts across contacts and external power sources are excluded (e.g. throughseparate multicore cables). Please note that, in the event of an error in the feedback loop,the safety system switches to a safe condition and shuts down all the outputs.

Page 14: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Commissioning

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

14

Feedback loop Redundant output

Contacts from external contactors K1

L+

L-

K2

O0 (O2)

O1 (O3)

IM0

L-

Connection examples for feedback loop

Page 15: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Operation

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

15

7 OperationWhen the supply voltage is switched on, the PNOZmulti safety system copies the configur­ation from the chip card.

The LEDs "POWER","DIAG", "FAULT", "IFAULT" and "OFAULT" light up on the base unit.

The PNOZmulti control system is ready for operation when the "POWER" and "RUN" LEDson the base unit are lit continuously.

7.1 MessagesLegend:

LED on

LED flashes

LED off

LED Fault

POWER

Run

Diag Fault

IFault

OFault

No supply voltage

Expansion module PNOZ m EF 8DI4DO running without error

Expansion module PNOZ m EF 8DI4DO is in a STOP condition

Internal error on the expansion module Referenz auf VariableSAP_P_TYP or on the overall system. Expansion module is in asafe condition.

External error on the expansion module Referenz auf VariableSAP_P_TYP or on the overall system. Expansion module is in asafe condition.

Internal error on the inputs of the expansion module PNOZ m EF8DI4DO. Expansion module is in a safe condition, e.g. pulse error.

Internal error on the outputs of the expansion module PNOZ m EF8DI4DO. Expansion module is in a safe condition.

External error on the inputs of the expansion module PNOZ m EF8DI4DO. Expansion module is in a safe condition.

External error on the outputs of the expansion module PNOZ m EF8DI4DO. Expansion module is in a safe condition, e.g. defectivefeedback loop

Page 16: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Technical details

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

16

8 Technical details

General 772142Approvals BG, CCC, CE, GOST, TÜV, cULus ListedApplication range FailsafeModule's device code 00E0hElectrical data 772142Supply voltage

for Supply to the SC outputsVoltage 24 VKind DCVoltage tolerance ­20 %/+25 %Current load capacity at UB 8,0 APotential isolation Yes

Supply voltagefor Module supplyinternal Via base unitVoltage 24,0 VKind DCCurrent consumption 39 mAPower consumption 1,0 W

Max. power dissipation of module 4,50 WStatus indicator LEDPermitted loads inductive, capacitive, resistiveInputs 772142Number 8Input voltage in accordance with EN 61131­2 Type 1 24 V DCInput current at rated voltage 5 mAInput current range 2,5 ­ 5,3 mAPulse suppression 0,5 msMaximum input delay 8 msPotential isolation NoSemiconductor outputs 772142Number of positive­switching single­pole semicon­ductor outputs 4Switching capability

Voltage 24 VTyp. output current at "1" signal and rated voltage ofsemiconductor output 2,00 APermitted current range 0,00 ­ 2,50 AResidual current at "0" signal 0,05 mAMax. transient pulsed current 12 AMax. capacitive load 1 µFMax. internal voltage drop 500 mVMax. duration of off time during self test 330 µsSwitch­off delay 3 ms

Page 17: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Technical details

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

17

Semiconductor outputs 772142Potential isolation YesShort circuit­proof YesEnvironmental data 772142Ambient temperature

In accordance with the standard EN 60068­2­14Temperature range 0 ­ 60 °CForced convection in control cabinet off 55 °C

Storage temperatureIn accordance with the standard EN 60068­2­1/­2Temperature range ­25 ­ 70 °C

Climatic suitabilityIn accordance with the standard EN 60068­2­30, EN 60068­2­78

Condensation during operation Not permittedEMC EN 61131­2Vibration

In accordance with the standard EN 60068­2­6Frequency 5,0 ­ 150,0 HzAcceleration 1g

Shock stressIn accordance with the standard EN 60068­2­27Acceleration 15gDuration 11 ms

Max. operating height above sea level 2000 mAirgap creepage

In accordance with the standard EN 61131­2Overvoltage category IIPollution degree 2

Rated insulation voltage 30 VProtection type

In accordance with the standard EN 60529Mounting area (e.g. control cabinet) IP54Housing IP20Terminals IP20

Potential isolation 772142Potential isolation between SC output and system voltageType of potential isolation Basic insulationRated surge voltage 2500 VMechanical data 772142Mounting position Horizontal on top hat railDIN rail

Top hat rail 35 x 7,5 EN 50022Recess width 27 mm

Max. cable lengthMax. cable length per input 1,0 km

Page 18: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Technical details

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

18

Mechanical data 772142Material

Bottom PCFront PCTop PC

Conductor cross section with screw terminals1 core flexible 0,25 ­ 2,50 mm², 24 ­ 12 AWG2 core with the same cross section, flexible withoutcrimp connectors or with TWIN crimp connectors 0,20 ­ 1,50 mm², 24 ­ 16 AWG

Torque setting with screw terminals 0,50 NmConnection type Spring­loaded terminal, screw terminalMounting type plug­inConductor cross section with spring­loaded terminals:Flexible with/without crimp connector 0,20 ­ 2,50 mm², 24 ­ 12 AWGSpring­loaded terminals: Terminal points per connec­tion 2Stripping length 9 mmDimensions

Height 101,4 mmWidth 22,5 mmDepth 120,0 mm

Weight 105 g

The standards current on 2012­04 apply.

Page 19: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Technical details

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

19

8.1 Safety characteristic data

Unit Operatingmode

EN ISO13849­1: 2008PL

EN ISO13849­1: 2008Category

EN IEC 62061SIL CL

EN IEC 62061PFHD [1/h]

EN ISO13849­1: 2008TM [year]

LogicCPU – PL e Cat. 4 SIL CL 3 2,84E­10 20InputSC inputs 1­channel PL d Cat. 2 SIL CL 2 2,10E­09 20SC inputs 2­channel PL e Cat. 4 SIL CL 3 4,27E­11 20SC inputs 1­ch., pulsed

light barrier PL e Cat. 4 SIL CL 3 2,10E­10 20OutputSC outputs 1­channel

with ad­vanced faultdetection PL e Cat. 4 SIL CL 3 2,12E­11 20

SC outputs 1­channel PL d Cat. 2 SIL CL 2 2,29E­10 20SC outputs 2­channel PL e Cat. 4 SIL CL 3 1,64E­10 20

All the units used within a safety function must be considered when calculating the safetycharacteristic data.

INFORMATION

A safety function's SIL/PL values are not identical to the SIL/PL values ofthe units that are used and may be different. We recommend that you usethe PAScal software tool to calculate the safety function's SIL/PL values.

Page 20: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Supplementary data

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

20

9 Supplementary data

9.1 Permitted ambient temperature Tamb dependent on the totalcurrent Isum

Page 21: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

Order reference

Operating Manual PNOZ m EF 8DI4DO1002661­EN­02

21

10 Order referenceOrder reference

Product type Features Order no.

PNOZ m EF 8DI4DO Expansion module 772 142

Order reference: Ac­cessories

Product type Features Order no.

Set spring terminals 1 set of spring­loaded terminals 751 004

Set screw terminals 1 set of screw terminals 750 004

Order reference: Terminator, jumper

Product type Features Order no.

PNOZ mm0.xp connectorleft

Jumper yellow/black to connect the modules, 1 piece 779 260

Page 22: PNOZ m EF 8DI4DO - RS ComponentsOperating Manual PNOZ m EF 8DI4DO 1002661EN02 12 6 Commissioning 6.1 Wiring The wiring is defined in the circuit diagram of the PNOZmulti Configurator

...

Sachnum

mer

Printe

d in G

erm

an

y

©

Pilz

Gm

bH

& C

o.

KG

, 2011

+49 711 [email protected]

Pilz GmbH & Co. KGFelix-Wankel-Straße 273760 Ostfildern, GermanyTelephone: +49 711 3409-0Telefax: +49 711 3409-133E-Mail: [email protected]: www.pilz.com

Technical supportIn many countries we are represented by our subsidiaries and sales partners.

Please refer to our homepage for further details or contact our headquarters.

Ind

ura

NE

T p

®, P

ilz®, P

IT®, P

MC

pro

teg

o®, P

MI®

, P

NO

Z®, P

rim

o®, P

SE

N®, P

SS

®, P

VIS

®, S

afe

tyB

US

p®, S

afe

tyE

YE

®, S

afe

tyN

ET

p®, th

e s

pirit o

f safe

ty® a

re r

eg

iste

red

and

pro

tecte

d t

rad

em

ark

s

of

Pilz

Gm

bH

& C

o. K

G in s

om

e c

ountr

ies. W

e w

ould

po

int

out

that

pro

duct

featu

res m

ay v

ary

fro

m t

he d

eta

ils s

tate

d in t

his

do

cum

ent,

dep

end

ing

on t

he s

tatu

s a

t th

e t

ime o

f p

ub

licatio

n a

nd

the s

co

pe

of

the e

quip

ment.

We a

ccep

t no

resp

onsib

ility

fo

r th

e v

alid

ity,

accura

cy a

nd

entire

ty o

f th

e t

ext

and

gra

ph

ics p

resen

ted

in t

his

info

rmatio

n. P

lease c

onta

ct

our

Technic

al S

up

po

rt if

yo

u h

ave a

ny q

uestio

ns.

1002661­EN­02, 2013­12 Printed in Germany

© Pilz GmbH

 & Co. KG, 2011

Back cover