(20) particular specifications - e...
TRANSCRIPT
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 221 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
(20) PARTICULAR SPECIFICATIONS
(ELECTRICAL WORKS)
20.1 GENERAL:
The intent of these specifications is to give general guidelines for the
equipment’s / components proposed to be used and best efforts are
made to cover all relevant requirements and apart intent specification.
However if any addition or alternation is necessitated and directed by
the competent Authority the same shall be done without any extra cost
of financial implication on the CIDCO as per the directives of
Engineer.
20.2 APPLICABLE STANDARDS:
All relevant Indian standards shall be made applicable with latest
amendments. Also if any other specific application is required by the
owners then the same shall be complied too.
ITEM NO. 1 & 2
20.3 SPECIFICATIONS FOR 13 MTRS. & 9 MTRS. RSJ POLES
20.3.1 The pole for H.T. line shall be 152mm x 152 mm rolled steel joist
pole of 13 mtr. height and 9 mtr. height the weight of the pole shall be
minimum of 37.1Kg/Mtr.
20.3.2 A base plate made out of CI and of size 300 mm x 300 mm x 10
mm shall be welded continuously at the pole bottom.
20.3.3 Provision for terminating the earthwire coming from the earthing
station shall be made for the pole at a height of 3.0 mtr. from the
pole bottom with 16 mm dia, 50 mm long G.I. bolt and G.I.
washers.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 222 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 20.3.4 The pole shall be erected in a perfectly vertical alignment by
excavating a pit of size 0.8 mtr. x 0.6 mtr. x 2.15 mtr. deep with
1:3:6 ratio cement concrete with duly plastered plinth or muffing of
width 400 mm and height of 600 mm from the ground level and of
appropriate shape. The center to center distance between two
consecutive poles shall be as per the I.E. rules & regulations and local
Electricity Supply Authority.
20.3.5 The poles shall be subjected to surface treatment with wire brushing
and cleaning prior to painting with one coat of red oxide and two
coats of black bituminous paint upto 2.5 mtr. height and for remaining
portion with alluminium paint of two coats.
ITEM NO. 3
20.4 ALUMINUM CONDUCTOR STEEL REINFORCED CONDUCTOR
20.4.1 Scope:
Supply and erection of aluminum conductor steel reinforced for
overhead line.
This specification provides for Supply & Erection of 0.2 ALUMINIUM
CONDUCTOR STEEL REINFORCED (ACSR) Conductor (PANTHER ) for
High Voltage overhead lines.
20.4.2 SERVICE CONDITIONS
The conductor to be supplied against this specification shall be suitable
for satisfactory continuous operation under the following tropical
climatic conditions:
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 223 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 20.4.3 STANDARDS
Sr.No. Particulars Values
(a) Maximum Ambient Temperature
in open air 50 Degree C.
(b) Maximum Ambient Temperature
in shade 45 Degree C.
(c) Minimum Ambient Temperature
in shade 3.5 Degree C.
(d) Relative Humidity 10 % to100%
(e) Maximum Annual Rainfall 1450 mm.
(f) Maximum Altitude above Mean
Sea level. 1000 metres
(g) Maximum Wind Pressure 150Kg/Sq.m.
(h) Isoceraunic level 50 days/year.
(i) Seismic level
(Horizontal acceleration ) 0.3 g
(j) General nature of climate Moderately hot and
humid tropical climate,
conductive to rust and
fungus growth Except as modified in this Specification, the conductor shall conform to
the following Indian Standards (Amended upto date).
Sr.No. Indian Standards
Title
1 IS:398 Part II
/1996
Specification for Aluminum conductors for
overhead Transmission purpose.
2 IS:1778 /
1980 Reels and Drums for Bare conductors.
3 IS:2629 Recommended practice for Hot Dip
Galvanising of Iron and Steel.
4 IS:4826 Galvanised Coating on Round Steel Wire.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 224 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
Sr.No. Indian Standards
Title
5 IS:5484 EC grade Aluminium rod produced by
continuous casting and rolling (First
Revision).
20.4.4 PROPERTIES OF CONDUCTOR
The details of ACSR “Panther” conductor are tabulated below:
Sr.No. Particulars Values (a) Stranding and wire
diameter
Aluminium: 30/3.00 mm.,
Steel: 7/3.00 mm.
(b) Number of Strands
(i) Steel Centre 1
(ii) 1st Steel Layer 6
(iii) 1st Aluminium Layer 12
(iv) 2nd Aluminium Layer 18
(c) Sectional area of
Aluminium in sq. mm. 212.1
(d) Sectional area of Steel in
sq. mm. 49.4
(e) Total sectional area in
sq.mm. 261.5
(f) Overall Diameter in mm. 21.00
(g) Approximate weight in
kg/km. 974
(h) Calculated D.C. Resistance
at 20 degree Celsius in
Ohm/km.
0.139
(i) Minimum Breaking load in
kN 89.67
(j) Modulus of Elasticity in
GN/sq.metre. 80.00
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 225 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 20.4.5 THE DETAILS OF ALUMINIUM STRANDS ARE AS BELOW:
Sr.No. Particulars Values
(a) Minimum Breaking Load of Strand before
stranding in kN
1.17
(b) Minimum Breaking Load of Strand after
stranding in kN.
1.11
(c) Maximum D.C. Resistance of Strand at 20
Degree Celsius in Ohm/km.
4.079
20.4.6 THE DETAILS OF STEEL STRANDS ARE AS BELOW:
WIRE SIZE
Sr.
No. Particulars Values
(a) Minimum Breaking Load of Strand before
stranding in kN. 9.29
(b) Minimum Breaking Load of Strand after
stranding in kN. 8.83
(c) Minimum weight of Zinc Coating after
stranding in gm/sq. Metre. 260
20.4.7 NOMINAL SIZE
The aluminium and galvanised steel wires for the stranded conductor
covered by this standard shall have diameters specified in Clause
20.4.1. The diameter of the galvanized steel wires shall be measured
over the zinc coating.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 226 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 20.4.8 TOLERANCE ON NORMAL SIZE
(i) ALUMINIUM WIRES: No negative tolerance shall be permitted
on the nominal diameter of Al wires. However, positive
tolerance in this regards shall be as provided in IS:398 ( part2)
amended upto date.
(ii) GALVANISED STEEL WIRES: A tolerance of +/2 % is permitted
on the nominal diameter.
20.4.9 FREEDOM FROM DEFECTS
The wires shall be smooth and free from all imperfections such as
spills, spilts, slag inclusion, die marks, scratches, fittings, blowholes,
projections, looseness, overlapping of strands, chipping of aluminium
layers etc. and all such other defects which may hamper the
mechanical and electrical properties of the conductor. Special care
should be taken to keep away dirt, grit etc. during stranding.
20.4.10 JOINTS IN WIRES
(i) Aluminium Wires: No joints shall be permitted in the aluminium
wires in the outermost layer of the ACSR conductor. Joints in the
inner layers are permitted, in addition to those made in the
base rod or wire before final drawing, but no two such joints
shall be less than 15 metre apart in the complete stranded
conductor. Such joints shall be made by cold pressure butt-
welding.
Joints are not permitted in the outermost layer of the conductor
in order to ensure a smooth conductor finish.
(ii) Galvanised Steel Wires: There shall be no joints except those in
the base rod or wire before final drawing, in steel wires forming
the core of the steel reinforced aluminium conductor.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 227 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
Joints are not permitted in the steel wires after final drawing in
order to avoid reduction in the breaking strength of the conduct
or that may occur as a result of failure of the joints.
20.4.11 STRANDING
(i) The wires used in the construction of galvanised steel reinforced
aluminium conductor shall before stranding, satisfy all the
relevant requirements of this specification.
(ii) The lay ratio of the different layers shall be within the limit given
in the following table:
20.4.12 LAY RATIO OF ALUMINIUM CONDUCTORS GALVANISED STEEL
REINFORCED ‘PANTHER’ CONDUCTOR
(1) Number of Wire : Aluminium : 30 Steel : 7
(2) Ratio of Diameter : 1.0
(3) Lay Ratio for Steel Core (6 Wire Layer) : Minimum : 13 Maximum : 28
(4) Lay Ratio for Aluminium Wires:
(i) Outermost Layer : Minimum : 10 Maximum : 14
(ii) Layer immediately beneath outermost Minimum: 10 Layer: Maximum: 16
NOTE: For the purpose of calculation, the mean lay ratio shall be taken as the
arithmetic mean of the relevant minimum and maximum values given
in the above table.
(iii) While stranding, pre forming and post forming method should be used for
stranded steel core. In order to relieve the residual tension in core wire to
avoid flaring of conductor.
(iv) In all constructions, the successive layers shall have opposite directions of lay,
the outermost layer being righthanded. The wires in each layer shall be
evenly and closely stranded.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 228 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 (v) In conductors having multiple layers of aluminium wires, the layratio of any
aluminium layer shall not be greater than the layratio of aluminium layer
immediately beneath it.
Table 20.4/1
Minimum Clearance between Conductors
(IS : 4237 – 1967)
Clearance in mm Sr. No.
Voltage Level (kN) Between Phases
Between Phase & Earth
7. 11 460 305
8. 22 610 460
9. 33 915 610
10. 110 1675 1000
11. 230 3350 1675
12. 400 4000 3500
20.4.13 The conductor shall be Panther alluminium conductor steel reinforced
and size as specified & with generally having current carrying capacity
of 325 amps. of 40 degree centigrade and consisting of a bunch of
six/ seven stranded alluminium conductors and one steel reinforcing
wire at the center. The weight of the conductor shall be 974Kg/Km.
20.4.14 The conductor shall generally conform to I.S. 398 Part-II - 1976 with
latest amendments.
20.4.15 STRINGING OF CONDUCTORS:
a) Peels of the conductor shall be handled carefully so that there is
no cutting, nicking of fraying of the conductor strands.
b) The conductor shall be paid out from a rotating red supported
on jacks for easy unwinding.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 229 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
c) Alluminium sheaves fitted with ball bearings shall be used at the
points of conductor supports for easy pulling and to ensure
uniform tension throughout the conductor length.
d) The conductor shall be pulled with proper care along clamp.
e) The conductor should be pulled up to a proper sag in a span at
or near the dead end section of the line.
f) The tension should then be adjusted until correct sag is obtained
in a span near the pulling end.
g) Generally in straight length cut points shall be provided at a
distance of about 1 Km. or as desired by MSEB/CIDCO.
h) The minimum clearances from the conductor shall be as per
rule `17 to 79’ and 80 of I.E. Rules.
20.4.16 a) Annealed alluminium wire shall be used for fastening the
conductors.
b) The anticlimbing device consisting of barbed wire extending
upto a minimum length of 38 cms. or any other suitable design
shall be provided on all H.T. poles.
c) The danger or caution sign board to be displayed on all H.T.
Poles shall be as per I.S. 2551 - 1963.
d) All stay wires are required to be properly earthed.
e) At all road crossing points guard wires are required to be
used as per rule No.88 of I.E. rules.
20.4.17 Method of Construction :
At first the conductor is removed from bundle / drum straighten
without knots, bends, etc.
Stringing of conductor shall be done with draw vice. Conductor shall
not be twisted while stringing. Disc insulators shall be used if the line
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 230 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
deviates by 30 degrees or more, terminal pole and tri-pole or four
pole structure at terminal pole and at junction / cut pole.
Parallel double groove clamp having two nut bolts designated to carry
full line current shall be used for making Jumper wire connections.
Universal parallel double groove clamp having two nut bolts shall be
used for Tap Off point.
On straight line the conductor shall be bounded on top groove of
insulator and at angular position binding shall be done in side groove.
Binding wire of 12 SWG shall be of the same metal as that of
conductor.
20.4.18 Mode of Measurement :
For measurement purpose, sum of the total conductor including
jumper connections shall be considered. (i.e. per km)
ITEM NO. : 4
20.5 PIN TYPE INSULATOR 11/22/33 KV
20.5.1 Scope:
Supplying porcelain Pin type insulator, suitable for 11/22/33 Kv and
necessary ancillary materials and complete erection on provided cross
arm / bracket and connected to the over-head line as per instructions
from the site engineer.
Material :
Insulator : Distribution class Pin type insulator made from porcelain,
suitable for specified voltage level, having ISI mark, with necessary
hardware
Hardware: Nuts, washers. Etc.
Binding Wire : Bare Copper wire or conductor.
Clamps : MS Clamps.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 231 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 20.5.2 General
a) All the insulators shall be made out of glazed porcelain or
rough glass and suitable for 22KV line voltage.
b) The pin insulators shall generally be as per I.S. 731-1963 and
the disc insulators shall be generally as per I.S. 731 – 1963 and
I.S. 3188 – 1965 with all latest amendments.
c) 4.3 The manufacturer’s dimensional drawings should be
submitted for pin type insulator.
d) Providing suitable size tension hardware made out of cast
alluminium suitable ACSR conductors etc. complete. The work
should be carried out as per instructions of the Engineer.
20.5.3 Method of Construction :
Distribution class porcelain pin type insulator, suitable for specified
voltage level, erected on provided cross arm or bracket with clamps,
ancillary materials, and connected to the over-head line. Connection
shall be made with bare copper wire of specified gauge.
20.5.4 Mode of Measurement :
Executed quantity will be measured on number basis (i.e. each)
ITEM NO. : 5
20.6 PORCELAIN DISC. TYPE INSULATOR 11/22/33 KV
Supplying and erecting porcelain disc type insulator suitable for 22KV
line complete erected with suitable hardware on provided cross arm
20.6.1 Scope:
Supplying porcelain disc type insulator, suitable for 11/22/33 KV and
necessary ancillary materials, and complete erection on provided cross
arm / bracket and connected to the over-head line as per instructions
from the site engineer.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 232 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
Material:
Insulator: Distribution class Disc type insulator made from porcelain,
suitable for specified for specified voltage level, having ISI mark, with
necessary hardware.
Hardware: Nuts, washers, etc.
Binding Wire: Bare Copper wire or conductor.
Clamps: MS clamps.
20.6.2 Method of construction:
Distribution class Disc type insulator made from porcelain, suitable for
specified voltage level, erected on provided cross arm or bracket with
clamps, ancillary materials, and connected to the over-head line.
Connection shall be made with bare copper wire of specified guage.
20.6.3 Mode of Measurement:
Executed quantity will be measured on number basis (i.e. each)
ITEM NO. : 6 & 7
20.7 PLATE TYPE EARTHING
(WITH OR WITHOUT CI COVER, FUNNEL, ETC)
20.7.1 Scope
Supplying and erecting galvanised cast iron / copper earth plate type /
G.I. pipe type earthing with / without C.I. cover as per instructions
from the site engineer.
Material:
Earth Plate: Galvanised cast iron / Copper earth plate or G.I. pipe as
per specifications given in Table No 20.7/1.
CI Cover: As per specifications given in Table No 20.7/1.
Earthing Conductor: Copper/G.I strip/Annealed bare copper wire/G.I.
earth wire of size as per specifications given in Table No 20.7/1.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 233 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
GI Pipe: As per specification (CW-PLB/GP) mentioned chapter no.
20.7/1.5 for watering, and as enclosure for Earth wire, refer
specifications given in Table No 20.7/1.
Hardware: Screw / nut bolts with required washer of dimensions, Rawl
plug / clip/ 'U' nails and material as per specifications given in Table
No 20.7/1.
Filling material: Coal /Charcoal/ salt as per specifications given in
Table No 20.7/1.1.
Lugs: As per specification (CB-LG/AL, CB-LG/CU) mentioned chapter
20.7/1.9 & 20.7/1.10 Copper/ Aluminum lugs as per specifications
given in Table No 20.7/1.
Table No. 20.7/1
Detailed Specifications of various types of Earthing
Type of earthing
S.
No. Particulars
Galvanised
cast iron
earth plate
type without
C. I. cover
Copper
earth plate
type with
C. I. cover
Galvanised
cast iron
earth plate
type with
C. I. cover
Pipe type
earthing
without C. I.
Cover
1. Depth from top of
plate
Up to Ground level
1.5 m
Galvanised 1.5 m
1.5 m
Galvanised -
2. Size & type of
material for pipe /
Plate type earthing
Cast iron
earth plate
size
60x60x0.6
cms
Copper
earth plate
size
60x60x0.6
cms
Cast iron
earth plate
size
60x60x0.6
cms
‘B’ grade
G. I. pipe
40 mm dia.
2.5 mtr.
Long or 20
mm dia. G.
I. Rod
3. Salt / Charcoal 30 Kg.
charcoal
and slat
30 Kg.
charcoal
and salt
40 Kg.
charcoal
and salt
N.A.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 234 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
Type of earthing
S.
No. Particulars
Galvanised
cast iron
earth plate
type without
C. I. cover
Copper
earth plate
type with
C. I. cover
Galvanised
cast iron
earth plate
type with
C. I. cover
Pipe type
earthing
without C. I.
Cover
each each each
4. Type of Wire Double G.I.
wire 8 SWG
Double G.I.
8 SWG
Double G.I.
6 SWG
Double G.I.
8 SWG
5. Wire enclosure 12 mm dia.
G. I. Pipe 2
mtr. long
12 mm dia.
G. I. Pipe 2
mtr. long
12 mm dia.
G. I. Pipe
2.5 mtr.
long
N.A.
6. Nut bolts 12 mm dia.
Cadmium /
GI
12 mm dia. Cadmium / N.A.
7. Washers GI GI GI N.A.
8. Watering Pipe 19 mm dia.
G. I. Pipe
19 mm dia.
G. I. Pipe
19 mm dia.
G. I. Pipe N.A.
9. Lungs Yes Yes Yes Yes
10. Funnel No Yes Yes N.A.
11. Brick Masonry No Yes Yes N.A.
20.7.2 Method of construction: Pit is' to be dug of required dimension and depth for the earthing at
site, and laying of Galvanised cast iron / Copper earth plate or G.I.
pipe shall be as per Table No 20.7/1. The earth connection to
equipment / switch gear and earthing electrode shall be connected as
shown in the diagram and as per IS 3043 amender up to-date. The
connections shall be made either by strip or double run of earth wire
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 235 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
with drilling, welding, riveting, brazing and nut bolting to plate or
pipe, where ever required in an approved manner. As far as possible
continuous strip shall be used, but where ever jointing of strip is
unavoidable; the overlap portion must not be less than 21/2 times the
width of the strip either welded/ brazed/soldered by all sides or 6
inches overlap with two nut bolts/riveting of adequate size with
requited washer and covered by anti-corrosive paint as per approved
jointing practice in the industry and as per directives from site engineer
in charge.
Pit shall then be filled with screened soil with alternate layer of coal
and3alt, and if, necessary brick masonry work (Where ever applicable)
shall be done as specified in IS: 3043, with laying wires in PVC/ G.I.
pipe and watering arrangement and covered with C.I. Cover (Where
ever applicable). .
Where ever required or as specified by Site Engineer, a Test link shall
be provided for facilitating the testing of resistance of earth electrode.
20.7.3 Testing:
The value of each earth electrode shall be measured by earth tester in
presence of site Engineer and record to be submitted.
20.7.4 Mode of Measurement:
Executed quantity will be measured on number basis (i.e. each)
ITEM NO. : 8
20.8 Providing cement Concrete for Foundation or for concrete filling in
1:3:6 ratio with 20 to 25 mm stone metal duly plastered with
necessary curing for pole muffing or any other purpose.
The work should be carried out as per the instructions of the Engineer.
And payment will be made as mentioned in Schedule “A.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 236 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 ITEM NO. : 9
20.9 VEE CROSS ARM
20.9.1 Scope :
Supplying Vee cross arm suitable for 22 kV and necessary ancillary
materials complete erection on provided pole with necessary painting
as per specification and as per instructions from the site engineer.
Material :
Cross arm : Channel Iron cross arm
Hardware : G. I. nut bolts
Flat : MS flat 80 x 10 mm thick
Clamp : Two clamps made from MS flat of size 80 x 10 mm.
Paint : Red oxide, Silver paint
20.9.2 Method of Construction :
Fabricating the Vee cross arm for erecting Insulators with channel 75 x
40 mm with 4.4 mm thick web and 7.3 mm thick flange, length of 45
mm for base of insulator, vertical member of suitable length to
maintain the clearance of 1530 mm, with angle of 60 degrees to
horizontal and M. S. flat of 80 x 10 mm. at centre of cross arm fixed to
the pole by means of two M. S. clamps of 80 x 10 mm M. S. flat with
15mm. dia bolts and nuts duly painted with one coat of red oxide
paint and two coats of aluminum paint.
Table No. 9/1
DETAILS OF IRON CROSS ARM / BRACKET AS PER ITEM IN CSR
Item
description Size of channel Clamps Nut bolts
100x50
channel cross
arm
100x50 mm with 4.7 mm
thick web and 7.5 mm thick
flange channel x 2.7 m length
Two clamps
of 50x6 mm
M. S. flat
15 mm. nuts and
bolts
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 237 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
Item
description Size of channel Clamps Nut bolts
Vee-cross
arm
Made out of channel 75 x 40
mm with 4.4 mm thick web
and 7.3 mm thick flange with
clearance of 1220 mm.
between the insulators as per
drawing attached here with
Clamps for
75x10 mm of
M. S. flat
15 mm. nuts and
bolts
Vee-cross arm 100x50 mm with 4.7 mm
thick web and 7.5 mm thick
web and 7.5 mm thick flange
size suitable with clearance of
1530 mm between the
insulators
Clamps for
75x10 mm of
M. S. flat
15 mm. nuts and
bolts
Channel with
clamp for
erection for
11/22 KV pin
insulators
75x40 mm with 4.4 mm thick
web and 7.3 mm thick flange
channel.
Clamps for
75x10 mm of
M. S. flat
with 3 sets screws
Channel
bracket for
guarding
Channel iron 1600 mm in
length and 75x40 mm with
4.4 mm thick web and 7.3
mm thick flange
Clamps for
50x6 mm of
M. S. flat
15 mm. dia nuts
and bolts with 2
earthing clips,
made from 25x3
mm.
Angle iron
bracket for
guarding
Angle iron bracket 65 x 65 x
6 mm. Angle 1600 mm in
length and 75x40 mm with
4.4 mm thick web and 7.3
mm thick flange.
Clamps for
50x6 mm of
M. S. flat
15 mm. dia nuts
and bolts with 2
earthing clips,
made from 25x3
mm.
20.9.3 Mode of Measurement :
Executed quantity will be measured on number basis (i.e. each)
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 238 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 ITEM NO. : 10
20.10 Supplying & Erecting G.I strip of different size used other purpose with
necessary G.I clamps fixed on wall painted with bituminous paint is an
approved manner.
The work should be carried out as per the instructions of the Engineer.
And payment will be made as mentioned in Schedule “A.
ITEM NO. : 11
20.11 22 KV DANGER BOARD:
Providing & fixing G.I Caution board fabricated from 16SWG sheet of
size 200 x 150 mm (min). The board shall be written in Marathi &
English indicating pressure of line danger etc. as required Electricity
Rules & Regulation and as per IS: 2551 of 1982.
Contractor has to provide to provide 22KV danger board one number
on each pole of appropriate size and with proper signals with
appropriate painting with approved colours as per IE rules.
ITEM NO. : 12
20.12 H.T. STAY SET:
Supplying and erecting G.I stay set for poles, complete with anchor
plate 300x300x6mm straining screws G.I stay wire 7/8 SWG G.I stay
rod 20mm x 1.8 meter length and pole clamps duly erected in
provided cement concrete foundation.
20.12.1. G.I Stay set for poles including loop insulators at in-accessible height
complete with anchor plate of size 15 x 15 x 0.6 cms, straining
screws, G.I Stay wire 7/10 size, G.I. Stay rod 20mm x 1.8 M long and
pole clamps etc. Stay sets erected in 1:3:6 cement concrete
foundation approx. quantity 0.35 m3 for each set.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 239 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 20.12.2 Providing G.I. stay wire for poles of appropriate thickness and length
suitable for H.T. line. The work should be carried out as per the
instructions of the Engineere.
20.12.3 Providing binding wire for binding the G.I. stay wire of the poles
suitable for H.T. overhead line of appropriate tensile strength &
thickness. The work should be carried out as per the instructions of the
Engineer.
20.12.4 Supplying and erecting anticlimbing devices, fabricated from pole
clamps with dropping spikes, welded to it and erected on pole
properly. The work should be carried out as per the instructions of the
Engineer.
20.12.5 Providing cement concrete foundation for above poles of size 0.8 mtr.
x 0.6 mtr. x 2.15 mtr. deep with 1:3:6 cement concrete ratio with duly
plastered plinth/muffing or width 400mm. & height of 600 mm. from
the ground level with appropriate shape. The plastering should be
done with approved quality cement with proper curing etc. complete.
The work should be carried out as per the instructions of the Engineer.
ITEM NO. 13
20.13 Preparation of schematic & detailed drawings as required by statutory
Authority and submission of the same in required sets to the statutory
authority on behalf of CIDCO, obtaining the approval for
commencement and commissioning of the work. Payment of statutory
authority, co-ordination with authority for the site visits etc. and
submission of As Built Drawings in 3 sets in the form of prints and in
the form of CD. The work also includes obtaining approvals of
material, handing over of the installation to the statutory authority on
completion of the work under the guidance of Engineer. And payment
will be made as mentioned in Schedule “A”.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 240 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 Item
No. Description
20.14 Supplying & erecting anticlimbing devices, fabricated from pole clamps with
drooping spikes welded to it and erected on pole.
20.15 Excavating hard rock or bituminous rod (B.T) by chiseling for preparing pit for
poles stay or earth plates or for laying cables, pipes & clearing the site by
removing debris & making the site good.
20.16 Supplying and erecting approved make 22KV out door type gang operated
air break triple pole switch 200 amperes capacity with 3post pin type
insulator per phase mounted in horizontal or vertical position with necessary
channels on provided cross arm with adequate length of 'C' class G.I pipe for
operating handle erected on extended square shaft. The operating handle
provided with lock and key at suitable height from ground level with
necessary clamp.
20.17 Supplying and erecting approved make thyrite type lightening arresters
suitable for 22KV supply with necessary ancillary materials complete erected
on provided cross arm and connected to the overhead line Distribution Class.
20.18 Supplying erecting approved make 22KV outdoor type drop out fuse with
insulator complete with fuse holder fuse barrel with metal fitting fuse element
mounted on MS channel with working current of 10A capacity complete
erected on provided cross arm
20.19 Supplying and laying (including excavation ) 15 cms. Dia full round RCC
hume pipe with coupling collar of standard thickness at required depth upto
90 cms. Below road /ground surface, for enclosing provided cable and
necessary back filling with light ramming to make the road / ground surface
as it was ( except bitumen carpet)
20.20 Providing & laying 75mm dia G.I pipe 'B' grade for enclosing cable below
ground / road surface complete.
The work should be carried out as per the instructions of the Engineer. And payment
will be made as mentioned in Schedule “A.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 241 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 ITEM NO. 21 & 22
20.21 TECHNICAL SPECIFICATIONS FOR 22KV/11KV XLPE CABLE
SCOPE
This technical specification covers design, manufacture, testing at
manufacturer’s works, packing & delivery of High Voltage Cross linked
polyethylene insulated PVC Sheathed cables round armoured suitable
for 11 KV and 22KV.
It is not the intent to specify completely herein all the details of design
& construction of the cables. However the cables shall conform to high
standards of engineering, design & workman ship. The equipment
offered shall be complete with all components necessary for its
effective and trouble free operation.
STANDARDS
Unless otherwise specified elsewhere in its specification, the rating,
performance and testing of cables & accessories shall conform to the
latest revision of all relevant standards.
A list of such standards is enclosed at ANNEXURE – I.
20.21.1 PRINCIPAL PARAMETERS
The high Voltage Cables and accessories covered in this specification
shall meet the technical requirements listed at ANNEXURE – II and the
following general technical requirement.
20.21.2 GENERAL TECHNICAL REQUIREMENT
Conductor
20.21.2.1 The conductor shall be made from electrically pure Aluminium wire.
The wires shall be stranded together and compacted.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 242 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 20.21.2.2 The conductor shall be circular in shape.
20.21.3 Conductor Shielding
An extruded semi conducting compound shall be provided on the
conductor to provide a smooth surface & eliminate electrical stress
concentration.
20.21.4 Insulation
The core insulation shall be with Cross linked polyethylene unfilled
insulation compound. It shall be free from voids and shall withstand all
mechanical and thermal stresses under steady state & transient
operating conditions. The insulation shall be applied by triple extrusion
process.
20.21.5 Insulation Shielding
The insulation shielding shall consist of non-metallic semi-conducting
compound in combination with non-metallic screening of copper. It
shall be possible to strip the insulation screening without applying
heat. The screen shall be capable to carry single line to ground fault
current for a duration of one second.
20.21.6 The conductor screen and XLPE insulation screen shall all be extruded
in one operation by extrusion to ensure perfect bonding.
20.21.7 Armouring
G.I. round steel wire armouring shall be provided over the inner
sheath.
20.21.8 Outer Sheath
An outer sheath shall be applied on the cable by extrusion over
armouring. The outer sheath shall be of PVC compound confirming to
Type ST2. The PVC compound shall be suitable for protection against
rodent and termite attack.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 243 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85 20.21.9 In addition to the above, binder tape, filler, core identification tape
shall be provided.
ANNEXURE-I
22KV/11KV XLPE CABLE APPLICABLE STANDARDS
The cables shall comply with the latest edition of the following standards:
Sr. No.
Indian Standard
Spec. No.
Title
1. IS 7098 (Part-II) Cross-linked Polyethylene insulated PVC
sheathed cables : Part II for working voltages
form 3.3KV upto and including 33KV.
2. IS:8130 Conductors for insulated electric cables and
flexible cords.
3. IS:5831 PVC insulation and sheath of electrical cables.
4. IS:3975 Mild steel wires, strips and tapes for
armouring of cables.
5. IS:2633 Methods of testing weight, thickness and
uniformity of coating on hot dipped
galvanized articles.
6. IS:209 Specification for Zinc
7. IS:1753 Aluminium conductors for insulated cables.
8. IEC:502 Extruded solid dielectric insulated power
cables for rated voltages form 11KV upto 30
KV.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 244 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
Sr. No.
Indian Standard
Spec. No.
Title
9. IEC:540 & 540A Test methods for insulation and sheaths of
electric cables and cords.
ANNEXURE-II
22KV/11KV XLPE CABLES
DESIRED TECHNICAL PARTICULARS
Sr. No.
Description Unit 11kV Particulars 22kV Particulars
1. Cable Size Core x Sq.mm.
Upto 3C x 300 & 1C x 1000
sq.mm.
31C x 300 sq.mm.
2. System Voltage kV 11 22
3. Type of cable XLPE Insulated XLPE Insulated
4. Conductor material Aluminium Aluminium
5. Minimum No. of
strands
No. 30 37
6. Nominal thickness of
XLPE insulation
mm 3.6 6.00 mm
7. Minimum thickness of
common covering
mm 0.7 0.7mm
8. Armouring - round mm 3.15 mm dia 4mm dia
9. Minimum thickness of
outer sheath
mm 2.84 3.00
10. Approximate overall
diameter
mm 81 87.5
11. Approximate net
weight
kg/km 10400 13850
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 245 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
Sr. No.
Description Unit 11kV Particulars 22kV Particulars
12. Normal Delivery
Length
m 250 250
13. Max. DC Resistance at
20 deg C
Ohms/km 0.1 As per IS 7098
Paer-II
14. Approximate AC
Resistance
Ohms/km 0.13 0.130
15. Approximate
reactance at 50 Hz.
Ohms/km 0.095 0.97
16. Approximate
Capacitance per
phase
Mfd/km 0.475 0.319
17. Current rating Amps 355 (in ground)
450 (in air
350 (in ground)
455 (in air
18. Short time current
rating
kA 28.2 28.3
19. Permissible short
circuit temperature
Deg.C 250 250
ITEM NO. 23
20.23 CABLE TRENCHES (EXCAVATED):
20.23.1 The cable trenches shall be excavated 1000 mm below the finished
ground level and shall have a minimum width of 300 mm. for laying
of single cable. When more than one cables are laid in the same
trench, the width of the trench shall be increased such that the spacing
between the cables is 25 cms. and the end cables are at minimum 15
cms. from the side of the trenches. At the turning of the cable route
the trench shall be dug with radius equal to 15 times the cable
diameter.
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 246 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
20.23.2 The trenches shall be cut square with vertical side walls and with
uniform depth. Suitable shoring and propping may be done to avoid
caving in of trench walls. The floor of the trench shall be rammed and
leveled. The bottom of the cable trench shall be prepared with
100mm. sand bed for laying the cables.
20.23.3 The cables shall be laid in trenches over the rollers. After the cable is
laid and straightened it shall be covered with sand, and RCC half
round/semi circular pipe of appropriate strength & size.
20.23.4 The cable trench then shall be refilled with excavated materials after
removing the stones and other sharp materials and the refilled
materials shall be compacted with light ramming.
20.23.5 Approved cable markers made of G.I. with 15 cms crown shall be
provided along the route of cables at a spacing of 40 – 50 meters and
also at both ends of road crossings or at the cable turning points. The
class, type and No. of cables shall be indicated on the markers.
20.23.6 Cable shall be laid in hume pipes at all road crossings and in GI pipes
at the wall entries.
ITEM NO. 24
20.24.0 Outdoor/Indoor end termination Kit : LT/HT Cables
Before providing end termination kit to the cable, the cable end of the
equivalent length of the moulds, shall be prepared by removing the
outer PVC insulation along with the steel armouring. The ferrule shall
then be inserted over the bare core of the cable, and shall be crimped
with hydraulic / mechanical type heavy duty crimping tool. The
crimping shall be done in such a manner that there shall be no air
gap. Then the crimped portion shall be wrapped first with the PVC
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 247 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
insulation tape and then with the insulation tape used for wrapping HT
conductor. The above method shall be carried out for all the cores
strictly using the epoxy spacer, for having sufficient gap in-between the
leads. The earth continuity lead shall be clamped to theends of the
cable. After covering the cable leads with the PVC moulds, the edges
shall be clipped after applying the adhesive on the inside face of the
epoxy compound shall not spill out. Now the duly stirred epoxy
compound shall be poured and fill till the compound rises through the
risers provided on the moulds.
After completing the above procedure, the joint shall be allowed to dry
out for at least 8 to 10 hours (for epoxy compound to get hardened)
depending upon the size of cable. Before connecting to supply, the dry
and hardened joint shall be tested for its insulation level with 1000 V/
5000 V Meggar.
ITEM NO. 25
20.25 Straight through joint Kit: L T/HT Cables
Before providing joint to the cable, the cable ends of the
equivalent length of the joint moulds, shall be prepared by removing
the outer PVC insulation along with the steel armouring. The ferrule
shall then be inserted over the bare core of the cable, and shall be
crimped with hydraulic I mechanical type heavy duty crimping tool.
The crimped portion shall be wrapped first with the PVC insulation
tape and then with the insulation tape used for wrapping HT
conductor. The above method shall be carried out for all the cores
strictly following the colour code. The leads of the both the cables now
shall be placed into the mould by using the epoxy spacer, for having
sufficient gap in-between the leads. The earth continuity lead shall be
CIDCO OF MAHARASHTRA LIMITED. Sl.Pg.No. 248 C.A.NO. CIDCO/EE(ELECT-S)/2010-2011/85
clamped to the both ends of the cable. After covering the cable leads
with the PVC moulds, the edges shall be clipped after applying the
adhesive on the inside face of the moulds. The pasting of moulds shall
be rigid and as far as possible leak proof, so that the epoxy compound
shall not spill out. Now the duly stirred epoxy compound shall be
poured and fill till the compound rises through the risers provided on
the moulds.
After completing the above procedure, the joint shall be allowed to
dry out for at least 8 to 10 hours (for epoxy compound to get
hardened) depending upon the size of cable. Before connecting to
supply, the dry and hardened joint shall be tested for its insulation
level with 1000 VI 5000 V Meggar.
The cable should be fixed or laid in such manner that there should
not be pressure on end of moulds or on jointing position of cables.
Signature of Tenderer
Date.:
Chief Engineer & General Manager(T)
Date :