Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71 · 2002

Upload: vuongkiet

Post on 08-Mar-2018

239 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker SwitchgearTypes NXAIR, NXAIR M and NXAIR Pup to 24 kV, Air-Insulated

Medium-VoltageSwitchgear

Catalog HA 25.712003

Supersedes:Catalog HA 25.71 · 2002

Page 2: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

2 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

Page

© Siemens AG 2003

Versions

Withdrawable circuit-breakerswitchgear types NXAIR, NXAIR Mand NXAIR P are factory-assembled,type-tested, metal-enclosed andmetal-clad switchgear for indoorinstallation according to IEC 60 298/VDE 0670 Part 6.

Typical uses

refer to page 4

R-HA

25-3

10ep

s

Application

Versions 2Typical uses 3 and 4Ratings 4

Requirements

Security of investment 5Cost-efficiency 5Service friendliness 5

Technical Data

Electrical data, dimensions 6 and 7Room planning 7

Product Range

NXAIR 8 and 9NXAIR M 10 and 11NXAIR P 12 and 13

Design

Basic panel design,operation, compartments 14 to 19

Components

NXACT vacuum circuit-breaker 20 and 21Other switching devices 22Current transformers, post insulators 23Low-voltage equipment 24

Standards

Standards, specifications,guidelines 25 to 27

Notes

NXAIR panel

Maximum ratings12 kV / 25 kA / 2500 A

NXAIR M panel

Maximum ratings15 kV / 31.5 kA / 2500 A17.5 kV / 25 kA / 2500 A24 kV / 25 kA / 2500 A

NXAIR P panel

Maximum ratings15 kV / 50 kA / 4000 A

R-HA

25-3

12ep

s

R-HA

25-3

11ep

s

Contents Application

Page 3: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

3Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

Application

ApplicationIndustry

ApplicationIndustry

ApplicationPublic powersupply system

NXAIR M switchgear

R-HA

25-3

26ep

s

R-HA

25-3

27ep

s

R-HA

25-3

08ep

s

Typical uses

R-HA25-328 eps

Page 4: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

4 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

NXAIR, NXAIR M and NXAIR P circuit-breakerswitchgear types are used in transformerand switching substations, e.g.

ApplicationPublic power supply system

■ Power supply companies

ApplicationIndustry

■ Power stations

■ Cement industry

■ Automobile industry

■ Iron and steel works

■ Rolling mills

■ Mining industry

■ Textile, paper and food industries

■ Chemical industry

■ Petroleum industry

■ Pipeline installations

■ Offshore installations

■ Electrochemical plants

■ Petrochemical plants

■ Shipbuilding industry

■ Diesel power plants

■ Emergency power supply installations

■ Lignite open-cast mines

■ Traction power supplies

Application

Typical uses Ratings

Electrical data (maximum values) of the NXAIR family

Ratings Rated values(max.)

Switchgear up to 7.2 kV

Rated voltage 7.2 kV

Rated frequency 50/60 Hz

Rated short-duration power-frequency withstand voltage 20 kV

Rated lightning impulse withstand voltage 60 kV

Rated short-time withstand current, 3 s 50 kA

Rated peak withstand current at 50 Hz 125 kA

Rated short-circuit breaking current 50 kA

Rated short-circuit making current at 50 Hz 125 kA

Rated normal current of busbar 4000 A

Rated normal current of feeders 4000 A

Switchgear up to 12 kV

Rated voltage 12 kV

Rated frequency 50/60 Hz

Rated short-duration power-frequency withstand voltage 28 kV

Rated lightning impulse withstand voltage 75 kV

Rated short-time withstand current, 3 s 50 kA

Rated peak withstand current at 50 Hz 125 kA

Rated short-circuit breaking current 50 kA

Rated short-circuit making current at 50 Hz 125 kA

Rated normal current of busbar 4000 A

Rated normal current of feeders 4000 A

Switchgear up to 15 kV

Rated voltage 15 kV

Rated frequency 50/60 Hz

Rated short-duration power-frequency withstand voltage 35 kV

Rated lightning impulse withstand voltage 95 kV

Rated short-time withstand current, 3 s 50 kA

Rated peak withstand current at 50 Hz 125 kA

Rated short-circuit breaking current 50 kA

Rated short-circuit making current at 50 Hz 125 kA

Rated normal current of busbar 4000 A

Rated normal current of feeders 4000 A

Switchgear up to 17.5 kV

Rated voltage 17.5 kV

Rated frequency 50/60 Hz

Rated short-duration power-frequency withstand voltage 38 kV

Rated lightning impulse withstand voltage 95 kV

Rated short-time withstand current, 3 s 25 kA

Rated peak withstand current at 50 Hz 63 kA

Rated short-circuit breaking current 25 kA

Rated short-circuit making current at 50 Hz 63 kA

Rated normal current of busbar 2500 A

Rated normal current of feeders 2500 A

Switchgear up to 24 kV

Rated voltage 24 kV

Rated frequency 50/60 Hz

Rated short-duration power-frequency withstand voltage 50 kV

Rated lightning impulse withstand voltage 125 kV

Rated short-time withstand current, 3 s 25 kA

Rated peak withstand current at 50 Hz 63 kA

Rated short-circuit breaking current 25 kA

Rated short-circuit making current at 50 Hz 63 kA

Rated normal current of busbar 2500 A

Rated normal current of feeders 2500 A

Page 5: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

5Siemens HA 25.71· 2003

* IP3XD for the enclosure,IP2X for the compartmentalization

Requirements

Security of investment Cost-efficiency Service friendliness

Modular structure

• Module compartment and/orconnection compartment canbe replaced

• Replacement of bushing-type current transformerspossible from front

• Low-voltage compartmentcan be replaced

• Flexibile operation aswithdrawable or truck-typeswitchgear

Bushing-type currenttransformer

• Current measurement, postinsulator function, compart-mentalization, capacitivevoltage indication integratedin one component

• Selective shutdown of anarc up to 31.5 kA in the con-nection compartment of apanel in combination withpressure-resistant compart-mentalization without anyadditional measures

NXACT

• Maintenance-free vacuumcircuit-breaker

• Circuit-breaking, disconnect-ing and earthing (operatingmechanism) integrated inone component

SIPROTEC 4

• Multifunction protection relaySIPROTEC 4 with integratedprotection, control, commu-nications, operating andmonitoring functions

• Can be integrated in overallprocess control system(SICAM)

Reliability

• Type and routine-tested

• Standardized, NC productionprocesses

• Quality assurance in accord-ance with DIN EN ISO 9001

• More than 300,000 air-insulated switchgear panelsin operation worldwide

Personal safety

• All switching operations canbe performed with high-voltage door closed

• Standard degree of protectionIP3XD * according toIEC 60 529 / VDE 0470 Part 1

• Panels tested for internalarcs up to 50 kA according toIEC 60 298, Appendix AA /VDE 0670 Part 6, Appendix AA

• Metallic, positively drivenshutters protect against acci-dental contact with live parts

• Mechanical switch positionindicators on panel front forcircuit-breaker, movable partand earthing switch

• Logical interlocks preventmaloperation

• Option: Verification of safeisolation from supply withhigh-voltage door closed,by means of a voltage detec-tion system according toIEC 61 243-5 / VDE 0682Part 415

• Earthing of feeders by meansof make-proof earthingswitches

Operating safety

• Operation of all switching,disconnecting and earthingfunctions from panel front

• Unambiguous assignment ofaccess openings and controlelements to mechanicalswitch position indicators

• Mechanical switch positionindicators integrated in mimicdiagram

• User-friendly height of accessopenings, control elementsand switch position indicatorson high-voltage door, as wellas secondary equipment indoor of low-voltage compart-ment

Flexibility

• Wall-standing or free-standing arrangement

• Cable connection from frontor rear

• Available as truck-type orwithdrawable switchgear

• Optional left or right-handarrangement of hinges

– of high-voltage doors– of doors of low-voltage

compartments

• Extension of existing switch-gear at both ends withoutmodification of panels

• Replacement of bushing-typecurrent transformers possiblefrom front

• Secondary multiratio forcurrent transformers

• Screw-type fixed contacts onbushing-type current trans-formers can be easilyreplaced from front (frommodule compartment)

Re-availability

• Easy replacement of com-partments thanks to self-supporting, modular andbolted construction ofcompartments

• Replacement of modulecompartment and/or connec-tion compartment possible

• Option: Bushing-type currenttransformers offer selectiveshutdown for an arc up to31.5 kA in the connectioncompartment of a panel

• Busbar voltage transformerand make-proof earthingswitch

– up to 31.5 kA in a separateadditional compartment withpressure-resistant partition tobusbar compartment

– for 40 kA and 50 kA inmetering panel

• Confinement of an internalarc up to 31.5 kA within thesame compartment

• Pressure relief upwards foreach compartment

• Option: Pressure-resistantfloor cover

• Internal control cables run inmetallic cable ducts

• Cable testing without isolat-ing the busbar assured byseparately opening shuttersof module compartment

Maintenance-free design

• Vacuum circuit-breakersmaintenance-free within therange of the permissibleoperating cycles

• Switchgear maintenanceintervals > 10 years

Operation

• Operation of all switching,disconnecting and earthingfunctions from panel front

• Self-explanatory controlsymbols

• Mechanical switch positionindicators for all functions

Page 6: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

6 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

Electrical data, dimensions

Dimensionsin mm

H1H2

TB

HA25

-268

6a e

ps

HA25

-268

7b e

ps

H1H2

TB

H3

Dimensionsin mmAll panel types

Width B Standard 800

At 24 kV / 2500 A 1000

For vacuum contactor panel 400

Height H1 With standard low-voltage compartment 2200

H2 – With mounted air guides (standard)– With high low-voltage compartment– With natural ventilation

2550

H3 With additional compartment for busbar fittings 2770

Depth T Single busbar cubicle-type 2)metal-clad

14541554

Vacuum contactor panel 1650

Double busbar in cubicle-type 2)back-to-back arrangement metal-clad

29583158

Technical Data

* Depending on rated current of HV HRC fuses installed

** Higher value on request

NXAIR Dimensions NXAIR M Dimensions

NXAIR Ratings

Rated

voltage kV 7.2 12

frequency Hz 50 50

short-duration power-frequency kVwithstand voltage

20 28 **

lightning impulse withstand voltagekV 60 75

short-circuit breaking current max. kA 25 25

short-time withst. current, 3 s max. kA 25 25

short-circuit making current max. kA 63 63

peak withstand current max. kA 63 63

normal current of busbar max. A 2500 2500

normal current of feeders:

with circuit-breaker max. Awith switch max. A

2500800 *

2500800 *

All panel types

Width B For all panels 800

Height H1 Standard 2000

H2 – With highlow-voltage compartment

– With natural ventilation– With additional compart-

ment for busbar fittings

2350

Depth T For all panels 1350

NXAIR M Ratings

Rated

voltage kV 7.2 12 15 17.5 24

frequency Hz 50/60 50/60 50/60 50/60 50/60

short-duration power-frequency kVwithstand voltage

20 28 35 38 50

lightning impulse withstand voltage kV 60 75 95 95 125

short-circuit breaking current max. kA 31.5 31.5 31.5 25 25

short-time withst. current, 3 s max. kA 31.5 31.5 31.5 25 25

short-circuit making current 1) max. kA 80 80 80 63 63

peak withstand current 1) max. kA 80 80 80 63 63

normal current of busbar max. A 2500 2500 2500 2500 2500

normal current of feeders:

with circuit-breaker max. Awith switch max. Awith vacuum contactor max. A

2500800 *400 *

2500800 *–

2500800 *–

2500800 *–

2500800 *–

* Depending on rated current of HV HRC fuses installed

1) Values for 50 Hz

2) For 24 kV only

Page 7: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

7Siemens HA 25.71· 2003

aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa a aaaaaaaaaaaaaa32³100

32³100

THA25

-268

9c e

ps

1250

1)³

50

BB

Single-row arrangement (plan view)for single-busbar switchgear

For dimensions B (width) and T (depth) refer to table on page 6

1) For panel replacement: Control aisle W 1410 mm

NXAIR

Single-row arrangement (plan view)for single-busbar switchgear

For dimensions B (width) and T (depth) refer to table on page 6

2) For panel replacement: Control aisle W 1700 mm

For back-to-back arrangement and face-to-face arrangement, thesame room dimensions apply as for single-row arrangement.

For back-to-back arrangement, a 1200 mm control aisle isrequired on the left or on the right of the switchgear.

Single-row arrangement (plan view)for single-busbar switchgear

For dimensions B1, B2 (width) and T (depth) refer to table on the left

3) For panel replacement: Control aisle W 1800 mm

For back-to-back arrangement and face-to-face arrangement, thesame room dimensions apply as for single-row arrangement.

For back-to-back arrangement, a 1200 mm control aisle isrequired on the left or on the right of the switchgear.

T

HA25

-268

8c e

ps

H1

B1B2

H2H3

Dimensionsin mmAll panel types (except vacuum contactor panel)

Width B1 w 2000 A (standard) 800

B2 > 2000 A (with panel ventilation) 1000

Height H1 With standard low-voltage compartment 2225

H2 With top-mounted pressure relief duct 2550

H3 With forced ventilation (4000 A) 2710

Depth T Single busbar 1635

Double busbar inback-to-back arrangement

3320

NXAIR Maaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa a aaaaaaaaaaaaaaaaaaaaaaaaa32³100

32³100

T

HA25

-269

0c e

ps

1350

2)³

50

BB

NXAIR Paaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa a aaaaaaaaaaaaaaaaaaaaaaaaa32³100

32³100

T

HA25

-269

1c e

ps

1450

3)³

50

B1, B2B1, B2

Room planning (room height W 2800 mm)

NXAIR P Dimensions

NXAIR P Ratings

Rated

voltage kV 7.2 12 15

frequency Hz 50/60 50/60 50/60

short-duration power-frequency kVwithstand voltage

20 28 35

lightning impulse withstand voltage kV 60 75 95

short-circuit breaking current max. kA 50 50 50

short-time withst. current, 3 s max. kA 50 50 50

short-circuit making current 1) max. kA 125 125 125

peak withstand current 1) max. kA 125 125 125

normal current of busbar max. A 4000 4000 4000

normal current of feeders:

with circuit-breaker max. Awith switch max. Awith vacuum contactor max. A

4000800 *400 *

4000800 *400 *

4000800 *–

* Depending on rated current of HV HRC fuses installed

1) Values for 50 Hz

Vacuum contactor panel

Width B1 Standard 400

Height H1 With standard low-voltage compartment 2225

H2 With top-mounted pressure relief duct 2550

Depth T Single busbar 1650

Technical Data

Electrical data, dimensions

Page 8: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

8 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

HA25

-266

0c e

ps

and/or

and/or

and/or

and/or

or

or

or

and/or

HA25

-265

9a e

ps

and/or

and/or

and/or

and/or

and/or

or

and/or

or

or

or

or

HA25

-265

8a e

ps

and/or

and/or

and/or

and/or

and/or

or

and/or

or

or

or

or

Circuit-breaker panel Disconnecting panel

For other components forbusbar and connectioncompartments refer topage 15

1) The details refer toconventional RXSsingle-core sealingends for XLPE cables orother makes with similardimensions.

HA25

-269

2a e

ps

and/or

and/or

and/or

and/or

Product Range

NXAIR Panels

Switch panel Spur panel

Components

HA25

-269

3a e

ps

Make-proofearthing switch

Busbar connection(bars only)

Panel ventilationas natural ventilation

Capacitive voltagedetection system

Cable sealing ends 1)max. 4 x 500 mm2

per phase

Bar feeder

HV HRC fuse

NXACT vacuumcircuit-breakermodule

Disconnecting moduleor fixed-mountedconnection

Vacuum switch module

Current transformer

Current transformerin run of busbar

Voltage transformer

Page 9: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

9Siemens HA 25.71· 2003

HA25

-266

1a e

ps and/or

or

or

or

HA25

-266

2a e

ps

and/or

and/or

and/or

or

or

or

and/or

Bus sectionalizer (mirror-image installation also possible)

Withdrawablepanel

Bus riserpanel

Metering panel

NXAIR Panels

For other components forbusbar and connectioncompartments refer topage 15

Components

HA25

-269

4 ep

s

Current transformer

Current transformerin run of busbar

Voltage transformer

Make-proofearthing switch

Busbar connection(bars only)

Panel ventilationas natural ventilation

Capacitive voltagedetection system

HV HRC fuse

NXACT vacuumcircuit-breakermodule

Disconnecting moduleor fixed-mountedconnection

Withdrawablevoltage transformerwith primary fuses

Withdrawablevoltage transformer

Product Range

Page 10: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

10 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

NXAIR M Panels

HA25

-266

8a e

ps

and/or

and/or

and/or and/or

or

or

HA25

-266

5a e

ps

and/or

and/or

and/or

and/or

or

or

or

or

and/or

HA25

-266

4a e

ps

and/or

and/or

and/or

and/or

or

or

or

and/or

or

and/or

HA25

-266

9a e

ps

and/or

and/or

and/or

or

Circuit-breaker panel Disconnecting panel Switch panel

Components

HA25

-269

5 ep

s

Panel ventilationas natural ventilation

Capacitive voltagedetection system

Cable sealing ends 1)max. 4 x 500 mm2

per phase

Bar feeder

HV HRC fuse

Vacuum contactormodule with controltransformer andHV HRC fuses

NXACT vacuumcircuit-breakermodule

Disconnecting module

Vacuum switch modulewith HV HRC fuses

Vacuum contactormodulewith HV HRC fuses

Current transformer

Voltage transformer

Make-proofearthing switch

Busbar connection(bars only)

For other components forbusbar and connectioncompartments refer topage 17

1) The details refer toconventional RXSsingle-core sealingends for XLPE cables orother makes with similardimensions.

Product Range

Vacuum contactor panel(7.2 kV)

Page 11: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

11Siemens HA 25.71· 2003

Panels fordouble-busbarapplications

Double-busbar switchgear con-sists of components from therange of single-busbar panels.

It can have the followingdesigns:

• Face-to-face arrangement

• Back-to-back arrangement

Face-to-face arrangement

• Panels from the range ofsingle-busbar switchgear(circuit-breaker panel, bussectionalizer and meteringpanel)

• The two switchgear rows areinterconnected by means ofcables or bars beneath thepanels

• Bus coupler consisting of:– Circuit-breaker panel– Disconnecting panel

Back-to-back arrangement

• Panels from the range ofsingle-busbar switchgear(circuit-breaker panel, bussectionalizer and meteringpanel)

• The two switchgear rows areinterconnected by means ofbars within the panels

• Bus coupler consisting of:– Circuit-breaker panel with

current and voltagetransformers

– Disconnecting panel, withoptional current transformers

Note

Double-busbar switchgearwith top-mounted busbardisconnector unit on request

HA25

-267

0a e

ps

and/or

and/or

and/or

or

or

and/or

or

and/or

and/or

and/or

or

or

or

NXAIR M Panels

HA25

-266

6a e

ps and/or

or

For other components forbusbar and connectioncompartments refer topage 17

Components

HA25

-269

6 ep

s

Current transformer

Voltage transformer

Make-proofearthing switch

Busbar connection(bars only)

Panel ventilationas natural ventilation

Capacitive voltagedetection system

HV HRC fuse

NXACT vacuumcircuit-breakermodule

Disconnecting module

Product Range

Bus sectionalizer (mirror-image installation also possible) Metering panel

Withdrawablepanel

Bus riserpanel

Page 12: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

12 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

NXAIR P Panels

HA25

-267

4a e

psand/or

and/or

orand/or

and/or

HA25

-267

2a e

ps

and/or

and/or

and/or

or

or

and/or

and/or

HA25

-267

5a e

ps and/or

or

and/or

and/or

Components

HA25

-269

7 ep

s

Capacitive voltagedetection system

Cable sealing ends 1)max. 6 x 500 mm2

per phase 2)

Bar feeder

HV HRC fuse

Vacuum contactormodule with controltransformer andHV HRC fuses

Current transformer

Voltage transformer

Make-proofearthing switch

Busbar connection(bars only)

HA25

-267

3a e

ps

and/or

and/or

and/or

or

or

and/or

and/or

Product Range

Circuit-breaker panel Disconnecting panel Switch panel

NXACT vacuumcircuit-breakermodule

Disconnecting moduleor fixed-mountedconnection

Vacuum switch modulewith HV HRC fuses

Vacuum contactormodulewith HV HRC fuses

For other components forbusbar and connectioncompartments refer topage 19

1) The details refer toconventional RXSsingle-core sealingends for XLPE cables orother makes with similardimensions.

2) Exception:Switch panel

Vacuum contactor panel(7.2 kV,12 kV)

Page 13: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

13Siemens HA 25.71· 2003

NXAIR P Panels

Panels fordouble-busbarapplications

Double-busbar switchgear con-sists of components from therange of single-busbar panels.

It can have the followingdesigns:

• Face-to-face arrangement

• Back-to-back arrangement

Face-to-face arrangement

• Panels from the range ofsingle-busbar switchgear(circuit-breaker panel, bussectionalizer and meteringpanel)

• The two switchgear rows areinterconnected by means ofcables or bars beneath thepanels

• Bus coupler consisting of:– Circuit-breaker panel– Disconnecting panel

Back-to-back arrangement

• Panels from the range ofsingle-busbar switchgear(circuit-breaker panel, bussectionalizer and meteringpanel)

• The two switchgear rows areinterconnected by means ofbars within the panels

• Bus coupler consisting of:– Circuit-breaker panel

with current and voltagetransformers

– Disconnecting panel, withoptional current transformers

HA25

-267

9c e

ps

and/or

and/or

orand/or

HA25

-267

6a e

ps or

For other components forbusbar and connectioncompartments refer topage 19

Components

HA25

-269

8 ep

s

Busbar connection(bars only)

Capacitive voltagedetection system

NXACT vacuumcircuit-breakermodule

Withdrawablevoltage transformerwith primary fuses

Withdrawablevoltage transformer

Product Range

Bus sectionalizer (mirror-image installation also possible) Metering panel

Withdrawablepanel

Bus riserpanel

Current transformer

Voltage transformer

Make-proofearthing switch

Page 14: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

14 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

Circuit-breaker panel12 kV, 1250 A

A Module compartment

B Busbar compartment

C Connection compartment

D Vacuum circuit-breaker module

E Low-voltage compartment

1 Door of low-voltage compartment

2 Protection device

3 Option: Capacitive voltage detection systemfor feeder and busbar

4 High-voltage door to module compartment

5 Door knob for opening the high-voltage door

7 Mechanical switch position indicator andaccess opening for movable part

8 “Closing spring charged” indicator andoperating cycle counter

9 Mechanical switch position indicator forswitching device

10 “ON/OFF” pushbuttons for switching device

11 Mechanical switch position indicatorand access opening for make-proofearthing switch

12 Mimic diagram

Operation at the panel

Features

• Integrated mechanicalswitch position indicators inthe mimic diagram

• CLOSED/OPEN switch posi-tion indicators for circuit-breaker, movable part andearthing switch can be ob-served without opening thehigh-voltage door

• Unambiguous assignment ofaccess openings and controlelements to the correspond-ing switch position indicators

• All switching operationspossible with high-voltagedoor closed

• Ergonomically favorableheight for all controlelements

• Option: Verification ofsafe isolation from supply –of feeder or busbar – bymeans of a capacitivevoltage detection system onthe panel front

Interlocks

• Interlocking conditions aresatisfied according toIEC 60 298 / VDE 0670 Part 6

• Earthing switch can only beoperated with movable partin disconnected position

• Movable part can only bemoved with circuit-breaker“OPEN” and earthing switch“OPEN”

• Switchgear module can onlybe inserted in a panel withmovable part in disconnectedposition

• Mechanical coding on theswitchgear module preventsinsertion of similar switch-gear modules for lower ratednormal currents into panelswith higher rated normal cur-rents

• Option: Interlocking ofhigh-voltage door againstmovable part

• Option: Electromagneticinterlocks

Basic panel design (example)

1234

1

2

3

4

7

8

9

10

12

HA25

-261

1c e

ps

14

21

15

16

17

18

19

20

26

23

24

25

28

29

E

D

A

C

B

225

11

14 Pressure relief duct

15 Busbars

16 Bushing-type insulator

17 Bushing-type current transformer

18 Make-proof earthing switch

19 Cable connection for 4 cables per phase

20 Cable sealing ends

21 Cable bracket

22 Low-voltage plug connector

23 Movable part

24 Combined operating and interlocking unitfor circuit-breaker, movable part andearthing switch

25 Vacuum interrupters

26 Contact system

28 Earthing busbar

29 Option: Truck

Design

NXAIR Panel design, operation

Page 15: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

15Siemens HA 25.71· 2003

Design

NXAIR Compartments

Module compartment

• Enclosure made ofsendzimir-galvanizedsheet-steel

• Pressure relief upwards

• Panel front powder-coatedwith epoxy resin

• Shutter operating mecha-nisms separately for

– Busbar compartment– Connection compartment

• High-voltage door pressure-resistant in the event ofinternal arcs in the panel

• Pressure-resistant partitionsto connection and busbarcompartments

• Metallic ducts on the side forlaying control cables

• Option: Test sockets forcapacitive voltage detectionsystem

• Automatically couplinglow-voltage plug connectorfor connection of switchgearmodules to auxiliary voltagecircuits

• Module compartment to ac-commodate components forimplementing various panelversions with:

– NXACT vacuumcircuit-breaker module

– Disconnecting module– Vacuum switch module– Metering module

Busbar compartment

• Enclosure made ofsendzimir-galvanizedsheet-steel

• Pressure relief upwards

• Option: Busbar transversepartition between panels

• Busbars made of flat copper,bolted from panel to panel

– For rated normal currentsup to 2500 A

– Option: Insulated busbars

• Pressure-resistant partitionsto connection and modulecompartments, pressure-resistant rear wall

• Separately opening shutters

• Bushing-type insulators forsupporting busbars and foraccommodating upper fixedcontacts for switchgearmodule

• Option: Max. 3 bushing-typecurrent transformers

• Option: Coupling electrodefor capacitive voltage detec-tion system

Additional compartments(optional) for busbar fittings

• Separate, pressure-resistantcompartment above busbarcompartment

• Bolted onto busbarcompartment

• Pressure-resistant wall withbushings betweenadditional compartment andbusbar compartment

• Separate pressure relief foradditional compartment,upwards via pressure reliefflaps

• Options: Possibility of in-stalling the following compo-nents (but not for panels withnatural ventilation):

– Voltage transformers– Current transformers in run

of busbar– Surge arresters– Busbar earthing switch– Busbar connection

(bars only)

Connection compartment

• Enclosure made ofsendzimir-galvanizedsheet-steel

• Pressure relief upwardsthrough rear pressure reliefduct

• Suitable for connection of:– Bars– Single-core cables– Three-core cables

• Pressure-resistant partitionsto module and busbar com-partments

• Separately opening shuttersto permit cable testing

• Earthing busbar

• Option: Installation of bush-ing-type insulators instead ofbushing-type current trans-formers

• Connection from front or rear

• Option: Pressure-resistantfloor cover

• Option: Deep bottom pan,e.g. for connection of three-core cables or cable-typecurrent transformers

Components at the panelconnection (optional)

• Single-core XLPE cablesup to max. 4 x 500 mm2

per phase

• Plug-in sockets for shock-proof cable plugs, includingfloor cover

• Bars in flat copper withbushings including floorcover or as fully-insulatedbars including floor cover

• Bushing-type insulators ormax. 3 bushing-type currenttransformers

• Coupling electrode forcapacitive voltage detectionsystem

• Voltage transformers– Cast-resin insulated– Max. 3 x 1-pole or 2 x 2-pole– Fixed-mounted, without

primary fuses

• Make-proof earthing switches– With manual operating

mechanism– Option: With motor operat-

ing mechanism integrated inswitchgear module

– In addition to standard inter-locking of earthing switch/movable part, optionallylockable or with electromag-netic interlock

• Surge arresters or limiters– Surge arresters for protecting

the switchgear against exter-nal overvoltages

– Surge limiters for protectingconsumers against switchingovervoltages

Page 16: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

16 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

Basic panel design (example)Operation at the panel

Features

• Integrated mechanical switchposition indicators in themimic diagram

• CLOSED/OPEN switch posi-tion indicators for circuit-breaker, movable part andearthing switch can be ob-served without opening thehigh-voltage door

• Unambiguous assignment ofaccess openings and controlelements to the correspond-ing switch position indicators

• All switching operationspossible with high-voltagedoor closed

• Ergonomically favorableheight for all controlelements

• Option: Verification ofsafe isolation from supply –of feeder or busbar – bymeans of a capacitivevoltage detection systemon the panel front

Interlocks

• Interlocking conditions aresatisfied according toIEC 60 298 / VDE 0670 Part 6

• Earthing switch can only beoperated with movable partin disconnected position

• Movable part can only bemoved with circuit-breaker“OPEN” and earthing switch“OPEN”

• Switchgear module can onlybe inserted in a panel withmovable part in disconnectedposition

• Coding on the switchgearmodule prevents insertion ofsimilar switchgear modulesfor lower rated normal cur-rents into panels with higherrated normal currents

• Interlocking of high-voltagedoor against movable part

• Option: Electromagneticinterlocks

A Module compartment

B Busbar compartment

C Connection compartment

D Vacuum circuit-breaker module

E Low-voltage compartment

HA25

-264

1c e

ps

1234

A

C

B

D

E1

2

3

4

5

7

8

9

12

30

14

21

15

16

17

18

19

20

26

23

24

25

28

29

22

27

30

10

11

Circuit-breaker panel Metal-clad version

HA25

-264

2b e

ps

E

A

C

B

D

21

15

16

17

18

19

20

26

23

24

25

28

29

22

301 Door of low-voltage compartment

2 Protection device

3 Option: Capacitive voltage detection systemfor feeder and busbar

4 High-voltage door to module compartment

5 Door knob for opening the high-voltage door

7 Mechanical switch position indicator andaccess opening for movable part

8 “Closing spring charged” indicator andoperating cycle counter

9 Mechanical switch position indicator forswitching device

10 “ON/OFF” pushbuttons for switching device

11 Mechanical switch position indicatorand access opening for make-proofearthing switch

12 Mimic diagram

14 Pressure relief duct

15 Busbars

16 Bushing-type insulator

17 Bushing-type current transformer

18 Make-proof earthing switch

19 Cable connection for 4 cables per phase

20 Cable sealing ends

21 Cable bracket

22 Low-voltage plug connector

23 Movable part

24 Combined operating and interlocking unitfor circuit-breaker, movable part andearthing switch

Cubicle-type version (feature: common module andconnection compartment)

NXAIR M Panel design, operation

Design

28 Earthing busbar

29 Option: Truck

30 Air guide

25 Vacuum interrupters

26 Contact system

27 Lower partition

Page 17: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

17Siemens HA 25.71· 2003

NXAIR M Compartments

Design

Connection compartment

• Enclosure made ofsendzimir-galvanizedsheet-steel

• Pressure relief upwards:– In metal-clad panels through

rear pressure relief duct– In cubicle-type panels

through modulecompartment

• Suitable for connection of:– Bars– Single-core cables– Three-core cables

• Pressure-resistant partitionsto module and busbar com-partments

• Cubicle-type version withoutlower partition to modulecompartment for 24 kV

• Separately opening shuttersto permit cable testing

• Earthing busbar

• Connection from front or rear

• Option: Installation of bush-ing-type insulators instead ofbushing-type current trans-formers

• Option: Pressure-resistantfloor cover

• Option: Deep bottom pan,e.g. for connection ofthree-core cables or cable-type current transformers

Components at the panelconnection (optional)

• Single-core XLPE cablesup to max. 4 x 500 mm2

per phase

• Bars in flat copper withbushings including floorcover or as fully-insulatedbars including floor cover

• Bushing-type insulatorsor max. 3 bushing-typecurrent transformers

• Coupling electrode forcapacitive voltage detectionsystem

• Voltage transformers– Cast-resin insulated– Max. 3 x 1-pole– Fixed-mounted, without

primary fuses

• Make-proof earthing switches– With manual operating

mechanism– Option: With motor operat-

ing mechanism integrated inswitchgear module

– In addition to standard inter-locking of earthing switch/movable part, optionallylockable or with electromag-netic interlock

• Surge arresters or limiters– Surge arresters for protecting

the switchgear againstexternal overvoltages

– Surge limiters for protectingconsumers against switchingovervoltages

Module compartment

• Enclosure made ofsendzimir-galvanizedsheet-steel

• Pressure relief upwards

• Panel front powder-coatedwith epoxy resin

• Shutter operating mecha-nisms separately for

– Busbar compartment– Connection compartment

• High-voltage door pressure-resistant in the event ofinternal arcs in the panel

• Pressure-resistant partitionsto connection and busbarcompartments

• Metallic ducts on the side forlaying control cables

• Option: Test sockets forcapacitive voltage detectionsystem

• Low-voltage plug connectorfor connection of switchgearmodules to auxiliary voltagecircuits

• Module compartment toaccommodate componentsfor implementing variouspanel versions with:

– NXACT vacuumcircuit-breaker module

– Disconnecting module– Vacuum contactor module– Vacuum switch module– Metering module

• Cubicle-type version withoutlower partition to connectioncompartment for 24 kV

Busbar compartment

• Enclosure made ofsendzimir-galvanizedsheet-steel

• Pressure relief upwards

• Option: Busbar transversepartition between panels

• Busbars made of flat copper,bolted from panel to panel

– For rated normal currents upto 2500 A

– Option: Insulated busbars

• Pressure-resistant partitionsto connection and modulecompartments, pressure-resistant rear wall

• Separately opening shutters

• Bushing-type insulators forsupporting busbars and foraccommodating upper fixedcontacts for switchgearmodule

• Option: Max. 3 bushing-typecurrent transformers

• Option: Coupling electrodefor capacitive voltagedetection system

Additional compartments(optional) for busbar fittings

• Separate, pressure-resistantcompartment above busbarcompartment

• Bolted onto busbarcompartment

• Pressure-resistant wall withbushings betweenadditional compartment andbusbar compartment

• Separate pressure relief foradditional compartment,upwards via pressure reliefflaps

• Options: Possibility of in-stalling the following compo-nents (but not for panels withnatural ventilation):

– Voltage transformers– Make-proof busbar earthing

switch with manual operatingmechanism

– Busbar connection(bars only)

Page 18: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

18 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

Operation at the panel

Features

• Integrated mechanical switchposition indicators in themimic diagram

• CLOSED/OPEN switch posi-tion indicators for circuit-breaker, movable part andearthing switch can be ob-served without opening thehigh-voltage door

• Unambiguous assignment ofaccess openings and controlelements to the correspond-ing switch position indicators

• All switching operationspossible with high-voltagedoor closed

• Ergonomically favorableheight for all controlelements

• Option: Verification ofsafe isolation from supply –of feeder or busbar – bymeans of a capacitivevoltage detection systemon the panel front

Interlocks

• Interlocking conditions aresatisfied according toIEC 60 298 / VDE 0670 Part 6

• Earthing switch can only beoperated with movable partin disconnected position

• Movable part can only bemoved with circuit-breaker“OPEN” and earthing switch“OPEN”

• Switchgear module can onlybe inserted in a panel withmovable part in disconnectedposition

• Mechanical coding on theswitchgear module preventsinsertion of similar switch-gear modules for lower ratednormal currents into panelswith higher rated normalcurrents

• Option: Interlocking ofhigh-voltage door againstmovable part

• Option: Electromagneticinterlocks

1 Door of low-voltagecompartment

2 Protection device

3 Option: Capacitive voltagedetection system forfeeder and busbar

4 High-voltage door to modulecompartment

5 Mechanical lifting mechanism foropening the high-voltage door

6 Locking device for high-voltagedoor

8 “Closing spring charged”indicator, switch positionindicator for switching deviceand operating cycle counter

Basic panel design (example)

Circuit-breaker panel 3150 A panel with natural ventilation

4000 A panel with forced ventilation

1

2

3

14

21

15

16

17

18

19

20

26

24

25

28

29

23

A

C

B

D

E

HA25

-268

1c e

ps

5

6

9

12

10

11

8

4

13

31

22

32

HA25

-268

2b e

ps

32

9 “ON/OFF” pushbuttons forswitching device

10 Mechanical switch positionindicator and access openingfor movable part

11 Mechanical switch positionindicator and access openingfor make-proof earthing switch

12 Mimic diagram

13 Ventilation duct

14 Pressure relief duct

15 Busbars

16 Bushing-type insulator

17 Bushing-type current transformer

18 Make-proof earthing switch

19 Cable connection for 6 cablesper phase

20 Cable sealing ends

21 Cable bracket

22 Low-voltage plug connector

23 Movable part

24 Operating unit

25 Vacuum interrupters

26 Contact system

28 Earthing busbar

29 Option: Truck

31 Interlocking unit for circuit-breaker and earthing switch

32 Fan unit with fan

A Module compartment

B Busbar compartment

C Connection compartment

D Vacuum circuit-breaker module

E Low-voltage compartment

NXAIR P Panel design, operation

Design

Page 19: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

19Siemens HA 25.71· 2003

NXAIR P Compartments

Design

Module compartment

• Enclosure made ofsendzimir-galvanizedsheet-steel

• Pressure relief upwards

• Panel front powder-coatedwith epoxy resin

• Shutter operating mecha-nisms separately for

– Busbar compartment– Connection compartment

• High-voltage door pressure-resistant in the event ofinternal arcs in the panel

• Metallic ducts on the side forlaying control cables

• Option: Test sockets forcapacitive voltage detectionsystem located in low-voltage compartment abovethe module compartment

• Automatically couplinglow-voltage plug connectorfor connection of switchgearmodules to auxiliary voltagecircuits

• Module compartment toaccommodate componentsfor implementing variouspanel versions with:

– NXACT vacuumcircuit-breaker module

– Disconnecting module– Vacuum contactor module

(for 7.2 kV and 12 kV)– Switch module

• Metering module to accom-modate max. 3 single-polevoltage transformers

– Withdrawable– With or without primary

fuses

Busbar compartment

• Enclosure made ofsendzimir-galvanizedsheet-steel

• Pressure relief upwards

• Inter unit bus supportbetween panels

• Busbars made of flat copper,bolted from panel to panel:– Powder-coated with epoxy

resin– Option: Insulated busbars

• Connection bars betweenbusbars and bushing-typeinsulators or current trans-formers made of silver-platedflat copper

• For rated normal currents:< 2500 Awithout ventilation,w 3150 Awith natural ventilation,w 4000 Awith forced ventilation

• Separately opening shutters

• Bushing-type insulators forsupporting busbars and foraccommodating upper fixedcontacts for switchgearmodule

• Option: Max. 3 bushing-typecurrent transformers

• Option: Coupling electrodefor capacitive voltagedetection system

• Option: Busbar connection(bars only)

Connection compartment

• Enclosure made ofsendzimir-galvanizedsheet-steel

• Pressure relief upwards

• Suitable for connection of:– Bars– Single-core cables– Three-core cables

• Separately opening shuttersto permit cable testing

• Earthing busbar

• Connection from front or rear

• Option: Pressure-resistantfloor cover

• Option: Deep bottom pan,e.g. for connection of three-core cables or cable-typecurrent transformers

Components at the panelconnection (optional)

• Single-core XLPE cablesup to max. 6 x 500 mm2

per phase

• Bars in flat copper withbushings including floorcover or as fully-insulatedbars including floor cover

• Bushing-type insulatorsor max. 3 bushing-typecurrent transformers

• Coupling electrode forcapacitive voltage detectionsystem

• Voltage transformers– Cast-resin insulated– Max. 3 x 1-pole– Fixed-mounted, without

primary fuses

• Make-proof earthing switches– With manual operating

mechanism– Option: With motor operat-

ing mechanism integrated inswitchgear module

– In addition to standard inter-locking of earthing switch/movable part, optionallylockable or with electromag-netic interlock

• Surge arresters or limiters– Surge arresters for protecting

the switchgear againstexternal overvoltages

– Surge limiters for protectingconsumers against switchingovervoltages

Page 20: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

20 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

for NXAIR for NXAIR M for NXAIR P

NXACT vacuum circuit-breaker modules (mounted on truck for moving into the panel)

Circuit-breaker function 1 Hand crank opening for spring charging2 “OFF” pushbutton3 “ON” pushbutton4 Switch position indicator5 “Closing spring charged” indicator6 Operating cycle counter

Disconnecting function 7 Switch position indicator8 Access opening

Earthing switch function 9 Switch position indicator10 Access opening

Moving function of thewithdrawable unit

11 Pole columns with isolating contacts (included in the movable part of NXAIR and NXAIR M)12 Operating unit13 Interlocking unit14 Truck (optional)

6

9

14

10 13

12

11

547

8

1

2

3

3

2

1

8

7

4 5

11

12

13

10

14

9

6

7

14

813

12

11

3

5

4

6

1

2

9

10

R-HA

25-3

13ep

s

R-HA

25-3

14ep

s

R-HA

25-3

15ep

s

Switching of capacitive currents > 5 A on request

Electrical data NXACT for NXAIR

Rated operatingvoltage

up to 12 kV

Max. ratedshort-circuitbreaking current

25 kA

Rated normalcurrent

1250 A and 2500 A

Max. number of operating cycles:

Mechanical 10000

At ratednormal current

10000

At ratedshort-circuitbreaking current

25 (50 optionally)

Mechanical formovable part

1000

Mechanical forearthing switch

1000

Electrical data NXACT for NXAIR M

Rated operatingvoltage

up to 15 kV 17.5/24 kV

Max. ratedshort-circuitbreaking current

31.5 kA 25 kA

Rated normalcurrent

1250 Aand2500 A

630 Ato2500 A

Max. number of operating cycles:

Mechanical 10000 10000

At ratednormal current

10000 10000

At ratedshort-circuitbreaking current

50 50

Mechanical formovable part

1000 1000

Mechanical forearthing switch

1000 1000

Electrical data NXACT for NXAIR P

Rated operatingvoltage

up to 15 kV

Max. ratedshort-circuitbreaking current

50 kA

Rated normalcurrent

1250 A to 4000 A

Max. number of operating cycles:

Mechanical 10000

At ratednormal current

10000

At ratedshort-circuitbreaking current

50

Mechanical formovable part

1000

Mechanical forearthing switch

1000

Components

NXACT vacuum circuit-breaker module

Page 21: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

21Siemens HA 25.71· 2003

Features

• Integrated mechanical interlocksbetween operating mechanisms

• Integrated mechanical switch positionindicators for circuit-breaker,movable part and earthing switch

• Isolating distance established bymoving the movable part

• Permanent interlock of carriagemechanism of switchgear module withthe panel of a switchgear

• Manual or motor operating mechanism

• Positive connection of the low-voltageplug connector with the panel as soon asthe switchgear module is inserted intothe panel

• Maintenance-free operating mechanismswithin a specified number of operatingcycles

Switchgear moduleThe module consists of the followingthree assemblies:

Operating unit to accommodate

• Control board with control, indicatingand interlocking elements

• Operating mechanisms for circuit-breaker, movable part, feederearthing switch and busbar earthingswitch

Movable part (pole column)consisting of

• Vacuum interrupters

• Isolating contacts

• Pole shells

Interlocking unitconsisting of

• Support element for operating unitand movable part

• Guides for moving the pole column tothe service/disconnected position

• Pole operating linkages and operatingshafts

• Adaptation possibilities for truck(to move switchgear module into panel)

• Operating elements for shutter operation

Module versions

• NXACT vacuum circuit-breaker module

• Disconnecting module for disconnectingpanel and metering panel

• Vacuum switch module

Features

• Integrated mechanical interlocksbetween operating mechanisms

• Integrated mechanical switch positionindicators for circuit-breaker,movable part and earthing switch

• Isolating distance established bymoving the movable part

• Permanent interlock of carriagemechanism of switchgear module withthe module compartment

• Manual or motor operating mechanism

• Low-voltage plug connector plugged inmanually

• Maintenance-free operating mechanismswithin a specified number of operatingcycles

Switchgear moduleThe module consists of the followingthree assemblies:

Operating unit to accommodate

• Control board with control, indicatingand interlocking elements

• Operating mechanisms for circuit-breaker, movable part, feederearthing switch

Movable part (pole column)consisting of

• Vacuum interrupters

• Isolating contacts

• Pole shells

Interlocking unitconsisting of

• Support element for operating unitand movable part

• Guides for moving the pole column tothe service/disconnected position

• Pole operating linkages and operatingshafts

• Adaptation possibilities for truck(to move switchgear module into panel)

• Operating elements for shutter operation

Module versions

• NXACT vacuum circuit-breaker module

• Disconnecting module for disconnectingpanel and metering panel

• Vacuum contactor module (for 7.2 kV)

• Vacuum switch module (for 24 kV)

Features

• Integrated mechanical interlocksbetween operating mechanisms

• Integrated mechanical switch positionindicators for circuit-breaker,movable part and earthing switch

• Isolating distance established bymoving the movable part

• Manual or motor operating mechanism

• Positive connection of the low-voltageplug connector with the panel as soon asthe switchgear module is inserted intothe panel

• Maintenance-free operating mechanismswithin a specified number of operatingcycles

Switchgear moduleThe module consists of the followingtwo assemblies:

Movable partconsisting of

• Vacuum circuit-breaker

• Contact system

• Pole shells

• Operating unit:consisting of

– Control, indicating and interlockingelements

– Operating mechanism for vacuumcircuit-breaker

Interlocking unitconsisting of

• Support element for movable part andcontrol elements for earthing switch

• Support element for integrated, mechani-cal interlocking between circuit-breaker,movable part and earthing switch

• Operating elements for shutter operation

Module versions

• NXACT vacuum circuit-breaker module

• Disconnecting module for disconnectingpanel

• Vacuum contactor module(for 7.2 kV and 12 kV)

• Vacuum switch module

• Metering module

for NXAIR for NXAIR M for NXAIR P

NXACT vacuum circuit-breaker module

Components

Page 22: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

22 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

Switching devices

Vacuum switch module

• Vacuum switch integra-ted on module or vacu-um switch with HV HRCfuses integrated onmodule

• According to– IEC 60 265-1– IEC 60 420– VDE 0670 Parts 301

and 303

• For product range referto pages 8, 10 and 12

Vacuum contactormodule

• Module withvacuum contactor

• According to– IEC 60 470– IEC 60 632– VDE 0660 Parts 103

and 105

• Up to 2 HV HRC fusesconnected in parallel withdimension e = 442 mmper phase

• Option: Control transfor-mer with primary fuses

• Option: Latching unit

• For product range referto pages 10 and 12

Vacuum switch modulefor switch panel 12 kV

Vacuum contactor 3TL8for vacuum contactor panel 7.2 kV

for NXAIR M

Vacuum switch modulefor switch panel 24 kV

Vacuum switch modulefor switch panel (example)

for NXAIR

R-HG

11-0

84ep

s

R-HA

25-3

23ep

sR-

HA25

-324

eps

R-HA

25-3

22ep

s

for NXAIR P

Vacuum contactor 3TL6for vacuum contactor panel 7.2 kV or 12 kV

R-HG

11-0

85ep

s

Other switching devices

Components

Page 23: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

23Siemens HA 25.71· 2003

Bushing-type currenttransformers

• According toIEC 60044-1/ VDE 0414Part 1

• Cast-resin insulated

• Include:– Bushing between

compartments– Post insulator function– Current conduction– Current measuring– Option: Coupling

electrode for capacitivevoltage detection system

• Completely replaceablefrom front

• Secondary multiratiopossible

• Screwed fixed contactreplaceable from front

• Current transformer canbe certified

• Primary connections inseparate compartments

Bushing-type insulators

• Construction similar tobushing-type currenttransformer but withoutcurrent transformer core

• Option: Coupling elec-trode for capacitive volt-age detection system

Bushing-type current transformers

for NXAIR for NXAIR M for NXAIR P

1 Partition between module andconnection compartment

2 Cup bushing

3 Mounting plate

4 Coupling electrode

5 Screwed fixed contact

6 Core with secondary winding

7 Primary conductor

8 Primary connection

Bushing-type insulators

for NXAIR for NXAIR M for NXAIR P

1 Partition between module andconnection compartment

2 Cup bushing

3 Mounting plate

4 Coupling electrode

5 Screwed fixed contact

6 Core with secondary winding

7 Primary conductor

8 Primary connection

1 Partition between module andconnection compartment

2 Cup bushing

3 Mounting plate

4 Coupling electrode

5 Screwed fixed contact

6 Core with secondary winding

7 Primary conductor

8 Primary connection

HA25

-268

3 ep

s

5 6 7 8

1 2 3 4

HA25

-268

4 ep

s

5 6 7 8

1 2 3 4

HA25

-268

5 ep

s

5 6 7 8

1 2 3 4

Section Section Section

Bushing-type currenttransformer 1250 A

Bushing-type currenttransformer 2500 A

Bushing-type currenttransformer 4000 A (example)

R-HA

25-3

16ep

s

R-HA

25-3

17ep

s

R-HA

25-3

18ep

s

R-HA

25-3

19ep

s

R-HA

25-3

20ep

s

R-HA

25-3

21ep

s

(example)

Current transformers and post insulators

Components

Page 24: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

24 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

Low-voltagecompartment

• Accommodates equip-ment for protection,control, measuring andmetering, e.g.SIPROTEC 4 7SJ62

• Separated from thehigh-voltage part of thepanel, safe-to-touch

• Low-voltage compart-ment can be removed,bus wires and controlcables are plugged in

• Option: High low-voltage compartmentpossible

• Option: Partitionbetween panels

Low-voltage cables

• Control cables of thepanel are flexible andhave metallic covers

• Connection betweenwithdrawable unit andpanel wiring to low-voltage compartment via10-pole coded moduleplug connectors

• Bus wires pluggablefrom panel to panel

Electronic control board(example)

Multifunction protectionrelay SIPROTEC 4type 7SJ62 for control andprotection

Features

1 LCD for process andequipment data, e.g. for:

– Measuring and meteringvalues

– Binary data on the statusof panel and device

– Protection data– General indications– Alarm

2 Keys for navigation inmenus and for enteringvalues

3 Seven user-programmableLEDs with application-specific label, for dis-playing any desiredprocess and equipmentdata

4 Four user-programmablefunction keys forfrequently performedactions

1 LCD

2 Navigation keys

3 LEDs

4 Function keys

SIPROTEC 4 7SJ62

1

2

4

3R-

HA25

-291

eps

Door of low-voltagecompartment (example)

Low-voltage compartmentwith components (example)

R-HA

25-3

05a

eps

R-HA

25-2

92ep

s

Low-voltage equipment

Components

Page 25: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

25Siemens HA 25.71· 2003

Standards

Standards, specifications, guidelines

Table – Insulating capacity

Rated voltage (rms value) kV 7.2 12 15 17.5 24

Rated short-duration power-frequency withstand voltage (rms value)

– Across isolating distances kV 23 32 39 45 60

– Between phases and to earth kV 20 28 35 38 50

Rated lightning impulse withstand voltage (peak value)

– Across isolating distances kV 70 85 105 110 145

– Between phases and to earth kV 60 75 95 95 125

Correction factor a for the site altitude

For site altitudesabove 1000 m, theadjacent correctionfactor a is recom-mended, depend-ing on the actualsite altitude abovesea level.

Rated short-duration power-frequency withstand voltage to be selected

WRated short-dur. power-fre. withstand volt. (IEC 60 694/ VDE 0670 Part 1000)

1.1 · a

Rated lightning impulse withstand voltage to be selected

WRated lightning impulse withstand volt. (IEC 60 694/ VDE 0670 Part 1000)

1.1 · a

Example:

3000 m site altitude above sea level12 kV switchgear rated voltage75 kV rated lightning impulse withstand voltage

Rated lightning impulse 75 kVwithstand volt. to be selected 1.1 · 0.73

= 93 kV

Standards

The switchgear complies withthe relevant standards andspecifications applicable atthe time of type tests.

In accordance with theharmonization agreementreached by the countries ofthe European Community,their national specificationsconform to IEC 60 298.

Switchgear according to ANSI

The NXAIR P switchgear isalso available as ANSI versionaccording to the followingANSI standards:

Type of service location

The switchgear can be usedfor indoor installation inaccordance with IEC 61 936(Power installations exceeding1 kV AC) and VDE 0101

• Outside lockable electricalservice locations at placeswhich are not accessible tothe public. Enclosures ofswitchgear can only beremoved with tools.

• Inside lockable electricalservice locations. A lockableelectrical service location isa place outdoors or indoorsthat is reserved exclusivelyfor housing electrical equip-ment and which is kept un-der lock and key. Access isrestricted to authorized per-sonnel and persons whohave been properly instruc-ted in electrical engineering.Untrained or unskilled per-sons may only enter underthe supervision of authorizedpersonnel or properly instruc-ted persons.

500040003000200010000

0,9

0,8

0,7

0,6

0,1

0

1

HA40

-203

7 ep

s

Insulating capacity

• The insulating capacity is veri-fied by testing the switchgearwith rated values of short-duration power-frequencywithstand voltage and light-ning impulse withstand volt-age according to IEC 60 694/VDE 0670 Part 1000 (seetable “Insulating capacity”).

• The rated values are referredto sea level and to normalatmospheric conditions(1013 hPa, 20 °C, 11 g/m3

humidity in accordance withIEC 60 071 and VDE 0111).

• The insulating capacitydecreases with increasingaltitude.For site altitudes above1000 m (above sea level)the standards do not provideany guidelines for the insula-tion rating. Instead, specialregulations apply to thesealtitudes.

Site altitude

As the altitude increases, theinsulating capacity of insulationin air decreases due to thedecreasing air density.

For the switchgear thedecreasing insulating capacitymust be taken into accountfor site altitudes above 1000 m(above sea level), see alsoIEC 60 694 /VDE 0670Part 1000.

Result:According to the abovetable, a switchgear for arated voltage of 15 kV isto be selected.

Overview of standards (December 2002)

1) Circuit-breaker

2) Disconnector and earthing switch

3) Switch

4) Switch - fuse combination

5) Voltage detection systems

6) HV HRC fuses

* In future, all standards for switchingdevices and switchgear will besummarized in IEC 62 271

** Withdrawn standard

Switchgear C37.100

C37.20.2

C37.04

C37.06

C37.09

IEEE 1313.1

Current transformer C57.13

Voltage transformer C57.13

IEC standard VDE standard EN standard

up to now current in future current in future current

Switchgear IEC 60 694 * IEC 60 694 * IEC 62 271-1 VDE 0670 Part 1000 VDE 0671-001 EN 60 694

IEC 60 298 * IEC 60 298 * IEC 62 271-200 VDE 0670 Part 6 VDE 0671-200 EN 60 298

Devices 1) IEC 60 056 ** IEC 62 271-100 IEC 62 271-100 VDE 0670 P. 101 to 106 VDE 0671-100 EN 60 0562) IEC 60 129 ** IEC 62 271-102 IEC 62 271-102 VDE 0670 Part 2 VDE 0671-102 EN 60 1293) IEC 60 265-1 * IEC 62 265-1 * IEC 62 271-103 VDE 0670 Part 301 VDE 0671-103 EN 60 265-14) IEC 60 420 ** IEC 62 271-105 IEC 62 271-105 VDE 0670 Part 303 VDE 0671-105 EN 60 4205) IEC 61 243-5 IEC 61 243-5 IEC 61 243-5 VDE 0682 Part 415 VDE 0682 Part 415 EN 61 243-56) IEC 60 282 IEC 60 282 IEC 60 282 VDE 0670 Part 4 VDE 0670 Part 4 EN 60 282

Degree ofprotection

IEC 60 529 IEC 60 529 IEC 60 529 VDE 0470 Part 1 VDE 0470 Part 1 EN 60 529

Insulation IEC 60 071 IEC 60 071 IEC 60 071 VDE 0111 VDE 0111 EN 60 071

Currenttransformers

IEC 60 044-1 IEC 60 044-1 IEC 60 044-1 VDE 0414 Part 1 VDE 0414 Part 1 EN 60 044-1

Voltagetransformers

IEC 60 044-2 IEC 60 044-2 IEC 60 044-2 VDE 0414 Part 2 VDE 0414 Part 2 EN 60 044-2

Cor

rect

ion

fact

ora

Site altitude in m above sea level

Page 26: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

26 Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Types NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

Terms

“Make-proof earthing switches”are earthing switches withshort-circuit making capacityaccording to– IEC 62 271-102 and– VDE 0670 Part 2/ EN 60 129

Standards

Standards, specifications, guidelines

Current-carrying capacity

• According to IEC 60 694 /VDE 0670 Part 1000 andIEC 60 298 / VDE 0670 Part 6current-carrying capacitiesrefer to the following ambienttemperatures:

– Maximum of24-hour mean + 35 °C

– Maximum + 40 °C

• The current-carrying capacityof the panels and busbarsdepends on the ambienttemperature outside theenclosure.

• To attain the maximum ratednormal currents, the panelsare provided with natural orforced ventilation.

Climate and ambientconditions

The switchgear may be used,subject to possible additionalmeasures under the followingambient conditions and climateclasses:Ambient conditions– Natural foreign materials– Chemically active pollutants– Small animals

Climate classes– 3K3– 3K5– 3KX

The climate classes areclassified according toIEC 60 721-3-3

Aseismic capacity

NXAIR and NXAIR P switch-gear types are tested in ac-cordance with internationallyaccepted requirements.

Protection against solidforeign bodies, electric shockand ingress of water

NXAIR, NXAIR M and NXAIR Pswitchgear types fulfill acc. tothe standards– IEC 60 298– IEC 60 529– VDE 0470 Part 1– VDE 0670 Part 6the following degrees ofprotection:

NXAIR and NXAIR Mpanels without ventilation

NXAIR and NXAIR Mpanels with ventilation

NXAIR P panels with andwithout ventilation

Degree of protection

Standard Option

Enclosure IP 4X /IP 3XD

IP 51

Compartments IP 2X –

Degree of protection

Standard

Enclosure IP 4X /IP 3XD

Compartments IP 2X

Degree of protection

Standard

Enclosure IP 4X /IP 3XD

Compartments IP 2X

Page 27: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

27Siemens HA 25.71· 2003

Circuit-Breaker Switchgear Type NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated

If not stated otherwise onthe individual pages of thiscatalog, we reserve theright to include modifica-tions, especially regardingthe stated values, dimen-sions and weights.

Drawings are not binding.

All product designationsused are trademarksor product names ofSiemens AG or othersuppliers.

If not stated otherwise,all dimensions in thiscatalog are given in mm.

KGK 08.03 8.0 VO/- 24 En100701 6101/D6291

Responsible for:

Technical contents:Tushar RaneSiemens AG,Dept. PTD M 1 SErlangen

General editing:Gabriele PollokSiemens AG,Dept. PTD CC T,Erlangen

Resistance to internalarc faults

• Safety of operating person-nel ensured by tests to verifyresistance to internal arcfaults

• Internal arc tests in accord-ance with IEC 60 298 /VDE 0670 Part 6 by agree-ment between operator andmanufacturer

• Internal arc tests performed inaccordance with IEC 60 298,Appendix AA / VDE 0670Part 6, Appendix AA

• The switchgear complieswith criteria 1 to 6 specifiedin the mentioned standards(page 25) for the basic ver-sion up to 50 kA.

Standards, specifications, guidelines Notes

• The switchgear up to 31.5 kAis designed with resistanceto internal arcs going beyondthe scope of the mentionedstandards; that means that inthe event of an internal fault(arc) in a particular compart-ment, the effects of the arcremain confined to that com-partment:

– No burn-through of partitionsto adjacent compartments

– No burn-through of partitionwalls to adjacent panels

– Pressure-resistant wallsbetween adjacentcompartments and panels.

• Resistance to internal arcfaults prevents

– Restrike of an arc fault onlive parts in adjacentcompartments

– Impermissible deformationof partitions.

Standards

• Definitions of criteria:

– Criterion 1Correctly secured doors,shutters etc. must not open

– Criterion 2Parts of the enclosedswitchgear which may causea hazard must not fly off

– Criterion 3No holes in the freelyaccessible external parts ofthe enclosure as the result ofburning in or tearing open

– Criterion 4Vertically arrangedindicators must not ignite

– Criterion 5Horizontally arrangedindicators must not ignite

– Criterion 6The effectiveness of theearth connection must notbe detrimentally influenced

Page 28: Types NXAIR, NXAIR M and NXAIR P - · PDF fileTypes NXAIR, NXAIR M and NXAIR P up to 24 kV, Air-Insulated Medium-Voltage Switchgear Catalog HA 25.71 2003 Supersedes: Catalog HA 25.71

Published by

Siemens AG

Power Transmission and DistributionMedium Voltage DivisionPostfach 32 20

91050 ErlangenGermany

www.siemens.com/medium-voltage-switchgear