final report - 289 blessed trinity · assessment – final report on blessed trinity catholic...
TRANSCRIPT
FINAL REPORT
Asbestos-Containing Building Material Assessment
Toronto Catholic District School Board
Blessed Trinity Catholic School,
3205 Bayview Avenue
North York, Ontario
PROJECT NO. 1025760
PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board
80 Sheppard Avenue East Toronto, Ontario
M2N 6E8
FOR Asbestos-Containing Building Materials Assessment – Final Report
ON Blessed Trinity Catholic School 3205 Bayview Avenue
North York, Ontario
March 3, 2008
Jacques Whitford
7271 Warden Avenue
Markham, Ontario
L3R 5X5
Phone: 905-474-7700
Fax: 905-479-9326
www.jacqueswhitford.com
© 2008 PROJECT 1025760 March 3, 2008 i
EXECUTIVE SUMMARY
Jacques Whitford Limited (Jacques Whitford) was commissioned by the Toronto Catholic District
School Board (TCDSB) to conduct an Asbestos-Containing Building Materials Assessment of Blessed
Trinity Catholic School, located at 3205 Bayview Avenue in North York, Ontario.
The purpose of the assessment was to assist the TCDSB to meet the requirements of the new
asbestos regulation, Ontario Regulation 278/05 made under the Occupational Health and Safety Act
(OHSA), effective November 1, 2005. The assessment also includes the identification of asbestos-
containing materials (ACMs) that may require special attention.
The assessment was performed for the purposes of long term management of asbestos, and not for
construction or renovations purposes. Additional intrusive testing may be required prior to using this
information for construction or renovation.
The work was carried out in accordance with the requirements of the OHSA.
Based on visual assessment and laboratory analysis, asbestos-containing materials were identified to
be present at the subject facility. Table 1 below provides a summary of the materials identified and
recommendations on their management.
Table 1 – Summary of Findings and Recommendations
Issue Comments Recommendation
Asbestos Friable asbestos-containing materials were identified to be present in the form of insulating cement on pipe fittings, and stucco texture coat. These materials were observed to be in good condition.
Non-friable asbestos-containing materials were identified to be present in the form of 12”x12” vinyl floor tiles and 9”x9” vinyl floor tiles. These materials were observed to be in good condition.
Presumed asbestos-containing materials (PACMs) were identified to be present in the form of caulking materials, roofing materials, mastics and chalkboards. These materials were observed to be in good condition and were not sampled to preserve their integrity.
Prior to demolition or renovation work, undertake testing of presumed asbestos-containing materials to determine their asbestos content.
Asbestos-containing materials should be removed prior to the start of renovation work that may impact the material, in accordance with O. Reg. 278/05.
Should a material suspected to contain asbestos fibres become uncovered during demolition or renovation activities, all work in the areas that may disturb the material should be stopped. Samples of the suspect material should be submitted for laboratory analysis to determine if asbestos fibres are present. Confirmed asbestos materials should be handled in accordance with O. Reg. 278/05.
The statements made in this Executive Summary text are subject to the same limitations included in the
Closure Section 8.0, and are to be read in conjunction with the remainder of this report.
© 2008 PROJECT 1025760 March 3, 2008 ii
Table of Contents
EXECUTIVE SUMMARY ............................................................................................................ i
Asbestos-Containing Building Materials Assessment ......................................................... 1
1.0 INTRODUCTION ..................................................................................................................... 1 1.1 Assessment Objectives ........................................................................................................... 1 1.2 Scope of Work ......................................................................................................................... 1
2.0 ASSESSMENT METHODOLOGY........................................................................................... 2
3.0 ASSESSMENT LIMITATIONS ................................................................................................ 2
4.0 REGULATORY FRAMEWORK .............................................................................................. 3
5.0 ASSESSMENT RESULTS AND DISCUSSION....................................................................... 4 5.1 Friable Asbestos-Containing Materials .................................................................................... 4 5.2 Non-Friable Asbestos-Containing Materials ............................................................................. 5 5.3 Presumed Asbestos-Containing Materials ............................................................................... 5 5.4 Non-Asbestos-Containing Materials ........................................................................................ 5
6.0 RECOMMENDATIONS ........................................................................................................... 5
7.0 CLOSURE ............................................................................................................................... 6
List of Tables
Table 1 – Summary of Findings and Recommendations .................................................................... i
List of Appendices
APPENDIX 1 Floor Plans Showing Locations of Asbestos-Containing Materials ...................... 1 APPENDIX 2 Summary of Results of Analysis of Bulk Samples for Asbestos Content ............. 2 APPENDIX 3 Summary of Occurrences of Asbestos-Containing Materials ............................... 3 APPENDIX 4 Laboratory Analytical Report – Asbestos: Polarized Light Microscopy ................. 4 APPENDIX 5 Evaluation Criteria for Assessing Asbestos-Containing Materials ........................ 5 APPENDIX 6 Terms and Definitions ......................................................................................... 6
© 2008 PROJECT 1025760 March 3, 2008 1
ASBESTOS-CONTAINING BUILDING MATERIALS ASSESSMENT
1.0 INTRODUCTION
Jacques Whitford Limited (Jacques Whitford) was commissioned by the Toronto Catholic District
School Board (TCDSB) to conduct an Asbestos-Containing Building Materials Assessment of Blessed
Trinity Catholic School, located at 3205 Bayview Avenue in North York, Ontario.
The purpose of the assessment was to assist the TCDSB to meet the requirements of the new
asbestos regulation, Ontario Regulation 278/05 made under the Occupational Health and Safety Act
(OHSA), effective November 1, 2005. The assessment also includes the identification of asbestos-
containing materials (ACMs) that may require special attention.
The assessment was performed for the purposes of long term management of asbestos, and not for
construction or renovations purposes. Additional intrusive testing may be required prior to using this
information for construction or renovation.
The work was carried out in accordance with the requirements of the OHSA.
1.1 Assessment Objectives
The objective of the assessment was to:
� prepare an assessment report that identifies asbestos-containing materials present at the subject facility; and,
� provide recommendations for the management of these materials.
1.2 Scope of Work
The scope of work for this assessment involved the following:
� a “room-by-room” visual assessment of readily accessible room spaces of the subject facility for the presence of asbestos-containing building materials;
� an inventory of building materials/components that are suspected to contain asbestos;
� the collection of representative bulk samples from building materials suspected of containing asbestos fibres;
� laboratory analysis for the determination of the type and concentration of asbestos present in the samples submitted; and,
� preparation of a report documenting the results of the assessment, providing an interpretation of the laboratory analysis results and recommendations for the management of any asbestos containing materials.
© 2008 PROJECT 1025760 March 3, 2008 2
2.0 ASSESSMENT METHODOLOGY
A room-by-room visual assessment of the subject facility was made in order to check for the presence
of materials suspected of containing asbestos.
During the assessment, locations to collect discrete bulk asbestos samples of suspect building
materials were identified. Samples of representative materials were then collected at these locations in
accordance with the requirements of Ontario Regulation 278/05 made under the Occupational Health
and Safety Act.
An assessment of the condition, accessibility and exposure risk was completed for each occurrence of
an asbestos-containing material. The Public Works and Government Services Canada (PWGSC)
document entitled “Deputy Ministers Directive 057 – Asbestos Management” (Last Revised June 16th,
1999) was used as the basis for the criteria that was applied in evaluating the presence of asbestos-
containing materials at the subject areas, where applicable.
Samples of suspect ACMs from various building materials were collected and submitted to EMSL
Laboratories Inc. (EMSL) located in Westmont, New Jersey, for analysis using Polarized Light
Microscopy (PLM) with dispersion staining. The analysis was conducted following the U.S. EPA/600/R-
93/116 Methods. EMSL is certified under the National Voluntary Laboratory Accreditation Program
(NVLAP) to perform asbestos analysis of bulk samples.
The number of bulk samples was based on the requirements of the new asbestos regulation that
specifies the minimum number of samples of a particular building material that should be collected and
tested to consider a material non-asbestos-containing. A positive stop option was used during the
laboratory analysis of the building materials suspected to contain asbestos. Multiple samples of
visually similar material were collected and submitted for laboratory analysis.
The positive stop option involves testing a series of samples from a particular building material until test
results indicate the presence of asbestos. When this occurs, the remaining samples are not tested.
This is a cost effective method of limiting the number of samples that are ultimately tested.
Additionally, materials that had been previously sampled and identified to contain asbestos were
referenced from available reports and not re-tested.
A summary list of the bulk samples collected by Jacques Whitford, including a description of the
material, sampling location, type of analysis and laboratory test results is provided in Appendix 2.
3.0 ASSESSMENT LIMITATIONS
This report reflects the observations made within the subject facility only, and the results of analyses
performed on specific materials sampled during the assessment. Analytical results reflect the sampled
materials at the specific sampling locations.
Due to access restrictions the following rooms could not be surveyed: 104A, 119A, 119B, and 123. The
following ceiling spaces could not be surveyed due to height limitations: 121, 124, and 126.
© 2008 PROJECT 1025760 March 3, 2008 3
Due to access restrictions imposed by working in occupied and operational spaces, the asbestos
content of some building materials could not be determined at some locations. Where applicable,
building materials that were not sampled but that may contain asbestos include, but are not limited to
the following:
� sub-grade materials;
� curtains;
� flooring material concealed beneath carpeting, ceramic tile, brickwork, hardwood flooring and/or concealed beneath existing sub-floors;
� drywall and/or wall plaster materials concealed behind new and/or additional walls;
� woven tape inside duct connection joints;
� inner ducting insulation;
� refractory brick;
� insulation material present inside walls (i.e. suspected asbestos-containing vermiculite insulation inside concrete block and/or brick walls);
� pipe straight-run and pipe elbow insulation within wall cavities, inaccessible ceiling spaces or crawlspaces;
� insulation materials inside fire doors;
� the mechanical inner linings of heating, ventilation and air conditioning (HVAC) units; and,
� heat protection materials inside mechanical installations and light fixtures.
If encountered during renovation or other activities, any suspected ACMs not identified within this report
should be presumed to contain asbestos and handled as such until otherwise shown to be non
asbestos-containing through analytical testing.
4.0 REGULATORY FRAMEWORK
Asbestos is included in the Designated Substances Regulations made under Ontario's OHSA. The
Designated Substance Regulation respecting Asbestos (R.R.O. 1990, Reg. 837, amended to O. Reg.
279/05) primarily regulates worker exposure to asbestos during manufacturing of asbestos containing
products, but also includes requirements related to respiratory equipment, measurement of airborne
fibres, and medical surveillance of exposed workers.
The Ontario Regulation 278/05 made under the OHSA for Asbestos on Construction Projects and in
Buildings and Repair Operations, clearly defines asbestos-containing material as a material that
contains 0.5 per cent or more asbestos by dry weight. The new asbestos regulation (O. Reg. 278/05)
became effective as of November 1, 2005.
The General Waste Management Regulation (O. Reg. 347/90), under the Environmental Protection Act
(EPA) of Ontario, sets out the requirements for the proper disposal of asbestos waste in Ontario. The
waste must be placed in a double sealed container, properly labeled, free of cuts, tears or punctures
and disposed of at a licensed waste station which has been properly notified of the presence of
asbestos waste.
© 2008 PROJECT 1025760 March 3, 2008 4
5.0 ASSESSMENT RESULTS AND DISCUSSION
The result of the assessment for asbestos-containing building materials is discussed below. The
evaluation criterion for assessing asbestos-containing materials is provided in Appendix 5. A list of
definitions for technical terms used in this report is provided in Appendix 6.
Asbestos-containing materials are grouped into two classifications, friable and non-friable materials.
Friable ACMs are those that can easily be crumbled or broken apart by mere hand pressure. When
these materials break apart asbestos fibres are then released into the atmosphere. Non-friable ACMs
or “manufactured products” are materials that by the nature of their manufacturing/construction do not
readily allow the release of asbestos fibres. These materials should not be cut or shaped with power
tools, since this procedure may allow for the release of the asbestos fibres.
O. Reg. 278/05 requires that an Asbestos Management Program (AMP) be implemented in buildings
that have been identified to contain friable and non-friable ACMs.
A summary list of the bulk samples that were collected during the assessment including a description of
the material, sampling location, type of analysis and laboratory test results is provided in Appendix 2.
A copy of the PLM laboratory Certificate of Analysis is provided in Appendix 4.
A summary of occurrences of asbestos-containing materials for areas that were inspected is provided
in Appendix 3. Each ACM occurrence includes the following information:
� room component that contains ACM;
� location of the ACM within the room space;
� ACM description;
� estimated quantity;
� original sample number or representative sample number;
� friability; and,
� condition.
5.1 Friable Asbestos-Containing Materials
During the assessment, friable ACMs were identified by laboratory analysis to be present at the subject
facility in the form of:
� Insulating cement on pipe fitting; and,
� Stucco texture coat.
Refer to Appendix 2 for the type and asbestos content; and Appendix 3 for specific location and
condition of these ACMs.
© 2008 PROJECT 1025760 March 3, 2008 5
5.2 Non-Friable Asbestos-Containing Materials
During the assessment, non-friable ACMs were identified by laboratory analysis to be present at the
subject facility in the form of:
� 12”x12” vinyl floor tiles; and,
� 9”x9” vinyl floor tiles.
Refer to Appendix 2 for the type and asbestos content; and Appendix 3 for specific location and condition of these ACMs.
5.3 Presumed Asbestos-Containing Materials
Presumed asbestos-containing materials were observed to be present at the subject facility. The
following materials were identified but not sampled:
� Window and door caulking materials;
� Roof caulking materials;
� Roofing materials;
� Mastics; and,
� Chalkboards.
These materials were not sampled during the assessment to avoid damage. The materials were
observed to be in good condition. As these materials are known to have been manufactured with
asbestos, they should be presumed to be asbestos-containing unless proven otherwise by laboratory
analysis.
5.4 Non-Asbestos-Containing Materials
Refer to Appendix 2 for a list of materials identified as non-asbestos containing through sampling and laboratory analysis.
6.0 RECOMMENDATIONS
Based on visual assessment and laboratory analysis, Jacques Whitford recommends the following with
regards to the ACMs and PACMs in the facility assessed:
� Prior to demolition or renovation work, undertake testing of presumed asbestos-containing materials to determine their asbestos content;
� Asbestos-containing materials should be removed prior to the start of renovation work that may impact the material, in accordance with O. Reg. 278/05;
� Should a material suspected to contain asbestos fibres become uncovered during demolition or renovation activities, all work in the areas that may disturb the material should be stopped. Samples of the suspect material should be submitted for laboratory analysis to determine if asbestos fibres are present. Confirmed asbestos materials should be handled in accordance with O. Reg. 278/05.
© 2008 PROJECT 1025760 March 3, 2008 6
7.0 CLOSURE
This report has been prepared for the sole benefit of the Toronto Catholic District School Board. The
report may not be used by any other person or entity without the express written consent of Jacques
Whitford Limited and the Toronto Catholic District School Board.
Any use which a third party makes of this report, or any reliance on decisions based on it, are the
responsibility of such third parties. Jacques Whitford Limited accepts no responsibility for damages, if
any, suffered by any third party as a result of decisions made or actions based on this report.
The information and conclusions contained in this report are based upon work undertaken by trained
professional and technical staff in accordance with generally accepted engineering and scientific
practices current at the time the work was performed. Conclusions presented in this report should not
be construed as legal advice.
The conclusions presented in this report represent the best technical judgment of Jacques Whitford
Limited based on the data obtained from the work. The conclusions are based on the site conditions
encountered by Jacques Whitford Limited at the time the work was performed at the specific
assessment and/or sampling locations, and can only be extrapolated to an undefined limited area
around these locations. The extent of the limited area depends on building construction and conditions,
weather, building usage and other factors. Due to the nature of the investigation and the limited data
available, Jacques Whitford Limited cannot warrant against undiscovered environmental liabilities.
If any conditions become apparent that differ significantly from our understanding of conditions as
presented in this report, we request that we be notified immediately to reassess the conclusions
provided herein.
We trust that the above is satisfactory for your purposes at this time. Should you have any questions or
concerns, or require additional information, please do not hesitate to contact the undersigned at your
convenience.
This report was prepared by Anil Panchal and reviewed by Martin Ling and Steven D. Fulford.
Sincerely,
JACQUES WHITFORD LIMITED
ORIGINAL SIGNATURE ON FILE ORIGINAL SIGNATURE ON FILE
Anil Panchal. BASc Steven D. Fulford Report Author Senior Technical Reviewer ORIGINAL SIGNATURE ON FILE Martin Ling Project Manager Enclosures P:\CMiC Jobs\1025xxx\1025760\REPORTS\289 - Blessed Trinity\Final Report - 289_Blessed Trinity.docx
APPENDIX 1
Floor Plans Showing Locations of Asbestos-Containing Materials
APPENDIX 2
Summary of Results of Analysis of Bulk Samples for Asbestos Content
Summary of Bulk Sample Analysis for Asbestos Type and Content
SampleNumber AnalysisDescription of Sampled
MaterialAsbestos Typeand ContentSampling Location
289-BS-01A None Detected PLM2' x 4' acoustical ceiling tile - medium fissure pinhole pattern
Room 104
289-BS-01B None Detected PLM2' x 4' acoustical ceiling tile - medium fissure pinhole pattern
Corridor 102
289-BS-01C None Detected PLM2' x 4' acoustical ceiling tile - medium fissure pinhole pattern
Corridor 102
289-BS-02A <0.25% Chrysotile PLM12" x 12" vinyl floor tile - black with white streaks
Room 104
289-BS-02B <0.25% Chrysotile PLM12" x 12" vinyl floor tile - black with white streaks
Room 104
289-BS-02C <0.25% Chrysotile PLM12" x 12" vinyl floor tile - black with white streaks
Room 104
289-BS-03A None Detected PLMdrywall joint-fill compoundRoom 113
289-BS-03B None Detected PLMdrywall joint-fill compoundRoom 113
289-BS-03C None Detected PLMdrywall joint-fill compoundRoom 113
289-BS-03D None Detected PLMdrywall joint-fill compoundRoom 113
289-BS-03E None Detected PLMdrywall joint-fill compoundRoom 113
289-BS-03F None Detected PLMdrywall joint-fill compoundRoom 113
289-BS-03G None Detected PLMdrywall joint-fill compoundRoom 113
289-BS-04A None Detected PLMinsulating cement on pipe fittingRoom 106
289-BS-04B None Detected PLMinsulating cement on pipe fittingRoom 106
289-BS-04C 10% Chrysotile PLMinsulating cement on pipe fittingRoom 109
PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)
1
Notes:
3-Mar-2008
SampleNumber AnalysisDescription of Sampled
MaterialAsbestos Typeand ContentSampling Location
289-BS-05A <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with black specks
Room 107A
289-BS-05B <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with black specks
Room 107A
289-BS-05C <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with black specks
Room 122
289-BS-06A None Detected PLMvinyl linoleum flooring - grey smearsRoom 112
289-BS-06B None Detected PLMvinyl linoleum flooring - grey smearsRoom 112
289-BS-06C None Detected PLMvinyl linoleum flooring - grey smearsRoom 112
289-BS-07A <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with purple smears
Room 113
289-BS-07B <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with purple smears
Room 113
289-BS-07C <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with purple smears
Room 113
289-BS-08A None Detected PLM12" x 12" vinyl floor tile - white with blue/brown specks
Room 114
289-BS-08B None Detected PLM12" x 12" vinyl floor tile - white with blue/brown specks
Room 114
289-BS-08C None Detected PLM12" x 12" vinyl floor tile - white with blue/brown specks
Room 114
289-BS-09A <0.25% Chrysotile PLM12" x 12" vinyl floor tile - greenRoom 118
289-BS-09B 2% Chrysotile PLM12" x 12" vinyl floor tile - greenRoom 118
289-BS-09C SP PLM12" x 12" vinyl floor tile - greenRoom 118
289-BS-10A None Detected PLM2' x 2' acoustical ceiling tile - medium fissure pinhole pattern
Room 118C
289-BS-10B None Detected PLM2' x 2' acoustical ceiling tile - medium fissure pinhole pattern
Corridor 102
PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)
2
Notes:
3-Mar-2008
SampleNumber AnalysisDescription of Sampled
MaterialAsbestos Typeand ContentSampling Location
289-BS-10C None Detected PLM2' x 2' acoustical ceiling tile - medium fissure pinhole pattern
Corridor 102
289-BS-11A None Detected PLM12" x 12" vinyl floor tile - beige with grey specks
Room 120
289-BS-11B None Detected PLM12" x 12" vinyl floor tile - beige with grey specks
Room 120
289-BS-11C None Detected PLM12" x 12" vinyl floor tile - beige with grey specks
Room 120
289-BS-12A None Detected PLM12" x 12" vinyl floor tile - blue with white streaks
Room 127
289-BS-12B None Detected PLM12" x 12" vinyl floor tile - blue with white streaks
Room 127
289-BS-12C None Detected PLM12" x 12" vinyl floor tile - blue with white streaks
Room 127
289-BS-13A None Detected PLM12" x 12" vinyl floor tile - pink smearsRoom 128
289-BS-13B None Detected PLM12" x 12" vinyl floor tile - pink smearsRoom 128
289-BS-13C None Detected PLM12" x 12" vinyl floor tile - pink smearsRoom 128
289-BS-14A <0.25% Chrysotile PLMstucco texture coatRoom 128
289-BS-14B <0.25% Chrysotile PLMstucco texture coatRoom 128
289-BS-14C 2% Chrysotile PLMstucco texture coatRoom 128
289-BS-15A None Detected PLMplasterRoom 103
289-BS-15B None Detected PLMplasterRoom 103
289-BS-15C None Detected PLMplasterRoom 103
289-BS-15D None Detected PLMplasterRoom 218
PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)
3
Notes:
3-Mar-2008
SampleNumber AnalysisDescription of Sampled
MaterialAsbestos Typeand ContentSampling Location
289-BS-15E None Detected PLMplasterRoom 217
289-BS-15F None Detected PLMplasterRoom 213
289-BS-15G None Detected PLMplasterRoom 105
289-BS-16A None Detected PLM12" x 12" vinyl floor tile - green smearsRoom 103
289-BS-16B None Detected PLM12" x 12" vinyl floor tile - green smearsRoom 103
289-BS-16C None Detected PLM12" x 12" vinyl floor tile - green smearsRoom 103
289-BS-17A 3% Chrysotile PLM9" x 9" vinyl floor tile - olive with white streaks
Room 218
289-BS-17B SP PLM9" x 9" vinyl floor tile - olive with white streaks
Room 218
289-BS-17C SP PLM9" x 9" vinyl floor tile - olive with white streaks
Room 218
289-BS-18A 3% Chrysotile PLM9" x 9" vinyl floor tile - green with beige streaks
Room 217
289-BS-18B SP PLM9" x 9" vinyl floor tile - green with beige streaks
Room 217
289-BS-18C SP PLM9" x 9" vinyl floor tile - green with beige streaks
Room 217
289-BS-19A 3% Chrysotile PLM9" x 9" vinyl floor tile - beige with orange streaks
Room 216
289-BS-19B SP PLM9" x 9" vinyl floor tile - beige with orange streaks
Room 216
289-BS-19C SP PLM9" x 9" vinyl floor tile - beige with orange streaks
Room 216
289-BS-20A None Detected PLM2' x 4' acoustical ceiling tile - small fissure pinhole pattern
Room 112
289-BS-20B None Detected PLM2' x 4' acoustical ceiling tile - small fissure pinhole pattern
Room 112A
PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)
4
Notes:
3-Mar-2008
SampleNumber AnalysisDescription of Sampled
MaterialAsbestos Typeand ContentSampling Location
289-BS-20C None Detected PLM2' x 4' acoustical ceiling tile - small fissure pinhole pattern
Room 112A
289-BS-21A None Detected PLM12" x 12" vinyl floor tile - white with black specks
Room 118
289-BS-21B None Detected PLM12" x 12" vinyl floor tile - white with black specks
Room 118
289-BS-21C None Detected PLM12" x 12" vinyl floor tile - white with black specks
Room 118
PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)
5
Notes:
3-Mar-2008
APPENDIX 3
Summary of Occurrences of Asbestos Containing Materials
Summary of Occurrences of Asbestos-Containing Materials
RoomSpecificLocation
ACM Type EstimatedQuantity
SampleNumber
OriginalSample?
Asbestos Content
Friable?Visible?
Access. Comments/Notes
ACMConditionLevel
ACMLocation
insulating cement on pipe fitting 10 Ref 289-BS-04C No 10% Chrysotile Yes No C good ACM102 (corridor) above ceilingabove ceiling1
insulating cement on pipe fitting 2 Ref 289-BS-04C No 10% Chrysotile Yes Yes A good ACM106 below ceilingbelow ceiling1
insulating cement on pipe fitting 3 289-BS-04C No 10% Chrysotile Yes Yes A good ACM109 below ceilingbelow ceiling1
12" x 12" vinyl floor tile - green 150 sq. m 289-BS-09B Yes 2% Chrysotile No Yes A good ACM118 floorfloor1
insulating cement on pipe fitting 4 Ref 289-BS-04C No 10% Chrysotile Yes Yes C good ACM118A below ceilingbelow ceiling1
12" x 12" vinyl floor tile - green 30 sq. m Ref 289-BS-09B No 2% Chrysotile No Yes A good ACM118B, 118C floorfloor1
stucco texture coat 75 sq. m 289-BS-14C Yes 2% Chrysotile Yes Yes C good ACM128 ceilingceiling1
9" x 9" vinyl floor tile - green with beige streaks
150 sq. m Ref 289-BS-18A No 3% Chrysotile No Yes A good ACM202, 203 floorfloor2
insulating cement on pipe fitting 1 Ref 289-BS-04C No 10% Chrysotile Yes Yes A good ACM208 below ceilingbelow ceiling2
9" x 9" vinyl floor tile - olive with white streaks
150 sq. m Ref 289-BS-17A No 3% Chrysotile No Yes A good ACM213, 219 floorfloor2
Yes - Suspect material is visible without opening hatches or lifting ceiling tiles No - Suspect material can only be viewed if access hatches are opened or ceiling tiles lifted.
A - Areas of the building within reach (from floor level) of all building usersB - Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladderC - Areas of the building above 2.4 m where use of a ladder is required to reach the asbestosD - Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc., where demolition of the ceiling, wall, or equipment, etc., is required to reach the asbestos
Accessibility Classification
Visibility
Notes: ACM - asbestos-containing material PACM - presumed asbestos-containing material Access. - accessibility nq - not quantified na - not applicable ns - not sampled REF - reference sample x - estimated number of units F - friable NF - non friable PFM - potentialy friable material S - Sample (original sample collected) V - Visually identical sample
1
* Based on a non-intrusive inspection of visible surfaces within the room space.
3-Mar-2008
RoomSpecificLocation
ACM Type EstimatedQuantity
SampleNumber
OriginalSample?
Asbestos Content
Friable?Visible?
Access. Comments/Notes
ACMConditionLevel
ACMLocation
9" x 9" vinyl floor tile - beige with orange streaks
25 sq. m 289-BS-19A Yes 3% Chrysotile No Yes A good ACM216 floorfloor2
9" x 9" vinyl floor tile - beige with orange streaks
30 sq. m Ref 289-BS-19A No 3% Chrysotile No Yes A good ACM216A, 214, 214A floorfloor2
9" x 9" vinyl floor tile - green with beige streaks
70 sq. m 289-BS-18A Yes 3% Chrysotile No Yes A good ACM217 floorfloor2
9" x 9" vinyl floor tile - olive with white streaks
70 sq. m 289-BS-17A Yes 3% Chrysotile No Yes A good ACM218 floorfloor2
stucco texture coat 450 sq. m Ref 289-BS-14C No 2% Chrysotile Yes Yes C good ACM218, 217, 213, 219, 202, 203
ceilingceiling2
insulating cement on pipe fitting 2 Ref 289-BS-04C No 10% Chrysotle Yes No C good ACMstair C above ceilingabove ceiling2
Yes - Suspect material is visible without opening hatches or lifting ceiling tiles No - Suspect material can only be viewed if access hatches are opened or ceiling tiles lifted.
A - Areas of the building within reach (from floor level) of all building usersB - Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladderC - Areas of the building above 2.4 m where use of a ladder is required to reach the asbestosD - Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc., where demolition of the ceiling, wall, or equipment, etc., is required to reach the asbestos
Accessibility Classification
Visibility
Notes: ACM - asbestos-containing material PACM - presumed asbestos-containing material Access. - accessibility nq - not quantified na - not applicable ns - not sampled REF - reference sample x - estimated number of units F - friable NF - non friable PFM - potentialy friable material S - Sample (original sample collected) V - Visually identical sample
2
* Based on a non-intrusive inspection of visible surfaces within the room space.
3-Mar-2008
APPENDIX 4
Laboratory Analytical Report – Asbestos: Polarized Light Microscopy
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/11/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-01A320714030-0001
Room 104 - 2x4 acoustical CT
White/Gray None Detected
FibrousHeterogeneous
Cellulose30%Glass20%
Non-fibrous (other)45%Perlite5%
289-BS-01B320714030-0002
Corridor 102 - 2x4 acoustical CT
Gray None Detected
FibrousHomogeneous
Cellulose25%Glass15%
Non-fibrous (other)55%Perlite5%
289-BS-01C320714030-0003
Corridor 102 - 2x4 acoustical CT
Gray None Detected
FibrousHomogeneous
Cellulose30%Glass30%
Non-fibrous (other)40%
289-BS-02A320714030-0004
Room 104 - 12x12 vinyl FT-blk w/white streaks
White N/A
Samples analyzed by 400 point count
Non-FibrousHeterogeneous
289-BS-02B320714030-0005
Room 104 - 12x12 vinyl FT-blk w/white streaks
White N/A
Samples analyzed by 400 point count
Non-FibrousHeterogeneous
289-BS-02C320714030-0006
Room 104 - 12x12 vinyl FT-blk w/white streaks
Black N/A
Samples analyzed by 400 point count
Non-FibrousHomogeneous
289-BS-03A320714030-0007
Room 113 - DW with joint-fill compound
White None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-03B320714030-0008
Room 113 - DW with joint-fill compound
White None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
1
Derrick Tanner, Laboratory Manageror other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (40)Wendy Liu (23)
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/11/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-03C320714030-0009
Room 113 - DW with joint-fill compound
White None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-03D320714030-0010
Room 113 - DW with joint-fill compound
White None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-03E320714030-0011
Room 113 - DW with joint-fill compound
White None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-04A320714030-0012
Room 106 - insulating cement on pipe fitting
Gray None Detected
FibrousHeterogeneous
Cellulose2%Glass30%
Non-fibrous (other)68%
289-BS-04B320714030-0013
Room 106 - insulating cement on pipe fitting
Gray None Detected
FibrousHeterogeneous
Cellulose<1%Glass20%
Non-fibrous (other)80%
289-BS-04C320714030-0014
Room 106 - insulating cement on pipe fitting
GrayFibrousHomogeneous
Chrysotile10%Non-fibrous (other)90%
289-BS-05A320714030-0015
Room 107A - 12x12 vinyl FT - beige w/blk specks
Tan/Black N/A
Samples analyzed by 400 point count
Non-FibrousHeterogeneous
289-BS-05B320714030-0016
Room 107A - 12x12 vinyl FT - beige w/blk specks
Tan/Black N/A
Samples analyzed by 400 point count
Non-FibrousHeterogeneous
2
Derrick Tanner, Laboratory Manageror other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (40)Wendy Liu (23)
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/11/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-05C320714030-0017
Room 122 - 12x12 vinyl FT - beige w/blk specks
Gray/Black N/A
Samples analyzed by 400 point count
Non-FibrousHeterogeneous
289-BS-06A320714030-0018
Room 112 - vinyl linoleum flooring - grey smears
Gray None Detected
Non-FibrousHomogeneous
Cellulose5% Non-fibrous (other)95%
289-BS-06B320714030-0019
Room 112 - vinyl linoleum flooring - grey smears
Gray None Detected
Non-FibrousHomogeneous
Cellulose10% Non-fibrous (other)90%
289-BS-06C320714030-0020
Room 112 - vinyl linoleum flooring - grey smears
Gray None Detected
Non-FibrousHeterogeneous
Cellulose10% Non-fibrous (other)90%
289-BS-07A320714030-0021
Room 113 - 12x12 vinyl FT - beige w/purple smears
Brown/Black N/A
Samples analyzed by 400 point count
Non-FibrousHeterogeneous
289-BS-07B320714030-0022
Room 113 - 12x12 vinyl FT - beige w/purple smears
Brown/Black N/A
Samples analyzed by 400 point count
Non-FibrousHeterogeneous
289-BS-07C320714030-0023
Room 113 - 12x12 vinyl FT - beige w/purple smears
Brown N/A
Samples analyzed by 400 point count
Non-FibrousHomogeneous
3
Derrick Tanner, Laboratory Manageror other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (40)Wendy Liu (23)
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/11/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-08A320714030-0024
Room 114 - 12x12 vinyl FT-wht w/blue/brown specks
Tan None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-08B320714030-0025
Room 114 - 12x12 vinyl FT-wht w/blue/brown specks
Tan None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-08C320714030-0026
Room 114 - 12x12 vinyl FT-wht w/blue/brown specks
White None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-09A320714030-0027
Room 118 - 12x12 vinyl FT - green
Green/Black N/A
Samples analyzed by 400 point count
Non-FibrousHomogeneous
289-BS-09B320714030-0028
Room 118 - 12x12 vinyl FT - green
Green/BlackNon-FibrousHomogeneous
Chrysotile2%Cellulose<1% Non-fibrous (other)98%
289-BS-09C320714030-0029
Room 118 - 12x12 vinyl FT - green
Green Stop Positive (Not Analyzed)
Non-FibrousHomogeneous
289-BS-10A320714030-0030
Room 118C - 2x2 acoustical CT
White/Gray None Detected
FibrousHeterogeneous
Cellulose30%Glass20%
Non-fibrous (other)40%Perlite10%
4
Derrick Tanner, Laboratory Manageror other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (40)Wendy Liu (23)
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/11/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-10B320714030-0031
Corridor 102 - 2x2 acoustical CT
White/Gray None Detected
FibrousHeterogeneous
Cellulose25%Glass20%
Non-fibrous (other)45%Perlite10%
289-BS-10C320714030-0032
Corridor 102 - 2x2 acoustical CT
Tan None Detected
FibrousHomogeneous
Cellulose25%Glass20%
Non-fibrous (other)55%
289-BS-11A320714030-0033
Room 120 - 12x12 vinyl FT - beige w/grey specks
Gray None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-11B320714030-0034
Room 120 - 12x12 vinyl FT - beige w/grey specks
Gray None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-11C320714030-0035
Room 120 - 12x12 vinyl FT - beige w/grey specks
Gray None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-12A320714030-0036
Room 127 - 12x12 vinyl FT - blue w/wht streaks
Black/Green None Detected
Non-FibrousHeterogeneous
Non-fibrous (other)100%
289-BS-12B320714030-0037
Room 127 - 12x12 vinyl FT - blue w/wht streaks
Black/Green None Detected
Non-FibrousHeterogeneous
Non-fibrous (other)100%
289-BS-12C320714030-0038
Room 127 - 12x12 vinyl FT - blue w/wht streaks
Black/Green None Detected
Non-FibrousHeterogeneous
Non-fibrous (other)100%
5
Derrick Tanner, Laboratory Manageror other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (40)Wendy Liu (23)
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/11/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-13A320714030-0039
Room 128 - 12x12 vinyl FT - pink smears
Pink None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-13B320714030-0040
Room 128 - 12x12 vinyl FT - pink smears
Pink None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-13C320714030-0041
Room 128 - 12x12 vinyl FT - pink smears
Pink None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-14A320714030-0042
Room 128 - stucco Gray/White N/A
Samples analyzed by 400 point count
Non-FibrousHeterogeneous
289-BS-14B320714030-0043
Room 128 - stucco Gray/White N/A
Samples analyzed by 400 point count
Non-FibrousHeterogeneous
289-BS-14C320714030-0044
Room 128 - stucco WhiteNon-FibrousHomogeneous
Chrysotile2%Non-fibrous (other)98%
289-BS-15A320714030-0045
Room 103 - plaster Gray/Yellow None Detected
Non-FibrousHeterogeneous
Non-fibrous (other)100%
289-BS-15B320714030-0046
Room 103 - plaster Gray/Yellow None Detected
Non-FibrousHeterogeneous
Non-fibrous (other)100%
6
Derrick Tanner, Laboratory Manageror other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (40)Wendy Liu (23)
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/11/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-15C320714030-0047
Room 103 - plaster Gray/White None Detected
Non-FibrousHeterogeneous
Non-fibrous (other)100%
289-BS-15D320714030-0048
Room 218 - plaster White None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-15E320714030-0049
Room 217 - plaster White None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-15F320714030-0050
Room 213 - plaster White None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-15G320714030-0051
Room 105 - plaster White None Detected
Non-FibrousHomogeneous
Non-fibrous (other)100%
289-BS-16A320714030-0052
Room 103 - 12x12 vinyl FT - green smears
Green/Yellow None Detected
Non-FibrousHeterogeneous
Non-fibrous (other)100%
289-BS-16B320714030-0053
Room 103 - 12x12 vinyl FT - green smears
Green/Yellow None Detected
Non-FibrousHeterogeneous
Non-fibrous (other)100%
289-BS-16C320714030-0054
Room 103 - 12x12 vinyl FT - green smears
Green/Yellow None Detected
Non-FibrousHeterogeneous
Non-fibrous (other)100%
7
Derrick Tanner, Laboratory Manageror other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (40)Wendy Liu (23)
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/11/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-17A320714030-0055
Room 218 - 9x9 vinyl FT - olive w/white streaks
Gray/BlackNon-FibrousHeterogeneous
Chrysotile3%Cellulose<1% Non-fibrous (other)97%
289-BS-17B320714030-0056
Room 218 - 9x9 vinyl FT - olive w/white streaks
Gray/Black Stop Positive (Not Analyzed)
Non-FibrousHeterogeneous
289-BS-17C320714030-0057
Room 218 - 9x9 vinyl FT - olive w/white streaks
Gray/Black Stop Positive (Not Analyzed)
Non-FibrousHeterogeneous
289-BS-18A320714030-0058
Room 217 - 9x9 vinyl FT - green w/beige streaks
Black/GreenNon-FibrousHeterogeneous
Chrysotile3%Cellulose<1% Non-fibrous (other)97%
289-BS-18B320714030-0059
Room 217 - 9x9 vinyl FT - green w/beige streaks
Black/Green Stop Positive (Not Analyzed)
Non-FibrousHeterogeneous
289-BS-18C320714030-0060
Room 217 - 9x9 vinyl FT - green w/beige streaks
Black/Green Stop Positive (Not Analyzed)
Non-FibrousHeterogeneous
289-BS-19A320714030-0061
Room 216 - 9x9 vinyl FT - beige w/orange streaks
TanNon-FibrousHomogeneous
Chrysotile3%Non-fibrous (other)97%
289-BS-19B320714030-0062
Room 216 - 9x9 vinyl FT - beige w/orange streaks
Tan Stop Positive (Not Analyzed)
Non-FibrousHomogeneous
8
Derrick Tanner, Laboratory Manageror other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (40)Wendy Liu (23)
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/11/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-19C320714030-0063
Room 216 - 9x9 vinyl FT - beige w/orange streaks
Tan Stop Positive (Not Analyzed)
Non-FibrousHomogeneous
** Individual layers were combined prior to analysis at client request.
9
Derrick Tanner, Laboratory Manageror other approved signatory
PLM-1
Analyst(s)
THIS IS THE LAST PAGE OF THE REPORT.
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (40)Wendy Liu (23)
Sample Location Appearance % TypeAsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Material via EPA 600/R-93/116. Quantitation using 400 Point Count Procedure.
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/3/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-02A320714030-0064
Room 104 - 12x12 vinyl FT-blk w/white streaks
WhiteNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
289-BS-02B320714030-0065
Room 104 - 12x12 vinyl FT-blk w/white streaks
WhiteNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
289-BS-02C320714030-0066
Room 104 - 12x12 vinyl FT-blk w/white streaks
WhiteNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
289-BS-05A320714030-0067
Room 107A - 12x12 vinyl FT - beige w/blk specks
Tan/BlackNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
289-BS-05B320714030-0068
Room 107A - 12x12 vinyl FT - beige w/blk specks
Tan/BlackNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
289-BS-05C320714030-0069
Room 122 - 12x12 vinyl FT - beige w/blk specks
Tan/BlackNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
289-BS-07A320714030-0070
Room 113 - 12x12 vinyl FT - beige w/purple smears
Brown/BlackNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
289-BS-07B320714030-0071
Room 113 - 12x12 vinyl FT - beige w/purple smears
Brown/BlackNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
289-BS-07C320714030-0072
Room 113 - 12x12 vinyl FT - beige w/purple smears
Brown/BlackNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
289-BS-09A320714030-0073
Room 118 - 12x12 vinyl FT - green
Green/BlackNon-FibrousHomogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
Derrick Tanner, Laboratory Manageror other approved signatory
PLMPointCount-1 1
Analyst(s)
Disclaimer:Some samples may contain asbestos fibers present in dimensions below PLM resolution limits. LA Testing suggests that samples reported as <0.25% or none detected undergo additional analysis via TEM. The above test report relates only to the items tested. This report may not be reproduced, except in full, without written approval of LA Testing. This test report must not be used by the client to claim product endorsement by NVLAP or any agency of the United States Government. LA Testing, bears no esponsibility for sample collection activities, analytical method limitations, or the accuracy of results when requested to separate layered samples. LA Testing, liability is limited to the cost of sample analysis. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (9)Wendy Liu (3)
Sample Location Appearance % TypeAsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Material via EPA 600/R-93/116. Quantitation using 400 Point Count Procedure.
320714030
Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5
Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM
1025760 / 985
Customer ID: 32JACQ30A
Fax: (905) 479-9326 Phone: (905) 474-7700Project:
LA Testing Order:
LA Testing Proj:1/3/2008Analysis Date:
Report Date: 1/3/2008
LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]
289-BS-14A320714030-0074
Room 128 - stucco Gray/WhiteNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
289-BS-14B320714030-0075
Room 128 - stucco Gray/WhiteNon-FibrousHeterogeneous
Chrysotile<0.25%Non-fibrous (other)100.00%
Derrick Tanner, Laboratory Manageror other approved signatory
PLMPointCount-1 2
Analyst(s)
THIS IS THE LAST PAGE OF THE REPORT.
Disclaimer:Some samples may contain asbestos fibers present in dimensions below PLM resolution limits. LA Testing suggests that samples reported as <0.25% or none detected undergo additional analysis via TEM. The above test report relates only to the items tested. This report may not be reproduced, except in full, without written approval of LA Testing. This test report must not be used by the client to claim product endorsement by NVLAP or any agency of the United States Government. LA Testing, bears no esponsibility for sample collection activities, analytical method limitations, or the accuracy of results when requested to separate layered samples. LA Testing, liability is limited to the cost of sample analysis. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)
Rafik Vartanian, Ph.D (9)Wendy Liu (3)
APPENDIX 5
Evaluation Criteria for Assessing Asbestos Containing Materials
© 2008 PROJECT 1025760 March 3, 2008 Appendix 5-1
Criteria for Assessing Asbestos Containing Materials
A description of the criteria used in evaluating the condition, accessibility and exposure risk of
asbestos-containing materials is provided below. The criteria is generally based on the Public Works
and Government Services Canada (PWGSC) document entitled “Deputy Ministers Directive 057 –
Asbestos Management” (Last Revised 1999/07/16) and industry standards of practice.
Assessment of Condition
Spray Applied Fireproofing, Insulation and Textured Finishes
In evaluating the condition of ACM spray applied as fireproofing, thermal insulation or texture,
decorative or acoustic finishes, the following criteria apply:
Good
Surface of material shows no significant signs of damage, deterioration or delamination. Up to one
percent visible damage to surface is allowed within range of GOOD. Evaluation of sprayed fireproofing
requires the Assessor to be familiar with the irregular surface texture typical of sprayed asbestos
products. GOOD condition includes unencapsulated or unpainted fireproofing or texture finishes,
where no delamination or damage is observed, and encapsulated fireproofing or texture finishes where
the encapsulation has been applied after the damage or fallout occurred.
Poor
Sprayed materials show signs of damage, delamination or deterioration. More than one percent
damage to surface of ACM spray.
In observation areas, where damage exists in isolated locations, both GOOD and POOR condition may
be reported. The extent or percentage of each condition will be recorded on the Assessor
reassessment form.
FAIR condition is not utilized or considered as a valid criterion in the evaluation of sprayed fireproofing,
sprayed insulation, or texture coat finishes.
The evaluation of ACM spray applied as fireproofing, non-mechanical thermal insulation, or texture,
decorative or acoustic finishes which are present above ceilings, may be limited by the number of
observations made, and by building components such as ducts or full height walls that obstruct the
above ceiling observations. Persons entering the ceiling area are advised to be watchful for ACM
DEBRIS prior to accessing or working above ceilings in areas of building with ACM, regardless of the
reported condition.
Other ACM
In evaluating the condition of mechanical insulation (on boilers, breaching, ductwork, piping, tanks,
equipment etc.) the following criteria are used:
© 2008 PROJECT 1025760 March 3, 2008 Appendix 5-2
Good
Insulation is completely covered in jacketing and exhibits no evidence of damage or deterioration. No
insulation is exposed. Includes conditions where the jacketing has minor surface damage (i.e., scuffs
or stains), but the jacketing is not penetrated.
Fair
Minor penetration damage to jacketed insulation (cuts, tears, nicks, deterioration or delamination) or
undamaged insulation that has never been jacketed. Insulation is exposed but not showing surface
disintegration. The extent of missing insulation ranges should be minor to none.
Poor
Original insulation jacket is missing, damaged, deteriorated or delaminated. Insulation is exposed and
significant areas have been dislodged. Damage cannot be readily repaired. The evaluation of
mechanical insulation may be limited by the number of observations made and building components
such as ducts or full height walls that obstruct observations. In these circumstances, it is not possible
to observe each foot of mechanical insulation from all angles.
Non-Friable and Potentially Friable Materials
Non-friable materials generally have little potential to release airborne fibres, even when damaged by
mechanical breakage. However, some non-friable materials, i.e., exterior asbestos cement products,
may have deteriorated so that the binder no longer effectively contains the asbestos fibres. In such
cases of significantly deteriorated non-friable material, the material will be treated as a friable product.
Evaluation of Accessibility
The accessibility of building materials known or suspected of being ACM is rated according to the
following criteria:
Access (A)
Areas of the building within reach of all building users. Includes areas such as gymnasiums,
workshops, and storage areas where activities of the building users may result in disturbance of ACM
not normally within reach from floor level.
Access (B)
Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladder.
Includes: frequently entered pipe chases, tunnels and service areas or areas within reach from a fixed
ladder or catwalk, i.e., tops of equipment, mezzanines.
Access (C) Exposed
Areas of the building above 8'0" where use of a ladder is required to reach the ACM. Only refers to
ACM materials that are exposed to view, from the floor or ladder, without removing or opening other
building components such as ceiling tiles, or service access doors or hatches. Does not include
infrequently accessed service areas of the building.
© 2008 PROJECT 1025760 March 3, 2008 Appendix 5-3
Access (C) Concealed
Areas of the building which require the removal of a building component, including lay-in ceilings and
access panels into solid ceiling systems. Includes rarely entered crawl spaces, attic spaces, etc.
Observations are limited to the extent visible from the access points.
Access (D)
Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc.
where demolition of the ceiling, wall or equipment, etc., is required to reach the ACM. Evaluation of the
condition and extent of ACM is limited or impossible, depending on the Assessor's ability to visually
examine the materials In Access D.
APPENDIX 6
Terms and Definitions
© 2008 PROJECT 1025760 March 3, 2008 Appendix 6-1
Terms and Definitions
Asbestos
Any of the following asbestiform silicate minerals: actinolite asbestos, anthophyllite asbestos,
chrysotile, crocidolite, cumming tonite-grunerite asbestos (amosite), tremolite asbestos with a dry
weight concentration greater than 0.5%.
Friable
Capable of being crumbled, pulverized or reduced to powder by hand pressure.
HEPA Filter
A high efficiency particulate aerosol filter that is at least 99.97 per cent efficient in collecting a 0.3
micrometre aerosol.
Homogeneous Material
A material that is uniform in colour and texture
Polarized Light Microscopy (PLM)
Polarized Light Microscopy is a technique accepted by the US Environmental Protection Agency as a
screening method for detecting asbestos fibres in bulk material samples.
Presumed Asbestos Containing Materials (PACMs)
Materials that are known to have been manufactured contain asbestos. Testing of the material is
required to determine if the material contains asbestos fibres.
Recommended Corrective Actions (RCAs)
Areas identified to consist of asbestos-containing or presumed asbestos-containing materials that
require attention to repair or remove damaged materials.
Building
Any structure, vault, chamber or tunnel including, without limitation, the electrical, plumbing, heating
and air handling equipment (including rigid duct work) of the structure, vault, chamber or tunnel.