final report - 289 blessed trinity · assessment – final report on blessed trinity catholic...

40
FINAL REPORT Asbestos-Containing Building Material Assessment Toronto Catholic District School Board Blessed Trinity Catholic School, 3205 Bayview Avenue North York, Ontario PROJECT NO. 1025760

Upload: others

Post on 05-Oct-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

FINAL REPORT

Asbestos-Containing Building Material Assessment

Toronto Catholic District School Board

Blessed Trinity Catholic School,

3205 Bayview Avenue

North York, Ontario

PROJECT NO. 1025760

Page 2: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

PROJECT NO. 1025760 REPORT TO Toronto Catholic District School Board

80 Sheppard Avenue East Toronto, Ontario

M2N 6E8

FOR Asbestos-Containing Building Materials Assessment – Final Report

ON Blessed Trinity Catholic School 3205 Bayview Avenue

North York, Ontario

March 3, 2008

Jacques Whitford

7271 Warden Avenue

Markham, Ontario

L3R 5X5

Phone: 905-474-7700

Fax: 905-479-9326

www.jacqueswhitford.com

Page 3: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 i

EXECUTIVE SUMMARY

Jacques Whitford Limited (Jacques Whitford) was commissioned by the Toronto Catholic District

School Board (TCDSB) to conduct an Asbestos-Containing Building Materials Assessment of Blessed

Trinity Catholic School, located at 3205 Bayview Avenue in North York, Ontario.

The purpose of the assessment was to assist the TCDSB to meet the requirements of the new

asbestos regulation, Ontario Regulation 278/05 made under the Occupational Health and Safety Act

(OHSA), effective November 1, 2005. The assessment also includes the identification of asbestos-

containing materials (ACMs) that may require special attention.

The assessment was performed for the purposes of long term management of asbestos, and not for

construction or renovations purposes. Additional intrusive testing may be required prior to using this

information for construction or renovation.

The work was carried out in accordance with the requirements of the OHSA.

Based on visual assessment and laboratory analysis, asbestos-containing materials were identified to

be present at the subject facility. Table 1 below provides a summary of the materials identified and

recommendations on their management.

Table 1 – Summary of Findings and Recommendations

Issue Comments Recommendation

Asbestos Friable asbestos-containing materials were identified to be present in the form of insulating cement on pipe fittings, and stucco texture coat. These materials were observed to be in good condition.

Non-friable asbestos-containing materials were identified to be present in the form of 12”x12” vinyl floor tiles and 9”x9” vinyl floor tiles. These materials were observed to be in good condition.

Presumed asbestos-containing materials (PACMs) were identified to be present in the form of caulking materials, roofing materials, mastics and chalkboards. These materials were observed to be in good condition and were not sampled to preserve their integrity.

Prior to demolition or renovation work, undertake testing of presumed asbestos-containing materials to determine their asbestos content.

Asbestos-containing materials should be removed prior to the start of renovation work that may impact the material, in accordance with O. Reg. 278/05.

Should a material suspected to contain asbestos fibres become uncovered during demolition or renovation activities, all work in the areas that may disturb the material should be stopped. Samples of the suspect material should be submitted for laboratory analysis to determine if asbestos fibres are present. Confirmed asbestos materials should be handled in accordance with O. Reg. 278/05.

The statements made in this Executive Summary text are subject to the same limitations included in the

Closure Section 8.0, and are to be read in conjunction with the remainder of this report.

Page 4: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 ii

Table of Contents

EXECUTIVE SUMMARY ............................................................................................................ i

Asbestos-Containing Building Materials Assessment ......................................................... 1

1.0 INTRODUCTION ..................................................................................................................... 1 1.1 Assessment Objectives ........................................................................................................... 1 1.2 Scope of Work ......................................................................................................................... 1

2.0 ASSESSMENT METHODOLOGY........................................................................................... 2

3.0 ASSESSMENT LIMITATIONS ................................................................................................ 2

4.0 REGULATORY FRAMEWORK .............................................................................................. 3

5.0 ASSESSMENT RESULTS AND DISCUSSION....................................................................... 4 5.1 Friable Asbestos-Containing Materials .................................................................................... 4 5.2 Non-Friable Asbestos-Containing Materials ............................................................................. 5 5.3 Presumed Asbestos-Containing Materials ............................................................................... 5 5.4 Non-Asbestos-Containing Materials ........................................................................................ 5

6.0 RECOMMENDATIONS ........................................................................................................... 5

7.0 CLOSURE ............................................................................................................................... 6

List of Tables

Table 1 – Summary of Findings and Recommendations .................................................................... i

List of Appendices

APPENDIX 1 Floor Plans Showing Locations of Asbestos-Containing Materials ...................... 1 APPENDIX 2 Summary of Results of Analysis of Bulk Samples for Asbestos Content ............. 2 APPENDIX 3 Summary of Occurrences of Asbestos-Containing Materials ............................... 3 APPENDIX 4 Laboratory Analytical Report – Asbestos: Polarized Light Microscopy ................. 4 APPENDIX 5 Evaluation Criteria for Assessing Asbestos-Containing Materials ........................ 5 APPENDIX 6 Terms and Definitions ......................................................................................... 6

Page 5: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 1

ASBESTOS-CONTAINING BUILDING MATERIALS ASSESSMENT

1.0 INTRODUCTION

Jacques Whitford Limited (Jacques Whitford) was commissioned by the Toronto Catholic District

School Board (TCDSB) to conduct an Asbestos-Containing Building Materials Assessment of Blessed

Trinity Catholic School, located at 3205 Bayview Avenue in North York, Ontario.

The purpose of the assessment was to assist the TCDSB to meet the requirements of the new

asbestos regulation, Ontario Regulation 278/05 made under the Occupational Health and Safety Act

(OHSA), effective November 1, 2005. The assessment also includes the identification of asbestos-

containing materials (ACMs) that may require special attention.

The assessment was performed for the purposes of long term management of asbestos, and not for

construction or renovations purposes. Additional intrusive testing may be required prior to using this

information for construction or renovation.

The work was carried out in accordance with the requirements of the OHSA.

1.1 Assessment Objectives

The objective of the assessment was to:

� prepare an assessment report that identifies asbestos-containing materials present at the subject facility; and,

� provide recommendations for the management of these materials.

1.2 Scope of Work

The scope of work for this assessment involved the following:

� a “room-by-room” visual assessment of readily accessible room spaces of the subject facility for the presence of asbestos-containing building materials;

� an inventory of building materials/components that are suspected to contain asbestos;

� the collection of representative bulk samples from building materials suspected of containing asbestos fibres;

� laboratory analysis for the determination of the type and concentration of asbestos present in the samples submitted; and,

� preparation of a report documenting the results of the assessment, providing an interpretation of the laboratory analysis results and recommendations for the management of any asbestos containing materials.

Page 6: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 2

2.0 ASSESSMENT METHODOLOGY

A room-by-room visual assessment of the subject facility was made in order to check for the presence

of materials suspected of containing asbestos.

During the assessment, locations to collect discrete bulk asbestos samples of suspect building

materials were identified. Samples of representative materials were then collected at these locations in

accordance with the requirements of Ontario Regulation 278/05 made under the Occupational Health

and Safety Act.

An assessment of the condition, accessibility and exposure risk was completed for each occurrence of

an asbestos-containing material. The Public Works and Government Services Canada (PWGSC)

document entitled “Deputy Ministers Directive 057 – Asbestos Management” (Last Revised June 16th,

1999) was used as the basis for the criteria that was applied in evaluating the presence of asbestos-

containing materials at the subject areas, where applicable.

Samples of suspect ACMs from various building materials were collected and submitted to EMSL

Laboratories Inc. (EMSL) located in Westmont, New Jersey, for analysis using Polarized Light

Microscopy (PLM) with dispersion staining. The analysis was conducted following the U.S. EPA/600/R-

93/116 Methods. EMSL is certified under the National Voluntary Laboratory Accreditation Program

(NVLAP) to perform asbestos analysis of bulk samples.

The number of bulk samples was based on the requirements of the new asbestos regulation that

specifies the minimum number of samples of a particular building material that should be collected and

tested to consider a material non-asbestos-containing. A positive stop option was used during the

laboratory analysis of the building materials suspected to contain asbestos. Multiple samples of

visually similar material were collected and submitted for laboratory analysis.

The positive stop option involves testing a series of samples from a particular building material until test

results indicate the presence of asbestos. When this occurs, the remaining samples are not tested.

This is a cost effective method of limiting the number of samples that are ultimately tested.

Additionally, materials that had been previously sampled and identified to contain asbestos were

referenced from available reports and not re-tested.

A summary list of the bulk samples collected by Jacques Whitford, including a description of the

material, sampling location, type of analysis and laboratory test results is provided in Appendix 2.

3.0 ASSESSMENT LIMITATIONS

This report reflects the observations made within the subject facility only, and the results of analyses

performed on specific materials sampled during the assessment. Analytical results reflect the sampled

materials at the specific sampling locations.

Due to access restrictions the following rooms could not be surveyed: 104A, 119A, 119B, and 123. The

following ceiling spaces could not be surveyed due to height limitations: 121, 124, and 126.

Page 7: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 3

Due to access restrictions imposed by working in occupied and operational spaces, the asbestos

content of some building materials could not be determined at some locations. Where applicable,

building materials that were not sampled but that may contain asbestos include, but are not limited to

the following:

� sub-grade materials;

� curtains;

� flooring material concealed beneath carpeting, ceramic tile, brickwork, hardwood flooring and/or concealed beneath existing sub-floors;

� drywall and/or wall plaster materials concealed behind new and/or additional walls;

� woven tape inside duct connection joints;

� inner ducting insulation;

� refractory brick;

� insulation material present inside walls (i.e. suspected asbestos-containing vermiculite insulation inside concrete block and/or brick walls);

� pipe straight-run and pipe elbow insulation within wall cavities, inaccessible ceiling spaces or crawlspaces;

� insulation materials inside fire doors;

� the mechanical inner linings of heating, ventilation and air conditioning (HVAC) units; and,

� heat protection materials inside mechanical installations and light fixtures.

If encountered during renovation or other activities, any suspected ACMs not identified within this report

should be presumed to contain asbestos and handled as such until otherwise shown to be non

asbestos-containing through analytical testing.

4.0 REGULATORY FRAMEWORK

Asbestos is included in the Designated Substances Regulations made under Ontario's OHSA. The

Designated Substance Regulation respecting Asbestos (R.R.O. 1990, Reg. 837, amended to O. Reg.

279/05) primarily regulates worker exposure to asbestos during manufacturing of asbestos containing

products, but also includes requirements related to respiratory equipment, measurement of airborne

fibres, and medical surveillance of exposed workers.

The Ontario Regulation 278/05 made under the OHSA for Asbestos on Construction Projects and in

Buildings and Repair Operations, clearly defines asbestos-containing material as a material that

contains 0.5 per cent or more asbestos by dry weight. The new asbestos regulation (O. Reg. 278/05)

became effective as of November 1, 2005.

The General Waste Management Regulation (O. Reg. 347/90), under the Environmental Protection Act

(EPA) of Ontario, sets out the requirements for the proper disposal of asbestos waste in Ontario. The

waste must be placed in a double sealed container, properly labeled, free of cuts, tears or punctures

and disposed of at a licensed waste station which has been properly notified of the presence of

asbestos waste.

Page 8: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 4

5.0 ASSESSMENT RESULTS AND DISCUSSION

The result of the assessment for asbestos-containing building materials is discussed below. The

evaluation criterion for assessing asbestos-containing materials is provided in Appendix 5. A list of

definitions for technical terms used in this report is provided in Appendix 6.

Asbestos-containing materials are grouped into two classifications, friable and non-friable materials.

Friable ACMs are those that can easily be crumbled or broken apart by mere hand pressure. When

these materials break apart asbestos fibres are then released into the atmosphere. Non-friable ACMs

or “manufactured products” are materials that by the nature of their manufacturing/construction do not

readily allow the release of asbestos fibres. These materials should not be cut or shaped with power

tools, since this procedure may allow for the release of the asbestos fibres.

O. Reg. 278/05 requires that an Asbestos Management Program (AMP) be implemented in buildings

that have been identified to contain friable and non-friable ACMs.

A summary list of the bulk samples that were collected during the assessment including a description of

the material, sampling location, type of analysis and laboratory test results is provided in Appendix 2.

A copy of the PLM laboratory Certificate of Analysis is provided in Appendix 4.

A summary of occurrences of asbestos-containing materials for areas that were inspected is provided

in Appendix 3. Each ACM occurrence includes the following information:

� room component that contains ACM;

� location of the ACM within the room space;

� ACM description;

� estimated quantity;

� original sample number or representative sample number;

� friability; and,

� condition.

5.1 Friable Asbestos-Containing Materials

During the assessment, friable ACMs were identified by laboratory analysis to be present at the subject

facility in the form of:

� Insulating cement on pipe fitting; and,

� Stucco texture coat.

Refer to Appendix 2 for the type and asbestos content; and Appendix 3 for specific location and

condition of these ACMs.

Page 9: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 5

5.2 Non-Friable Asbestos-Containing Materials

During the assessment, non-friable ACMs were identified by laboratory analysis to be present at the

subject facility in the form of:

� 12”x12” vinyl floor tiles; and,

� 9”x9” vinyl floor tiles.

Refer to Appendix 2 for the type and asbestos content; and Appendix 3 for specific location and condition of these ACMs.

5.3 Presumed Asbestos-Containing Materials

Presumed asbestos-containing materials were observed to be present at the subject facility. The

following materials were identified but not sampled:

� Window and door caulking materials;

� Roof caulking materials;

� Roofing materials;

� Mastics; and,

� Chalkboards.

These materials were not sampled during the assessment to avoid damage. The materials were

observed to be in good condition. As these materials are known to have been manufactured with

asbestos, they should be presumed to be asbestos-containing unless proven otherwise by laboratory

analysis.

5.4 Non-Asbestos-Containing Materials

Refer to Appendix 2 for a list of materials identified as non-asbestos containing through sampling and laboratory analysis.

6.0 RECOMMENDATIONS

Based on visual assessment and laboratory analysis, Jacques Whitford recommends the following with

regards to the ACMs and PACMs in the facility assessed:

� Prior to demolition or renovation work, undertake testing of presumed asbestos-containing materials to determine their asbestos content;

� Asbestos-containing materials should be removed prior to the start of renovation work that may impact the material, in accordance with O. Reg. 278/05;

� Should a material suspected to contain asbestos fibres become uncovered during demolition or renovation activities, all work in the areas that may disturb the material should be stopped. Samples of the suspect material should be submitted for laboratory analysis to determine if asbestos fibres are present. Confirmed asbestos materials should be handled in accordance with O. Reg. 278/05.

Page 10: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 6

7.0 CLOSURE

This report has been prepared for the sole benefit of the Toronto Catholic District School Board. The

report may not be used by any other person or entity without the express written consent of Jacques

Whitford Limited and the Toronto Catholic District School Board.

Any use which a third party makes of this report, or any reliance on decisions based on it, are the

responsibility of such third parties. Jacques Whitford Limited accepts no responsibility for damages, if

any, suffered by any third party as a result of decisions made or actions based on this report.

The information and conclusions contained in this report are based upon work undertaken by trained

professional and technical staff in accordance with generally accepted engineering and scientific

practices current at the time the work was performed. Conclusions presented in this report should not

be construed as legal advice.

The conclusions presented in this report represent the best technical judgment of Jacques Whitford

Limited based on the data obtained from the work. The conclusions are based on the site conditions

encountered by Jacques Whitford Limited at the time the work was performed at the specific

assessment and/or sampling locations, and can only be extrapolated to an undefined limited area

around these locations. The extent of the limited area depends on building construction and conditions,

weather, building usage and other factors. Due to the nature of the investigation and the limited data

available, Jacques Whitford Limited cannot warrant against undiscovered environmental liabilities.

If any conditions become apparent that differ significantly from our understanding of conditions as

presented in this report, we request that we be notified immediately to reassess the conclusions

provided herein.

We trust that the above is satisfactory for your purposes at this time. Should you have any questions or

concerns, or require additional information, please do not hesitate to contact the undersigned at your

convenience.

This report was prepared by Anil Panchal and reviewed by Martin Ling and Steven D. Fulford.

Sincerely,

JACQUES WHITFORD LIMITED

ORIGINAL SIGNATURE ON FILE ORIGINAL SIGNATURE ON FILE

Anil Panchal. BASc Steven D. Fulford Report Author Senior Technical Reviewer ORIGINAL SIGNATURE ON FILE Martin Ling Project Manager Enclosures P:\CMiC Jobs\1025xxx\1025760\REPORTS\289 - Blessed Trinity\Final Report - 289_Blessed Trinity.docx

Page 11: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

APPENDIX 1

Floor Plans Showing Locations of Asbestos-Containing Materials

Page 12: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden
Page 13: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden
Page 14: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

APPENDIX 2

Summary of Results of Analysis of Bulk Samples for Asbestos Content

Page 15: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Summary of Bulk Sample Analysis for Asbestos Type and Content

SampleNumber AnalysisDescription of Sampled

MaterialAsbestos Typeand ContentSampling Location

289-BS-01A None Detected PLM2' x 4' acoustical ceiling tile - medium fissure pinhole pattern

Room 104

289-BS-01B None Detected PLM2' x 4' acoustical ceiling tile - medium fissure pinhole pattern

Corridor 102

289-BS-01C None Detected PLM2' x 4' acoustical ceiling tile - medium fissure pinhole pattern

Corridor 102

289-BS-02A <0.25% Chrysotile PLM12" x 12" vinyl floor tile - black with white streaks

Room 104

289-BS-02B <0.25% Chrysotile PLM12" x 12" vinyl floor tile - black with white streaks

Room 104

289-BS-02C <0.25% Chrysotile PLM12" x 12" vinyl floor tile - black with white streaks

Room 104

289-BS-03A None Detected PLMdrywall joint-fill compoundRoom 113

289-BS-03B None Detected PLMdrywall joint-fill compoundRoom 113

289-BS-03C None Detected PLMdrywall joint-fill compoundRoom 113

289-BS-03D None Detected PLMdrywall joint-fill compoundRoom 113

289-BS-03E None Detected PLMdrywall joint-fill compoundRoom 113

289-BS-03F None Detected PLMdrywall joint-fill compoundRoom 113

289-BS-03G None Detected PLMdrywall joint-fill compoundRoom 113

289-BS-04A None Detected PLMinsulating cement on pipe fittingRoom 106

289-BS-04B None Detected PLMinsulating cement on pipe fittingRoom 106

289-BS-04C 10% Chrysotile PLMinsulating cement on pipe fittingRoom 109

PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)

1

Notes:

3-Mar-2008

Page 16: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

SampleNumber AnalysisDescription of Sampled

MaterialAsbestos Typeand ContentSampling Location

289-BS-05A <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with black specks

Room 107A

289-BS-05B <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with black specks

Room 107A

289-BS-05C <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with black specks

Room 122

289-BS-06A None Detected PLMvinyl linoleum flooring - grey smearsRoom 112

289-BS-06B None Detected PLMvinyl linoleum flooring - grey smearsRoom 112

289-BS-06C None Detected PLMvinyl linoleum flooring - grey smearsRoom 112

289-BS-07A <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with purple smears

Room 113

289-BS-07B <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with purple smears

Room 113

289-BS-07C <0.25% Chrysotile PLM12" x 12" vinyl floor tile - beige with purple smears

Room 113

289-BS-08A None Detected PLM12" x 12" vinyl floor tile - white with blue/brown specks

Room 114

289-BS-08B None Detected PLM12" x 12" vinyl floor tile - white with blue/brown specks

Room 114

289-BS-08C None Detected PLM12" x 12" vinyl floor tile - white with blue/brown specks

Room 114

289-BS-09A <0.25% Chrysotile PLM12" x 12" vinyl floor tile - greenRoom 118

289-BS-09B 2% Chrysotile PLM12" x 12" vinyl floor tile - greenRoom 118

289-BS-09C SP PLM12" x 12" vinyl floor tile - greenRoom 118

289-BS-10A None Detected PLM2' x 2' acoustical ceiling tile - medium fissure pinhole pattern

Room 118C

289-BS-10B None Detected PLM2' x 2' acoustical ceiling tile - medium fissure pinhole pattern

Corridor 102

PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)

2

Notes:

3-Mar-2008

Page 17: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

SampleNumber AnalysisDescription of Sampled

MaterialAsbestos Typeand ContentSampling Location

289-BS-10C None Detected PLM2' x 2' acoustical ceiling tile - medium fissure pinhole pattern

Corridor 102

289-BS-11A None Detected PLM12" x 12" vinyl floor tile - beige with grey specks

Room 120

289-BS-11B None Detected PLM12" x 12" vinyl floor tile - beige with grey specks

Room 120

289-BS-11C None Detected PLM12" x 12" vinyl floor tile - beige with grey specks

Room 120

289-BS-12A None Detected PLM12" x 12" vinyl floor tile - blue with white streaks

Room 127

289-BS-12B None Detected PLM12" x 12" vinyl floor tile - blue with white streaks

Room 127

289-BS-12C None Detected PLM12" x 12" vinyl floor tile - blue with white streaks

Room 127

289-BS-13A None Detected PLM12" x 12" vinyl floor tile - pink smearsRoom 128

289-BS-13B None Detected PLM12" x 12" vinyl floor tile - pink smearsRoom 128

289-BS-13C None Detected PLM12" x 12" vinyl floor tile - pink smearsRoom 128

289-BS-14A <0.25% Chrysotile PLMstucco texture coatRoom 128

289-BS-14B <0.25% Chrysotile PLMstucco texture coatRoom 128

289-BS-14C 2% Chrysotile PLMstucco texture coatRoom 128

289-BS-15A None Detected PLMplasterRoom 103

289-BS-15B None Detected PLMplasterRoom 103

289-BS-15C None Detected PLMplasterRoom 103

289-BS-15D None Detected PLMplasterRoom 218

PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)

3

Notes:

3-Mar-2008

Page 18: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

SampleNumber AnalysisDescription of Sampled

MaterialAsbestos Typeand ContentSampling Location

289-BS-15E None Detected PLMplasterRoom 217

289-BS-15F None Detected PLMplasterRoom 213

289-BS-15G None Detected PLMplasterRoom 105

289-BS-16A None Detected PLM12" x 12" vinyl floor tile - green smearsRoom 103

289-BS-16B None Detected PLM12" x 12" vinyl floor tile - green smearsRoom 103

289-BS-16C None Detected PLM12" x 12" vinyl floor tile - green smearsRoom 103

289-BS-17A 3% Chrysotile PLM9" x 9" vinyl floor tile - olive with white streaks

Room 218

289-BS-17B SP PLM9" x 9" vinyl floor tile - olive with white streaks

Room 218

289-BS-17C SP PLM9" x 9" vinyl floor tile - olive with white streaks

Room 218

289-BS-18A 3% Chrysotile PLM9" x 9" vinyl floor tile - green with beige streaks

Room 217

289-BS-18B SP PLM9" x 9" vinyl floor tile - green with beige streaks

Room 217

289-BS-18C SP PLM9" x 9" vinyl floor tile - green with beige streaks

Room 217

289-BS-19A 3% Chrysotile PLM9" x 9" vinyl floor tile - beige with orange streaks

Room 216

289-BS-19B SP PLM9" x 9" vinyl floor tile - beige with orange streaks

Room 216

289-BS-19C SP PLM9" x 9" vinyl floor tile - beige with orange streaks

Room 216

289-BS-20A None Detected PLM2' x 4' acoustical ceiling tile - small fissure pinhole pattern

Room 112

289-BS-20B None Detected PLM2' x 4' acoustical ceiling tile - small fissure pinhole pattern

Room 112A

PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)

4

Notes:

3-Mar-2008

Page 19: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

SampleNumber AnalysisDescription of Sampled

MaterialAsbestos Typeand ContentSampling Location

289-BS-20C None Detected PLM2' x 4' acoustical ceiling tile - small fissure pinhole pattern

Room 112A

289-BS-21A None Detected PLM12" x 12" vinyl floor tile - white with black specks

Room 118

289-BS-21B None Detected PLM12" x 12" vinyl floor tile - white with black specks

Room 118

289-BS-21C None Detected PLM12" x 12" vinyl floor tile - white with black specks

Room 118

PLM - Polarized Light Microscopy TEM - Transmission Electron MicroscopyBS - Bulk Samplend - None DetectedSP - Stop Positive (not analyzed)

5

Notes:

3-Mar-2008

Page 20: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

APPENDIX 3

Summary of Occurrences of Asbestos Containing Materials

Page 21: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Summary of Occurrences of Asbestos-Containing Materials

RoomSpecificLocation

ACM Type EstimatedQuantity

SampleNumber

OriginalSample?

Asbestos Content

Friable?Visible?

Access. Comments/Notes

ACMConditionLevel

ACMLocation

insulating cement on pipe fitting 10 Ref 289-BS-04C No 10% Chrysotile Yes No C good ACM102 (corridor) above ceilingabove ceiling1

insulating cement on pipe fitting 2 Ref 289-BS-04C No 10% Chrysotile Yes Yes A good ACM106 below ceilingbelow ceiling1

insulating cement on pipe fitting 3 289-BS-04C No 10% Chrysotile Yes Yes A good ACM109 below ceilingbelow ceiling1

12" x 12" vinyl floor tile - green 150 sq. m 289-BS-09B Yes 2% Chrysotile No Yes A good ACM118 floorfloor1

insulating cement on pipe fitting 4 Ref 289-BS-04C No 10% Chrysotile Yes Yes C good ACM118A below ceilingbelow ceiling1

12" x 12" vinyl floor tile - green 30 sq. m Ref 289-BS-09B No 2% Chrysotile No Yes A good ACM118B, 118C floorfloor1

stucco texture coat 75 sq. m 289-BS-14C Yes 2% Chrysotile Yes Yes C good ACM128 ceilingceiling1

9" x 9" vinyl floor tile - green with beige streaks

150 sq. m Ref 289-BS-18A No 3% Chrysotile No Yes A good ACM202, 203 floorfloor2

insulating cement on pipe fitting 1 Ref 289-BS-04C No 10% Chrysotile Yes Yes A good ACM208 below ceilingbelow ceiling2

9" x 9" vinyl floor tile - olive with white streaks

150 sq. m Ref 289-BS-17A No 3% Chrysotile No Yes A good ACM213, 219 floorfloor2

Yes - Suspect material is visible without opening hatches or lifting ceiling tiles No - Suspect material can only be viewed if access hatches are opened or ceiling tiles lifted.

A - Areas of the building within reach (from floor level) of all building usersB - Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladderC - Areas of the building above 2.4 m where use of a ladder is required to reach the asbestosD - Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc., where demolition of the ceiling, wall, or equipment, etc., is required to reach the asbestos

Accessibility Classification

Visibility

Notes: ACM - asbestos-containing material PACM - presumed asbestos-containing material Access. - accessibility nq - not quantified na - not applicable ns - not sampled REF - reference sample x - estimated number of units F - friable NF - non friable PFM - potentialy friable material S - Sample (original sample collected) V - Visually identical sample

1

* Based on a non-intrusive inspection of visible surfaces within the room space.

3-Mar-2008

Page 22: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

RoomSpecificLocation

ACM Type EstimatedQuantity

SampleNumber

OriginalSample?

Asbestos Content

Friable?Visible?

Access. Comments/Notes

ACMConditionLevel

ACMLocation

9" x 9" vinyl floor tile - beige with orange streaks

25 sq. m 289-BS-19A Yes 3% Chrysotile No Yes A good ACM216 floorfloor2

9" x 9" vinyl floor tile - beige with orange streaks

30 sq. m Ref 289-BS-19A No 3% Chrysotile No Yes A good ACM216A, 214, 214A floorfloor2

9" x 9" vinyl floor tile - green with beige streaks

70 sq. m 289-BS-18A Yes 3% Chrysotile No Yes A good ACM217 floorfloor2

9" x 9" vinyl floor tile - olive with white streaks

70 sq. m 289-BS-17A Yes 3% Chrysotile No Yes A good ACM218 floorfloor2

stucco texture coat 450 sq. m Ref 289-BS-14C No 2% Chrysotile Yes Yes C good ACM218, 217, 213, 219, 202, 203

ceilingceiling2

insulating cement on pipe fitting 2 Ref 289-BS-04C No 10% Chrysotle Yes No C good ACMstair C above ceilingabove ceiling2

Yes - Suspect material is visible without opening hatches or lifting ceiling tiles No - Suspect material can only be viewed if access hatches are opened or ceiling tiles lifted.

A - Areas of the building within reach (from floor level) of all building usersB - Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladderC - Areas of the building above 2.4 m where use of a ladder is required to reach the asbestosD - Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc., where demolition of the ceiling, wall, or equipment, etc., is required to reach the asbestos

Accessibility Classification

Visibility

Notes: ACM - asbestos-containing material PACM - presumed asbestos-containing material Access. - accessibility nq - not quantified na - not applicable ns - not sampled REF - reference sample x - estimated number of units F - friable NF - non friable PFM - potentialy friable material S - Sample (original sample collected) V - Visually identical sample

2

* Based on a non-intrusive inspection of visible surfaces within the room space.

3-Mar-2008

Page 23: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

APPENDIX 4

Laboratory Analytical Report – Asbestos: Polarized Light Microscopy

Page 24: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/11/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-01A320714030-0001

Room 104 - 2x4 acoustical CT

White/Gray None Detected

FibrousHeterogeneous

Cellulose30%Glass20%

Non-fibrous (other)45%Perlite5%

289-BS-01B320714030-0002

Corridor 102 - 2x4 acoustical CT

Gray None Detected

FibrousHomogeneous

Cellulose25%Glass15%

Non-fibrous (other)55%Perlite5%

289-BS-01C320714030-0003

Corridor 102 - 2x4 acoustical CT

Gray None Detected

FibrousHomogeneous

Cellulose30%Glass30%

Non-fibrous (other)40%

289-BS-02A320714030-0004

Room 104 - 12x12 vinyl FT-blk w/white streaks

White N/A

Samples analyzed by 400 point count

Non-FibrousHeterogeneous

289-BS-02B320714030-0005

Room 104 - 12x12 vinyl FT-blk w/white streaks

White N/A

Samples analyzed by 400 point count

Non-FibrousHeterogeneous

289-BS-02C320714030-0006

Room 104 - 12x12 vinyl FT-blk w/white streaks

Black N/A

Samples analyzed by 400 point count

Non-FibrousHomogeneous

289-BS-03A320714030-0007

Room 113 - DW with joint-fill compound

White None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-03B320714030-0008

Room 113 - DW with joint-fill compound

White None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

1

Derrick Tanner, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (40)Wendy Liu (23)

Page 25: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/11/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-03C320714030-0009

Room 113 - DW with joint-fill compound

White None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-03D320714030-0010

Room 113 - DW with joint-fill compound

White None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-03E320714030-0011

Room 113 - DW with joint-fill compound

White None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-04A320714030-0012

Room 106 - insulating cement on pipe fitting

Gray None Detected

FibrousHeterogeneous

Cellulose2%Glass30%

Non-fibrous (other)68%

289-BS-04B320714030-0013

Room 106 - insulating cement on pipe fitting

Gray None Detected

FibrousHeterogeneous

Cellulose<1%Glass20%

Non-fibrous (other)80%

289-BS-04C320714030-0014

Room 106 - insulating cement on pipe fitting

GrayFibrousHomogeneous

Chrysotile10%Non-fibrous (other)90%

289-BS-05A320714030-0015

Room 107A - 12x12 vinyl FT - beige w/blk specks

Tan/Black N/A

Samples analyzed by 400 point count

Non-FibrousHeterogeneous

289-BS-05B320714030-0016

Room 107A - 12x12 vinyl FT - beige w/blk specks

Tan/Black N/A

Samples analyzed by 400 point count

Non-FibrousHeterogeneous

2

Derrick Tanner, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (40)Wendy Liu (23)

Page 26: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/11/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-05C320714030-0017

Room 122 - 12x12 vinyl FT - beige w/blk specks

Gray/Black N/A

Samples analyzed by 400 point count

Non-FibrousHeterogeneous

289-BS-06A320714030-0018

Room 112 - vinyl linoleum flooring - grey smears

Gray None Detected

Non-FibrousHomogeneous

Cellulose5% Non-fibrous (other)95%

289-BS-06B320714030-0019

Room 112 - vinyl linoleum flooring - grey smears

Gray None Detected

Non-FibrousHomogeneous

Cellulose10% Non-fibrous (other)90%

289-BS-06C320714030-0020

Room 112 - vinyl linoleum flooring - grey smears

Gray None Detected

Non-FibrousHeterogeneous

Cellulose10% Non-fibrous (other)90%

289-BS-07A320714030-0021

Room 113 - 12x12 vinyl FT - beige w/purple smears

Brown/Black N/A

Samples analyzed by 400 point count

Non-FibrousHeterogeneous

289-BS-07B320714030-0022

Room 113 - 12x12 vinyl FT - beige w/purple smears

Brown/Black N/A

Samples analyzed by 400 point count

Non-FibrousHeterogeneous

289-BS-07C320714030-0023

Room 113 - 12x12 vinyl FT - beige w/purple smears

Brown N/A

Samples analyzed by 400 point count

Non-FibrousHomogeneous

3

Derrick Tanner, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (40)Wendy Liu (23)

Page 27: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/11/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-08A320714030-0024

Room 114 - 12x12 vinyl FT-wht w/blue/brown specks

Tan None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-08B320714030-0025

Room 114 - 12x12 vinyl FT-wht w/blue/brown specks

Tan None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-08C320714030-0026

Room 114 - 12x12 vinyl FT-wht w/blue/brown specks

White None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-09A320714030-0027

Room 118 - 12x12 vinyl FT - green

Green/Black N/A

Samples analyzed by 400 point count

Non-FibrousHomogeneous

289-BS-09B320714030-0028

Room 118 - 12x12 vinyl FT - green

Green/BlackNon-FibrousHomogeneous

Chrysotile2%Cellulose<1% Non-fibrous (other)98%

289-BS-09C320714030-0029

Room 118 - 12x12 vinyl FT - green

Green Stop Positive (Not Analyzed)

Non-FibrousHomogeneous

289-BS-10A320714030-0030

Room 118C - 2x2 acoustical CT

White/Gray None Detected

FibrousHeterogeneous

Cellulose30%Glass20%

Non-fibrous (other)40%Perlite10%

4

Derrick Tanner, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (40)Wendy Liu (23)

Page 28: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/11/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-10B320714030-0031

Corridor 102 - 2x2 acoustical CT

White/Gray None Detected

FibrousHeterogeneous

Cellulose25%Glass20%

Non-fibrous (other)45%Perlite10%

289-BS-10C320714030-0032

Corridor 102 - 2x2 acoustical CT

Tan None Detected

FibrousHomogeneous

Cellulose25%Glass20%

Non-fibrous (other)55%

289-BS-11A320714030-0033

Room 120 - 12x12 vinyl FT - beige w/grey specks

Gray None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-11B320714030-0034

Room 120 - 12x12 vinyl FT - beige w/grey specks

Gray None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-11C320714030-0035

Room 120 - 12x12 vinyl FT - beige w/grey specks

Gray None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-12A320714030-0036

Room 127 - 12x12 vinyl FT - blue w/wht streaks

Black/Green None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

289-BS-12B320714030-0037

Room 127 - 12x12 vinyl FT - blue w/wht streaks

Black/Green None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

289-BS-12C320714030-0038

Room 127 - 12x12 vinyl FT - blue w/wht streaks

Black/Green None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

5

Derrick Tanner, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (40)Wendy Liu (23)

Page 29: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/11/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-13A320714030-0039

Room 128 - 12x12 vinyl FT - pink smears

Pink None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-13B320714030-0040

Room 128 - 12x12 vinyl FT - pink smears

Pink None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-13C320714030-0041

Room 128 - 12x12 vinyl FT - pink smears

Pink None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-14A320714030-0042

Room 128 - stucco Gray/White N/A

Samples analyzed by 400 point count

Non-FibrousHeterogeneous

289-BS-14B320714030-0043

Room 128 - stucco Gray/White N/A

Samples analyzed by 400 point count

Non-FibrousHeterogeneous

289-BS-14C320714030-0044

Room 128 - stucco WhiteNon-FibrousHomogeneous

Chrysotile2%Non-fibrous (other)98%

289-BS-15A320714030-0045

Room 103 - plaster Gray/Yellow None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

289-BS-15B320714030-0046

Room 103 - plaster Gray/Yellow None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

6

Derrick Tanner, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (40)Wendy Liu (23)

Page 30: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/11/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-15C320714030-0047

Room 103 - plaster Gray/White None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

289-BS-15D320714030-0048

Room 218 - plaster White None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-15E320714030-0049

Room 217 - plaster White None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-15F320714030-0050

Room 213 - plaster White None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-15G320714030-0051

Room 105 - plaster White None Detected

Non-FibrousHomogeneous

Non-fibrous (other)100%

289-BS-16A320714030-0052

Room 103 - 12x12 vinyl FT - green smears

Green/Yellow None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

289-BS-16B320714030-0053

Room 103 - 12x12 vinyl FT - green smears

Green/Yellow None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

289-BS-16C320714030-0054

Room 103 - 12x12 vinyl FT - green smears

Green/Yellow None Detected

Non-FibrousHeterogeneous

Non-fibrous (other)100%

7

Derrick Tanner, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (40)Wendy Liu (23)

Page 31: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/11/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-17A320714030-0055

Room 218 - 9x9 vinyl FT - olive w/white streaks

Gray/BlackNon-FibrousHeterogeneous

Chrysotile3%Cellulose<1% Non-fibrous (other)97%

289-BS-17B320714030-0056

Room 218 - 9x9 vinyl FT - olive w/white streaks

Gray/Black Stop Positive (Not Analyzed)

Non-FibrousHeterogeneous

289-BS-17C320714030-0057

Room 218 - 9x9 vinyl FT - olive w/white streaks

Gray/Black Stop Positive (Not Analyzed)

Non-FibrousHeterogeneous

289-BS-18A320714030-0058

Room 217 - 9x9 vinyl FT - green w/beige streaks

Black/GreenNon-FibrousHeterogeneous

Chrysotile3%Cellulose<1% Non-fibrous (other)97%

289-BS-18B320714030-0059

Room 217 - 9x9 vinyl FT - green w/beige streaks

Black/Green Stop Positive (Not Analyzed)

Non-FibrousHeterogeneous

289-BS-18C320714030-0060

Room 217 - 9x9 vinyl FT - green w/beige streaks

Black/Green Stop Positive (Not Analyzed)

Non-FibrousHeterogeneous

289-BS-19A320714030-0061

Room 216 - 9x9 vinyl FT - beige w/orange streaks

TanNon-FibrousHomogeneous

Chrysotile3%Non-fibrous (other)97%

289-BS-19B320714030-0062

Room 216 - 9x9 vinyl FT - beige w/orange streaks

Tan Stop Positive (Not Analyzed)

Non-FibrousHomogeneous

8

Derrick Tanner, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (40)Wendy Liu (23)

Page 32: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/11/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-19C320714030-0063

Room 216 - 9x9 vinyl FT - beige w/orange streaks

Tan Stop Positive (Not Analyzed)

Non-FibrousHomogeneous

** Individual layers were combined prior to analysis at client request.

9

Derrick Tanner, Laboratory Manageror other approved signatory

PLM-1

Analyst(s)

THIS IS THE LAST PAGE OF THE REPORT.

Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. Samples reported as <1% or none detected may require additional testing by TEM to confirm asbestos quantities. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of LA Testing. LA Testing’s liability is limited to the cost of analysis. LA Testingbears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (40)Wendy Liu (23)

Page 33: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % TypeAsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Material via EPA 600/R-93/116. Quantitation using 400 Point Count Procedure.

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/3/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-02A320714030-0064

Room 104 - 12x12 vinyl FT-blk w/white streaks

WhiteNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

289-BS-02B320714030-0065

Room 104 - 12x12 vinyl FT-blk w/white streaks

WhiteNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

289-BS-02C320714030-0066

Room 104 - 12x12 vinyl FT-blk w/white streaks

WhiteNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

289-BS-05A320714030-0067

Room 107A - 12x12 vinyl FT - beige w/blk specks

Tan/BlackNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

289-BS-05B320714030-0068

Room 107A - 12x12 vinyl FT - beige w/blk specks

Tan/BlackNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

289-BS-05C320714030-0069

Room 122 - 12x12 vinyl FT - beige w/blk specks

Tan/BlackNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

289-BS-07A320714030-0070

Room 113 - 12x12 vinyl FT - beige w/purple smears

Brown/BlackNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

289-BS-07B320714030-0071

Room 113 - 12x12 vinyl FT - beige w/purple smears

Brown/BlackNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

289-BS-07C320714030-0072

Room 113 - 12x12 vinyl FT - beige w/purple smears

Brown/BlackNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

289-BS-09A320714030-0073

Room 118 - 12x12 vinyl FT - green

Green/BlackNon-FibrousHomogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

Derrick Tanner, Laboratory Manageror other approved signatory

PLMPointCount-1 1

Analyst(s)

Disclaimer:Some samples may contain asbestos fibers present in dimensions below PLM resolution limits. LA Testing suggests that samples reported as <0.25% or none detected undergo additional analysis via TEM. The above test report relates only to the items tested. This report may not be reproduced, except in full, without written approval of LA Testing. This test report must not be used by the client to claim product endorsement by NVLAP or any agency of the United States Government. LA Testing, bears no esponsibility for sample collection activities, analytical method limitations, or the accuracy of results when requested to separate layered samples. LA Testing, liability is limited to the cost of sample analysis. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (9)Wendy Liu (3)

Page 34: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

Sample Location Appearance % TypeAsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Asbestos Analysis of Bulk Material via EPA 600/R-93/116. Quantitation using 400 Point Count Procedure.

320714030

Attn: Martin LingJacques Whitford7271 Warden AvenueMarkham, Ontario L3R 5X5

Customer PO: 1025760 / 985Received: 12/11/07 9:00 AM

1025760 / 985

Customer ID: 32JACQ30A

Fax: (905) 479-9326 Phone: (905) 474-7700Project:

LA Testing Order:

LA Testing Proj:1/3/2008Analysis Date:

Report Date: 1/3/2008

LA Testing159 Pasadena Avenue, South Pasadena, CA 91030Phone: (323) 254-9960 Fax: (323) 254-9982 Email: [email protected]

289-BS-14A320714030-0074

Room 128 - stucco Gray/WhiteNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

289-BS-14B320714030-0075

Room 128 - stucco Gray/WhiteNon-FibrousHeterogeneous

Chrysotile<0.25%Non-fibrous (other)100.00%

Derrick Tanner, Laboratory Manageror other approved signatory

PLMPointCount-1 2

Analyst(s)

THIS IS THE LAST PAGE OF THE REPORT.

Disclaimer:Some samples may contain asbestos fibers present in dimensions below PLM resolution limits. LA Testing suggests that samples reported as <0.25% or none detected undergo additional analysis via TEM. The above test report relates only to the items tested. This report may not be reproduced, except in full, without written approval of LA Testing. This test report must not be used by the client to claim product endorsement by NVLAP or any agency of the United States Government. LA Testing, bears no esponsibility for sample collection activities, analytical method limitations, or the accuracy of results when requested to separate layered samples. LA Testing, liability is limited to the cost of sample analysis. Samples received in good condition unless otherwise noted.Analysis performed by LA Testing (NVLAP 200232-0)

Rafik Vartanian, Ph.D (9)Wendy Liu (3)

Page 35: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

APPENDIX 5

Evaluation Criteria for Assessing Asbestos Containing Materials

Page 36: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 Appendix 5-1

Criteria for Assessing Asbestos Containing Materials

A description of the criteria used in evaluating the condition, accessibility and exposure risk of

asbestos-containing materials is provided below. The criteria is generally based on the Public Works

and Government Services Canada (PWGSC) document entitled “Deputy Ministers Directive 057 –

Asbestos Management” (Last Revised 1999/07/16) and industry standards of practice.

Assessment of Condition

Spray Applied Fireproofing, Insulation and Textured Finishes

In evaluating the condition of ACM spray applied as fireproofing, thermal insulation or texture,

decorative or acoustic finishes, the following criteria apply:

Good

Surface of material shows no significant signs of damage, deterioration or delamination. Up to one

percent visible damage to surface is allowed within range of GOOD. Evaluation of sprayed fireproofing

requires the Assessor to be familiar with the irregular surface texture typical of sprayed asbestos

products. GOOD condition includes unencapsulated or unpainted fireproofing or texture finishes,

where no delamination or damage is observed, and encapsulated fireproofing or texture finishes where

the encapsulation has been applied after the damage or fallout occurred.

Poor

Sprayed materials show signs of damage, delamination or deterioration. More than one percent

damage to surface of ACM spray.

In observation areas, where damage exists in isolated locations, both GOOD and POOR condition may

be reported. The extent or percentage of each condition will be recorded on the Assessor

reassessment form.

FAIR condition is not utilized or considered as a valid criterion in the evaluation of sprayed fireproofing,

sprayed insulation, or texture coat finishes.

The evaluation of ACM spray applied as fireproofing, non-mechanical thermal insulation, or texture,

decorative or acoustic finishes which are present above ceilings, may be limited by the number of

observations made, and by building components such as ducts or full height walls that obstruct the

above ceiling observations. Persons entering the ceiling area are advised to be watchful for ACM

DEBRIS prior to accessing or working above ceilings in areas of building with ACM, regardless of the

reported condition.

Other ACM

In evaluating the condition of mechanical insulation (on boilers, breaching, ductwork, piping, tanks,

equipment etc.) the following criteria are used:

Page 37: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 Appendix 5-2

Good

Insulation is completely covered in jacketing and exhibits no evidence of damage or deterioration. No

insulation is exposed. Includes conditions where the jacketing has minor surface damage (i.e., scuffs

or stains), but the jacketing is not penetrated.

Fair

Minor penetration damage to jacketed insulation (cuts, tears, nicks, deterioration or delamination) or

undamaged insulation that has never been jacketed. Insulation is exposed but not showing surface

disintegration. The extent of missing insulation ranges should be minor to none.

Poor

Original insulation jacket is missing, damaged, deteriorated or delaminated. Insulation is exposed and

significant areas have been dislodged. Damage cannot be readily repaired. The evaluation of

mechanical insulation may be limited by the number of observations made and building components

such as ducts or full height walls that obstruct observations. In these circumstances, it is not possible

to observe each foot of mechanical insulation from all angles.

Non-Friable and Potentially Friable Materials

Non-friable materials generally have little potential to release airborne fibres, even when damaged by

mechanical breakage. However, some non-friable materials, i.e., exterior asbestos cement products,

may have deteriorated so that the binder no longer effectively contains the asbestos fibres. In such

cases of significantly deteriorated non-friable material, the material will be treated as a friable product.

Evaluation of Accessibility

The accessibility of building materials known or suspected of being ACM is rated according to the

following criteria:

Access (A)

Areas of the building within reach of all building users. Includes areas such as gymnasiums,

workshops, and storage areas where activities of the building users may result in disturbance of ACM

not normally within reach from floor level.

Access (B)

Frequently entered maintenance areas within reach of maintenance staff, without the need for a ladder.

Includes: frequently entered pipe chases, tunnels and service areas or areas within reach from a fixed

ladder or catwalk, i.e., tops of equipment, mezzanines.

Access (C) Exposed

Areas of the building above 8'0" where use of a ladder is required to reach the ACM. Only refers to

ACM materials that are exposed to view, from the floor or ladder, without removing or opening other

building components such as ceiling tiles, or service access doors or hatches. Does not include

infrequently accessed service areas of the building.

Page 38: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 Appendix 5-3

Access (C) Concealed

Areas of the building which require the removal of a building component, including lay-in ceilings and

access panels into solid ceiling systems. Includes rarely entered crawl spaces, attic spaces, etc.

Observations are limited to the extent visible from the access points.

Access (D)

Areas of the building behind inaccessible solid ceiling systems, walls, or mechanical equipment, etc.

where demolition of the ceiling, wall or equipment, etc., is required to reach the ACM. Evaluation of the

condition and extent of ACM is limited or impossible, depending on the Assessor's ability to visually

examine the materials In Access D.

Page 39: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

APPENDIX 6

Terms and Definitions

Page 40: Final Report - 289 Blessed Trinity · Assessment – Final Report ON Blessed Trinity Catholic School 3205 Bayview Avenue North York, Ontario March 3, 2008 Jacques Whitford 7271 Warden

© 2008 PROJECT 1025760 March 3, 2008 Appendix 6-1

Terms and Definitions

Asbestos

Any of the following asbestiform silicate minerals: actinolite asbestos, anthophyllite asbestos,

chrysotile, crocidolite, cumming tonite-grunerite asbestos (amosite), tremolite asbestos with a dry

weight concentration greater than 0.5%.

Friable

Capable of being crumbled, pulverized or reduced to powder by hand pressure.

HEPA Filter

A high efficiency particulate aerosol filter that is at least 99.97 per cent efficient in collecting a 0.3

micrometre aerosol.

Homogeneous Material

A material that is uniform in colour and texture

Polarized Light Microscopy (PLM)

Polarized Light Microscopy is a technique accepted by the US Environmental Protection Agency as a

screening method for detecting asbestos fibres in bulk material samples.

Presumed Asbestos Containing Materials (PACMs)

Materials that are known to have been manufactured contain asbestos. Testing of the material is

required to determine if the material contains asbestos fibres.

Recommended Corrective Actions (RCAs)

Areas identified to consist of asbestos-containing or presumed asbestos-containing materials that

require attention to repair or remove damaged materials.

Building

Any structure, vault, chamber or tunnel including, without limitation, the electrical, plumbing, heating

and air handling equipment (including rigid duct work) of the structure, vault, chamber or tunnel.