som jackson state office building pre-purchase rtu package trane … som jackson state office...

24
Prepared For: Engineering Applications EAI, LLC 726 Abbot Rd East Lansing, MI 48823 Date: May 07, 2015 Customer P.O. Number: To Follow Sold To: State of Michigan DTMB P.O. Box 30026 Lansing, MI 48909 Job Name: SOM Jackson State Office Building Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary Tag(s) Qty Product RTU-1 & 2 2 Commercial Rooftop Air Conditioning Units (Midrange) Bill Antcliff Trane 3350 Pine Tree Road Lansing, MI 48911 Phone: (517) 337-6517 Cell: (517) 898-4068 Fax: (517) 337-9493 The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval. Submittal J:\JOBS\70\27633\4\SOM Jackson State Office Building_Pre-Purchase RTU Package_Trane RTU Submittal For Approval.doc X BAK 5-29-2015 EAI Proj # 1521

Upload: others

Post on 17-Apr-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

Prepared For: Engineering Applications EAI, LLC 726 Abbot Rd East Lansing, MI 48823

Date: May 07, 2015 Customer P.O. Number: To Follow

Sold To: State of Michigan DTMB P.O. Box 30026 Lansing, MI 48909

Job Name: SOM Jackson State Office Building

Trane U.S. Inc. is pleased to provide the enclosed submittal for your review and approval. Product Summary

Tag(s) Qty Product RTU-1 & 2 2 Commercial Rooftop Air Conditioning Units (Midrange)

Bill Antcliff Trane 3350 Pine Tree Road Lansing, MI 48911 Phone: (517) 337-6517 Cell: (517) 898-4068 Fax: (517) 337-9493

The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval.

Submittal

J:\JOBS\70\27633\4\SOM Jackson State Office Building_Pre-Purchase RTU Package_Trane RTU Submittal For Approval.doc

X

BAK 5-29-2015

EAI Proj # 1521

Page 2: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

Table Of Contents

Product Summary ........................................................................................................................... 1

Commercial Rooftop Air Conditioning Units (Midrange) (Item A1) ........................................... 3

Tag Data .................................................................................................................................................. 3

Product Data ............................................................................................................................................ 3

Performance Data .................................................................................................................................... 4

Mechanical Specifications ........................................................................................................................ 6

Unit Dimensions ..................................................................................................................................... 10

Fan Curve .............................................................................................................................................. 13

Weight, Clearance & Rigging Diagram ................................................................................................... 14

Accessory .............................................................................................................................................. 16

Field Installed Options - Part/Order Number Summary ............................................................ 24

Commercial Rooftop Air Conditioning Units (Midrange) ......................................................................... 24

Page 3: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 3 of 24

Commercial Rooftop Air Conditioning Units (Midrange) (Qty: 2) Item Tag(s) Qty Description Model Number

A1 RTU-1, RTU-2 2 70 Ton Packaged Industrial Rooftop Unit SXHLF704

Product Data

Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2 DX Cooling Only w/ Extended Casing R410A Refrigerant 70 Nominal Ton Unit 460 / 3 / 60 100% Exhaust - 10 Hp w/ Statitrac 600 rpm – Exhaust Fan 0-100% Economize w/ Comparative Enthalpy Controls & DCV w/ Traq Flow Sensor Grease Lines & Filter Gauge 2.00" Spring Isolators MERV-8 Hi-Efficiency Throw Away Filter

Final Filter Rack w/ Cam Flo XLT 12” Pocket Filter 40 HP DDP 80W Supply Fan 2000 rpm - Supply fan VAV- Discharge Temp Control Supply & Exhaust Fan w/ VFD with Bypass Low Ambient Damper(s) Control cULus Non-Fused Unit Disconnect Switch EISA Std Motors w/ Shaft Grounding Ring Remote Human Interface (Fld) Ventilation Override Module Access Doors BACnet Communication Interface Module Supply Fan Piezometer Temperature Sensor (Fld) Factory-Powered 15A GFI Convenience Outlet Standard Flat Roof Curb (Fld, Ships Knocked Down) Duct Mounted CO2 Sensor (Fld) Start-Up Services 1

st Year Parts, Labor & Refrigerant Warranty

2nd

– 5th Year Parts & Refrigerant Warranty

Additional Field Services:

� 4-Hours of Owner Training

� 1st Year Maintenance Contract w/ 4-Quarterly Visits (12-Months From The Date of Start-Up)

� Filter Changes Per Contract Documents

Page 4: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 4 of 24

Performance Data

Tags RTU-1, RTU-2

Design airflow (cfm) 25000

Exhaust Airflow (cfm) 23000

Cooling EDB (F) 76.00

Cooling EWB (F) 62.00

Ambient DB (F) 95.00

Leaving Coil DB (F) 51.27

Leaving Coil WB (F) 50.74

Leaving Unit DB (F) 54.69

Leaving Unit WB (F) 52.20

Gross total capacity (MBh) 804.08

Gross sensible capacity (MBh) 711.15

Gross latent capacity (MBh) 92.93

Net total capacity (MBh) 709.28

Net sensible capacity (MBh) 616.35

Net sensible heat ratio (%) 86.90

Supply duct static pressure (in H2O) 3.265

Return duct static pressure (in H2O) 0.500

Component S.P. drop (in H2O) 1.715

Total static pressure (in H2O) 5.480

Supply motor BHP calculated (bhp) 34.66

Supply fan RPM calculated (rpm) 1981

Exhaust static pressure (in H2O) 0.507

Exhaust motor BHP calculated (bhp) 9.35

Exhaust fan RPM calculated (rpm) 623

System power (kW) 94.24

EER @ AHRI (EER) 10.6

Minimum circuit ampacity (A) 183.18

Maximum overcurrent protection (A) 200.00

Minimum disconnect switch size (A) 203.00

Recommended dual element (A) 200.00

Compressor 1 count (Each) 4.00

Compressor 1 RLA (A) 25.50

Supply fan motor FLA (A) 24.70

Supply motor count ( ) 2

Supply fan count (Each) 2.00

Condenser fan FLA (A) 10.80

Exhaust fan motor FLA (A) 12.60

Other FLA (A) 2.00

Evaporator face area (sq ft) 43.00

Min. unit operating weight (lb) 8970.0

Max. unit operating weight (lb) 12143.0

Fan motor heat (MBh) 94.80

Page 5: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 5 of 24

Tags RTU-1, RTU-2

Discharge duct - 63 Hz (dB) 98

Discharge duct - 125 Hz (dB) 96

Discharge duct - 250 Hz (dB) 91

Discharge duct - 500 Hz (dB) 89

Discharge duct - 1 kHz (dB) 86

Discharge duct - 2 kHz (dB) 82

Discharge duct - 4 kHz (dB) 80

Discharge duct - 8 kHz (dB) 77

Return duct - 63 Hz (dB) 90

Return duct - 125 Hz (dB) 91

Return duct - 250 Hz (dB) 84

Return duct - 500 Hz (dB) 80

Return duct - 1 kHz (dB) 77

Return duct - 2 kHz (dB) 75

Return duct - 4 kHz (dB) 71

Return duct - 8 kHz (dB) 68

Run acoustics Yes

Exhaust fan - 63 Hz (dB) 83

Exhaust fan - 125 Hz (dB) 82

Exhaust fan - 250 Hz (dB) 77

Exhaust fan - 500 Hz (dB) 75

Exhaust fan - 1 kHz (dB) 72

Exhaust fan - 2 kHz (dB) 70

Exhaust fan - 4 kHz (dB) 67

Exhaust fan - 8 kHz (dB) 62

Desired reheat set point (F) 70.00

EDB in HGRH (F) 73.00

EWB in HGRH (F) 64.00

Ambient DB in HGRH (F) 75.00

Ambient WB in HGRH (F) 68.00

Installed point load 1 (lb) 848.5

Installed point load 2 (lb) 928.2

Installed point load 3 (lb) 933.5

Installed point load 4 (lb) 1013.2

Installed point load 5 (lb) 1008.8

Installed point load 6 (lb) 1088.5

Installed point load 7 (lb) 1085.0

Installed point load 8 (lb) 1164.7

Installed point load 9 (lb) 1169.1

Installed point load 10 (lb) 1248.8

Total installed weight (lb) 10488.3

First X dimension (ft) 16.74

First Y dimension (ft) 5.01

Installed point load 1 - X (in) 4.000

Installed point load 1 - Y (in) 4.000

Installed point load 2 - X (in) 101.000

Installed point load 2 - Y (in) 112.000

Installed point load 3 - X (in) 187.000

Installed point load 4 - X (in) 274.000

Installed point load 5 - X (in) 370.000

Rated capacity at AHRI (tons) 67.50

HFCF-410A refrigerant charge - circuit 1 (lb) 41.5

HFCF-410A refrigerant charge - circuit 2 (lb) 39.8

IEER (EER) 15.4

Supply fan efficiency (%) 62.22

Page 6: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 6 of 24

Mechanical Specifications - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2 General - R410A Units shall be specifically designed for outdoor rooftop installation on a roof curb and be completely factory assembled and tested, piped, internally wired, fully charged with R-410A compressor oil and shipped in one piece. Units shall be available for direct expansion cooling only, or direct expansion cooling with natural gas, electric, hot water or steam heating. Filters, outside air system, exhaust air system, optional non-fused disconnect switches and all operating and safety controls shall be furnished factory installed. All units shall be cULus approved and factory run tested. Cooling capacity shall be rated in accordance with AHRI Standard 360. All units shall have decals and tags to aid in service and indicate caution areas. Electrical diagrams shall be printed on long life water resistant material and shall ship attached to control panel doors. Casing Exterior panels shall be zinc coated galvanized steel, phosphatized and painted with a slate grey air-dry finish durable enough to withstand a minimum of 500 hours consecutive salt spray application in accordance with standard ASTM B117. Screws shall be coated with zinc-plus-zinc chromate. Heavy gauge steel hinged access panels with tiebacks to secure door in open position shall provide access to filters and heating sections. Refrigeration components, supply air fan and compressor shall be accessible through removable panels as standard. Unit control panel, filter section, and gas heating section shall be accessible through hinged access panels as standard. Optional Double Wall Construction hinged access doors shall provide access to filters, return/exhaust air, heating and supply fan section. All access doors and panels shall have neoprene gaskets. Interior surfaces or exterior casing members shall have 1/2" Tuf-Skin fiberglass insulation. Unit base shall be watertight with heavy gauge formed load bearing members, formed recess and curb overhang. Unit lifting lugs shall accept chains or cables for rigging. Lifting lugs shall also serve as unit tiedown points. Compressors - R410A The Trane 3-D Scroll compressors have a simple mechanical design with only three major moving parts. Scroll type compression provides inherently low vibration. The 3-D Scroll provides a completely enclosed compressor chamber with optimized scroll profiles which leads to increased efficiency. The 3-D Scroll includes a direct-drive, 3600 rpm, suction gas cooled hermetic motor. Dependent on the compressor model, motor protection is provided by either a patented motor cap and integral line break motor protector or an external 24 VAC module which provides protection against incorrect phase sequence, excess motor temperatures, over current protection, and phase loss. Trane 3-D compressor includes centrifugal oil pump, scroll tips seals, internal heat shield that lowers the heat transfer from discharge and suction gas, oil level sight glass and oil charge valve. Some compressor models also provide a dip tube that allows for oil draining, in addition to a low leakage internal discharge check valve to help prevent refrigerant migration. Each compressor shall have a crankcase heater installed, properly sized to minimize the amount of liquid refrigerant present in the oil sump during off cycles. Phase and Voltage Monitor - R410A Standard on 20-75T air-cooled, 24-89T evaporative condensing units. Protects 3-phase equipment from phase loss, phase reversal and low voltage. Any fault condition will produce a Failure Indicator LED and send the unit into an auto stop condition. cULus approved. Supply Fan Supply fan motors are either open drip-proof or enclosed fan cooled. All supply fans shall be dynamically balanced in factory. Supply fan shall be test run in unit and shall reach rated rpm. All 60 Hz supply fan motors meet the Energy Independence Security Act of 2007 (EISA). All 50 Hz supply fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Direct-Drive Plenum Supply Fan Supply fan shall be [one] [two] single width, single inlet 9-blade plenum fan. Fan blades shall be aluminum backward-inclined airfoil. Plenum fans shall be direct-driven. Entire assembly shall be completely isolated from unit and fan board by 2" deflection spring isolation. Multiple fan widths shall be available to optimize efficiency. Fan shall not require routine maintenance such as fan bearing lubrication, belt tensioning and replacement, sheave alignment, and setscrew torque checks. Evaporator Coil - R410A Internally enhanced copper tubing of 3/8" or 1/2" O.D. shall be mechanically bonded to heavyduty aluminum fins of configured design. All coils shall be equipped with thermal expansion valves and factory pressure and leak tested.

Page 7: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 7 of 24

Air-Cooled Condenser Coil - R410A Condenser coils shall have all Aluminum Microchannel coils. All coils shall be leak tested at the factory to ensure pressure integrity. The condenser coil is pressure tested to 650 psig. Subcooling circuit(s) shall be provided as standard. Supply Airflow Measurement (Piezometer) Plenum supply fan shall have an airflow measurement device to measure differential pressure and to calculate fan airflow. The device shall be capable of measuring airflow within + or - 5 percent total accuracy when operating within the stable operating region of the fan curve. Fan airflow performance and noise levels shall not be affected by the installation of the device. The fan inlet shall not be obstructed by the airflow measurement device Note: Transmitter must be customer-supplied & field installed. Condenser Fans and Motors All condenser fans shall be vertical discharge, direct drive fans, statically balanced, with steel blades and zinc plated steel hubs. Condenser fan motors shall be three-phase motors with permanently lubricated ball bearings, built-in current and thermal overload protection and weathertight slingers over motor bearings. Ventilation Override Module (VOM) With the Ventilation Override Module installed, the unit can be programmed to transition to up to 5 different programmed sequences for Smoke Purge, Evacuation, Pressurization, Purge, Purge with duct control sequence and Unit off. The transition occurs when a binary input on the VOM is closed (shorted); this would typically be a hard wired relay output from a smoke detector or fire control panel. <Enter Text Here> Unit Controller DDC microprocessor controls shall be provided to control all unit functions. The control system shall be suitable to control CV or VAV applications. The controls shall be factory-installed and mounted in the main control panel. All factory-installed controls shall be fully commissioned (run tested) at the factory. The unit shall have a Human Interface Panel with a 16 key keypad, a 2 line X 40 character clear English display as standard to provide the operator with full adjustment and display of control data functions. The unit controls shall be used as a stand-alone controller, or as part of a building management system involving multiple units. 1 The unit shall be equipped with a complete microprocessor control system. This system shall consist of temperature and pressure (thermistor and transducer) sensors, printed circuit boards (modules), and a unit mounted HumanInterface Panel. Modules (boards) shall be individually replaceable for ease of service. All microprocessors, boards and sensors shall be factory mounted, wired and tested. The microprocessor boards shall be stand-alone DDC controls not dependent on communications with an on-site PC or a Building Management Network. The microprocessors shall be equipped with on-board diagnostics, indicating that all hardware, software and interconnecting wiring are in proper operating condition. The modules (boards) shall be protected to prevent RFI and voltage transients from affecting the board's circuits. All field wiring shall be terminated at separate, clearly marked terminal strip. Direct field wiring to the I/O boards is not acceptable. The microprocessor's memory shall be non-volatile EEPROM type requiring no battery or capacitive backup, while maintaining all data. 2 Zone sensors shall be available in several combinations with selectable features depending on sensor. 3 The Human Interface Panel's keypad display character format shall be 40 characters x 2 lines. The character font shall be 5 x 7 dot matrix plus cursor. The display shall be Supertwist Liquid Crystal Display (LCD) with blue characters on a ray/green background which provides high visibility and ease of interface. The display format shall be in clear English. Two or three digit coded displays are not acceptable. 4 The keypad shall be equipped with 16 individual touch-sensitive membrane key switches. The switches shall be divided into four separate sections and be password protected from change by unauthorized personnel. The six main menus shall be STATUS, SETPOINTS, DIAGNOSTICS, SETUP, CONFIGURATION and SERVICE MODE.

Page 8: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 8 of 24

Modulating 100 Percent Exhaust Fan with Statitrac Control Two, double-inlet, forward-curved fans shall be mounted on a common shaft with fixed sheave drive. All fans shall be dynamically balanced and tested in factory before being installed in unit. Exhaust fan shall be test run as part of unit final run test. Unit shall reach rated rpm before fan shaft passes through first critical speed. Fan shaft shall be mounted on two grease lubricated ball bearings designed for 200,000-hour average life. Optional extended grease lines shall be provided to allow greasing of bearings from unit filter section. Fan motor and assembly shall be mounted on common base to allow consistent belt tension with no relative motion between fan and motor shafts. Entire assembly shall be completely isolated from unit and fan board by double deflection, rubber in shear isolators or spring isolation on motor sizes larger than five hp. For both CV and VAV rooftops, the 100 percent modulating exhaust discharge dampers (or VFD) shall be modulated in response to building pressure. A differential pressure control system, (Statitrac), shall use a differential pressure transducer to compare indoor building pressure to outdoor ambient atmospheric pressure. The FC exhaust fan shall be turned on when required to lower building static pressure setpoint. The (Statitrac) control system shall then modulate the discharge dampers (or VFD) to control the building pressure to within the adjustable, specified dead band that shall be adjustable at the Human Interface Panel. All 60 Hz exhaust fan motors meet the Energy Independence Security Act of 2007 (EISA). Variable Frequency Drive General Description: The AC Drive and all associated optional equipment are UL listed according to Power Conversation Equipment cULus. The AC Drive is designed, constructed and tested in accordance with NEMA ICS, NFPA, and IEC standards. The Drive is housed in a metal NEMA 1 enclosure. All standard and optional features are included within the Drive enclosure, unless otherwise specified. The Drive converts incoming fixed frequency three-phase AC power into a variable frequency and voltage for controlling the speed of three-phase AC motors. DC link reactors are provided on both the positive and negative rails of the DC bus equal to 3% impedance to minimize power line harmonics. Full load amp ratings meet or exceed NEC Table 430-150. The Drive provides full rated output current continuously, 110% of rated current for 60 seconds and 160% of rated current for up to 0.5 second while starting. Isolation is provided between the Drive's power circuitry and control circuitry to ensure operator safety and to protect connected electronic control equipment from damage caused by voltage spikes, current surges, and ground loop currents. Audible motor noise is minimized through the use of an adjustable carrier frequency. Carrier frequency is automatically adjusted to optimize motor and AC Drive efficiencies while reducing motor noise. Operating range, ambient temperature, -10 to 50C (14 to 104F), 0 to 95% relative humidity, non-condensing, AC line voltage variation, -10 to +10% of nominal with full output Protective Features Class 10 I2t electronic motor overload protection for single motor applications is provided. Protection against input transients, loss of AC line phase, output short circuit, output ground fault, over-voltage, under voltage, AC Drive over-temperature and motor over-temperature. All faults are displayed in plain English. Protection from AC Drive sustained power or phase loss. Full rated output with an input voltage as low as 90% of nominal. Continuous operation with reduced output with an input voltage as low as 164 V AC for 208/230 volt units, 313 V AC for 460 volt units, and 394 volts for 600 volts units. Semi-conductor rated input fuses to protect power components. A "signal loss detection" circuit senses the loss of an analog input signal such as 4 to 20 mA or 0 to 10 V DC, and is programmable to react as desired in such an instance. Default: After 10-second time out the Drive will shut off. Will function normally when the keypad is removed while the AC Drive is running and continue to follow remote commands. AC Drive catches rotating motor operating forward or reverse up to full speed. The AC Drive is rated for 100,000 amperes interrupting capacity (AIC). Includes current sensors on three output phases to detect and report phase loss to the motor. Identifies which of the output phases is low or lost. Continues to operate without faulting until input voltage reaches 300 V AC on 208/230 volt units, 539 V AC on 460 volt units, and 690 volts on 600 volt units Interface Features Off/Stop and Auto/Start selector switches provided to start and stop the AC Drive and determine the speed reference. On units with bypass, an AC Drive/Off/Bypass Hand selector switch will be provided in the unit control box. In case of an external current overload, a normally closed dry contact will stop the motor whether in DRIVE or BYPASS mode. In DRIVE mode speed reference is provided by a 0 to 10 V DC analog input. The display is programmable to display in 9 languages including English, Spanish and French. The display has four lines, with 20 characters on three lines and eight large characters on one line. The following points are controlled and/or accessible: AC Drive Start/Stop. Speed reference, Fault diagnostics, Meter points to include - Motor power in HP, Motor power in kW, Motor kW-hr, Motor current, Motor voltage, Hours run, DC link voltage, Thermal load on motor, Thermal load on AC Drive and Heatsink temperature. The AC Drive stores in memory the last 10 faults and related operational data. Four simultaneous displays are available, frequency or speed, run time, output amps and output power. The following displays are accessible from the keypad. Reference Signal Value, Output Frequency in Hz or percent, Output Amps, Motor HP, Motor kW, kW hour, Output Voltage, DC Bus Voltage, AC Drive Temperature in degrees, and Motor Speed in RPM.

Page 9: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 9 of 24

Bypass control Provides full nominal airflow in the event of drive failure. Internal Shaft Grounding Ring Motors have internal bearing protection for use with VFDs. Economizer Control with Comparative Enthalpy Used with the fresh air economizer, two enthalpy sensors are provided to compare total heat content of the indoor air and outdoor air to determine the most efficient air source when economizing. TRAQ (Outside Air Measurement) TRAQ shall include Ventilation Control Module (VCM). The VCM shall be linked to the Intellipak UCM to control the minimum fresh air entering the unit. Using a velocity pressure sensing ring, the VCM monitors and controls the quantity of fresh air entering the unit. This allows it to control to the minimum outside airflow setpoint. An optional temperature sensor can be connected to the VCM which enables it to control a field installed fresh air preheater; and an optional carbon dioxide sensor can be connected to the VCM to control the carbon dioxide reset. Option is cULus approved. Economizer Control with Dry Bulb Used with the fresh air economizer, an outdoor temperature sensor is included for comparing the outdoor dry bulb temperature to a locally adjustable temperature setpoint. The setpoint is programmed at the human interface, or remote human interface, to determine if outdoor air temperature is suitable for economizer operation. Temperature Sensor Bullet or pencil type sensor that could be used for temperature input such as return air duct temperature. Remote Human Interface Panel (RHI) Remote Human Interface Panel can perform all the same functions as unit mounted Human Interface Panel, except for the Service Mode. Up to 4 rooftop units can be monitored and controlled with a single Remote Human Interface Panel. This panel uses the same attractive enclosure as our Tracker¿ building control panel. With features such as a 2 line X 40 character clear English display, a red LED light to indicate an alarm condition (alarm also shown on the two line display), a simple 16 key keypad that is used in conjunction with the display, to prompt the infrequent user when making desired changes and an attractive hinged door makes the RHI very suitable for mounting on any wall. The RHI can be mounted inside a building, up to 5,000 feet from the unit. The RHI is wired to the IPCB mounted in the rooftop with twisted wire pair communication wiring and 24V control wiring. BACnet Communication Interface Module Provides control and monitoring of the rooftop by Tracer SC or a 3rd party building management system utilizing BACnet protocol. Demand Control Ventilation Provide demand control ventilation (DCV) system fully integrated with unit economizer. Controller shall minimize fresh air intake during periods of low occupancy based on parts per million space CO2 in response to a customer defined parts per million CO2 setpoint. CO2 setpoint, and minimum DCV fresh air damper position shall be programmable at the human interface, or building management system Note: CO2 sensor used with Demand Control Ventilation must be powered from an external power source or separate 24 VAC transformer. BAYSENS016 -Temperature Thermistor The temperature thermistor is used to communicate temperature changes in either the Zone, Return Air, Supply Air or Outside Ambient. Equipment manufactured by Trane that includes required start-up and sold in North America will not be warranted by Trane unless Trane or its authorized independent Trane commercial sales office performs the startup on the equipment. Differential Pressure Gauge A factory-installed, dial-type, differential pressure gauge shall be piped to both sides of the filter to indicate status. Gauge shall maintain a +/- 5 percent accuracy within operating temperature limits of -20°F to 120°F. Gauge shall be flush-mounted with casing outer wall. Filter sections consisting of pre- and post-filters shall have a gauge for each.

Page 10: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 10 of 24

Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

EX

HA

US

T

2.

LO

W A

MB

IEN

T D

AM

PE

R O

NLY

CO

ME

S W

ITH

SE

LE

CT

ED

UN

IT

3. O

VE

RA

LL U

NIT

WID

TH

IN

CR

EA

SE

S 5

/8"

BE

YO

ND

LIF

TIN

G L

UG

WIT

H U

LT

RA

LO

W L

EA

K P

OW

ER

E

XH

AU

ST

DA

MP

ER

S.

69

3/8

"

39

4 9

/16

"

11

9 3

/8"

39

8 1

3/1

6"

14

4 1

/8"

114

3/8

"

92

9/1

6"

7 1

/16

" 29"

238

5/1

6"

22

1/8

"

20

3/8

"

17

7/8

"

15 7

/8"

9 7

/8"

8 1

5/1

6"

7 1

5/1

6"

10 1

/4"

70

3/8

"8

7 1

/4"

92

3/1

6"

53

3/8

"

5 1

3/1

6"

5 1

3/1

6"

94 3

/16

"8

1 1

/16"

119

3/8

"

18

4 5

/16

"

SU

PP

LY

60/7

0/7

5 T

ON

LE

FT

SID

E V

IEW

LIF

TIN

G P

OIN

TS

X 6

60/7

0/7

5 T

ON

PL

AN

VIE

W

4 1

/8"

CO

NN

. T

HR

U

BA

SE

FO

R P

OW

ER

SU

PP

LY

1 1

/8"

CO

ND

UIT

D.C

CO

NT

RO

L C

IRC

UIT

1 1

/8"

CO

ND

UIT

A.C

CO

NT

RO

L C

IRC

UIT

1 1

/8"

CO

ND

UIT

AC

&

DC

CO

NT

RO

L C

IRC

UIT

1 3

/8"

DR

AIN

HO

LE

S

(BO

TH

SID

E)

60

/70

/75

TO

N F

RO

NT

VIE

W

OP

TIO

NA

L L

OW

AM

BIE

NT

DA

MP

ER

SE

E N

OT

E 2

60

/70

/75

TO

N P

LA

N V

IEW

OF

UN

IT

NO

TE

S:

1.

VE

RIF

Y W

EIG

HT

, C

ON

NE

CT

ION

, A

ND

ALL

DIM

EN

SIO

N

WIT

H I

NS

TA

LLE

R

DO

CU

ME

NT

S B

EF

OR

E IN

ST

ALL

AT

ION

SE

E N

OT

E 3

1"

NP

T-F

CO

ND

EN

SA

TE

DR

AIN

(B

OT

H S

IDE

)1"

NP

T-F

CO

ND

EN

SA

TE

DR

AIN

(B

OT

H S

IDE

)

(NO

T U

SE

D O

N U

NIT

S

WIT

H D

DP

FA

NS

)

Page 11: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 11 of 24

Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

1"

5 5/8"

3 5/8"

1"

5 13/16"

5/8"1"

90°

30°

3"

9/16"

1 5/8"

5/8"

4 13/16"

2 3/4"1"

5/8" 1/2"

2 1/2"

3"

3"

2 1/2"

3/8"

DETAIL

TYPICAL ROOF CURB AND BASE PAN DETAIL

SHIPS WITH CURB

FIELD INSTALLED

GASKET

TYPICAL PEDESTAL AND BASE PAN DETAIL

DETAIL

PEDESTAL

UNIT BASE

LIFTING LUG

4" LONG

LIFTING LUG

4" LONG

2" X 4" NAILER

(FURNISHED WITH KIT)

ROOF CURB

TYPICAL PEDESTAL AND BASE

DIMENSION DRAWING

Page 12: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 12 of 24

Unit Dimensions - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

110.012.6

61.010.8

SXHLF70 (70Ton)

414-506460603

N/AN/AN/AN/A

ELECTRICAL / GENERAL DATA

TONS

COMPRESSOR

SUPPLY FAN MOTOR

CONDENSER FAN MOTOR FILTERS - TYPE

REFRIGERANT TYPE

EXHAUST / RETURN FAN MOTOR

ELECTRIC HEATER

GAS HEATING - PERFORMANCE

Notes:

1. LOAD 1=Current of the largest motor (compressor or fan motor); LOAD 2=Sum of the currents of all remaining motors; LOAD 3 =Current of electric heaters

LOAD 4 =Control Power Transformer (20-40 and 24-48 ton units add 3 FL amps for wire sizing formula, 50-75 and 59 - 89 ton units add 6 FL amps)

2. For Electric Heat MCA, MOP, RDE values, calculate for both cooling and heating modes. (When determining LOADS, the compressors

do not operate when the unit is in heating mode) (On 70-89 ton single source units, heating Load 4 = 12 amps on 200,230 volt units and

9 amps on 460,575 volt units)

3. If selected Max Over Cur is less than the Min CIr Amp, then select the lowest maximum fuse size which is equal to or larger than the Min Cir

Amp, provided the selected fuse size does not exceed 800 amps.

4. If the selected Recommended Dual Element fuse size is greater than the selected Max Over Cur Protection value, then select the Recommended Dual

Element fuse size value to equal the Max Over Protection value.

5. Compressor KW at AHRI rating conditions of 80/67 -95

6. Refrigerant charge is an approx. value. For a more precise value, see unit nameplate and service instructions.

7. Sump Heater is an optional feature.

Model (Tonnage):

Unit Operating Voltage Range:

Unit Primary Voltage:

Unit Hertz:

Unit Phase:

EER:

IEER:

HEATING - GENERAL DATA

Heating Input:

Heating Output:

Capacity Steps:

Gas inlet pressure: (in w.c.)

Gas Pipe Connection Size:

Compressor 1 Count:

Compressor 1 RLA:

Compressor 2 Count:

Compressor 2 RLA:

Compressor 3 Count:

Compressor 3 RLA:

Electric Heater Kw:

Electric Heater Full Load Amps:

Number of Fans:

Number of Motors:

Horsepower (Each):

Supply Fan Motor Full Load Amps:

Supply Fan Efficiency:

Number:

Horsepower (each):

Condenser Fan Motor Full Load Amps (Total):

Number:

Horsepower (Each):

Exhaust Fan Motor Full Load Amps:

Type:

Furnished:

Number:

Recommended Size:

Charge Type:

Factory Charge (Circuit #1):

Factory Charge (Circuit #2):

PREFILTERS

Furnished:

Number:

Recommended Size:

10.6 EER15.4 EER

R-410A

EVAPORATIVE CONDENSER

Pump Horsepower:

Pump Full Load Amps:

Sump Heater Full Load Amps:

Sump Heater kW:

(7)

(6)

41.5 lb39.8 lb

2.00 Each2 40 HP DDP 80W24.70 A62.22 %

4.00 Each25.50 AValue not availableValue not availableValue not availableValue not available

FINAL FILTERS - TYPE

Type:

Furnished:

Number:

Recommended Size:

PREFILTERS

Furnished:

Number:

Recommended Size:

Page 13: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 13 of 24

Fan Curve - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

7.

50

b

hp

10

.0

0

bh

p

15

.0

0

bh

p

20

.0

0

bh

p

25

.0

0

bh

p

30

.0

0

bh

p

40

.0

0

bh

p

50

.0

0

bh

p

1000 RPM

1100 RPM

1200 RPM

1300 RPM

1400 RPM

1500 RPM

1600 RPM

1700 RPM

1800 RPM

1900 RPM

2000 RPM

2100 RPM

44 %WO 50 %WO

60 %WO

70 %WO

80 %WO

90 %WO

UnitSize:

Operating Airflow: 25000.00 cfm

Operating Static Pressure: 5.48 in H2O

Operating RPM: 1981.00

Operating Brake Horse Power: 34.66 bhp

Altitude: 0.00

Design Temp: 76.00 F

Date: 5/7/15

0

1

2

3

4

5

6

7

8

9

10

11

12

0 5000 10000 15000 20000 25000 30000 35000 40000 45000

2-2707DPLA01FN

To

tal

Sta

tic

Pr

es

su

re

(in

H2

O)

Airflow (cfm)

63Hz 125Hz 250Hz 500Hz 1 kHz 2 kHz 4 kHz 8 kHz

Discharge duct: 98 96 91 89 86 82 80 77Return duct: 90 91 84 80 77 75 71 68Exhaust fan: 83 82 77 75 72 70 67 62

Page 14: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 14 of 24

Weight, Clearance & Rigging Diagram - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

48"

72"

96"

96"

96"

144"

CLEARANCE

CLEARANCE

CLE

AR

AN

CE

CL

EA

RA

NC

E

CLEARANCE

RIGGING AND CLEARANCE

AIR COOLED DRAWING

Page 15: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 15 of 24

Weight, Clearance & Rigging Diagram - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

N/A2. Double wall :

29"

96"

194 5/16"

0,0

X

Y

Center of Gravity X: 16.74 ftCenter of Gravity Y: 5.01 ft

Point Load 1: 848.5 lbPoint Load 2: 928.2 lbPoint Load 3: 933.5 lbPoint Load 4: 1013.2 lbPoint Load 5: 1008.8 lbPoint Load 6: 1088.5 lbPoint Load 7: 1085.0 lbPoint Load 8: 1164.7 lbPoint Load 9: 1169.1 lbPoint Load 10: 1248.8 lb

Total Weight: 10488.3 lb

PL 2, X1 PL 4, X2 PL 6, X3 PL 8, X4 PL 10, X5

PL 1, X1 PL 3, X2 PL 5, X3 PL 7, X4 PL 9, X5

Added Weight

1. IRU:

Notes:

1. The actual weight is stamped on the unit nameplate.

2. The weight shown represent the typical unit operating weights for the unit selected.

3. Add weight to the total unit weight.

4. Most Design Special weights are not displayed.

(3)

(3)

Point load X location 1: 4.000 inPoint load X location 2: 101.000 inPoint load X location 3: 187.000 inPoint load X location 4: 274.000 inPoint load X location 5: 370.000 inPoint load X location 6: N/APoint load X location 7: N/APoint load X location 8: N/APoint load X location 9: N/APoint load X location 10: N/APoint load Y location 1: 4.000 inPoint load Y location 2: 112.000 in

CENTER OF GRAVITY AND INSTALL WEIGHT X-Y POINTS

AIR COOLED DRAWING

Y

X

Page 16: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 16 of 24

Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

L1

117 119

L3

L3L1

CIRCUIT #2

ELECTRIC HEAT 200V/230V/60 HZ

UNITS ONLY

L2

4TB2, 4S15

118

L2

LINE VOLTAGE

CIRCUIT #1

MAIN UNIT CONTROL

1 2 3

L1 L2 L3

L3L2L1

1TB1 OR1S14

LINE VOLTAGE

4U15

HYDRONIC HEAT

ACTUATOR

CONNECT STEAM OR

HOT WATER VALVE AS

SHOWN WHEN REQUIRED

HEATINGSECTION

CONDENSERSECTION

37M 36AL

T1 T2

483A484A

(-)(+)

BLK WHT

SPLICE SPLICE

4

3 3

ADVERTENCIAiVOLTAJE PELIGROSO!

DESCONECTE TODA LA ENERGIA ELECTRICA,

INCLUSO LAS DESCONEXIONES REMOTAS Y

SIGA LOS PROCEDIMIENTOS DE CIERRE Y

ETIQUETADO ANTES DE PROCEDER AL

SERVICIO. ASEGURESE DE QUE TODOS

LOS CAPACITORES DEL MOTOR HAYAN

DESCARGADO EL VOLTAJE ALMACENADO.

PARA LAS UNIDADES CON EJE DE

DIRECCION DE VELOCIDAD VARIABLE,

CONSULTE LAS INSTRUCCIONES PARA LA

DESCARGA DEL CONDENSADOR.

EL NO REALIZAR LO ANTERIORMENTE

INDICADO, PODRIA OCASIONAR LA MUERTE

O SERIAS LESIONES PERSONALES.

DO NOT ENERGIZE UNIT

UNTIL CHECK-OUT AND

START-UP PROCEDURE HAS

BEEN COMPLETED.

IMPORTANT!

HAZARDOUS VOLTAGE!

WARNING AVERTISSEMENTTENSION DANGEREUSE!

SI NO LO HACE, PUEDE OCASIONAR DANO AL

DISENADAS PARA ACEPTAR OTROS TIPOS DE

LAS TERMINALES DE LA UNIDAD NO ESTAN

IUTILICE UNICAMENTE CONDUCTORES DE

PEUT ENDOMMAGER L'EQUIPEMENT.

L'UTILISATION DE TOUT AUTRE CONDUCTEUR

EQUIPO.

PRECAUCION

CONDUCTORES.

COBRE!

FAILURE TO DO SO MAY CAUSE DAMAGE TO

ACCEPT OTHER TYPES OF CONDUCTORS.

UNIT TERMINALS ARE NOT DESIGNED TO

CONCUES POUR RECEVOIR D'AUTRES TYPES

LES BORNES DE L'UNITE NE SONT PAS

N'UTILISER QUE DES CONDUCTEURS EN

THE EQUIPMENT.

ATTENTION

DE CONDUCTEURS.

CUIVRE!

CAUTIONUSE COPPER CONDUCTORS ONLY!

COUPER TOUTES LES TENSIONS ET

OUVRIR LES SECTIONNEURS A DISTANCE,

PUIS SUIVRE LES PROCEDURES DE

VERROUILLAGE ET DES ETIQUETTES AVANT

TOUTE INTERVENTION. VERIFIER QUE TOUS

LES CONDENSATEURS DES MOTEURS SONT

DECHARGES. DANS LE CAS D'UNITES

COMPORTANT DES ENTRAINEMENTS A

VITESSE VARAIBLE, SE REPORTER AUX

INSTRUCTIONS DE L'ENTRAINEMENT POUR

DECHARGER LES CONDENSATEURS.

NE PAS RESPECTER CES MESURES DE

PRECAUTION PEUT ENTRAINER DES

BLESSURES GRAVES POUVANT ETRE

MORTELLES.

DISCONNECT ALL ELECTRIC POWER

INCLUDING REMOTE DISCONNECTS

AND FOLLOW LOCK OUT AND TAG

PROCEDURES BEFORE SERVICING.

INSURE THAT ALL MOTOR

CAPACITORS HAVE DISCHARGED

STORED VOLTAGE. UNITS WITH

VARIABLE SPEED DRIVE, REFER

TO DRIVE INSTRUCTIONS FOR

CAPACITOR DISCHARGE.

FAILURE TO DO THE ABOVE

BEFORE SERVICING COULD RESULT

IN DEATH OR SERIOUS INJURY.

Note:

All wiring and components shown dashed to be

supplied and installed by the customer in

accordance with local electrical codes.

EXTERNAL FIELD MOUNTED DEVICE

INSIDE UNIT CONTROL BOX

DEVICE PREFIX LOCATION CODE

CONDENSER SECTION

AIR HANDLER SECTION

LOCATION

5

HEATING SECTION4

3

2

1

AREA

Page 17: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 17 of 24

Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

268 1/2"

2"

2"

110 5/16"

119 15/16"

7"

94 1/16"

14 1/16"

12 11/16"

1 1/8"

12 11/16"

6 3/16"

2 3/8"

91 3/4"

29 5/16"24" 42"

94 5/16"

268 1/8"

1 13/16"

121 7/16"

7 1/2"

6"

1 13/16" 6"

22 5/8"

233"

60/70/75 TON PLAN VIEW

60/70/75 TON ISOMETRIC VIEW

RETURN /

EXHAUST

OPENING

SUPPLY

OPENING

PEDESTAL

PEDESTAL

RETURN / EXHAUST OPENING

SUPPLY OPENING

Page 18: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 18 of 24

Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

ALL WIRING AND COMPONENTS SHOWN DASHED TO BE SUPPLIED AND INSTALLED BY THE

CUSTOMER IN ACCORDANCE WITH LOCAL ELECTRICAL CODES.

CUSTOMER CONNECTIONS - MAIN UNIT CONTROL (CIRCUIT #1) - ARE LOCATED IN THE

CONDENSER SECTION FOR 20 THRU 75 TON UNITS.

SEE CUSTOMER CONNECTION WIRE RANGE TABLE FOR ACCEPTABLE WIRE SIZES FOR

CONNECTION TO MAIN UNIT TERMINAL BLOCK (1TB1/4TB2) OR DISCONNECT

SWITCH (1S14/4S15).

WIRES TO THE OPTIONAL STEAM AND/OR HOT WATER HEAT VALVE ARE SUPPLIED WITH

THE UNIT. WIRE CONNECTIONS TO THE VALVE TO BE MADE BY THE CUSTOMER.

OPTIONAL 5U57 REMOTE ZONE TEMP SENSOR IS USED FOR UNOCCUPIED HEAT/COOL

TEMP CONTROL SENSING.

WHEN 5U69 REMOTE ZONE TEMP SENSOR IS USED, REMOVE 5U58 INTERGRAL ZONE

TEMP SENSOR ATTACHED TO TERMINALS S1 AND S2.

WIRES USE SHIELDED TWISTED PAIR WIRE.

USE SHIELDED TWISTED PAIR WIRE. WRAP SHIELDS WITH TAPE TO PREVENT CONTACT

WITH GROUND.

REMOVE JUMPER (1TB4-15 & 1TB4-16) AND INSTALL HIGH DUCT TEMP T-STAT /OR

FIELD SUPPLIED DEVICE.

REMOVE JUMPER (1TB4-17 & 1TB4-18) WHEN FIELD SUPPLIED

EXTERNAL AUTO/STOP SWITCH (5S67) IS INSTALLED.

CHANGEOVER (5K87) AVAILABLE ONLY ON HYDRONIC HEAT UNITS OR MODULATING

GAS HEAT UNITS.

ALARM OUTPUT SWITCHES ON ANY MANUAL RESET DIAGNOSTIC.

OPTIONAL HEAT MODULE AUX. TEMP (5RT16) IS USED FOR MORNING WARM-UP

CONTROL ON UNITS WITH HEATING OPTION.

TERMINAL BLOCK 1TB17 AND ASSOCIATED WIRING REQUIRED WITH GBAS (1U51) OPTION.

DEMAND LIMIT RELAY (5K89) TO BE PROVIDED BY CUSTOMER.

VENTILATION OVERRIDE MODE CONTACTS RATED 12MA @ 24VDC MINIMUM

(5K90 - 5K91 - 5K92 - 5K93 - 5K94) TO BE PROVIDED BY CUSTOMER.

WIRE NODES 533 & 534 REQUIRED WITH BAS/NETWORK COMM MODULE (1U54) OPTION.

USE SHIELDED TWISTED PAIR WIRE.

FIELD CONNECTIONS TO DRIVE VAV BOXES FULL OPEN DURING NIGHT SETBACK MODE.

15A FUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60 TON - 0.50 KVA TRANSFORMER

WITH 200V - 230V - 460V OR 575V UNIT VOLTAGE.

20A FUSE REPLACEMENT IS REQUIRED FOR 50 THRU 60 TON - 0.50 KVA TRANSFORMER

WITH 380V OR 415V UNIT VOLTAGE.

CONTACTS RATED 12 MA @ 24VDC MINIMUM.

CONNECT TO 24VAC CLASS 2 CIRCUITS ONLY.

REMOVE JUMPER WHEN OPTIONAL FIELD SUPPLIED OUTSIDE AIR SENSOR

(3RT3) IS INSTALLED AND THE UNIT DOES NOT HAVE ECONOMIZER.

FIELD SUPPLIED AND INSTALLED OCCUPIED/UNOCCUPIED CONTACTS (5K86)

FOR USE ON UNITS WITHOUT REMOTE PANEL WITH NIGHT SETBACK (5U58).

GBAS 0-5V OPTION CONNECTIONS.

GBAS 0-10V OPTION CONNECTIONS.

FOR GBAS INPUTS AI1-AI4, "GBAS 0-5V" REQUIRES 0-5V VDC

AND "GBAS 0-10V" REQUIRES 0-10VDC.

"ACTIVE DIAGNOSTICS (BO5)" APPEARS WITH BOTH "GBAS 0-5V" AND "GBAS 0-10V".

SEE FUSE REPLACEMENT TABLE ON VFD PANEL FOR VFD POWER FUSES (F40, F41, F42).

SWITCH A53, LOCATED ON THE VFD, MUST BE SET TO "U" (OFF).

NOTES:

1

2

3

4

6

7

8

9

10

11

13

14

15

16

17

19

21

22

23

24

25

26

27

28

29

30

12

18

Page 19: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 19 of 24

Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

CUSTOMER CONNECTION WIRE RANGE

NOTES: UNITS WITH MAIN POWER

TERMINAL BLOCK (ALL VOLTAGES)

UNITS WITH MAIN POWER

DISCONNECT SWITCH (ALL VOLTAGES)A. BLOCK SIZE & DISCONNECT SIZE

ARE

CALCULATED BY SELECTING THE

SIZE

GREATER THAN OR EQUAL TO 1.15 X

(SUM OF UNIT LOADS). SEE UNIT

LITERATURE FOR UNIT LOAD

VALUES.

335 AMP (1) #6 - 350 MCM 100 AMP (1) #14 - 1/0

760 AMP (2) #4 - 500 MCM 250 AMP (1) #4 - 350 kcmil

840 AMP (2) #2 - 600 MCM 400 AMP (1) OR #1 - 600 kcmil OR

(2) #1 - 250 kcmil

600 AMP (2) 250 - 500 MCM

1000 AMP (3) 3/0 - 500 kcmil

FUSE REPLACEMENT TABLE

CONDENSER FAN FUSE

1F1 THRU 1F6 CLASS RK5

UNIT VOLTAGE 200 230 380 415 460 575

TIME DELAY 25A 25A 15A 15A 15A 15A

CONTROL POWER FUSE

CONTROL (1T1) TRANSFORMER RATING0.25

KVA

0.30

KVA

0.50

KVA

0.75

KVA

1.00

KVA

1.50

KVA

1F7

CLASS CC - TYPE

FNQ-R

20-30 TON 6.25A 6.25A -- 10A -- --

40 TON 15A 20A -- 20A -- --

50-60 TON -- -- 15A -- 20A --

70-75 TON -- -- -- -- 15A 20A

ELECTRIC HEAT FUSE 4F19 THRU 4F36, 4F46, 47, 48 CLASS K5 60A

COMPRESSOR PROTECTION FUSE 1F44 & 1F45 TYPE MTH 6A

TRANSFORMER CIRCUIT FUSE 1F72 THRU 1F74 TYPE FNQ-R 15A

STANDARD MOTORS

UNIT

VOLTAGE

FUSE

RATING1.5 HP 3 HP 5 HP 7.5 HP 10 HP 15 HP 20 HP 25 HP 30 HP 40 HP

200V/60/3 600V 15A 35A 45A 70A 100A 150A 175A 225A 225A 400A

230V/60/3 600V 15A 25A 45A 70A 80A 125A 150A 200A 225A 350A

380V/50/3 600V 10A 15A 30A 50A 60A 90A 110A 125A 125A N/A

415V/50/3 600V 10A 15A 30A 45A 50A 90A 100A 125A 125A N/A

460V/60/3 600V 10A 15A 25A 35A 40A 70A 80A 100A 125A 175A

575V/60/3 600V 10A 15A 15A 25A 30A 40A 50A 60A 90A 100A

HIGH EFFICIENCY MOTORS

UNIT

VOLTAGE

FUSE

RATING1.5 HP 3 HP 5 HP 7.5 HP 10 HP 15 HP 20 HP 25 HP 30 HP 40 HP

200V/60/3 600V N/A 40A 45A 80A 100A 125A 175A 225A 225A 350A

230V/60/3 600V N/A 25A 45A 60A 90A 125A 150A 175A 225A 300A

460V/60/3 600V N/A 15A 25A 35A 45A 60A 90A 110A 125A 150A

575V/60/3 600V 10A 15A 15A 25A 30A 40A 50A 60A 90A 100A

OPTIONAL CONVENIENCE OUTLET FUSE

1F55 AND 1F56 (TIME DELAY TYPE FNQ-R FUSE)

200V/60/3 230V/60/3 380V/50/3 415V/50/3 460V/60/3 575V/60/3

12A 10A N/A N/A 5A 4A

VFD PROTECTION FUSES

----------------

OPTIONAL SUPPLY FAN

20 THRU 75 TON

1F57-1F62

-----------------

OPTIONAL EXHAUST /

RETURN

FAN

20 THRU 75 TON

1F63-1F65

(CLASS "T" FUSES)

BLOCK SIZE WIRE QTY CONNECTOR WIRE RANGE DISCONNECT SIZE WIRE QTY CONNECTOR WIRE RANGE

Page 20: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 20 of 24

Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

411

409

HEAT 7

COOL 8

SYS ON 9

SERVICE 10

GND 11

COMM (+) 12

COMMON

1

5S71

EMERGENCY

STOP SWITCH

435 431

J1-1 (+)

436

537

538

408 1

J1-3

2

5U57

REMOTE

ZONE

TEMP

SENSOR

408

409

403

436

537

538

5U66

REMOTE

HUMAN

INTERFACE

MODULEJ2-1 (+)

J1-2 (-)

J2-2 (-) J2-3

EARTH

GROUND

1

2

ZONE

TEMP

4 MODE

5U68

ZONE PANEL

417

416

415

414

413

418

5U58

REMOTE PANEL

WITH NSB

5K86

OCCUPIED/

UNOCCUPIED

CONTACTS

408

5U61

ZONE

RESET

TEMP

SENSOR

424425

5U59

REMOTE

PANEL

7 HEAT

9 SYS ON

10 SERVICE

6 GND

413

414

415

416

417

8 COOL

409

412

1

2

3

4

12

13

14

15

5

6

7

8

9

16

17

18

19

20

10

11

21

22

1TB4

410

412

413

414

415

416

417

425

424

403

435

437

431

434

438

437

438

5S67

EXTERNAL AUTO/STOP

SWITCH

434 438

410 3 SA CSP

VAV ZONE

RESET OPTION

5U69

REMOTE

ZONE TEMP

SENSOR

S1

S2

40324 VAC 14

418

8

7

24

21

21112110

10

11

7

9

6

ADVERTENCIAiVOLTAJE PELIGROSO!

DESCONECTE TODA LA ENERGIA ELECTRICA,

INCLUSO LAS DESCONEXIONES REMOTAS Y

SIGA LOS PROCEDIMIENTOS DE CIERRE Y

ETIQUETADO ANTES DE PROCEDER AL

SERVICIO. ASEGURESE DE QUE TODOS

LOS CAPACITORES DEL MOTOR HAYAN

DESCARGADO EL VOLTAJE ALMACENADO.

PARA LAS UNIDADES CON EJE DE

DIRECCION DE VELOCIDAD VARIABLE,

CONSULTE LAS INSTRUCCIONES PARA LA

DESCARGA DEL CONDENSADOR.

EL NO REALIZAR LO ANTERIORMENTE

INDICADO, PODRIA OCASIONAR LA MUERTE

O SERIAS LESIONES PERSONALES.

DO NOT ENERGIZE UNIT

UNTIL CHECK-OUT AND

START-UP PROCEDURE HAS

BEEN COMPLETED.

IMPORTANT!

HAZARDOUS VOLTAGE!

WARNING AVERTISSEMENTTENSION DANGEREUSE!

SI NO LO HACE, PUEDE OCASIONAR DANO AL

DISENADAS PARA ACEPTAR OTROS TIPOS DE

LAS TERMINALES DE LA UNIDAD NO ESTAN

IUTILICE UNICAMENTE CONDUCTORES DE

PEUT ENDOMMAGER L'EQUIPEMENT.

L'UTILISATION DE TOUT AUTRE CONDUCTEUR

EQUIPO.

PRECAUCION

CONDUCTORES.

COBRE!

FAILURE TO DO SO MAY CAUSE DAMAGE TO

ACCEPT OTHER TYPES OF CONDUCTORS.

UNIT TERMINALS ARE NOT DESIGNED TO

CONCUES POUR RECEVOIR D'AUTRES TYPES

LES BORNES DE L'UNITE NE SONT PAS

N'UTILISER QUE DES CONDUCTEURS EN

THE EQUIPMENT.

ATTENTION

DE CONDUCTEURS.

CUIVRE!

CAUTIONUSE COPPER CONDUCTORS ONLY!

COUPER TOUTES LES TENSIONS ET

OUVRIR LES SECTIONNEURS A DISTANCE,

PUIS SUIVRE LES PROCEDURES DE

VERROUILLAGE ET DES ETIQUETTES AVANT

TOUTE INTERVENTION. VERIFIER QUE TOUS

LES CONDENSATEURS DES MOTEURS SONT

DECHARGES. DANS LE CAS D'UNITES

COMPORTANT DES ENTRAINEMENTS A

VITESSE VARAIBLE, SE REPORTER AUX

INSTRUCTIONS DE L'ENTRAINEMENT POUR

DECHARGER LES CONDENSATEURS.

NE PAS RESPECTER CES MESURES DE

PRECAUTION PEUT ENTRAINER DES

BLESSURES GRAVES POUVANT ETRE

MORTELLES.

DISCONNECT ALL ELECTRIC POWER

INCLUDING REMOTE DISCONNECTS

AND FOLLOW LOCK OUT AND TAG

PROCEDURES BEFORE SERVICING.

INSURE THAT ALL MOTOR

CAPACITORS HAVE DISCHARGED

STORED VOLTAGE. UNITS WITH

VARIABLE SPEED DRIVE, REFER

TO DRIVE INSTRUCTIONS FOR

CAPACITOR DISCHARGE.

FAILURE TO DO THE ABOVE

BEFORE SERVICING COULD RESULT

IN DEATH OR SERIOUS INJURY.

Note:

All wiring and components shown dashed to be

supplied and installed by the customer in

accordance with local electrical codes.

EXTERNAL FIELD MOUNTED DEVICE

INSIDE UNIT CONTROL BOX

DEVICE PREFIX LOCATION CODE

CONDENSER SECTION

AIR HANDLER SECTION

LOCATION

5

HEATING SECTION4

3

2

1

AREA

Page 21: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 21 of 24

Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

3RT3

OPTIONAL

OUTSIDE

AIR

SENSOR

427

426

5K92

VENTILATION

OVERRIDE

MODE C CONTACTS

5K93

VENTILATION

OVERRIDE

MODE D CONTACTS

489 490

5K94

VENTILATION

OVERRIDE

MODE E CONTACTS

5K91

VENTILATION

OVERRIDE

MODE B CONTACTS

5K89

DEMAND

LIMIT

CONTACTS

426427

489

490 476

533

534

5RT16

HEAT

MODULE

AUX TEMP

BLU

WHT

5U70

REMOTE

MINIMUM

POSITION

POTENTIOMETER

475 476

TRACER

COMMUNICATIONS

533534

549

550

5K87

CHANGEOVER

CONTACTS

1TB5

443

444

1

444

443

2

3

4

12

13

14

15

5

6

7

8

9

16

17

18

19

20

10

11

21

22

475

523

524

525

526

527

549

550

528

529

530

531

532

528

5K90

VENTILATION

OVERRIDE

MODE A CONTACTS

524523

527

526

525

532

531

529 530

RED

}

16 15

21

16

14

16

16

16

17

21

12

2316

23

ADVERTENCIAiVOLTAJE PELIGROSO!

DESCONECTE TODA LA ENERGIA ELECTRICA,

INCLUSO LAS DESCONEXIONES REMOTAS Y

SIGA LOS PROCEDIMIENTOS DE CIERRE Y

ETIQUETADO ANTES DE PROCEDER AL

SERVICIO. ASEGURESE DE QUE TODOS

LOS CAPACITORES DEL MOTOR HAYAN

DESCARGADO EL VOLTAJE ALMACENADO.

PARA LAS UNIDADES CON EJE DE

DIRECCION DE VELOCIDAD VARIABLE,

CONSULTE LAS INSTRUCCIONES PARA LA

DESCARGA DEL CONDENSADOR.

EL NO REALIZAR LO ANTERIORMENTE

INDICADO, PODRIA OCASIONAR LA MUERTE

O SERIAS LESIONES PERSONALES.

DO NOT ENERGIZE UNIT

UNTIL CHECK-OUT AND

START-UP PROCEDURE HAS

BEEN COMPLETED.

IMPORTANT!

HAZARDOUS VOLTAGE!

WARNING AVERTISSEMENTTENSION DANGEREUSE!

SI NO LO HACE, PUEDE OCASIONAR DANO AL

DISENADAS PARA ACEPTAR OTROS TIPOS DE

LAS TERMINALES DE LA UNIDAD NO ESTAN

IUTILICE UNICAMENTE CONDUCTORES DE

PEUT ENDOMMAGER L'EQUIPEMENT.

L'UTILISATION DE TOUT AUTRE CONDUCTEUR

EQUIPO.

PRECAUCION

CONDUCTORES.

COBRE!

FAILURE TO DO SO MAY CAUSE DAMAGE TO

ACCEPT OTHER TYPES OF CONDUCTORS.

UNIT TERMINALS ARE NOT DESIGNED TO

CONCUES POUR RECEVOIR D'AUTRES TYPES

LES BORNES DE L'UNITE NE SONT PAS

N'UTILISER QUE DES CONDUCTEURS EN

THE EQUIPMENT.

ATTENTION

DE CONDUCTEURS.

CUIVRE!

CAUTIONUSE COPPER CONDUCTORS ONLY!

COUPER TOUTES LES TENSIONS ET

OUVRIR LES SECTIONNEURS A DISTANCE,

PUIS SUIVRE LES PROCEDURES DE

VERROUILLAGE ET DES ETIQUETTES AVANT

TOUTE INTERVENTION. VERIFIER QUE TOUS

LES CONDENSATEURS DES MOTEURS SONT

DECHARGES. DANS LE CAS D'UNITES

COMPORTANT DES ENTRAINEMENTS A

VITESSE VARAIBLE, SE REPORTER AUX

INSTRUCTIONS DE L'ENTRAINEMENT POUR

DECHARGER LES CONDENSATEURS.

NE PAS RESPECTER CES MESURES DE

PRECAUTION PEUT ENTRAINER DES

BLESSURES GRAVES POUVANT ETRE

MORTELLES.

DISCONNECT ALL ELECTRIC POWER

INCLUDING REMOTE DISCONNECTS

AND FOLLOW LOCK OUT AND TAG

PROCEDURES BEFORE SERVICING.

INSURE THAT ALL MOTOR

CAPACITORS HAVE DISCHARGED

STORED VOLTAGE. UNITS WITH

VARIABLE SPEED DRIVE, REFER

TO DRIVE INSTRUCTIONS FOR

CAPACITOR DISCHARGE.

FAILURE TO DO THE ABOVE

BEFORE SERVICING COULD RESULT

IN DEATH OR SERIOUS INJURY.

Note:

All wiring and components shown dashed to be

supplied and installed by the customer in

accordance with local electrical codes.

EXTERNAL FIELD MOUNTED DEVICE

INSIDE UNIT CONTROL BOX

DEVICE PREFIX LOCATION CODE

CONDENSER SECTION

AIR HANDLER SECTION

LOCATION

5

HEATING SECTION4

3

2

1

AREA

Page 22: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 22 of 24

Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

450

509

543

542

543 VO

RELAY

OUTPUT

NO

COM

NC

NO

COM

NC

508

NC

COM

NO

509 NC

507

COM

508

NO507

545

546

1

2

3

4

12

13

14

15

5

6

7

8

9

16

17

18

19

20

10

11

21

22

1TB16

445

446

447

448

449

HEAT MODE RELAY OUTPUT

(HYDRONIC HEAT OR MODULATING

GAS HEAT)

NC

544

545

546

COM

NO

541

542

544

447

446

445

448

449

450

ALARM

OUTPUT

(24 VAC MAX)

541

DIRTY

FILTER

(BO1)

VAV BOX

RELAY

24 VAC MAX

612

613

612

613 (-)

(+)

5U108

SPACE

HUMIDITYSENSOR

614

615

616

NC

COM

615

616

NO 614

HUMIDIFICATION

}}

{{{

}}

508 (-)0-10 VDC

(AO1)}509 (+)

22

22

18

22

13

22

22

25

22

26

ADVERTENCIAiVOLTAJE PELIGROSO!

DESCONECTE TODA LA ENERGIA ELECTRICA,

INCLUSO LAS DESCONEXIONES REMOTAS Y

SIGA LOS PROCEDIMIENTOS DE CIERRE Y

ETIQUETADO ANTES DE PROCEDER AL

SERVICIO. ASEGURESE DE QUE TODOS

LOS CAPACITORES DEL MOTOR HAYAN

DESCARGADO EL VOLTAJE ALMACENADO.

PARA LAS UNIDADES CON EJE DE

DIRECCION DE VELOCIDAD VARIABLE,

CONSULTE LAS INSTRUCCIONES PARA LA

DESCARGA DEL CONDENSADOR.

EL NO REALIZAR LO ANTERIORMENTE

INDICADO, PODRIA OCASIONAR LA MUERTE

O SERIAS LESIONES PERSONALES.

DO NOT ENERGIZE UNIT

UNTIL CHECK-OUT AND

START-UP PROCEDURE HAS

BEEN COMPLETED.

IMPORTANT!

HAZARDOUS VOLTAGE!

WARNING AVERTISSEMENTTENSION DANGEREUSE!

SI NO LO HACE, PUEDE OCASIONAR DANO AL

DISENADAS PARA ACEPTAR OTROS TIPOS DE

LAS TERMINALES DE LA UNIDAD NO ESTAN

IUTILICE UNICAMENTE CONDUCTORES DE

PEUT ENDOMMAGER L'EQUIPEMENT.

L'UTILISATION DE TOUT AUTRE CONDUCTEUR

EQUIPO.

PRECAUCION

CONDUCTORES.

COBRE!

FAILURE TO DO SO MAY CAUSE DAMAGE TO

ACCEPT OTHER TYPES OF CONDUCTORS.

UNIT TERMINALS ARE NOT DESIGNED TO

CONCUES POUR RECEVOIR D'AUTRES TYPES

LES BORNES DE L'UNITE NE SONT PAS

N'UTILISER QUE DES CONDUCTEURS EN

THE EQUIPMENT.

ATTENTION

DE CONDUCTEURS.

CUIVRE!

CAUTIONUSE COPPER CONDUCTORS ONLY!

COUPER TOUTES LES TENSIONS ET

OUVRIR LES SECTIONNEURS A DISTANCE,

PUIS SUIVRE LES PROCEDURES DE

VERROUILLAGE ET DES ETIQUETTES AVANT

TOUTE INTERVENTION. VERIFIER QUE TOUS

LES CONDENSATEURS DES MOTEURS SONT

DECHARGES. DANS LE CAS D'UNITES

COMPORTANT DES ENTRAINEMENTS A

VITESSE VARAIBLE, SE REPORTER AUX

INSTRUCTIONS DE L'ENTRAINEMENT POUR

DECHARGER LES CONDENSATEURS.

NE PAS RESPECTER CES MESURES DE

PRECAUTION PEUT ENTRAINER DES

BLESSURES GRAVES POUVANT ETRE

MORTELLES.

DISCONNECT ALL ELECTRIC POWER

INCLUDING REMOTE DISCONNECTS

AND FOLLOW LOCK OUT AND TAG

PROCEDURES BEFORE SERVICING.

INSURE THAT ALL MOTOR

CAPACITORS HAVE DISCHARGED

STORED VOLTAGE. UNITS WITH

VARIABLE SPEED DRIVE, REFER

TO DRIVE INSTRUCTIONS FOR

CAPACITOR DISCHARGE.

FAILURE TO DO THE ABOVE

BEFORE SERVICING COULD RESULT

IN DEATH OR SERIOUS INJURY.

Note:

All wiring and components shown dashed to be

supplied and installed by the customer in

accordance with local electrical codes.

EXTERNAL FIELD MOUNTED DEVICE

INSIDE UNIT CONTROL BOX

DEVICE PREFIX LOCATION CODE

CONDENSER SECTION

AIR HANDLER SECTION

LOCATION

5

HEATING SECTION4

3

2

1

AREA

Page 23: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 23 of 24

Accessory - Commercial Rooftop Air Conditioning Units (Midrange) Item: A1 Qty: 2 Tag(s): RTU-1, RTU-2

DANFOSS VARIABLE FREQUENCY DRIVE

PROGRAMMING PARAMETERS

MENU PARAMETER DESCRIPTION SETTING

LOAD/MOTOR

1-21 MOTOR POWER

SET ONLY FOR

APPLICATIONS USING

3HP HIGH EFFICIENCY

MOTORS

1-22 MOTOR VOLTAGE

SET ONLY FOR

200/230V 60HZ

380/415V 50HZ

APPLICATIONS

1-24 MOTOR CURRENTSET BASED ON

MOTOR NAMEPLATE

1-25 MOTOR NOMINAL SPEED 1800 RPM

1-73 FLYING START ENABLED

BRAKES 2-01 DC BRAKE CURRENT 0%

REFERENCE/

RAMPS

3-15 REFERENCE 1 SOURCE ANALOG INPUT 53

3-41 RAMP 1 RAMP UP TIME 30 SECONDS

3-42 RAMP 1 RAMP DOWN TIME 30 SECONDS

LIMITS/

WARNINGS

4-12 MOTOR SPEED LOW LIMIT 22HZ

4-18 CURRENT LIMIT 100% RATED CURRENT

DIGITAL

IN/OUT

5-40[0] FUNCTION RELAY 1 NO ALARM

5-40[1] FUNCTION RELAY 2 RUNNING

SPECIAL

FUNCTIONS

14-01 SWITCHING FREQUENCY 4.5KHZ

14-12FUNCTION AT MAINS

IMBALANCEDERATE

14-20 RESET MODE AUTOMATIC RESET X 3

14-60FUNCTION AT OVER

TEMPERATUREDERATE

30

Page 24: SOM Jackson State Office Building Pre-Purchase RTU Package Trane … SOM Jackson State Office Building May 07, 2015 FLD = Furnished by Trane U.S. Inc. / Installed by Others Equipment

SOM Jackson State Office Building May 07, 2015

FLD = Furnished by Trane U.S. Inc. / Installed by Others

Equipment Submittal Page 24 of 24

Field Installed Options - Part/Order Number Summary

This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job.

Product Family - Commercial Rooftop Air Conditioning Units (Midrange)

Item Tag(s) Qty Description Model Number

A1 RTU-1, RTU-2 2 70 Ton Packaged Industrial Rooftop Unit SXHLF704

Field Installed Option Description Part/Ordering Number

Remote human interface

Temperature sensor

Flat roof curb 0368-0165-0100

Duct mounted CO2 sensor BAYCO2K012A