  • Gas-insulated Instrument Transformers for outdoor Installation

  • 2Gas-insulated Instrument Transformers for outdoor Installation

    Trench Germany the former MWB, founded in1946 is a recognized word-wide leader in thedesign and manufacture of high voltage equipmentfor electrical and industrial systems.

    In its long history while utilizing severalinsulation mediums, e. g. epoxy resin, traditionaloil-paper-insulation the company decided tofocus on SF6-gas as an insulation medium for itscomplete production range.

    Due to the good experience with SF6-gas as aninsulation medium Trench Germany being thefirst supplier of SF6-voltage transformers for GISin 1965 it was decided in 1985 to abandoncompletely the conventional oil-paper insulatedinstrument transformer product line for outdoorinstallations.

    Since this milestone conventional instrument trans-formers with SF6-insulation manufactured by thecompany have found world-wide recognition.

    Today Trench is a market leader with more than 10,000 units in service under different environ-mental conditions.

    Our full range of instrument transformers covering

    voltage (potential) current combined

    units is available for system voltages from 72.5 kV up to 800 kV.

    800 kV Voltage Transformer

  • 3 explosion-proof design by thecompressible insulation mediumSF6-gas and rupture disc

    no ageing of the insulation systemand minimum risk of failure

    insulation medium SF6:non-toxic / inert / non-flammable

    gas monitoring by a densimeter

    guaranteed SF6-leakage rate ofless than 1% per year

    transformer operates at ratedvoltage, even in the case of lossof SF6-pressure

    resource-saving due to ecologi-cally beneficial insulation systemand ideal recycling features

    optimum field grading is accom-plished by a fine condensergrading system especially devel-oped for this application

    meets all IEC and ANSI meteringand protection classes (otherstandards on request)

    Features

    Hollow Composite Insulator

    800 kV Current Transformer

    shedded with a high quality sili-cone, therefore long lasting hydrophobicity transfer to pollu-tion layers

    significant reduction of leakagecurrents as well as surface dis-charges

    cleaning not necessary

    seamless sheds based on ourunique single mould method forassembling the silicone sheds

    variable shed distances withoutadditional tool cost

    earthquake resistant

    resistant against vandalism

    easy handling during transporta-tion and installation

    20 years experience in greatlydifferent climatic zones

  • Voltage TransformersType SVS

    4

    head type design

    available for the full voltagerange 72.5 kV up to 800 kV andfull current range 100 A up to4800 A

    low reactance bar type primaryproviding optimal short-circuitperformance

    multiple-turn primaries for smallprimary currents

    uniformly distributed secondarywindings guarantee accuratetransformation at both rated andhigh currents

    stable accuracy over a long period of time

    perfect transient performance

    maintenance free due to use ofcorrosion-resistant materials only

    core changes after assembly donot require the destruction ofthe high voltage insulation

    1

    2

    available for the full voltagerange 72.5 kV up to 800 kV

    wide range ferroresonance freedesign without the use of an external damping device (pleaseask for details)

    essentially unaffected by externalstray magnetic fields

    stable accuracy over a long periodof time

    suitable for line-discharging

    optimized high voltage coil assuresidentical electric stresses underboth transient and steady stateconditions

    maintenance free due to use ofcorrosion-resistant materials only

    Rupture Disc

    Primary Conductor

    Secondary Housing

    CT Cores

    Head Housing

    Flange

    Outlet Tube

    Composite Insulator

    Terminal Box

    1

    2

    3

    4

    5

    6

    7

    8

    9

    3

    4

    5

    6

    7

    8

    9

    CurrentTransformersType SAS

  • 5Rupture Disc

    Flange

    Outlet Tube

    Capacitive Grading

    Composite Insulator

    Spacer

    HV-Winding

    Magnetic Core

    Core Housing

    1

    2

    3

    4

    5

    6

    7

    8

    9

    Rupture Disc

    HV Winding

    Magnetic Core

    Spacer

    Primary Conductor

    CT Cores

    Head Housing

    Flange

    Outlet Tube

    Composite Insulator

    Terminal Box

    3

    4

    5

    6

    7

    8

    9

    2

    1

    3

    4

    5

    6

    7

    8

    9

    2

    1

    10

    11

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    low weight and compact SF6-design

    the single-section high voltagecoil (not cascaded) of the voltagetransformer section enables aproduct range for combined instrument transformers up to800 kV

    head type design with voltagetransformer section located ontop of the current transformer

    wide range ferroresonance freedesign without the use of an external damping device (pleaseask for details)

    low reactance type primary conductor allows for high short-circuit currents and covers allcore standards

    less foundation space requiredcompared to the use of individualcurrent transformers and voltagetransformers

    suitable for line-discharging

    essentially unaffected by externalstray magnetic fields

    maintenance free due to use ofcorrosion-resistant materials only

    CombinedTransformersType SVAS

  • 6Gas-insulated Current Transformers

    Electrical and Mechanical Data

    Voltage Max. Test voltage Impulse Switching Min. Standardrange system 50/60 Hz, withstand impulse flashover creepage

    voltage 1 min 1.2/50 s test withstand distance distancedry/wet

    kV kV kV kV kV mm mm

    123 123 230 550 1216 2880123 123 230 550 1216 2880123 123 230 550 1216 2880145 145 275 650 1396 3300145 145 275 650 1396 3300145 145 275 650 1396 3300170 170 325 750 1636 3780245 245 460 1050 2350 6135245 245 460 1050 2350 6135300 300 460 1050 2350 6135300 300 460 1050 2350 6135362 362 575 1300 1050/1175 3728 10155420 420 630/680 1425/1550 1050/1175 3728 10155550 550 680 1550 1175 3728 10155550 550 800 1800 1300 4020 11755800 800 920 2050 1425/1550 6000 14112

  • 7Current Transformer123 kV

    Dh2 h1

    Net weight(approx.) Dimensions

    h1 h2 D

    kg mm mm mm

    350 2660 1950 450645 2760 2035 450260 2480 1865 450360 2840 2130 450655 2940 2215 450270 2660 2045 450720 3180 2455 450880 4110 3350 6001250 4280 3450 600880 4110 3350 6001250 4280 3450 6001550 5780 4940 9001550 5780 4940 9001550 5780 4940 9002580 6670 5790 11004000 9605 8650 1100

  • 8Gas-insulated Voltage Transformers

    Electrical and Mechanical Data

    Voltage Max. Test voltage Impulse Switching Min. Standardrange system 50/60 Hz withstand impulse test flashover creepage

    voltage 1 min 1.2/50 s withstand distance distancedry/wet

    kV kV kV kV kV mm mm

    123 123 230 550 1216 2880145 145 275 650 1396 3300170 170 325 750 1636 3780245 245 460 1050 2350 6135300 300 460 1050 850 2350 6135362 362 575 1300 1050/1175 3728 10155420 420 630/680 1425/1550 1050/1175 3728 10155550 550 680 1550 1175 3728 10155550 550 800 1800 1300 4020 11755800 800 920 2050 1425/1550 6000 14112

  • 9Net weight(approx.) Dimensions

    h1 h2 D

    kg mm mm mm

    330 2150 2075 450340 2330 2255 450420 2910 2815 450790 3685 3565 600790 3685 3565 6001600 5440 5350 9001600 5440 5320 9001600 5440 5320 9002150 5940 5820 9003570 9400 9325 1250

    Voltage Transformer123 kV

    D

    h2 h1

  • 10

    Gas-insulated Combined Current and Voltage Transformers

    Electrical and Mechanical Data

    Voltage Max. Test voltage Impulse Switching Min. Standardrange system 50/60 Hz withstand impulse test flashover creepage

    voltage 1 min 1.2/50 s withstand distance distancedry/wet

    kV kV kV kV kV mm mm

    123 123 230 550 1216 2880123 123 230 550 1216 2880123 123 230 550 1216 2880145 145 275 650 1396 3300145 145 275 650 1396 3300145 145 275 650 1396 3300170 170 325 750 1636 3780245 245 460 1050 2350 6135245 245 460 1050 2350 6135300 300 460 1050 2350 6135300 300 460 1050 2350 6135362 362 575 1300 1050/1175 3728 10155420 420 630/680 1425/1550 1050/1175 3728 10155

  • 11

    Net weight(approx.) Dimensions

    h1 h2 D

    kg mm mm mm

    430 3275 1950 450820 3370 2035 450420 3070 1865 450440 3455 2130 450830 3550 2215 450430 3250 2045 450840 3840 2520 5001500 4950 3350 6001870 5150 3450 6001500 4950 3350 6001870 5150 3450 6002500 6900 4940 6002500 6900 4940 600

    Combined Current andVoltage Transformer

    123 kV

    Dh2

    h1

  • Subject to change without notice04.2000

    E 216.11

    www.trenchgroup.com

    Trench Austria GmbHPaschinger Strasse 49, Postfach 13A-4060 Linz-Leonding/AustriaPhone +43.732.6793-0Fax +43.732.671341E-Mail [email protected]

    Trench Brasil LTDAVia Expressa de Contagem, 2685CEP: 32370-485Cpmtagem, MG - BrasilPhone 55. 31. 391-5959Fax 55. 31. [email protected]

    Trench LimitedCoil Product Division71 Maybrook Drive, ScarboroughOntario, Canada M1V 4B6Phone (416) 298-8108Fax (416) 298-2209E-Mail [email protected]

    Trench LimitedInstrument Transformer Division390 Midwest Road, ScarboroughOntario, Canada M1P 3B5Phone (416) 751-8570Fax (416) 751-6952E-Mail [email protected]

    Trench France S.A.16, rue du Gnral CassagnouB.P. 70F- 68302 St-Louis Cedex/FrancePhone +33.3.89 70 23 23Fax +33.3.89 67 26 63E-Mail [email protected]

    Trench Germany GmbHNrnberger Strasse 19996050 Bamberg/GermanyPhone +49.951.1803-0Fax +49.951.1803-224E-Mail [email protected]

    Trench Switzerland AGLehenmattstrasse 353CH - 4028 Basel/SwitzerlandPhone +41.61.315 5111Fax +41.61.315 59 00E-Mail [email protected]