® D Z000713D >10cm >10cm D D/2 D/2 INSTALLATION GUIDELINES RASCOtight QBR Hydrophilic Strip GENERAL To ensure watertightness, a complete and continuous system of hydrophilic strip shall be incorporated. Spalling failure (due to swelling pressure) can be prevented by provision for a minimum concrete cover of 10 cm on all sides. Strip that has swollen by over 20% shall not be cast in. INCORPORATION (GROUND SLABS, SUSPENDED SLABS, WALLS) For element thicknesses up to 40 cm: along centreline of element For element thicknesses exceeding 40 cm with 20 cm distance to the injection side Minimum concrete cover: 10 cm BONDING WITH FIXING ADHESIVE Full contact of hydrophilic strip with base is required Apply RASCObond fixing adhesive Lay RASCOtight hydrophilic strip in adhesive and press to remove voids MECHANICAL FIXING Full contact of hydrophilic strip with base is required E.g. using grid-type clamping device PERSONAL PROTECTIVE EQUIPMENT Wear suitable protective gloves and goggles

Upload: others

Post on 12-Aug-2020

10 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: INSTALLATION GUIDELINES RASCOtight QBR Hydrophilic Strip RASCOtight... · RASCOtight QBR Hydrophilic Strip GENERAL To ensure watertightness, a complete and continuous system of hydrophilic

®

D

Z000713D

>10cm >10cm

Z000709D

D

D/2 D/2

INSTALLATION GUIDELINES

RASCOtight QBR Hydrophilic Strip

GENERALTo ensure watertightness, a complete and continuous system of hydrophilic strip shall be incorporated. Spalling failure (due to swelling pressure) can be prevented by provision for a minimum concrete cover of 10 cm on all sides. Strip that has swollen by over 20% shall not be cast in.

INCORPORATION (GROUND SLABS, SUSPENDED SLABS, WALLS) For element thicknesses up to 40 cm: along centreline of element

For element thicknesses exceeding 40 cm with 20 cm distance to the injection side Minimum concrete cover: 10 cm

BONDING WITH F IXING ADHESIVE Full contact of hydrophilic strip with base is required Apply RASCObond fixing adhesive Lay RASCOtight hydrophilic strip in adhesive and press to remove voids

MECHANICAL F IXING Full contact of hydrophilic strip with base is required E.g. using grid-type clamping device

PERSONAL PROTECTIVE EQUIPMENT Wear suitable protective gloves and goggles

Page 2: INSTALLATION GUIDELINES RASCOtight QBR Hydrophilic Strip RASCOtight... · RASCOtight QBR Hydrophilic Strip GENERAL To ensure watertightness, a complete and continuous system of hydrophilic

2 | 2

®

Rascor International Ltd.Gewerbestrasse 4CH-8162 Steinmaur / SwitzerlandPhone: + 41 ( 0 ) 44 857 11 11Fax: + 41 ( 0 ) 44 857 11 00www.rascor.com

LEGAL NOTICE: The information provided on the use and application of our products in this technical

data sheet is based on the present state of our knowledge. The customer shall bear sole

responsibility for the proper specification, application and use of the products in line with the intended

purpose, project-specific conditions and external actions. The most recent technical data sheet shall

apply. The current technical data sheets are available at www.rascor.com. Our General Terms of

Business shall form an integral part of this technical data sheet.

EN

B 0

9.1

2.1

4 S

AH

JO INTS Lap strip at side (without gap) by approx. 5 - 7 cm Or butt ends of strip (without gap)

FLAT ANGLES Butt joint Lap joint

INTERSECTIONS Butt joint Crossover

INTERNAL/EXTERNAL ANGLES Feasible with continuous length of strip