  • 8/10/2019 Lecture3 CT & VT

    1/19

    CURRENT AND

    VOLTAGE

    TRANSFORMERS

  • 8/10/2019 Lecture3 CT & VT

    2/19

    Voltage transformers:

    The function of voltage transformers isgrouped as:

    Measurement VTs- Limits well defined. Protection VTs.

    - Operation over wide range of

    voltages.

    They have different characteristics.

  • 8/10/2019 Lecture3 CT & VT

    3/19

    They may be single phase or three phases.VTs are necessary for voltage, directional,and distance protection.

    The primary of VT is connected directly topower circuit between phase and grounddepending upon rated voltage and

    application. The volt- ampere rating of voltage

    transformer is lesser as compared with thatof power transformers.

    Voltage transformers:

  • 8/10/2019 Lecture3 CT & VT

    4/19

    There are two types of constructions:

    Electromagnetic potential transformer inwhich primary and secondary are

    wound on magnetic core.

    Capacitor potential transformer, inwhich the primary voltage is applied to

    to series capacitor group.

    Voltage transformers:

  • 8/10/2019 Lecture3 CT & VT

    5/19

    Specifications for VTs:

    Rated primary voltage

    Rated secondary voltage

    Rated burden Supply frequency

    Number of phases

    Class of accuracy

    Insulation level, power frequency andimpulse voltage withstand.

    Limits of dimensions, types ofconstruction,

  • 8/10/2019 Lecture3 CT & VT

    6/19

    Rated characteristics:

    Rated voltage.

    The voltage marked on the rating plate ofthe VT. There are several values of

    standard primary voltages. (11 kV, 33 kV,132 kV, 400 kV)

    Rated transformation ratio:

    The ratio of rated primary voltage to ratedsecondary voltage.

    Rated secondary voltage:It is the value of secondary voltage markedon name plate. For example: 110/3 V

  • 8/10/2019 Lecture3 CT & VT

    7/19

    Rated characteristics:

    Residual voltage:

    Vector sum of three lines to earth

    voltages, i.e

    Vres = Vrn + Vyn +Vbn

    Phase error:

    The phase angle between primary voltage

    vector and the reversed secondary voltagevector (measured in minutes).

  • 8/10/2019 Lecture3 CT & VT

    8/19

    Rated characteristics:

    Ratio error:

    Percentage ratio error = 100(KnVs - Vp)/ Vp

    Where Kn = normal ratio

    Vs = secondary voltage

    Vp= primary voltage

    Rated burden:

    The burden assigned by manufacturer at which theV.T performs with specified accuracy.

  • 8/10/2019 Lecture3 CT & VT

    9/19

    Site testing of VTs

    Ratio test Insulation test

    Resistance test

    On load test

  • 8/10/2019 Lecture3 CT & VT

    10/19

    Sample of low voltage VT

  • 8/10/2019 Lecture3 CT & VT

    11/19

    Current transformers:

    The function of current transformers isgrouped as:

    Measurement CTs- Limits well defined.

    Protection CTs.- Operation over wide range of

    currents.

    They have different characteristics.

  • 8/10/2019 Lecture3 CT & VT

    12/19

    Current transformers:

    The current transformers(CT) step down AC current

    to a low value (1 A, 5A).The volt- ampere rating of

    current transformer is lesseras compared with that ofpower transformers.

  • 8/10/2019 Lecture3 CT & VT

    13/19

    Specification for CTs:

    Rated primary current

    Rated secondary current

    Rated burden

    Supply frequency Number of phases

    Class of accuracy

    Insulation level, power frequency and

    impulse voltage withstand. Limits of dimensions, types of

    construction,

  • 8/10/2019 Lecture3 CT & VT

    14/19

    Rated characteristics:

    Rated primary current.

    The value of primary current on which the performanceof the current transformer is specified by themanufacturer. (rms value)

    Rated short time current (Primary)

    It is defined as r.m.s value of a.c component which theCT can carry for rated time without damage due tothermal or electrodynamics stresses.

    Rated secondary current:

    It is the value of secondary current marked on nameplate.

  • 8/10/2019 Lecture3 CT & VT

    15/19

    Rated characteristics:

    Phase error:

    The phase angle between primary current vectorand the reversed secondary current vector(measured in minutes).

    Ratio error:

    Percentage ratio error = 100(KnIs - Ip)/ Ip

    Where Kn = normal ratio

    Is = secondary current

    Ip = primary current Rated burden:

    The burden assigned by manufacturer at which theC.T performs with specified accuracy.

  • 8/10/2019 Lecture3 CT & VT

    16/19

    Rated characteristics:

    Accuracy class

    The class assigned to the current

    transformer with the specified limitsof ratio error and phase angle error.

    (5P20)

    Rated exciting currentThe r.m.s value of current taken by

    the secondary-winding of a C.T.

  • 8/10/2019 Lecture3 CT & VT

    17/19

    Site testing of CTs

    Ratio test

    Insulation test

    Resistance test

    Magnetizing current test

    Polarity test

    On load test

  • 8/10/2019 Lecture3 CT & VT

    18/19

  • 8/10/2019 Lecture3 CT & VT

    19/19

    Sample of low voltage CT