SmartStruxure™ Solution

MNL controller support

Supplementary technical information for system integrators

Page 2: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 2

Topics

1. Native MNL controller support overview● Native MNL support for “new” MNL controllers in a SmartStruxure Solution

powered by StruxureWare Building Operation v1.2

● Scalability guidelines and system requirements

2. Benefits of native MNL controller support

3. Support for existing controllers

4. MNL controller support overview

Page 3: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

NATIVE MNL SUPPORT

SmartStruxure Solution powered by StruxureWare Building Operation software

3

Page 4: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 4

Native MNL support

● StruxureWare Building Operation v1.2 softwareallows for native support for MNL controllers

● Connected directly to an AS-L

● MNL support targeted for new “greenfield” projects

● New MNLs – i.e. not previously configured

● Requires WorkPlace Tech Editor software● Installation included with StruxureWare Building

Operation WorkStation v1.2 software● WorkPlace Tech Editor license included with

Editor Pack licensing

● Script & function block programming, and TGML graphics editing

StruxureWare Building OperationWorkStation

StruxureWareBuilding Operation WebStation

Page 5: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 5

Version 1.2 scalability guidelines

●Ideal for new sites or a new section of an existing site

●Scalability guidelines for a SmartStruxure Solution powered by StruxureWare Building Operation v1.2:

Components per system:

Recommended # of MNL controllers per AS-L 32

Max # of LON devices on the bus(includes maximum 64 MNL controllers)

64

Max # of Automation Servers(Sites using more than one Automation Server require an Enterprise Server)

32

Max # of Enterprise Server 1

Max # of concurrent operator users, includes max 2 engineering users(includes sum of WorkStation + WebStation users simultaneously)

10

Page 6: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 6

Minimum system requirements

● StruxureWare Building Operation v1.2 software

● MNL controller versions:● Standard MNL controllers: v4.1● MNL-800: v2.0

● Microsoft OS & SQL versions:● Windows XP SP3 (32-bit)● Windows 7 (32-bit)● Windows 7 (64-bit)● Windows Server 2008 R2 (64-bit)● SQL Server 2008 R2 - Standard & Express versions with Advanced Services (64-bit)

● Required for Reports Server

● Pre-requisite for configuring and programming MNL controllers:● Microsoft Visio 2010 SP1 or Microsoft Visio 2007 SP2

● Visio 2003 is still supported however upgrade is recommended

Page 7: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 7

Multiple Automation Servers

Multiple Automation Servers in one system will require a StruxureWare Enterprise Server

● Manage multiple Automation Servers

● Full system view

● Stores extended trend log data

MO

DB

US

* Server includes software only; server machine is not included.

StruxureWareBuilding Operation WebStation

StruxureWare Building Operation Enterprise Server*

StruxureWare Building OperationWorkStation

Page 8: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 8

Multiple Automation Servers

MO

DB

US

* Server includes software only; server machine is not included.

Depending on machine specifications, Reports Server may reside on the Enterprise Server machine.

StruxureWare Building Operation Reports Server*

StruxureWareBuilding Operation WebReports

StruxureWareBuilding Operation WebStation

StruxureWare Building Operation Enterprise Server*

StruxureWare Building OperationWorkStation

Included when purchasing the StruxureWare Building Operation Enterprise Server

● Reports Server:● Reports Server software

● WebReports:● Web browser access direct to

Reports Server (just for reports)

Page 9: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

BENEFITS OF NATIVE MNL CONTROLLER SUPPORT

SmartStruxure Solution powered by StruxureWare Building Operation software

9

Page 10: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 10

Use of MNL controllers

●Native support under an Automation Server● Unlike the UNC (or ENC) which only understands

the LonWorks profile

●Automation Server contains all of the controller and S-LINK sensor information

●Existing MNL controllers can be brought over into a SmartStruxure Solution powered by StruxureWare Building Operation

● Import existing .VSD files

●.VSD file resides within the Automation Server● No need to remotely manage versions of the

configuration file on a PC

Benefits:

• Using the same familiar MNL controllers natively within a new system

• Configuration information and file hosted within Automation Server

• Eliminates the need for remote version management

• Protect existing investment, can use or re-use existing controllers with engineering and configuration changes

• Existing installed hardware• Existing wiring

Page 11: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 11

Configuration and engineering benefits

●ListViews● Quickly view the configuration of multiple objects in a folder or device in a

spreadsheet-like format

● Customize columns shown to display desired object attributes

●Rapidly create LonWorks Network Variables (NVs)● Simply right click on a selected device Network Variable (NV) and choose to

create and bind a new local node network variable at the Enterprise Server or Automation Server

● Can be done for multiple Network Variables at the same time from a Watch list or a search result

●Binding templates● Quick association of excessive point binding to graphics, programs, and

schedules using standard naming conventions

Page 12: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 12

Configuration and engineering benefits

● Use the text report feature for calibration of items such as S-LINK sensors, analog inputs, and flow balance

● Exposure of S-Link related values and MNL controller point objects● Change setpoint and setpoint limits via software

● No need to open application drawing in WorkPlace Tech or walk up to physically connect to the sensor

● WorkPlace Tech Editor monitor view● Use the monitor view within WorkPlace Tech Editor to see simulation of programs with

the MNL controller

● Controller Types Listed when adding a device● System pre-populates LonWorks profile associated with hardware model (e.g. MNL-

800) and LON profile

● MNL controller model and version number are exposed in device discovery

Page 13: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 13

Watch window view and objects

● Create WatchObjects: saved lists of groups of points to monitor their live values

● Quickly create a customizable “controller summary” to monitor point values

●Eliminates the need to create a graphic to monitor a group of points

● Drag and drop points down in the “watch window”● Save as a “WatchObject” in the system tree

●Can create many, unique “Watch Objects”● Open the saved “WatchObject” at any time

Benefits:

• Easy create a customizable “controller summary”

• Eliminates the need to create a graphic to monitor a group of points

• Effective as a trouble-shooting tool

• Examples:• Temperatures across zones• Status of all values on the same

equipment – e.g. AHU

• Combine points from different parts of the system - e.g. another building

• Easily save and retrieve the same Watch list of points at a later time

• Create a new ad hoc Watch list and save it for later use

Page 14: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 14

Microsoft operating systems

●Support for current Microsoft operating systems● 64-bit environment support

●In StruxureWare Building Operation v1.2:● Windows XP SP3 (32-bit)

● Windows 7 (32-bit)

● Windows 7 (64-bit)

● Windows Server 2008 R2 (64-bit)

● Encrypted communications by default

● Between WorkStation and Servers (Enterprise Server & Automation Server)

●Continued compliance with IT standards moving forward

Benefits:

• Commitment to support current and upcoming operating systems and IT standards

Page 15: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 15

EcoStruxure™

● Leverage Schneider Electric’s EcoStruxure architecture to expand your customers’ systems beyond building management

● Lighting● Power monitoring● Energy management● Security● IT

● Use the features of StruxureWare Building Operation to easily integrate to other Schneider Electric products and systems

● Available today:●Open protocols●Smart Widgets●EcoStruxure™ Web Services

Page 16: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 16

Smart Widgets

● A Smart Widget is a package that can be used to import a particular model of a device – e.g. Power Meter (PM 210), VSD (ATV 61)

● Package includes import files for:● Standard graphics (to map to the device) for initial

configuration & diagnostic purpose● Points that map to the device’s objects and

corresponding values in the system tree and bound to the graphics

Benefits:

• Push button engineering• Bring on a Power Meter in

less than a minute rather than several hours of programming (including graphic and third party “register mapping”)

• Easy integration with other Schneider Electric products with available Smart Widgets

• Use existing Smart Widgets or create your own & share with the engineering community

Page 17: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 17

Web Services (Generic Consume)● General web services implementation to bring in third

party data into StruxureWare Building Operation● Ideal when reading from and writing to third party

systemso Connect to both SOAP and POX/REST web services

● Two approaches:o Binding tool, Script programming based

● IT-friendly and flexible● Opens systems to exchange data beyond industry-

specific protocols● Because web services use IT standards-based

communications methods, integration is platform independent

● Use case examples:● Return outside conditions or weather forecast data:

Pass in latitude/longitude coordinates, return temperature, humidity and Barometric pressure

● Return cost per energy unit from utility company

Benefits:• Ideal when integrating to third

party systems

• “Consume” configuration is flexible:

1.Binding tool is easy to configure

2.Script programming based is well suited for processing complicated web services

• Customize, adjust and control site based on incoming information for greater efficiency – e.g. demand control

Page 18: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 18

EcoStruxure Web Services● Consistent web services standard for Schneider Electric

products implementing web services functionality● Common and easy integration into other Schneider Electric

systems● Reduce time to market & complexity

● Additional web services functionality available when integrating multiple Schneider Electric systems

● Functionality defined: Serve and Consumeo Browse the other system’s directorieso Read/Write real time valueso Receive and acknowledge active alarmso Read historical (trend log) data

● Secure log on with system user name and password

● Manage access to system directories and data

● Can be used with third parties (if third party supports the EWS standard)

Benefits:

• EcoStruxure Web Services (EWS) provide additional features when integrating with other EWS compliant systems

Page 19: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 19

Reports Server

● Multiple Automation Server systems require an Enterprise Server

● Enterprise Server includes Reports Server

● Powerful reporting tool ● Customized reports

● Includes out of the box reports● Pre-packaged report packs

● Energy Report● Tenant Billing Reports

Benefits:

• Powerful reporting server included with Enterprise Server by default

• Includes pre-configured reports

• Additional customized reports can be created using Microsoft Report Builder

● Easy configuration ● Based on any pre-configured or ad hoc criteria

(e.g. date range, consumption, and CO2 emissions)

● Graphical reporting

● In WorkStation or web-based: WebReports

Page 20: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

SUPPORT FOR EXISTING CONTROLLERS

SmartStruxure Solution powered by StruxureWare Building Operation software

20

Page 21: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 21

MNL support

●Existing MNL controllers (already configured under a UNC or ENC) can be connected directly to an AS-L (replacing the UNC/ENC)

● Database conversion process is not available for content

● Requires manual import of current standalone WorkPlace Tech application into AS-L

● System can only support features currently available in StruxureWare Building Operation

●Cannot support features such as third-party drivers, and oBIX

●TAC I/A Series Enterprise Server is replaced by StruxureWare Building Operation software

TAC I/A SeriesEnterprise Server

Page 22: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 22

Integrating existing controllers

●Import existing .VSD file (per MNL) into the Automation Server

● .VSD file now resides in the Automation Server

●Only MNL controllers at v4.1 are compatible with a SmartStruxure Solution powered by StruxureWare Building Operation

● MNLs with earlier versions can be learned in as third party LON devices

●Replacing a UNC/ENC with an Automation Server will require re-engineering the following:

● Alarms

● Schedules

● Trends

● Graphics

● Logic/control objects● Math● Loops

StruxureWareBuilding Operation WebStation

StruxureWare Building OperationWorkStation

Page 23: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 23

MNB support

● MNB MS/TP devices can be learned in as third party BACnet devices into an AS-B

● MNB controllers are not natively supported in StruxureWare Building Operation v1.2

● Discover BACnet/IP devices (e.g. MNB-1000) into an AS-B or Enterprise Server

● Provides the same functionality as currently integrating an MNB device into a UNC (or ENC)

● Since not natively supported:● Must use standalone WorkPlace Tech (as

done in I/A Series today) to engineer● Visio drawings are not stored in the

Automation Server (as done with the MNL controllers)

StruxureWareBuilding Operation WebStation

StruxureWare Building OperationWorkStation

AS-B

Page 24: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

MNL CONTROLLER SUPPORTOVERVIEW

SmartStruxure Solution powered by StruxureWare Building Operation software

24

Page 25: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 25

Overview of MNL support processTAC I/A SeriesEnterprise Server

Describes how to move existing MNL controllers from a UNC (or ENC) to an Automation Server

● Assumes .VSD are available for use● System is not dependent on functionality not yet

supported by StruxureWare Building Operation – e.g. third party drivers, oBIX

1.Install Visio software 2010 SP1 or 2007 SP2 on StruxureWare Building Operation WorkStation machine(s)

● Pre-requisite for StruxureWare Building Operation WorkStation software

● Note: Visio 2003 is supported in StruxureWare Building Operation v1.2 but upgrade is recommended

StruxureWare Building OperationWorkStation

Page 26: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 26

Overview of MNL support process

2. Install StruxureWare Building Operation software components on one machine:a) Install the License Administrator

b) Install the Device Administrator

c) If Enterprise Server to be used, install Enterprise Server software● Note: Enterprise Server only required if using two or more Automation Servers● Software Administrator is installed automatically with the Enterprise Server

Otherwise, install the Software Administrator

3. Install StruxureWare Building Operation WorkStation software● On WorkStation(s) to be used for system

engineering, check editor tools to be installed (e.g. Graphics, Script, Function Block Programming)

● Include WorkPlace Tech Editor

● Note: StruxureWare Editor Pack license required for each WorkStation machine that will use WorkPlace Tech Editor functionality

Page 27: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 27

Overview of MNL support processTAC I/A SeriesEnterprise Server

4. Add Automation Server(s) to the network• AS-L used to support MNL

controllers

• Automation Server automatically includes web access via WebStation

StruxureWareBuilding Operation WebStation

StruxureWare Building OperationWorkStation

Page 28: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 28

TAC I/A SeriesEnterprise Server

4. Add Automation Server(s) to the network• AS-L used to support MNL

controllers

• Automation Server automatically includes web access via WebStation

5. Move LON bus wiring from UNC (or ENC) to the AS-L

Overview of MNL support processStruxureWareBuilding Operation WebStation

StruxureWare Building OperationWorkStation

Page 29: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 29

Overview of MNL support process6. Import .VSD file into the corresponding AS-L

● Importing Lon applications created outside of StruxureWare Building Operation (e.g. stand-alone WorkPlace Tech) using WorkPlace Tech Editor

● Two methods:

Single .VSD file import:

• Stops after file has been opened to allow the user the opportunity to make changes prior to saving the file, including:

• changing the hardware type• fixing issues that may have

caused a failure as part of a multiple import

• Allows the ability to change the application name, add a description and define a Category as they appear in the Control Panel

• Once saved, the hardware type is fixed

Multiple .VSD files import:

• Allows multiple applications to be selected at one time within the same directory

• only one directory can be used at a time

• Uses original application name when saving and does not add the description and category information

• Note: Duplicate names are prevented. Names containing unsupported characters will fail.

• All selected (LON) applications will be opened, processed, saved using original name if succeeded (error message logged in Log Viewer on failure), file closed and move to the next

• When import multiple process has completed, the Import Log Viewer will be displayed with the results

Page 30: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 30

Notes on .VSD import

● Import Log Viewer● Results from the import are stored in this file● View the file to verify all imports were successful

● Review file names, number of imports succeeded/failed, and reasons for failure● Log file is saved in the Windows directory and can be later referenced

● Import errors and how they are handled● Any applications that appeared in the Log Viewer as failed can be imported

individually providing the opportunity to correct the issues● All applications are compiled before saving, identifying any errors that would affect

StruxureWare Building Operation● Imported MNL-800 apps containing inappropriately numbered SNVT indexes are fixed

during the import● Applications prior to (stand-alone) WorkPlace Tech v3.2 SP1 will fail and will require

conversion to v3.2 or later and be changed to a supported hardware version

● Upon successfully importing an application to the Automation Server, it will appear in the StruxureWare Building Operation WorkStation Control Panel

Page 31: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 31

Overview of MNL support process

7. After import of the .VSD file into the AS-L, some re-engineering will be required:

● Alarms● Schedules● Trends

At this point, the system is converted to a SmartStruxure Solution. Leverage the features within the new system:

a)Create user accounts

b)Customize workspaces and assign to new StruxureWare Building Operation software users

c)Assign custom permissions to users and groups● Modify, Read, No Access

d)If there is an Enterprise Server in the system, create reports in the Reports Server using MS Reports Builder

StruxureWareBuilding Operation WebStation

StruxureWare Building OperationWorkStation

● Graphics● Logic/control objects

● Math● Loops

Page 32: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 32

Expanding the system

●Use Automation Server I/O Modules for local hardwired points

●AS-L also supports Modbus

MO

DB

US

StruxureWareBuilding Operation WebStation

StruxureWare Building OperationWorkStation

Page 33: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 33

Expanding the system

MO

DB

US

* Server includes software only; server machine is not included.

StruxureWareBuilding Operation WebStation

StruxureWare Building Operation Enterprise Server*

StruxureWare Building OperationWorkStation

● Systems with two or more Automation Servers require an Enterprise Server

● WebStation can be used to connect to either:

● the Enterprise Server for full system view

● directly to an Automation Server for local view

● Or, add an Enterprise Server for:● extra server storage● to host extended log data● to support Reports Server

Page 34: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators

Schneider Electric – StruxureWare Building Operation v1.2: MNL controller support 34

Expanding the system

MO

DB

US

* Server includes software only; server machine is not included.

Depending on machine specifications, Reports Server may reside on the Enterprise Server machine.

StruxureWare Building Operation Reports Server*

StruxureWareBuilding Operation WebReports

StruxureWareBuilding Operation WebStation

StruxureWare Building Operation Enterprise Server*

StruxureWare Building OperationWorkStation

Included when purchasing the StruxureWare Building Operation Enterprise Server:

● Reports Server (software) - used to set up a system Reports Server

● Powerful reporting tool● Graphical Reporting● Customized reports● Includes out of the box reports

● WebReports● Web browser access direct to Reports

Server (just for reports)

Note: Enterprise Server and Reports Server can be added even if system only has one Automation Server

Page 35: SmartStruxure™ Solution MNL controller support Supplementary technical information for system integrators