    Biosco: MV/LV prefabricatedsubstations

    IEC 62271-202

    Presentation of the standard

    Safety is a choic e

  • 7/15/2019 Iec 62271-202 Standards_en

    2/27

    2Biosco - Prsentation clientle - 08/2007

    Contents

    Introduction

    Type-tested substations

    The type tests

    A specification tool

    Conclusion

  • 7/15/2019 Iec 62271-202 Standards_en

    3/27

    3Biosco - Prsentation clientle - 08/2007

    Contents

    Introduction

    Type-tested substations

    The type tests

    A specification tool

    Conclusion

  • 7/15/2019 Iec 62271-202 Standards_en

    4/27

    4Biosco - Prsentation clientle - 08/2007

    > Introductio

    Standard IEC 62271-202: an international influence

    Biosco conforms to IEC 62271-202 international standard

    IEC 62271-202 standard applies to most of prefabricated substations

    world-wide.

    UL

    IEC

    IEC

    IEC

    IEC

    IEC

  • 7/15/2019 Iec 62271-202 Standards_en

    5/275Biosco - Prsentation clientle - 08/2007

    > Introductio

    Introduction

    IEC 62271-202 standardspecifies the rated characteristics, the

    design and construction rules and the test methods applicable to

    prefabricated substations.

    A prefabricated substation is defined as a type-tested assemblycomprising an enclosure that includes:

    Transformer

    LV switchboard

    MV switchboard

    MV and LV interconnections

    Auxiliary equipment

  • 7/15/2019 Iec 62271-202 Standards_en

    6/276Biosco - Prsentation clientle - 08/2007

    > Introductio

    Introduction

    These substations are located in places accessible to the general

    public. Consequently, safety of persons must be guaranteed

    Conformity to the IEC standard guarantees:

    Protection of the general public

    Protection of operators

  • 7/15/2019 Iec 62271-202 Standards_en

    7/277Biosco - Prsentation clientle - 08/2007

    Contents

    Introduction

    Type-tested substations

    The type tests

    A specification tool

    Conclusion

  • 7/15/2019 Iec 62271-202 Standards_en

    8/278Biosco - Prsentation clientle - 08/2007

    > Type-tested substation

    Type-tested equipment

    All substation components must conform to IEC standards and in

    particular:

    Transformers: IEC 60076-1 or 60076-11

    MV switchboard: IEC 62271-200 or 62271-201

    LV switchboard: IEC 60439-1 and IEC 60947-1

  • 7/15/2019 Iec 62271-202 Standards_en

    9/279Biosco - Prsentation clientle - 08/2007

    > Type-tested substation> Type-tested substation

    The prefabricated substation undergoes type tests

    MVLV

    Use of equipment conform to

    IEC standards

    Oil retentionEarthingcircuit test

    Mechanical resistance

    of the enclosure

    Temperature

    class

    Sound level

    Degree ofprotection

    Insulationlevel

    Internalarcingwithstand

    Non

    flammable

    materials

    Electromagnetic

    compatibility

    Functional tests

  • 7/15/2019 Iec 62271-202 Standards_en

    10/2710Biosco - Prsentation clientle - 08/2007

    > Type-tested substation

    The 4 designs of the Biosco range conform to IEC

    62271-202 standard

    Biosco W:Substation with corridor

    Operation protected from bad weather

    conditions

    Biosco N: Substation with external operation

    Ground space savings

    Biosco H: Half-buried substation

    Visual impact limited

    Biosco U: Underground substation Blends completely

    into the environment

    Biosco UBiosco N Biosco HBiosco W

  • 7/15/2019 Iec 62271-202 Standards_en

    11/2711Biosco - Prsentation clientle - 08/2007

    Contents

    Introduction

    Type-tested substations

    The type tests

    A specification tool

    Conclusion

  • 7/15/2019 Iec 62271-202 Standards_en

    12/27

    12Biosco - Prsentation clientle - 08/2007

    > The type test

    The type tests

    1. Dielectric tests

    2. Temperature rise tests

    3. Main circuit and earthing tests

    4. Functional tests

    5. Degree of protection verification tests

    6. Mechanical tests

    7. Arcing due to an internal fault tests

    8. Sound verification tests

    9. Electromagnetic compatibility tests

  • 7/15/2019 Iec 62271-202 Standards_en

    13/27

    13Biosco - Prsentation clientle - 08/2007

    > The type test

    Dielectric tests

    Aim of test

    To guarantee insulation of HV and LV interconnections

    Our performance

    The HV and LV interconnections of the Biosco range are tested

    as per standards IEC 60694 and 60439 Example for 24 kV switchgear:

    Withstand to voltage of 50 kV at power frequency for 1

    min

    Withstand to lightning impact voltage tests for a 1.2 s

    wave and a voltage of 125 kV

  • 7/15/2019 Iec 62271-202 Standards_en

    14/27

    14Biosco - Prsentation clientle - 08/2007

    > The type test

    Temperature rise tests

    Aim of test

    To determine the enclosure class

    To guarantee that none of the substation components willovershoot its standard-defined limits

    To guarantee temperature on the parts of the enclosure likely tobe touched during operation

    To guarantee lifetime of insulating devices and thus safety ofequipment during the period of operation

    Our performance

    The Biosco substation enclosures are class 10 as standard

    This performance can be adapted to your needs according toambient temperatures, degrees of protection or transformerlosses

    Numerical modelling and thermal simulations are performed.

  • 7/15/2019 Iec 62271-202 Standards_en

    15/27

    15Biosco - Prsentation clientle - 08/2007

    > The type test

    Main circuit and earthing tests

    Aim of test:

    To guarantee the capacity to withstand short-circuit currents

    Our performance

    The Biosco substations are tested up to 12 kA

    Th t t t

  • 7/15/2019 Iec 62271-202 Standards_en

    16/27

    16Biosco - Prsentation clientle - 08/2007

    > The type test

    Functional tests

    Aim of tests

    To guarantee that it is possible to carry out all the operationsrequired for commissioning, operation and maintenance

    Our performance

    The Biosco substations undergo a series of verifications

    Switchgear operation

    Mechanical operation of substation doors

    Reading transformer temperatures and oil levels

    Monitoring voltage readings

    Installation of earthing devices

    Cable tests

    Replacement of fuses and monitoring of locking systems

    Operating the transformer on-load tap changer Cleaning the ventilation grids

    Monitoring the locking systems

    > The t pe test

  • 7/15/2019 Iec 62271-202 Standards_en

    17/27

    17Biosco - Prsentation clientle - 08/2007

    > The type test

    Degree of protection verification test

    Aim of test

    To ensure the protection of people against access to hazardous

    parts

    To guarantee the protection of equipment against ingress of

    foreign solid objects and water.

    Our performance

    The degree of protection of the Biosco substations is between

    IP23 and IP54

    This performance can be adapted to your needs: stipulations of

    standards and climatic requirements.

    > The type test

  • 7/15/2019 Iec 62271-202 Standards_en

    18/27

    18Biosco - Prsentation clientle - 08/2007

    > The type test

    Mechanical tests

    Aim of test

    To guarantee withstand of roof in event of overload: people,

    snow, etc.

    To guarantee the resistance of substation to wind pressure and

    to mechanical impacts on walls, covers, doors, ventilation

    opening.

    Our performance

    Roof withstand greater than 250 daN/m

    IK10 (including doors and ventilation grids)

    > The type test

  • 7/15/2019 Iec 62271-202 Standards_en

    19/27

    19Biosco - Prsentation clientle - 08/2007

    > The type test

    Arc due to an internal fault test

    Aim of test

    To guarantee the protection of operators and the general public.

    The standard defines a classification:

    Class A: operator protection

    Class B: general public protection

    Class AB: operator and general public protection

    Our performance

    Koolarc system (cools and reduces pressure of arc gases)

    Classification for all substation types

    Example Biosco N India IAC-AB-20kA-1s

    Pressure and temperature simulation

    > The type test

    http://localhost/var/www/apps/conversion/tmp/scratch_9/Test_manque2b.wmvhttp://localhost/var/www/apps/conversion/tmp/scratch_9/Film%20biosco_closed_intranet.wmv
  • 7/15/2019 Iec 62271-202 Standards_en

    20/27

    20Biosco - Prsentation clientle - 08/2007

    > The type test

    Sound verification test

    Aim of test

    To ensure that the substation enclosure does not increase the

    transformer noise level.

    Our performance

    The Biosco substations conform to the requirements of the IEC

    standard

    > The type test

  • 7/15/2019 Iec 62271-202 Standards_en

    21/27

    21Biosco - Prsentation clientle - 08/2007

    The type test

    Electromagnetic compatibility test

    Aim of test

    To satisfy emission requirements laid down by international

    standards

    To guarantee the proper operation of equipment in an

    environment comprising large electromagnetic disturbance

    sources

    Our performance

    HV and LV switchgear comply with the specifications of

    standards IEC 60694 and 60439-1.

    Electromagnetic fields are simulated.

  • 7/15/2019 Iec 62271-202 Standards_en

    22/27

    22Biosco - Prsentation clientle - 08/2007

    Contents

    Introduction

    Type-tested substations

    The type tests

    A specification tool

    Conclusion

    > A specification too

  • 7/15/2019 Iec 62271-202 Standards_en

    23/27

    23Biosco - Prsentation clientle - 08/2007

    p

    A specification tool

    Standard IEC 62271-202 tells users which information should be

    supplied for invitations to tender and orders.

    Network specificities

    Nominal and highest voltages

    Frequencies

    Neutral earthing mode

    Operating conditions

    Minimum and maximum temperatures

    Altitudes

    The specificities and electrical characteristics of prefabricated

    substations

    Voltage, power, frequency

    > A specification too

  • 7/15/2019 Iec 62271-202 Standards_en

    24/27

    24Biosco - Prsentation clientle - 08/2007

    A specification tool

    The information required for specifications is summarised in table

    form. All the electrical utility has to do is complete this information.

  • 7/15/2019 Iec 62271-202 Standards_en

    25/27

    25Biosco - Prsentation clientle - 08/2007

    Contents

    Introduction

    Type-tested substations

    The type tests

    A specification tool

    Conclusion

  • 7/15/2019 Iec 62271-202 Standards_en

    26/27

    26Biosco - Prsentation clientle - 08/2007

    Conclusion

    Type-tested MV, LV equipment and

    transformer

    A series of type tests to guarantee safety and

    reliability of the prefabricated substation

    throughout its life cycle.

    An MV/LV substation specification guide

    providing all characteristics and installation

    and operation conditions

    MVLV

    Use of equipment conform

    to IEC standards

    Oil retention

    Internal

    arcingwithstand

    Earthing

    circuit test

    Mechanical resistanceof the enclosure

    Temperature

    class

    Soundlevel

    Insulation

    level

    Non

    flammablematerials

    Electromagneticcompatibility

    Functional tests

    http://f/Local%20Settings/Temp/My%20Documents/DOCS/SLIDES%20CONF/Conf%20RM6/RM6%C2%B2%20pr%C3%A9sentation%20fran%C3%A7ais.ppt