power is our business we keep you ahead BITORON-12 MV indoor switchgears rated upto 2500A-31.5kA - 12kV Adaptaon of New Standard IEC 62271-200 for Bitoron 12 Metalclad, arc resistant switchgears

Upload: ngobao

Post on 12-May-2018

299 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

p o w e r i s o u r b u s i n e s s w e k e e p y o u a h e a d

BITORON-12MV indoor switchgearsrated upto 2500A-31.5kA - 12kV

Adaptation of New StandardIEC 62271-200 for Bitoron 12Metalclad, arc resistant switchgears

Page 2: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

J SF6 / Vacuum Circuit breaker a compact modular circuit breaker & tested solution for both withdrawable & fixed installation 3.3 kV to 12 kV 630A to 2500A, 20-31.5 kA with metallic protection shutter on cradle racking in/out operation possible with the cubicle door closed

conformity standards IEC 62271-1 : common specifications for high voltage switchgear and controlgear standardsIEC 62271-100 : high voltage AC circuit breakerIEC 62271-200 : AC metal enclosed switchgearIEC 60529 : degree of protection

operating safetyas for switch-units, accidental over-pressures are eliminated by opening of thesafety membrane.

internal arc withstand of the cubiclesAll bitoron-12 switchboards comply with the five criteria relative to internal arc classification (IAC)as defined in IEC recommendation 62271-200. To ensure complete safety of people, any internaloverpressure is directed upward the cubicles, towards the arc chamber.

ISO 9001 : 2008 Certified

The load break switch is filled with SF6 gas, having exceptional isolating properties and arc extinguishing particularities. Optimal security is ensured by means of a " sealed for life " concept and seal tightness is always checked in the factory. The choice of an ideal operational speed allows a short arcing time.All non-ferrous components of the switch are free of halogen, resistant to the ultra violet and ozone, reinforced with fiberglass and manufactured according to the class UL 94 V0.By using a fuse combination, the load break switch will be completed with the fuse holders and a second earthing switch. Both earthing switches are mechanically linked and so they are opening and closing at the same time.When a fuse is blowing, switch off mechanism through a hitting bolt opens the three phases of the load break switch simultaneously.

bitoron 12the evaluative, arc resistant switchgear

Safety at works:J switch- disconnector and earthing switch

bitoron 12 02

Page 3: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

bitoron-12 is an indoor metal-enclosed switchgear designedin conformity with IEC recommendations for the protectionof life and property as well as easy of installation, operationand protecting the environment bitoron-12 meet all thefollowing recommendations and specifications:J IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100

Adaptations for compliance with national standards andcorporate specifications are available as well. The switchingdevices are of the metalclad. Bitoron-12's design takes into account three categories of user's requirements:J reliability necessary for continuity of power supplyJ simple installation, operation and maintenance,J safety of operating personnel

The bitoron-12 range is made up of modular units containing fixed and/or withdrawable metal-enclosed SF6 and/or vacuum switchgears :

J SF6 fused switch disconnectorJ SF6 circuit breakersJ Vacuum circuit breakersJ Contactor J Disconnector.bitoron 12 units are used for the medium voltage section inMV/LV transformer substations in public distribution systemsand medium voltage consumer or distribution substationsupto 12 kV.

bitoron 12MV switchgear assemblies630-2500A, 16-25kA 3.3 to 12 kV system

Compartmented Switchgear to IEC 62271-200A = Switching Compartment B = Busbar CompartmentC = Cable Connection CompartmentD = LV CompartmentE = Arc Chamber (with pressure relief flap)

General technical databitoron-12rated voltage kV 7.2 12

rated power-frequencywithstand voltage, 1mn kV 20 28

rated lightning impulsewithstand voltage kV 60 75

frequency Hz 50/60

rated current of busbars A 800-1250-2500

rated current of the - switch-fuse unit A 800-1250

- SF6 circuit breaker A 630-1250-2500

- vacuum circuit breaker A 630-1250-2500

short time withstand current of the :- switch fuse unit kA 25 25

- SF6 circuit breaker kA 20-25

- vacuum circuit breaker kA 20-31.5

rated short-circuit breaking current of the:- SF6 circuit breaker kA 20/25

- vacuum circuit breaker kA 25/31.5

auxiliary voltage V DC 24/48/110/220

AC 110/220

ISO 9001 : 2008 Certified

Classification for bitoron-12Service Continuity LSC2BPartitioning PMAccessibility Code AFLRInternal Arc 31.5 kA x 1s

J Loss of Service Continuity : LSC2BThe main busbar and circuit-breaker/cable compartments are physically and electrically segregated. This is the category for equipment that enables access to the circuit-breaker/cables compartment with the main busbars energized.

J Partition Metallic: PMThis covers switchgears with continuous metallic partitions intended to be earthed, between opened accessible compartments and live parts of the main circuit. Metallic partitions or metallic parts of them shall be connected to the earthing point of the switchgear.

J Accessibility Code: AFLRA: Accessibility type A restricted to authorized personnel only. Distance of indicators are 300 from the panel.

FLR: access from the front (F), from the sides (L) and from the rear (R).

J Internal Arc: 31.5 kA x 1s

I (Test Current)=31.5 kAt (Internal arc duration)=1sIn accordance to IEC 62271-200, internal arc classification IAC A FLR 31.5kA x 1s, our bitoron -12 switchgear offers maximum possible personal protection.

bitoron 12 03

D

B

E

A

C

Page 4: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

3

ISO 9001 : 2008 Certified

Switchgear selections : bitoron 12W

Protection cubicle withdrawout vacuum circuit breaker

Application : Protection of feeders, transformers and MV- equipment

Standard equipment - withdrawable circuit breaker interlocking between circuit breaker & cradle position makes operation safer; - current transformers - 4 racked in/out position contacts

Options - voltage detector - key interlock on load break switch - key interlock on earthing switch - no door interlock - floor plans - short circuit indicator - sets of VT and double core CT - metering (A, V, F, kwh, kVARh etc.) - shunt trip - close coil

Operating voltages : 24-48-110V AC/DC & 220V ACPlease consult us for other options and dimensions.

- cable supporting- door interlock- low voltage compartment- trip coil- block of 4 O/C contacts

- block auxiliary contacts on load break switch- block aux contacts on earthing switch- motor operation : 24-48-110 V AC/DC- press button control- distance control- switching counter- automatic recloser- under voltage release

Common characteristics according to IEC 60 056short-time withstand current IK for tk=3s (kA) rms Ik=Iscrated peak withstand current Ip peak(kA) Ip= 2.5 & 2.6 Ikrated short circuit making current peak(kA) = 2.5 & 2.6 Iscoperating times opening ms < 50 breaking ms < 60 closing ms < 65mechanical endurance class M2 no. of operations with maintenance 25000electrical endurance class E2 no. of operations 25kA 100capacitive current braking C1 class

Specifications to be indicated forcircuit breaker : - short circuit capacity - rated current - rated voltage - capacity to be secured

Technical data :

rated voltage kV 7.2 12

rated current A 630-1250-2500 630-1250-2500

short time current (maximum) kA 25 25

short time current duration sec 1 1

operating sequence 0-3mn - CO - 3mn - CO

0-0.3s - CO - 3mn - CO

0-0.3s - CO -15s - CO

cubicle dimensions:

width mm 850 850

depth mm 1200/1500 1200/1500

height mm 2000 2000

height (with arc chamber) mm 2300 2300

bitoron 12 04

Page 5: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

Switchgear selections:bitoron 12V

Application : Protection of feeders, transformers and MV- equipment

Standard equipment - three phase load break switch according to IEC 62271-103 SF6 - insulation interlocked earthing switch- vacuum circuit breaker with integrated protection relay, current transformers & open release

Options

Protection cubicle with SF6Isolator & vacuum circuit breaker

3

ISO 9001 : 2008 Certified

- voltage detector- key interlock on load break switch- key interlock on earthing switch- no door interlock- floor plans- short circuit indicator- sets of VT and double core CT- metering- shunt trip- close release

- block auxiliary contacts on load break switch- block auxiliary contacts on earthing switch- motor operation : 24-48-110V AC/DC- press button control- distance control- switching counter- automatic recloser- under voltage release

operating voltages : 24-48-110V AC/DC & 220V ACPlease consult us for other options and dimensions.

- cable supporting- door interlock- low voltage compartment

Technical data :rated voltage kV 7.2 12

rated current A 630-1250 630-1250

short time current (maximum) kA 25 25

short time current duration sec 1 1

operating sequence 0-3mn - CO - 3mn - CO

0-0.3s - CO - 3mn - CO

0-0.3s - CO -15s - CO

cubicle dimensions:

width mm 850 850

depth mm 1200/1500 1200/1500

height mm 2000 2000

height (with arc chamber) mm 2300 2300

Common characteristics according to IEC 60 056short-time withstand current IK for tk=3s (kA) rms Ik=Iscrated peak withstand current Ip peak(kA) Ip= 2.5 & 2.6 Ikrated short circuit making current peak(kA) = 2.5 & 2.6 Iscoperating times opening ms < 50 breaking ms < 60 closing ms < 65mechanical endurance class M2 no. of operations with maintenance 25000electrical endurance class E2 no. of operations 25kA 100capacitive current braking C1 classSpecifications to be indicated forcircuit breaker : - short circuit capacity - rated current - rated voltage - capacity to be secured

bitoron 12 05

Page 6: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

Application : Transformer protection and MV- equipment protection

Standard equipment - three phase fused load break switch - 3pole fuse trip according to IEC 62271-105 - door interlock - earthing switch with interlock - low voltage compartment - socle for DIN HRC fuses - switch off mechanism through - cable supporting hitting bolt

Options - capacitive voltage detector - block auxiliary contacts on load - key interlock on load break switch break switch - key interlock on earthing switch - block auxiliary contacts on earthing switch - floor plans - motor operation : 24-48-110 V AC/DC - short circuit indicator - press button control - DIN HRC fuses and/or spare fuses - distance control - metering - sets of VT and/or CT - shunt trip - close release

operating voltages : 24-48-110 V AC/DC & 220V AC Please consult us for other options and dimensions.

Transformer protection cubiclewith SF6 insulated fused load break switch andinterlocked earth switch

Switchgear selections : bitoron 12SF

Technical data :

rated voltage kV 7.2 12

rated current A 800-1250 800-1250

short time current kA 25 25

short time current duration sec 1 1

cubicle dimensions:

width mm 750 750

depth mm 1050/1475 1050/1475

height mm 2000 2000

height (with arc chamber) mm 2300 2300

Fuse selection table kVA/kV 5 6 10 11 12 100 25A 20A 16A 10A 10A 125 31.5A 25A 16A 16A 16A 160 40A 31.5A 20A 16A 16A 200 50A 40A 25A 20A 20A 250 63A 50A 31.5A 25A 25A 315 75A 63A 40A 31.5A 31.5A 400 100A 75A 50A 40A 40A 500 100A 100A 63A 50A 50A 630 75A 63A 63A 800 100A 75A 75A 1000 100A 100A 100A

ISO 9001 : 2008 Certified

bitoron 12 06

Page 7: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

Switchgear selections : bitoron 12AF

Application : Transformer protection and MV- equipment protection

Standard equipment - three phase fused load break switch - 3 pole fuse trip according to IEC 62271-105 - door interlock - interlock earthing switch - low voltage compartment - socle for DIN HRC fuses - switch off mechanism through - cable supporting hitting bolt

Options - capacitive voltage detector - block auxiliary contacts on load - key interlock on load break switch break switch - key interlock on earthing switch - block auxiliary contacts on earthing switch - floor plans - sets of VT and/or CT - short circuit indicator - DIN HRC fuses and/or spare fuses - metering

operating voltages : 24-48-110 V AC/DC & 220V AC Please consult us for other options and dimensions.

Transformer protection cubiclewith Air insulated type fused load breakswitch and interlocked earth switch

Fuse selection table kVA/kV 5 6 10 11 12 100 25A 20A 16A 10A 10A 125 31.5A 25A 16A 16A 16A 160 40A 31.5A 20A 16A 16A 200 50A 40A 25A 20A 20A 250 63A 50A 31.5A 25A 25A 315 75A 63A 40A 31.5A 31.5A 400 100A 75A 50A 40A 40A 500 100A 100A 63A 50A 50A 630 75A 63A 63A 800 100A 75A 75A 1000 100A 100A 100A

Technical data :

rated voltage kV 7.2 12

rated current A 800-1250 800-1250

short time current kA 25 25

short time current duration sec 1 1

cubicle dimensions:

width mm 850 850

depth mm 1200/1500 1200/1500

height mm 2000 2000

height (with arc chamber) mm 2300 2300

ISO 9001 : 2008 Certified

bitoron 12 07

Page 8: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

Switchgear selections : bitoron 12A

Application : Incoming cable connection, isolation etc

Standard equipment - three phase load break switch - cable supporting according to IEC 62271-103, SF6 - insulation - door interlock - interlocked earthing switch with - low voltage compartment making capacity upto 63kA

Options - capacitive voltage detector - block auxiliary contacts on load - key interlock on load break switch break switch - key interlock on earthing switch - block auxiliary contacts on earthing switch - no door interlock - press button control - floor plans - distance control - short circuit indicator

Please consult us for other options and dimensions.

Incoming cubiclewith load break switch andinterlocked earth switch

Technical data :rated voltage kV 7.2 12

rated current A 800-1250 800-1250

short time current kA 25 25

short time current duration sec 1 1

cubicle dimensions :

width mm 850 850

depth mm 1200/1500 1200/1500

height mm 2000 2000

height (with arc chamber) mm 2300 2300

ISO 9001 : 2008 Certified

bitoron 12 08

Page 9: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

CompactIndoor Current Transformers

Design

The primary is wound with pure heavy copper, to provide a maximum mechanical strength against short circuit currents.

The secondary is evenly distributed on a very low losses core for best accuracy.

The transformer is hot cast in an insulating resin under vacuum, to achieve a very compact unit. The base plate is supplied as a standard. A secondary cover is available upon request.

Advantages

The casting process and the resin employed allows reduced outlines and excellent dielectric strength. The reduced dimensions of these transformers are typically well adapted for their mounting in metal enclosed and metalclad cubicles.

They can be fixed in any position and require no maintenance.

Function

These current measuring units provide two functions:

- they insulate the high voltage power network from the low voltage metering circuit.

- they supply a low voltage alternative signal proportional to the network current, and intented to supply meters, protection relays, measuring instruments, etc...

Standards and tests

the transformers are manufactured according to the required standard: IEC 60044-1 They can also be designed according to any customers specification. All the routine tests required by the relevant standard are performed on each unit. The results are noted in the report referred to the order.

The type tests have been passed when qualifying each type of transformer, the reports are available upon request.

ConnectionThe secondary terminals supply a L.V. current to the measuring circuits.They must never be open- circuited.For each secondary winding, one terminal (one only) is to be grounded.The primary terminals are connected to the busbars, and properly tightened.A slot is provided near each M12 primary holes on to offer an anti- rotating option if necessary to the equipment connected.

Rated tightening torques:Primary terminal (M12) : 35N.mCoupling primary (M8) : 12.4N.mSecondary terminal (M6) : 3N.m

Typical ratingsInsulation : 7.2 kV to 12 kVFrequency : 50Hz or 60HzShort time current : max 500In upto 600A max 800In upto 1250A Permanent over current factor : 1.0 (over upon request)Primary current : SW447 & SW4412 upto 600A SW457 & SW4512 upto 1250A SW477& SW4712 upto 3000A Secondary current : 5A or 1ANumber of cores : SW447 and SW45 : 1 or 2 SW47 : 1 to 3 (upon request)Accuracy metering : CI 0.2 to CI 3 relaying : CI 5P to CI 10P20 (IEC)special uses : CI X to B.S. standard

ISO 9001 : 2008 Certified

bitoron 12 09

Page 10: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

Current transformers typical ratings upto 600A

CT-MODEL SW447-1 SW4412-1 SW447-2 SW4412-2Common characteristics:IEC standard : 60044-1 50 HzNo partial dischargeaccording to standardInsulating class kV 7.2 12 7.2 12Cores number 1 1 2 2Rated primary A from 10 from 10 upto 600A upto 600Acurrent Ipn or 2X300A or 2X300ARated secondary A 5 or 1A 5/5 or 1/1Acurrent IsnThermal current lth 100 Ipn 100 IpnShort time current ..XIn upto 500In upto 500InPrecision classescore of measure cl 0.2 0.5 1 0.2 0.5 1Rating VA 10 20 40 10 20 40Precision classescore of protection cl 5P10/5P20/10P10 5P10/5P20/10P10Rating VA 10 15 10 15

185

92.5M12

P1H1

P2H2

COVER(OPTIONAL)0

250-2

285

67

98.5122

φ 12 195 12.5

125100125148

120 37.5

220

RATED TIGHTENING TORQUE (W5%)

Primary terminals (M12) : 35N.mcoupling primary (M8) : 12.4N.mSecondary terminals (M6) : 3N.m

SECONDARY TERMINALS

27

NAME PLATE

15

148

20.5

120M8 M12

40

1534

HIGHRATIO

LOWRATIO

PRIMARY TERMINALSDOUBLERATION

X11S1

X21S2

Y12S1

Y22S2

ANSI - CSAIEC

SCREW M6-12

X1S1

X2S2

ISO 9001 : 2008 Certified

bitoron 12 10

Page 11: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

Current transformers typical ratings upto 1250A

HIGH RATIOLOW RATIO

X1S1

X2S2

X3S3

X1S1

X2S2

X3S3

X4S4

Ck

Ck

X1S1

X2S2

Ck

X11S1

X21S2

y12S1

y22S2

Ck

ANSI - CSAIEC

M6-12

Secondary Terminals

ArresterWhen

CapacitorDivider

x11S1

x21S2

y12S1

y22S2

z13S1

z23S2

x11S1

x21S2

x31S3

y12S1

y12S1

y22S2

x1S1

x2S2

x3S3

x4S4

x11S1

x21S2

y22S2

y32S3

ANSI - CSAIEC

120

M8

M12

40

153232

40

120 M12

UP TO 300/600A UP TO 1250A

120 37.5

12.5195φ 12

120

UP TO 600A

125

148

220

122

67

209

104.5M12

98.5

0120

- 2

120Cover

(Optional)

P1H1

P2H2

27

NAME PLATE15

178

20.5

CT-MODEL SW457-1 SW4512-1 SW457-2 SW4512-2Common characteristics:IEC standard : 60044-1 50 HzNo partial dischargeaccording to standardInsulating class kV 7.2 12 7.2 12Cores number 1 1 2 2Rated primary current Ipn A upto 1250A upto 1250ARated secondary A 5 or 1A 5/5 or 1/1Acurrent IsnThermal current lth 100 Ipn 100 IpnShort time current ..XIn upto 800In upto 800InPrecision classescore of measure cl 0.2 0.5 1 0.2 0.5 1Rating VA 10 20 40 10 20 40Precision classescore of protection cl 5P10/5P20/10P10 5P10/5P20/10P10Rating VA 10 15 10 15

ISO 9001 : 2008 Certified

bitoron 12 11

Page 12: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

ISO 9001 : 2008 Certified

Indoor Voltage transformersdry cast resin insulatedup to 12 kV

Connection

The secondary terminals supply L.V. to the measuring circuits. They must never be short- circuited.

For each secondary winding, one terminal (one only) is to be grounded.

The core is connected to the base and so grounded

Line to ground:

The H.V. primary terminal is connected to the bus bar directly or by mean of a high voltage fuse.

Design

The primary and secondary windings are mounted on a very low losses core, hot cast in an insulating resin. The mounting base is supplied as a standard and is not to be dismounted.

Advantages

The casting process and the resin employed allows reduced outlines and excellent dielectric strength. The reduced dimensions of these transformers are typically well adapted for their mounting in metal enclosed and metalclad cubicles. They can be fixed in any position. These units compact and rugged, require no maintenance.

Function

These voltage measuring units provide two functions:

- they insulate the high voltage power network from the low voltage metering circuit.

-they supply a low voltage alternative signal proportional to the network voltage, and intented to supply meters, protection relays, measuring instruments, etc...

Standards and Tests

The transformers are manufactured according to the required standard : IEC 60044-2

They can also be designed according to any customers specification. All the routine tests required by the relevant standard are performed on each unit. the results are noted in the report referred to the order. The type tests have been passed when qualifying each type of transformer, the reports are available on request.

The L.V. primary terminal, located near the secondary terminals, must be grounded. The residual voltage winding is to be connected in open delta, closed by a resistor (typical value 100 ohms, 320W). One end of the delta must be grounded.

Line to line:

The two H.V. terminals are connected to the busbars directly or by mean of high voltage fuses.

Note:

The purpose of the H.V. fuses is to isolate the busbars from the transformer if any incident occurs on it, and not to protect the transformer in case of an overload.

Rated tightening torques :

Primary terminal (M10) : 15Nm

Secondary terminal (M5) : 2Nm

Secondary terminal (M6) : 3Nm

Ground terminal (M8) : 8Nm

a

H.V.

FUSE

IECA

IECA

a

H.V.

FUSE

IEC IECdadn residuala1 voltagea2n

A

Bdampingresistor

connectionresidual voltage windings

Typical ratings

Insulation 7.2kV to 12kV

Frequency 50Hz or 60 Hz

connection phase to ground phase to phase

Primary voltage 6600/A3 V 6600 V

to 11000/A3 V to 11000 V

Secondary voltage 100/A3 V 100V, 110V

110/A3 V 220V

Accuracy metering : 15 VA CI 0.2 to 300 VA CI 1

relaying : 15 VA CI 3P to 100 VACI 5P

Voltage factor for line to ground units:

1.5 x Un-30 sec for grounded neutral

1.9 x Un-30 sec for impedant neutral

1.9 x Un-8h for isolated neutral

(residual voltage winding 100/3 on request)

Voltage factor for line to line and line to ground units:

1.2 x Un -continuous

bitoron 12 12

Page 13: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

Rated voltage factor : All units : 1.2 Un continuous Phase to ground units : 1.9 Un-30sec (8th upon request)

Phase to ground VT : Residual Voltage winding 100/3 or 110/3 2A-8h upon request *60% ** 80% of burden with residual voltage winding 2A-8h

Secondary voltage : 100, 110, 100/A3, 110/A3 V Other value upon request

Voltage transformersTypical ratings of each unitIEC 60044-2 50 or 60 HzCompact range

Insul. BIL kV Max. Prim. Type Available Burdens (VA) Thermal

kV Voltage 1 Secondary 2 Secondaries Burden

V CL0.2 CL0.5 CL1.0 CL0.5 + CL0.5 CL1 + CL1 (VA)

7.2 60 6600 V7P 15 50 100 15 15 30 30 250

12 75 11000/V3 Y12P 10 50 100 15 15 40 40 250

Y12G 30 100 200 40 40 80 80 400

11000 V12G 30 100 200 50 50 100 100 600

50 50

148125105

235

2804 HOLESDIAN11

13

145

110

2

SADTEM

Name Plate

H.V TERM. M10-20 + SCREW

200

40

162

142

113

20

M8

SealableScrew

Dia 16 forCable

AI

BI

Secondary Terminals M5

a

1a 1b 2a 2b

b

ISO 9001 : 2008 Certified

bitoron 12 13

Page 14: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

Protection, control and monitoring

FunctionsProtection ANSI codePhase overcurrent 50/51Earth fault, sensitive earth fault 50N/51NBreaker failure 50BFNegative sequence/ unbalance 46Directional phase overcurrent 67Directional earth fault 67N/67NCActive overpower 32PThermal overload 49RMSPhase undercurrent 37Locked rotor, excessive starting time 48/51LRStarts per hour 66Ruminant undervoltage 27RPhase-to-phase undervoltage 27Phase-to-neutral undervoltage 27SPhase-to-phase overvoltage 59Neutral voltage displacement 59NNegative sequence overvoltage 47Recloser (4 cycles) 79Thermostat / BuchholzTemperature monitoring 38/49T

Network and machine diagnosisTripping current l1, l2, l3, loTripping contextUnbalance ratio / negative sequence current liPhase angle jo, j1, j2, j3Disturbance recordingThermal capacity usedWaiting time after overload trippingRunning hours counter / operating timeStarting current and timestart inhibit time delay, number of starts before inhibition

Switchgear diagnosisCumulative breaking currentTrip circuit supervisionNumber of operations, operating time, charging timeCT/VT supervisionControl and monitoringCircuit breaker / contactor control (2)Logic discrimination

Additional modules8 temperature sensor outputs - MET 148 module1 low level analog output - MSA141 moduleLogic inputs and outputs - MES108 module (4-wire) moduleRS485 interface - ACE949-2 (2-wire) or ACE959 (4 wire) module.

Phase overcurrent ANSI code : 50/51phase overcurrent protection isthree-pole. It picks-up when one, two orthree of the currents reaches the set point. It is time delayed.

Earth fault ANSI code : 50N/51NIt picks-up when earth fault current reaches the set point.It is time delayed.The time delay may be definite (definite, DT) or IDMT (standard inverse, SITvery inverse VIT, extremely inverse EIT, ultrainverse UTT, RI).the protection comprises two units ;-IDMT or definite time low set unit,-Instantaneous or time-delayed, definite time high set unit

IDMT protectionIDMT protection operates in according withIEC 60255-3 and BS 142 standards

Definite time protectionIs in the set point expressed Iso is the set point expressedin A and to> is the protection In A and to> is the protectiontime delay time delay

All other protections , metering & controls like differential transformer protections (87), distance (21) relay,temperatures alarm & trip, DC failure etc are available on request

t

to

1 1.2 10 20 I/Iso

IDMT protection principle

v

t

to

1 1.2 10 20 I/Iso

IDMT protection principle

v

t

t

Is I

v

t

to

Iso Io

v

Definite time protection principle Definite time protection principle

A complete range of digital & microprocessor based protection and monitoring units are designed for the operation of machines and electrical distribution networks of industrial installations and utility substations for all levels of voltage. It consists of a complete range but with simple and reliable solutions, suited to the following applications:M Protection of substations (incomers and feeders)M Protection of transformersM Protection of motorsM Protection of busbars.

ISO 9001 : 2008 Certified

bitoron 12 14

Page 15: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

ISO 9001 : 2008 Certified

CIRWATT is a family of mult i-function energy meters capable of satisfying the most demanding requirements of energy measurement systems. Other features to highlight are quality, accuracy, security and reliability.

Including new technology in i ts measuring circuitry has al lowed CIRCUTOR to develop highly responsive new equipment and to include additional functions for the control and management of measuring.

The CIRWATT family offers a complete range of electrical energy meters adapted to its type of applications.

High accuracy, 4 quadrant measurement and advanced programming plus flexible communications for the most demanding of requirements. The best solution for large consumers: generation, substations and heavy industry.

A balance between cost and benefits without compromising maximum quality. Ideal, both for industry and commercial buildings.

Latest generation domestic use energy meters. The last word in measurement, high performance and ease of reading. Anti-fraud protection included.

TYPES

CIRWATT D CIRWATT C CIRWATT A/B

The meter can be read remotely and several readings from different meters may be performed at the same time. This allows different CIRWATT energy meters to be connected via RS-485 and data to be received via a PC or from a central data system. Data may also be received via a Modem using an RS-485 converter to Ethernet TCP/IP, etc.

APPLICATIONSRemote reading

Multifunction Energy metersfor billing

APPLICATIONHeavy Industry

SubstationsLight industry

Commercial buildings Domestic use

CIRWATT D

H.V. and M.V. L.V.

CIRWATT C

CIRWATT A/ B

Medium sizedindustry

bitoron 12 15

Page 16: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

ISO 9001 : 2008 Certified

CIRWATT D

CIRWATT C

CIRWATT A/B

Medium sized industry Domestic use CIRWATT C CIRWATT A/B 410-T5-C ( /5, /1 A) 410-D1-C (Direct) 210-A (Direct) 210-B (Direct)Type 410-UTxA-xxC 410-UD1A-xxC 410-UTxA-xxC 410-UD1A-xxC 210-A 210-BQuadrants 2 2 2 2Active energy accuracy 1 1 1 1Reactive energy accuracy 2 2 - - Multi-range Multi-rangeRated voltages 3x57.7/100 V up to 3 x 57.7/100 V up to 127 V or 127 V or 3x230/400 V A.C. 3 x 230/400 V A.C. 230 V A.C. 230 V A.C.In (I b) 5 A 10 A 10 A 10 AImax 10 A 100 A 60 / 120 A 60 / 120 AContracts 2 2 1 1Tariffs 9 9 2 4Profiles 10 10 4 4Regulated market Yes Yes Yes YesFree market Yes Yes Yes YesConsumers Type 4 Type 4 Type 5 Type 5Optical port Yes Yes Yes YesPort 1 RS-232 or RS-485 RS-232 or RS-485 - RS-232Port 2 No No - -Hourly load curve 213 days 213 days - -2nd programmable curve Optional Optional - 365 days (30 min)Nr. of bill summaries 64 64 - 16Nr. of events 512 512 64 64

Heavy industry - CIRWATT D 402-D ( /5/1 A) 405-D ( /5/1 A) 410-T5-D ( /5, /1 A)

405-MTxA-xxD 410-MTxA-xxDType 402-MTxA-xxD 405-NTxA-xxD 410-NTxA-xxD 405-QTxA-xxD 410-QTxA-xxD

Quadrants 4 4 4

Active energy accuracy 0.2S 0,5S 1

Reactive energy accuracy 0.5 1 2

M 3 x 63.5/110 V A.C. M 3 x 63,5/110 V A.C.Rated voltages M 3 x 63.5/110 V A.C. N 3 x 127/220 V A.C. N 3 x 127/220 V A.C. Q 3 x 230/400 V A.C. Q 3 x 230/400 V A.C.

In (I b) /5 A /1 A /5 A /1 A /5 A /1 A

Imax 10 A (2 A) 10 A (2 A) 10 A (2 A) Contracts

3 3 3

Tariffs 9 9 9

Profiles 10 10 10

Regulated market Yes Yes Yes

Free market Yes Yes Yes

Consumers Type 1, 2, 3, 4 Type 2, 3, 4 Type 3, 4

Optical port Yes Yes Yes

Port 1 RS-232 RS-232 RS-232

Port 2 RS-232 or RS-485 RS-232 or RS-485 RS-232 or RS-485

Hourly load curve 213 days 213 days 213 days

2nd programmable curve 5 120 records 5 120 records 5 120 records

Nr. of bill summaries 64 64 64

Nr. of events 512 512 512

MultifunctionEnergy metersfor billing

Technical features

bitoron 12 16

Page 17: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

Power is our business we keep you ahead

Complete solution for:- > HVAC control > lighting control > parking management > high level integration (HLI)

Building Management system (BMS)for:- > commercial building > hotel > hospital > shopping mall > educational Institute

Home automation:- > anti theft control > automatic gate control > access control > temperature control > lighting control

A complete system solution for Metering & Measurement:-1. The meter can be read remotely & data can be received via a pc or from a central data system.2. Prepayment solution using a recharging card.3. Readings of different types of consumption at the same time (electricity, water & gas).4. Power control with programmable CUTOFF RELAY & Communications with PLC is possible in Multifunction electronic energy meters.

Protection, automation, metering & measurement-PAMMis responsible for e3 (electrical energy e�ciency)

COMMITMENT

REVIEW

IMPL

EMENT

SOLU

TIONS

Low Energy LampsCombined Heat

and Power

Supp

ly V

oltag

eO

ptim

isatio

n

high Efficiency

Motors

Variable speed

Drives

ORG

AN

ISE

FOR

AC

TION

AUDITIN

G

TR

AIN

ING

MONITOR &

Power

Managem

ent

Solutions

Increased

Factory or

Process AutomationIntelligentLightingControls

contro

lsBuilding

PROCESSTARGETING MAPPING

10 2

34

6 57

89

Monitoringand Targeting

Systems

1

as per ISO 50001 Standard

Ener

gy M

anagement System Approach

bitoron 12 17

TerminalPrinter / Fax

RS 232BASICline

ModemAnalog ISDN

RS232

C2 CAN

RS232

C1 CANRS232

RS232

RS232

RS232RS485

RS485 RS485

TCP/IP-Bus LON

MODBUS

TCP/IPKNXBACnet/IP

CANKNX

USB

BACnet MS/TPRS485

PLDx-24-BACAI

0...10V

AI

AI

AI0...10V

AI

AI

PWDx-24-BAC

BACnet MS/TPRS485

BACnet MS/TPRS485

BACnet MS/TPRS485

BACnet MS/TP - RS485

C1 CAN

OPEN 4100 EMSNative BACnet Controller

OPEN 810 EMSNative BACnet Controller

OPEN 600 EMSNative BACnet Controller

BACnet / IP

OPEN SRUBACnet Single RoomController

TUP 5,7”

TUP 3,5”

TCP /IP

CORA-B GALAXY One

BACnet MS/TP

TCP/IPController GSM

Modem(s)

Connection to external systems

further connections on request

BMSOPENweb

GPRS / UMTSBluetooth

Germantechnology for

intelligentbuildings.

BAC

net/I

P

TCP/

IP

EBMPapst fan

GRUNDFOSpump

OPEN 4100 EMSmax. length each CAN-bus 5 kmmax. 198 IO modulesmax. 60 LSD-C, FBG 5max. 192 IO 7-B, IO 7, GALAXY One, CORA

OPEN 810 EMSmax. CAN-bus length 5 kmmax. 32 IO modulesmax. 10 LSD-C, FBG 5max. 32 IO 7-B, IO 7, GALAXY One, CORA

OPEN 600 EMS32 integrated IOsmax. CAN-bus length 5 kmmax. 5 IO modulesmax. 2 LSD-C, FBG 5max. 5 IO 7-B, IO 7, GALAXY One, CORA

OPEN SRU16 integrated IOs

all are via

GSM/GPRS

mobile networkall are via

GSM/GPRS

mobile network

Page 18: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

ISO 9001 : 2008 Certified

Panel mounted equipment

Introduction

SM Series analyzers are highly accurate measuring stations which control and supervise the main electrical parameters in three or four wire, single-phase and/or three-phase systems (in L.V. or M.V.)

Measuring is in true effective value (TRMS), using three voltage inputs and neutral with external current transformer connection shaving ƒ/5A or ƒ/1A secondaries (current inputs are insulated in ITF types).

In addition to displaying and transmitting all measured or calculated electrical parameters through communications, SM analyzers include a meter function being able to store the systems consumed and generated energy within the SQMs internal memory without the need of an auxiliary power supply.

SM system analyzers may include an hourly time slots, according to type, using a preset program. This system obtains a kWh total for each of the preset tariffs. These analyzers, like the single tariff analyzers, record active, inductive reactive, capacitive reactive and apparent power for each of the preset periods.

The whole series has a built in power demand meter in which calculates integrated demand in a preset period. This sliding integration may be carried out for a selected parameter: three-phase current, three-phase active power, three-phase apparent power or current per phase.

The expandable or modular equipment may be supplied with additional functions from a selected expansion card or from the type of SM selected. They have the option for analogue I/O (multi-converter function), digital I/O (central alarm function or impulse generation / kWh) which may be linked to any measured or calculated electrical parameter.

Due to the large volume of information from each of the SM system analyzers, the equipment has communication output. Connection topology and system protocols are varied (RS-232, RS-485, RTB modem, GSM modem, Radio (Modbus RTU, Profi bus DP and Metasys N2) and Ethernet (Web or XML)).

SM system analyzers

DIN rail mounted equipment

bitoron 12 18

Page 19: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

+

Three-phase system analyzers PANEL DIN RAIL

96 x 96 mm 3 modules 8 modules

SM-96SP SM-NRG96 SM-96 SM-144 SMk SM-MINI SM-BC3 SM-BD SM-BDM

+ +- - -MEASURING FEATURES

Single-phase O

Phase-phase voltage O O O O O O O O

True effective value (TRMS) O O O O O O O O O

Quadrants 2 4 2 2 4 4 2 4 4

Power demand (Pd) O O O O O O O O

Neutral current O O O O O O O O

Leakage current O

THD Measuring (V , A) O O O O O O O O O

Harmonic decomposition O O O O O O O O

Energy meter O O O O O O O O O(kWh, kvarh C, kvarh L)

Multi-tariff O O

Analogue inputs (0/4...20mA) O

Analogue outputs (0/4...20mA) O O O O

Digital inputs O

Digital outputs O O O O O O O O O

ASSEMBLY FEATURES

Display LCD LCD LED LED LED/LCD LCD LCD LCD LCD

Screen saver O O O O O O

Password protection O O O O O O

COMMUNICATIONS FEATURES

RS-232 O O O O O

RS-485 O O O O O O O O O

Ethernet O O

COMMUNICATIONS PROTOCOL

Modbus RTU O O O O O O O O O

Profibus DP O

Johnson Controls O O O O

XML (Ethernet types only) O

Measured or calculated, according to type

SM system analyzers

ISO 9001 : 2008 Certified

bitoron 12 19

Page 20: Bitoron-12 - Adexbdadexbd.com/adexbd/images/pdf/Bitoron_12_2016.pdfJ IEC 62271-200, 62271-103, 62271-102, 62271-1, 62271-100 Adaptations for compliance with national standards and

ISO 9001 : 2008 Certified

Corporate Office : Baitul Abed53 Purana Paltan (3rd Floor)Dhaka-1000, Bangladesh.Phone : +88 02 9559868, 9559826Fax : +88 02 956 2705e-mail : [email protected]

Sales Office : Shekh Centre56 Purana Paltan (3rd Floor)Dhaka-1000, Bangladesh.Phone : +88 02 956 0626Fax : +88 02 956 2705e-mail : [email protected]

Chittagong Office : bti Kanchan, Flat - A2, House# 25Road# 2, O.R Nizam Road R/AGEC Circle, Chittagong – 4000Tel : +88 031 651177e-mail : [email protected]

ADEX CORPORATION LIMITED.ADEX ENGINEERING LIMITED.

crea

tion

by p

ulin

| may

, 15

| 400

0 pc

s

Khulna Office : 115/2ka, Ground FloorSonadanga Thana RoadSonadanga, KhulnaMob : +88 01787 668677e-mail : [email protected]

Sylhet Office:7, Jalalabad R/A (Ground Floor)Darshandawri, AmborkhanaSylhet-3100Mob : +88 01713 436288e-mail : [email protected]

Comilla Office:32/ka, Tri-Ratno (3rd Floor)Islampur, Fousdari ChowmohoniJudge Court Road, ComillaMob : +88 01713 436283e-mail : [email protected]

Bogra Office:House No. 02 (2nd Floor)Road# 01, Upashahor Bazar, BograMob : +88 01777 790232e-mail : [email protected]

Web: www.adexbd.com

After 5 years of continuous Research, Development and Testing, ADEX R & D team has developed and validated quality performance of these range of products.