    e

    3

    CO - Crown Energy Recovery Unit > Technical Catalogue

    Compact & Self-regulated

    High Efficiency Plate Exchanger up to 95%

    Plug & Play Controls

    Indoor or Outdoor Installation

    Side-by-side or Double Deck Formats

    Up to 1.33 m 3 /s (4800 m 3 /h)

    Full BMS Communication

    EC Motors

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    2/13

    2

    Application

    High efficiency, high performance self regulating ventilation and energy recovery for office and industrial applications

    Thermal efficiency up to 95 % (EN308), in compliance with ErP 2009/125/EC directive

    Air filtration and temperature control included

    Compact, plug n play units complete with BMS communications in accordance with (EN 15232)

    Range

    Available in 6 models, the e 3 co Crown range covers flow rates from 200 to 4,800 m 3 /h (0.05 to 1.33m 3 /s).

    Every e 3 co Crown model has two programmable air flow rates (VAV & CAV control options)

    e 3 co Crown range is available in 3 variants:

    e 3 ssential : self regulating air handling unit dedicated to use in temperate climate area

    e 3 nhanced : self regulating air handling unit fitted with an electric or a hot water coil for external temperatures down to -10C e 3 lite : same as the e 3nhanced series but includes an electric pre-heater for external temperatures down to -20C

    Construction

    Aluminium penta-post framework incorporates anti thermal bridging feature (polyamide sections) which offers class TB2

    thermal performance in accordance with EN1886

    Corners are manufactured from reinforced polyamide

    Double skin panels have steel inner and outer skins that are 1mm in thickness (class 2 in accordance with EN 1886)

    - Insulation: high density 50 mm MO wool mineral (class T2 and class A for air leakage in accordance with EN1886)

    - External face : Pre-painted sheet (RAL 7035)

    - Internal face: galvanized steel

    Circular spigot connections with lip seals to guarantee that systems are airtight

    Brackets are clamped to unit framework for fixing to the ground or ceiling

    Integrated controls compartment is included to house electrical components and regulation system

    Lockable, removable, hinged access panels include integrated IP65 control panel with LCD display and pad lockable local

    electrical isolator

    Access to internal components via lockable panels

    Integral condensate tray and condensate pipework and connection

    100% internal bypass, damper, motorized and self-regulating

    Fans and Motors

    Complete with high efficiency centrifugal plug fans

    Direct driven via EC (Electronically Cumulated) motors with high-performance, thermal protection and built in speed control.

    The EC technology is an ecological solution guaranteeing low energy consumption and better management and control of

    the operating point (air flows can be control led from 10 to 100 %). Low sound levels

    Controls

    User friendly interface

    Fast and easy commissioning

    Pre-configured controls. Constant Air Volume, Variable Air Volume and Constant Pressure options

    Plug and play solution

    Full BMS capability as standard, using a MODBUS protocol. Other protocol options

    available on request

    Heat Exchanger

    Static high-performance counter-flow heat exchanger core with aluminium plates (EUROVENT certified)

    Efficiency greater than 90 % (EN 308) under operating conditions as stated below:

    Fresh air : -10C/90 % RH Return air 20C/50 % RH

    Automatic defrost function by opening the bypass damper and modulation of the fresh air flow if necessary - e 3 ssential ande 3 nhanced series. The e 3lite series, includes an extra integrated electric pre-heater (frost heater)

    Filters

    Filters are included to provide protection to other components (ie, exchanger/fans)

    Media frames are mounted on runners fitted with lip seals to ensure effective air tightness The e 3 co Crown unit is equipped with a high efficiency F7 grade filter fitted to the fresh air intake and a G4 grade filter to

    the extracted air intake. The F7 grade filter has vee form media to deliver a high surface area and low pressur e drop

    Benefits and Features

    Integrated ventilation control is provided by an IP65 rated display panel, suitable for either outdoor or indoor installation,

    BMS communication using MODBUS is via an RS485 port. TCP/IP communication is available on request

    100 % bypass, internal to the central unit, fitted with servomotors controlled automatically by built-in controls which

    provides FREE-COOLING and NIGHT-COOLING functions

    Wide choice of flow modulations to optimise energy consumption (EN 15232)

    Temperature probes (x4) are included to monitor supply air, exhaust air and external temperature There is also a probe

    to control the defrost function. An additional probe is fitted to the e 3lite BE version for control of the pre-heater An integrated de-icing sensor is included to protect the hot water coil fitted into the e 3nhanced/ e 3 lite BC versions e 3 nhanced/ e 3 lite BE versions are complete with a manual reset safety thermostat to protect the electric heater

    elements

    Programmable on board time clocks are included

    Weekly clock and public holiday clock functions

    Supply air filter pressure switch provides a dirty filter alarm

    Press ure switches are used within the control of air flows of each fan, and provide fan ail alarms

    Lockable local electrical isolator mounted on unit casing

    Installation Double Deck or Side-by-Side options (except e 3 co Crown 90-6)

    Indoor or outdoor (with weather roof and rain canopy accessories fitted)

    Low profile - suitable for mounting in ceiling voids

    Specification Specification

    ENERGY EXPERTISEENVIRONMENT

    Klingenburg participates in the ECC programme for AAHE.Check ongoing validity of certificate:www.eurovent-certification.com or www.certiflash.com

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    3/13

    4

    With any system it is always important to have the right product and application to maximise efficiency, with

    Flkt Woods new e 3 co Crown ERU units we have a variety of applications which benefit from our new range.

    The applications below give an indication of where the new e 3 co Crown ERU units can be installed and used to

    minimise energy consumption and provide precise air volume control.

    Environmental Assessment SchemesIt is now very common for new build projects to try and achieve environmental standards such as those set

    out in LEED and BREEAM programs. Flkt Woods, with its market leading knowledge and products in energy

    recovery, has helped many projects achieve the very highest levels in both of these schemes.

    Energy using Products Directive (EuP) The various lots within the EuP directive dictates the eco design requirements for minimum efficiency grades and

    labelling. Efficiency grades for fans from 125W to 500W are already published, and e 3 co Crown products are

    expected to be included in the near future. The efficiency requirement is the combination of the fan and drive

    efficiency, so EC technology will offer the end user or the designer a solution that is better than the minimum

    eco design standards.

    Energy Performance of Buildings Directive (EPBD) The Commission of the European Union has recently proposed a revision of the EPBD (Energy Performance

    in Buildings Directive, 2002/91/EC). The objective is to further strengthen the effectiveness and impact of the

    existing Directive.

    The background to this initiative is to optimise energy usage. It was noted that even in member states where the

    existing Directive has been successfully implemented, the Commission still identified an untapped potential forimprovements that could further reduce the energy consumption and CO 2 emissions from buildings.

    Building Regulations - Part L2 for New (A) and Existing Buildings (B)Effective from October 2010, Building Regulations Part L and F outline the need for a healthier working/indoor

    environment, with the target to decrease CO 2 emissions by a further 25% from the initial reduction stated

    within the 2006 document. The eco design of our e 3 co Crown range will allow specifiers to create designs which

    incorporate the necessary energy usage reductions, whilst still providing precise control of mechanical ventilation.

    European Energy Related Products Directive (ErP)Not only does the e 3co-Crown meet the requirements of the ErP 2009/125/EC, but also EN15232. In addition,

    at the heart of the product, its heat exchanger core is Eurovent Certificated.

    LEGISLATION

    In Europe, all countries now have to design their new buildings to meet energy targets thatare set out in the Energy Performance in Buildings Directive (EPBD). All Flkt Woods EnergyPerformance of Buildings Directive solutions are designed to enable full compliance with thisand other directives regarding ventilation and air conditioning.

    Being a global manufacturer and supplier makes meeting legislation easier for Flkt Woods. It means that

    Flkt Woods must produce solutions at standards that equal the most stringent legislation and guidelines around.

    Only by doing this can we ensure that we meet relevant standards within every market.

    Applications Legislation

    OFFICES

    Flkt Woods offer a highperformance product rangecovering all key elements ofthe overall ventilation system.Our products are designedto secure the best overallperformance of the system as a

    whole, considering parameterssuch as health and air quality,energy efficiency, noise, firesafety and ease of installation.

    EDUCATION

    High occupancy levelsduring teaching periodsrequire energy-efficient andcontrollable demand-basedmanagement of air quality andtemperature. The comfort,health and alertness ofstaff and pupils is ensuredduring the learning process,but operating costs can beminimised when these facilitiesare unoccupied.

    GYMNASIUM/INDOOR SPORTS

    Differing types of activityand occupancy mean abroad spectrum of functionalrequirements to ensure efficientremoval of used air and theintroduction of fresh supplies.Systems need to contain andcontrol the periodic build upof high humidity levels andtemperature.

    HEALTHCARE

    For a hospital to operate atits maximum potential, it has tohave all systems workingat the optimum. This notonly applies to staff,communications and lifesupport systems, but alsoto pipework, cleaning andventilation systems.

    RETAIL/SHOPPING AREAS

    With high activity levelsduring the working week andweekends, its important tomake sure that all areas ofventilation are maintained andFlkt Woods has the systemsto achieve all requirements.

    RESIDENTIAL

    The purpose of ventilation is toprovide clean good quality airby removing the stale, pollutedair from our homes. The maintask is of course to ensure thatthe indoor air is healthy andsafe to breathe. Ventilationtoday is also about energy andsaving energy costs by addingheat recovery to the ventilationsystem.

    TOILETS

    Fast, efficient removal ofodours and air-borne pollutantscontribute to the maintenance

    of cleanliness and anacceptable environment incommunal sanitary areas.

    INDUSTRY

    Flkt Woods technologyis used widely in industrialprocessing plants and factoriesfor ventilation of work spaces,as vital components in hightech manufacturing facilities,and for maintaining delicateenvironments within hightolerance levels inpetro-chemical andpharmaceutical plants.

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    4/13

    6

    Fresh air

    Configurations and Electrical Information

    Configuration W Configuration Y

    Configuration LExcept e 3 co Crown 90-6

    Configuration PExcept e 3co Crown 90-6

    Side-by-side format (air flows side-by-side) (view from above)

    Double Decked format (air flows one above the other) (side access view)

    ElectrovalveKit Type

    Application Water Coil

    HOT WATER COIL: Include in PREMIUM/INFINITE BC CHILLED WATER COIL: Add a COMBIBOX CBF BF module

    HOT WATER CHILLED WATER

    DN/Kvs - 90/ 7 0 8 0/ 60 6 0/ 50 4 5/ 50 7/12 6/11

    10/1,6 - 3/8 M - IP54

    90-1 90-1 90-1 90-1 - -

    90-2 90-2 90-2 90-2 - -

    90-3 90-3 90-3 90-3 - -

    15/2,5 - 1/2 M - IP54 90-4 90-4 90-4 90-4 90-1-90-2 + CBX 1-2 BF 9008-9010+ CBX 1-2 BF

    20/4 - 1/2 F - IP54 90-5 90-5 90-5 90-5 90-3 + CBX 3 BF 9016 + CB X 3 B F

    25/6,3 - 3/4 F - IP54 90-6 90-6 90-6 90-6 90-4 + CBX 4 BF 9023 + CB X 4 B F

    25/10 - 1 F - IP54 - - - - 90-5 + CBX 5 BF 9035 + CB X 5 B F

    32/16 - 1 1/4 F - IP41 - - - - 90-6 + CBX 6 BF 9048 + CBX 6 BF

    Electro valve kit consists 1 off 3-wayvalve, 3 connectors, servomotorsuitable for control via a 0-10vsignal.

    Servomotors fitted to valves areavailable with either an IP41enclosure (indoor installation) orIP54 rated, suitable for outdoorinstallation.

    CrownModel

    FanMotorpower

    (W)

    TempRangeC/C(min/max)

    IP.Rating

    OverheatProtection*

    e 3 ssentiale 3 nhanced BC e

    3 lite BC e 3 nhanced BE e 3- lite BE

    Voltage V

    FLC AmpRating

    **

    Voltage V

    FLC AmpRating

    **

    Voltage V Model

    FLC AmpRating

    **

    Voltage V Model

    FLC AmpRating

    **

    90-1 2 x 220 -20 / 60 IP44 PTI 230/1/50 3.4 230/1/50 14.3 230/1/50 BE 025 14.3 230/1/50 BE 025 25.2

    90-2 2 x 485 -20 / 60 IP54 PTO 230/1/50 6.2 230/1/50 22.5 230/1/50 BE 025 17.1 230/1/50 BE 025 33.4

    90-3 2 x 900 -20 / 40 IP54 PTO 230/1/50 7.8 400/3/50 15.42 30 /1 /5 0 B E 0 37 2 4. 1

    4 00 /3 /5 0 B E 0 52 2 3. 04 00 /3 /5 0 B E 0 52 1 5. 4

    90-4 2 x 900 -20 / 40 IP54 PTO 230/1/50 7.8 400/3/50 17.52 30 /1 /5 0 B E 0 37 2 4. 1

    4 00 /3 /5 0 B E 0 67 2 7. 24 00 /3 /5 0 B E 0 67 1 7. 5

    90-5 2 x 2500 -20 / 40 IP54 PTO 400/3N/50 8.0 400/3/50 19.9 400/3/50B E 0 67 1 7.7

    400/3/50B E 0 67 2 9.6

    BE 135 27.5 BE 135 39.4

    90-6 2 x 2500 -20 / 40 IP54 PTO 400/3N/50 8.0 400/3/50 34.0 400/3/50B E 0 67 1 7.7

    400/3/50B E 0 67 4 3.7

    BE 135 27.5 BE 135 53.5

    * PTO: Overheat protection opening (output on terminal block) / PTI: built-in overheat protection (in series with the windings).** SC is the same as the FLC as EC motors use a soft start function.

    Extract air

    F re sh a ir E xt ra ct a ir

    Drawing and Dimensions

    * Available in double deck configuration only.

    Double Deck format - 90-1 To 90-6

    Model A B C D E F F1 F2 G J K T e3 ssential

    kge 3 nhanced

    kge 3 lite

    kg

    90-1 315 1915 915 505 255 405 1097 362 456 465 245 540 1 / 2

    215 218 220

    90-2 315 1915 915 505 255 405 1097 362 456 465 245 540 1 / 2

    215 218 220

    90-3 400 2230 1115 605 305 505 1261 362 607 565 345 690 1 / 2

    310 315 318

    90-4 450 2345 1315 705 355 605 1376 362 607 565 445 690 3 / 4

    400 407 412

    90-5 500 2625 1515 805 405 705 1520 450 655 640 545 740 3 / 4

    550 560 564

    90-6* 630 2970 1715 1030 455 805 1677 535 758 685 645 840 1 710 725 732

    Dimensions Table

    Model RC WeightkgK

    mmH

    mmJ

    mmMD Weight

    kg

    90-1 4 340 362 362 8

    90-2 4 340 362 362 8

    90-3 5 440 462 462 10

    90-4 7 540 562 562 13

    90-5 10 640 662 662 15

    90-6* 13 740 762 762 17

    Optional Extras

    Option RC Option MD

    RC - RainCanopy

    MD - MotorisedDamper

    Integrated Exchanger

    Side-by-Side format - 90-1 To 90-5

    Integrated Exchanger

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    5/13

    8

    R e t u r n a i r

    2 0 C / 5 0 % -5C / 90% HR

    -10C / 90% HR

    300Pa

    250Pa200Pa

    150Pa

    300Pa

    250Pa 200Pa 150Pa

    0C / 90% HR

    +5C / 90% HR

    E f f i c i e n c y

    ( % ) - E N 3 0 8

    p e r

    f a n

    P o w e r c o n s u m p t

    i o n

    ( W )

    S t a t i c p r e s s u r e

    ( P a )

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    100%90%

    80%70%60%50%40%

    0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m 3 /s)

    0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m 3 /s)

    0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m 3 /s)

    0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m 3 /s)

    Performance curves shown are based on the e 3nhanced or e 3 lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e 3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e 3nhanced or e 3 lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.

    Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.

    Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.NSC4 = Sound level at 4 m,

    in free field, intakes andoutlets connected up

    Performance - 90-1 Heating Data - 90-1

    BC for e 3nhanced and e 3lite versions - Hot Water Coil

    Watertemp

    (C/C)

    Coilair onTemp(C)

    Flow rate (m/h)(m/s)

    300(0.08)

    400(0.11)

    500(0.14)

    600(0.17)

    700(0.19)

    800(0.22)

    82/71

    11Power (kW)/Air supply temp. (C) 5.1/60 6.3/56 7.3/53 8.3/51 9.2/49 10/47

    Water flow rate (l/h)/DP water (kPa) 410/11 510/17 590/22 670/28 740/34 800/41

    15Power (kW)/Air supply temp. (C) 4.8/61 5.8/58 6.8/55 7.7/52 8.5/51 9.33/49

    Water flow rate (l/h)/DP water (kPa) 380/10 470/14 550/20 620/24 690/31 750/35

    90/70

    11Power (kW)/Air supply temp. (C) 5.3/62 6.5/58 7.5/55 8.5/52 9.4/50 10.2/48

    Water flow rate (l/h)/DP water (kPa) 240/4 290/6 340/8 380/10 420/12 450 /12

    15Power (kW)/Air supply temp. (C) 4.9/63.9 6.1/59 7.05/56 7.9/54 8.7/52 9.5/50.4

    Water flow rate (l/h)/DP water (kPa) 220/3 270/5 310/6 350/8 390 /10 420 /11

    45/40

    11Power (kW)/Air supply temp. (C) 2.4/34 3/32.7 3.5/31 3.9/30.1 4.3/29 4.7/28

    Water flow rate (l/h)/DP water (kPa) 430/13 520/19 610/24 680/30 760/37 820/43

    15Power (kW)/Air supply temp. (C) 2.1/35.6 2.5/34 3/32 3.3/31.8 3.7/30.9 4/30.1

    Water flow rate (l/h)/DP water (kPa) 370/10 450/14 520/18 590/23 650/27 710/32

    60/50

    11Power (kW)/Air supply temp. (C) 3.4/43.7 4.2/41 4.8/39 5.4/37.5 6/36 6.5/34.9

    Water flow rate (l/h)/DP water (kPa) 300/6 360/9 420/12 480/15 530/18 570 /20

    15Power (kW)/Air supply temp. (C) 3/44 3.7/42 4.3/40 4.9/39.3 5.4/37 5.8/36.8

    Water flow rate (l/h)/DP water (kPa) 270/5 330/8 380/10 430/12 470/14 510/17

    BE for e 3 nhanced and e 3 lite versions - Electric Heater

    Notes:1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RH

    or 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.

    2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.

    Fresh Air 0C 0C -5C -10C -15C -20C

    Qv (m/h) 800 800 800 800 800 800

    Versione 3 ssential e 3 nhanced BE 025 e 3lite BE 025

    E lect ri c Hea te r P re -hea te r + Pos t Hea te r

    Total power (kW) - 2.5 2.5 2.5 2.5 + 2.5 2.5 + 2.5

    Air supply Temp. (C) 16.8 26.2 25.6 20.8 24.6 19.7

    Typical Plate Heat Exchanger Core Performance data

    Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH

    Model Air ow rate Recovered

    kW Air Off temp C / RHThermal

    Efficiency %m 3 /h m 3 /s

    Crown 90-1 450 0.13 3.7 19.3C 16.1%RH 90.1

    Watertemp

    (C/C)

    New airtemp(C)

    Flow rate (m/h) 400 600 800 1000

    7/12

    32/40P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 3 .4 /1 4. 5- 82 4 .4 /1 6 .4 -7 9 5 .1 /1 7. 7- 77 5 .7 /1 8. 8- 75

    Water flow rate (l/h)/DP water (kPa) 580/5 750/8 880/10 970/12

    27/50P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 2 .6 /1 3. 9- 86 3 .3 /1 5. 4- 83 3 .8 /1 6. 5- 82 4 .2 /1 7. 3- 81

    Water flow rate (l/h)/DP water (kPa) 440/3 560/5 650/6 720/7

    25/50P ow er (k W) /A ir s up pl y t em p. ( C- %H R) 2 .0 /1 3. 6- 85 2 .5 /1 5- 83 2 .9 /1 5. 9- 82 3 .1 /1 6. 6- 81

    Water flow rate (l/h)/DP water (kPa) 350/2 430/3 490/4 530/4

    6/11

    32/40P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 3 .6 /1 3. 8- 82 4 .7 /1 5. 7- 79 5 .5 /1 7. 1- 77 6 .2 /1 8. 2- 75

    Water flow rate (l/h)/DP water (kPa) 620/5 800/9 940/11 1050/14

    27/50P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 2 .8 /1 3. 2- 86 3 .6 /1 4. 7- 84 4 .2 /1 5 .8 -8 2 4 .7 /1 6. 7- 81

    Water flow rate (l/h)/DP water (kPa) 480/4 620/5 720/7 810/9

    25/50P ow er ( kW )/ Ai r su pp ly t em p. ( C -% HR ) 2 .3 /1 2. 9- 85 2 .9 /1 4. 3- 83 3 .3 /1 5 .2 -8 2 3 .6 /1 6- 81

    Water flow rate (l/h)/DP water (kPa) 390/2 490/4 560/5 620/5

    CBX 1-2 BF for Chilled Water Module

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    6/13

    10

    Performance - 90-2 Heating Data - 90-2

    0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28

    -5C / 90% HR

    +5C / 90% HR

    0C / 90% HR

    -10C / 90% HR

    300Pa250Pa

    150Pa

    300Pa

    250Pa

    200Pa 150Pa

    200Pa150Pa

    R e t u r n a i r

    2 0 C / 5 0 %

    E f f i c i e n c y

    ( % ) - E N 3 0 8

    p e r f a n

    P o w e r c o n s u m p t

    i o n

    ( W )

    S t a t

    i c p r e s s u r e

    ( P a )

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /s)

    0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m 3 /s)

    0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28

    Flow rate (m 3 /s)

    0.06 0.08 0.11 0.14 0.17 0.19 0.22 0.25 0.28Flow rate (m 3 /s)

    80%

    70%

    60%

    50%40%

    Performance curves shown are based on the e 3nhanced or e 3lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e 3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e 3nhanced or e 3 lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.

    Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.

    Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.

    BC for e 3 nhanced and e 3 lite versions - Hot Water Coil Water

    temp(C/C)

    Coilair onTemp(C)

    Flow rate (m/h)(m/s)

    400(0.11)

    500(0.14)

    600(0.17)

    700(0.19)

    800(0.22

    900(0.25)

    82/71

    11Power (kW)/Air supply temp. (C) 6.3/56 7.3/53 8.3/51 9.2/49 10/47 10.8/45

    Water ow rate (l/h)/DP water (kPa) 510/17 590/22 670/28 740/34 800/41 870/47

    15Power (kW)/Air supply temp. (C) 5.8/58 6.8/55 7.7/52 8.5/51 9.33/49 10.1/47.8

    Water ow rate (l/h)/DP water (kPa) 470/14 550/20 620/24 690/31 750/35 810/41

    90/70

    11Power (kW)/Air supply temp. (C) 6.5/58 7.5/55 8.5/52 9.4/50 10.2/48 11/46.8

    Water ow rate (l/h)/DP water (kPa) 290/6 340/8 380/10 420/12 450 /12 490/15

    15Power (kW)/Air supply temp. (C) 6.1/59 7.05/56 7.9/54 8.7/52 9.5/50.4 10.3/48.8

    Water ow rate (l/h)/DP water (kPa) 270/5 310/6 350/8 390 /10 420 /11 450/13

    45/40

    11Power (kW)/Air supply temp. (C) 3/32.7 3.5/31 3.9/30.1 4.3/29 4.7/28 5.1/27.5

    Water ow rate (l/h)/DP water (kPa) 520/19 610/24 680/30 760/37 820/43 890/51

    15Power (kW)/Air supply temp. (C) 2.5/34 3/32 3.3/31.8 3.7/30.9 4/30.1 4.4/29.5

    Water ow rate (l/h)/DP water (kPa) 450/14 520/18 590/23 650/27 710/32 760/38

    60/50

    11Power (kW)/Air supply temp. (C) 4.2/41 4.8/39 5.4/37.5 6/36 6.5/34.9 7/33

    Water ow rate (l/h)/DP water (kPa) 360/9 420/12 480/15 530/18 570 /20 620/24

    15Power (kW)/Air supply temp. (C) 3.7/42 4.3/40 4.9/39.3 5.4/37 5.8/36.8 6.4/35.9

    Water ow rate (l/h)/DP water (kPa) 330/8 380/10 430/12 470/14 510/17 550/20

    BE for e 3 nhanced and e 3 lite versions - Electric Heater Fresh Air 0C 0C -5C -10C -15C -20C

    Qv (m/h) 980 980 980 980 980 980

    Versione 3 ssential e 3 nhanced BE 025 e 3lite BE 025

    E lect ri c Hea te r P re -hea te r + Pos t Hea te r

    Total power (kW) - 2.5 2.5 2.5 3.75 + 2.5 3.75 + 2.5

    Air supply Temp. (C) 16.7 24.4 23.8 19 24.6 19.7

    Notes:1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RH

    or 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.

    2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.

    Typical Plate Heat Exchanger Core Performance data

    Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH

    Model Air ow rate Recovered

    kW Air Off temp C / RHThermal

    Efficiency %m 3 /h m 3 /s

    Crown 90-2 600 0.17 4.8 19.0C 16.4%RH 89.0

    NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up

    Watertemp

    (C/C)

    New airtemp(C)

    Flow rate (m/h) 400 600 800 1000

    7/12

    32/40P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 3 .4 /1 4. 5- 82 4 .4 /1 6 .4 -7 9 5 .1 /1 7. 7- 77 5 .7 /1 8. 8- 75

    Water flow rate (l/h)/DP water (kPa) 580/5 750/8 880/10 970/12

    27/50P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 2 .6 /1 3. 9- 86 3 .3 /1 5. 4- 83 3 .8 /1 6. 5- 82 4 .2 /1 7. 3- 81

    Water flow rate (l/h)/DP water (kPa) 440/3 560/5 650/6 720/7

    25/50P ow er (k W) /A ir s up pl y t em p. ( C- %H R) 2 .0 /1 3. 6- 85 2 .5 /1 5- 83 2 .9 /1 5. 9- 82 3 .1 /1 6. 6- 81

    Water flow rate (l/h)/DP water (kPa) 350/2 430/3 490/4 530/4

    6/11

    32/40P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 3 .6 /1 3. 8- 82 4 .7 /1 5. 7- 79 5 .5 /1 7. 1- 77 6 .2 /1 8. 2- 75

    Water flow rate (l/h)/DP water (kPa) 620/5 800/9 940/11 1050/14

    27/50P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 2 .8 /1 3. 2- 86 3 .6 /1 4. 7- 84 4 .2 /1 5 .8 -8 2 4 .7 /1 6. 7- 81

    Water flow rate (l/h)/DP water (kPa) 480/4 620/5 720/7 810/9

    25/50P ow er ( kW )/ Ai r su pp ly t em p. ( C -% HR ) 2 .3 /1 2. 9- 85 2 .9 /1 4. 3- 83 3 .3 /1 5 .2 -8 2 3 .6 /1 6- 81

    Water flow rate (l/h)/DP water (kPa) 390/2 490/4 560/5 620/5

    CBX 1-2 BF for Chilled Water Module

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    7/13

    12

    Performance - 90-3 Heating Data - 90-3

    BC for e 3 nhanced and e 3 lite versions - Hot Water Coil Water

    temp(C/C)

    Coilair onTemp(C)

    Flow rate (m/h)(m/s)

    600(0.17)

    800(0.22)

    1000(0.28)

    1200(0.33)

    1400(0.39)

    1500(0.42)

    82/71

    11Power (kW)/Air supply temp. (C ) 10.1/59.7 12.4/55.8 14.4/52 16/50 18/48 18.8/47.3

    Water ow rate (l/h) /DP water (kPa) 810/18 990/27 1150/36 1310/46 1440/55 1510/60

    15P owe r ( kW )/A ir s up pl y t em p. ( C ) 9. 4/6 1 11 .5/ 57. 4 1 3. 4/ 54 .5 15 .2 /5 2. 2 1 6. 7/5 0 17 .5 /4 9.3

    Water ow rate (l/h)/DP water (kPa) 750/16 920/24 1070/31 1220/40 1340/48 1400/52

    90/70

    11P owe r ( kW )/A ir s u pp ly t e mp . ( C) 1 0. 5/6 2. 1 1 3/5 7.8 1 4. 9/ 54 .4 16 .7 /5 1. 7 1 8.5 /49 .5 19 .3 /4 8.6

    Water ow rate (l/h)/DP water (kPa) 460/6 570/9 660/12 740/15 820/18 850/20

    15Power ( kW)/Air s upply t emp. ( C ) 9.8/63.4 12/59 13.9/56.2 15.6/53.7 17.2/51.5 18/50.7

    Water ow rate (l/h)/DP water (kPa) 430/6 530/8 610/10 690/13 760/16 800/18

    45/40

    11P owe r ( kW )/A ir s up pl y t em p. ( C ) 4. 8/ 34 .2 5 .8 /3 2. 4 6 .8 /30 .9 7 .7 /2 9.7 8 .5/ 28 .7 8. 91 /2 8. 3

    Wa te r ow r at e ( l/h )/ DP w at er ( kP a) 83 0/2 0 1 020 /30 1 19 0/4 0 13 40/ 49. 1 1 48 0/6 0 15 50/ 68

    15Power (kW)/Air supply temp . (C) 4.1/35.4 5/33.8 5.88/32.5 6.6/31.4 7.3/30.6 7.6/30.2

    Water ow rate (l/h)/DP water (kPa) 720/15 880/22 1020/30 1160/37.3 1280/45 1330/51

    60/50

    11Power ( kW)/Air s upply t emp. ( C) 6.6/43.4 8.1/40.8 9.4/38.7 10.7/37 11.8/35.6 12.3/35

    Water ow rate (l/h)/DP water (kPa) 580/10 710/14 830/20 940/24 1030/30 1080/33

    15P owe r ( kW )/A ir s up pl y t emp . ( C ) 5. 9/4 4. 6 7 .3 /4 2. 2 8 .5 /40 .3 9 .6 /3 8. 8 1 0. 6/ 37 .5 11 .1 /3 6. 9

    Water ow rate (l/h)/DP water (kPa) 520/8 640/12 750/16 840/20 930/25 970/27

    BE for e 3 nhanced and e 3 lite versions - Electric Heater Fresh Air 0C 0C -5C -10C -15C -20C

    Qv (m/h) 1550 1550 1550 1550 1550 1550

    Versione 3 ssential e 3 nhanced BE 025 e 3lite BE 025

    E lect ri c Hea te r P re -Hea te r + Pos t Hea te r

    Total power (kW) - 3.75 3.75 3.75 5.25 + 3.75 5.25 + 5.25

    Air supply Temp. (C) 16.7 24 23.5 21.5 23.7 21.6

    -5C / 90% HR

    +5C / 90% HR

    0C / 90% HR

    -10C / 90% HR

    300Pa250Pa200Pa

    300Pa

    250Pa

    200Pa 150Pa

    150Pa

    300Pa

    150Pa

    250Pa200Pa150Pa

    R e t u r n a i r

    2 0 C / 5 0 %

    E f f i c i e n c y

    ( % ) - E N 3 0 8

    p e r f a n

    P o w e r c o n s u m p t

    i o n

    ( W )

    S t a t

    i c p r e s s u r e

    ( P a )

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    80%

    70%

    60%

    50%

    40%

    0.11 0.14 0.17 0.19 0.22 0.25 0.28 0.31 0.33 0.36 0.39 0.42 0.44Flow rate (m 3 /s)

    0.11 0.14 0.17 0.19 0.22 0.25 0.28 0.31 0.33 0.36 0.39 0.42 0.44Flow rate (m 3 /s)

    0.11 0.14 0.17 0.19 0.22 0.25 0.28 0.31 0.33 0.36 0.39 0.42 0.44Flow rate (m 3 /s)

    0.11 0.14 0.17 0.19 0.22 0.25 0.28 0.31 0.33 0.36 0.39 0.42 0.44Flow rate (m 3 /s)

    Performance curves shown are based on the e 3nhanced or e 3lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e 3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e 3nhanced or e 3 lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.

    Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.

    Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.

    30%

    Notes:1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RH

    or 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.

    2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.

    Typical Plate Heat Exchanger Core Performance data

    Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH

    Model Air ow rate Recovered

    kW Air Off temp C / RHThermal

    Efficiency %m 3 /h m 3 /s

    Crown 90-3 950 0.26 7.7 19.0C 16.4%RH 89.0

    NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up

    Watertemp

    (C/C)

    New airtemp(C)

    Flow rate (m/h) 1000 1200 1400 1600

    7/12

    32/40P ow er (k W) /A ir s up pl y t em p. ( C- %H R) 7 .3 /1 6. 4- 78 8 .1 /1 7 .2 -7 7 8 .8 /1 8- 76 9 .4 /1 8. 6- 75

    Water flow rate (l/h)/DP w ater (kPa) 17 1/4 21 10/19 24 2/1 1 26

    27/50P ow er ( kW )/ Ai r s up pl y t em p. ( C -% HR ) 5 .6 /1 5. 3- 83 6 .2 /1 6- 82 6 .7 /1 6. 6- 81 7 .1 /1 7- 81

    Water flow rate (l/h)/DP water (kPa) 960/10 6 11 10/13 15

    25/50P ow er (k W) /A ir s up pl y t em p. ( C- %H R) 4 .3 /1 5 -8 2 4 .6 /1 5 .6 -8 2 4 .9 /1 6. 1- 81 5 .1 /1 6. 5- 80

    Water flow rate (l/h)/DP water (kPa) 730/6 790/7 840/8 880/8

    6/11

    32/40P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 7 .7 /1 5. 9- 78 8 .6 /1 6 .8 -7 7 9 .3 /1 7. 5- 76 9 .9 /1 8. 2- 75

    W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 1 32 0/ 17 1 47 0/ 20 1 59 0/2 3 1 70 0/2 6

    27/50P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 6 .0 /1 4. 8- 83 6 .7 /1 5. 5- 82 7 .2 /1 6. 1- 81 7 .7 /1 6. 6- 81

    W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 1 03 0/ 11 1 14 0/ 13 1 23 0/1 5 1 31 0/1 7

    25/50P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 4 .8 /1 4. 3- 83 5 .2 /1 4. 9- 82 5 .6 /1 5. 5- 81 5 .9 /1 5. 9- 80

    Water flow rate (l/h)/DP water (kPa) 820/7 900/9 960/10 1010/11

    CBX 3 BF for Chilled Water Module

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    8/13

    14

    Performance - 90-4 Heating Data - 90-4

    BC for e 3 nhanced and e 3 lite versions - Hot Water Coil Water

    temp(C/C)

    Coilair onTemp(C)

    Flow rate (m/h)(m/s)

    1000(0.28)

    1250(0.35)

    1500(0.42)

    1750(0.49)

    2000(0.56)

    2250(0.63)

    82/71

    11Power (kW)/Air supply temp. (C) 16/58 19.4/55 22/53 24.3/51.3 26/49.5 28/47

    Water ow rate (l/h) /DP water (kPa) 1320/16 1560/22 1760/28 1950/34 2130/41 2300/47

    15Power (kW)/Air supply temp. (C) 15.4/60.3 18/57 20.5/55 22.7/53 24.7/51 26/50

    Water ow rate (l/h)/DP water (kPa) 1240/14 1440/19 1640/24 1820/30 1980/35 2140/41

    90/70

    11P ow er ( kW )/ Ai r s up pl y t em p. ( C ) 1 7. 2/ 61 .1 2 0. 1/ 57 .8 2 2. 7/ 55 .1 2 5. 1/ 52 .9 2 7. 3/ 50 .9 2 9. 4/ 49 .2

    Water ow rate (l/h)/DP water (kPa) 760/6 890/8 1000/10 1110/12 1210/14 1300/16

    15P owe r ( kW )/A ir s u pp ly t e mp . ( C) 16 /62 .5 18 .7/ 59. 5 2 1. 2/ 56 .9 23 .4 /5 4. 7 2 5.5 /52 .9 27 .5 /5 1.3

    Water ow rate (l/h)/DP water (kPa) 710/5 830/7 940/9 1030/10 1130/13 1210/14

    45/40

    11P ow er ( kW )/ Ai r s up pl y t em p. ( C ) 7 .8 3/ 33 .8 9 .2 /3 2. 4 1 0. 4/ 31 .2 1 1. 5/ 30 .2 1 2. 6/ 29 .4 1 3. 6/ 28 .6

    Water ow rate (l/h)/DP water (kPa) 1360 /19 1600/26 1810/32 2000/38 2190/46 2370/54

    15P ow er ( kW )/ Ai r s up pl y t em p. ( C ) 6 .7 5/ 35 7 .9 /3 3. 8 8 .9 7/ 32 .8 1 0/ 31 .9 1 0. 8/ 31 .1 1 1. 7/ 30 .4

    Water ow rate (l/h)/DP water (kPa) 1180/14 1380/20 1560/24 1730/30 1880/35 2040/41

    60/50

    11P owe r ( kW )/A ir s u pp ly t e mp . ( C ) 1 0. 9/4 2. 9 1 2. 8/ 40. 8 1 4. 4/3 9. 1 1 6/3 7.7 1 7. 4/ 36 .5 18 .8 /3 5. 4

    Water ow rate (l/h)/DP water (kPa) 950/10 1120/13 1260/16 1400/19 1520/22 1650/26

    15P owe r ( kW )/A ir su pp ly te mp . ( C ) 9. 8/4 4. 1 1 1. 5/ 42. 2 13 /40 .7 14 .4/ 39. 4 1 5. 7/ 38 .3 16 .9 /3 7. 3

    Water ow rate (l/h)/DP water (kPa) 860/8 1010/10 1140/13 1260 /16 1370/19 1480/22

    BE for e 3 nhanced and e 3 lite versions - Electric Heater Fresh Air 0C 0C -5C -10C -15C -20C

    Qv (m/h) 2300 2300 2300 2300 2300 2300

    Versione 3 ssential e 3 nhanced BE 025 e 3lite BE 025

    E lect ri c Hea te r P re -Hea te r + Pos t-Heat er

    Total power (kW) - 3.75 3.75 6.75 6.75 + 3.75 6.75 + 6.75

    Air supply Temp. (C) 16.6 21.5 21 20.1 20.1 19.1

    -5C / 90% HR

    +5C / 90% HR

    0C / 90% HR

    -10C / 90% HR

    300Pa250Pa 200Pa

    300Pa

    200Pa250Pa

    150Pa

    150Pa

    200Pa

    200Pa 150Pa

    R e t u r n a i r

    2 0 C / 5 0 %

    E f f i c i e n c y

    ( % ) - E N 3 0 8

    p e r

    f a n

    P o w e r c o n s u m p t

    i o n

    ( W )

    S t a t

    i c p r e s s u r e

    ( P a )

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    100%90%

    80%

    70%

    60%

    50%

    40%

    0.17 0.22 0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67Flow rate (m 3 /s)

    0.17 0.22 0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67Flow rate (m 3 /s)

    0.17 0.22 0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67

    Flow rate (m 3 /s)

    0.17 0.22 0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67Flow rate (m 3 /s)

    Performance curves shown are based on the e 3nhanced or e 3 lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e 3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e 3nhanced or e 3lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.

    Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.

    Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.

    Notes:1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RH

    or 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.

    2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.

    Typical Plate Heat Exchanger Core Performance data

    Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH

    Model Air ow rate Recovered

    kW Air Off temp C / RHThermal

    Efficiency %m 3 /h m 3 /s

    Crown 90-4 1450 0.40 11.9 19.5C 16 %RH 90.7

    NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up

    Watertemp

    (C/C)

    New airtemp(C)

    Flow rate (m/h) 1400 1800 2200 2600

    7/12

    32/40Power (kW)/Air supply temp. (C-%HR) 10.7/15.9-79 12.4/17.1-77 13.7/18.0-76 14.8/18.8-75

    W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 1 83 0/ 14 2 12 0/ 18 2 35 0/2 1 2 53 0/2 4

    27/50Power (kW)/Air supply temp. (C-%HR) 8.2/15.0-84 9.4/15.9-82 10.4/16.6-81 11.1/17.2-80

    Water flow rate (l/h)/DP water (kPa) 140 0/8 1610/11 1 770/1 3 1910 /15

    25/50P ow er (k W) /A ir s up pl y t em p. ( C- %H R) 6 .4 /1 4. 5- 83 7 .2 /1 5. 3- 82 7 .9 /1 6- 81 8 .3 /1 6. 5- 80

    Water flow rate (l/h)/DP water (kPa) 1090/6 1240/7 1350/8 1430/9

    6/11

    32/40Power (kW)/Air supply temp. (C-%HR) 11.4/15.2-79 13.3/16.4-77 14.8/17.4-76 16.0/18.2-75

    W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 1 96 0/ 15 2 27 0/ 20 2 53 0/ 24 2 75 0/2 8

    27/50Power (kW)/Air supply temp. (C-%HR) 8.9/14.3-84 10.3/15.2-82 11.5/16-81 12.4/16.6-81

    W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 1 53 0/ 10 1 77 0/ 13 1 96 0/ 15 2 12 0/1 8

    25/50P ow er ( k W) /A ir s u p pl y t em p. ( C- %H R) 7 .2 /1 3. 8- 83 8 .2 /1 4. 7- 82 9 .0 /1 5 .4 -8 1 9 .6 /1 5. 9- 80

    Water flow rate (l /h)/DP water (kPa) 12 20/7 1400/9 1 530/10 1640 /11

    CBX 4 BF for Chilled Water Module

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    9/13

    16

    Performance - 90-5 Heating Data - 90-5

    BC for e 3 nhanced and e 3 lite versions - Hot Water Coil Water

    temp(C/C)

    Coilair onTemp(C)

    Flow rate (m/h)(m/s)

    1500(0.42)

    1900(0.53)

    2300(0.64)

    2700(0.75)

    3100(0.86)

    3500(0.97)

    82/71

    11Power (kW)/Air supply temp. (C ) 24.8/58 29.3/55 33.5/53.1 37.2/50.9 40.7/49 44/47.4

    Wa te r ow r at e ( l/h )/ DP wa te r ( kP a) 1 99 0/4 2 2 350 /58 2 69 0/7 4 29 80/ 91 3 260 /1 08 35 30/ 125

    15P owe r ( kW )/A ir su pp ly te mp . ( C ) 2 3. 1/6 0. 3 27 .4/ 57. 3 3 1. 2/ 54 .8 34 .7 /5 2. 8 3 7. 9/5 1 41 /4 9. 4

    Wa te r ow ra te (l /h )/ DP wa te r ( kP a) 1 85 0/3 7 2 200 /51 2 50 0/6 5 2 78 0/ 80 3 040 /94 .7 32 90/ 110

    90/70

    11P ow er ( kW )/ Ai r s up pl y t em p. ( C ) 2 5. 3/ 60 .2 2 9. 7/ 56 .7 3 3. 8/ 53 .9 3 7. 5/ 51 .5 4 0. 9/ 49 .5 4 4. 1/ 47 .8

    Water ow rate (l/h)/DP water (kPa) 1120/4 1310/6 1490/8 1660/9 1810/11 1950/13

    15P ow er ( kW )/ Ai r s up pl y t em p. ( C ) 2 3. 5/ 61 .6 2 7. 7/ 58 .3 3 1. 5/ 55 .6 3 4. 9/ 53 .4 3 8. 1/ 51 .5 4 1. 1/ 49 .9

    Water ow rate (l/h)/DP water (kPa) 1040/4 1220/5 1390/7 1540/8 1680/10 1820/11

    45/40

    11P owe r ( kW )/A ir su pp ly te mp . ( C ) 1 1. 5/3 3. 5 1 3.6 /32 1 5. 5/3 0. 7 17 .3/ 29. 7 1 8.9 /28 .8 2 0. 4/ 28

    Water ow rate (l/h)/DP water (kPa) 2000/14 2370/20 2700/25 3010/10 3290/36 3550/41

    15P owe r ( kW )/A ir s u pp ly t e mp . ( C ) 10 /34 .7 1 1. 7/ 33. 4 1 3. 4/3 2. 3 14 .9/ 31. 3 1 6. 3/ 30 .6 17 .6 /2 9. 9

    Water ow rate (l/h)/DP water (kPa) 1730/11 2040/15 2330 /19 2600/23 2840/27 3070/32

    60/50

    11P owe r ( kW )/A ir s u pp ly t e mp . ( C ) 16 /42 .3 1 8. 9/ 40. 1 2 1. 5/3 8. 3 23 .9/ 36. 9 2 6. 1/ 35 .6 28 .2 /3 4. 5

    Water ow rate (l/h)/DP water (kPa) 1410/7 1650/9.4 1880/12 2090/15 2280/18 2470/20

    15P owe r ( kW )/A ir su pp ly te mp . ( C ) 1 4. 4/4 3. 6 1 7/4 1. 6 19 .3 /4 0 21 .5/ 38. 6 2 3. 5/ 37 .5 25 .3 /3 6. 5

    Water ow rate (l/h)/DP water (kPa) 1260/6 1490/8 1690/10 1880 /12 2060/15 2210/17

    BE for e 3 nhanced and e 3 lite versions - Electric Heater Fresh Air 0C 0C -5C -10C -15C -20C

    Qv (m/h) 3500 3500 3500 3500 3500 3500

    Versione 3 ssential e 3 nhanced BE 025 e 3lite BE 025

    E lect ri c Hea te r P re -Hea te r + Pos t-Heat er

    Total power (kW) - 6.75 6.75 13.5 8.25 + 6.75 8.25 + 13.5

    Air supply Temp. (C) 16.7 22.5 22 20.2 19.5 20.5

    -5C / 90% HR

    +5C / 90% HR

    0C / 90% HR

    300Pa250Pa

    250Pa200Pa

    200Pa

    150Pa

    150Pa

    300Pa

    -10C / 90% HR

    200Pa

    200Pa

    150Pa

    150Pa

    R e t u r n a i r

    2 0 C / 5 0 %

    E f f i c i e n c y

    ( % ) - E N 3 0 8

    p e r

    f a n

    P o w e r c o n s u m p t

    i o n

    ( W )

    S t a t i c p r e s s u r e

    ( P a )

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    70%

    60%

    50%

    40%

    30%

    0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67 0.72 0.78 0.83 0.89 0.94 1.00Flow rate (m 3 /s)

    0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67 0.72 0.78 0.83 0.89 0.94 1.00Flow rate (m 3 /s)

    0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67 0.72 0.78 0.83 0.89 0.94 1.00Flow rate (m 3 /s)

    0.28 0.33 0.39 0.44 0.50 0.56 0.61 0.67 0.72 0.78 0.83 0.89 0.94 1.00Flow rate (m 3 /s)

    Performance curves shown are based on the e 3nhanced or e 3lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e 3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e 3nhanced or e 3 lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.

    Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.

    Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.

    Notes:1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RH

    or 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.

    2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.

    Typical Plate Heat Exchanger Core Performance data

    Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH

    Model Air ow rate Recovered

    kW Air Off temp C / RHThermal

    Efficiency %m 3 /h m 3 /s

    Crown 90-5 2100 0.58 17.0 19.1C 16.4%RH 89.2

    NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up

    Watertemp

    (C/C)

    New airtemp(C)

    Flow rate (m/h) 2000 2500 3000 3500

    7/12

    32/40Power (kW)/Air supply temp. (C-%HR) 19.2/12.7-84 22.4/13.8-83 25.2/14.7-81 27.7/15.4-80

    W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 3 30 0/ 14 3 84 0/ 18 4 32 0/2 2 4 74 0/2 6

    27/50Power (kW)/Air supply temp. (C-%HR) 14.9/12.5-88 17.3/13.3-86 19.4/14-85 21.2/14.6-84

    Water flow rate (l/h)/DP water (kPa) 256 0/9 2960/11 33 20/1 4 3630 /16

    25/50Power (kW)/Air supply temp. (C-%HR) 12.0/12.3-87 13.8/13-86 15.3/13.7-85 16.6/14.2-84

    Water flow rate (l/h)/DP water (kPa) 205 0/6 2360/8 2620/9 2850 /10

    6/11

    32/40Power (kW)/Air supply temp. (C-%HR) 20.4/11.9-85 23.8/13-83 26.8/13.9-82 29.5/14.7-80

    W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 3 49 0/ 15 4 07 0/ 20 4 59 0/2 4 5 06 0/2 9

    27/50Power (kW)/Air supply temp. (C-%HR) 16.1/11.6-88 18.7/12.5-87 21.0/13.3-86 23.1/13.9-85

    W at er fl ow r at e (l /h )/ DP w at er ( kPa ) 2 76 0/ 10 3 20 0/ 13 3 60 0/1 6 3 95 0/1 9

    25/50Power (kW)/Air supply temp. (C-%HR) 13.2/11.4-87 15.2/12.2-86 17.0/12.9-85 18.6/13.5-84

    Water flow rate (l /h)/DP water (kPa) 22 60/7 2610/9 2 910/11 3180 /13

    CBX 5 BF for Chilled Water Module

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    10/13

    18

    Performance - 90-6 Heating Data - 90-6

    BC for e 3 nhanced and e 3 lite versions - Hot Water Coil Water

    temp(C/C)

    Coilair onTemp(C)

    Flow rate (m/h)(m/s)

    2200(0.61)

    2700(0.75)

    3200(0.89)

    3700(1.03)

    4200(1.17)

    4700(1.31)

    82/71

    11Power (kW)/Air supply temp. (C) 36/59 42/56 47.8/54.2 52.7/52.3 57.3/50 61/49

    Wa te r ow ra te (l /h )/D P wa te r ( kP a) 29 40/ 8 3 41 0/ 11 3 830 /1 3. 3 42 30/ 16 4 600 /18 .7 49 50/ 22

    15Power (kW)/Air supply temp. (C ) 34/60.6 39/58 44.5/55.8 49.1/54 53.4/52.4 57.4/50.9

    Wa te r ow r at e ( l/h )/D P wa te r ( kP a) 27 30/ 7 31 70/ 9. 3 3 570 /1 1. 6 39 40/ 14 4 28 0/1 6 46 00/ 19

    90/70

    11P ow er (k W) /A ir su pp ly te mp . ( C ) 3 7. 9/ 61 .3 4 3. 7/ 58 .3 4 9. 1/ 55 .8 5 4. 1/ 53 .7 5 8. 7 / 51 .8 6 3. 1/ 50 .2

    Water ow rate (l/h)/DP water (kPa) 1670/3 1930/4 2170/5 2390/6 2590/7 2790/8

    15P ow er ( kW )/ Ai r s up pl y t em p. ( C ) 3 5. 3/ 62 .7 4 0. 8/ 59 .8 4 5. 8/ 57 .5 5 0. 4/ 55 .4 5 4. 7/ 53 .7 5 8. 8/ 52 .2

    Water ow rate (l/h)/DP water (kPa) 1560/3 1800/4 2020/4 2230/5 2420/6 2600/7

    45/40

    11P owe r ( kW )/A ir s u pp ly t e mp . ( C) 17 .3 /3 4 20 .1/ 32. 7 2 2. 6/ 31 .6 24 .9 /3 0. 6 2 7.1 /29 .8 29 .1 /2 9.1

    Water ow rate (l/h)/DP water (kPa) 3010/10 3500/12 3940/15 4340/18 4720/22 5070/24

    15P owe r ( kW )/A ir su pp ly te mp . ( C ) 1 4. 9/3 5. 1 1 7. 3/ 34 1 9. 4/3 3 21 .4 /3 2. 2 2 3.3 /31 .5 25 .1 /3 0.8

    Water ow rate (l/h)/DP water (kPa) 2600/7 3010/10 3380 /11 3730/14 4060/16 4370/19

    60/50

    11P owe r ( kW )/A ir s up pl y t em p. ( C ) 24 /4 3 27 .9/ 41. 1 3 1. 3/ 39 .5 34 .5 /3 8. 2 3 3.6 /38 .8 40 .3/ 36

    Water ow rate (l/h)/DP water (kPa) 2110/5 2440/6 2740/8 3020/9 2940/9 3530/12

    15P owe r ( kW )/A ir s u pp ly t e mp . ( C) 2 1. 6/4 4. 2 2 5/4 2.5 2 8. 1/4 1. 1 30 .9 /3 9. 8 3 7.5 /37 .1 36 .2 /3 7. 9

    Water ow rate (l/h)/DP water (kPa) 1890/4 2190/5 2460/6 2700/8 3280/11 3170/10

    BE for e 3 nhanced and e 3 lite versions - Electric Heater Fresh Air 0C 0C -5C -10C -15C -20C

    Qv (m/h) 4800 4800 4800 4800 4800 4800

    Versione 3 ssential e 3 nhanced BE 025 e 3lite BE 025

    E lect ri c Hea te r P re -Hea te r + Pos t-Heat er

    Total power (kW) - 6.75 6.75 13.5 18 + 6.75 18 + 13.5

    Air supply Temp. (C) 16.6 20.8 20.3 19.7 20.9 20.9

    -5C / 90% HR

    +5C / 90% HR

    0C / 90% HR

    -10C / 90% HR

    300Pa

    250Pa

    250Pa

    200Pa

    300Pa200Pa150Pa

    150Pa

    300Pa200Pa

    200Pa

    R e t u r n a i r

    2 0 C / 5 0 %

    E f f i c i e n c y

    ( % ) - E N 3 0 8

    p e r f a n

    P o w e r c o n s u m p t

    i o n

    ( W )

    S t a t i c p r e s s u r e

    ( P a )

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    Flow rate (m 3 /h)

    80%

    70%

    60%

    50%40%

    30%

    Performance curves shown are based on the e 3nhanced or e 3lite product versions, with an Electric Post Heater fitted (i.e. BE variant).Performance (in terms of pressure) for the e 3ssential variant (with no heaters fitted) is approximately 25 Pa higher, while performance(in terms of pressure) for the e 3nhanced or e 3lite versions, with a Hot Water Post heater fitted (i.e. BC variant) is 45 Pa lower than the BE variant.

    Aerodynamic performance has been obtained from tests based upon EN 13053 and conform to ISO 5801.

    Max Fan Pressure is optimum for HVAC applications. Data for higher pressures is available on request.

    0. 39 0.50 0.61 0.72 0.83 0.94 1.06 1.17 1.28 1.39Flow rate (m 3 /s)

    0. 39 0.50 0.61 0.72 0.83 0.94 1.06 1.17 1.28 1.39Flow rate (m 3 /s)

    0. 39 0.50 0.61 0.72 0.83 0.94 1.06 1.17 1.28 1.39

    Flow rate (m3

    /s)

    0. 39 0.50 0.61 0.72 0.83 0.94 1.06 1.17 1.28 1.39Flow rate (m 3 /s)

    Notes:1) Coil air on temperatures are based on 2 scenarios, where the external air temperature onto the plate heat exchanger is either -5C/90% RH

    or 0C/90% RH, which typically result in plate heat exchange air off temperatures of 11C or 15C respectively, which we have then stated aswater coil air on temperatures.

    2) Rated kW Powers and coil air off temperatures stated above are max valves, so should not be used to calculate heating loads.

    Typical Plate Heat Exchanger Core Performance data

    Thermal performance data for the Counter-flow Plate Heat Exchanger core is basedon a nominal Air flow per unit (approx. 80% of maximum) and the foll owing air conditions:External air temperature: -5C @ 90% RH and Return air temperature: 22C @ 50% RH

    Model Air ow rate Recovered

    kW Air Off temp C / RHThermal

    Efficiency %m 3 /h m 3 /s

    Crown 90-6 3000 0.83 24.3 19.1C 16.4%RH 89.1

    NSC4 = Sound level at 4 m,in free field, intakes andoutlets connected up

    Watertemp

    (C/C)

    New airtemp(C)

    Flow rate (m/h) 2000 3000 4000 5000

    7/12

    32/40Power (kW)/Air supply temp. (C-%HR) 17.1/12.5-100 28.9/12.7-84 35.1/14.1-82 40.4/15.2-81

    Water flow rate (l/h)/DP water (kPa) 293 0/4 4950/10 60 20/1 4 6920 /17

    27/50Power (kW)/Air supply temp. (C-%HR) 13.0/12.5-100 22.3/12.5-88 27.0/13.5-88 30.9/14.4-85

    Water flow rate (l/h)/DP water (kPa) 223 0/3 3830/6 4620/9 5290 /11

    25/50Power (kW)/Air supply temp. (C-%HR) 9.9/12.3-100 17.9/12.3-87 21.4/13.3-85 24.2/14-84

    Water flow rate (l/h)/DP water (kPa) 1710/2 3070/4 3660/6 4150/7

    6/11

    32/40Power (kW)/Air supply temp. (C-%HR) 18.3/11.8-100 30.6/11.9-85 37.3/13.3-83 43.1/14.4-81

    Water flow rate (l /h)/DP water (kPa) 31 40/5 5230/11 6 390/15 7380 /20

    27/50Power (kW)/Air supply temp. (C-%HR) 14.2/11.7-100 24.1/11.6-88 29.3/12.8-86 33.6/13.7-85

    Water flow rate (l /h)/DP water (kPa) 24 40/3 4130/7 5 010/10 576 0/13

    25/50Power (kW)/Air supply temp. (C-%HR) 11.4/11.4-100 19.7/11.4-87 23.7/12.5-86 27.0/13.3-84

    Water flow rate (l/h)/DP water (kPa) 1950/2 3380/5 4060/7 4630/9

    CBX 6 BF for Chilled Water Module

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    11/13

    20

    Modulation Solutions Flow Rate Modulation

    HS air flow

    LS air flow

    Air flow

    HS constant air flow

    LS constant air flow

    Air flow

    CAV ECConstant Air Volume2 Constant Air flow Options

    VAV TB EC Variable Air Volume - Trickle & Boost Strategy2 Air flow rates - Low Speed/High Speed

    View of access to technica l compartment

    Access door to technical compartment

    features integral display and user interface.

    Remote control unit (optional)

    HS air flow

    LS air flow

    Air flow

    HS constant air flow

    Air flow

    LS constant air flow

    COP ECConstant Pressure Control

    All control options use EC motor technology

    VAV AQ EC Variable Air Volume/CO 2 sensor & EC FansProportional air flow control via CO 2 sensor

    CAV AQ ECConstant Air Volume/CO 2 sensor2 Constant Air flow options controlled byCO2 sensor

    The e 3 co Crown unit has a factory-programmable controller as standard, which can be used to configure how the airflow can be modulated:

    Constant pressure

    Air flow

    The e 3 co Crown ERU product includes an integral control panel with LCD displaymounted on the unit casing, and can be used to adjust time clocks, air flow rates,temperatures (proportional control of the internal bypass, internal hot water coil for BCversion or electric heater for BE version, Night cooling). Fault alarms are also displayed.

    Stop HS Stop LS HS Stop LS + LS HS Forced Stop

    e 3 co-Crown VAV TB EC

    Variable Air Volume control (2

    air flows) - Trickle and Boost

    Functions

    Clock Clock Clock + VF Contact #1Easy LCD display or

    remote control

    or or or or

    VF Contact #1 VF Contact #1 VF Contact #1 + VF Contact #1 VF Contact #1

    e 3 co-Crown CAV EC

    Constant Air Volume control (1 or

    2 air flows). EC Fans Fitted

    Clock Clock Clock + VF Contact #1Easy LCD display or remote

    control

    or or or or

    VF Contact #1 VF Contact #1 VF Contact #1 + VF Contact #1 VF Contact #1

    e 3 co-Crown COP EC

    Constant Pressure control at

    Variable Air flows. EC Fans Fitted

    Clock Easy LCD display or remote

    control

    or or

    VF Contact #1 VF Contact #1

    e 3co-Crown VAV AQ EC

    PROPORTIONAL Variable Air

    Volume control via CO 2 Sensor,

    between 2 adjustable air flows. EC

    Fans Fitted.

    Clock + 0-10V CO 2 ProbesEasy LCD display or remote

    control

    or or

    0-10V CO 2 Probes VF Contact #1

    e 3 co-Crown CAV AQ EC

    PROPORTIONAL control via CO 2 Sensor, between 2 Constant Air

    Volumes (adjustable #2). EC Fans

    Fitted.

    Clock + 0-10V CO 2 ProbesEasy LCD display or remote

    control

    or or

    0-10V CO 2 Probes VF Contact #1

    Notes :#1: Volt Free Contact can be either : Remote ON-OFF /

    ON-OFF CO 2 Probe / ON-OFF Humidity Probe

    #2 Except e 3co-Crown 90-1

    Control Function Options:

    Standard Function Optional Function

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    12/13

    22

    Sound Data Product Codes

    As standard, integrated controls can manage one or several heaters

    (depending on the unit version selected : e 3 ssential, e 3 nhanced or e 3 lite)

    Climate Solutions

    Integrated Coil

    CrownType

    Pre-Heating Heating

    Electric coil Electric coil Water water coil

    e 3 ssential - - -

    e 3 nhanced BC - -

    e 3 nhanced BE - -

    e 3 lite BC -

    e 3 lite BE -

    1 2 3 4 5 e 3 co-CROWN 90-1 L - P - W - Y e 3 ssential Controls

    e 3 nhanced BC/BE xxxe 3 lite BC/BE xxx

    1 - High Thermal Efficiency unit (90%) - complete with automatic control and Counter Flow Plate Heat Exchange r

    2 - Unit Model Code Examples:

    90 -1 Efficiency = 90 %, Unit size = 1 (0.22 m 3 /s)

    90 -5 Efficiency = 90 %, Unit size = 5 (1.00 m 3 /s)

    3 - Unit Configuration Options:

    L & P: Side-by-Side format (except unit model 90-6)

    W & Y: Double Deck format

    4 - Unit Version Options:

    e 3 ssential Unit with NO coils fitted

    e 3 nhanced BC Hot water coil (POST Heater) plus appropriate controls fitted

    e 3 nhanced BE xxx Electric heater (POST Heater) plus appropriate controls fitted

    e 3 lite BC Unit with Electric PRE-Heater and hot water POST Heater plus controls

    e 3 lite BE xxx Unit with Electric PRE-Heater and Electric POST heater plus controls

    For BE versions, the xxx relates to the power rating of the electrical heater. Options shown below:

    BE 025 = 2.50 (single phase)

    BE 037 = 3.70 (single phase)

    BE 052 = 5.25 (three phase)

    BE 067 = 6.75 (three phase)BE 082 = 8.25 (three phase)

    BE 105 = 10.5 (three phase)

    BE 135 = 13.5 (three phase)

    5 - Controls:

    VAV TB EC (Std) - Variable Air Volume Trickle and Boost

    VAV AQ EC - Variable Air Volume and CO 2 Sensor

    CAV EC - Constant Air Volume

    CAV AQ EC - Constant Air Volume and CO 2 Sensor

    COP EC - Constant Pressure - All motors are EC Type

    All units feature EC motors

    Accessory Options Weather Roof

    Code: WR

    For Outdoor installation.Pre-Painted Steel

    (RAL 7035)

    Motorized DamperCode: MD

    For Unit shut-off andFrost protection.

    Features Opposed blades

    Rain CowlCode: RC

    Complete with safety grille(bird guard)

    Constructed fromGalvanised Steel

    Support Legs (set of 4)Code: SLK

    Can be used instead ofIntegral mounting brackets

    Flexible ConnectorsCode: FC MO

    Circular: 315 to 630mm

    ElectroValve KitCode: EVK

    0-10V motorized 3 way valvefor used with e 3 nhanced

    and e 3 lite BCAvailable IP 41 or IP 54

    Damper MotorCode: DA

    Open / Closed 24V Servo Motor to control

    Fresh air damper and toprovide Frost protection

    Remote ControlCode: RC-10ML

    Additional LCD displayCan be used local to Easy

    Control compartment or remote (10m) from unit

    BMS Controller UnitCode: BCU

    Controller with LON orTCP/IP BMS protocol

    Control Repeater UnitCode: CRU

    Repeater unit used toBooster control signal

    between 10m and 1kmfrom unit

    Acoustic data has been obtained from tests based upon the EN 13053 standard

    External Chilled waterCoil Section - Code: CBX-BF

    orExternal DX Coil Section

    Code: CBX-DX

    Summer/Winter ChangeoverThermoStat

    For use with CBX-BF

    ModelIn-duct Sound Power Levels (Supply Air and Exhaust Air Connections) Breakout

    dBA @3m

    SFP63 Hz 125 Hz 250 Hz 500 Hz 1 KHz 2 KHz 4 KHz 8 KHz Lw LwA

    Crown 90-1 66 65 67 68 64 59 56 56 73 69 33 0.85

    Crown 90-2 64 65 66 69 64 58 57 61 74 70 34 0.88

    Crown 90-3 66 69 70 68 68 60 57 55 76 71 35 0.72

    Crown 90-4 65 69 71 68 67 60 57 55 76 71 35 0.72

    Crown 90-5 65 72 73 72 69 66 63 65 78 74 39 1.06

    Crown 90-6 70 78 79 78 75 73 70 72 85 81 45 1.01

  • 8/13/2019 e 3co Crown ERU - Techinical Catalogue

    13/13

    Flkt Woods Group SA 18, avenue Louis Casa, CH-1209 Geneva, SwitzerlandTel. +41 22 309 3800email [email protected] www.flaktwoods.com

    Flkt Woods operates a policy of continuous improvement and reserves the right to supply products that may differ fromFlkt Woods operates a policy of continuous improvement and reserves the right to supply products that may differ from

    Flkt Woods Group - Ventilation Solutions

    The Flkt Woods Group is divided into three businesses:

    Global Infrastructure and Industry (GII)A leader for Air Movement using fans to improve performance of equipment and industrialprocesses

    Air Climate Solutions (ACS)A worldwide HVAC leader recognized by our customers as a provider of superior Air ClimateSolutions combining Indoor Air Quality and Energy Ef ciency applied to speci ed buildings

    Ventilation Solutions (VS)A European Ventilation Specialist Servicing our customers with a complete range of

    ventilation products focused on Non residential buildings. For more speci c productinformation for Ventilation Solutions, please visit :

    www.vsecatalogue.flaktwoods.com

    Flkt Woods LimitedAxial Way, ColchesterEssex, C04 5ZDUNITED KINGDOMTel: +44 (0)1206 222 555Fax: +44 (0)1206 222 777E-mail: [email protected]

    Flkt Woods OyKalevantie 39FI-20520TurkuFINLANDTel: +358 20 442 3000Fax: +358 20 442 3018E-mail: [email protected]

    Flkt Woods OyHmeentie 23FI-37800ToijalaFINLANDTel: +358 20 442 3500Fax: +358 20 442 3502E-mail: [email protected]

    Flkt Woods ABGesllgatan 17745 39EnkpingSWEDENTel: +46 36 19 30 00Fax: +46 17 12 40 97E-mail: [email protected]

    Flkt Woods ABKung Hans vg12 192 68, SollentunaSwedenTel: +46 (0)771 26 26 26Fax: +46 (0)8 626 73 10E-mail: [email protected]

    Flkt Woods ABFlktvgen 2, Box 84153 22JrnaSWEDENTel: +46 8-551795 00Fax: +46 8-551744 80E-mail: [email protected]

    Flkt Woods4 Avenue LaurentCELY-Batiment C - Etage 3Asnieres Sur Seine92600 FRANCETel: +33 1 80 21 07 00Fax: +33 1 80 21 07 00E-mail: [email protected]

    Flkt Woods Ventilatoren GmbHAm Sportplatz 4DE-40882RatingenGERMANY Tel: +49 2012 61038 11Fax: +49 2102 61038 18E-mail: [email protected]

    Flkt Woods SpA Via Pacinotti, 28IT-20092, Cinisello BalsamoITALY Tel: +39 02 6186 6091Fax: +39 02 6186 0947E-mail: [email protected]

    Flkt Bovent Sp. z o.o.Panattoni Park Pruszkw IIul. Poudniowa 2, Otarzew05-850 O arw MazowieckiPOLANDTel: +48 22 392 43 43Fax: +48 22 392 43 44E-mail: [email protected]

    LLC Flkt Industrial& Building Systems23, ul. ProfsojuznayaRU-117418 MoscowRUSSIATel: +7 (495) 589-31-08Fax: +7 (495) 589-31-74E-mail: [email protected]

    V S / E R U C T B G R O U P - 0

    4 / 0 4 1 3