SF6 Gas insulated Switchgear RMR-24/36 Series 24kV ,. Up to 36kV,…… Technical Manual ROCKWILL ELECTRIC CO.,LTD

Post on 25-Jan-2017

202 views

Category:

Documents

8 download

Embed Size (px)

TRANSCRIPT

  • SF6 Gas insulated Switchgear RMR-24/36 Series 24kV ,. Up to 36kV,

    Technical Manual

    ROCKWILL ELECTRIC CO.,LTD

  • C Unit

    F Unit

    V Unit

    ++++General RMR-24/46kV is completely insulated SF6 SAFERINhereinafter short as SF6 Gas insulated SwitchgearThis product is in conformity with the standards the GB/IEC standard and the design of a high safety combined switch cabinets.

    The system of RMR-24/36kV of combined switch cabinets can be divided into three kinds of unit cabinet

    ++++ 3 position cable connection unit (Cable switch unit), additional live shows and configuration of surge arresters and grounding fault component. Code C

    ++++3 position switch and fuse tripping system and earthing switch interlock system fuse combined electrical unit (Fuse combination unit), additional live shows and configuration of surge arresters and grounding fault component. Code F

    ++++3 position switch and vacuum circuit breaker combined appliances unit (Vacuum circuit breaker unit), additional current transformer, live shows and configuration of surge arresters and grounding fault component. Code V The combination of the current transformer and the microcomputer protection to constitute the basic circuit protection function. Microcomputer protection using passive protection and CT electric no need of additional PT power supply

    Reference standard

    ----IEC62271-200 ----IEC62271-100 ----GB3804-2004 ----GB3906-1991 ----GB16926-1997 ----GB/T11022-1999

    Remark

    Fuse combined electrical follow IEC 60420

    VCB unit according to IEC 62271-100/GB1984-2003

  • ++++Service environment a) Air temperature: 40; Daily average 25C b)Altitude above sea level: Maximum installation altitude: 4000m c)Wind: less than 35m/s d)Earthquake intensity: no more than 8 degrees;

    ++++ Main technical specifications No Item Unit Data 1 Rated voltage 24/36

    Dry Power Frequency withstand voltage Wet

    60/70/80/95 2

    Lightning Impulse withstand Voltage (peak value)

    kV

    125/150/170/185/200

    3 Rated Current A 630/1250/2500 4 Rated short circuit breaking current (peak) kA 20/25(V) 31.5(F) 5 Rated closed-loop breaking current A 630/1250(C) 6 Rated cable charging interrupting current A 50(C) 7 Rated line cable charging interrupting current A 10(C) Rated off circuit transformer breaking current A 16 8 Rated making current (peak) 9 Rated withstand current (peak)

    50(63/80)/2.5(main switch/grounding)

    10 Rated short time withstand current kA

    16/20/25/31.5 11 Rated short time withstand time S 3/4 12 Mechanical life times C/F2000V(10,000) 13 Main busbar A 630/1250/2000/2500

    ++++Each Panel face, dimension & function Customized Panel View Type & functions WDH mm

    1C=5009501360mm 2C=10009501360mm 3C=15009501360mm

    Mainly for switching kiosk or cable branch box

    Extra bushing=140mm

    Note: Above unit is for special type using for like solar plant, wind plant cable system.

  • Standard Panel View Unit C Standard Panel View Unit F Standard Panel View Unit V

    5009501950 500(568)9501950 500(568)9501950

    Note: 1, Unit V type LBS can be changed to be mounted on top for feeder cable outgoing system. 2, Unit V type incomer type with 3 nos VTs configuration width is 568mm. 3, Each unit can be connected with top busbar to be combined as Ring main unit

    Standard economic type Ring main unit Combination complete common gas tank CCF

    Dimension 15009501950

  • ++++Busbar system RMR type GIS switchgear can be used for main station as main switchgear, the main busbar current up to 2500A, 40kA.. Below is different schema for range of busbar current selection on RMR type GIS switchgear.

    Main busbar 2500A,40kA, Max Busbar 630/1250A ,31.5kA, Max.

    Busbar Section Max. up to 2500mm2 Busbar Section Max. up to 600mm2

    ++++Other expanding configurations for reference Vacuum circuit breaker unit for incomer using

    Fuse combination for transformer protection using

    Cable switch unit

    Remark: Other accessories like PT, CT, relays can be equipped by special requirement. For more question pls consult with Rockwill: [email protected]