the new switchgear standard
TRANSCRIPT
-
7/28/2019 The new switchgear standard
1/8
Siemens AGPower Transmission and DistributionMedium Voltage DivisionMozartstr. 31c91052 ErlangenGermany
www.siemens.com/energy
For questions on power transmission anddistribution, please contact our CustomerSupport Center, 24 hours a day.Tel.: +49 180 / 524 70 00Fax: +49 180 / 524 24 71(Subject to charge: e.g. 12 ct/min)E-mail: [email protected]/energy-support
Subject to change without prior notice
Order no. E50001-U229-A282-X-7600
Printed in Germany
Dispo 30403
GB 06612 101976 08064.
The inormation in this document contains general descriptions o the technical eatures, which may not always be available.
An obligation to provide the respective perormance eature shall exist only i expressly agreed in the terms o contract.
-
7/28/2019 The new switchgear standard
2/8
Power Transmission and Distribution
We are ready: IEC 62271-200The new switchgear standard
-
7/28/2019 The new switchgear standard
3/8
Standards for all
Switchgear are important nodal points
in modern power distribution. Corre-
spondingly important is their reliable
unctioning, a clearly deined switch-
ing behavior according to speciied
parameters as well as the protection o
personnel and protection against oper-
ational interruptions when an overload
occurs.
The International Electrotechnical
Commission (IEC) has taken up thetask o developing the required speci-
ications, their worldwide standard-
ization and urther development. The
same applies to IEC 62271-200 the
new standard or medium-voltage
switchgear.
As one o the irst manuacturers,
Siemens has implemented these
requirements and already oers the
complete product range o air-insu-
lated and gas-insulated switchgear
today, type-tested according toIEC 62271-200.
2
IEC 62271-200
IEC 62271-200
-
7/28/2019 The new switchgear standard
4/8
IEC 60298 or our decades this abbre-
viation was the decisive actor or the type
testing o metal-enclosed switchgear. In
the meantime there are tens o thousands
o switchgear panels o the primary and
secondary distribution level based on this
standard in use certied according to
the mandatory part o the standard and,
i required, according to optional tests.
The passing o the ollowing tests was
obligatory in order to identiy switchgear as
type-tested:
Dielectric test to veriy the insulation
level o the switchgear (tests with rated
lightning impulse withstand voltage and
rated short-duration power requency
withstand voltage with the specied
values depending on the respective rated
voltage).
Temperature rise tests to veriy the
current carrying capacity with rated normal
currents.
Peak and short-time withstand current
tests to veriy the dynamic and thermal
current carrying capacity o the main and
earth circuits; the tests are perormed with
rated peak short-circuit current or rated
short-circuit making current or rated short-
time current or rated short-circuit breaking
current.
Switching capacity test to veriy the
making/breaking capacity o the installed
switchgear.
Mechanical unction test to veriy the
mechanical unctions and interlocks.
Degree o protection tests to veriy the
protection against electric shock and oreign
objects.
Pressure and strength tests to veriy
the gas tightness and pressure resistance or
gas-lled switchgear.
There is also the possibility o voluntarily
certiying switchgear or resistance to inter-nal arc aults and or personal protection.
Manuacturers and operators can select the
criteria which are relevant to them rom the
ollowing six criteria and have them tested.
Criterion 1:
Doors and covers must not open.
Criterion 2:
Parts o the switchgear must not fy o.
Criterion 3:
Holes must not develop in the external parts
o the enclosure.
Criterion 4:
Vertical indicators must not ignite.
Criterion 5:
Horizontal indicators must not ignite.
Criterion 6:Earth connections must remain eective.
In order to guarantee sae access to the
individual switchgear components, e.g.the
incoming cable, without isolating the busbar,
the IEC 60298 standard dierentiates bet-
ween three types o compartmentalization
that serve exclusively as protection against
electric shock.
Metal-clad switchgear: Division o the
switchgear panel into our compartments
(busbar compartment, switching-devicecompartment, connection compartment
and low-voltage compartment); partitions
between the compartments made o sheet
steel, ront plate made o sheet steel or
insulating material.
Compartmented switchgear: Division o
the switchgear panel same as or metal-clad
switchgear, but with the partitions between
the individual compartments made o insu-
lating material.
Cubicle-type switchgear: All other typeso construction that do not meet the above
eatures o the metal-clad or compartmented
designs.
In this context, access to the then common
minimum-oil-content circuit-breakers or
maintenance work without longer opera-
tional interruptions was o prime importance
because o the limited number o operating
cycles. Thereore, with switchgear in metal-
clad or compartmented design, the busbar in
the busbar compartment and the incom-
ing cable in the connection compartmentcould remain in operation. With a cubicle-
type design, the incoming cable had to be
isolated, but the busbar itsel could remain in
operation.
Retrospective
3
-
7/28/2019 The new switchgear standard
5/8
Although the old IEC 60298 standard
was very helpul, in time it was super-
seded by the technological progress.
Above all, the appearance o mainte-
nance-ree vacuum circuit-breakers,
with operating cycles ar exceeding
the normal number, made requent
access to this circuit-breaker no longer
o prime importance.
The vacuum arc-quenching principle
is technologically so superior to otherarc-quenching principles that the
circuit-breaker can be ixed-mounted
again. This resulted in the irst-time
use o gas insulation with the impor-
tant eatures o climatic independence,
compactness and maintenance-ree de-
sign. However, both technologies the
vacuum arc-quenching principle and
gas insulation were not adequately
taken into account in the existing
standard.
Thereore, at the end o the nine-ties, the responsible IEC committees
decided on the reormulation o the
switchgear standard, which inally
came into eect as IEC 62271-200 in
November 2003. At the same time the
old IEC 60298 standard was withdrawn
without any transition period.
Four key eatures are o special note with
the new IEC 62271-200 standard:
1. Changed dielectric requirements
According to IEC 60298, two disruptive
discharges were permitted in a series o
15 voltage impulses or the test with rated
lightning impulse withstand voltage. Ac-
cording to the new standard, the series
must be extended by another ve voltage
impulses i a disruptive discharge has oc-
curred during the rst 15 impulses. This canlead to a maximum o 25 voltage impulses,
whereas the maximum number o permis-
sible disruptive discharges is still two.
2. Increased demands on the circuit-
breaker and earthing switch
In contrast to the previous standard, the
switching capacity test o both switching
devices is no longer carried out as a pure
device test. Instead, it is now mandatory
to carry out the test in the corresponding
switchgear panel. The switching capacity
may get a negative infuence rom thedierent arrangement o the switchgear
with contact arms, moving contacts,
conductor bars, etc.
For this reason, the test duties T100s and
T100a rom the IEC 62271-100 standard
are stipulated or the test o the circuit-
breaker inside the switchgear panel.
3. New partition classifcation
The new partition classes PM (partitions
metallic = partitions and shutters made
o metal) or PI (partitions nonmetallic =partitions and shutters made o insulat-
ing material) now apply with respect to
the protection against electric shock dur-
ing access to the individual components.
The assignment is no longer according
to the constructional description (metal-
clad, compartmented or cubicle-type
design), but according to operator-related
criteria (Tables 1 and 2).
4. Stricter internal arc classifcation
Signicantly stricter changes have also
been implemented here. The energy fow
direction o the arc supply, the maximum
number o permissible panels with the
test in the end panel and the dependency
o the ceiling height on the respective
panel height have been redened. In
addition, the ve ollowing new criteria
must always be completely ullled (no
exceptions are permitted):
1) Covers and doors remain closed.
Limited deormations are accepted.
2) No ragmentation o the enclosure,
no projection o small parts above
60 g weight.
3) No holes in the accessible sides up
to a height o 2 meters.
4) Horizontal and vertical indicators do not
ignite due to the eect o hot gases.
5) The enclosure remains connected to
its earthing parts.
For the internal arc classication osubstations with and without control
aisle, the testing o the substation with
installed switchgear is mandatory in the
new IEC 62271-202 standard. The clas-
sication o the substation is only valid
in combination with the switchgear used
or the test. The classication cannot be
transerred to a combination with an-
other switchgear type as each switchgear
behaves dierently in the case o an in-
ternal arc (pressure relie equipment with
dierent cross-sections and pickup pres-
sures, dierent arcing conditions becauseo dierent conductor geometries).
New specications new challengesOverview o IEC 62271-200
4
-
7/28/2019 The new switchgear standard
6/8
Loss o servicecontinuity category
When an accessible compartment othe switchgear is opened:
Constructional design
LSC 1 then the busbar and thereorethe complete switchgear must beisolated.
No partitions within the panel, nopanel partition walls to adjacentpanels.
LSC 2 LSC 2A then the incoming cable must beisolated. The busbar and the adjacentswitchgear panels can remain inoperation.
Panel partition walls and i solatingdistance with compartmentaliza-tion to the busbar.
LSC 2B then the incoming cable, thebusbar and the adjacent switchgearpanels can remain in operation.
Panel partition walls and i solatingdistance with compartmentaliza-tion to the busbar and to the cable.
The notation IAC A FLR, I and t contains the abbreviations or the ollowing values:
IAC Internal Arc Classiication
ADistance between the indicators 300 mm, i.e. installation in rooms with access orauthorized personnel, closed electrical service location
FLR Access rom the ront (F), rom the sides (L = lateral) and rom the rear (R)
I Test current = rated shor t-circuit breaking current (in kA)
t Internal arc duration (in seconds)
Type o accessibilityto a compartment
Access eatures
Interlock-based Opening or normal operation andmaintenance, e.g. use replacement.
Access is controlled by theconstruction o the switchgear,i.e. integrated interlocks preventimpermissible opening.
Procedure-based Opening or normal operation andmaintenance, e.g. use replacement.
Access control via a suitable pro-cedure (work instruction o theoperator) combined with a lockingdevice (lock).
Tool-based Opening not or normal operation ormaintenance, e.g. cable testing.
Access only with tool or opening,special access procedure(instruction o the operator).
Nonaccessible Opening not possible / not intended or operator,opening can destroy the compartment.
This applies generally to the gas-illed compartments o gas-insulatedswitchgear. As the switchgear is maintenance-ree and climate-indepen-dent, access is neither required nor possible.
Table 2
Overview o the characteristic values
The IAC classication describes a success-
ul test. It results rom the denition o
the degree o accessibility, the possibili-
ties o arrangement inside a room, as
well as the test current and test time
(Table 3).
Medium-voltage switchgear in the pri-
mary and secondary distribution level is
generally classied with degree o acces-
sibility A. This means they are intendedor use in rooms that are only accessible
to authorized personnel (closed electrical
service locations).
Switchgear that is accessible by general
public has the degree o accessibility B
(distance o indicators = 100 mm) and
polemounted switchgear has the degree
o accessibility C (indicators below a
tower in an area o 3 x 3 m).
Consequences or operators
With the new IEC 62271-200 standard,the ollowing conditions must be satised
by the switchgear operators:
Already existing switchgear can still be
operated in accordance with IEC 60298.
However, new switchgear must ulll the
IEC 62271-200 standard in order to avoid
any resulting legal disadvantages. A situ-
ation which has a number o advantages.
For example, the comparison and evalu-
ation o switchgear eatures is now more
transparent. But also rom an economic
point o view, they are an investment inthe uture.
Table 1
Table 3
5
-
7/28/2019 The new switchgear standard
7/86
With intensive development work and
comprehensive tests, Siemens has al-
ready implemented the perormance
eatures requested by IEC 62271-200 at
an early stage. As one o the irst man-
uacturers, we oer the entire product
range o air- and gas-insulated switch-
gear or medium-voltage applications
in primary and secondary distribution
systems today type-tested according
to the new IEC 62271-200 standard.
A greater margin or your saety
Not only that: the more stringent require-
ments o the dielectric type tests have
been implemented without exception.
All switching capacity tests or the various
circuit-breakers and earthing switches
were perormed in installed condition,
i.e. inside the switchgear panel with the
associated arrangement o the conducting
path, contacts, etc. This means or you as
the operator: One hundred percent cer-
tainty that this combination o switchgearand switchgear panel unctions reliably.
All switchgear series were also tested or
the internal arc classication in accordance
with the new standard. The maximum
permissible number o test objects (gener-
ally two or three panels) as well as the
changed direction o energy fow o the arc
supply signicantly increased the demands
on the switchgear panels. All switchgear
certied in accordance with IEC 62271-
200 satises all ve criteria required or
the internal arc test without exception.
Siemens medium-voltage switchgear
thereore corresponds to the IAC A FLR
classication or short-circuit currents up
to 50 kA (depending on the system type)
and short-circuit times up to one second.
Ready or the uture with Siemens
With the ulllment o the new IEC 62271-
200 standard, all our switchgear types
represent the latest state o development
in technology, saety and reliability.
Without exception, Siemens switchgear
ullls the internal arc classication as vital
proo o the personal saety. Our switch-
gear thereore also meets the require-
ments o CAPIEL the European associa-
tion o national switchgear manuacturerassociations: This is now a type test and
not anymore subject o agreement be-
tween manuacturer and user.
An investment in the switchgear technol-
ogy made by Siemens is a protable invest-
ment in the uture.
With the successully veried internal arc
classication, IAC A FLR up to 50 kA and
one second arc duration, our switchgear
oers maximum possible personal protec-
tion. Our type-tested series also entirelyulll the specications o IEC 62271-200
in all aspects. In addition, they guarantee
the highest possible degree o operational
reliability and thereore an extremely low
ailure rate.
Air- and gas-insulated switchgearfrom Siemens in accordance withIEC 62271-200We are ready to make you ready as well
-
7/28/2019 The new switchgear standard
8/8
Overviewo
fSiemenss
witchgear
*Maximump
ossibleIA
Cclassiication
Distribution
level
Insula-
tion
Design
Lossoservicecon-
tinuity
Partition
class
Internalarcclassif-
cation*
S
witchgear
t
ype
Busbarsystem
Voltage
(kV)
Short-circuit
current(kA)
1s
3s
Ratedcurrent,
busbar(A)
Ratedcurrent,
eeder(A)
Primary
Gas-
insulated
Extendable
LSC2B(panels
withoutHVHRCuses)
LSC2A(panelswith
HVHRCuses)
PM
IACAFLR31,5kA,1s
NXPLUSC
Single
15
24
31,5
25
31,5
25
2500
2500
2500
2000
LSC2B(panels
withoutHVHRCuses)
LSC2A(panelswith
HVHRCuses)
PM
IACAFLR25kA,1s
NXPLUSC
Double
24
25
25
2500
1250
LSC2B
PM
IACAFLR31,5kA,1s
NXPLUS
Single
40,5
31,5
31,5
2500
2500
LSC2B
PM
IACAFLR31,5kA,1s
NXPLUS
Double
36
31,5
31,5
2500
2500
LSC2B
PM
IACAFL40kA,1s
8DA10
Single
40,5
40
40
4000
2500
LSC2B
PM
IACAFL40kA,1s
8DB10
Double
40,5
40
40
4000
2500
Air-
insulated
Extendable
LSC2B
PM
IACAFLR40kA,1s
NXAIR
Single
12
40
40
3150
3150
LSC2B
PM
IACAFLR40kA,1s
NXAIR
Double
12
40
40
3150
3150
LSC2B
PM
IACAFLR25kA,1s
NXAIRM
Single
24
25
25
2500
2500
LSC2B
PM
IACAFLR25kA,1s
NXAIRM
Double
24
25
25
2500
2500
LSC2B
PM
IACAFLR50kA,1s
NXAIRP
Single
15
50
50
4000
4000
LSC2B
PM
IACAFLR50kA,1s
NXAIRP
Double
15
50
50
4000
4000
LSC2B
PM
IACAFLR31,5kA,1s
SIMOPRIME
Single
17,5
31,5
31,5
3150
3150
LSC2A
PM
IACAFLR25kA,1s
8BT1
Single
24
25
25
2000
2000
LSC2B
PM
IACAFL31,5kA,1s
8BT2
Single
36
31,5
31,5
2500
2500
LSC1
PM
IACAFL16kA,1s
8BT3
Single
36
16
16
1250
1250
Secondary
Gas-
insulated
Non-
extendable
LSC2B(panels
withoutHVHRCuses)
LSC2A(panelswith
HVHRCuses)
PM
IACAFL21kA,1s
8DJ10
Single
17,5 2
4
25
20
20
20
630
630
630
630
LSC2B(panels
withoutHVHRCuses)
LSC2A(panelswith
HVHRCuses)
PM
IACAFL21kA,1s
8DJ20
Single
17,5 2
4
25
20
20
20
630
630
630
630
Extendable
LSC2B(panels
withoutHVHRCuses)
LSC2A(panelswith
HVHRCuses)
PM
IACAFLR21kA,1s
8DH10
Single
17,5 2
4
25
20
20
20
1250
1250
630
630
Air-
insulated
Extendable
LSC2B(panels
withoutHVHRCuses)
LSC2A(panelswith
HVHRCuses)
PM
IAC
AF
LR
20
kA,
1s
SIMOSEC
Single
17,5 2
4
25
20
11,5
20
1250
1250
1250
1250