feeder_protn - akhil

Upload: netygen1

Post on 02-Jun-2018

228 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 Feeder_Protn - Akhil

    1/57

    ee er ro ec on

    Akhil K G tkhil Kumar GuptaSr. Faculty Member PMI)

  • 8/11/2019 Feeder_Protn - Akhil

    2/57

    Introduction

    Fuse Coordination

    Relay Coordination

    Conclusion

  • 8/11/2019 Feeder_Protn - Akhil

    3/57

    Fuses & Its CoordinationFuses & Its Coordination

  • 8/11/2019 Feeder_Protn - Akhil

    4/57

    Feeder Protection

    ensuring the safety of personnel working with electricalsys ems an or preven ng amage ue o var oustypes of faults such as over currents, short circuits andover vo tage etc.

    A short circuit may melt a conductor, resulting in arcingand the possibility of fire ; the high electromechanicalforces associated with a short circuit also causemechanical stresses which can result in severe damage,a heav short circuit ma also cause an ex losion

    4

  • 8/11/2019 Feeder_Protn - Akhil

    5/57

    Feeder Protection

    Used in Lower End Systems

    IDMT O/C, Definite Time O/C, High Set O/C Relays used Extensivel used at Medium Volta e level and also at HV

    EHV Systems as Backup Protection

    Unit Protection (Pilot Wire Protection) Used for critical Medium Voltage Circuits like Long cable

    feeders, Tie feeders etc. Also some times used for HV /EHV

    applied

    Primarily Longitudinal Differential Protection Supplemented by Backup Protection, usually IDMT O/C type

    5

  • 8/11/2019 Feeder_Protn - Akhil

    6/57

    Protection Co-ordination

    protective devices is the prospective current

    Prospective current is the current which would flow ata particular point in an electrical system if a shortcircuit of negligible impedance were applied

    6

  • 8/11/2019 Feeder_Protn - Akhil

    7/57

    Protection Co-ordination

    protection system so that when fault occurs, minimumsec on o e sys em aroun e au s sconnec e

    Protective devices are described by a timecurrentcharacteristic and in order to achieve co ordination

    between protective devices, their timecurrentcharacteristics must be sufficiently separated so that afault downstream of both of rotective devicesoperates only the device nearest to the fault

    7

  • 8/11/2019 Feeder_Protn - Akhil

    8/57

    Protection Co-ordination

    8

  • 8/11/2019 Feeder_Protn - Akhil

    9/57

    Fuses

    use s e mos common an w e y useprotective device in electrical circuits

    Because element of fuse is of much smallercross sectional area than cable it protects(assuming of same material), element will

    reach its melting point before the cable Larger the current, quicker the element melts If deterioration of element occur it o erates

    even faster, hence fail safe

    9

  • 8/11/2019 Feeder_Protn - Akhil

    10/57

    Fuses

    sem -enc ose or rew rea e use

    10

    Cartr idge type

  • 8/11/2019 Feeder_Protn - Akhil

    11/57

    Cut Section of Fuse

    11

  • 8/11/2019 Feeder_Protn - Akhil

    12/57

    Fuses

    Silver element, specially shaped, enclosed in a barrel of insulating material, filled with quartz

    Advantages Correct rating and characteristic fuse always fitted to a

    Arc and fault energy contained within insulating tube prevents damage

    Normally sealed therefore not affected by atmosphere hence gives more stable characteristic reliable grading

    12

  • 8/11/2019 Feeder_Protn - Akhil

    13/57

    Design of Fuse Elements

    13

  • 8/11/2019 Feeder_Protn - Akhil

    14/57

    Fuses ,

    at the notches when an overcurrent flows and this results in a number of controlled arcs in series

    The voltage across each arc contributes to the total voltage across the fuse, and this total voltage results in the current fallin to zero and because the number of arcs is limited the fuselink voltage should not be high enough to cause damage

    elsewhere in

    the

    circuit

    14

  • 8/11/2019 Feeder_Protn - Akhil

    15/57

    Fuses

    in shorter times so short that current will be cut off before it reaches its eak value o eration < 5 ms

    Hence serious overheating and electromagnetic forcesin the system can be avoided

    Extremely high breaking

    capacity of up to 100KA,also known as HRC (highrupturing capacity) fuses

    15

  • 8/11/2019 Feeder_Protn - Akhil

    16/57

    Fuses

    Simple & Economical Ver Fast O eration

    Current Time Characteristic

    Limits fault energy Disadvanta es

    Require close coordination

    Poor sensitivity for earth faults Cause single phasing Inconvenient of replacement

    can be set to trip on as little as 5% over current while thefuse has a fusing factor of about 1.75)

    Fusing factor = minimum fusing current current rating16

  • 8/11/2019 Feeder_Protn - Akhil

    17/57

    Selection of Fuses

    17

  • 8/11/2019 Feeder_Protn - Akhil

    18/57

    Selection of Fuses

    Fuses can be used as either for overload and short circuit protection or for short circuit protection

    Fuse se ect on gu e ne or motor app cat on Fuse should not blow during running Fuse should not blow during starting

    12 x Ie for 10 msec & 6 x Ie for Motor Starting Time

    Coordination with Starter

    18

  • 8/11/2019 Feeder_Protn - Akhil

    19/57

    Selection of Fuses- Case Study

    Motor data M1 S. C. Induction motor

    50 HP, IRM = 70 A, ILR = 6 x IRM Starting method : D.O.L. Starting time = 15 sec

    19

  • 8/11/2019 Feeder_Protn - Akhil

    20/57

    Selection of Fuses

    20

  • 8/11/2019 Feeder_Protn - Akhil

    21/57

    Coordination with Starter

    Type 1 Coordination Requires that, under short circuit conditions, the contactor

    or s ar er s a cause no anger o persons or ns a a on an

    may not be suitable for further service without repair andreplacement of parts

    Type 2 Coordination

    or starter shall cause no danger to persons or installation andshall be suitable for further use. The risk of contact welding is

    z , w u umeasures to be taken as regards the maintenance of theequipment

    21

  • 8/11/2019 Feeder_Protn - Akhil

    22/57

    Type 2 Coordination

    22

  • 8/11/2019 Feeder_Protn - Akhil

    23/57

    Type 2 Coordination

    23

  • 8/11/2019 Feeder_Protn - Akhil

    24/57

    Rela sRela s

  • 8/11/2019 Feeder_Protn - Akhil

    25/57

    Definite Current Relay

    Relay operates instantaneously when the current reaches a

    predetermined value.

    t me

    Definite

    25

    current

  • 8/11/2019 Feeder_Protn - Akhil

    26/57

    Definite Time Relay

    Relay operates after a definite time delay when the current

    reaches a pre-determined value.

    time

    Definite

    currentDefinite

    26

    current

  • 8/11/2019 Feeder_Protn - Akhil

    27/57

    Over Current Relays

    Definite Time

    Normal Inverse

    IDMT

    T

    I

    27

  • 8/11/2019 Feeder_Protn - Akhil

    28/57

    IDMT O/C Relays

    . . . . RELAYS Current/time tripping characteristic

    equation of IDMT (Inverse Definite Minimum Time) Over Current relays

    28

  • 8/11/2019 Feeder_Protn - Akhil

    29/57

    IDMT O/C Relays

    applications

    there is substantial reduction in the fault current as thedistance from the power source increases

    Extremely Inverse Characteristic is particularly suitable

    in grading with fuses Long Inverse Characteristic is primarily used for

    overload protection or earth fault protection in

    resistance grounded system IDMT relays provide both time and current grading to achieve

    29

  • 8/11/2019 Feeder_Protn - Akhil

    30/57

    IDMT O/C Relays

    is usually represented on a lo arithmic scale and ives

    the operating

    time

    at

    different multiples of setting current, for the maximum Time Multiplier

    TMS is adjustable giving a

    characteristics

    30

  • 8/11/2019 Feeder_Protn - Akhil

    31/57

    IDMT O/C Relays

    5A, 2.2sec, IDMT and having a relay setting of 125%, TMS =0.6. It is connected to a supply circuit through a CT 400/5 ratio. The au curren s .

    Solution The pick up value of the relay is 5A but since the rela settin is 125% therefore the o eratin current of the relay is 5 X 1.25 = 6.25A

    The PSM

    (Plug

    Setting

    Multiplier)

    of

    the

    relay,

    PSM = 4000 / (6.25 x 80) = 8(PSM = Prim Current / Relay Current Setting X CT Ratio)

    . u v , = 3.2 secSince TMS is 0.6 actual o eratin time of the rela is 1.92s

    31

  • 8/11/2019 Feeder_Protn - Akhil

    32/57

    Relay Coordination Methods

    Methods used to achieve correct relay co ordination are

    Time grading

    Current grading

    Combination of Time and Current grading

    The common aim of these methods is to give correctdiscrimination so that each method isolate only the

    faulty section of the power system network, leavingthe rest of the system undisturbed

    32

  • 8/11/2019 Feeder_Protn - Akhil

    33/57

    Time Grading

    pera ng me o e pro ec on s ncrease rom e ar en o the protected feeder towards the generating source

    The time difference between two adjacent relay is usually

    approximately 0.5 s, this is provided to cover operating time of CBs & errors

    33

  • 8/11/2019 Feeder_Protn - Akhil

    34/57

    Time Grading

    When fault occur beyond B, all relays come into action as fault current flows through all of them, the least time setting is for re ay B, ence re ay B operates a ter . 5 s; B at B opens an clears the fault, with this, all other relays (C, D and E) reset

    If relay or CB at B fails to operate, fault remains un cleared, in this case, relay C will operate after 0.65 s and trip CB at C, if the CB at C also fails to operate, then relay D will operate after 1.05 s

    , high and it should be cleared very quickly, but time grading method takes longest time to open the CB near the source, i.e.

    e more severe au s e mos e aye

    34

  • 8/11/2019 Feeder_Protn - Akhil

    35/57

    Feeder Protection

    Relay R1 Current Setting =100% (100A Prim) = = = . , Operating Time @ PSM20 & TMS0.10 = 0.22 S (i.e.2.2 x 0.1)

    Relay R2 Current Setting = 100% (150A Prim) TMS selected = 0.25, PSM = 3000/ 150 = 20 Operating time @ PSM30 & TMS0.25 = 0.55S (i.e. 2.2 x 0.25)

    Grading Margin between Relay R1 / R2 = 0.55 0.22 = 0.33 S

    35

  • 8/11/2019 Feeder_Protn - Akhil

    36/57

    Current Grading

    It relies

    on

    the

    fact

    that

    the

    fault

    current

    varies

    with

    the

    position

    of the fault because of the difference in impedance values

    etween t e source an t e au t Relays are set to pick up at progressively higher values of

    current towards the source and rela s em lo ed are hi h set (high speed) instantaneous over current relays

    The operating time is kept same for all the relays protecting the

    i erent sections

    Advantage compared to time graded system is that the

    36

  • 8/11/2019 Feeder_Protn - Akhil

    37/57

    Current Grading

    at F2, since the distance between these points may be only a few meters, corresponding to a change in fault current of approx ma e y .

    The magnitude of fault current cannot be accurately determined as all the circuit arameters ma not be known sometimes

    During a fault, there is a transient condition and the

    performance of

    the

    relay

    is

    not

    accurate

    37

  • 8/11/2019 Feeder_Protn - Akhil

    38/57

    Feeder Protection

    Relay R1 Current Setting = 100% (100A Prim) = = = . , Operating time @ PSM30 & TMS0.10 = 0.22 S (i.e. 2.2 x 0.1)

    RELAY R2 Current Setting = 100% (750A Prim) TMS selected = 0.10, PSM = 3000/750 = 4 Operating time @ PSM4 & TMS0.10 = 0.50 S (i.e. 5 x 0.10)

    Grading margin

    between

    Relay

    R1

    / R2

    = 0.50

    0.22

    = 0.28

    S

    38

  • 8/11/2019 Feeder_Protn - Akhil

    39/57

    Discrimination by Time and Current

    , to the fact that the more severe faults are cleared in the longest operating time. On the other hand, discrimination by current can be applied only where there is appreciable impedance

    between the two circuit breakers concerned ,

    proportional to the fault current level and the actual

    characteristic is

    a function

    of

    both

    time

    and

    'current'

    settings

    39

  • 8/11/2019 Feeder_Protn - Akhil

    40/57

    Grading Margin in IDMT O/C Relays

    u Grading Margin (t)

    Rela timin Error + 7.5% for EM 5% for Numerical Version)

    Relay Over shoot (40 60 ms for EM, N.A. for Numerical

    C.B. Trip time (40 60 ms)

    Safety Margin Recommended Grading Margin: 0.3 0.4s for EM & 0.2 0.3s for Numerical Version

    40

  • 8/11/2019 Feeder_Protn - Akhil

    41/57

    NON-DIRECTIONAL IDMT O/C RELAY

    41

  • 8/11/2019 Feeder_Protn - Akhil

    42/57

    DIRECTIONAL IDMT O/C RELAY

    42

  • 8/11/2019 Feeder_Protn - Akhil

    43/57

    DIRECTIONAL IDMT O/C RELAY

    43

    DIRECTIONAL IDMT O/C RELAY

  • 8/11/2019 Feeder_Protn - Akhil

    44/57

    DIRECTIONAL IDMT O/C RELAY

    44

    DIRECTIONAL IDMT O/C RELAY

  • 8/11/2019 Feeder_Protn - Akhil

    45/57

    DIRECTIONAL IDMT O/C RELAY

    45

    DIRECTIONAL IDMT O/C RELAY

  • 8/11/2019 Feeder_Protn - Akhil

    46/57

    DIRECTIONAL IDMT O/C RELAY

    46

    DIRECTIONAL IDMT O/C RELAY

  • 8/11/2019 Feeder_Protn - Akhil

    47/57

    DIRECTIONAL IDMT O/C RELAY

    47

    DIRECTIONAL IDMT O/C RELAY

  • 8/11/2019 Feeder_Protn - Akhil

    48/57

    DIRECTIONAL IDMT O/C RELAY

    48

    DIRECTIONAL IDMT O/C RELAY

  • 8/11/2019 Feeder_Protn - Akhil

    49/57

    DIRECTIONAL IDMT O/C RELAY

    49

    Fuse Coordination

  • 8/11/2019 Feeder_Protn - Akhil

    50/57

    Fuse Coordination

    u u The operating time of a fuse is a function of both the

    ,

    which follows an I 2t law, so, to achieve proper co ordination between two fuses in series it is necessar to ensure that the total I 2t taken by the smaller fuse is

    less than

    the

    pre

    arcing

    I 2

    t value

    of

    the

    larger

    fuse

    It has been established by tests that satisfactory grading between the two fuses will generally be

    achieved if

    the

    current

    rating

    ratio

    between

    them

    is

    greater than two

    50

    Fuse Coordination

  • 8/11/2019 Feeder_Protn - Akhil

    51/57

    Fuse Coordination

    51

    Fuse Coordination

  • 8/11/2019 Feeder_Protn - Akhil

    52/57

    Fuse Coordination

    u y For grading inverse time relays with fuses, the basic

    backs up

    the

    fuse

    and

    not

    vice

    versa If the fuse is upstream of the relay, it is very difficult to

    maintain correct discrimination at high values of fault current because of the fast operation of the fuse

    e re ay c aracter st c est su te or coor nat on with fuses is normally the extremely inverse (EI)

    2

    52

    IDMT Relay Coordination

  • 8/11/2019 Feeder_Protn - Akhil

    53/57

    IDMT Relay Coordination

    53

    IDMT Relay Coordination

  • 8/11/2019 Feeder_Protn - Akhil

    54/57

    IDMT Relay Coordination

    Rate Current = 87.5 A 66KV 525 A 11KV S.C. Current for Fault on LV side (assuming infinite source)

    t

    = 525 x 100 / 10 = 5250 A (11 KV side) = 87.5 x 100 10 = 875A 66 KV side

    IDMT Relay with Normal Inverse Characteristic (IEC)

    Operating time (t) = (0.14 / ( I0.02

    1) ) x TMSwhere I = Plug Setting Multiplier (PSM) t @ PSM 10 / TMS 1.0 = 3.0s

    t @

    PSM

    20

    / TMS

    1.0

    = 2.2s

    t @ PSM 8.75 / TMS 1.0 = 3.16s

    54

    IDMT Relay Coordination

  • 8/11/2019 Feeder_Protn - Akhil

    55/57

    IDMT Relay Coordination

    O/C Setting= 1A (200A), TMS = 0.10, PSM=10500/200 >20

    > =

    11KV B/C

    (R2) O/C Setting = 1A (600A), PSM= 5250/600 = 8.75

    Desired Operating Time (DOT)= 0.22 + 0.30 = 0.52sOperating time @PSM 8.75 / TMS 1.0 = 3.16sTMS to achieve DOT of 0.52S = 0.52/3.16 = 0.16

    11KV I/C (R3) e ng = , = = .

    DOT = 0.52 + 0.30 = 0.82s . . .

    TMS to achieve DOT of 0.82S = 0.82/3.16 = 0.2655

    IDMT Relay Coordination

  • 8/11/2019 Feeder_Protn - Akhil

    56/57

    e ay Coo d at o

    O/C Setting = 1A (100A), PSM = 875 / 100 = 8.75

    = + =

    Operating time

    @

    PSM

    8.75

    / TMS

    1.0

    = 3.16s

    TMS to achieve DOT of 1.12S = 1.12 / 3.16 = 0.35Note:

    Grading between Relay R3 & R4 is optional since it does not a ect own stream coor ination, i oregone, i entica TMS can be adopted for Relay R4 (TMS 0.26) with similar response time of 0.82s as relay R3, this would reduce the up stream fault

    clearance time Grading margin of 0.3s is used considering EM IDMT relays,

    w umer ca re ays, gra ng marg n can e re uce o . s, in view of reduced timing errors and no over shoot

    56

  • 8/11/2019 Feeder_Protn - Akhil

    57/57