1431928792session ii ct & vt
TRANSCRIPT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 1/201
CT & VT PARAMETERS
ByVivek Pushpakar
Dy MANAGER(EMD)
NTPC BARH
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 2/201
BASICS OF ONE ANDHALF
CIRCUIT BREAKERSCHEME
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 3/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1. IN THIS TWO BUSES ARE PRIOVIDED.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 4/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
2. THESE TWO BUSES ARE INTER-CONNECTED BY THREE CIRCUIT BREAKERS.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 5/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
3. THEY ARE DESIGNATED AS 1-52 CB, 2-52 CB, 3-52 CB.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 6/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
LINE-1
LINE-2
LINE-1 LINE-2
4. LINE - 1 IS CONNECTED IN BETWEEN 1-52 CB & 2-52 CB.
5. LINE - 2 IS CONNECTED IN BETWEEN 3-52 CB & 2-52 CB.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 7/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
LINE-1
LINE-2
LINE-1 LINE-2
6. LINE-1 HAVING TWO FEEDING PATHS i.e
A. VIA BUS-1 & 1-52 CB
B. VIA BUS-2, 3-52 CB & 2-52 CB
7. LINE-2 HAVING TWO FEEDING PATHS i.eA. VIA BUS-2 & 3-52 CB
B. VIA BUS-1, 1-52 CB & 2-52 CB
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 8/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
LINE-1
LINE-2
LINE-1 LINE-2
8. FOR INTURUPTING LINE-1 THE 1-52CB AND 2-52CB IS TO BE TRIPPED.
9. FOR INTURUPTING LINE-2 THE 3-52CB AND 2-52CB IS TO BE TRIPPED.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 9/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
LINE-1
LINE-2
LINE-1 LINE-2
10. FOR ANY PROBLEM IN LINE-1 OR LINE-2 ALONG WITH MAIN BREAKER
THE MIDDLE BREAKER OR SAY TIE BREAKER (2-52 CB) MUST TRIP.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 10/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
LINE-1
LINE-2
LINE-1 LINE-2
13. SO THESE TWO FEEDERS CONTROLLED BY THREE CIRCUIT BREAKERS
IT IS CALLED ONE & HALF BREAKER SYSTEM.
11. NORMALLY IN ALL TYPES OF BUSBAR CONFIGUARATIONS ONE BREAKER
IS SUFFICIENT FOR ONE FEEDER.12. HERE TWO FEEDERS ARE CONTROLED BY THREE BREAKERS.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 11/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
LINE-1
LINE-2
LINE-1 LINE-2
14. THE BAY BETWEEN BUS-1 & LINE-1 IS CALLED MAIN BAY FOR FEEDER-1.
M A I N B A Y ( 1 S T B
A Y ) F O
R F E E D E R - 1
M A I N B A Y ( 1 S T B
A Y ) F O R F E E D E R - 1
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 12/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
LINE-1
LINE-2
LINE-1 LINE-2
M A I N B A Y ( 1 S T B
A Y ) F O
R F E E D E R - 1
M A I N B A Y ( 1 S T B
A Y ) F O R F E E D E R - 1
15. THE BAY BETWEEN LINE-1 & LINE-2 IS CALLED TIE BAY FOR FEEDER-1 & 2.
T I E B A Y ( 2 N D
B A Y ) F O R F E E D E R - 1 & 2
TIE BAY (2 ND BAY ) FOR FEEDER-1 & 2.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 13/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
LINE-1
LINE-2
LINE-1 LINE-2
M A I N B A Y ( 1 S T B
A Y ) F O
R F E E D E R - 1
M A I N B A Y ( 1 S T B
A Y ) F O R F E E D E R - 1
T I E B A Y ( 2 N D
B A Y ) F O R F E E D E R - 1 & 2
TIE BAY (2 ND BAY ) FOR FEEDER-1 & 2.
M A
I N B A Y ( 3 R D
B A Y ) F O R F E E D E R - 2
16. THE BAY BETWEEN BUS-2 & LINE-2 IS CALLED MAIN BAY FOR FEEDER-2.
M A I N B A Y ( 3 R D B A Y ) F O R F E E D E R - 2
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 14/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
LINE-1
LINE-2
LINE-1 LINE-2
M A I N B A Y ( 1 S T B
A Y ) F O
R F E E D E R - 1
M A I N B A Y ( 1 S T B
A Y ) F O R F E E D E R - 1
T I E B A Y ( 2 N D
B A Y ) F O R F E E D E
R - 1 & 2
TIE BAY (2 ND BAY ) FOR FEEDER-1 & 2.
M A
I N B A Y ( 3 R D
B A Y ) F O R F E E D E R - 2
M A I N B A Y ( 3 R D B A Y ) F O R F E E D E R - 2
17. IN THIS SYSTEM FULL DIA MEANS 2 FEEDERS CONTROLLED BY 3 CBs.18. HALF DIA MEANS 1 FEEDER CONTROLLED BY 2 CBs.
(Nothing but Double CB System)
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 15/201
ONE & HALF BREAKER DESCRIPTIONBUS-1
BUS-2
BUS-1 BUS-2
1-52 CB
2-52 CB
3-52 CB
1-52 CB
2-52 CB
3-52 CB
LINE-1
LINE-2
LINE-1 LINE-2
M A I N B A Y ( 1 S T B
A Y ) F O
R F E E D E R - 1
M A I N B A Y ( 1 S T B
A Y ) F O R F E E D E R - 1
T I E B A Y ( 2 N D
B A Y ) F O R F E E D E
R - 1 & 2
TIE BAY (2 ND BAY ) FOR FEEDER-1 & 2.
M A
I N B A Y ( 3 R D
B A Y ) F O R F E E D E R - 2
M A I N B A Y ( 3 R D B A Y ) F O R F E E D E R - 2
GOPALA KRISHNA PALEPU
ADE/MRT/ T&C/400KV SS/
O/O CE/400KV / L&SS/ VS
APTRANSCO, HYDERABAD
Mobile: 9440336984
SUBSTATION DESIGN/LAYOUT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 16/201
SUBSTATION DESIGN/LAYOUT(I-CONFIGUARATION)
FEEDER2 FEEDER4 FEEDER6 FEEDER8 FEEDER10 FEEDER12
FEEDER1 FEEDER3 FEEDER5 FEEDER7 FEEDER9 FEEDER11
BUS-2
BUS-1
B A Y 1
B A Y 2
B A Y 3
B A Y 4
B A Y 5
B A Y 6
B A Y 7
B A Y 8
B A Y 9
B A Y 1 0
B A Y 1 1
B A Y 1 2
B A Y 1 3
B A Y 1 4
B A Y 1 5
B A Y 1 6
B A Y 1 7
B A Y 1 8
DIA1 DIA2 DIA3 DIA4 DIA5 DIA6
SUBSTATION DESIGN/LAYOUT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 17/201
SUBSTATION DESIGN/LAYOUT(D-CONFIGUARATION)
BUS-2
BUS-1
FEEDER3 FEEDER4 FEEDER7 FEEDER8 FEEDER11 FEEDER12
FEEDER1 FEEDER2 FEEDER5 FEEDER6 FEEDER9 FEEDER10
B A Y 1
BAY2
B A Y 3
B
A Y 4
BAY5
B A Y 6
B A Y 7
BAY8
B A Y 9
B A Y 1 0
BAY11
B A Y 1 2
B A Y 1 3
BAY14
B A Y 1 5
B A Y 1 6
BAY17
B
A Y 1 8
DIA1
DIA2
DIA3
DIA4
DIA5
DIA6
SUBSTATION DESIGN/LAYOUT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 18/201
SUBSTATION DESIGN/LAYOUT(DOUBLE BUS & DOUBLE BREAKER SYSTEM)
FEEDER1
B A Y 1
B A Y 2
B
A Y 3
B
A Y 4
FEEDER2
FEEDER3
B A Y 5
B A Y 6
B
A Y 7
B
A Y 8
FEEDER4
FEEDER1
BUS-2
BUS-1
B A Y 1
B A Y 2
BUS-2
BUS-1
FEEDER2
B A Y 3
B A Y 4
FEEDER3
B A Y 5
B A Y 6
B A Y 7
B A Y 8
FEEDER4
FOR ECONOMICAL& RELIABULITY PURPOSE THIS SYSTEM ADOPTED IN 800KV SYSTEM
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 19/201
MESH / RINGLAYOUT
FEEDER 1 FEEDER 2
FEEDER 3
FEEDER 4FEEDER 5FEEDER 6
FEEDER 7
FEEDER 8
1-52 CB 2-52 CB
3-52 CB
4-52 CB
5-52 CB6-52 CB
8-52 CB
7-52 CB
SUBSTATION DESIGN/LAYOUT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 20/201
SUBSTATION DESIGN/LAYOUT(DOUBLE MAIN BUS & TRANSFER BUS SYSTEM)
FEEDER1
BUS-2
BUS-1
FOR ECONOMICAL& RELIABULITY PURPOSE THIS SYSTEM ADOPTED IN 400 & 220 KV SYSTEM
FEEDER2
T R A N S F E R B U S
C O U P L E R
T/F-1 T/F-2
B U S C
O U P L E R
TRANSFER BUS
FEEDER3 FEEDER4
BAY1 BAY2
BAY3 BAY4 BAY5
BAY6 BAY7 BAY8
SUBSTATION DESIGN/LAYOUT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 21/201
SUBSTATION DESIGN/LAYOUT(DOUBLE MAIN BUS & CB BYPASS ISO SYSTEM)
FEEDER1
BUS-2
BUS-1
FOR ECONOMICAL& RELIABULITY PURPOSE THIS SYSTEM ADOPTED IN 220KV SYSTEM
T/F-1
B U S C O U P L E R
FEEDER2
T/F-2
FEEDER3 FEEDER4
BAY1 BAY2
BAY3
BAY4
BAY5
BAY6 BAY7
WHEN ANY CB PROBLEM OR FORPREVENTIVE MAINTANENCE THEN ALL
OTHER FEEDERS SHIFTED TO ANOTHER
BUS OF FAULTED CB BUS AND CLOSE
THE BYPASS ISOLATOR, THEN
PROTECTION IS SHIFTED TO BUS
COUPLER AND OPEN THE FAULTY CB.
SUBSTATION DESIGN/LAYOUT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 22/201
SUBSTATION DESIGN/LAYOUT(SINGLE BUS & TRANSFER BUS SYSTEM)
FEEDER1
BUS-1
TRANSFER BUS
FOR ECONOMICAL& RELIABULITY PURPOSE THIS SYSTEM ADOPTED IN 220 & 132 KV SYSTEM
FEEDER2
T R A
N S F E R B U S C O U P L E R
T/F-1 T/F-2
FEEDER3 FEEDER4
BAY1 BAY2 BAY3 BAY4 BAY5 BAY6 BAY7
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 23/201
CT METHODSIN
ONE AND HALFCIRCUIT BREAKER
SCHEME
DIFFERENT CT METHODS OF ONE & HALF BREAKER SYSTEM
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 24/201
DIFFERENT CT METHODS OF ONE & HALF BREAKER SYSTEM
3 CT METHOD
4 CT METHOD
6 CT METHOD
6 CT METHOD
LINE
LINE
LINE
LINE
CB CB CB
CB CB CB
CB CB CB
CB CB CB
AT/F
AT/F
AT/F
AT/F
5 CT METHODLINE
CB CB CB
AT/F
6 CT METHOD
LINECB CB CB
AT/F
ONE & HALF BREAKER SYSTEM
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 25/201
ONE & HALF BREAKER SYSTEM
LINE 1
1-89
1-89A
1-52CB
3-89
3-89A
3-52CB
2-52CB2-89A 2-89B
1-89L 3-89T
BUS-1 BUS-2
T/F-1
1-CT 3
P1
P2
3-CT
P1
3P2
2-CT
P1 3
P2 3
(3CT METHOD)
ONE & HALF BREAKER SYSTEM
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 26/201
ONE & HALF BREAKER SYSTEM
LINE 1
1-89
1-89A
1-52CB
3-89
3-89A
3-52CB
2-52CB
2-89A 2-89B
1-89L 3-89T
BUS-1 BUS-2
T/F-1
1-CT 3
P1
P2
3-CT
P1
3P2
2-ACT
3
P1P2
2-BCT
3
P1 P2
(4CT METHOD)
ONE & HALF BREAKER SYSTEM
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 27/201
ONE & HALF BREAKER SYSTEM
LINE 1
1-89A
1-52CB
1-CT
3-89
3-89A
3-52CB
3-CT
2-52CB
1L-CT
2-CT
2-89A 2-89B
1-89L 3-89T
BUS-1 BUS-2
T/F-1
3T-CT
1-89
3
P2
P1
3P2
P1
3
P1 P2
3
P2
P1
3P2
P1
(5CT METHOD)
ONE & HALF BREAKER SYSTEM
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 28/201
ONE & HALF BREAKER SYSTEM
LINE 1
1-89A
1-52CB
1B-CT
3-89
3-89A
3-52CB
3B-CT
2-52CB
2B-CT
2-89A 2-89B
1-89L 3-89T
BUS-1 BUS-2
T/F-1
1-89
3
P2
P1
3 P2
P1
3
P1 P2
3
P2 P1
3
P2
P1
3P2
P1
1A-CT
2A-CT
3A-CT
(6CT METHOD)
ONE & HALF BREAKER SYSTEM
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 29/201
ONE & HALF BREAKER SYSTEM
LINE 1
1-89A
1-52CB
1-CT
3-89
3-89A
3-52CB
3-CT
2-52CB
2B-CT
2-89A 2-89B
1-89L 3-89T
BUS-1 BUS-2
T/F-1
1-89
3
P2
P1
3 P2
P1
3
P1 P2
3
P2 P1
3P2
P13P2
P1
1L-CT
2A-CT
3T-CT
(6CT METHOD)
ONE & HALF BREAKER SYSTEM
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 30/201
ONE & HALF BREAKER SYSTEM
LINE 1
1-89A
1-52CB
1-CT
3-89
3-89A
3-52CB
3-CT
2-52CB
2B-CT
2-89A 2-89B
1-89L 3-89T
BUS-1 BUS-2
T/F-1
1-89
3P2
P1
3P2
P1
3
P1 P2
3P2
P1
3
P2 P1
3P2
P1
1L-CT
2A-CT
3T-CT
(6CT METHOD)
TYPICAL ONE & HALF BREAKER
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 31/201
TYPICAL ONE & HALF BREAKER
SYSTEM ADOPTED IN GISDS : DISCONNECTOR SWITCH, GS: GROUNDING SWITCH, CT: CURRENT TRANSFORMER, VD: VOLTAGE DIVIDER
TYPICAL ONE & HALF BREAKER
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 32/201
TYPICAL ONE & HALF BREAKERSYSTEM ADOPTED IN GIS
CT CT CT CT CT CT
1-1/2 CB SYSTEM
(SIEMENS VATECH)
VDVD
DSDSDSDSDSDS
G S
G S
G S
G S
G S
G S
G S
G S
VDVD
CB CB CB
DS : DISCONNECTOR SWITCH, GS: GROUNDING SWITCH, CT: CURRENT TRANSFORMER, VD: VOLTAGE DIVIDER
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 33/201
CORE WISE
APLICATION OFCTs IN
ONE AND HALFCIRCUIT BREAKER
SCHEME
CURRENT TRANSFORMER
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 34/201
CURRENT TRANSFORMER CONNECTIONS IN 3CT METHOD
1 – CT 2 – CT 3 – CT
CORE – 1( PS)
BUSBAR-1
PROTECTION
2CT’s SECONDARIES ARE CONNECTED IN PARALLEL AND
CONNECTED TO MAIN PROTECTION FOR TRANSFORMER
CORE – 2( PS)
BUSBAR-1 CHECKUP
PROTECTION (SPARE)
2CT’s SECONDARIES ARE CONNECTED IN PARALLEL AND
CONNECTED TO BACKUP PROTECTION AFTER LBB/BFR
FOR TRANSFORMER
CORE – 3( 0.5 / 0.2)
SPARE METERING & ENERGY METER FOR AT/F
CORE – 4(0.5 / 0.2)
METERING & ENERGY METER FOR FEEDER SPARE
CORE – 5( PS)
2CT’s SECONDARIES ARE CONNECTED IN PARALLEL AND
CONNECTED TO MAIN-2 PROTECTION AFTER LBB/BFR FOR
FEEDER
BUSBAR-2 CHECKUP
PROTECTION (SPARE)
CORE – 6( PS)
2CT’s SECONDARIES ARE CONNECTED IN PARALLEL AND
CONNECTED TO MAIN-1 PROTECTION FOR FEEDER
BUSBAR-2
PROTECTION
CURRENT TRANSFORMER
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 35/201
CURRENT TRANSFORMERCONNECTIONS IN 3CT METHOD
1 – CT 2 – CT 3 – CT
CORE – 1( PS)
BUSBAR-1
PROTECTION
2CT’s SECONDARIES ARE CONNECTED IN PARALLEL AND
CONNECTED TO MAIN PROTECTION FOR TRANSFORMER
CORE – 2( PS)
BUSBAR-1 CHECKUP
PROTECTION (SPARE)
2CT’s SECONDARIES ARE CONNECTED IN PARALLEL AND
CONNECTED TO BACKUP PROTECTION AFTER LBB/BFR
FOR TRANSFORMER
CORE – 3(0.5 / 0.2)
METERING & ENERGY METER FOR FEEDER SPARE
CORE – 4( PS)
2CT’s SECONDARIES ARE CONNECTED IN PARALLEL AND
CONNECTED TO MAIN-2 PROTECTION AFTER LBB/BFR FOR
FEEDER
BUSBAR-2 CHECKUP
PROTECTION (SPARE)
CORE – 5( PS)
2CT’s SECONDARIES ARE CONNECTED IN PARALLEL AND
CONNECTED TO MAIN-1 PROTECTION FOR FEEDER BUSBAR-2
PROTECTION
BUSHING CT
METERING
CORE (0.5 / 0.2)
NORMALLY THIS SYTEM ADOPTS, WHEN ONE SIDE LINE, OTHER SIDE AUTO
TRANSFORMER / BUS REACTOR IS PROVIDED IN A DIA OF ONE AND HALF BREAKER
SYSTEM, IF BUSHING CT METERING CORE IS AVAILABLE, THEN IT IS USED FORMETERING & ENERGY METER FOR AT/F OR BUS REACTOR.
CURRENT TRANSFORMER
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 36/201
CURRENT TRANSFORMER CONNECTIONS IN 4CT METHOD
1- CT 2-BCT 2-ACT 3-CT
CORE-1(PS)
CT SECONDARY
CORE IS
CONNECTED TO
BUSBAR-1
PROTECTION
SPARE SPARE CT SECONDARY
CORE IS
CONNECTED TO
BUSBAR-2
PROTECTION
CORE-2(PS)
BUSBAR-1
CHECKUPPROTECTION
(SPARE)
SPARE SPARE BUSBAR-2
CHECKUPPROTECTION
(SPARE)
CORE-3(0.5/0.2)
2CT’s SECONDARIES ARE
CONNECTED IN PARALLEL AND
CONNECTED TO
PANEL METERS & ENERGY METER
2CT’s SECONDARIES ARE
CONNECTED IN PARALLEL AND
CONNECTED TO
PANEL METERS & ENERGY METER
CORE-4(PS)
2CT’s SECONDARIES ARECONNECTED IN PARALLEL AND
CONNECTED TO
MAIN-2 PROTECTION
AFTER LBB/BFR
2CT’s SECONDARIES ARECONNECTED IN PARALLEL AND
CONNECTED TO
BACKUP PROTECTION
AFTER LBB/BFR
CORE-5(PS)
2CT’s SECONDARIES ARE
CONNECTED
IN PARALLEL AND CONNECTED TOMAIN-1 PROTECTION
2CT’s SECONDARIES ARE
CONNECTED
IN PARALLEL AND CONNECTED TOMAIN PROTECTION
CURRENT TRANSFORMER
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 37/201
CURRENT TRANSFORMER
CONNECTIONS IN 5CT METHOD
1-CT 1-LCT 2-CT 3-TCT 3-CT
CORE-1
(PS)
BUSBAR-1PROTECTION
TEED PROT-1(BAY 1&2)
TEED PROT-1(BAY 2&3)
TEED PROT-1(BAY 2&3)
BUSBAR-2PROTECTION
CORE-2
(PS)
BUSBAR-1
CHECKUP
PROTECTION
(SPARE)
TEED PROT-2
(BAY 1&2)
TEED PROT-2
(BAY 2&3)
TEED PROT-2
(BAY 2&3)
BUSBAR-2
CHECKUP
PROTECTION
(SPARE)
CORE-3
(0.5/0.2)
SPARE METERING &
ENERGY
METER
SPARE METERING &
ENERGY
METER
SPARE
CORE-4
(PS)
TEED PROT-2
(BAY 1&2)
AFTER
LBB/BFR(1-52)
MAIN-2
PROTECTION
TEED PROT-2
(BAY 1&2)
AFTERLBB/BFR
(2-52)
BACKUP
PROTECTION
TEED PROT-2
(BAY 2&3)
AFTERLBB/BFR
(3-52)
CORE-5
(PS)
TEED PROT-1
(BAY 1&2)
MAIN-1
PROTECTION
TEED PROT-1
(BAY 1&2)
MAIN
PROTECTION
TEED PROT-1
(BAY 2&3)
Paralleling of 2Nos CTs to the Main-1/Main-2/Backup line protection is not required. This gives bettertransient response. Separate STUB protection can be connected (Nothing BUT TEED Protection).
CURRENT TRANSFORMER
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 38/201
CURRENT TRANSFORMER CONNECTIONS IN 6CT METHOD
(GIS or AIS with DEAD TANK CBs)
1B-CT 1A-CT 2B-CT 2A-CT 3A-CT 3B-CT
CORE-1
(PS)
BUSBAR-1PROTECTION
2CT’s SECONDARIES
ARE CONNECTED
IN PARALLEL AND
CONNECTED TO
MAIN-1 PROTECTION
2CT’s SECONDARIES
ARE CONNECTED
IN PARALLEL AND
CONNECTED TO
MAIN-1 PROTECTION
BUSBAR-2PROTECTION
CORE-2
(PS)
BUSBAR-1
CHECKUPPROTECTION
(SPARE)
2CT’s SECONDARIES
ARE CONNECTED IN
PARALLEL AND
CONNECTED TO
MAIN-2 PROTECTION
AFTER LBB/BFR
2CT’s SECONDARIES
ARE CONNECTED IN
PARALLEL AND
CONNECTED TO
BACKUP PROTECTION
AFTER LBB/BFR
BUSBAR-2
CHECKUPPROTECTION
(SPARE)
CORE-3(0.5/0.2)
SPARE 2CT’s SECONDARIESARE CONNECTED IN
PARALLEL AND
CONNECTED TO
PANEL METERS &
ENERGY METER
2CT’s SECONDARIESARE CONNECTED IN
PARALLEL AND
CONNECTED TO
PANEL METERS &
ENERGY METER
SPARE
CURRENT TRANSFORMER
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 39/201
CURRENT TRANSFORMER CONNECTIONS IN 6CT METHOD
1-CT 1L-CT 2A-CT 2B-CT 3T-CT 3-CT
CORE-1
(PS)
BUSBAR-1
PROTECTION
TEED PROT-1
(BAY 1&2)
SPARE SPARE TEED PROT-1
(BAY 2&3)
BUSBAR-2
PROTECTION
CORE-2
(PS)
BUSBAR-1
CHECKUP
PROTECTION(SPARE)
TEED PROT-2
(BAY 1&2)
SPARE SPARE TEED PROT-2
(BAY 2&3)
BUSBAR-2
CHECKUP
PROTECTION(SPARE)
CORE-3
(0.5/0.2)
SPARE METERING &
ENERGY
METER
SPARE SPARE METERING &
ENERGY
METER
SPARE
CORE-4(PS)
TEED PROT-2(BAY 1&2)
AFTER LBB/BFR
(1-52)
MAIN-2PROTECTION
TEED PROT-2(BAY 2&3)
TEED PROT-2(BAY 1&2)
AFTER LBB/BFR
(2-52)
BACKUPPROTECTION
TEED PROT-2(BAY 2&3)AFTER LBB/BFR
(3-52)
CORE-5
(PS)
TEED PROT-1
(BAY 1&2)
MAIN-1
PROTECTION
TEED PROT-1
(BAY 2&3)
TEED PROT-1
(BAY 1&2)
MAIN
PROTECTION
TEED PROT-1
(BAY 2&3)
CT CORES
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 40/201
CT CORES
CONEECTIONDIAGRAMS IN
ONE AND HALFCIRCUIT BREAKER
SCHEME
SINGLE BUS SYSTEM
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 41/201
SINGLE BUS SYSTEM
1-52CB1-89 1-89L
3
1-CT
P2 P1 3
3
3
3
CORES
1 2 3 4 5
B U S B A R P R O T E
C T I O N
B U S B A R C H E C K U
P P R O T
M E T E R I N
G
M A I N - 2 / B A C K U P P R O T E C T I O N
M A I N - 1 P R O T E
C T I O N
BUS
1-CVT
3
3
3
3
1 2 3 33
3
3
3
2
1
BB-EVT
/ CVT
ONE & HALF BREAKER ( 3 CT METHOD) WITH PROTECTION SCHEME
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 42/201
87BB1
87BB2
CVT
CVT
VBB1
VBB2
79
25
79
25
79
25VBB2
BF
BF
VL2 / VL1
OR VBB1
VL1 / VL2
OR VBB2
VBB1
FEEDER1 / LINE1
FEEDER2 / LINE2
87L 21M2
CVT VL2
CVT VL1
BF
VL1
BUSBAR-1
BUSBAR-2
MAIN-1
MAIN-2PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
21M1 VL1
VL1 / VBB1
VL2 / VBB2
FOR TRANSFORMER PROTECTION &
METERING VOLTAGE SELECTION RELAYSFOR BUS-1, BUS-2& LINE ARE PROVIDED .
ONE & HALF BREAKER ( 4 CT METHOD) WITH PROTECTION SCHEME
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 43/201
87BB1
87BB2
CVT
CVT
VBB1
VBB2
79
25
79
25VBB2
BF
BF
VL2 / VL1
OR VBB1
VL1 / VL2
OR VBB2
VBB1
FEEDER1 / LINE1
FEEDER2 / LINE2
87L 21M2
CVT VL2
CVT VL1
BF
VL1
BUSBAR-1
BUSBAR-2
MAIN-1
MAIN-2PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
21M1 VL1
79
25VL1 / VBB1
VL2 / VBB2
FOR TRANSFORMER PROTECTION &
METERING VOLTAGE SELECTION RELAYSFOR BUS-1, BUS-2& LINE ARE PROVIDED .
ONE & HALF BREAKER ( 6 CT METHOD) WITH PROTECTION SCHEME
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 44/201
87BB1
87BB2
CVT
CVT
VBB1
VBB279
25VBB2
BF
BFVL2 / VL1
OR VBB1
79
25
VL1 / VL2
OR VBB2
VBB1
FEEDER1 / LINE1
FEEDER2 / LINE2
87L 21M2
CVT VL2
CVT VL1
BF
VL1
BUSBAR-1
BUSBAR-2
MAIN-1
MAIN-2
PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
21M1 VL1
79
25VL1 / VBB1
VL2 / VBB2
FOR TRANSFORMER PROTECTION &
METERING VOLTAGE SELECTION RELAYSFOR BUS-1, BUS-2& LINE ARE PROVIDED .
ONE & HALF BREAKER ( 5 CT METHOD) WITH PROTECTION SCHEME
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 45/201
87BB1
87BB2
CVT
CVT
VBB1
VBB2
79
25
79
25
79
25VBB2
BF
BF
VL2 / VL1
OR VBB1
VL1 / VL2
OR VBB2
VBB1
FEEDER1 / LINE1
FEEDER2 / LINE2
CVT VL2
CVT VL1
BF
87L 21M2
VL1
BUSBAR-1
BUSBAR-2
MAIN-1
MAIN-2
PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
21M1 VL1
VL1 / VBB1
VL2 / VBB2
87 TD1 HZ
87 TD2 LZ
87 TD1 HZ
87 TD2 LZ
.
.
FOR TRANSFORMER PROTECTION &
METERING VOLTAGE SELECTION RELAYSFOR BUS-1, BUS-2& LINE ARE PROVIDED .
ONE & HALF BREAKER ( 6 CT METHOD) WITH PROTECTION SCHEME
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 46/201
87BB1
87BB2
CVT
CVT
VBB1
VBB2
79
25
79
25VBB2
BF
BF
VL2 / VL1
OR VBB1
VL1 / VL2
OR VBB2
VBB1
FEEDER1 / LINE1
FEEDER2 / LINE2
CVT VL2
CVT VL1
BF
87L 21M2
VL1
BUSBAR-1
BUSBAR-2
MAIN-1
MAIN-2
PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
21M1 VL1
79
25VL1 / VBB1
VL2 / VBB2
87 TD1 HZ
87 TD2 LZ
87 TD1 HZ
87 TD2 LZ
.
.
FOR TRANSFORMER PROTECTION &
METERING VOLTAGE SELECTION RELAYSFOR BUS-1, BUS-2& LINE ARE PROVIDED .
ONE & HALF BREAKER ( 6 CT METHOD) WITH PROTECTION SCHEME
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 47/201
87BB1
87BB2
CVT
CVT
VBB1
VBB2
79
25
BF
BF
79
25VBB2
VL2 / VL1
OR VBB1
VL1 / VL2
OR VBB2
VBB1
FEEDER1 / LINE1
FEEDER2 / LINE2
CVT VL2
CVT VL1
BF
87L 21M2
VL1
BUSBAR-1
BUSBAR-2
MAIN-1
MAIN-2
PROTECTION OF LINE2
(OR TRANSFORMER, IF APPLICABLE)
21M1 VL1
79
25VL1 / VBB1
VL2 / VBB2
87 TD1 HZ
87 TD2 LZ
87 TD1 HZ
87 TD2 LZ
FOR TRANSFORMER PROTECTION &
METERING VOLTAGE SELECTION RELAYSFOR BUS-1, BUS-2& LINE ARE PROVIDED .
COMPARISION BETWEEN DIFFERENT CT METHODS
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 48/201
CTPURPOSE
3 CTMETHOD
4 CTMETHOD
6 CT (S)METHOD
5 CTMETHOD
6 CT (T1)METHOD
6 CT (T2)METHOD
BUSBAR &
BUSBAR
CHECKUP
PROTECTION
1 CT 1 CT 1B CT 1 CT 1 CT 1 CT
ABOVE FOR BUS-1 & BELOW FOR BUS-2
3 CT 3 CT 3B CT 3 CT 3 CT 3 CT
MAIN-1
MAIN-2
PROTECTION
&
METERING
1 - CT & 2 - CT 1 CT & 2 B - CT 1 A – CT & 2 B – CT 1 L - CT 1 L - CT 1 L - CT
ABOVE CT SECONDARIES ARE CONNECTED PARALLEL FOR FEEDER-1
BELOW CT SECONDARIES ARE CONNECTED PARALLEL FOR FEEDER-2
ABOVE FOR FEEDER-1
BELOW FOR FEEDER-2
3 - CT & 2 – CT 3 - CT & 2 A - CT 3 A - CT & 2 A - CT 3 L - CT 3 L - CT 3 L – CT
ADDITIONAL
PROTECTION
AVAILABLE
STUB-1 & STUB-2 PROTECTIONFOR LINE & AT/F
TEED-1 & TEED-2 PROTECTIONFOR LINE & AT/F
STUB-1 & STUB-2 PROTECTION IS A NORMALLY INBUILT
PROTECTION FOR MAIN-1 & MAIN-2 RELAYS, IN CASE OF LATEST
NUMERICAL RELAYS. STUB PROTECTION WORKS WHEN LINE
ISOLATOR OPEN CONDITION ONLY.
TEED–1 IS NORMALLY HIGH IMPEDENCE DIFFERENTIAL RELAY &
TEED-2 IS NORMALLY LOW IMPEDENCE DIFFERENTIAL RELAY.
THESE ARE NOT INBUILT FUNCTIONS OF MAIN-1 & MAIN-2
RELAYS.
BLINDZONE
A FAULT BETWEEN CIRCUIT BREAKERS AND CT (END FAULT) MAY THEN STILL BE FED FROM ONE SIDE
EVEN WHEN THE BREAKER HAS BEEN OPENED. CONSEQUENTLY, FINAL FAULT CLEARING BY CASCADEDTRIPPING HAS TO BE ACCEPTED IN THIS CASE. THIS SITUATION LBB/BFR OPERATES AND TIME TAKEN TOCLEAR FAULT IS ABOUT 300 mSECs. THIS IS BLIND ZONE AREA.
ADVANTAGES
MINIMUM CT
METHOD. REDUCING
THE COST OF CTs
TIE CB BLIND ZONE
AREA IS TAKEN
CARE.
MAIN CB & TIE CB
BLIND ZONE AREA IS
TAKEN CARE
BLIND ZONE FOR
MAIN CB & TIE CB
TIE CB BLIND ZONE
AREA IS TAKEN CARE
TIE CB BLIND ZONE
AREA IS TAKEN CARE
WHEN THE FAULT IS TAKEN PLACE BETWEEN THE MAIN
CB, TIE CB & LINE ISOLATOR, DURING SERVICE ONLY,DISTANCE SCHEME SHOULD TAKE CARE.
WHEN THE FAULT IS TAKEN PLACE BETWEEN THE MAIN CB, TIE CB &
LINE ISOLATOR DURING SERVICE ONLY, TEED PROTECTION INADDITION TO DISTANCE SCHEME SHOULD TAKE CARE.
400KV C T INFORMATION
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 49/201
400KV C.T. INFORMATION
3 3 U
3 U
3 U
3
1S11S21S3
2S12S22S3
3 S 1
3 S 2
3 S 3
3 S 4
5S1
5S25S35S4
4S14S24S34S4
P1 P2
P1 P2
3 U
3 S 1
3 S 2
3 S 3
3 S 4
EYE BOLT
DESIGN
HAIR
PIN /U SHAPE
DESIGN
DEAD TANK DESIGN
PRIMARY CONNECTIONS : P1 – P2
CURRENT RATING : 2000 AMPS
CORES CLASS PURPOSE
SECONDARY CONNECTIONS
CURRENT RATING : 1A
2000/ 1A 1000/ 1A 500/ 1A
CORE-1 PS
BUSBAR
PROTECTION 1S1 – 1S3
1S1 – 1S2
1S2 – 1S3
__
CORE-2 PS
BUSBAR
CHECKUP
PROTECTION
2S1 – 2S32S1 – 2S2
2S2 – 2S3__
CORE-3 0.5 / 0.2 METERING 3S1 – 3S4 3S1–
3S33S4 – 3S2 3S1–
3S23S4 – 3S3
CORE-4 PSMAIN-2
PROTECTION4S1 – 4S4
4S1 – 4S3
4S4 – 4S2
4S1 – 4S2
4S4 – 4S3
CORE-5 PSMAIN-1
PROTECTION5S1 – 5S4
5S1 – 5S3
5S4 – 5S2
5S1 – 5S2
5S4 – 5S3
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 50/201
CT PARAMETERS
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 51/201
1. Top cover
2. Oil level indicator
3. Oil expansion device4. Metal box LV screen and cores
5. Bar-type or wound type primary
6. Paper-oil insulation
7. Porcelain insulator
8. LV screens
9. Secondary terminal box10. Base
Current Transformers (Paper/Oil) up to 765 kV
Eye Bolt Design
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 52/201
Eye Bolt Design
IT range
Primary conductor (1,2 or 4 turns)
Primary steel pipe
Paper insulation
Secondary cores
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 53/201
1. Dome
2. Nitrogen filling valve
3. Primary terminal4. Collar
5. Porcelain insulator
6. Primary conductor with
insulation
7. Adaptor cylinder
8. Secondary cores9. Base
10. Oil drain plug
Current Transformers (Paper/Oil) up to 420 kV
Hair-Pin design
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 54/201
1. Oil filling plug
2. Dome
3. Nitrogen filling valve4. Collar
5. Primary terminal
6. Porcelain insulator
7. Insulated primary
8. Cover plate for tank
9. Tank10. Secondary cores
Current Transformers (Paper/Oil) up to 245 kV
Eye bolt design
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 55/201
FUNDAMENTALS
WHAT IS CT?
WHEN IS CT REQUIRED ?
WHY IS CT REQUIRED?
HOW IS CT CONNECTED?
WHERE IS CT CONNECTED?
WHICH CT IS CONNECTED?
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 56/201
WHAT IS CT?
IT’S AN INSTRUMENT TRANSFORMER
WHICH TRANSFORMS CURRENT FROMONE LEVEL TO ANOTHER LEVEL SUCH AS
1000/1 (CT RATIO) i.e. TRANSFORMS
CURRENT OF THE LEVEL OF 1000 AMPS
INTO CURRENT OF 1 AMP LEVEL.
back
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 57/201
WHEN IS CT REQUIRED ?
ELECTRICAL SYSTEMS IN WHICH LARGE
AMOUNT OF CURRENT ( TO THE TUNE OF
100AMPS OR MORE) FLOWS , DIRECTMEASUREMENT OF THAT CURRENT IS
NOT POSSIBLE AS DEVICES USED FOR
MEASUREMENT OF CURRENT ARE NOT
DESIGNED TO HANDLE SUCH HUGE
AMOUNT OF CURRENT.
back
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 58/201
WHY IS CT REQUIRED?
THE SYSTEM WHICH CARRIES CURRENTMEANS THERE IS A SOURCE WHICHINJECTS THE CURRENT INTO THE SYSTEM
AND THERE IS A LOAD WHICH CONSUMESTHE CURRENT (OR POWER/ENERGY).SUCHA SYSTEM HAS TWO BASICREQUIREMENTS:
METERING OF ENERGY SOURCED ORCONSUMED.
PROTECTION OF THE ELECTRICALSYSTEM FROM FAULTS AND
DISTURBANCES. back
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 59/201
HOW IS CT CONNECTED?
CT HAS A PRIMARY AND ONE OR MORE
SECONDARY WINDINGS. SECONDARY
WINDING IS WOUND AROUND THE
MAGNETIC CORE. METERING AND
PROTECTION DEVICES ARE CONNECTED
TO THE SECONDARIES OF THE CT.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 60/201
HOW IS CT CONNECTED?contd
M/R
PRIMARY
Ip
Ψ
Is
back
P1
P2
S1
S2
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 61/201
WHERE IS CT CONNECTED?
FOR METERING AND PROTECTION OF
A FEEDER, CT IS CONNECTED AT THE
BEGINNING OF THE FEEDER.
WHERE IS CT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 62/201
WHERE IS CT
CONNECTED? contd
Power Station to be protected
back
Unit
protUnit
prot
Non-
unit
prot
meter meter prot meterDist
prot
One prim one sec
One prim two or more sec
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 63/201
WHICH CT IS CONNECTED?
METERING: IF WE WANT TO MEASURECURRENT FOR METERING PURPOSE, WEDESIRE THAT:
WHATEVER CURRENT WE MEASURE,THAT SHOULD BE VERY ACCURATE ASTHE METERED DATA MAY BE USED FORTARIFF PURPOSE i.e. MONEY EXCHANGE
IS INVOLVED AMONG VARIOUS PARTIES.MOREOVER, THE DATA IS USED FORDECISION MAKING SUCH AS DECISIONON RAISING/LOWERING OF POWER
OUTPUT etc.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 64/201
WHICH CT IS CONNECTED?Contd meter ing
WHAT IS INACCURACY?
THE SECONDARY CURRENT WHICH WEGET IS NOT TRUE REFLECTION OF ITSPRIMARY CURRENT. FOR EXAMPLE, FOR ACT WITH CT RATIO OF 1000/1AMPS, IF WEGET 0.99 AMPS IN SECONDARY LEADINGPRIMARY CURRENT BY 15 MINUTES FOR
PRIMARY CURRENT OF 1000AMPS, SO THECT HAS RATIO ERROR OF (0.99-1)/1 x 100=-1% AND PHASE ERROR OF 15 MINUTES.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 65/201
WHICH CT IS CONNECTED?Contd meter ing
CURRENT OR RATIO ERROR AS PER IEC IS:
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 66/201
WHICH CT IS CONNECTED?Contd meter ing
NOW SECOND QUERY WHICH COMES IN
MIND IS WHY AT ALL CTS ARE
INACCURATE?
THE CULPRIT IS CORE LOSS AND
MAGNETISING CURRENT, WHICH
INTRODUCES RATIO AS WELL AS PHASE
ERROR.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 67/201
WHICH CT IS CONNECTED?Contd meter ing
THE INTSRUMENT CONNECTED TO THESECONDARY ESPECIALLY ANALOGINDICATING METER SHOULD NOT GET
DAMAGED DURING PRIMARY FAULTCONDITION.
FOR THIS INSTRUMENT SECURITYFACTOR (FS) IS DEFINED WHICH IS RATIOOF MINIMUM PRIMARY CURRENT AT
WHICH COMPOSITE ERROR OF THE CT (ATRATED BURDEN) IS EQUAL TO ORGREATER THAN 10% OF RATED PRIMARYCURRENT.
THE TYPICAL VALUES ARE 5,10 etc.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 68/201
WHICH CT IS CONNECTED?contd
IEC60044-1 HAS LAID DOWN STANDARDS ON
THIS:
25 25 25
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 69/201
WHICH CT IS CONNECTED?Contd meter ing
FOR ACHIEVING ABOVE, A CT IS
CHOSEN HAVING VERY HIGHPERMEABILITY AND HIGH
REMANENCE
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 70/201
WHICH CT IS CONNECTED?Contd meter ing
THE ABOVE CT PARAMETERS ARE
THEREFORE SPECIFIED AS FOR
EXAMPLE: CTR:1000/1,0.2FS5 ,30VA
etc.
IN NTPC, WE TYPICALLY SPECIFY,
CTR: 2000/1, 0.2,FS 5, 20VA
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 71/201
WHICH CT IS CONNECTED?contd
PROTECTION CLASS:
HERE, MAIN REQUIREMENT IS ABILITY OFCT TO FAITHFULLY TRANSFORM THEPRIMARY CURRENT DURING FAULTCONDITION.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 72/201
WHICH CT IS CONNECTED?Contd p rotection PR
DURING FAULT CONDITION, VALUE OFPRIMARY CURRENT MAY BE 10 TO 20 TIMESTHE RATED PRIMARY CURRENT.
PROTECTIVE RELAY BURDEN ISCONNECTED TO THE CT SECONDARY. ATSUCH HIGH LEVEL OF PRIMARY CURRENT,IF CT IS NOT PROPERLY DESIGNED, IT MAYSATURATE AND RELAY WILL RECEIVE
VERY LESS CURRENT AND, THEREFORE,DOES NOT TAKE RIGHT DECISION.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 73/201
WHICH CT IS CONNECTED?Contd p rotection PR
FOR NON-UNIT TYPE PROTECTION SUCHAS O/C TYPE OF PROTECTION, CLASS PR TYPE CTs ARE USED.
THE PARAMETERS THAT ARE DEFINEDFOR THE CT ARE:
STANDARD ACCURACY LIMITFACTOR(SALF):
= RATED ACC. LIMIT PRIMARY CURR.
RATED CURRENT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 74/201
WHICH CT IS CONNECTED?Contd p rotection PR
WHEREAS, RATED ACCURACY LIMITPRIMARY CURRENT IS THE VALUE OF
THE PRIMARY CURRENT UPTO WHICHCT WILL COMPLY WITH THEREQUIREMENT OF COMPOSITE ERROR.
STANDARD VALUES OF SALF ARE5,10,15,20,30
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 75/201
WHICH CT IS CONNECTED?Contd p rotection PR
THE ABOVE CT PARAMETERS ARE
THEREFORE SPECIFIED AS FOREXAMPLE: CTR:1000/1, 5PR20 @
30VA etc.
IN NTPC, FOR GENERATORPROTECTION WE TYPICALLY
SPECIFIY CTR 10000A/5A,5PR20 @
75VA
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 76/201
WHICH CT IS CONNECTED?Contd protect ion
FOR UNIT TYPE PROTECTION:
HERE , REQUIREMENTS ARE RATHERSTRINGENT AS WE COMPARE CURRENTOF TWO OR MORE CTS AND RELY ON THETHEIR MUTUAL FAITHFULL-NESS .MOREOVER, OUR AIM IS THAT THE
PROTECTION MUST BE STABLE FOR EVENWORST THROUGH FAULT AND FASTACTING FOR INTERNAL FAULT.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 77/201
WHICH CT IS CONNECTED?Contd protect ion PX
FOR THIS PX CLASS OF CTs ARE
NEEDED (THESE CTs ARE SIMILAR IN
ALL RESPECTS TO CLASS PS OF IS-2705 AND CLASS-X OF BS-3938 WITH
SOME ADDITIONAL FEATURES)
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 78/201
WHICH CT IS CONNECTED?Contd protect ion PX
THE PARAMETERS WHICH ARE DEFINED
IN THIS CT ARE:
KNEE POINT VOLTAGE (KPV):
That minimum sinusoidal voltage (r.m.s.) at rated
power frequency when applied to the secondary
terminals of the transformer, all the terminals
being open-circuited, which when increased by10% causes the r.m.s. exciting current to increase
by no more than 50%.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 79/201
WHICH CT IS CONNECTED?Contd protect ion PX
FOR WORST THROUGH FAULT, CTs
SHOULD NOT GET SATURATED.WHEN ONE
OF THE CTs GETS SATURATED, LARGE
AMOUNT OF CURRENT MAY FLOW
THROUGH DIFFERENTIAL CIRCUIT AND
RESULT IN OPERATION OF
RELAY.HOWEVER, IF RELAY IS SETABOVE THIS VALUE
i.e. Iset= Ifx (Rct+2xRl),
Rstab
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 80/201
WHICH CT IS CONNECTED?contd protect ion PX
MAGNETISING CURRENT AT KPV OR%AGE THEREOF:
TWO OR MORE CTs USED FOR UNITPROTECTION SHOULD WORK LIKE CLONEBROTHERS i.e. FOR THROUGH FAULTCONDITION, THE SPILL CURRENTSHOULD BE IDEALLY ZERO. BUTPRACTICALLY, THIS IS NOT THE CASE.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 81/201
WHICH CT IS CONNECTED?contd protect ion PX
IF TWO CTs HAVE DIFFERENTMAGNETISING CURRENT AND HIGH
LEAKAGE REACTANCE, IT WILLINTRODUCE HIGH CURRENT AS WELL ASPHASE ERROR.THUS, RESULTANTCURRENT OF THESE CT SECONDARIESMAY LEAD TO HIGH SPILL(DIFFERENTIAL)
CURRENT DURING THROUGH FAULT.THISMAY LEAD TO PROTECTION OPERATIONDURING THROUGH FAULT.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 82/201
WHICH CT IS CONNECTED?Contd protect ion PX
CT DC RESISTANCE AT 75 deg C(Rct):
THIS VALUE IS VERY IMPORTANT FROM
THE POINT OF VIEW OF KPVCALCULATION AS IT IS ONE OF THE
LIMITING FACTORS TO THIS. THEREFORE,
IT IS DEFINED.
TURN RATIO ERROR: LIMITED TO 0.25%.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 83/201
WHICH CT IS CONNECTED?contd
THE ABOVE CT PARAMETERS ARE
THEREFORE SPECIFIED AS FOR
EXAMPLE:CTR: 1000/1 ,PX , KPV=1000V,
Ie=30mAmp @ KPV/2, Rct< 5OHMS @75
deg C etc. (TYPICAL TO NTPC)
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 84/201
Current Transformers
Causes of Failure andMonitoring/Maintenance
CT Failure and remedial action
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 85/201
CT Failure and remedial action
Generally failures can happen due to the following reasons
• Opening of C terminal (used for tan delta and
capacitance measurement) when CTs are in energisation. This
leads to very high voltages resulting in failure.
CT Failure and remedial action
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 86/201
CT Failure and remedial action
Remedial actions in CT at site to avoid failures
• Tangent delta and Capacitance measurement from the C terminal at periodic
intervals every years or during shutdown.
• Dissolved gas analysis of oil taken out from CT alteast once in ten years.
• Thermo vision scanning of CTs of rating 132kV ( or above).
Multiple Chopped Impulse test
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 87/201
Multiple Chopped Impulse test
Application of 100 chopped impulses of negative polarity
on CTs of ratings above 300kV. These impulses will be
applied at the rate of one impulse per minute. The test
Voltage shall be 60% of the rated lightning impulse voltage
Before the test and three days after the test the dissolved
gas analysis of oil taken from CT will be carried out.Analysis
procedure and fault diagnosis shall be as per IEC 60599.
As per IEC 60044-1 ( 2002)
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 88/201
Special test
A. Thermal Stability test :
This involves simultaneous application of rated voltage
(1.1Um/Sqrt3) and rated simultaneous current (1.2,1.5 etc)
by using a synthetic test circuit.Capacitance, tangent delta,
secondary resistance and temperature of primary terminal
are recorded until stable values are acquired.
This test demonstrates the insulation capacity (healthiness) under energised
conditions.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 89/201
Special test
B. Temperature coefficient test:
The CT is heated in a oven to approximately 90Deg C. The tan delta is
measured at ambient, 80 and 90 deg C at voltages of 0.3,0.7,1.0 and1.1Um/Sqrt3.
This test demonstrates the healthiness at high extreme temperature conditions.
Current Transformers
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 90/201
Current Transformers
Type Tests
IEC 600 44-1a) short-time current tests
b) temperature rise test
c) lightning impulse test
d) switching impulse test
e) wet test for outdoor type transformers
f) determination of errors
Current Transformer
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 91/201
Routine testsCEI 600 44-1
CEI 60-1
Routine tests
The following tests apply to each individual transformers:
a) verification of terminal markings
b) power-frequency withstand test on primary windingc) partial discharge measurement
d) power-frequency withstand test on secondary windings
e) power-frequency withstand tests, between sections
f) inter-turn overvoltage testg) determination of errors
The order of the tests is not standardized, but determination of
errors shall be performed after the other tests.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 92/201
VT PARAMETERS
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 93/201
FUNDAMENTALS
WHAT IS VT?
WHEN IS VT REQUIRED ?
WHY IS VT REQUIRED?
HOW IS VT CONNECTED?
WHERE IS VT CONNECTED?
WHICH VT IS CONNECTED?
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 94/201
1. Oil level indicator (optional)
2. Expansion device
3. Capacitor units
4. Insulating oil5. Porcelain insulator
6. Sealing
7. Electromagnetic unit
8. Low voltage terminals box/
HF terminal
9. Series inductance
10. Medium voltage transformer
11. Damping circuit againstferroresonance effects
Capacitor Voltage Transformers (Paper/Film/Oil) up to 765 kV
1
2
3
4
5
7
8
9
11
6
10
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 95/201
Capacitor stack
Inductive VT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 96/201
CCV 72.5 to 765 kV
Capacitor elements
Capacitor column
Insulating oil
Insulator flange
Secondary terminal box
Inductance
MV Transformer
Oil expansion device
Damping circuit
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 97/201
WHAT IS VT?
IT’S AN INSTRUMENT TRANSFORMER
WHICH TRANSFORMS VOLTAGE FROM
ONE LEVEL TO ANOTHER LEVEL SUCH AS400KV/√3:110V/√3 (VT RATIO) i.e.
TRANSFORMS VOLTAGE OF THE LEVEL OF
400KV/√3 INTO VOLTAGE OF 110V/√3
LEVEL.
back
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 98/201
WHEN IS VT REQUIRED ?
ELECTRICAL SYSTEM WHICH HASHIGH LEVEL OF VOLTAGE ( TO THE
TUNE OF 3.3KV OR MORE) , DIRECTMEASUREMENT OF THAT VOLTAGEIS NOT POSSIBLE AS DEVICES USEDFOR MEASUREMENT OF VOLTAGEARE NOT DESIGNED TO HANDLESUCH HIGH LEVEL OF VOLTAGE.
back
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 99/201
WHY IS VT REQUIRED?
THE SYSTEM WHICH CARRIES VOLTAGEAND CURRENT MEANS THERE IS ASOURCE WHICH INJECTS THE POWER INTO
THE SYSTEM AND THERE IS A LOADWHICH CONSUMES POWER/ENERGY.SUCHA SYSTEM HAS TWO BASICREQUIREMENTS:
METERING OF ENERGY SOURCED OR
CONSUMED.PROTECTION OF THE ELECTRICAL
SYSTEM FROM FAULTS ANDDISTURBANCES.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 100/201
WHY IS VT REQUIRED?Contd
FAULTS CAN BE MANY KINDS. SOMEFAULTS SUCH AS O/C CAN BE DETECTEDSOLELY ON CURRENT MEASUREMENT,
BUT CURRENT DOES NOT PROVIDEDISCRETION ABOUT NATURE ANDLOCATION OF THE FAULT. FOR HIGHLYINTERCONNECTED ELECTRICAL SYSTEMCARRYING HUGE AMOUNT OF POWER,
SUB-SYSTEM ISOLATION SELECTIVITY ISIMMENSLY DESIRABLE.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 101/201
HOW IS VT CONNECTED?
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 102/201
HOW IS VT CONNECTED?
VT HAS A PRIMARY AND ONE OR MORE
SECONDARY WINDINGS.
METERING AND PROTECTION DEVICES
ARE CONNECTED TO THE SECONDARIES
OF THE VT.
HOW IS VT CONNECTED?
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 103/201
HOW IS VT CONNECTED?contd
M
P
P
INDUCTIVE VOLTAGE TRANSFORMER
HOW IS VT CONNECTED?
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 104/201
HOW IS VT CONNECTED?contd
back
M
P
P
CAPACITIVE VOLTAGE TRANSFORMER
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 105/201
WHERE IS VT CONNECTED?
FOR METERING AND PROTECTION OF A
FEEDER, VT IS CONNECTED AT THEBEGINING OF THE FEEDER.
WHERE IS VT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 106/201
WHERE IS VT
CONNECTED? contd
Power Station to be protected
back
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 107/201
WHICH VT IS CONNECTED?
AS STATED FOR CT, WE NEED IT FOR
METERING: VOLTAGE MEASUREMENT,ENERGY, POWER MEASUREMENT.
PROTECTION: FOR DISTANCE
PROTECTION, O/V,U/V, O/F AND U/FPROTECTIONS, FIELD FAILURE, OVER-FLUXING,etc.
WHICH VT IS CONNECTED?
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 108/201
WHICH VT IS CONNECTED?contd
FOR METERING VTs WE NEED HIGHACCURACY IN THE VOLTAGEMEASUREMENT DURING STABLE
CONDITIONS i.e 80% TO 120% OF NOMINALSYSTEM VOLTAGE WITH BURDENS FROM25% TO 100% OF RATED BURDEN ATPOWER FACTOR OF 0.8 . IN VTs ALSO AS IN
CTs, RATIO AS WELL AS PHASE ERRORSARE THERE.
WHICH VT IS CONNECTED?
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 109/201
WHICH VT IS CONNECTED?Contd meter ing
IEC 60044-2 AND 60044-5 DEFINES THIS AS :
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 110/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 111/201
WHICH VT IS CONNECTED?
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 112/201
WHICH VT IS CONNECTED?contd protect ion
IEC 60044-2 AND 60044-5 DEFINES THIS AS :
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 113/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 114/201
Capacitor Voltage
Transformer
Causes of Failure andMonitoring/Maintenance
Capacitor Voltage Transformers
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 115/201
p g
Monitoring and maintenance
Causes of Failure
Due to Ferroresonance caused by primary/secondary disturbances
Oil leak at sealing points leading to ingress of moisture and
degradation of capacitor
Monitoring
Capacitance and tangent measurement using the tan delta kit at
periodic intervals or whenever there is a shut down
Using thermovision camera especially for 220kV to detect any high
temperature abnormalities IR check on secondary
To check the resistance of the damping wdg externally and also the
condition of the Lightning arrester in the sec terminal box
Capacitor Voltage Transformer
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 116/201
Definitions
Element Pack
(or pack)
Pile of elements : ± 10 to 25 kV
Capacitor Voltage Transformer
D fi i i
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 117/201
Definitions
Assembly of elements in an
insulating container: ± 245 kV.Can be connected to a HV line
Capacitor Unit
(or unit)
HV Power line
Ground
Capacitor Voltage Transformer
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 118/201
Definitions
Capacitor STACK
(or stack)
Assembly of elements to reach
higher voltage levels : ± 800 kV
HV Power line
Ground
In general, the term
CAPACITOR
stands for a capacitor element
as well as a capacitor stack.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 119/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 120/201
Capacitor Voltage Transformer
Magnetic Transformer
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 121/201
Lµ = Inductance equivalent to magnetic losses of the magnetic circuit.
R w = Resistance equivalent to the watt losses of the magnetic circuit.
Lfs = Secondary leakage inductance of the magnetic VT.
Rs = Resistance of the secondary winding
g
Ce La Lfs Ra Rs
Lμ Rw Zc Us U’P = Vp . C1 k . (C1+C2)
Equivalent Diagram
Capacitor Voltage TransformerCapacitor Elements
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 122/201
Capacitor Elements All Paper Dielectric design Mixed dielectric design
Paper PPR film + paper
Copper tabs for
connection
Aluminum foil
folded for contact
with next element
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 123/201
Capacitor Voltage Transformer
Damping Circuit
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 124/201
Short-circuit at zero crossing
Primary voltage
Secondary voltage
t
Vs
Vi
t
Damping CircuitPrimary Short Circuit & Transient Response
Capacitor Voltage TransformerDamping Circuit
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 125/201
Short-circuit at zero crossing
Primary voltage
Secondary voltage
t
Vs
Vi
t
5%
10%
Secondary error
t
0 100 200 300 [ms]
Necessary to add a damping circuit
20 msIEC 186
error limits
IEC today :
max 10% after 20ms
Primary Short Circuit & Transient Response
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 126/201
Capacitor Voltage TransformerDamping Circuit
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 127/201
R R-L-C R-L-RHow to solve transient problems :
• High
burden
• jeopardize
accuracy
• Efficient
• Easy to design
• Expensive
• Efficient
• Sophisticated design
• Economical
Primary Short Circuit & Transient Response
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 128/201
Capacitor Voltage TransformerDamping Circuit
150200
Tension primaire
Primary Voltage
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 129/201
Primary Short Circuit & Transient Response
-200
-100
0
100
200
3 0 0
3 5 0
4 0 0
4 5 0
5 0 0
5 5 0
6 0 0
Tension secondaireSecondary Voltage
-2
-1
0
1
2
3
4
5
6
7
3 0 0
3 5 0
4 0 0
4 5 0
5 0 0
5 5 0
6 0 0
% Erreur secondaire (transitoi re)% error at secondary
R-L-RR-L-R
-200-150
-100-50
050
100150
3 0 0
3 5 0
4 0 0
4 5 0
5 0 0
5 5 0
6 0 0
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 130/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 131/201
Transformers
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 132/201
Routine tests (IEC 60044-5)Routine tests
The following tests apply to each individual transformer:
a) Verification of terminal markings
b) Power-frequency withstand tests on primary windings
c) Partial discharge measurementd) Power-frequency withstand tests on secondary
windings
e) Power-frequency withstand tests between sections
f) Determination of errors.
G) Ferroresonance test
h) Sealing test
Voltage transformersProtection accuracy classes
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 133/201
Protection accuracy classesIEC 600 44-2
Accuracy classes (Protection)
Maximum error in % of VP
- Voltage between 5 % and f T x VNP
- Burden between 25% and 100% of SN
- Maximum error doubled for VNP=2%
Accuracy
class
Voltage
(ratio)
error
Phase
displacement
[minutes]Cl 3P
3 %
120
Cl 6P
6 %
24O
Capacitor Voltage Transformer
T t t (IEC 60044 5)
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 134/201
Type tests (IEC 60044-5)
a) Temperature-rise test
b) Short-circuit withstand capability test
c) Lightning impulse test
d) Switching impulse test
e) Wet test for outdoor type transformers
f) Determination of errors.
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 135/201
Condition Monitoring
and FailureInvestigations of
Instrument
Transformers
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 136/201
Live Tank CTs
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 137/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 138/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 139/201
CT Design
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 140/201
g
Core Material –
The main aim is togive high accuracy with low
saturation factor.
Core Material is made of CRGO
Silicon steel
For very low loss characteristics, µ
material (Alloy of Ni-Fe) is used
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 141/201
CT accuraciesAs per IEC-60044(1)
Metering Core – ±0.2 or 0.5% atrated Currents
Protection Cores –
±
1% at ratedcurrent
Accuracies as per IEC-60044-1
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 142/201
p
Class 5% of
rated I
20% of
rated I
100% of
rated I
120% of
rated I
0.2 0.75 0.35 0.2 0.2
0.5 1.5 0.75 0.5 0.5
Protection Cores
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 143/201
Protection Cores
Class Current Error at
rated Primary
Current
Composite Error at
rated accuracy limit
Primary Current
5P ±1% ±5%
10P ±3% ±10%
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 144/201
Ph A l E
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 145/201
Phase Angle Error
The difference in Phase between
the Primary and Secondary
current vectors
i
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 146/201
Knee Point Voltage
10% increase in Voltage will lead to
30% or more increase in Current.
Insulation Levels
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 147/201
Insulation Levels
For Windings having Um greater than
300kV, the rated insulation level is
determined by rated switching and
lightning impulse withstand voltage
For voltages < 300kV, insulation levels
are decided by lightning impulse and
power-frequency withstand voltages
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 148/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 149/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 150/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 151/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 152/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 153/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 154/201
CT Insulation
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 155/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 156/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 157/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 158/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 159/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 160/201
GSTg Mode of Measurement
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 161/201
g
Here measurement is done for CHE
as L is guarded
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 162/201
Negative Tan delta
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 163/201
Negative Tan delta
Negative tan delta may result if there is
shunt to ground in between the points of
measurement
Heavily polluted porcelain exterior surface
or porcelain internal surface contamination
may result in negative tan delta reading
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 164/201
Negative Tan Delta
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 165/201
g
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 166/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 167/201
CT FAILURES
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 168/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 169/201
Primary Insulation failure
due to moisture entry
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 170/201
due to moisture entry
Violent failure due to arcing
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 171/201
g
CT under Flames
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 172/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 173/201
Burnt CT
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 174/201
Puncturing of Paper Insulation
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 175/201
g p
Depression and wrinkles in paper
wrapping
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 176/201
wrapping
Wrinkles in Paper
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 177/201
Sharp edges on primary
conductor
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 178/201
conductor
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 179/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 180/201
CVT Construction Details
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 181/201
CVT Construction Details
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 182/201
There are 280 – 300 elements inC1 & C2
C1 will be about 260 to 280
elements
C2 will be 15 to 20 elements
Ratio of C1/ C2 is about 20
400/ 20 = 20kV (Tap Voltage)
Compensating Reactor
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 183/201
Compensating Reactor
Compensating Reactor is provided
to compensate for the phase
displacement in Capacitor elements
ωL = 1/ω (C1+C2)
L = 1/ ω
2 (C1+C2)
Ferro Resonance
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 184/201
Ferro resonance in CVTs is due to the
Capacitance in Voltage Divider in series with
the inductance of the Transformer and series
reactor. This circuit is brought to resonanceby various disturbances in the network that
may saturate the iron core of the transformer,
over heat electro magnetic unit and lead toinsulation breakdown.
Ferro Resonance Circuit
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 185/201
Ferro resonance circuit is provided in
CVT Secondary to suppress Ferro
resonance oscillations
There can be active or passive Ferro
resonance circuits
It can be RLC circuit (ABB make CVTs)
or RL circuit (CGL, BHEL CVTs)
CVT VA Ratings VA ratings for core 1 core 2 and core 3 are
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 186/201
VA ratings for core-1, core-2 and core-3 are
generally 200VA, 200VA and 100VArespectively.
CVT accuracies are guaranteed if connected
burdens are within 25% to 100% of therated burdens
In POWERGRID, with static meters andstatic/ numerical relays, connected burdensare 10 to 20 VA in each core which are verylow as compared to rated burdens.
CVT Secondary Voltage
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 187/201
CVT Secondary Voltage v = k * V * C1/ (C1+C2)
V – Primary Voltage
k – Secondary Transformation ratio
Note:
Puncturing of C1 – Secondary Voltage will increase
Puncturing of C2 – Secondary Voltage will decrease
Condition Monitoring
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 188/201
Condition Monitoring
Secondary Voltage
measurement
Capacitance and Tan delta
measurement of stacks
Secondary Voltage measurement
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 189/201
Periodic measurement to be carried out. In caseof doubt, simultaneous measurement to be
carried out with another feeder/ Bus CVT.
For 400kV CVTs puncturing of one Capacitorelement in C1 side is likely to increase Secondary
Voltage by about 0.35 – 0.45% (0.22 – 0.28V)
Failure of one Capacitor element in C2 side islikely to decrease Secondary Voltage by 5 – 6%
(3.2 – 3.8V)
Capacitance and Tan delta
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 190/201
p
measurement of stacks
Change in Capacitance value
above 6%, CVT need to bereplaced
Tan delta values more than 0.003
from pre-commissioning value
needs replacement
Reasons for Failure of CVTs
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 191/201
WRINKLES ON ALUMINUM FOIL
POOR SOLDERING QUALITY
POOR QUALITY OF PAPER (LOCAL SOURCE)
PINHOLES IN BELLOWS
SNAPPING OF BELLOW CONNECTION
OVERHEATING OF DAMPING RESISTOR
SHORTING OF TRANSFORMER CORES
FAILURES OF FR CIRCUIT COMPONENTS
RUSTING OF COUPLING BOLTS (BETWEENFLANGE AND EMU TANK)
RUSTING OF FLANGE
Reasons for Failure of CVTs …
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 192/201
LOOSENESS OF CORE BOLTS SNAPPING OF CONNECTION BETWEEN
PRIMARY WINDING AND COMPENSATINGREACTOR
FAILURE OF VARISTORS PROVIDED INSECONDARY
ENTRY OF MOISTURE IN CAPACITORSTACKS
MOISTURE ENTRY DUE TO POOR GASKETQUALITY
CVT Failures
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 193/201
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 194/201
Failure of Bellow
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 195/201
Rusting of Coupling bolt
and moisture entry
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 196/201
and moisture entry
Rusting of flange
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 197/201
Rusting of EMU Tank
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 198/201
Capacitive Voltage Transformers
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 199/201
0
1
2
3
4
1 9 9 4
1 9 9 5
1 9 9 6
1 9 9 7
1 9 9 8
1 9 9 9
2 0 0 0
2 0 0 1
2 0 0 2
2 0 0 3
2 0 0 4
2 0 0 5
2 0 0 6
YEAR
% a
g e p e r
y e a r
In last 4-1/2 yrs, newly commissioned CVTs failed 40 nos.
Old CVTs failed- 101 nos.
Secondary Voltage measurement Norms
Sr.
N
Drift in Sec.
Voltage
Condition of CVT Measurement
Frequency
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 200/201
No. Voltage Frequency
1 Upto ±0.5 Volts Healthy Six monthly
2 ±0.5 to ±0.8 Volts Needs monitoring Three monthly
3 +0.8 to +1.2 Volts Needs close
monitoring4 +1.2 to +2.0 Volts Needs close
monitoring
15 days
5 Above +2.0 volts Alarming/ critical Needs replacement
6 -0.8 to -4.0 volts Needs closemonitoring 15 days
7 Less than -4.0 volts Alarming Needs replacement
7/26/2019 1431928792session II Ct & Vt
http://slidepdf.com/reader/full/1431928792session-ii-ct-vt 201/201