Test Report issued under the responsibility of www.nemko.com This Test Report , when bearing the Nemko name and logo is only valid when issued by a Nemko laboratory, or by a laboratory having special agreement with Nemko. TEST REPORT IEC 6059822 Luminaires Part 2: Particular requirements: Section Two Recessed luminaires Report Reference No. ..................... : 170496 Date of issue..................................... : 20110331 Total number of pages ...................... 10 CB/CCA Testing Laboratory Name: Nemko A/S Phone: (+47) 22 96 03 30 Address ........................................... : P.O. Box 73 Blindern, N0314 Oslo, Norway Applicant’s name............................ : Nordtronic Aps Address ............................................ : Aalborgvej 86, DK9300 Sæby, Denmark Test specification: Standard ........................................... : IEC 6059822:1996+A1:1997 used in conjunction with IEC 605981:2008 Test procedure ................................. : CB Nonstandard test method…………..: N/A Test Report Form No. ..................... : IEC60598_2_2A Test Report Form(s) Originator ...................... : Intertek Semko AB Master TRF ................................................... : 200812 Copyright © 2008 IEC System for Conformity Testing and Certification of Electrical Equipment (IECEE), Geneva, Switzerland. All rights reserved. This publication may be reproduced in whole or in part for noncommercial purposes as long as the IECEE is acknowledged as copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from the reader's interpretation of the reproduced material due to its placement and context. If this Test Report Form is used by nonIECEE members, the IECEE/IEC logo and the reference to the CB Scheme procedure shall be removed. This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02. Test item description .....................: Recessed downligths Trade Mark ....................................... : Nordtronic Aps Manufacturer .................................... : Nordtronic Aps Model/Type reference ...................... : See page 3 Ratings ............................................. : See page 3

Upload: others

Post on 24-Mar-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: TEST REPORT IEC 60598.2.2 Luminaires Part 2: Particular ... · Test Report issued under the responsibility of This Test Report , when bearing the Nemko name and logo is only valid

Test Report issued under the responsibility of

www.nemko.com

This Test Report , when bearing the Nemko name and logo is only valid when issued by a Nemko laboratory,

or by a laboratory having special agreement with Nemko.

TEST REPORTIEC 60598-­2-­2Luminaires

Part 2: Particular requirements:Section Two – Recessed luminaires

Report Reference No...................... : 170496

Date of issue..................................... : 2011-­03-­31

Total number of pages ...................... 10

CB/CCA Testing Laboratory Name: Nemko A/S Phone: (+47) 22 96 03 30

Address ........................................... : P.O. Box 73 Blindern, N-­0314 Oslo, Norway

Applicant’s name............................ : Nordtronic Aps

Address ............................................ : Aalborgvej 86, DK-­9300 Sæby, Denmark

Test specification:

Standard ........................................... : IEC 60598-­2-­2:1996+A1:1997 used in conjunction with

IEC 60598-­1:2008

Test procedure ................................. : CB

Non-­standard test method…………..: N/A

Test Report Form No...................... : IEC60598_2_2A

Test Report Form(s) Originator ...................... : Intertek Semko AB

Master TRF ................................................... : 2008-­12

Copyright © 2008 IEC System for Conformity Testing and Certification of Electrical Equipment(IECEE), Geneva, Switzerland. All rights reserved.This publication may be reproduced in whole or in part for non-­commercial purposes as long as the IECEE is acknowledged as

copyright owner and source of the material. IECEE takes no responsibility for and will not assume liability for damages resulting from

the reader's interpretation of the reproduced material due to its placement and context.

If this Test Report Form is used by non-­IECEE members, the IECEE/IEC logo and the reference to the CB Scheme

procedure shall be removed.

This report is not valid as a CB Test Report unless signed by an approved CB Testing Laboratory and appendedto a CB Test Certificate issued by an NCB in accordance with IECEE 02.

Test item description .....................: Recessed downligths

Trade Mark ....................................... : Nordtronic Aps

Manufacturer ....................................: Nordtronic Aps

Model/Type reference ...................... : See page 3

Ratings ............................................. : See page 3

Page 2: TEST REPORT IEC 60598.2.2 Luminaires Part 2: Particular ... · Test Report issued under the responsibility of This Test Report , when bearing the Nemko name and logo is only valid

Page 2 of 10 Report No.:170496

TRF No. IEC60598_2_2A

Testing procedure and testing location:

CB Testing Laboratory:

Testing location/ address ..........................:

Associated CB Laboratory:

Testing location/ address ..........................:

Tested by (name + signature) .........: Tore Ledaal

Approved by (+ signature)...............: Per-­Tore Storelvmo

Testing procedure: TMP

Tested by (name + signature) .........:

Approved by (+ signature)...............:

Testing location/ address ..........................:

Testing procedure: WMT

Tested by (name + signature) .........:

Witnessed by (+ signature) .............:

Approved by (+ signature)...............:

Testing location/ address ..........................:

Testing procedure: SMT

Tested by (name + signature) .........:

Approved by (+ signature)...............:

Supervised by (+ signature) ............:

Testing location/ address ..........................:

Testing procedure: RMT

Tested by (name + signature) .........:

Approved by (+ signature)...............:

Supervised by (+ signature) ............:

Testing location/ address ..........................:

Page 3: TEST REPORT IEC 60598.2.2 Luminaires Part 2: Particular ... · Test Report issued under the responsibility of This Test Report , when bearing the Nemko name and logo is only valid

Page 3 of 10 Report No.:170496

TRF No. IEC60598_2_2A

Summary of testing:

Tests performed (name of test and test clause):

Heating test according Cl.12

Testing location:

Nemko ASGaustadalleen 300373 Oslo

Page 4: TEST REPORT IEC 60598.2.2 Luminaires Part 2: Particular ... · Test Report issued under the responsibility of This Test Report , when bearing the Nemko name and logo is only valid

Page 4 of 10 Report No.:170496

TRF No. IEC60598_2_2A

Test item particulars .............................................. :

Classification of installation and use ........................ :

Supply Connection ................................................... :

.................................................................................. :

.................................................................................. :

Possible test case verdicts:

-­ test case does not apply to the test object............. : N/A

-­ test object does meet the requirement................... : P (Pass)

-­ test object does not meet the requirement............. : F (Fail)

Testing..................................................................... :

Date of receipt of test item ....................................... :

Date (s) of performance of tests............................... :

General remarks:

The test results presented in this report relate only to the object tested.

This report shall not be reproduced, except in full, without the written approval of the Issuing testing

laboratory.

"(See Enclosure #)" refers to additional information appended to the report.

"(See appended table)" refers to a table appended to the report.

Throughout this report a comma (point) is used as the decimal separator.

Clause numbers between brackets refer to clauses in IEC 60598-­1

General product information:

Product group 1 – Models: 1651, 1652, 1653, 1654, 1657, 1661, 1662, 1663, 1664, 1681, 1682Product group 2 -­ Models: 1655, 1656, 1665, 1666Product group 3 – Models: 1671, 1672, 1673, 1674Product group 4 – Models: 1675, 1676

Heating tests only performed at one model in each group identified to be representative for theseries.

Numbers in red text and Bold in the tables below indicates that the temperature measured is overthe limits and deemed to fail this test.

Rosetta and Rina 230VRosetta and Rina 12VPerla 12VPerla 230V

Page 5: TEST REPORT IEC 60598.2.2 Luminaires Part 2: Particular ... · Test Report issued under the responsibility of This Test Report , when bearing the Nemko name and logo is only valid

Page 9 of 10 Report No.:170496

IEC 60598-­2-­2

Clause Requirement + Test Result -­ Remark Verdict

TRF No. IEC60598_2_2A

Type reference .....................................................: Nordtronic type 1662

Lamp used............................................................: 25W ALU

Lamp control gear used .......................................:

Mounting position of luminaire .............................: Recessed in ceiling, in box

14cmx15.5cm x 5.5 cm covered

in 200mm insulation

Supply wattage (W)..............................................: 26,25

Supply current (A) ................................................:

Calculated power factor .......................................:

Table: measured temperatures corrected for ta = 25 C:

-­ abnormal operating mode ..................................:

-­ test 1: rated voltage ...........................................:

-­ test 2: 1,06 times rated voltage or 1,05 times

rated wattage........................................................:

1,05 x 25W = 26,25W

-­ test 3: Load on wiring to socket-­outlet,

1,06 times voltage or 1,05 times wattage ............:

-­ test 4: 1,1 times rated voltage or 1,05 times

rated wattage........................................................:

Through wiring or looping-­in wiring loaded by a

current of A during the test ..................................:

temperature ( C) of part Clause 12.4 – normal Clause 12.5 – abnormal

test 1 test 2 test 3 limit test 4 limit

Top Enclosure 92,7 -­

Mounting surface between

mounting hole and

enclosure

77,4 90

Terminal 64,6 Depending

certificate of

terminal

Ceiling inside box 82,3 90

Separation of wires

Lampholder

125 Depending

certificate of

lampholder

Rosetta / Rina 230V - 63mm

90

180

Page 6: TEST REPORT IEC 60598.2.2 Luminaires Part 2: Particular ... · Test Report issued under the responsibility of This Test Report , when bearing the Nemko name and logo is only valid

Page 10 of 10 Report No.:170496

IEC 60598-­2-­2

Clause Requirement + Test Result -­ Remark Verdict

TRF No. IEC60598_2_2A

Type reference .....................................................: Nordtronic type 1672

Lamp used............................................................: MR16 20W ALU

Lamp control gear used .......................................: incorporated

Mounting position of luminaire .............................: Recessed in ceiling, in box

14cmx15.5cm x 5.5 cm covered

in 200mm insulation

Supply wattage (W)..............................................: 21

Supply current (A) ................................................:

Calculated power factor .......................................:

Table: measured temperatures corrected for ta = 25 C:

-­ abnormal operating mode ..................................:

-­ test 1: rated voltage ...........................................:

-­ test 2: 1,06 times rated voltage or 1,05 times

rated wattage........................................................:

1,05 x 20W = 21W

-­ test 3: Load on wiring to socket-­outlet,

1,06 times voltage or 1,05 times wattage ............:

-­ test 4: 1,1 times rated voltage or 1,05 times

rated wattage........................................................:

Through wiring or looping-­in wiring loaded by a

current of A during the test ..................................:

temperature ( C) of part Clause 12.4 – normal Clause 12.5 – abnormal

test 1 test 2 test 3 limit test 4 limit

Top Enclosure 82,9 -­

Mounting surface between

mounting hole and

enclosure

63 90

Terminal 62,2 Depending

certificate of

terminal

Transformer 56,6 85

Ceiling inside box 78 90

Separation of wires

Lampholder

105 Depending

certificate of

lampholder

Rosetta / Rina 12V - 63 mm

90

180

Page 7: TEST REPORT IEC 60598.2.2 Luminaires Part 2: Particular ... · Test Report issued under the responsibility of This Test Report , when bearing the Nemko name and logo is only valid

Page 5 of 10 Report No.:170496

IEC 60598-­2-­2

Clause Requirement + Test Result -­ Remark Verdict

TRF No. IEC60598_2_2A

ANNEX 2: temperature measurements, thermal tests of Section 12

Type reference .....................................................: Nordtronic type 1676

Lamp used............................................................: 20W ALU

Lamp control gear used .......................................: Incorporated controlgear

Mounting position of luminaire .............................: Recessed in ceiling directly

covered in 200mm insulation.

Supply wattage (W)..............................................: 21

Supply current (A) ................................................:

Calculated power factor .......................................:

Table: measured temperatures corrected for ta = 25 C: P

-­ abnormal operating mode ..................................:

-­ test 1: rated voltage ...........................................:

-­ test 2: 1,06 times rated voltage or 1,05 times

rated wattage........................................................:

1.05 x 20 = 21W

-­ test 3: Load on wiring to socket-­outlet,

1,06 times voltage or 1,05 times wattage ............:

-­ test 4: 1,1 times rated voltage or 1,05 times

rated wattage........................................................:

Through wiring or looping-­in wiring loaded by a

current of A during the test ..................................:

temperature ( C) of part Clause 12.4 – normal Clause 12.5 – abnormal

test 1 test 2 test 3 limit Test 4 limit

Separation of wires in

Lampholder

120.6 Depending

certificate of

lampholder

Mounting surface between

mounting hole and

enclosure

78.8 90

Top of enclosure 86,3 90

Surface of transformer 53 85

Perla 12V - 65 mm

250

Page 8: TEST REPORT IEC 60598.2.2 Luminaires Part 2: Particular ... · Test Report issued under the responsibility of This Test Report , when bearing the Nemko name and logo is only valid

Perla 65 mm

GU10/C 25W 220-240 V

Perla 230V - 65mm