transformer protn. areva
TRANSCRIPT
Transformer Protection
P:\applics\Powerpoint Cabinet\Training Courses\APPS1
Alan WixonSenior Applications Engineer
> Transformer Protection - January 20043 3
Transformer Fault Categories
1. Winding and terminal faults
2. Sustained or uncleared external faults
3. Abnormal operating conditions such as overload, overvoltage and overfluxing
4. Core faults
> Transformer Protection - January 20044 4
- “Clock Face” numbers refer to position of low voltage phase-neutral vector with respect to high voltage phase neutral vector
- Line connections made to highest numbered winding terminal available
- Line phase designation is same as windingExample 1 : Dy 11 Transformer
B1B2 b2b1
a2a1A1A2
C1C2 c2c1
Question : How to connect windings ?
High Voltage
Windings
Low VoltageWindings
A PhaseWindings
B PhaseWindings
C PhaseWindings
Transformers Connections
> Transformer Protection - January 20045 5
1. Draw Phase-Neutral Voltage Vectors
30°
A
C B
a
c
b
Line Designation
Transformers Connections
> Transformer Protection - January 20046 6
2. Draw Delta Connection
A
C B
a
c
b
Transformers Connections
> Transformer Protection - January 20047 7
3. Draw A Phase Windings
A
C B
a
c
b
a2
a1
A2
A1
Transformers Connections
> Transformer Protection - January 20048 8
4. Complete Connections (a)
A
C B
a
c
b
a2
a1
A2
A1
C1
C2
B1 B2
b2b1c1
c2
Transformers Connections
> Transformer Protection - January 20049 9
4. Complete Connections (b)
c1 c2
b1 b2
a1 a2 a
b
c
A
B
CC2 C1
B2 B1
A2 A1
Transformers Connections
> Transformer Protection - January 200410 10
Phase displacement0Group 1
Phase displacement180Group 2
Lag phase displacement30Group 3
Lead phase displacement30Group 4
Yy0Dd0Zd0Yy6Dd6Dz6Yd1Dy1Yz1
Yd11Dy11Yz11
Transformer Vector Groups
> Transformer Protection - January 200411 11
Overcurrent & Earthfault Protection
> Transformer Protection - January 200412 12
11kV Distribution Transformers Typical Fuse Ratings
Transformer rating Fuse
kVA
100
200
300
500
1000
5.25
10.5
15.8
26.2
52.5
16
25
36
50
90
3.0
3.0
10.0
20.0
30.0
Full loadcurrent (A)
Ratedcurrent (A)
Operating time at3 x rating(s)
> Transformer Protection - January 200413 13
Transformer Overcurrent Protection
Requirements
Fast operation for primary short circuits
Discrimination with downstream protections
Operation within transformer withstand
Non-operation for short or long term overloads
Non-operation for magnetising inrush
> Transformer Protection - January 200414 14
Use of Instantaneous Overcurrent Protection
Source HVLV
50
51
50 set to 1.2 - 1.3 x through fault level
> Transformer Protection - January 200415 15
Concerns relay response to offset waveforms(DC transient)
Definition
I1 - I2I2
x 100
I1 = Steady state rmspick up current
I2 = Fully offset rms pickup current
I1 I2D.C
.
Transient Overreach
> Transformer Protection - January 200416 16
Earthfault on Transformer Winding
: 3 ratio turns Effective
. 3
. current Fault : at fault a For
. x 3
current,primary Thus, values load full to current E/F limits Resistor
F.L.2
F.L.
F.L.P
χ
χχχ
χχ
=
Ι=Ι=
Ι=Ι
secondary C.T. then r,transforme of current loadfull on based is side)primary (on ratio C.T. If
3 circuit
2χ=
1 p.u. turns√3 p.u. turns
xIP
PRR IFProtective
Relay
> Transformer Protection - January 200417 17
Overcurrent Relay Setting > IF.L.
χIF
51
OvercurrentRelay
If as multipleof IF.L.1.00.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
Star Side
Delta Side
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0χ p.u..
Overcurrent Relay Setting > IF.L.
> Transformer Protection - January 200418 18
χIF
109
8
7
6
5
4
3
2
1
Star Side
Delta Side
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0χ
p.u..
If as multipleof IF.L.
51
OvercurrentRelay
Overcurrent Relay Sensitivity to Earth Faults
> Transformer Protection - January 200419 19
χ
IF
IP IN
109
8
7
654321
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0χ
p.u..
If as multipleof IF.L.
IN
IP
IF
Overcurrent Relay Sensitivity to Earth Faults
> Transformer Protection - January 200420 20
Star Winding REF
ProtectedZone
REF
Relay only operates for earthfaults within protected zone.Uses high impedance principle.Stability level : usually maximum through fault level of
transformer
> Transformer Protection - January 200421 21
Restricted E/F Protection Low Voltage Windings (1)
A B C N
LV restricted E/Fprotection tripsboth HV and LV breaker
Recommended setting : 10% rated
> Transformer Protection - January 200422 22
Restricted E/F Protection Low Voltage Windings (2)
A B C N
LV restricted E/F protection trips both HV and LV breakerRecommended setting : 10% rated
> Transformer Protection - January 200423 23
Delta Winding Restricted Earth Fault
Delta winding cannot supply zero sequence current to system
Stability : Consider max LV fault level Recommended setting : less than 30% minimum
earth fault level
Protected zoneREF
Source
> Transformer Protection - January 200424 24
High Impedance Principle (2)
Maximum voltage across relay circuit, Vs = If (RCT + 2RL)
To limit current through relay to < Is the relay impedance Rrelay > Vs/Is
ProtectedCircuit
ZM RCT
RL
ZMRCT
RLIF
VS
RL RL
IS
R
> Transformer Protection - January 200425 25
Non-Linear Resistors (Metrosils)
During internal faults the high impedance relay circuit constitutes an excessive burden to the CT’s.A very high voltage develops across the relay circuit and the CT’s which can damage the insulation of CT’s, secondary wiring and relay.Magnitude of peak voltage VP is given by an approximate formula (based on experimental results)
VP = 2 √2VK (VF - VK)Where VF = If (RCT + 2RL + RSTAB + Rrelay)Metrosil required if VP > 3kV
> Transformer Protection - January 200426 26
High Impedance Circuit Arrangement
Metrosil Characteristic
V = C I β
Suitable values of C & β chosen based on :(1) Max secondary current under fault conditions(2) Relay setting voltage
I
RST
VSVM
RR
> Transformer Protection - January 200427 27
Unrestricted Earthfault Protection (1)
51 515151N
- Provides back-up protection for system- Time delay required for co-ordination
> Transformer Protection - January 200428 28
Unrestricted Earthfault Protection (2)
- Can provide better sensitivity(C.T. ratio not related to full load current)(Improved “effective” setting)
- Provides back up protection for transformer and system
51 515151N51N
> Transformer Protection - January 200429 29
ANT1
Bus Section
T2
415 VoltSwitchboard
CB
Parallel Transformers (LV)
> Transformer Protection - January 200430 30
ANT1
Bus SectionOpen
T2
415 Volt Switchboard
CB
51N
51N
Parallel Transformers - CT In Earth
> Transformer Protection - January 200431 31
ANT1
Bus SectionOpen
T2
415 Volt Switchboard
CB
51N
51N
Parallel Transformers - CT In Earth & Neutral
> Transformer Protection - January 200432 32
ZG1289C
Bus section
415 volt switchboard
T1 N A B C
F2
F1
Will maloperate if bus section is openfor fault at F1
No maloperation for fault at F2 (but setting must begreater than load neutral current)
T2
Parallel Transformers - Residual Connection
> Transformer Protection - January 200433 33
Differential Protection
> Transformer Protection - January 200434 34
Differential Protection
Overall differential protection may be justified for larger transformers (generally > 5MVA).
Provides fast operation on any windingMeasuring principle :
Based on the same circulating current principle as the restricted earth fault protectionHowever, it employs the biasing technique, to maintain stability for heavy thro’ fault current
Biasing allows mismatch between CT outputs.It is essential for transformers with tap changing facility.Another important requirement of transformer differential protection is immunity to magnetising in rush current.
> Transformer Protection - January 200435 35
Biased Differential Scheme
Bias = Differential (or Spill) CurrentMean Through Current
BIASBIAS I2I1
OPERATEI1 - I2
DifferentialCurrent
OPERATE
RESTRAIN
Mean Thro Current
I1 + I22
I1 - I2
> Transformer Protection - January 200436 36
Differential Protection
LV
R
HV
PROTECTED ZONE
Correct application of differential protection requires CT ratio and winding connections to match those of transformer.CT secondary circuit should be a “replica” of primary system.Consider :
(1) Difference in current magnitude(2) Phase shift(3) Zero sequence currents
> Transformer Protection - January 200437 37
Earthfault on Transformer Winding
I
DifferentialRelaySetting = IS
χ
protected not is ng windiof 59% Thus59% i.e.
operation for 20% 3
then 20%, If e.g.
operation,relay For
3
2S
S
2
>
>=Ι
Ι>Ι
=Ι
χ
χ
χ
Differential Relay Setting % of Star Winding Protected
10% 58%20% 41%30% 28%40% 17%50% 7%
> Transformer Protection - January 200438 38
Differential Connections
P1 P2 A2 A1 a1 a2 P2 P1
A B C
> Transformer Protection - January 200439 39
Use of Interposing CT
RR
R
P1 P2 A2 A1 a1 a2 P2 P1
S2 S1 P1 P2
Interposing CT provides : Vector correction Ratio correction Zero sequence compensation
S1 S2 S1 S2
> Transformer Protection - January 200440 40
S2S1
P1P2A1A2 a2a1P2
15MVA66kV / 11kV150/5 800/5
P1
Dy1
S1S2
Given above : Need to consider -(1) Winding full load current(2) Effect of tap changer (if any)(3) C.T. polarities
Assuming no tap changerFull load currents :- 66kV : 131 Amp = 4.37 Amps secondary
11kV : 787 Amp = 4.92 Amps secondaryHowever, require 11kV C.T.’s to be connected in ∆Thus, secondary current = √3 x 4.92 = 8.52A
∴ RATIO CORRECTION IS REQUIRED
Use of Interposing CT - Example
> Transformer Protection - January 200441 41
It is usual to connect 11kV C.T.’s in and utilise a / interposting C.T. (this method reduces lead VA burden on the line C.T.’s).Current from 66kV side = 4.37 AmpThus, current required from winding of int. C.T. = 4.37 Amp.Current input to winding of int. C.T. = 4.92 Amp.∴ Required int. C.T. ratio = 4.92 / 4.37 = 4.92 / 2.52
√3May also be expressed as : 5 / 2.56
RR
R
P1 P2 A2 A1 a1 a2 P2 P1150/5
S1 S2 S2 S1
800/5
4.37A 4.92AS1 S2 P1 P2
(5)(2.56)
Use of Interposing CT - Example
> Transformer Protection - January 200442 42
25MVA11KV
63MVA132KV
1600/5300/5
50MVA33KV
1000/5
4.59
2.88
10.33
2.88
5.51
5
5
All interposing C.T. ratio’s refer to common MVA base (63MVA)
Three Winding Transformer - Example
> Transformer Protection - January 200443 43
Combined Differential and Restricted Earthfault Protection
To differential relayS2
S1P1P2
REFS2
S1P1
P2
S2S1P1 P2a2a1A1A2
> Transformer Protection - January 200444 44
Integral Vectorial and Ratio Compensation
Power transformer
Differentialelement
KBCH Relay
Virtual interposing CT
Vectorialcorrection
Ratiocorrection
Virtual interposing CT
> Transformer Protection - January 200445 45
Vector Group Correction
HV VectorCorLV1 VectorCorLV2 VectorCor
Yy0, Yd1, Yd5, Yy6, Yd7, Yd11, Ydy00 , -30 , -150 , 180 , +150 , +30 , 0
87
KBCH
Yy0 Yd110 +30
Dy1 (-30 )
> Transformer Protection - January 200446 46
In Zone Earthing Transformer
P2P1a2a1
A2A1 P1P2
S1S2
P2P1S1S2 T1T2
> Transformer Protection - January 200447 47
Transformer Magnetising Characteristic
TwiceNormal
Flux
NormalFlux
NormalNo Load Current
No Load Current at Twice Normal
Flux
> Transformer Protection - January 200448 48
Typical Magnetising Inrush Waveforms
A
C
B
> Transformer Protection - January 200449 49
Transformer Differential Protection
Appears on one side of transformer only
Seen as fault by differential relay
Normal steady state magnetising current is less than relay setting
Transient magnetising inrush could cause relay to operate
Effect of magnetising current
> Transformer Protection - January 200450 50
Transformer Differential Protection (2)
Solution 1 : 2nd (and 5th) harmonic restraint
Makes relay immune to magnetising inrush
Slow operation may result for genuine transformer faults if CT saturation occurs
> Transformer Protection - January 200451 51
Transformer Differential Protection (3)
Inhibits relay operation during magnetising inrush
Operate speed for genuine transformer faults unaffected by significant CT saturation
Solution 2 : Gap measurement technique
Effect of magnetising inrush
> Transformer Protection - January 200452 52
Protection of Auto-Transformer by High Impedance Differential Relays (1)
(a) Earth Fault Scheme
A
B
C
High impedancerelay
87
> Transformer Protection - January 200453 53
Protection of Auto-Transformer by High Impedance Differential Relays (2)
(b) Phase and Earth Fault Scheme
A
B
Cabc
87 87 87
n
> Transformer Protection - January 200454 54
Additional Protection
> Transformer Protection - January 200455 55
Inter-Turn Fault
Nominal turns ratioFault turns ratioCurrent ratio
- 11,000 / 240- 11,000 / 1- 1 / 11,000
Requires Buchholz relay
CTE
Shortedturn
Load
> Transformer Protection - January 200456 56
100
80
60
40
20
05 10 15 20 25
10
8
6
4
2
Fault current inshort circuited turns
Primary input currentFault current(multiples ofrated current)
Primary current(multiples ofrated current)
Turn short-circuited (percentage of winding)
Interturn Fault Current / Number of Turns Shorted
> Transformer Protection - January 200457 57
Buchholz Relay Installation
5 x internal pipediameter (minimum)
3 x internal pipediameter (minimum)
Transformer
3 minimum
Oil conservator
Conservator
> Transformer Protection - January 200458 58
Buchholz Relay
PetcockCounter balanceweight
Oil level
From transformer
Aperture adjuster
Deflector plateDrain plug
Trip bucket
To oilconservator
Mercury switch
Alarm bucket
> Transformer Protection - January 200459 59
Overfluxing
- Generator transformers- Grid transformers
Usually only a problem during run-up or shut down, but can be caused by loss of load / load shedding etc.
Flux O ∝ Vf
Effects of overfluxing :- Increase in mag. Current- increase in winding temperature- increase in noise and vibration- overheating of laminations and metal parts (caused by stray flux)
Protective relay responds to V/f ratioStage 1 - lower A.V.R.Stage 2 - Trip field
> Transformer Protection - January 200460 60
ΦV f α K
Trip and alarm outputs for clearing prolonged overfluxing
Alarm : Definite time characteristic to initiate corrective action
Trip : IDMT or DT characteristic to clear overfluxing condition
Settings
Pick-up 1.5 to 3.0i.e. 110V x 1.05 = 2.3150Hz
DT setting range 0.1 to 60 seconds
Volts / Hertz Protection
> Transformer Protection - January 200461 61
Enables co-ordination with plant withstand characteristics
1000
100
10
11 1.1 1.2 1.3 1.4 1.5 1.6
M =
Operatingtime (s)
V HzSetting
K = 63K = 40K = 20K = 5K = 1
t = 0.8 + 0.18 x K (M - 1)2
Volts / Hertz Characteristics
> Transformer Protection - January 200462 62
Effect of Overload on Transformer Insulation Life
90 100 110 120 130 140Hot spot temp C
0.1
1.0
10
100
Relativerateof usinglife
With ambient of 20 C.Hot spot rise of 78 isdesign normal.A further rise of 6 Cdoubles rate ofusing life.
98
80
> Transformer Protection - January 200463 63
Typical Schemes
> Transformer Protection - January 200464 64
Up to 1MVA
51
3.3kV
200/5 P1215051
1MVA3.3/0.44kV1500/5
1500/564
P120
MCAG14
N50N
51N
> Transformer Protection - January 200465 65
1 - 5MVA
11kV
P1215051
5MVA11/3.3kV1000/5
1000/564
P120
MCAG14
51N
MCAG1464
3.3kV
> Transformer Protection - January 200466 66
Above 5MVA
33KV
P1415051200/5
P12010MVA33/11KV 51
N 87600/5 P631
MCAG1464
600/55/5A
> Transformer Protection - January 200467 67
Worked Examples
> Transformer Protection - January 200468 68
REF Calculations
> Transformer Protection - January 200469 69
Restricted Earth Fault Protection
1MVA(5%)
11000V 415V
1600/1RCT = 4.8Ω
Vk =330V
80MVA
RS1600/1
RCT = 4.8Ω MCAG14IS = 0.1 Amp
2 Core 7/0.67mm (7.41Ω/km)100m Long
Calculate :1) Setting voltage (VS)2) Value of stabilising
resistor required3) Peak voltage
developed by CT’s for internal fault
> Transformer Protection - January 200470 70
Solution :
1 P.U.1 4
I1
4
I2
4
I0
Sequence Diagram
Earth fault calculation :-Using 80MVA base
Source impedance = 1 p.u.Transformer impedance = 0.05 x 80 = 4 p.u.
1Total impedance = 14 p.u.∴ I1 = 1 = 0.0714 p.u.
14Base current = 80 x 106
√3 x 415= 111296 Amps
∴ IF = 3 x 0.0714 x 111296= 23840 Amps (primary)= 14.9 Amps (secondary)
> Transformer Protection - January 200471 71
Solution :(1) Setting voltage
VS = IF (RCT + 2RL)Assuming “earth” CT saturates,
RCT = 4.8 ohms2RL = 2 x 100 x 7.41 x 10-3 = 1.482 ohms∴ Setting voltage = 14.9 (4.8 + 1.482)
= 93.6 Volts(2) Stabilising Resistor (RS)
RS = VS - 1IS IS
2 Where IS = relay current setting∴ RS = 93.6 - 1 = 836 ohms
0.1 0.12
> Transformer Protection - January 200472 72
Solution :
3) Peak voltage = 2√2 √VK (VF - VK)VF = 14.9 x VS = 14.9 x 936 = 13946 Volts
IS
For ‘Earth’ CT, VK = 330V∴ VPEAK = 2√2 √330 (13946 - 330)
= 6kVThus, metrosil voltage limiter will be required.
> Transformer Protection - January 200473 73
ICT’s
> Transformer Protection - January 200474 74
CT Ratio Mismatch Correction - Modern Approach
87
200/1
0.875A 1.31 Amps
I = 175A I = 525A 400/1L L33kV : 11kV
10 MVA
KBCH
1.14 0.76
HV Ratio CorLV1 Ratio CorLV2 Ratio Cor
0.05 to 2 in steps of 0.01
1A 1A
> Transformer Protection - January 200475 75
Stability for External Earth Faults - Modern Approach
Selection of suitable vector correction factor
87
Dy11 (+30 )
Yy00
Yd1-30 87
Dy11
Yy00
Yy00
> Transformer Protection - January 200476 76
Current Distributions
> Transformer Protection - January 200477 77
Current Distributions
RR
R
P1 P2 A2 A1 a1 a2 P2 P1
S2 S1 P1 P2
Connections check : Arbitary current distribution
S1 S2 S1 S2
> Transformer Protection - January 200478 78
Current Distributions
RR
R
P1 P2 A2 A1 a1 a2 P2 P1
S2 S1 P1 P2
Add winding current :-
S1 S2 S1 S2
> Transformer Protection - January 200479 79
Current Distributions
RR
R
P1 P2 A2 A1 a1 a2 P2 P1
S2 S1 P1 P2
Complete primary distribution :-
S1 S2 S1 S2
> Transformer Protection - January 200480 80
Current Distributions
RR
R
P1 P2 A2 A1 a1 a2 P2 P1
S2 S1 P1 P2
Complete secondary distribution :-
S1 S2 S1 S2