enr458 presentation spring2013

Upload: akira-zamudio

Post on 04-Jun-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 ENR458 Presentation SPRING2013

    1/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    2/75

    Agenda

    What is Distribution System Protection?

    System Protection Considerations.

    Why do we care?

    Commonly used Distribution Protective Devices.

    Distribution Protection Basic Concepts.

    Information/data required to perform a Study. Review of Hospital Case Study.

    Miscoordination Case Study.

    Conclusion/Questions?

  • 8/13/2019 ENR458 Presentation SPRING2013

    3/75

    Distribution System Protection involves the selection,

    arrangement, installation and programming ofprotective devices selectively coordinated to limitthe effects of an overcurrent (short-circuit) situationto the smallest area by clearing a fault in the

    minimum amount of time possible, while minimizingthe impact to customers and the electric distributionsystem.

    WhatisDistributionSystemProtection?

  • 8/13/2019 ENR458 Presentation SPRING2013

    4/75

    SystemProtectionDesignCriteria

    Reliability: System operates as designed.

    o Security: Dont trip when you shouldnt.

    o Dependability: Trip when you should.

    o Safety: Preventing hazards to the public by isolatingand removing a faulted section from the system.

    Selectivity: Trip the minimal amount to clear the fault orabnormal operating condition.

    Speed: Usually the faster the better in terms of minimizingequipment damage and maintaining system integrity.

    Economics: Dont break the bank while maintaining ability

    to operate correctly under all predictable power systemconditions.

  • 8/13/2019 ENR458 Presentation SPRING2013

    5/75

    What isthefirstconsiderationwhen

    designingSystemProtection?

    Is what results from a short caused by lowimpedance and a three phase bolted,phase-to-phase or phase-to-groundconnection.

    Passes through all the components in theaffected circuit path.

    Is often several orders of magnitude

    greater than normal operating current. Needs to be interrupted or it can destroy

    insulation, melt metal, start fires, or causeexplosion if arcing occurs.

    FAULT CURRENT

  • 8/13/2019 ENR458 Presentation SPRING2013

    6/75

    What isthesecondconsiderationwhen

    designingSystemProtection?

    TIME

    High-speed fault clearance with correctselectivity.

    High Sensitivity to faults and insensitivity to

    maximum load currents. The more time a protection scheme allows,

    the greater the flexibility, if a fuse blowsinstead of a circuit breaker opening, a lotfewer customers are affected.

  • 8/13/2019 ENR458 Presentation SPRING2013

    7/75

    Selection of protective devicesrequires compromises: Protection isdesigned to be as inexpensive aspossible. Maximum and Reliableprotection at minimum equipmentcost.

    Minimum standards vary. A circuit toa hospital needs greater reliabilitythan a circuit to a shopping center.

    Cost of protective devices should bebalanced against risks involved ifprotection is not sufficient and not

    enough redundancy is provided.

    Whatisthethirdconsiderationwhen

    designingSystemProtection?

    COST

  • 8/13/2019 ENR458 Presentation SPRING2013

    8/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    9/75

    WhatisaShortCircuit?

    A short circuit orfault current is a

    path of lowimpedance whichallows an abnormally

    high amount ofcurrent to flow. Thisfault current if notinterrupted, can

    cause catastrophicdamage to electricalequipment.

  • 8/13/2019 ENR458 Presentation SPRING2013

    10/75

    MostCommonFaultTypesonDistributionSystem

    Three-phase

    Phase-to-ground

    Phase-to-phase

    X

    X

    Z

    Z

    Z

    G

    BC

    A

    X

    X

    Z

    Z

    Z

    G

    BC

    A

    Z

    Z

    Z

    G

    BC

    A

    X

    X

    X

  • 8/13/2019 ENR458 Presentation SPRING2013

    11/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    12/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    13/75

    Polesknockeddownduringastorm

  • 8/13/2019 ENR458 Presentation SPRING2013

    14/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    15/75

    MylarBalloonscaughtinPowerLines

  • 8/13/2019 ENR458 Presentation SPRING2013

    16/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    17/75

    Groundsleft

    connectedinside

    switchgearcompartment

    atsubstation.

  • 8/13/2019 ENR458 Presentation SPRING2013

    18/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    19/75

    MostCommonProtectiveDevicesusedon

    DistributionCircuits

    Feeder Circuit Breaker

    Line Recloser

    Subsurface Fault Interrupter

    Fuses both Overhead and Underground

  • 8/13/2019 ENR458 Presentation SPRING2013

    20/75

    Substation12kVCircuitBreaker

  • 8/13/2019 ENR458 Presentation SPRING2013

    21/75

    Substation12kVCircuitBreaker

  • 8/13/2019 ENR458 Presentation SPRING2013

    22/75

    SubstationFeederRelay

  • 8/13/2019 ENR458 Presentation SPRING2013

    23/75

    ElectromechanicalRelays

    Have moving parts.

    Can get out ofadjustment.

    Can wear out.

    Have broad tripping

    ranges. Have Tap and Lever

    settings.

    Best approximation ofprotection.

  • 8/13/2019 ENR458 Presentation SPRING2013

    24/75

    MicroprocessorbasedRelays

    Have multiple functions.

    Can be utilized for SCADAoperating.

    Provide present and previous faultdata.

    Provide fault locating capability.

    Can be accessed remotely toprovide fault data/location and orchange settings.

    Have very specific trip ranges.

    Easy to test.

    Easy to install settings and settingchanges.

  • 8/13/2019 ENR458 Presentation SPRING2013

    25/75

    SubstationFeederRelays

    Device 50/51- ThreeSingle Phase

    Time/ InstantaneousPhase Overcurrent

    Relays

    Device 50G/51GTime/ InstantaneousGround OvercurrentRelay

    Device 79Reclosing Relay

  • 8/13/2019 ENR458 Presentation SPRING2013

    26/75

    TypicalNumberofCBAutomaticReclosing

    Two Tests (Three Shots to Lock-Out): Used for overhead andcombination overhead / underground circuits. With reclosing

    interval times of 5 and 20 seconds.

    Zero or One Test (One or Two Shots to Lock-Out): Used forexclusively underground circuits. One test (two shots) shouldbe considered on underground circuits with exposure due to

    risers. The reclose time can be between 10 and 20 seconds. Zero or one test is a very helpful way of reducing I2T since it is

    cumulative.

    With a generation facility located on the load side of a line

    recloser, the first reclosing time must be equal to or greaterthan 10 seconds.

  • 8/13/2019 ENR458 Presentation SPRING2013

    27/75

    Line

    RecloserReclosers are overhead pole mounted protective deviceswhich combine:

    Three-phase oil or vacuum circuit breaker withcapabilities for closing into or interrupting faults.

    Phase relay protection and ground relay protection.

    Reclosing capabilities. Typically set for two tests(three shots to lockout) at 5, 10 and 15 second intervals.

    A combination of slow and fast curves for fuse savingand other features.

  • 8/13/2019 ENR458 Presentation SPRING2013

    28/75

    PoleMountedAutomaticLineRecloser

  • 8/13/2019 ENR458 Presentation SPRING2013

    29/75

    PoleMountedAutomaticLineRecloser

  • 8/13/2019 ENR458 Presentation SPRING2013

    30/75

    LineRecloser&

    Controller

  • 8/13/2019 ENR458 Presentation SPRING2013

    31/75

    SubsurfaceFaultInterrupters

    Three phase subsurface, underground vacuum oroil insulated device.

    Capabilities for testing into and interrupting faults.

    One shot to lock out.

    Three phase and ground protection.

  • 8/13/2019 ENR458 Presentation SPRING2013

    32/75

    SubsurfaceFaultInterrupter

  • 8/13/2019 ENR458 Presentation SPRING2013

    33/75

    SubsurfaceFaultInterrupter

  • 8/13/2019 ENR458 Presentation SPRING2013

    34/75

    Subsurface

    Interrupter

    installed

    in

    Underground

    Vault

  • 8/13/2019 ENR458 Presentation SPRING2013

    35/75

    Fuses

    Fuses are low cost automatic sectionalizing devices.They have fault sensing and interruption capability

    but, obviously, lack automatic reclosing capability.

    Two fundamental different types of fuses in distributionsystems:

    Expulsion for Overhead Applications.

    Current limiting for Underground Applications.

  • 8/13/2019 ENR458 Presentation SPRING2013

    36/75

    Overhead

    Fuse

    Types The two typical types of fuses commonly used on

    the overhead for line protection, are T Fuses and E

    fuses. The decision to use T or E fuses is based onthe asymmetrical fault duty at the fuse location andcoordination.

    If an E fuse will coordinate with the source side

    device where a T fuse will not, then an E fuse couldbe used.

    Other types of Fuses are used for fusing in fire

    danger areas, transformer fusing, and capacitorfusing.

  • 8/13/2019 ENR458 Presentation SPRING2013

    37/75

    65Evs.65TFuses

  • 8/13/2019 ENR458 Presentation SPRING2013

    38/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    39/75

    PoleMountedFusedCutoutsProtectingCapacitorBank

  • 8/13/2019 ENR458 Presentation SPRING2013

    40/75

    PoleMountedFusedCutoutsProtecting3singleTransformers

  • 8/13/2019 ENR458 Presentation SPRING2013

    41/75

    NoteonUndergroundFuseApplication

    There are typically two types of fuses used in the undergroundsystem:

    Current limiting fuses E fuses.

    Existing underground radial and looped taps should be fused tocorrect I2t and service reliability problems.

    Ground coordination is essential with these devices because mostinitial faults in the underground are line to ground faults.

    It is not a good practice to install fuses of any type on the load side ofcurrent limiting fuses. Although they may appear to coordinate perthe fuse curves there may be miscoordination at the higher fault

    currents. If possible, current limiting fuses should be used to minimize cable

    damage. However, it is acceptable to use E fuses to obtaincoordination or to accommodate loading.

  • 8/13/2019 ENR458 Presentation SPRING2013

    42/75

    SubsurfaceFusedSwitch

  • 8/13/2019 ENR458 Presentation SPRING2013

    43/75

    SubsurfaceFusedSwitchshowingFuseWells

  • 8/13/2019 ENR458 Presentation SPRING2013

    44/75

    DistributionProtection: BasicConcepts

    Minimum Time Coordination Interval

    Minimum to TripCurrent and Potential transformer ratio

    Time/Current Inverse Curves

    Zones of ProtectionMost Commonly used Relays

  • 8/13/2019 ENR458 Presentation SPRING2013

    45/75

    Coordination

    Time

    Between

    Protective

    DevicesA coordinating time should be allowed betweencharacteristic curves of protective devices installed in

    series. This is to allow a margin for any of the following: Breaker time.

    Relay over-travel.

    Current transformer errors.

    Variation from published curves of devices due tomanufacturing Tolerances or actual relayperformance.

    Errors of short-circuit current due to small variationsin voltage.

    Errors due to tolerance in system data.

  • 8/13/2019 ENR458 Presentation SPRING2013

    46/75

    Timeittakestoclearafault

    1 second = 60 Cycles

    1 cycle = 1/60 = 0.0167 secCircuit Breakers take approx. 5 cycles (0.083sec) from relay sensing to circuit interruption.

    Power Fuses typically require no more than 1cycle (.016 sec) for circuit interruption.

  • 8/13/2019 ENR458 Presentation SPRING2013

    47/75

    Mi i ti di ti i t l

  • 8/13/2019 ENR458 Presentation SPRING2013

    48/75

    Minimumtimecoordinationinterval

    BT

    I

    A

    Typical CB Opening Time = 5 Cycles (0.083 sec)

    +

    Induction Disc Overtravel of EM relays = 6 Cycles(0.1 sec)

    Minimum Safety margin = 12 Cycles(0.2 sec)

    Mi i T T i

  • 8/13/2019 ENR458 Presentation SPRING2013

    49/75

    The Minimum To Trip (MTT) is the minimum amount ofcurrent it takes a relay to trip.

    In the illustration below, the fuses on the threephases should trip before the Line Recloser (LR), andCircuit Breaker so the LRs and CBs relay MMT is setat a higher current.

    MinimumToTrip

  • 8/13/2019 ENR458 Presentation SPRING2013

    50/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    51/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    52/75

    TimeCurrentCurves(TCC)

    Current (Multiples of pick-up)

  • 8/13/2019 ENR458 Presentation SPRING2013

    53/75

    ZonesofProtection

    Are based on protective device timing.

    The closer the fault occurs to a C ircuitBreaker or Line Recloser, the more likelythe protection will trip instantaneously.

    Zones of Protection

  • 8/13/2019 ENR458 Presentation SPRING2013

    54/75

    CB LR

    Phase A

    Phase B

    Phase C

    X

    XX

    3,000Customers

    Lost

    1,500Customers

    Lost

    150Customers

    Lost

    Zones of ProtectionFuses

  • 8/13/2019 ENR458 Presentation SPRING2013

    55/75

    CommonlyUsedRelays

    Device 25 Synchronizing or Synch Check Relay

    Device 27 Undervoltage Relay

    Device 32 Directional or Reverse Power Relay Device 50 AC Phase Instantaneous Overcurrent Relay

    Device 50G AC Ground Instantaneous Overcurrent Relay

    Device 51 AC Phase Time Overcurrent Relay

    Device 51G AC Ground Time Overcurrent Relay

    Device 59 Overvoltage Relay

    Device 67 AC Directional Overcurrent Relay

    Device 79 AC Reclosing Relay Device 81U Underfrequency Relay

    Device 81O Overfrequency Relay

    Device 87 Differential Relay

  • 8/13/2019 ENR458 Presentation SPRING2013

    56/75

    Current Transformers

  • 8/13/2019 ENR458 Presentation SPRING2013

    57/75

    Current transformers are used to step down primary systemcurrents to values usable by relays, meters, SCADA, etc.

    CT ratios are expressed as primary to secondary; 2000:5, 1200:5,800:5, 600:5, 400:5, 200:5, etc.

    A 1200:5 CT has a CT Ratio of 240.

    CT Saturation: Select the CT ratio and burden so the CT will notbe saturated because of high currents and/or high secondaryvoltage.

    Current Transformers

    S d d IEEE CT R l A

  • 8/13/2019 ENR458 Presentation SPRING2013

    58/75

    IEEE relay class is defined in terms of the voltage a CT can

    deliver at 20 times the nominal current rating withoutexceeding a 10% composite ratio error.

    For example, a relay class of C100 on a 1200:5 CT meansthat the CT can develop 100 volts at 24,000 primary amps

    (1200*20) without exceeding a 10% ratio error. Maximumburden = 1 ohm.

    100 V = 20 * 5 * (1ohm)

    200 V = 20 * 5 * (2 ohms)400 V = 20 * 5 * (4 ohms)

    800 V = 20 * 5 * (8 ohms)

    Standard IEEE CT Relay Accuracy

  • 8/13/2019 ENR458 Presentation SPRING2013

    59/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    60/75

  • 8/13/2019 ENR458 Presentation SPRING2013

    61/75

    CT SaturationCalculationExample

  • 8/13/2019 ENR458 Presentation SPRING2013

    62/75

    p

    I Asymmetrical 3: 8630 Amps CT Class: C20

    I Line-Ground: 4490 Amps CT Ratio: 600:5 = 120

    CT Burden: 0.285 Ohms

    Wiring Burden: 0.024 Ohms

    Relay Burden: 0.0108 Ohms

    Total Burden=Relay Burden + Wiring Burden + CT Burden

    Total Burden: 0.285 + 0.024 + 0.0108 = 0.3198 Ohms

    Maximum Symmetrical Secondary Current = Maximum Fault Duty/CT Ratio

    Maximum Symmetrical Secondary Current: 8630/ 120 = 71.92 Amps

    Maximum Symmetrical Secondary Voltage Produced = Maximum Sym. Secondary Current x Total Burden

    Maximum Symmetrical Secondary Voltage Produced:71.92 x 0.3198

    = 23.00 Volts

    CT Will Saturate

    CT SaturationCalculationExample

  • 8/13/2019 ENR458 Presentation SPRING2013

    63/75

    p

    AdditionalInformationCT Burden value can usually be found on CT excitation curve or on manufacturer's cut sheet.

    Wiring Burden can be calculated if size and length of wire is known.

    Example: 20 ft of #10AWG wire in CT circuit (1.21 ohm/1000 ft per NEC) = 0.024 ohm

    Relay burden value can usually be found on manufacturer's cut sheet or relay manual.

    If Relay burden value is given in VA's convert to Ohms.

    Example: SEL-351 relay burden per SEL Manual (0.27VA@5A) = 0.27/5^2 = 0.0108 ohms.

  • 8/13/2019 ENR458 Presentation SPRING2013

    64/75

    Hospital Case Study

  • 8/13/2019 ENR458 Presentation SPRING2013

    65/75

    HospitalCaseStudy

  • 8/13/2019 ENR458 Presentation SPRING2013

    66/75

    ShortCircuitStudy

  • 8/13/2019 ENR458 Presentation SPRING2013

    67/75

    y

    Provides fault duty information required forproperly setting overcurrent devices.

    Ensures adequately sized protectionprevents exceeding the AmpereInterrupting Capacity or (AIC) rating ofelectrical equipment which refers to themaximum level at which the equipmentcan safely interrupt or withstand fault orshort circuit" currents in order to prevent

    catastrophic damage to the equipment.

    Performed when utilitys available faultduty is increased.

    Performed when substantial systemmodifications are planned i.e. new feederor generation is installed.

    Assists in conceptual design.

    Transmission115kV

    Bus12.47kV

    BUS712.47kV

    BUS612.47kV

    BUS012.47kV

  • 8/13/2019 ENR458 Presentation SPRING2013

    68/75

    Phase

  • 8/13/2019 ENR458 Presentation SPRING2013

    69/75

    PhaseProtectiveDevice

    Coordination

    1200:5

    51

    50

    Ground

  • 8/13/2019 ENR458 Presentation SPRING2013

    70/75

    GroundProtectiveDevice

    Coordination

    1200:5

    51N

    50N

  • 8/13/2019 ENR458 Presentation SPRING2013

    71/75

    MiscoordinationCaseStudy Electric service interruption to 4,881 customers

    due to miscoordination between protectivedevices.

    Had devices been selectively coordinated,outage could have been limited to only 420

    customers. Minimum time coordination interval between

    fuses may have extended outage to 1,005customers.

    Relatively low fault duty magnitude of 1,596 AmpsLine-to-Ground contributed to miscoordination.

  • 8/13/2019 ENR458 Presentation SPRING2013

    72/75

    Automatic Line Recloser

    Operated interrupting service to4,881 customers.

    50T Fuse failed to blow andinterrupt fault. 420 customerspast this point in circuit.

    Location of section ofunderground cable that failed.Line to ground fault withmagnitude of 1,596 Amps.

    65T Fuse failed to blow andinterrupt fault. 1.005 customerspast this point in circuit.

    TCC Showing Miscoordination

  • 8/13/2019 ENR458 Presentation SPRING2013

    73/75

    TCC Showing Miscoordination

    between Fuses and LineRecloser.

    Given the fault dutymagnitude of 1,596 Amps

    Line to Ground, the LineRecloser was operatingbefore allowing the 50T or 65Tfuses to blow.

    Notice the overlap between

    the two fuses. Removing theLine Recloser from theequation, the possibility existsthat both fuses could haveblown during the fault.

    Conclusions

  • 8/13/2019 ENR458 Presentation SPRING2013

    74/75

    The use of TCC Curves as agraphical technique to illustrateproactive device coordination

    makes it easy to demonstratewhether or not coordination hasbeen obtained by the devicesettings and whether theyadequately protect thedistribution equipment.

    Once you become accustomedto reading these curves, thesystem evaluation can be donerelatively quickly.

  • 8/13/2019 ENR458 Presentation SPRING2013

    75/75

    Questions?Thanks for your time!